Preview only show first 10 pages with watermark. For full document please download

C Technical Data

   EMBED


Share

Transcript

COMPACT C Model Inverter Nominal battery voltage Input voltage range Continuous power @ 25°C Power 30 min. @ 25°C Power 5 sec. @ 25°C Maximum power Asymmetric load Stand-by adjustment Cos j Maximum efficiency Consumption OFF/Stand-by/ON Output voltage Output frequency Total harmonic distortion Overload and short-circuit protection Overheat protection Battery charger (4 STEP) I-U-Uo-Equalize (every 25 cycles) Charging current adjustable Input current balance adjustment Maximum input voltage Input AC voltage range Input frequency Power Factor Correction (PFC) Battery control (thresholds and times adjustable by the user) Absorption time End charge cycle voltage* Floating voltage* Equalization time* Equalization voltage* Deep-discharge protection* Temparature compensation (optional CT-35) General data Multifunction contact programmable Max. current on transfer relay Transfer time Weight Dimensions h/w/l [mm] Protection index Certification ECE-R 10 (E24) EC conformity Operating temperature range Relative humidity in operation Ventilation Accoustic level Warranty ISO Certification Option solar charger (4 stages) Maximum PV open circuit voltage (V) Maximum charge current (A) Charging curve Accessories RCC-01 Remote control CT-35 Temperature sensor ARM-01 Auxiliary relay module CFC-01 Cover C-IP22 Cover * Factory settings Data may change without any notice C 1600-12 C 2600-24 C 4000-48 12 Vdc 9.5 - 16 Vdc 1300 VA 1600 VA 24 Vdc 19 - 32 Vdc 2300 VA 2600 VA 3 x Pnom Up to short-circuit Up to Pcont. 1 to 25W 48 Vdc 38 - 64 Vdc 3500 VA 4000 VA 0.1 - 1 94 % 0.5 / 0.6 / 6 W 95 % 0.8 / 0.9 / 9 W 1.2 / 1.4 / 12 W Sine wave 230 Vac (± 5 %) (XPC also available in 120 Vac) 50 Hz ± 0.05 % (crystal controlled) <2% Automatic disconnection with 3 time restart attempt Acoustic warning before shut-off - with automatic restart 0 - 55 Adc 0 - 50 Adc 1 - 16 A 265 Vac Adjustable threshold from 150 to 230 Vac (XPC also available in 120 Vac) 45 - 65 Hz EN 61000-3-2 14.4 Vdc 13.6 Vdc 15.6 Vdc 10.8 Vdc 16 kg 0-4h 28.8 Vdc 27.2 Vdc 0-4h 31.2 Vdc 21.6 Vdc -3mV / ° C / Cell 16 A - 250 Vac (potential free 3 points) 16 Aac < 40 ms 17.1 kg 124 / 215 / 480 IP20 (IP22 with top cover C-IP22) 57.6 Vdc 54.4 Vdc 62.4 Vdc 43.2 Vdc 29.4 kg 124 / 215 / 670 l l Not available EN 61000-6-1, EN 61000-6-3, EN 55014, EN 55022, EN 61000-3-2, EN 50091-2 Low voltage directive 2006/95/EC: EN 62040-1-1, EN 60950-1 -20°C to +55°C 95 % without condensation From 45°C <40 dB / <45 dB (without/with ventilation) 5 years 9001:2008 / 14001:2004 25 Vdc 30 Adc 45 Vdc 30 Adc I-U-Uo-Equalize (every 25 cycles) l l l l l 90 Vdc 20 Adc