Transcript
GENERAL NOTES: 1.
MOST EXISTING UNDERGROUND UTILITIES ARE NOT INDICATED. THE EXISTING UNDERGROUND UTILITIES INDICATED ARE SCHEMATIC ONLY. THE CONTRACTOR SHALL BE RESPONSIBLE FOR JOBSITE LOCATING AND PROTECTING ALL EXISTING UNDERGROUND UTILITIES PRIOR TO TRENCHING OR BORING.
2.
INFORMATION INCLUDED ON THIS DRAWING IS INTENDED TO INDICATE THE GENERAL CHARACTER AND EXTENT OF WORK REQUIRED. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
UG
UG
UG UG TO LIGHTING FIXTURE BEYOND A-7,9 BLDG E
UG
NOTES:
TECH BUILDING BUILDING "E"
REMOVE EXISTING LIGHT POLE AND CONCRETE FOUNDATION. REMOVE CONDUCTORS FROM UNDERGROUND CONDUIT TO NEAREST JUNCTION. ABANDON EXISTING CONDUIT BELOW GRADE. JOBSITE SURVEY DEMOLITION REQUIREMENTS. EXISTING POWER UTILITY DIP POLE
UG
EXISTING SPLICE BOX
G E-U
UG
HE E-O
PRESERVE CONTINUITY OF EXISTING CIRCUIT AFTER REMOVAL OF EXISTING LIGHT POLE. EXISTING LIGHT POLE SHALL REMAIN. APPROXIMATE ROUTE OF PRIMARY CABLES. JOBSITE LOCATE AND PROTECT DURING CONSTRUCTION.
E-U
G
UG
UG E-OHE
UG
EXISTING PAD MOUNTED TRANSFORMER
G
BLDG C
E-U
UG
E-UG
HE E-O
EXISTING MAIN SWITCHBOARD "MDP"
UG EXISTING PANEL "B"
LIBRARY & CLASSROOM BUILDING "C"
EXISTING PANEL "DPA"
B-14 BLDG D
B-16 BLDG D
UG
SRRGC BUILDING "D"
UG
ODGE
BERMEA BUILDING "A"
BOB R
ADMINISTRATION BUILDING
RS DR
IVE
SRRGC BUILDING "B"
STRIDDE, CALLINS & ASSOCIATES INC. CONSULTING MECHANICAL
*
ENGINEERS ELECTRICAL
(361) 883-9199 Fax (361) 883-9177 342 S. Navigation Blvd. Corpus Christi, TX 78405-3615 Registration # F-006328
GENERAL NOTES: 1.
MOST EXISTING UNDERGROUND UTILITIES ARE NOT INDICATED. THE EXISTING UNDERGROUND UTILITIES INDICATED ARE SCHEMATIC ONLY. THE CONTRACTOR SHALL BE RESPONSIBLE FOR JOBSITE LOCATING AND PROTECTING ALL EXISTING UNDERGROUND UTILITIES PRIOR TO TRENCHING OR BORING.
2.
INFORMATION INCLUDED ON THIS DRAWING IS INTENDED TO INDICATE THE GENERAL CHARACTER AND EXTENT OF WORK REQUIRED. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
PANEL "HK" PANEL "LK" UG
NEW LIBRARY & CLASSROOM ADDITION
UG
PANEL "LCA3" PANEL "LA2"
PANEL "LA"
UG
PANEL "LCA2"
PANEL "LCA"
PANEL "HA"
PANEL "LCA1"
EXISTING PAD MOUNTED TRANSFORMER
PANEL "LA1"
NOTES: EXISTING LIGHT POLE AND FIXTURES TO REMAIN.
TECH BUILDING BUILDING "E"
PANEL "MDP" UG
BORE BELOW EXISTING DRIVE AS REQUIRED TO INSTALL CONDUIT.
PANEL "HDPA"
E
H E-O
UG
UG
HE
E-O
E-UG
EXISTING SPLICE BOX METER #10
E-U
G
NEW PAD MOUNTED TRANSFORMER
UG
TUNNEL BELOW EXISTING CONCRETE FLATWORK AS REQUIRED TO INSTALL CONDUIT. IN-GRADE BOX SHALL BE QUAZITE CAT. NO. PG1324BA18 WITH PG1324HA17. TOP OF BOX SHALL BE 1" ABOVE FINISHED GRADE. PROVIDE 12" DEEP SAND BED BELOW BOX. BOX SHALL BE FOR PULLTHROUGH ONLY. SPLICES IN BOX WILL NOT BE PERMITTED. TWO (2) - #1, #6 GRND., 1 1/4"C.
HA-13,15
TWO (2) - #8, #10 GRND., 1"C. #10
G E-U
30A., 250V., 2P, NF, NEMA-3R DISCONNECT SWITCH. MOUNT TO SIGN/ MARQUEE BASE AS REQUIRED. COORDINATE LOCATION WITH SIGN VENDOR.
E-U
G
UG
E-OHE
#10
UG EXISTING MAIN MAIN SWITCHBOARD "MDP"
PROVIDE GROUND ROD, GROUNDING CONDUCTOR, AND REQUIRED GROUNDING / BONDING FOR SIGN / MARQUEE. REFER TO POWER RISER DIAGRAM ON SHEET E3-2 FOR REQUIREMENTS. ROUTE CONDUIT BELOW EXISTING CONCRETE FLATWORK AND TRANSFORMER FOUNDATION AS REQUIRED TO INSTALL CONDUIT INTO PRIMARY COMPARTMENT OF EXISTING PAD MOUNTED TRANSFORMER.
EXISTING PANEL "A"
MAIN SHUNT-TRIP PUSHBUTTON. REFER TO POWER RISER DIAGRAM 2/E3-2 FOR REQUIREMENTS. EXISTING PANEL "B"
THREE (3) - 2" CONDUIT WITH PULLCORD. STUB CONDUIT TO 2'-0" ABOVE FINISHED FLOOR. COORDINATE LOCATION WITH OWNER.
NEW PANEL "DPA" TO REPLACE EXISTING
LIBRARY & CLASSROOM BUILDING "C"
ROUTE CONDUIT UP FROM BELOW GRADE EXPOSED ON EXTERIOR WALL. EXTEND CONDUIT UP TO ABOVE ACCESSIBLE CEILING AND ROUTE THROUGH EXISTING WALL VIA "LB" CONDUIT BODY. STUB CONDUIT TO 2'-0" BEYOND EXTERIOR WALL INSIDE EXISTING BUILDING.
SRRGC BUILDING "D"
TWO (2) - #4, #8 GRND., 1" C ROUTE CONDUIT UP FROM BELOW GRADE EXPOSED ON EXTERIOR WALL. EXTEND CONDUIT UP TO LEVEL OF PANEL "DPA" AND ROUTE THROUGH EXISTING WALL VIA "LB" CONDUIT BODY. EXTEND TO PANEL "DPA". JOBSITE VERIFY REQUIREMENTS. NEW PANEL "C"
DPA-31
SRRGC BUILDING "B"
BERMEA BUILDING "A"
ODGE
C-13,15 C-9,11
BOB R
ADMINISTRATION BUILDING
RS DR IV
E
NEW ADDITION SRRGC BUILDING "D"
UG UG
C-9,11 C-13,15
UG UG UG
DPA-31
UG
UG
UG
UG C-13,15
UG C-9,11
DPA-31
NEW SIGN / MARQUEE
UG
#10 #10
UG
UG
UG
#10
UG #10 UG #10 UG
STRIDDE, CALLINS & ASSOCIATES INC. CONSULTING MECHANICAL
*
ENGINEERS ELECTRICAL
(361) 883-9199 Fax (361) 883-9177 342 S. Navigation Blvd. Corpus Christi, TX 78405-3615 Registration # F-006328
PANEL "HK" PANEL "LK"
CANTEEN 100
HK-1
LK-60 LK-59
101A
JAN. 104 CLASSROOM 108
STOR. 101B MEN 105
KITCHEN 101
101C
STOR. 102
WOMEN 106
HALL 107
(1)
D. 103
HA-9
#10 DL CLASSROOM 169
HALL 109
STOR. 159
PREP. 158
HALL 124 OFFICE 119
OFFICE 120
PHYSICS CLASSROOM 157
DL CLASSROOM 168 HALL 125
LIBRARY 110
MULTIPURPOSE 161
COMPUTER 118
STORAGE 117 WORK 116
D.L. CLASSROOM 121
SEMINAR ROOM 115
MEN 163
HA-4
HA-6
CLASSROOM 122
WOMEN 162
PANEL "HA"
MECH. 166
STOR 164
HA-2
HALL 165
HA-7
JAN. 167 HALL 126
HA-8 SEMINAR ROOM 114 SEMINAR ROOM 113
HA-1,3,5 SEMINAR ROOM 123
SEMINAR ROOM 111
LIBRARY OFFICE 112
#10
#10
HALL 127
CLASSROOM 130
CLASSROOM 131
CLASSROOM 132
DL COMPUTER 133
GENERAL NOTES: 1.
INFORMATION INCLUDED ON THIS DRAWING IS INTENDED TO INDICATE THE GENERAL CHARACTER AND EXTENT OF WORK REQUIRED. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
HA-9
#10 #10
#10 (1)
#10
NOTES: CONNECT FIXTURES WITHIN SPACE TO PROVIDE DUAL SWITCHING VIA THE INSTALLED 50% TO 100% STEP DIMMING BALLAST UNLESS OTHERWISE INDICATED. SWITCH NEAREST STRIKE SIDE OF DOOR SHALL CONTROL 50% LEAD OF STEPPED BALLAST WITHIN FIXTURES. ALL LAMPS WITHIN FIXTURE SHALL BE CONTROLLED BY 100% SWITCH. CONNECT BALLAST AND EMERGENCY BATTERY PACK TO UNSWITCHED CONDUCTOR. ROUTE CONDUIT AND CONDUCTORS THROUGH LIGHTING CONTACTOR "CA" LOAD / POLE (INDICATED). DERIVE UNSWITCHED CONDUCTOR FOR EMERGENCY BALLAST IN FIXTURES TYPE "J1" AND "P1" FROM LINE SIDE OF LIGHTING CONTACTOR. TIME CLOCK "TC1" SHALL BE INTERMATIC CAT. NO. T174CR. CONNECT LOAD SIDE TO CONTACTOR "CA" CONTROL COIL. LIGHTING CONTACTOR "CA" SHALL BE SQUARE D, CLASS 8903, TYPE LG80VO4CPI. REFER TO SHEET E2-2 FOR CONTINUATION. CEILING FAN SHALL BE BIG ASS FAN HAIKU 60 CAT. NO. S3150-X2-20 WITH CLEAR LENS LED MODULE. COORDINATE FINISH COLOR WITH ARCHITECT / OWNER. REFER TO MANUFACTURER'S INSTALLATION INSTRUCTIONS FOR REQUIREMENTS. PROVIDE ALL ACCESSORIES FOR A COMPLETE INSTALLATION. BIG ASS FANS HAIKU 60 WIRELESS WALL CONTROL. CONTROL FANS AS INDICATED. REFER TO MANUFACTURER'S INSTALLATION INSTRUCTIONS FOR REQUIREMENTS. PROVIDE ALL ACCESSORIES FOR A COMPLETE INSTALLATION.
STRIDDE, CALLINS & ASSOCIATES INC. CONSULTING MECHANICAL
*
ENGINEERS ELECTRICAL
(361) 883-9199 Fax (361) 883-9177 342 S. Navigation Blvd. Corpus Christi, TX 78405-3615 Registration # F-006328
LIGHTING FIXTURE SCHEDULE FIXTURE TYPE
ACRYLIC PRISMATIC
RECESSED
PROVIDE STEP DIMMING (50% TO 100%) BALLAST.
LITHONIA CAT. NO. 2SP8 G 2 32 A12125 BSNP LP841 EL14
2-F32T8 FURNISHED 65[W] 41K
MVOLT
WHITE ENAMEL
ACRYLIC PRISMATIC
RECESSED
PROVIDE STEP DIMMING (50% TO 100%) BALLAST. PROVIDE FACTORY INSTALLED BATTERY PACK.
