Preview only show first 10 pages with watermark. For full document please download

Calculite® Incandescent Open Downlight C7055

   EMBED


Share

Transcript

Calculite® Incandescent Open Downlight Page 1 of 2 C7055 7 3/8" Aperture A21 / A23 / PS25 C700 Top View Remodel (C700RM) Frame-In Kit 1 13 1/2" 12-1/16" PS25 4 7/8" 11-5/16" A23 2 11 1/2" 12 1/2" 4 10-9/16" A21 5 3" Flush Trim (Molded trim ring removed) 6 1" min.- 2-1/8" max. (Ceiling Runner) 7-3/8"Dia. 3 7-7/8"Flush 7 8-5/8" Overlap 1-1/8" max. Ceiling Thickness Molded Trim Ring Overlap Self-Flange Matte White or polished 9 8 C700 Ceiling Cutout: 8" Dia.; C700RM Ceiling Cutout: 8" Dia. Reflector Trims Frame-In Kit Lamp C7055CLW C7055CLP C7055CL C7055 C700 A21, 150W max.; A23, 200W max.; PS25, 300W max. Specular Clear finish with white flange Specular Clear finish with polished flange Specular Clear finish with molded trim ring (flangeless) Add suffix for other finishes (see options) Remodeler Frame-In Kit Lamp C700RM (for use in existing ceilings with 3/8" min. to 2" max. thickness.) Same as C700 Features Options & Accessories 1. Socket Cup: Die-cast aluminum effectively dissipates heat and assures lamps maintain proper optical alignment to reflector. Snaps onto reflector neck for easy tool-less installation. Tool-less adjustable inside or outside fixture to accommodate three different lamp sizes. Medium base porcelain socket with nickel plated screw shell wired and No 18 SF1 leads to J-Box. 2. Mounting Brackets: Adjust vertically from inside of fixture. Durable 16 ga. steel construction. Use standard 3/4” or 1 1/2” lathing channels, or 1/2” (11/16" O.D.) EMT pipe (by others) or Lightolier accessory mounting bars. 3. Retaining Springs: Precision tooled springs secure reflector to mounting frame for quick tool-less installation. 4. Reflector: 16 ga. Specular Alzak® aluminum, 45˚ visual cutoff to lamp and lamp image. Available with white or polished flange, or with removable white molded trim ring (field paintable). 5. Junction Box: 14 ga. steel, 4" x 3 1/2" x 2" box allows inspection from below. 6. Thermal Protector: Meets NEC and UL requirements. Insulation must be kept 3" away from fixture sides and wiring compartments and must not be placed above fixture in a manner which will entrap heat. 7. Mounting Frame: Die-cast aluminum suitable for dry or plaster ceilings. Provides flangeless trim in plaster ceiling. 8. Multi-Groove Baffle (C7055MG): One piece seamless aluminum. Sharply detailed concentric rings with “sawtooth” profile, optical black finish. Permanently fastened to specular clear reflector. 9. Black Cone (C7055BK): Specular black Alzak® aluminum. Permanently fastened to specular clear reflector. 18" Mounting Bars 27" Mounting Bars T-Bar Anchor Clips Existing Ceiling Clips Sloped Ceiling Adapters Step Down Transformer Chicago Air Plenum 1950 (set of 2) 1951 (set of 2) 1956 (set of 4, for 1950 & 1951 bars) 7998 (set of 2) 7920 (see SCA specification sheet) 7997 (277V PRi, 120V Sec. 300W) LC (add suffix to Frame-In Kit) Electrical C700 UL Listed for through branch circuit wiring with max. of (8) No. 12 AWG 90°C supply conductors. C700RM UL Listed for No. 12 AWG 60° C supply conductors. Labels UL Listed for damp locations, I.B.E.W. Alzak® is a registered trademark of ALCOA. Job Information Type: Job Name: Cat. No.: Lamp(s): Notes: Other Reflector Finish Options Comfort Clear Diffuse CCD Specular Black BK Specular Gold GD Multi-Groove Baffle MG White WH (MG available with molded trim ring only) Specify desired flange W White, P Polished Flange, Flangeless Leave