UPS systems
BP-0625
Extended
Extended
6 V / 2.5 Ah
Temperature range from -30…+70 °C Up to 15 years lifetime Flexible configurations The high-quality battery pack BP-0625 functions as an energy store for the DC-UPS UPSI-1202. The CYCLON cells used in this battery pack are characterized by a very broad operating temperature range of -30…+70 °C. The CYCLON cells have a lifetime of up to 15 years which is a multiple of that of conventional lead-gel batteries.
This battery pack consists of powerful and long living CYCLON cells!
Te c h n i c a l d a t a Nominal voltage Capacitance Number of batteries Type of battery Life cycles Fuse Operating temperature Storage temperature Dimensions Weight (net)
6 V DC 2.5 Ah 3 cells à 2 V Maintenance-free CYCLON cells 10 000…300 depending on ambient temperature, charge and discharge 7.5 A, safety fuse -30…+70 °C -30…+70 °C 110 x 70 x 35 mm, ±2 mm 0.6 kg
Back up time, measured at +21 °C by means of UPSI-1202 Constant current 1 A 3 A Time app. 1 h 46 min 30 min
5 A 15.5 min
Note: 202 2 pieces For the UPSI-1 e needed! of BP-0625 ar
Drawing BP-0625 110 mm
70 mm
300 mm
7,5A
Ring terminal: 4,8 x 0,8 mm Cable: 1,5mm²
Fuse
red heat shrink tube
black
66 mm
400 mm 35 mm
102 mm
Replace only by trained service people. Danger of explosion if battery is incorrectly replaced! Keep away from open flame. Danger of explosion! Charge and discharge only in horizontal position. Stored batteries have to be charged at least every 6 months (25 °C), 18 weeks (45 °C) or 4 weeks (65 °C), respectively. Service life depends on ambient temperature, depth of discharge and charging characteristics.
Bicker Elektronik GmbH | 86609 Donauwörth | Germany Tel. +49 906 70595-0 |
[email protected] | www.bicker.de
DC UPS
Specification is subject to change without notice. Errors excepted. Status as at: 26.11.2015
The Back up time depends on battery capacitance, load and temperature.