LITHONIA CAT. NO. SP8 G 1 32 A12125 GEB10PS LP841
1-F32T8 FURNISHED 35[W] 41K
MVOLT
WHITE ENAMEL
ACRYLIC PRISMATIC RECESSED
LITHONIA CAT. NO. SP8 G 1 32 A12125 GEB10PS LP841 EL
1-F32T8 FURNISHED 35[W] 41K
MVOLT
WHITE ENAMEL
ACRYLIC PRISMATIC RECESSED
LITHONIA CAT. NO. 2SP8 G 2 32 A12125 GEB10IS LP841
2-F32T8 FURNISHED 65[W] 41K
MVOLT
WHITE ENAMEL
ACRYLIC PRISMATIC
RECESSED
LITHONIA CAT. NO. 2SP8 G 2 32 A12125 GEB10PS EL14
2-F32T8 FURNISHED 65[W] 41K
MVOLT
WHITE ENAMEL
ACRYLIC PRISMATIC
RECESSED
LITHONIA CAT. NO. 2SP8 G 2 17 A12125 GEB10IS
2-F17T8 35[W] 41K
MVOLT
WHITE ENAMEL
ACRYLIC PRISMATIC
RECESSED
D
LITHONIA CAT. NO. 2SP8 G 2 17 A12125 GEB10IS EL14
2-F17T8 35[W] 41K
MVOLT
WHITE ENAMEL
ACRYLIC PRISMATIC
RECESSED
PROVIDE FACTORY INSTALLED BATTERY PACK.
D1
LITHONIA CAT. NO. ELM 2 LED
L.E.D. FURNISHED
NONE
WHITE THERMOPLASTIC
ARCYLIC
SURFACE WALL
PROVIDE FACTORY INSTALLED BATTERY PACK. REFER TO SPECIFICATIONS FOR MOUNTING REQUIREMENTS.
LITHNOIA CAT. NO. ZL2 L48 4600 LP840
L.E.D. FURNISHED 75[W] 40K
MVOLT
WHITE ENAMEL
MEDIUM DIFFUSE LENSE
SURFACE
COORDINATE LOCATION WITH STRUCTURE, DUCT, PIPING, ETC.
LITHONIA CAT. NO. 2SP8 G 2 17 A12125 BSNP
2-F17T8 35[W] 41K
MVOLT
WHITE ENAMEL
ACRYLIC PRISMATIC
RECESSED
PROVIDE STEP DIMMING (50% TO 100%) BALLAST.
LITHONIA CAT. NO. 2ES8 P 2 32 BSNP L841HT8
2-F32T8 FURNISHED 65[W] 41K
MVOLT
WHITE ENAMEL
WHITE ANGLED BLADES
RECESSED
PROVIDE STEP DIMMING (50% TO 100%) BALLAST. PROVIDE WITH 3100 LUMEN, LONG LIFE, 41K LAMPS.
GOTHAM CAT. NO. EVO 41/22 8 AR
L.E.D. FURNISHED 40[W] 41K
NONE
CRS
SEMISPECULAR
RECESSED
GOTHAM CAT. NO. EVO 41/22 8 AR ELR
L.E.D. FURNISHED 40[W] 41K
NONE
CRS
SEMISPECULAR
RECESSED
PROVIDE FACTORY INSTALLED BATTERY PACK AND REMOTE MOUNTED TEST SWITCH. COORDINATE REMOTE TEST SWITCH LOCATION WITH OWNER.
LITHONIA CAT. NO. 2SP8 G 3 32 A12125 GEB10IS LP841 LG
3-F32T8 FURNISHED 100[W] 41K
MVOLT
WHITE ENAMEL
ACRYLIC PRISMATIC
RECESSED
PROVIDE DUAL BALLASTS TO ALLOW DUAL SWITCHING WITHIN SPACE. PROVIDE PREMIUM LENS GASKETING, INVERTED LENS, AND WHITE ALUMINUM DOOR FRAME.
3-F32T8 LITHONIA CAT. NO. 2SP8 G 3 32 A12125 GEB10IS LP841 LG FURNISHED 100[W] EL14 41K
MVOLT
WHITE ENAMEL
ACRYLIC PRISMATIC
RECESSED
PROVIDE DUAL BALLASTS TO ALLOW DUAL SWITCHING WITHIN SPACE. PROVIDE PREMIUM LENS GASKETING, INVERTED LENS, AND WHITE ALUMINUM DOOR FRAME. PROVIDE FACTORY INSTALLED BATTERY PACK AND TEST SWITCH
LITHONIA CAT. NO. 2SP8 G 3 17 A12125 GEB10IS LP841 LG
3-F17T8 FURNISHED 55[W] 41K
MVOLT
WHITE ENAMEL
ACRYLIC PRISMATIC
SURFACE
PROVIDE DUAL BALLASTS TO ALLOW DUAL SWITCHING WITHIN SPACE. PROVIDE PREMIUM LENS GASKETING, INVERTED LENS, AND WHITE ALUMINUM DOOR FRAME.
LITHONIA CAT. NO. DSXW1 LED 20C 530 50K T3M DDBXD
L.E.D. FURNISHED 40[W] 50K
MVOLT
DIE-CAST ALUMINUM DARK BRONZE
PRECISION MOLDED ACRYLIC
SURFACE
MOUNT AT 14'-6" ABOVE FINISHED FLOOR UNLESS OTHERWISE DIRECTED BY ARCHITECT.
LITHONIA CAT. NO. DSXW1 LED 20C 530 50K T3M ELCW DDBXD
L.E.D. FURNISHED 40[W] 50K
MVOLT
DIE-CAST ALUMINUM DARK BRONZE
PRECISION MOLDED ACRYLIC
SURFACE
MOUNT AT 14-6" ABOVE FINISHED FLOOR UNLESS OTHERWISE DIRECTED BY ARCHITECT.PROVIDE FACTORY INSTALLED BATTERY PACK. MOUNT FIXTURE3 ABOVE DOOR AT ELEVATION SELECTED BY ARCHITECT.
LITHONIA CAT. NO. DSX2 LED 80C 1000 50K T2M RPA PER DDBXD
L.E.D. FURNISHED 275[W] 50K
MVOLT
DIE-CAST ALUMINUM DARK BONZE
PRECISION MOLDED ACRYLIC
POLE
PROVIDE LITHONIA CAT. NO. RTA 30 8G FBC VD DDB POLE. COORDINATE FACTORY DRILL MOUNTING WITH FIXTURE QUANTITIES AS INDICATED. PROVIDE FACTORY WELDED STUD IN POLE SHAFT ADJACENT TO HAND HOLE FOR CONNECTION OF GROUNDING CONDUCTOR. PROVIDE FACTORY INSTALLED PHOTOELECTRIC CELL.
XA
LITHONIA CAT. NO. LE S 1R EL
L.E.D. FURNISHED
NONE
BRUSHED ALUMINUM
RED THERMOPLASTIC
SURFACE
PROVIDE FACTORY INSTALLED BATTERY PACK. PROVIDE MOUNTING HARDWARE FOR TOP, BACK, END MOUNTING.
XB
LITHONIA CAT. NO. LE S 2R EL
L.E.D. FURNISHED
NONE
BRUSHED ALUMINUM
RED THERMOPLASTIC
SURFACE
PROVIDE FACTORY INSTALLED BATTERY PACK. PROVIDE MOUNTING HARDWARE FOR TOP, END MOUNTING.
B1
C
C1 CLASSROOM 148
CLASSROOM 147
CLASSROOM 145
CLASSROOM 146
OFFICE 150
OFFICE 154
EM
F
G
H OFFICE 149
OFFICE 153
HA-11
HALL 144
#10
#10
J
J1
K
HA-10
HALL 143
K1
OFFICE 142
OFFICE 138
M
P HA-12 #10 (2)
DL CLASSROOM 134
CLASSROOM 135
#10
CLASSROOM 136
#10
#10
GENERAL NOTES: 1.
CLASSROOM 137
OFFICE 139
#10
STOR. 140
#10
REMARKS
DIFFUSER
WHITE ENAMEL
B
HALL 152
MOUNTING BODY
MVOLT
A1
OFFICE 151
FINISH
2-F32T8 FURNISHED 65[W] 41K
FIRE 160
I.T. OFFICE 155
LAMPS
LITHONIA CAT. NO. 2SP8 G 2 32 A12125 BSNP LP841
A I.T. 156
CATALOG REFERENCE
BALLAST/ DRIVER VOLTAGE
P1 OFFICE 141
R
PROVIDE WITH FACTORY INSTALLED EMERGENCY BATTERY PACK AND TEST SWITCH.
PROVIDE FACTORY INSTALLED BATTERY PACK.
NOTES:
INFORMATION INCLUDED ON THIS DRAWING IS INTENDED TO INDICATE THE GENERAL CHARACTER AND EXTENT OF WORK REQUIRED. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
CONNECT FIXTURES WITHIN SPACE TO PROVIDE DUAL SWITCHING VIA THE INSTALLED 50% TO 100% STEP DIMMING BALLAST UNLESS OTHERWISE INDICATED. SWITCH NEAREST STRIKE SIDE OF DOOR SHALL CONTROL 50% LEAD OF STEPPED BALLAST WITHIN FIXTURES. ALL LAMPS WITHIN FIXTURE SHALL BE CONTROLLED BY 100% SWITCH. CONNECT BALLAST AND EMERGENCY BATTERY PACK TO UNSWITCHED CONDUCTOR. REFER TO SHEET E2-1 FOR CONTINUATION. DERIVE UNSWITCHED CONDUCTOR FOR EMERGENCY BALLAST IN FIXTURES TYPE "J1" AND "P1" FROM LINE SIDE OF LIGHTING CONTACTOR. ROUTE CONDUIT AND CONDUCTORS THROUGH LIGHTING CONTACTOR "CA" LOAD / POLE (INDICATED).
FROM LINE SIDE REFER TO SHEET E2-1 FOR LOCATION OF PANEL / LIGHTING CONTACTOR.
N PHASE COLOR WHITE
PP SW
PHASE COLOR WITH WHITE SW TRACER
N
RED BLACK BLUE
LOW VOLTAGE 3 CONDUCTOR CONTROL CABLE OCCUPANCY SENSOR AS SCHEDULED.
O*
POWER PACK AS SCHEDULED
SWITCHING AS INDICATED ON FLOOR PLAN. PHASE COLOR WITH WHITE TRACER
TO LIGHT FIXTURES BEYOND.
OCCUPANCY SENSOR SCHEDULE MARK
DESCRIPTION
MANUFACTURER/ MODEL NO.
OCCUPANCY SENSOR GENERAL NOTES : 1. OCCUPANCY SENSOR LOCATIONS INDICATED ON THE DRAWINGS ARE SCHEMATIC. 2. CEILING MOUNTED MOTION SENSORS IN TYPICAL INSTRUCTIONAL SPACES SHALL BE MOUNTED AS NEAR THE CENTER OF ROOM AS IS POSSIBLE. 3. ALL MOTION SENSORS (WHETHER WALL OR CEILING MOUNTED) SHALL BE INSTALLED OR MOUNTED TO A JUNCTION BOX. 4. ALL MOTION SENSORS SHALL BE MOUNTED AT LEAST 4'-0" AWAY FROM HVAC SUPPLY GRILLS. 5. ALL OCCUPANCY SENSOR TERMINATIONS SHALL BE MADE IN AN APPROVED JUNCTION BOX.
