Preview only show first 10 pages with watermark. For full document please download

Cable And Termination Summary Horizontal Horizontal 4

   EMBED


Share

Transcript

CABLE AND TERMINATION SUMMARY (THIS PROJECT) DESCRIPTION 4 PAIR UTP CATEGORY 6A 4 PAIR UTP CATEGORY 6A 4 PAIR UTP CATEGORY 6A 4 PAIR UTP CATEGORY 6A 4 PAIR UTP CATEGORY 5e 4 PAIR UTP CATEGORY 5e MULTI-PAIR UTP CAT 3 SINGLEMODE ARMORED MULTIMODE ARMORED RG-6 VIDEO COAX (RF) RG-11 VIDEO COAX (RF) USE HORIZONTAL VOICE HORIZONTAL DATA VIDEO CONFERENCE NON-NKU NETWORK SERVICE SOUND MASKING SYSTEM SOUND MASKING SPEAKERS COPPER BACKBONE FIBER OPTIC BACKBONE FIBER OPTIC BACKBONE HORIZONTAL RF RF BACKBONE COLOR WHITE BLUE ----YELLOW GRAY TERMINATION 1 HORIZONTAL PANEL HORIZONTAL PANEL HORIZONTAL PANEL HORIZONTAL PANEL HORIZONTAL PANEL SEE DETAILS SEE DETAILS YELLOW SC CONN IN PANEL SEE SPEC SC CONN IN PANEL BACKBOARD (SEE DTL) BACKBOARD (SEE DTL) TERMINATION 2 WHITE JACK BLUE JACK ORANGE JACK BLACK JACK YELLOW JACK SEE DETAILS SEE DETAILS SC CONN IN PANEL SC CONN IN PANEL F STYLE ON DEVICE BACKBOARD (SEE DTL) SPEC. TYPE TYPE UTP 1 TYPE UTP 1 TYPE UTP 1 TYPE UTP 1 TYPE UTP 1 TYPE UTP 1 TYPE UTP 2 TYPE FO 1 TYPE FO 2 TYPE CX1 TYPE CX2 NAME 4 PAIR UTP CAT 6A 4 PAIR UTP CAT 6A 4 PAIR UTP CAT 6A 4 PAIR UTP CAT 6A 4 PAIR UTP CAT 5e 4 PAIR UTP CAT 5e MULTI-PAIR UTP SM FIBER OPTIC MM FIBER OPTIC RG-6 RG-11 EACH ER/TR CABLE DESTINATION SHALL INDICATE THE ER /TR NUMBER AND THE RACK/CABINET NUMBER AS INDICATED ON THE DETAIL DRAWINGS 1 25 26 50 51 75 76 100 BLDG ENTR CABLE AND TERMINATION SUMMARY TRx-02 Scale = NONE TRx-02 x13 x19 1.75" WIRE MANAGEMENT A1 B TR2-01 SPACE A ER1--05 SPACE TERMINATE PAIRS 1-X ON EACH ROW UTILIZING INDUSTRY STANDARD POSITIVE IDENTIFICATION COLOR CODING 1 25 26 50 51 75 76 100 COMPLY WITH THE CURRENT OWNER’S STANDARDS DOCUMENTS FOR FINAL CABLE TYPES, TERMINATION TYPES, AND IDENTIFICATION SCHEMA. x3 x9 x4 x10 x5 x11 x6 x12 x14 x20 x15 x21 x16 x22 x17 x23 x18 x24 TERMINATE HORIZONTAL 4 PAIR UTP CABLES TO EIA/TIA T568a WIRING SPECIFICATION ON BOTH ENDS . MULTI-PAIR CATEGORY-RATED UTP CABLE. SEE DETAIL DRAWINGS FOR QUANTITIES . SEE SPECIFICATIONS FOR CATEGORY -RATING. LABEL EACH 4 PORT CONNECTING BLOCK WITH THE ALPHA PANEL DESIGNATOR AND THE PORT NUMBER AB – VOICE BACKBONE B BLANK PANEL (1RU) MOUNTED IN RACK/CABINET OR ON TELECOMMUNICATIONS BACKBOARD (AS SHOWN ON DETAIL DRAWINGS) 3.5" WIRE MANAGEMENT PROVIDE 100-PAIR FOR EACH 24 PORTS IN RACK/CABINET; PUNCH ALL 25 PAIR ACROSS EACH ROW; UTILIZE 