Blank (molded trim ring) Lightolier a Genlyte Thomas Company www.lightolier.com 631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710 We reserve the right to change details of design, materials and finish. © 2002 Genlyte Thomas Group LLC (Lightolier Division) • A0902 Calculite® Incandescent Open Downlight Page 2 of 2 7 3/8" Aperture A21 / A23 / PS25 C7055CL C7055BK Spacing Ratio = 1.3 0 2 1/2 7 1/2 12 1/2 17 1/2 22 1/2 27 1/2 32 1/2 37 1/2 42 1/2 45 47 1/2 52 1/2 55 57 1/2 500 60 1000 1500 2000 Spacing Ratio = 1.3 Candlepower Summary CP ZONAL FLUX DEG 90 30 2459 2438 2290 2184 2141 2194 2247 2019 986 313 0 58 164 259 353 460 569 595 329 116 42 11 17 5 2 1 DEG Efficiency: 76.2% ZONE LUMENS LAMP 0-30 0-40 0-60 0-90 90-180 0-180 1863 2787 2926 2926 0 2926 48.5 72.6 76.2 76.2 0 76.2 FIXT ITL, Inc. Report No. 18423 Date: 10-2-74 63.7 95.2 100.0 100.0 0 100.0 Efficiency: 64.4% Coefficients of Utilization % Effective Ceiling Cavity Reflectance 80 70 50 30 10 0 80 10 .82 .75 .69 .65 .60 .56 .52 .49 .45 .41 50 .84 .79 .74 .70 .66 .62 .59 .55 .52 .48 30 .82 .76 .71 .67 .62 .59 .55 .51 .48 .44 10 .81 .74 .69 .64 .59 .56 .52 .49 .45 .41 50 .81 .76 .72 .68 .65 .62 .58 .55 .51 .48 30 .79 .74 .70 .66 .62 .59 .54 .51 .47 .44 10 .78 .73 .69 .63 .59 .55 .52 .49 .44 .41 50 .78 .74 .71 .67 .63 .60 .57 .54 .51 .47 ZONE LUMENS LAMP 0-30 0-40 0-60 0-90 90-180 0-180 1801 2436 2554 2583 0 2583 44.9 60.7 63.7 64.4 0 64.4 FIXT 69.7 94.3 98.8 100.0 0 100.0 70 50 30 10 0 % Wall Reflectance 30 .76 .73 .68 .65 .61 .58 .54 .51 .47 .44 10 .76 .71 .67 .63 .59 .55 .51 .48 .44 .41 50 .75 .72 .70 .66 .62 .60 .56 .53 .49 .47 30 .74 .71 .67 .63 .60 .57 .53 .50 .46 .44 10 .74 .70 .65 .62 .58 .55 .51 .48 .44 .41 0 .72 .68 .64 .61 .57 .54 .50 .47 .43 .40 1 2 3 4 5 6 7 8 9 10 Room Cavity Ratio Room Cavity Ratio 30 .84 .77 .71 .67 .62 .59 .55 .52 .48 .44 0 193 636 971 635 99 19 17 9 1 0 Coefficients of Utilization % Effective Ceiling Cavity Reflectance % Wall Reflectance 50 .85 .80 .75 .71 .67 .63 .59 .56 .52 .49 1988 2038 2248 2098 1011 128 21 17 8 1 0 0 5 15 25 35 45 55 65 75 85 90 Zonal Summary ITL, Inc. Report No. 11516 Date: 3-4-69 Candlepower Summary CP ZONAL FLUX Zonal Summary 2500 1 2 3 4 5 6 7 8 9 10 C7055 50 .72 .67 .52 .58 .54 .51 .48 .45 .42 .39 30 .70 .64 .59 .55 .51 .47 .44 .41 .38 .35 10 .69 .62 .57 .52 .48 .45 .42 .38 .35 .32 50 .70 .66 .61 .58 .54 .51 .48 .44 .41 .38 30 .69 .63 .59 .54 .50 .47 .44 .41 .38 .35 10 .68 .61 .56 .52 .48 .45 .41 .38 .35 .32 50 .68 .64 .60 .56 .53 .50 .47 .44 .41 .38 30 .67 .62 .57 .53 .50 .47 .44 .40 .37 .34 10 .66 .60 .55 .51 .47 .44 .41 .38 .35 .32 50 .65 .62 .58 .55 .52 .49 .46 .43 .40 .37 30 .64 .60 .56 .52 .49 .46 .43 .40 .37 .34 10 .64 .59 .55 .51 .47 .44 .41 .38 .35 .32 50 .63 .60 .57 .54 .51 .48 .45 .42 .40 .37 30 .62 .59 .55 .52 .48 .46 .43 .40 .37 .34 10 .62 .58 .54 .50 .46 .44 .41 .38 .35 .32 0 .61 .57 .53 .49 .46 .43 .40 .37 .34 .31 20% Floor Cavity Reflectance 20% Floor Cavity Reflectance Conversion Factor: For 150W A21 and 300W PS25 with clear reflector, multiply C.U.’s by 1.0. For 150W A21, 200W A23, and 300W PS25 with gold reflector, multiply C.U.’s by 0.9. Conversion Factor: For 150W A21 and 300W PS25 with Black Alzak reflector, multiply C.U.’s by 1.0. For 150W A21, 200W A23, and 300W PS25 with Multi-Groove, multiply C.U.’s by 0.9. Job Information Type: Lightolier a Genlyte Thomas Company www.lightolier.com 631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710 We reserve the right to change details of design, materials and finish. © 2002 Genlyte Thomas Group LLC (Lightolier Division) • A0902