STRIDDE, CALLINS & ASSOCIATES INC. CONSULTING MECHANICAL
*
ENGINEERS ELECTRICAL
(361) 883-9199 Fax (361) 883-9177 342 S. Navigation Blvd. Corpus Christi, TX 78405-3615 Registration # F-006328
ENTRY PORCH 125
OFFICE 206
OFFICE 208
MECH. 207
B-6
B-2
OFFICE 106
C-3
OFFICE 105
OFFICE 104
C-5 C-7 PANEL "C"
LARGE CLASSROOM 124
CORR. 204 MEDIUM CLASSROOM 111
SMALL CLASSROOM 110
STUDENT AREA 109
CONFERENCE 108
OFFICE 103 OFFICE 107
FILE STORAGE 122
WAIT/ SECR. 102
OFFICE 209
OFFICE 205
CLASSROOM 210
JAN. 123
CORRIDOR 200
EXISTING PANEL "B"
C-1 CLASSROOM 202 FIBER OPTIC 115 WOMEN 112
LIBRARY 121
TELECONF. 116
MECH. 114
MEN 113
COMP. LAB 117
OBSERVATION 119
NEW PANEL "DPA" TO REPLACE EXISTING
B-4
COMP. LAB 118
CLASSROOM 201
PRODUCTION ROOM 101
STORAGE 120
B-8
CLASSROOM 203
ENTRY PORCH 126
GENERAL NOTES: 1.
INFORMATION INCLUDED ON THIS DRAWING IS INTENDED TO INDICATE THE GENERAL CHARACTER AND EXTENT OF WORK REQUIRED. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
NOTES: CONNECT FIXTURES WITHIN SPACE TO PROVIDE DUAL SWITCHING VIA THE INSTALLED 50% TO 100% STEP DIMMING BALLAST UNLESS OTHERWISE INDICATED. SWITCH NEAREST STRIKE SIDE OF DOOR SHALL CONTROL 50% LEAD OF STEPPED BALLAST WITHIN FIXTURES. ALL LAMPS WITHIN FIXTURE SHALL BE CONTROLLED BY 100% SWITCH. CONNECT BALLAST AND EMERGENCY BATTERY PACK TO UNSWITCHED CONDUCTOR. DERIVE UNSWITCHED CONDUCTOR FOR EMERGENCY BALLAST IN FIXTURES TYPE "J1" FROM LINE SIDE OF LIGHTING CONTACTOR / TIME CLOCK / PHOTOCELL. JOBSITE LOCATE SOURCE. EXISTING FIXTURE SHALL REMAIN. INSTALL ADDITIONAL UNSWITCHED CONDUCTOR IN EXISTING CONDUIT. JOBSITE SURVEY REQUIREMENTS. INTERCEPT EXISTING CONDUIT AND CONDUCTORS AT APPROXIMATE LOCATION INDICATED. EXTEND NEW CONDUIT AND CONDUCTORS TO NEW FIXTURES AS INDICATED. JOBSITE SURVEY REQUIREMENTS. EXISTING FIXTURE SHALL BE REMOVED. REMOVE CONDUCTORS BACK TO LAST EXISTING FIXTURE TO REMAIN UNLESS OTHERWISE INDICATED. CONTRACTOR SHALL REWORK EXISTING CONDUIT AND CONDUCTORS TO PRESERVE EXISTING CONTINUITY AS REQUIRED. JOBSITE SURVEY REQUIREMENTS. REPLACE EXISTING LIGHT FIXTURE WITH NEW FIXTURE AS INDICATED. JOBSITE SURVEY REQUIREMENTS. PRESERVE EXISTING CIRCUIT CONTINUITY DURING FIXTURE REPLACEMENT. INSTALL NEW FIXTURE AT ELEVATION OF EXISTING BUILDING MOUNTED LIGHT FIXTURES. JOBSITE SURVEY ELEVATION. PROVIDE FIRE RATED ENCLOSURE FOR FIXTURE INDICATED.
STRIDDE, CALLINS & ASSOCIATES INC. CONSULTING MECHANICAL
*
ENGINEERS ELECTRICAL
(361) 883-9199 Fax (361) 883-9177 342 S. Navigation Blvd. Corpus Christi, TX 78405-3615 Registration # F-006328
NOTE: ALL WIRING DEVICES AND DISCONNECT SWITCHES SERVING KITCHEN 1.
NOTES:
EQUIPMENT SHALL BE INSTALLED AT LOCATIONS / ELEVATIONS COORDINATED WITH APPROVED KITCHEN EQUIPMENT SUBMITTALS / SHOP DRAWINGS.
GENERAL NOTES: INFORMATION INCLUDED ON THIS DRAWING IS INTENDED TO INDICATE THE GENERAL CHARACTER AND EXTENT OF WORK REQUIRED. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
TV BOX 2" CONDUIT CAMERA BOX
MOUNT 2" ABOVE COUNTER OR SPLASH.
2" CONDUIT TO ABOVE ACCESSIBLE CEILING
PANEL "LK"
ACF-1 4" 4"
4"W x 4"H x 4"D NEMA-1 BOX WITH COVER. PROVIDE 2" CLOSE NIPPLE IN COVER. 6'-5"
INSTALL OUTLET BOX FLUSH IN SUSPENDED CEILING. COORDINATE LOCATION WITH ARCHITECT.
PANEL "HK"
CORNER WALL
3'
FURNISH AND INSTALL FLUSH MOUNTED JUNCTION BOX FOR CCTV CAMERA BY OWNER. REFER TO TELEVISION / CAMERA DETAIL 3/E3-1 FOR REQUIREMENTS. PROVIDE A TOTAL OF TWO (2) - 2-GANG BOXES WITH TWO (2) - 2" CONDUIT FROM EACH BOX TO ABOVE ACCESSIBLE CEILING.
STOR. 101B
LK-54
LK-1,3
REFER TO TELEVISION / CAMERA DETAIL 3/E3-1 FOR REQUIREMENTS.
LK-7,9,11
TRANSFORMER "TXLK" (SUSPENDED)
101A
LK-51
JAN. 104
INSTALL OUTLET BOXES FLUSH IN CASEWORK / MILLWORK. REFER TO ARCHITECTURAL DETAILS FOR REQUIREMENTS.
MEN 105
LK-11
ONE (1) - 2-GANG BOX WITH TWO (2) - 1" CONDUIT FROM BOX TO ABOVE ACCESSIBLE CEILING.
LK-53
C
LK-13
COORDINATE ROUGH-IN REQUIREMENTS WITH PLUMBING CONTRACTOR.
2'-10"
ONE (1) - 1" CONDUIT WITH PULLCORD. ROUTE CONDUIT FROM DEMONSTRATION DESK / CASEWORK / FLOOR BOX IN SLAB TO WALL INDICATED. ROUTE CONDUIT UP CONCEALED IN WALL TO ABOVE ACCESSIBLE CEILING.
FCU LK-61 I.M.
C
LK-10
LK-8
C C C
FCU
ROUTE CONDUIT AND CONDUCTORS IN SLAB TO WALL INDICATED. ROUTE CONDUIT AND CONDUCTORS UP CONCEALED IN WALL TO ABOVE ACCESSIBLE CEILING.
LK-12,14,16 LK-18,20
FLOOR
101C
1'-6"
COORDINATE RECEPTACLE LOCATION FOR RECESSED MOUNTED CHILLER WITH PLUMBING CONTRACTOR. PROVIDE #12 / 2 SJO PORTABLE CORD AND CORD CAP FOR RECESSED CHILLER. COORDINATE REQUIREMENTS WITH PLUMBING CONTRACTOR.
#10 LK-15,17,19
UG
LK-21,23 (S.T.)
LK-48,50,52
#10
FREEZER
COOLER
LK-22,24,26 (S.T.)
KEF-1
LK-30,32,34 (S.T.)
KITCHEN 101
ROUTE FLEXIBLE METAL CONDUIT CONCEALED IN CASEWORK / MILLWORK. COORDINATE ROUTING WITHIN CASEWORK / MILLWORK WITH CASEWORK / MILLWORK VENDOR / INSTALLER.
REFRIGERATION RACK / CONDENSING UNIT ON ROOF.
TWO (2) - 1" CONDUIT WITH PULLCORD. ROUTE CONDUIT FROM CASEWORK / MILLWORK IN SLAB TO WALL INDICATED. ROUTE CONDUIT UP CONCEALED IN WALL TO ABOVE ACCESSIBLE CEILING.
STOR. 102
DAISY CHAIN A MAXIMUM THREE (3) - DATA OUTLETS TOGETHER WITHIN CASEWORK / MILLWORK INDICATED. PROVIDE 1" FLEXIBLE METAL CONDUIT BETWEEN DAISY CHAINED DATA OUTLETS. COORDINATE ROUTING WITHIN CASEWORK / MILLWORK WITH CASEWORK / MILLWORK VENDOR / INSTALLER.
LK-27,29,31 (S.T.) HALL 107
LK-38 (S.T.)
PROVIDE POWER AND CONTROL CONNECTIONS AS REQUIRED FOR MOTORIZED PROJECTION SCREEN. COORDINATE LOCATION AND REQUIREMENTS WITH ARCHITECT / MOTORIZED PROJECTION SCREEN VENDOR.
3-#3, #8 GRND., 1 1/4"C. PANEL "HK" PANEL "LK" TRANSFORMER "TXLK" SUSPENDED
STOR. 101B
LK-42
FLUSH MOUNTED OUTLET BOX FOR MOTORIZED PROJECTION SCREEN CONTROL DEVICE. CONTROL DEVICE SHALL BE FURNISHED BY MOTORIZED PROJECTION SCREEN VENDOR. ELECTRICAL CONTRACTOR SHALL PROVIDE CONDUIT, CONDUCTORS, TERMINATIONS, AND INSTALLATION OF VENDOR FURNISHED CONTROLLER. COORDINATE LOCATION AND REQUIREMENTS WITH ARCHITECT / VENDOR.
WOMEN 106
LK-43,45,47 (S.T.)
JAN. 104
101A
LK-35,37,39 (S.T.) LK-44 (S.T.)
SWITCH FURNISHED INTEGRAL TO KITCHEN HOOD CONTROL PANEL.
D. 103
MEN 105
PROVIDE POWER AND CONTROL CONNECTIONS TO AIR CURTAIN FAN / DOOR SWITCH FURNISHED BY KITCHEN EQUIPMENT VENDOR.
LK55,57 CANTEEN 100
REFER TO ENLARGED PARTIAL POWER PLAN 2/E3-1 FOR REQUIREMENTS WITHIN AREA INDICATED.
101C
30A., 250V., 3P., NF, NEMA-4X STAINLESS STEEL DISCONNECT SWITCH. MOUNT SWITCH BELOW POT WASH SINK COUNTER. KEF-1 STOR. 102
PROVIDE LINE CONNECTIONS AT JUNCTION BOX FURNISHED WITH REFRIGERATION EQUIPMENT.
WOMEN 106
LIGHT SWITCH FURNISHED WITH COOLER / FREEZER.
HALL 107
D. 103
KITCHEN 101
30A., 250V., 2P., NF, NEMA-4X STAINLESS STEEL DISCONNECT SWITCH. MOUNT SWITCH ABOVE AIR CURTAIN FAN.
CLASSROOM 108
PROVIDE CONNECTION TO FIXTURE / DEVICE FURNISHED WITH COOLER / FREEZER AT NOTE NO. 21.
LCA1-1 LCA1-3,5 HALL 124
EF-2 DF-1
LA1-22 LA1-16
HALL 109
MANUAL MOTOR STARTER FOR USE AS SERVICE DISCONNECT SWITCH SHALL BE SQUARE D CLASS 2510, TYPE FW1P.
LA1-1,3,5
ALL CONDUIT PENETRATIONS THROUGH COOLER / FREEZER PANELS SHALL HAVE SEAL FITTINGS WITH SEALANT. SEAL ALL PENETRATIONS.
LA1-23 LCA-13
LCA1-35,37,39
FURNISH AND INSTALL ALL CONTROL INTERLOCK WIRING TO REFRIGERATION RACK / CONDENSING UNIT ON ROOF AS REQUIRED BY CONTROL WIRING DIAGRAMS FURNISHED BY REFRIGERATION EQUIPMENT VENDOR.