4-PAIR CONNECTING BLOCKS CORRESPONDING TO PORT NUMBERS ON PATCH PANELS. TH SPARE THE 25 PAIR. 48p HORIZONTAL DATA PATCH PANEL 3.5" WIRE MANAGEMENT A (24p or 48p Panel) TYPICAL OF ER CROSS-CONNECT FIELD 24p VOICE BACKBONE PANEL 1 A2 SD MULTI-PAIR CATEGORY -RATED UTP CABLE. SEE DETAIL DRAWINGS FOR QUANTITIES . SEE SPECIFICATIONS FOR CATEGORY -RATING. SD x2 x8 UTILIZE ON EACH 2" OR 4" CONDUIT/SLEEVE WHERE CABLE DROPS 2" OR GREATER MOUNT ON TELECOMMUNICATIONS BACKBOARD (AS SHOWN ON DETAIL DRAWINGS ) BLOCK TO BLOCK CABLES SHALL BE TERMINATED WITH 5-PAIR CONNECTING BLOCKS AND SHALL BE LABELED WITH PAIR NUMBERS x1 x7 TRx-01 PAIRS 1-50 51-100 TYPICAL OF BUILDING ENTRANCE POINT (LOCATED AT COMMUNICATIONS UTILITY ENTRANCE) UTILIZE THE CABLE DESTINATION CHART (SAMPLE SHOWN) AS WELL AS THE BACKBONE DIAGRAM FOR INFORMATION ABOUT CABLES, QUANTITIES AND DESTINATIONS LABEL EACH CABLE DESTINATION NOTE 1: UNLESS OTHERWISE SPECIFICALLY NOTED, ALL CABLES USED ABOVE CEILING LINE SHALL HAVE A PLENUM RATING EACH 3.5" (2RU) SHALL BE GIVEN A LETTER DESIGNATION FROM A-x; WHEN TWO SEPARATE PANELS SHARE A POSITION THE SUFFIX OF 1/2 SHALL BE ADDED 7 12 1 3 1 81 9 Scale = NONE 24 TYPICAL OF EACH ER /TR MOUNTED IN HORIZONTAL CROSS-CONNECT RACK/ CABINET(S) (AS SHOWN ON DETAIL DRAWINGS ) 50 PAIR FOR EACH 24 PORTS; 2 PAIR PER PORT SPARE 25 TH PAIR IN EACH BUNDLE TERMINATE PAIRS 1-X ON EACH ROW UTILIZING INDUSTRY STANDARD POSITIVE IDENTIFICATION COLOR CODING E 6 CONDUIT SPILLWAY "WATERFALL" WATERFALL " TERMINATE TO EIA /TIA T 568a WIRING SPECIFICATION TOP HOOK SHALL CONTAIN BACKBONE CABLES UTILIZE SEPARATE HOOKS FOR VOICE/DATA/VIDEO, FIRE ALARM, AND SOUND SYSTEMS COPPER BACKBONE TERMINATION AND IDENTIFICATION LABELING CLEAR SPACE RESERVED FOR TELECOMMUNICATIONS CABLING 6" Scale = NONE C 48p HORIZONTAL DATA PATCH PANEL 3.5" WIRE MANAGEMENT D 48p HORIZONTAL DATA PATCH PANEL EACH PANEL SPACE SHALL BE CONSECUTIVELY LETTERED FROM TOP TO BOTTOM IN THE ORDER OF THE RACK/ CABINET DESIGNATIONS. (LEFT TO RIGHT TOP TO BOTTOM OR RIGHT TO LEFT TOP TO BOTTOM ) EACH CABLE SHALL BE LABELED ON EACH END WITHIN 4 INCHES TO 6 INCHES OF THE TERMINATION (TYPICAL) CABLE(S) SHALL HAVE A 25-FOOT SERVICE LOOP SUPPORTED BY A J HOOK DEVICE. LABEL EACH CABLE WITH A WRAP-AROUND TYPEWRITTEN LABEL 4 INCHES TO 6 INCHES FROM THE TERMINATION . WAP L COMPLY WITH THE CURRENT OWNER’S STANDARDS DOCUMENTS FOR FINAL CABLE TYPES, TERMINATION TYPES, AND IDENTIFICATION SCHEMA. TRx-153-L6-WAP 48p ‘SPECIAL USE’ PATCH PANEL SAMPLE CABLE