Transcript
1
2
3
4
5
6
A
7
8
A
4A PI4A018
GPS Ant UHF Ant 3G/GSM Ant 900MHz Ant
PI4A017
PI000
Fuse
Note 1
Solenoid valve
CO4A 4A PI4A018
CO0
PI4A017
PI000
Fuse
+ -
26 25 24 23 22 21 20 19 18 17 16 15 14
PI0 26 PI0 25 PI0 24 PI0 23 PI0 2 PI0 21 PI0 20 PI0 19 PI0 18 PI0 17 PI0 16 PI0 15 PI0 14
+ -
Solenoid valve RL4 NO RL4 C RL3 NO RL3 C RL2 NC RL2 C RL2 NO RL1 NC RL1 C RL1 NO RL0 NC RL0 C RL0 NO
Note 6
Note 2
ADAM - 4069
B
B
TYPE SIGNAL RELAY 0,1,2,7 FORM C RELAY 3,4,5,6 FORM A CONTACT: 5A
Note 3 CONote 15 Note
DATA+ DATA +Vs GND
RL5 NO RL5 C RL6 NO RL6 C RL7 NO RL7 C RL7 NC
PI004
PINote 10Orange PINote 10Grey
PI003 PI002 PI001
24VAC Gnd
CONote 3 240VAC(L) 240VAC(N)
240VAC/24VAC power supply
PI0 1 PI0 2 PI0 3 PI0 4 PI0 5 PI0 6 PI0 7 PI0 8 PI0 9 PI0 10 PI0 1 PI0 12 PI0 13
240VAC(L) 240VAC(N) Earth
Mains supply
240VAC breaker
1 2 3 4 5 6 7 8 9 10 11 12 13
C3 Module
240VAC(L) 240VAC(N) Gnd
GND
Note 4 CONote 25 Note
4A
C
PINote 30Orange
PI4A018
Fuse
PI4A017
PINote 20Orange PINote 20Grey
12VDC Gnd
C 240VAC(L) 240VAC(N)
240VAC/12V power supply
Note 2
Notes
D
1: Up to 8 solenoids can be controlled from a single ADAM-4069 2: Multiple ADAM-4069s can be connected on the Modbus RS485 bus, allowing control of dozens of solenoids 3: Solenoid power supply voltage must match solenoid rating (eg. 12VDC, 24VDC, 24VAC), and be capable of supplying current for number of solenoids expected to be on at one time 4: The ADAM-4069 and C3 require a DC power supply in the range of 10-30V 5: If DC solenoids are used they can share a single 12 or 24VDC power supply of appropriate rating with the ADAM-4069 and C3 6: Manual backup/over-ride can be implemented with hand operated valves in series and parallel with each solenoid valve
D
OBS-USR-D005 - C3 ADAM solenoids.SchDoc
Example wiring 1
2
3
4
5
6
7
Date
14-May-13
Size
A4
Drawn by
AJKahl
Sheet
1
t: 1300 224 688
of
w: observant.com.au
1
©2013 Observant pty ltd
8