LCA-25,27 LA-40 PREP. 158
LCA1-45
LA1-21
STOR. 159
LCA-55 OFFICE 119
LCA1-42
LCA1-13
D.L. CLASSROOM 169
LA1-19
LCA1-22
LCA1-28
LCA1-30
OFFICE 120
MANUAL MOTOR STARTER FOR USE A SERVICE DISCONNECT SHALL BE SQUARE D CLASS 2510, TYPE FW2P.
MULTIPURPOSE 161
LCA1-32
ROUTE CONTROL AND INTERLOCK WIRING TO COOLER / FREEZER / "FCU" UNIT AS REQUIRED.
LCA-29
MOUNT DEVICE AS REQUIRED TO REGISTER TABLE. COORDINATE REQUIREMENTS WITH ARCHITECT / KITCHEN CONSULTANT. LCA-55
LCA1-40
LCA-26,28
TYPICAL
LCA-47 D.L. CLASSROOM 168
LCA1-2
LCA1-48 WORK 116
TYPICAL
LCA1-7
LCA1-11 STOR. LCA1-9 117
LCA1-38
LCA1-49
TRANSFORMER "TXLCA" LCA1-19,21
LA-21,23 LCA-30 JAN. 167
SEMINAR ROOM 115
LCA1-55, 57,59
STOR 164
TRANSFORMER "TXLA"
LCA1-4
TYPICAL
HOOD CONTROL PANEL FURNISHED BY KITCHEN EQUIPMENT VENDOR AND INSTALLED BY ELECTRICAL CONTRACTOR.
LA-7,9,11
TYPICAL LA19,11
TERMINATE AT LOAD SIDE POLE OF NORMALLY OPEN CONTACT IN FIRE SUPPRESSION PANEL. PROVIDE PARALLEL CONNECTION TO SHUNT TRIP CIRCUIT BREAKER CONTROL COILS AT PANEL "LK". REFER TO HOOD VENDOR FURNISHED WIRING DIAGRAMS.
LA-19
LA1-26
LCA1LA1-12,14 24,26 LA113,15
PROVIDE POWER CONNECTION TO FIRE SUPPRESSION PANEL FURNISHED AND INSTALLED BY THE FIRE SUPPRESSION CONTRACTOR. COORDINATE LOCATION WITH FIRE SUPPRESSION CONTRACTOR.
LCA-49
LCA-53
D.L. CLASSROOM 121
PANEL "LA1"
LIBRARY 110
TYPICAL
LA1-6,8,10
4 - #3, #8 GRND., 1 1/4" CONDUIT. PROVIDE LINE SIDE CONNECTION TO LOAD CENTER FURNISHED WITH SERVING UNIT.
LA-37
LCA1-50 LA1-2,4
1" CONDUIT WITH PULLCORD ROUTED IN SLAB TO COMPUTER IN KITCHEN OFFICE. TERMINATE AT COMMUNICATION OUTLET IN KITCHEN OFFICE.
PHYSICS 157
LCA1-6,8
LA1-25 PANEL "LCA1"
LA-22,24
LA-20
LCA1-41
TYPICAL
PROVIDE #12/2 WITH GROUND SJO CORD AND CORD CAP. TERMINATE AT ICE MACHINE AS REQUIRED.
LCA-51
HALL 125
COMPUTER 118
COORDINATE LOCATION OF REFRIGERATION RACK / CONDENSING UNIT WITH ARCHITECT / EQUIPMENT VENDOR.
LA-38
HALL 165
PANEL "LCA" PANEL "LA" LA-8,10
TYPICAL
MECH. 166
WOMEN 162
MEN 163
PROVIDE 120 VOLT CONNECTION AS REQUIRED AT JUNCTION BOX FURNISHED WITH HOOD FOR LIGHTING FIXTURES.
LCA-43
3 - #8, #8 GRND., 1 1/4" CONDUIT.
LA-12,14,16
3 - #4, #8 GRND., 1 1/4" CONDUIT.
PANEL "HA" PANEL "HDPA"
LCA-28 LA-25,27
LCA-18
LCA-26
PROVIDE OCTAGON BOX IN WALL AT 48" ABOVE FINISHED FLOOR. ROUTE A 1/2" CONDUIT WITH PULLCORD TO FIRE SUPPRESSION PANEL. COORDINATE ROUTE WITH FIRE SUPPRESSION CONTRACTOR. PROVIDE LINE SIDE CONNECTION TO LOAD CENTER FURNISHED WITH SERVING UNIT.
LCA1-47 SEMINAR ROOM 114
TYPICAL
30A., 250V., 3P., NF, NEMA-3R DISCONNECT SWITCH. MOUNT SWITCH ABOVE ROOF. PROVIDE SWITCH SUPPORT IN ACCORDANCE WITH ROOFING CONTRACTOR REQUIREMENTS.
DF-1 CLASSROOM 122
PANEL "MDP"
HALL 126
LCA-48,50
LA-13,15,17 LCA-45
LCA-42
LCA-44,46
LCA-56,58 LCA-52,54
PROVIDE LINE AND LOAD SIDE TERMINATIONS AT DISPOSAL CONTROL PANEL AS REQUIRED. COORDINATE REQUIREMENTS WITH KITCHEN EQUIPMENT VENDOR FURNISHED DRAWINGS.
LIBRARY OFFICE 112 SEMINAR ROOM 111
LCA1-58
SEMINAR ROOM 113
LA1-18,20
PROVIDE POWER CONNECTION TO SECURITY GATE AS REQUIRED. COORDINATE REQUIREMENTS WITH ARCHITECT / OWNER.
LA1-17 LCA-33,35
LCA1-15
LCA-31 CLASSROOM 123
METER
MAIN SHUNT-TRIP PUSHBUTTON. REFER TO POWER RISER DIAGRAM 2/E3-2 FOR REQUIREMENTS.
100A., 250V., 3P., NF, NEMA-4X STAINLESS STEEL DISCONNECT SWITCH.
LCA-34,36 LCA-32
LCA-37,39
FLOOR BOX SHALL BE HUBBELL CAT. NO. HBLCFB401CB WITH HUBBELL CAT. NO. HBLTCGNTSW COVER FLANGE ASSEMBLY. PROVIDE TWO (2) - HUBBELL CAT. NO. HBLST302SGY DUPLEX FACE PLATES AND ONE (1) - HUBBELL CAT. NO. HBLDE301SGY STYLE LINE FACE PLATES. PROVIDE ALL ACCESSORIES FOR A COMPLETE INSTALLATION. COORDINATE FLOOR BOX LOCATION WITH ARCHITECT / OWNER.
LCA-41
LA-29 D.L. COMPUTER 133
LCA1-43
HALL 127
CLASSROOM 130
LCA1-44,46
CLASSROOM 131
CLASSROOM 132
FLOOR BOX SHALL BE HUBBELL CAT. NO. 3SFBC WITH HUBBELL CAT. NO. 3SFBCGYA COVER FLANGE ASSEMBLY. PROVIDE ONE (1) - HUBBELL CAT. NO. 3SFBRP DUPLEX KNOCKOUT AND ONE (1) - HUBBELL CAT. NO.L 3SFBDS STYLE LINE OPENING. PROVIDE ALL ACCESSORIES FOR A COMPLETE INSTALLATION. COORDINATE FLOOR BOX LOCATION WITH ARCHITECT / OWNER. PROVIDE POWER AND CONTROL CONNECTIONS AS REQUIRED FOR AUTOMATIC DOOR OPENER. COORDINATE LOCATION AND REQUIREMENTS WITH ARCHITECT / AUTOMATIC DOOR OPENER VENDOR.
LCA-38,40 LA-30
FLUSH MOUNTED OUTLET BOX FOR AUTOMATIC DOOR OPENER CONTROL DEVICE. CONTROL DEVICE SHALL BE FURNISHED BY AUTOMATIC DOOR OPENER VENDOR. ELECTRICAL CONTRACTOR SHALL PROVIDE CONDUIT, CONDUCTORS, TERMINATIONS, AND INSTALLATION OF VENDOR FURNISHED CONTROLLER. COORDINATE LOCATION AND REQUIREMENTS WITH ARCHITECT / AUTOMATIC DOOR OPENER VENDOR. SECURITY GATE CONTROLLER MOUNTED BELOW DESK. PROVIDE POWER CONNECTION TO / FROM SECURITY GATE AS REQUIRED. MOUNT AT ELEVATION SELECTED BY ARCHITECT / OWNER.
STRIDDE, CALLINS & ASSOCIATES INC. CONSULTING MECHANICAL
*
ENGINEERS ELECTRICAL
(361) 883-9199 Fax (361) 883-9177 342 S. Navigation Blvd. Corpus Christi, TX 78405-3615 Registration # F-006328
ELECTRICAL LEGEND NOTE:
SYMBOL
I.T. 156
SYMBOL
S
RACEWAY WITH NUMBER OF CONDUCTORS INDICATED
WALL OUTLET WITH SURFACE MOUNTED FIXTURE AS SCHEDULED
RACEWAY IN CONCRETE FLOOR SLAB AND/OR WALLS WITH NUMBER OF CONDUCTORS INDICATED
LA2-15
RECEPTACLE - SEE WIRING DEVICE SCHEDULE
FIRE 160
MANUAL MOTOR STARTER, SURFACE MOUNTED
E LA1,2
1"
DISCONNECT SWITCH CONTROL TIME CLOCK - SEE DRAWING NOTES
J
JUNCTION BOX
UNGROUNDED CONDUCTORS CONDUCTOR SIZE INDICATED IF OTHER THAN NO. 12 AWG
208 VOLT OR 240 VOLT SINGLE PHASE CONNECTION TO EQUIPMENT NOTED
#10
CONDUCTORS SHALL BE SIZE INDICATED FOR ENTIRE LENGTH OF CIRCUIT
208 VOLT OR 240 VOLT THREE PHASE CONNECTION TO EQUIPMENT NOTED
LCA3-2, 4,6 PANEL "LCA3"
ELECTRICAL BRANCH CIRCUIT PANEL AS NOTED
277 VOLT SINGLE PHASE CONNECTION TO EQUIPMENT NOTED
OFFICE 151
DISTRIBUTION PANEL OR SWITCHBOARD AS NOTED
480 VOLT THREE PHASE CONNECTION TO EQUIPMENT NOTED
TELEPHONE BOARD
CONTROL OUTLET AND CONNECTIONS AS REQUIRED COMBINATION TELEPHONE/DATA TRANSMISSION OUTLET BOX SEE SPECIFICATIONS
CLASSROOM 148 OFFICE 154
CLASSROOM 145
CLASSROOM 146
CLASSROOM 147
OFFICE 150
BRANCH CIRCUIT BREAKER SIZE IN PANEL INDICATED IF OTHER THAN 1P20A NEUTRAL CONDUCTOR
120 VOLT SINGLE PHASE CONNECTION TO EQUIPMENT NOTED
LCA38,10
PANEL AND CIRCUIT NUMBERS
CONDUIT SIZE IF INDICATED
30/2
T
EXISTING RACEWAY
ARROWS INDICATE HOME RUN TO PANEL
CONTACTOR - C
LCA312,14 LCA3-19, 21,23
UNDERGROUND RACEWAY
WALL SWITCH - SEE WIRING DEVICE SCHEDULE
C
DESCRIPTION
CEILING OUTLET WITH FIXTURE AS SCHEDULED
UG
LCA318,20
LCA3-25, 27,29
OFFICE 155
DESCRIPTION
CEILING OUTLET WITH FLUORESCENT FIXTURE AS SCHEDULED
LCA3-22, 24,26
LCA3-28,30
THIS IS A STANDARD LEGEND. ALL SYMBOLS AND ABBREVIATIONS HEREIN MAY NOT BE APPLICABLE TO THIS PROJECT.