LABEL FOR ROOM 153 TO TR -x TERMINATED ON PANEL L PORT 6 COORDINATE PATHWAY PLACEMENT WITH ALL TRADES (TYPICAL) EACH CABLE SHALL BE LABELED ON EACH END WITHIN 4 INCHES TO 6 INCHES OF THE TERMINATION (TYPICAL) BLANK PANEL (2RU) 153 G 1 153 PROVIDE ONE 4" J-HOOK PER 50 HORIZONTAL CABLES PLUS ONE SPARE; FILL TOP HOOKS AND WORK DOWN WITH HORIZONTAL CABLES, SPARE HOOK SHALL BE LOCATED AT BOTTOM ACCESSIBLE CEILING LINE 153 PORT IDENTIFIER SHALL INDICATE ROOM NUMBER OF THE FAR END TERMINATION (TYPICAL) 3.5" WIRE MANAGEMENT E CABLE(S) SHALL BE SUPPORTED ABOVE ACCESSIBLE CEILING FOR FUTURE CONNECTION SHALL BE TERMINATED WITH DISCRETE CONNECTORS. 2'-0" (MIN) FIELD VERIFY D B SWITCH SWITCH 8" MIN. CABLE 1 2 3 4 5 6 7 8 9 10 11 COMPLY WITH THE CURRENT OWNER’S STANDARDS DOCUMENTS FOR FINAL CABLE TYPES, TERMINATION TYPES, AND IDENTIFICATION SCHEMA. PAIRS A 1-50 INCOMING 51-100 SPACE 153 6 7 18 19 FACEPLATE IDENTIFIER SHALL INDICATE SOURCE AND DESTINATION IDENTIFIER (TYPICAL) 24 48p HORIZONTAL DATA PATCH PANEL SD TRx-168-H6 TRx-153 3.5" WIRE MANAGEMENT SAMPLE PANELS FROM “TR -x” (EXAMPLE OF REQUIRED LABELING) G4 G5 PORT IDENTIFIER SHALL INDICATE PANEL AND PORT OF THE FAR END TERMINATION (TYPICAL) H7 F LAN SWITCH W 168 3.5" WIRE MANAGEMENT H G 1 6 168 7 18 19 TRx-168-H6 24 48p HORIZONTAL VOICE PATCH PANEL SAMPLE CABLE LABEL FOR ROOM 168 TO TR -x TERMINATED ON PANEL H PORT 6 LAN SWITCH 3.5" WIRE MANAGEMENT LAN SWITCH 3.5" WIRE MANAGEMENT TERMINATE HORIZONTAL 4 PAIR UTP CABLES TO EIA /TIA T568a WIRING SPECIFICATION ON BOTH ENDS . LETTERING SHALL CONTINUE FOR EACH “GANGED RACK OR CABINET; AA, AB, ETC. SHALL FOLLOW Z . F TYPICAL HALLWAY CABLING PATHWAY (NO CABLE TRAY) TRAY) Scale = NONE 3 SAMPLE PANELS FROM “TR -x” (EXAMPLE OF REQUIRED LABELING) H B TRx-153-G4 TRx-153-G5 TRx-153-H7 SAMPLE CABLE LABEL(S) FOR ROOM 153 TO TR -x TERMINATED ON PANEL G PORTS 4-5 AND PANEL H PORT 7 PR 3 FIBER OPTIC CABLE DESTINATION Panel 1 - Position Fibers MOUNTED ON TELECOMMUNICATIONS BACKBOARD (AS SHOWN ON DETAIL DRAWINGS) SD BLANK PANEL (1RU) 3.5" WIRE MANAGEMENT K1 BLANK PANEL (1RU) K2 BLANK PANEL (1RU) Conn Type C Destination 1 6 SC SM ENTRANCE FACILITY 2 - - - SPACE 3 - - - SPACE 4 - - - SPACE 5 12 SC MM TR2-01 6 12 SC MM TR2-01 COMPLY WITH THE CURRENT OWNER’S STANDARDS DOCUMENTS FOR FINAL CABLE TYPES, TERMINATION TYPES, AND IDENTIFICATION SCHEMA. PR 4 T R T RT RT R T RT RT RT R 12 34567 8 123 45678 T568A T568B 1 1 2 2 3 3 4 4 LEAD TIP RING TIP RING TIP RING TIP RING COLOR T568A PIN # T568B