TS
SPRINKLER SYSTEM TAMPER SWITCH - SEE SPECIFICATIONS
FS
SPRINKLER SYSTEM FLOW SWITCH - SEE SPECIFICATIONS
TV
TELEVISION OUTLET BOX - SEE SPECIFICATIONS
RTU
H
FIRE ALARM SYSTEM HEAT DETECTOR
FPB
FAN POWERED BOX
FA
FIRE ALARM SYSTEM MANUAL STATION
EWC
ELECTRIC WATER COOLER
FACP
FIRE ALARM SYSTEM CONTROL PANEL
EWH
ELECTRIC WATER HEATER
RA
WP
S
FIRE ALARM SYSTEM SMOKE DETECTOR
FL
FIRE ALARM SYSTEM STROBE
F
FIRE ALARM SYSTEM COMBINATION HORN/STROBE
F
HALL 152
HWCP
FIRE ALARM SYSTEM REMOTE ANNUNCIATOR
HOT WATER CIRCULATION PUMP WEATHERPROOF DEVICE OR ENCLOSURE
RTVAV EF
PACKAGED ROOFTOP VAV UNIT EXHAUST FAN
TYP.
FIRE ALARM SYSTEM EXTERIOR HORN
PACKAGED ROOFTOP UNIT
TYPICAL
WP
FL
C
F
CEILING MOUNTED FIRE ALARM SYSTEM STROBE CEILING MOUNTED FIRE ALARM SYSTEM COMBINATION HORN/STROBE
C
OFFICE 153
LA2-16 OFFICE 149
LCA2-22,24
LCA2-20
LA2-17
LCA2-19,21
LCA2-17
LCA2-14
LCA2-16,18
WIRING DEVICE LEGEND AND SCHEDULE
LCA2-10,12 LCA2-8
SYMBOL CHARACTERISTICS #10 LA2-8
LA2-1,3,5
LA2-10,12,14
HALL 144
LA2-18
LCA3-1 #10
OFFICE 138 HALL 143
LCA2-13,15 LCA2-11
LCA2-2
LCA2-5
120-277
20
SINGLE POLE SWITCH
CSB20AC1
CSB120
CSB1-20
3-WAY
120-277
20
THREE-WAY SWITCH
CSB20AC3
CSB320
CSB3-20
4-WAY
120-277
20
FOUR-WAY SWITCH
CSB20AC4
CSB420
CSB4-20
SD
ELECTRONIC DIMMER
120
-
SINGLE POLE DIMMER SWITCH
NEMA 5-20R
125
20
DUPLEX CONVENIENCE OUTLET
5362A
HBL5366
5366
NEMA 5-20R
125
20
GFI RECEPTACLE
2095
GF5362
7899
NEMA 5-20R
125
20
WEATHERPROOF GFI CONVENIENCE RECEPTACLE
2095
GF5362
7899
NEMA 14-20R
125/250
20
3820
HBL8410
NEMA 5-20R
125
20
ISOLATED GROUND RECEPTACLE - ORANGE
IG6300
IG5362
5362IG
NEMA 18-20R
120/208
20
THREE PHASE, 4-WIRE, 4-POLE RECEPTACLE
3822
HBL7250
7250-FR
NEMA 18-50R
120/208
50
THREE PHASE, 4-WIRE, 4-POLE RECEPTACLE
-
HBL8350A
8350-A
277/480V. GEAR
18 [KA] A.I.C.
GFI
120/240V. GEAR
10 [KA] A.I.C.
WP GFI
LIGHTING LCA2-7,9
LCA2-4,6 LCA2-1
LA2-13
A/C LOADS: HEATING COOLING
OFFICE 141 CLASSROOM 135
CLASSROOM 136
CLASSROOM 137
OFFICE 139
84.3 [KVA] *
MISC. EQUIPMENT
LA2-7,9
10.5 [KVA] 20 50
30[KA] A.I.C.
LA2-4,6 METER BY POWER UTILITY COMPANY.
STOR. 140
-
EXISTING PAD MOUNTED TRANSFORMER AT TECH. BUILDING "E".
PANEL "MDP"
SURFACE MOUNTED
SURFACE MOUNTED
PAD MOUNTED TRANSFORMER BY POWER UTILITY COMPANY. PAD BY CONTRACTOR. COORDINATE TRANSFORMER PAD REQUIREMENTS WITH POWER UTILITY COMPANY.
LA-39 #10
#10
2"C. BY CONTRACTOR FOR METER CABLES INSTALLED BY POWER UTILITY COMPANY.
UG
UG
4 - #1, #6 GRND, 1 1/2"C.
2 - 4" CONDUIT WITH PULLCORD.
GENERAL NOTES:
25[KA] A.I.C.
4-#6, #6 GRND., 1"C.
PANEL "HA" 250A. M.L.O. SQUARE D NF WITH 1-2P-20A. EDB 30-1P-20A. EDB 4-1P-15A. EDB 6-1P-SPACES
PANEL "LCA2"
1200A. 100% RATED WITH INTEGRAL GROUND FAULT AND PHASE FAILURE MAIN ELECTRONIC C/B SQUARE D I-LINE TYPE HCP PROTECTION WITH 1-3P-500A. LC 1-3P-150A. HG 3-3P-125A. HG 1-3P-100A. HG 1-3P-90A. HG 1-3P-70A. HG 2-3P-60A. HG 1-3P-35A. HG 1-3P-15A. HG 3-3P-SPACES HG
TVSS DEVICE SQUARE D TVS4EMA24A
PANEL "HDPA" SURFACE MOUNTED 600A. M.L.O. SQUARE D I-LINE TYPE NF (84-CIRCUIT PANEL) WITH 1-3P-30A. EGB 7-3P-25A. EGB 14-3P-20A. EGB 2-3P-15A. EGB 1-1P-40A. EGB 3-1P-35A. EGB 1-1P-25A. EGB 1-1P-20A. EGB 6-1P-SPACES EGB
2 - 2 1/2" CONDUITS WITH 3 - #250 MCM, #1 NEUT., #2 GRND., IN EACH
#3/0 GRND., 1 1/4"C.
4 - 3" CONDUITS WITH 4 - #350 MCM IN EACH CONDUIT.
UG
NOTES: (POWER RISER DIAGRAM ONLY) PROVIDE CIRCUIT BREAKER, CONDUIT, AND CONDUCTORS AS REQUIRED BY TVSS DEVICE.
NOTES: (ELECTRICAL POWER FLOOR PLAN ONLY) ONE (1) - 2-GANG BOX WITH TWO (2) - 1" CONDUIT FROM BOX TO ABOVE ACCESSIBLE CEILING.
MOUNT ADJACENT TO OR ABOVE GEAR TO BE PROTECTED. CONDUCTOR LENGTH SHALL BE AS SHORT AS POSSIBLE.
INSTALL OUTLET BOX FLUSH IN SUSPENDED CEILING. COORDINATE LOCATION WITH ARCHITECT.
3/4" X 10' COPPER GROUND ROD.
FURNISH AND INSTALL FLUSH MOUNTED JUNCTION BOX FOR CCTV CAMERA BY OWNER. REFER TO TELEVISION / CAMERA DETAIL 3/E3-1 FOR REQUIREMENTS.
INSTALL GROUND BOND TO WATER MAIN AND BUILDING STEEL AS REQUIRED BY N.E.C.
4-#1/0, #6 GRND., 1 1/2"C. 3 - #6, #8 GRND., 3/4"C.
3 - #3, #8 GRND., 1 1/4"C.
4-#6, #6 GRND., 1"C. TVSS DEVICE SQUARE D TVS4EMA16A
PANEL "HK"
PROVIDE A TOTAL OF TWO (2) - 2-GANG BOXES WITH TWO (2) - 2" CONDUIT FROM EACH BOX TO ABOVE ACCESSIBLE CEILING.
THREE (3) - 3/4" X 10' COPPER GROUND RODS SPACED 10'-0" APART.
REFER TO TELEVISION / CAMERA DETAIL 3/E3-1 FOR REQUIREMENTS.
ROUTE CONDUIT BELOW EXISTING CONCRETE FLATWORK AND TRANSFORMER FOUNDATION AS REQUIRED TO INSTALL CONDUIT IN PRIMARY COMPARTMENT OF EXISTING PAD MOUNTED TRANSFORMER.
INSTALL SURFACE RACEWAY 6" ABOVE COUNTER OR SPLASH. SURFACE RACEWAY SHALL BE WIREMOLD CAT. NO. 4,000 SERIES RACEWAY. PROVIDE RACEWAY BASE, COVER, DIVIDER, WIRE CLIPS, COUPLINGS, SEAM CLIP, BLANK END FITTINGS, WALL BOX CONNECTOR, FACEPLATES, ETC. AS REQUIRED FOR A COMPLETE INSTALLATION. CONDUIT RACEWAYS TO WIREMOLD RACEWAYS SHALL BE CONCEALED FLUSH IN WALL. ALL CONDUIT SHALL ENTER WIREMOLD RACEWAY VIA WALL BOX CONNECTOR.
PROVIDE RED MUSHROOM HEAD MOMENTARY CONTACT PUSHBUTTON (130 VOLT RATED) IN A NEMA 3-R DIE-CAST LOCKABLE ENCLOSURE. PROVIDE ENGRAVED LABEL WHICH IS 1/8" THICK WHITE PLASTIC WITH RED SUNKEN LETTERS (3/4" STROKE) TO READ "MAIN ELECTRICAL DISCONNECT". PROVIDE REQUIRED CONNECTION TO SHUNT TRIP CONTROL COIL IN MAIN CIRCUIT BREAKER OF MAIN SWITCHBOARD "MS". REFER TO ELECTRICAL SITE PLAN FOR LOCATION.
TWO (2) - 1" CONDUIT WITH PULLCORD. ROUTE CONDUIT FLUSH IN WALL FROM WIREMOLD WALL BOX CONNECTOR TO ABOVE ACCESSIBLE CEILING.
FLUSH MOUNTED
#6 GRND., 1/2"C.
4" 4"
REFER TO TELEVISION / CAMERA DETAIL 3/E3-2 FOR REQUIREMENTS.
6'-5"
2'-10"
1'-6"
PANEL "LA"
PANEL "LCA"
SURFACE MOUNTED
SURFACE MOUNTED
150A. MAIN C/B SQUARE D NQ (54-CIRCUIT PANEL) WITH 1-3P-100A. QOB 1-3P-60A. QOB 1-2P-30A. QOB 38-1P-20A. QOB 8-1P-SPACES
250A. MAIN C/B WITH ISOLATED AND EQUIPMENT GROUND BAR SQUARE D NQ (72-CIRCUIT PANEL) WITH 1-3P-100A. QOB 3-3P-60A. QOB 45-1P-20A. QOB 15-1P-SPACES
3-#1/0, #6 GRND, 1 1/2"C.
TVSS DEVICE SQUARE D TVS2EMA12A
CORNER WALL
CAMERA BOX WINDOW 1' 2'
4"W x 4"H x 4"D NEMA-1 BOX WITH COVER. PROVIDE 2" CLOSE NIPPLE IN COVER.
FURNISH AND INSTALL FLUSH MOUNTED JUNCTION BOX FOR CCTV CAMERA BY OWNER. REFER TO TELEVISION / CAMERA DETAIL 3/E3-2 FOR REQUIREMENTS.
3 - #250 MCM, #500 MCM NEUT., #2 ISOL. GRND., #2 GRND., 3"C. 4-#6, #6 GRND., 1"C.
#1/0 GRND., 3/4"C.
FLUSH MOUNTED OUTLET BOX FOR AUTOMATIC DOOR OPENER CONTROL DEVICE. CONTROL DEVICE SHALL BE FURNISHED BY AUTOMATIC DOOR OPENER VENDOR. ELECTRICAL CONTRACTOR SHALL PROVIDE CONDUIT, CONDUCTORS, TERMINATIONS, AND INSTALLATION OF VENDOR FURNISHED CONTROLLER. COORDINATE LOCATION AND REQUIREMENTS WITH ARCHITECT / AUTOMATIC DOOR OPENER VENDOR.
#1/0 GRND., 3/4"C.
4 - #1/0, #6 GRND., 1 1/2"C.
PROVIDE POWER AND CONTROL CONNECTIONS TO ELECTRIC GONG. INSTALL ELECTRIC GONG FURNISHED BY FIRE SPRINKLER CONTRACTOR AT LOCATION SELECTED BY FIRE SPRINKLER CONTRACTOR. COORDINATE REQUIREMENTS AND WIRING DIAGRAMS WITH / FROM FIRE SPRINKLER CONTRACTOR.
2" CONDUIT
75 KVA K-13 RATED
.
.
2" CONDUIT TO ABOVE ACCESSIBLE CEILING TV BOX
TRANSFORMER "TXLCA"
45 KVA
.
112.5 KVA
ONE (1) - 1" CONDUIT WITH PULLCORD. ROUTE CONDUIT FLUSH IN WALL FROM WALL BOX CONNECTOR TO BELOW CONCRETE SLAB. ROUTE BELOW CONCRETE SLAB TO WALL INDICATED, RISE UP CONCEALED IN WALL TO ABOVE ACCESSIBLE CEILING.
TRANSFORMER "TXLA"
250A. M.L.O. SQUARE D I-LINE TYPE HCN WITH 1-3P-150A. HD 1-3P-60A. FA 2-3P-15A. FA 12-1P-20A. FA 6-1P-SPACES
TRANSFORMER "TXLK"
PROVIDE POWER AND CONTROL CONNECTIONS AS REQUIRED FOR AUTOMATIC DOOR OPENER. COORDINATE LOCATION AND REQUIREMENTS WITH ARCHITECT / AUTOMATIC DOOR OPENER VENDOR.
SEE DRAWING NOTES
* N.E.C. PERMITTED DIVERSITY HAS BEEN REMOVED FROM LOAD QUANTITY INDICATED.
LCA2-3
INFORMATION INCLUDED ON THIS DRAWING IS INTENDED TO INDICATE THE GENERAL CHARACTER AND EXTENT OF WORK REQUIRED. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
-
711.3 [KVA]
LA2-11
1.
-
478.5 [KVA] 276.1 [KVA]
TOTAL CONNECTED LOAD
PANEL "LA2"
SINGLE PHASE, 4-WIRE, 3-POLE, GROUNDING LIGHT DUTY RECEPTACLE
-
REMARKS
102.9 [KVA] *
* KITCHEN EQUIPMENT
LA2-19
20
35.1 [KVA]
*
OFFICE 142
#10
D.L. CLASSROOM 134
SPST
CONNECTED LOADS:
LCA3-3,5
MANUFACTURER'S REFERENCE P. & S. HUBBELL LEVITON
DESCRIPTION
S S3 S4
THE FOLLOWING MINIMUM FAULT CURRENT RATINGS SHALL BE REQUIRED UNLESS OTHER FAULT CURRENT RATINGS ARE INDICATED:
LA2-2
RATING VOLTS AMPS
FLOOR
2'-6"
4 - #500 MCM, #1/0 GRND., 4"C. 4-#6, #6 GRND., 1"C. TVSS DEVICE SQUARE D TVS2EMA12A
4 - #3, #6 GRND., 1 1/4"C.
4 - #3, #6 GRND., 1 1/4"C.
3 - # 3, #4/0 NEUT., #6 ISOL. GRND., #6 GRND., 2"C.
4 - # 3, #6 ISOL. GRND., #6 GRND., 2"C.
3 - # 6, #3 NEUT., #8 ISOL. GRND., #8 GRND., 1 1/2"C.
PANEL "LK"
PANEL "LA1"
PANEL "LA2"
PANEL "LCA1"
PANEL "LCA2"
PANEL "LCA3"
FLUSH MOUNTED
SURFACE MOUNTED
SURFACE MOUNTED
SURFACE MOUNTED
SURFACE MOUNTED
SURFACE MOUNTED
350A. MAIN C/B SQUARE D NQ (84-CIRCUIT PANEL) WITH 1-3P-90A. QOB 1-3P-90A. QOB (S.T.) 1-3P-80A. QOB (S.T.) 1-3P-60A. QOB 2-3P-50A. QOB (S.T.) 2-3P-30A. QOB 1-3P-20A. QOB (S.T.) 1-3P-15A. QOB 1-2P-40A. QOB 1-2P-20A. QOB (S.T.) 1-2P-15A. QOB 2-1P-20A. QOB (S.T.) 28-1P-20A. QOB 10-1P-SPACES
225A. M.L.O SQUARE D NQ WITH 34-1P-20A. QOB 8-1P-SPACES
100A. M.L.O SQUARE D NQ WITH 24-1P-20A. QOB 6-1P-SPACES
225A. M.L.O WITH ISOLATED AND EQUIPMENT GROUND BAR SQUARE D NQ (72-CIRCUIT PANEL) WITH 59-1P-20A. QOB 13-1P-SPACES
225A. M.L.O WITH ISOLATED AND EQUIPMENT GROUND BAR SQUARE D NQ WITH 34-1P-20A. QOB 8-1P-SPACES
225A. M.L.O. WITH ISOLATED AND EQUIPMENT GROUND BAR SQUARE D NQ WITH 30-1P-20A. QOB
STRIDDE, CALLINS & ASSOCIATES INC. CONSULTING MECHANICAL
*
ENGINEERS ELECTRICAL
(361) 883-9199 Fax (361) 883-9177 342 S. Navigation Blvd. Corpus Christi, TX 78405-3615 Registration # F-006328
GENERAL NOTES: NOTES: 1.
INFORMATION INCLUDED ON THIS DRAWING IS INTENDED TO INDICATE THE GENERAL CHARACTER AND EXTENT OF WORK REQUIRED. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
INSTALL OUTLET BOX FLUSH IN SUSPENDED CEILING. COORDINATE LOCATION WITH ARCHITECT.
ENTRY PORCH 125
MOUNT AT 4'-5" ABOVE FINISHED FLOOR. ONE (1) - 2-GANG BOX WITH TWO (2) - 1" CONDUIT FROM BOX TO ABOVE ACCESSIBLE CEILING.
PROVIDE A 4"W X 4"H X 4"D NEMA-1 FLUSH BOX WITH COVER. PROVIDE A 3" CLOSE NIPPLE IN COVER. PROVIDE A 3" CONDUIT WITH PULLCORD TO ABOVE ACCESSIBLE CEILING. MOUNT AT 4'-5" ABOVE FINISHED FLOOR.
REMOVE EXISTING GFI RECEPTACLE AND WEATHER-PROOF COVER. PROVIDE AND INSTALL NEW DUPLEX RECEPTACLE WITH STAINLESS STEEL COVERPLATE.
PROVIDE A 4"W X 4"H X 4"D NEMA-1 FLUSH BOX WITH COVER. PROVIDE A 3" CLOSE NIPPLE IN COVER. PROVIDE A 3" CONDUIT WITH PULLCORD TO ABOVE ACCESSIBLE CEILING.
MECH. 207 OFFICE 106
OFFICE 105
LC-33
LC-41
OFFICE 104
OFFICE 206 OFFICE 208
LARGE CLASSROOM 124
LC-35
CLASSROOM 210
PANEL "C" CORRIDOR 204
MEDIUM CLASSROOM 111
SMALL CLASSROOM 110
STUDENT AREA 109
OFFICE 205
CONFERENCE 108
OFFICE 107
LC-40,42
LC-43
LC-29,31
OFFICE 103
WAIT/ SECR. 102
OFFICE 209
A-26 FILE STORAGE 122
JAN. 123
CORRIDOR 200
LC-17,19 LC-37,39
LC-21,23
LC-36,38
LC-25,27
EXISTING PANEL "A" EXISTING PANEL "B"
FIBER OPTIC 115
WOMEN 112
LIBRARY 121
COMP. LAB 117
TELECONF. 116
MECH. 114
COMP. LAB 118
OBSERVATION 119
PRODUCTION ROOM 101
CONFERENCE 203
CLASSROOM 202
CLASSROOM 201
NEW PANEL "DPA" TO REPLACE EXISTING
MEN 113
STORAGE 120
ENTRY PORCH 126
4-#6, #6 GRND., 1"C.
EXISTING MAIN SWITCHBOARD "MDP" EXISTING METER
EXISTING POWER UTILITY COMPANY PAD MOUNTED TRANSFORMER
#3/0 GRND., 3/4"C.
EXISTING PANEL "DPA"
PAD MOUNTED NEMA-3R SERVICE ENTRANCE RATED 1200A. MAIN C/B WITH 1-3P-600A. (EXISTING COMPLEX) 1-3P-600A. (BUILDING D) 1-3P-400A. (ADMIN. BUILDING) 1-3P-225A. (SPARE)
LIGHTING
A/C LOADS: HEATING COOLING TOTAL CONNECTED LOAD
79.8 [KVA] 105.1 [KVA]
EXISTING POWER UTILITY COMPANY PAD MOUNTED TRANSFORMER
198.1 [KVA]
* N.E.C. PERMITTED DIVERSITY HAS BEEN REMOVED FROM LOAD QUANTITY INDICATED.
TO POWER UTILITY COMPANY DIP POLE
TWO (2) - 4" CONDUIT WITH 4-#500 MCM, #1/0 GRND., IN EACH.
UG
#3/0 GRND., 3/4"C.
PAD MOUNTED NEMA-3R SERVICE ENTRANCE RATED 1200A. MAIN C/B WITH 1-3P-600A. (EXISTING COMPLEX) 1-3P-800A. (BUILDING D) 1-3P-400A. (ADMIN. BUILDING) 1-3P-225A. (SPARE)
TO ADMIN BUILDING
FOUR (4) - 4" CONDUIT WITH 4-#500 MCM, #1/0 GRND., IN EACH.
TO EXISTING COMPLEX
#2/0 GRND., 3/4"C.
3/4" X 10' COPPER GROUND ROD
UG
UG TWO (2) - 4" CONDUIT WITH 4-#500 MCM, #1/0 GRND., IN EACH.
4-#500 MCM, #1/0 GRND., 4"C.
UG
UG
TWO (2) - 4" CONDUIT WITH 4-#500 MCM, #1/0 GRND., IN EACH.
UG UG
TWO (2) - 4" CONDUIT WITH 4-#500 MCM, #1/0 GRND., IN EACH.
4-#500 MCM, #1/0 GRND., 4"C. TO ADMIN BUILDING
TO EXISTING COMPLEX 4-#350 MCM, #2 ISOL. GRND., #2 GRND., 4"C.
NOTES: (POWER RISER DIAGRAM ONLY) EXISTING CIRCUIT BREAKER SHALL BE REPLACED BY NEW CIRCUIT BREAKER. REFER TO REVISED PARTIAL POWER RISER DIAGRAM - BUILDING "D" FOR REQUIREMENTS.
3.0 [KVA] 4-#4/0, #4 GRND., 3"C.
21.0 [KVA] 64.8 [KVA]
4-#1/0, #6 GRND., 2"C.
141.4 [KVA]
* N.E.C. PERMITTED DIVERSITY HAS BEEN REMOVED FROM LOAD QUANTITY INDICATED.
EXISTING METER
3.0 [KVA]
TOTAL CONNECTED LOAD
57.4 [KVA] * MISC. EQUIPMENT
66.5 [KVA] * A/C LOADS: HEATING COOLING
16.2 [KVA]
*
23.5 [KVA]
MISC. EQUIPMENT
UG
UG
EXISTING BUILDING "D" CALCULATED LOADS:
EXISTING MAIN SWITCHBOARD "MDP"
BOND AT BUILDING D
UG
FOUR (4) - 4" CONDUIT WITH 4-#500 MCM, #1/0 GRND., IN EACH.
800A. MAIN C/B SQUARE D I-LINE TYPE HCP WITH ISOLATED GROUND AND EQUIPMENT GROUND BAR WITH 1-3P-300A. LA 1-3P-225A. (PANEL "A") QB 1-3P-150A. QB 1-3P-125A. (PANEL "B") QB 2-3P-100A. QB 1-3P-60A. FA 2-3P-30A. FA 1-2P-30A. FA 2-1P-20A. FA
SURFACE MOUNTED
10 [KA] A.I.C.