PIN # WHITE-BLUE 5 5 BLUE-WHITE 4 4 WHITE-ORANGE 3 1 ORANGE-WHITE 6 2 WHITE-GREEN 1 3 GREEN-WHITE 2 6 WHITE-BROWN 7 7 BROWN-WHITE 8 8 3.5" WIRE MANAGEMENT 1.75" WIRE MANAGEMENT FLIP DOWN PANEL OR PULL OUT CARD SHALL INDICATE DESTINATION, FIBER SIZE, AND STRAND NUMBER Fiber Optic Panel BLDG ENT SM 8.3 1 2 3 5 4 6 SD SD SD SD TR-x MM 50 TR-x SM 8.3 1 3 11 2 4 12 1 3 5 2 4 6 TR-y MM 50 TR-y SM 8. 3 SD SD SD SD 1 3 11 2 4 12 1 2 3 5 4 6 TYPICAL OF ER FIBER OPTIC PANELS ; QUANTITY, SIZE, AND POSITIONING AS SHOWN ON DETAIL DRAWINGS MOUNTED IN RACK / CABINET (AS SHOWN ON DETAIL DRAWINGS ) ER-x SM 8.3 COMBINATION OF RACKS AND CABINETS SHOWN AS EXAMPLE ONLY ER-x MM 50 1 2 3 4 B. THESE DETAILS ARE NOT INTENDED TO SHOW EXACT PROJECT REQUIREMENTS FOR RACK /CABINET LAYOUTS, FACEPLATE CONFIGURATION, EXACT CABLE TYPES, CABLE DESTINATIONS OR CABLE QUANTITIES. THESE DETAILS DIAGRAMMATICALLY INDICATE PROJECT REQUIREMENTS FOR LABELING, COLOR-CODING, AND TERMINATIONS FOR THE PROJECT. USE THESE DETAILS AS A GUIDE; SUBMIT ANY QUESTIONS IN WRITING PER THE SPECIFICATIONS . REFERENCE THE OWNER’S CURRENT STANDARDS DOCUMENTS FOR ADDITIONAL INFORMATION AND REQUIREMENTS . C. LABEL PATCH PANELS AS TO USE AND WITH UNIQUE IDENTIFIER AS SHOWN IN THE DIAGRAM . D. COORDINATE FINAL (POST-CONSTRUCTION) ROOM NUMBERS OR IDENTIFIERS WITH OWNER PRIOR TO PERFORMING WORK; ALL LABELING SHALL CONFORM TO OPERATIONAL ROOM IDENTIFIERS FOR BUILDING USE. IF ACTUAL ROOM NUMBER AND ARCHITECTURAL ROOM NUMBERS ARE DIFFERENT , BOTH SHALL BE INCLUDED ON AS-BUILT FLOOR PLANS. E. CABLES SHALL BE TERMINATED IN ALPHA NUMERICAL ORDER ON EACH PATCH PANEL OR TERMINATION DEVICE . F. LABEL FACEPLATES WITH AN OUTLET IDENTIFIER AND LABEL EACH PORT; FOLLOW THE EXAMPLES IN THE DIAGRAM AS A GUIDE. COMPLY WITH THE OWNER’S CURRENT STANDARDS DOCUMENTS FOR ADDITIONAL INFORMATION AND REQUIREMENTS. G. LABEL CROSS-CONNECT FIELDS, BACKBOARDS, RACKS/CABINETS PANELS, FACEPLATES AND CABLES UTILIZING THE EXAMPLES IN THE DIAGRAM AS A GUIDE. COMPLY WITH THE OWNER’S CURRENT STANDARDS DOCUMENTS FOR ADDITIONAL INFORMATION AND REQUIREMENTS. H. FIBER OPTIC PANELS SHALL BE IDENTIFIED WITH SOURCE, DESTINATION, STRAND IDENTIFIER AS WELL AS WITH THE CORE DIAMETERS. I. CABLES USED FOR DATA SHALL BE TERMINATED ON"HORIZONTAL" DATA PATCH PANELS IN THE ER/TR. CABLES USED FOR VOICE (TELEPHONE) SHALL BE TERMINATED ON "HORIZONTAL" VOICE PATCH PANELS IN THE ER/TR. J. DECORA STYLE JACK FRAMES SHALL MATCH THE COLOR OF THE ELECTRICAL DEVICES. K. SEE CABLE AND