LIGHTING
600A. M.L.O. WITH 1-3P-225A. (PANEL "A") 1-3P-125A. (PANEL "B") 2-3P-100A. 2-3P-30A. 1-2P-30A. 1-1P-20A.
UG
UG
120/208V. GEAR
*
BOND AT BUILDING D
TO POWER UTILITY COMPANY DIP POLE
NEW PANEL "DPA"
NEW BUILDING "D" CALCULATED LOADS:
SURFACE MOUNTED
TVSS DEVICE SQUARE D TVS2EMA16A(C)
THE FOLLOWING MINIMUM FAULT CURRENT RATINGS SHALL BE REQUIRED UNLESS OTHER FAULT CURRENT RATINGS ARE INDICATED:
EXISTING PANEL "A"
EXISTING PANEL "A1"
EXISTING PANEL "B"
SURFACE MOUNTED
SURFACE MOUNTED
SURFACE MOUNTED
225A. M.L.O. WITH FEED THROUGH LUGS WITH 37-1P-20A. 5-1P-SPACE
225A. M.L.O. WITH 1-2P-20A. 37-1P-20A. 3-1P-SPACE
125A. M.L.O. WITH 36-1P-20A. 6-1P-SPACE
4-#4/0, #4 GRND., 3"C.
EXISTING DISTRIBUTION PANELBOARD SHALL BE REPLACED BY NEW DISTRIBUTION PANELBOARD. DISCONNECT AND RECONNECT ALL EXISTING CONDUIT AND CONDUCTORS ENTERING PANELBOARD AS REQUIRED. JOBSITE SURVEY REQUIREMENTS. REFER TO REVISED PARTIAL POWER RISER DIAGRAM - BUILDING "D" FOR REQUIREMENTS.
4-#1/0, #6 GRND., 2"C. 4-#6, #6 GRND., 1"C.
PROVIDE AND INSTALL NEW CIRCUIT BREAKER INDICATED IN EXISTING MAIN SWITCHBOARD "MDP". PROVIDE ALL ACCESSORIES FOR A COMPLETE INSTALLATION. JOBSITE SURVEY REQUIREMENTS AND CIRCUIT BREAKER MANUFACTURER.
EXISTING PANEL "A"
EXISTING PANEL "A1"
EXISTING PANEL "B"
NEW PANEL "C"
SURFACE MOUNTED
SURFACE MOUNTED
SURFACE MOUNTED
SURFACE MOUNTED
INSTALL NEW DISTRIBUTION PANELBOARD "DPA" IN / AT SAME APPROXIMATE LOCATION OF EXISTING DISTRIBUTION PANELBOARD "DPA" IN EXISTING MECHANICAL ROOM IN BUILDING "D". RECONNECT ALL EXISTING CONDUIT AND CONDUCTORS AT NEW DISTRIBUTION PANELBOARD AS REQUIRED. JOBSITE SURVEY REQUIREMENTS.
225A. M.L.O. WITH FEED THROUGH LUGS WITH 37-1P-20A. 5-1P-SPACE
225A. M.L.O. WITH 1-2P-20A. 37-1P-20A. 3-1P-SPACE
125A. M.L.O. WITH 36-1P-20A. 6-1P-SPACE
400A. M.L.O. SQUARE D NQ (84-CIRCUIT PANEL) WITH ISOLATED GROUND AND EQUIPMENT GROUND BAR WITH 1-3P-60A. QOB 1-3P-40A. QOB 1-3P-35A. QOB 2-2P-50A. QOB 2-2P-30A. QOB 2-2P-20A. QOB 51-1P-20A. QOB 12-1P-SPACE
BOND ISOLATED GROUND BAR AND EQUIPMENT GROUND BAR IN PANEL AS REQUIRED BY NFPA 70. PROVIDE CIRCUIT BREAKER, CONDUIT, AND CONDUCTORS AS REQUIRED BY TVSS DEVICE. A 3P/60A. CIRCUIT BREAKER IS INCLUDED WITHIN PANEL.
4-#4/0, #4 GRND., 3"C.
MOUNT ADJACENT TO OR ABOVE GEAR TO BE PROTECTED. CONDUCTOR LENGTH SHALL BE AS SHORT AS POSSIBLE. PROVIDE GROUND BOND TO BUILDING STEEL AND WATER MAIN AS REQUIRED BY N.E.C. REMOVE EXISTING BOND TO BUILDING STEEL AND WATER MAIN.
4-#4/0, #4 GRND., 3"C.
TVSS DEVICE SQUARE D TVS2EMA12A
STRIDDE, CALLINS & ASSOCIATES INC. CONSULTING MECHANICAL
*
ENGINEERS ELECTRICAL
(361) 883-9199 Fax (361) 883-9177 342 S. Navigation Blvd. Corpus Christi, TX 78405-3615 Registration # F-006328
PANEL "HK" PANEL "LK"
EWH-1
JAN. 104 STOR. 101B
101A
2-#8, #10 GRND, 3/4"C.
LK-56,58
MEN 105 KITCHEN 101
CANTEEN 100
HK-8,10,12
HK-7,9,11
101C
KSF-1 ON ROOF
CLASSROOM 108
KEF-1 WOMEN 106
STOR. 102
KEF-1 ON ROOF RTU-1 ON ROOF
MDP-7
HALL 107
D. 103
EF-2 ON ROOF
VB1-4 HA-23
EF-2
HALL 124
FPB2-3 LA1-24 FPB1-4
MDP-6
HALL 109
#10
HDPA-27
RTVAV-1
FPB2-1
#10
HDPA-11
STOR. 159
HDPA-7
FPB1-5
FPB1-1
VB2-2 OFFICE 119
HA-16
DL CLASSROOM 169
OFFICE 120
I.T. 156
MULTIPURPOSE 161
FPB2-4
#10
#10
PREP. 158
HDPA-1 HALL 125
HDPA-9
COMPUTER 118
HDPA-13
FPB2-2 MDP-11 DL CLASSROOM 168
HDPA-25
D.L. CLASSROOM 121
HA-17
RTVAV-2 ON ROOF
PHYSICS CLASSROOM 157
HDPA-15
FPB1-2
STOR. 117
#10 WORK 116
OFFICE 154
LA-34,36 HVAC DDC PANEL
EF-3
#10
FPB2-6
EWH-2 HWCP-1
HDPA-5 #10
SEMINAR ROOM 115
STOR 164
CLASSROOM 122
MEN 163
WOMEN 162
LA-31 EF-1 ON ROOF
LA-32 LA-33 JAN. 167
HDPA-17
PANEL "HDPA"
MDP-10
HA-14 HALL 129
VB2-1
RTU-2 ON ROOF
SEMINAR ROOM 113
RTVAV-3 ON ROOF
HDPA-31
HDPA-24
HA-21
FPB3-1
PANEL "MDP"
HALL 126
VB1-3
#10
HDPA-2
OFFICE 153
MDP-9 LA-35
SEMINAR ROOM 114
HA-19
HALL 165
PANEL "HA" MDP-8
VB1-2
PANEL "LA"
MECH. 166
#10
FPB1-3
LIBRARY OFFICE 112
HALL 152
HDPA-3
LIBRARY 110
SEMINAR ROOM 111
I.T. OFFICE 155
FPB2-5
VB1-1 PANEL "LA1"
RTU-3 ON ROOF
#10
HDPA-29 #10
FPB2-7 HDPA-19 CLASSROOM 123
HDPA-21
FPB2-8
HDPA-23
FPB2-9
FPB2-10
CLASSROOM 130
FPB2-11
CLASSROOM 131
FPB2-12
DL COMPUTER 133
DL CLASSROOM 134
CLASSROOM 132
HALL 127
GENERAL NOTES: 1.
2.
NOTES:
INFORMATION INCLUDED ON THIS DRAWING IS INTENDED TO INDICATED THE GENERAL CHARACTER AND EXTENT OF WORK REQUIRED. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
THREE (3) - #8, #8 GRND., 3/4"C.
30A. 250V., 2P, NF, NEMA-1 DISCONNECT SWITCH.
THREE (3) - #4, #8 GRND., 1"C.
MANUAL MOTOR STARTER FOR USE AS SERVICE DISCONNECT SHALL BE SQUARE D CLASS 2510, TYPE FG1P.
VERIFY EXACT LOCATION OF PARTITIONS, WALLS, FIXTURES, ETC. WITH DIMENSIONED ARCHITECTURAL PLANS.
THREE (3) - #1, #6 GRND., 1 1/4"C. 60A., 250V., 2P, NF, NEMA-1 DISCONNECT SWITCH. RECEPTACLE FURNISHED INTEGRAL TO UNIT. ROUTE CONDUIT AND CONDUCTORS THROUGH KITCHEN HOOD CONTROL PANEL. REFER TO NOTE 36 ON SHEET E3-1 FOR LOCATION OF KITCHEN HOOD CONTROL PANEL. ROUTE CONDUIT AND CONDUCTORS THROUGH RELAY FURNISHED AND INSTALLED BY HVAC CONTROLS CONTRACTOR. COORDINATE RELAY LOCATION WITH HVAC CONTROLS CONTRACTOR. COORDINATE DEVICE LOCATION WITH DEVICE INDICATED ON SHEET E2-1. TWO (2) - #8, #8 GRND., 3/4"C.
STRIDDE, CALLINS & ASSOCIATES INC. CONSULTING MECHANICAL
*
ENGINEERS ELECTRICAL
(361) 883-9199 Fax (361) 883-9177 342 S. Navigation Blvd. Corpus Christi, TX 78405-3615 Registration # F-006328
FIRE 160
I.T. 156
FPB3-2
OFFICE 151
HDPA-4 I.T. OFFICE 155
VB3-1
HALL 152
CLASSROOM 148
HA-24 OFFICE 150
OFFICE 154
CLASSROOM 147
FPB3-4
CLASSROOM 145
CLASSROOM 146
FPB3-5
FPB3-6
FPB3-7
FPB3-3
OFFICE 153
OFFICE 149
HDPA-6
HDPA-8
HDPA-10
HDPA-12
HDPA-26
HALL 144
HDPA-28 FPB3-12 HA-26
VB3-2 HDPA-14
HDPA-16
HDPA-18
OFFICE 142
HDPA-20 OFFICE 138
FPB3-8
FPB3-9
FPB3-10
DL CLASSROOM 134
CLASSROOM 135
CLASSROOM 136
HALL 143
FPB3-11
CLASSROOM 137
OFFICE 141
OFFICE 139
STOR. 140
GENERAL NOTES: 1.
INFORMATION INCLUDED ON THIS DRAWING IS INTENDED TO INDICATE THE GENERAL CHARACTER AND EXTENT OF WORK REQUIRED. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
2.
VERIFY EXACT LOCATION OF PARTITIONS, WALLS, FIXTURES, ETC. WITH DIMENSIONED ARCHITECTURAL PLANS.
3.
REFER TO SHEET E3-1 FOR LOCATION OF PANELS "HDPA" AND "HA".
NOTES: TWO (2) - #8, #8 GRND., 3/4"C.
STRIDDE, CALLINS & ASSOCIATES INC. CONSULTING MECHANICAL
*
ENGINEERS ELECTRICAL
(361) 883-9199 Fax (361) 883-9177 342 S. Navigation Blvd. Corpus Christi, TX 78405-3615 Registration # F-006328
ENTRY PORCH 125
MECH. 207
PANEL "C" OFFICE 106
OFFICE 105
OFFICE 104
C-44 OFFICE 206
FSD
LARGE CLASSROOM 124
FSD
OFFICE 208
FSD
C-32,34 FSD #10
MEDIUM CLASSROOM 111
SMALL CLASSROOM 110
STUDENT AREA 109
CLASSROOM 210
OFFICE 205
WAIT/ SECR. 102
CONFERENCE 108
CORRIDOR 204 FSD
FPB-4-6 FSD
FSD
C-28,30
C-24,26
OFFICE 103
OFFICE 107
#10
FSD
FPB-4-4 OFFICE 209
FSD JAN. 123
FILE STORAGE 122
RTVAV-4 ON ROOF
FPB-4-5 C-8,10
FSD
FSD
C-18,20,22
FSD
DPA-14, 16,18 FPB-4-1
FPB-4-3 CORRIDOR 200
C-45
EXISTING PANEL "A" EXISTING PANEL "B" FSD FSD
FSD
FSD
FSD
FSD
FSD
FSD
C-12,14,16
FIBER OPTIC 115
FPB-4-2
WOMEN 112
LIBRARY 121
FSD
FSD
TELECONF. 116
MECH. 114
COMP. LAB 117
OBSERVATION 119
COMP. LAB 118
CLASSROOM 202
PRODUCTION ROOM 101
CLASSROOM 201
CLASSROOM 203 MEN 113
NEW PANEL "DPA" TO REPLACE EXISTING STORAGE 120
ENTRY PORCH 126
GENERAL NOTES: 1.
2.
NOTES:
INFORMATION INCLUDED ON THIS DRAWING IS INTENDED TO INDICATE THE GENERAL CHARACTER AND EXTENT OF WORK REQUIRED. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
THREE (3) - #1, #6 GRND., 1 1/4"C.
VERIFY EXACT LOCATION OF PARTITIONS, WALLS, FIXTURES, ETC. WITH DIMENSIONED ARCHITECTURAL PLANS.
FOUR (4) - #8, #10 GRND., 1"C.
THREE (3) - #8, #10 GRND., 3/4"C.
DEVICE FURNISHED INTEGRAL TO UNIT.
STRIDDE, CALLINS & ASSOCIATES INC. CONSULTING MECHANICAL
*
ENGINEERS ELECTRICAL
(361) 883-9199 Fax (361) 883-9177 342 S. Navigation Blvd. Corpus Christi, TX 78405-3615 Registration # F-006328
STOR. 101B
101A
JAN. 104 CANTEEN 100
MEN 105
CLASSROOM 108
101C
KITCHEN 101 STOR. 102
KEF-1
HALL 107
RTU-1 ON ROOF
WOMEN 106
D. 103
EF-2
MULTIPURPOSE 161
HALL 109
PREP. 158
HALL 124
RTVAV-1 ON ROOF STOR. 159
OFFICE 119
OFFICE 120
DL CLASSROOM 169 HALL 125
COMPUTER 118
RTU-3 ON ROOF RTVAV-2 ON ROOF
PHYSICS CLASSROOM 157
DL CLASSROOM 121
LIBRARY 110
CLASSROOM 168
WORK 116
STOR. 117
SEMINAR ROOM 115
MECH. 166 HALL 165
SEMINAR ROOM 114
CLASSROOM 122
CLASSROOM 123
HALL 127
CLASSROOM 130
1.
INFORMATION INCLUDED ON THIS DRAWING IS INTENDED TO INDICATE THE GENERAL CHARACTER AND EXTENT OF WORK REQUIRED. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
2.
VERIFY EXACT LOCATION OF PARTITIONS, WALLS, FIXTURES, ETC. WITH DIMENSIONED ARCHITECTURAL PLANS.
3.
FURNISH AND INSTALL DUCT TYPE SMOKE DETECTORS AT SUPPLY AND RETURN AIR DUCTS FOR AIR HANDLING UNITS MARK "RTU-1", "RTU-2", "RTU-3", RTVAV-1", RTVAV-2", AND "RTVAV-3" INDICATED ON HVAC AND ELECTRICAL DRAWINGS. PROVIDE DETECTORS WITH AUXILIARY RELAYS, VISUAL (LED) ANNUNCIATORS, AND ENCLOSURE. REFER TO SPECIFICATIONS FOR REQUIREMENTS.
4.
SYSTEMS CABLING SUCH AS FIRE ALARM CABLING MAY BE RUN EXPOSED ONLY ABOVE ACCESSIBLE CEILING. ALL CABLING INSTALLED IN WALLS, BELOW CEILING, IN UNFINISHED SPACES (SUCH AS MECHANICAL ROOMS), AND CABLING THAT WILL BE VISIBLE TO THE OWNER MUST BE IN CONDUIT. REFER TO SPECIFICATIONS.
RTVAV-3 ON ROOF
RTU-2 ON ROOF
SEMINAR ROOM 113
LIBRARY OFFICE 112
GENERAL NOTES:
MEN 163
JAN. 167
HALL 126
SEMINAR ROOM 111
WOMEN 162
STOR 164
CLASSROOM 131
CLASSROOM 132
D.L. COMPUTER 133
NOTES: 1/2" CONDUIT WITH PULLCORD ROUTED FROM DOOR HEADER TO ABOVE ACCESSIBLE CEILING. REFER TO SHEET E3-1 FOR FLOOR BOX AND CONDUIT STUB REQUIREMENTS. PROVIDE FIRE ALARM SYSTEM MONITOR MODULE AND CONNECTION TO MONITOR STATUS OF HOOD FIRE SUPPRESSION PANEL.
STRIDDE, CALLINS & ASSOCIATES INC. CONSULTING MECHANICAL
*
ENGINEERS ELECTRICAL
(361) 883-9199 Fax (361) 883-9177 342 S. Navigation Blvd. Corpus Christi, TX 78405-3615 Registration # F-006328
FIRE 160
I.T. 156
OFFICE 151
OFFICE 155
CLASSROOM 148 OFFICE 154
CLASSROOM 147
CLASSROOM 146
CLASSROOM 145
OFFICE 150
HALL 152
OFFICE 153
OFFICE 149
HALL 157 144
HALL 143
CLASSROOM 134
CLASSROOM 135
CLASSROOM 136
OFFICE 138
OFFICE 142
OFFICE 139
OFFICE 141
CLASSROOM 137
STOR. 140
GENERAL NOTES: 1.
INFORMATION INCLUDED ON THIS DRAWING IS INTENDED TO INDICATE THE GENERAL CHARACTER AND EXTENT OF WORK REQUIRED. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
2.
VERIFY EXACT LOCATION OF PARTITIONS, WALLS, FIXTURES, ETC. WITH DIMENSIONED ARCHITECTURAL PLANS.
3.
SYSTEMS CABLING SUCH AS FIRE ALARM CABLING MAY BE RUN EXPOSED ONLY ABOVE ACCESSIBLE CEILING. ALL CABLING INSTALLED IN WALLS, BELOW CEILING, IN UNFINISHED SPACES (SUCH AS MECHANICAL ROOMS), AND CABLING THAT WILL BE VISIBLE TO THE OWNER MUST BE IN CONDUIT. REFER TO SPECIFICATIONS.
NOTES: 1/2" CONDUIT WITH PULLCORD ROUTED FROM DOOR HEADER TO ABOVE ACCESSIBLE CEILING.
STRIDDE, CALLINS & ASSOCIATES INC. CONSULTING MECHANICAL
*
ENGINEERS ELECTRICAL
(361) 883-9199 Fax (361) 883-9177 342 S. Navigation Blvd. Corpus Christi, TX 78405-3615 Registration # F-006328
ENTRY PORCH 125
MECH. 207 OFFICE 106
OFFICE 105
OFFICE 104
OFFICE 206
OFFICE 208
FSD
FSD
FSD
LARGE CLASSROOM 124
FSD FSD
CORRIDOR 204 MEDIUM CLASSROOM 111
SMALL CLASSROOM 110
STUDENT AREA 109
WAIT/ SECR. 102
CONFERENCE 108
OFFICE 107
FSD
EXISTING FIRE ALARM CONTROL PANEL
FSD
OFFICE 205
OFFICE 103
CLASSROOM 210 OFFICE 209
FSD FILE STORAGE 122
JAN. 123
FSD
FSD
FSD
FSD
RTVAV-4 ON ROOF CORRIDOR 200
FSD FSD
FSD
FSD
FSD
FSD
FSD FSD
FSD
FIBER OPTIC 115 WOMEN 112
LIBRARY 121
TELECONF. 116
MECH. 114
COMP. LAB 117
OBSERVATION 119
COMP. LAB 118
CLASSROOM 202
PRODUCTION ROOM 101
CLASSROOM 201
CLASSROOM 203 MEN 113 STORAGE 120
ENTRY PORCH 126
GENERAL NOTES:
NOTES:
1.
INFORMATION INCLUDED ON THIS DRAWING IS INTENDED TO INDICATE THE GENERAL CHARACTER AND EXTENT OF WORK REQUIRED. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
1/2" CONDUIT WITH PULLCORD ROUTED FROM DOOR HEADER TO ABOVE ACCESSIBLE CEILING.
2.
VERIFY EXACT LOCATION OF PARTITIONS, WALLS, FIXTURES, ETC. WITH DIMENSIONED ARCHITECTURAL PLANS.
REMOVE EXISTING REMOTE ANNUNCIATOR AND RELOCATE TO NEW LOCATION INDICATED BY NOTE 3. PROVIDE AND INSTALL A STAINLESS STEEL COVERPLATE ON / OVER EXISTING FLUSH MOUNTED BOX.
3.
FURNISH AND INSTALL DUCT TYPE SMOKE DETECTORS AT SUPPLY AND RETURN AIR DUCTS FOR AIR HANDLING UNIT MARK RTVAV-4 INDICATED ON HVAC AND ELECTRICAL DRAWINGS. PROVIDE DETECTORS WITH AUXILIARY RELAYS, VISUAL (LED) ANNUNCIATORS, AND ENCLOSURE. REFER TO SPECIFICATIONS FOR REQUIREMENTS.
4.
SYSTEMS CABLING SUCH AS FIRE ALARM CABLING MAY BE RUN EXPOSED ONLY ABOVE ACCESSIBLE CEILING. ALL CABLING INSTALLED IN WALLS, BELOW CEILING, IN UNFINISHED SPACES (SUCH AS MECHANICAL ROOMS), AND CABLING THAT WILL BE VISIBLE TO THE OWNER MUST BE IN CONDUIT. REFER TO SPECIFICATIONS.
5.
CONTRACTOR SHALL PROVIDE EXTENSIONS FROM THE EXISTING FIRE-LITE MS502UD FIRE ALARM CONTROL PANEL TO SERVE NEW DEVICES INDICATED AS REQUIRED. JOBSITE SURVEY EXTENSION REQUIREMENTS.
6.
CONTRACTOR SHALL PROVIDE RELAYS, POWER SUPPLY, LINE CARD, ETC., AS REQUIRED TO ADD NEW DEVICES TO THE EXISTING FIRE-LITE MS502UD FIRE ALARM CONTROL PANEL. JOBSITE SURVEY REQUIREMENTS.
7.
CONTRACTOR SHALL RE-CERTIFY THE EXISTING FIRE ALARM AND DETECTION SYSTEM WITHIN THE BUILDING AT OR NEAR COMPLETION OF PROJECT. THE CONTRACTOR SHALL INSERT THE INSPECTION / CERTIFICATION REPORT WITHIN THE OPERATION AND MAINTENANCE MANUALS.
NEW LOCATION FOR EXISTING REMOTE ANNUNCIATOR. EXTEND FIRE ALARM CABLE / CONDUCTORS AS REQUIRED. MOUNT SMOKE DETECTOR IN SKYLIGHT AT OR NEAR PEAK AS REQUIRED BY NFPA 72. COORDINATE REQUIREMENTS WITH ARCHITECTURAL SECTIONS / DETAILS. PROVIDE MONITOR MODULE TO MONITOR STATUS OF FIRE SMOKE DAMPER. COORDINATE REQUIREMENTS WITH HVAC CONTRACTOR.
STRIDDE, CALLINS & ASSOCIATES INC. CONSULTING MECHANICAL
*
ENGINEERS ELECTRICAL
(361) 883-9199 Fax (361) 883-9177 342 S. Navigation Blvd. Corpus Christi, TX 78405-3615 Registration # F-006328