TERMINATION SUMMARY CHART FOR COLOR CODING OF JACKS AND CABLES ON THIS PROJECT . COMPLY WITH THE OWNER’S CURRENT STANDARDS DOCUMENTS FOR ADDITIONAL INFORMATION AND REQUIREMENTS . SD 11 12 FIBER OPTIC RUNS SHALL RETURN TO THE ER TERMINATE EACH FIBER STRAND USING INDUSTRY STANDARD POSITIVE IDENTIFICATION COLOR CODING ; (BLUE STRAND 1 EACH END, ORANGE STRAND 2, ETC.) FIBERS TO BE TERMINATED WITH FUSION -SPLICED, FACTORY-POLISHED PIGTAILS. SEE SPECIFICATIONS . FIBER OPTIC RUNS WITHIN THE FACILITY SHALL BEGIN HERE AND CONTINUE WITHOUT SPLICES TO THE INDICATED DESTINATION FIBER OPTIC BACKBONE TERMINATION AND IDENTIFICATION LABELING Scale = NONE 2 4 6 SD MOUNTED IN HORIZONTAL CROSS-CONNECT RACK(S) (AS SHOWN ON DETAIL DRAWINGS) FIBERS SHALL BE TERMINATED WITH FUSION -SPLICED, FACTORY-POLISHED PIGTAILS . SEE SPECIFICATIONS. G 1 3 5 SD TYPICAL OF EACH TR OR LOCATION AS INDICATED ON THE DETAIL DRAWINGS TERMINATE EACH FIBER STRAND USING INDUSTRY STANDARD POSITIVE IDENTIFICATION COLOR CODING ; (BLUE STRAND 1 EACH END, ORANGE STRAND 2, ETC.) TYPICAL ER/TR RACK/CABINET LAYOUT CABLES SHALL HAVE A LABEL AFFIXED TO THE JACKET AT EACH END, 4 INCHES TO 6 INCHES FROM THE TERMINATION POINT. THIS LABEL SHALL IDENTIFY THE SOURCE, DESTINATION, AND PORT IDENTIFIER. SEE THE OWNER’S CURRENT STANDARDS DOCUMENTS FOR ADDITIONAL INFORMATION AND REQUIREMENTS . HYBRID CABLES (MULTIMODE AND SINGLEMODE) ARE ACCEPTABLE; SEE SPECIFICATION FOR OPTICAL PROPERTIES FLIP DOWN PANEL OR PULL OUT CARD SHALL INDICATE DESTINATION, FIBER SIZE , AND STRAND NUMBER COUPLER PANELS SHALL BE COLOR CODED PER INDUSTRY STANDARDS (E.G., SINGLEMODE BLUE, MULTIMODE - BEIGE) UPS A. Fiber Optic Panel LABEL INSIDE COVER SHALL INDICATE DESTINATION, FIBER SIZE, AND STRAND NUMBER 48p ‘SPECIAL USE’ PATCH PANEL ER/ ER/TR RAC/ RAC/CABINET IDENTIFICATION LABELING LA B E LIN G N O T E S : (T H IS P R O JE C T ) FIBER OPTIC CABLE SHALL BE INTERLOCKING ARMORED PLENUM RATED CABLE(S). SEE SPECIFICATIONS SD 5 6 HORIZONTAL 4-PAIR COPPER PINPIN-OUTS DETAIL Scale = NONE ER-x SM 8.3 3 4 Scale = NONE PR 1 FIBER OPTIC CABLE (S) (SEE DETAIL DRAWINGS FOR QUANTITIES AND TYPES ) UTILIZE THE CABLE DESTINATION CHART (SAMPLE SHOWN) AS WELL AS THE BACKBONE DIAGRAM FOR INFORMATION ABOUT CABLES , QUANTITIES AND DESTINATIONS. 1 2 H PR 2 BLANK PANEL (1RU) 3.5" WIRE MANAGEMENT L PR 4 HORIZONTAL CABLING TERMINATION AND IDENTIFICATION LABELING TYPICAL OF BUILDING ENTRANCE POINT (LOCATED AT COMMUNICATIONS UTILITY ENTRANCE) J PR 1 PAIR Scale = NONE I PR 3 PR 2