GCN-MEP Gas-Actuated Concrete Nailer The new GCN-MEP gas-actuated concrete nailer is the ideal solution for attaching light-duty fixtures to concrete and metal deck for mechanical, electrical and plumbing (MEP) applications. Since the tool does not require electrical cords or pneumatic hoses, the gas-actuated GCN-MEP is completely portable, increasing productivity.
NEW
FEATURES Easy magazine attachment with no extra tools Power to drive .125" diameter pins Pin-depth control dial Easy nose piece change-out (for .25" and .300" headed fasteners) with no extra tools • High-voltage spark for cleaner fuel combustion • Comfortable, “sure-grip” rubber handle • Battery charge indicator light • Ladder hook SPECIFICATIONS • Tool dimensions: • Length – 15.3" (439mm), 17.3" with magazine • Width – 4.2" (107mm) • Height – 15.3" (389mm) • Tool weight: 8.3 lbs (3.7kg) • Suitable Fasteners: • Length – 1⁄2" (12.7mm) to 1 1⁄2" (38mm), • Diameter – For .25" and .300" headed pins • Magazine capacity: 40 + 2 pins* • Average number of shots per fuel cell: 1,200 • Average number of shots per battery charge: 3,300 • 6V NiMH batteries • Average battery charge time: 2 hours • Operates at temperatures between 20°F–120°F (-6°C– 49°C) • 2 shots per second *To ensure the tool does not discharge without pins in the magazine, all but the last two pins will be used before reloading is necessary. KEY FASTENING APPLICATIONS: • • • • •
Conduit clips Ceiling clips Low-voltage cable Cable straps Drywall track to concrete, steel, CMU or lightweight concrete on metal deck with magazine
Magazine sold separately (MEP-MAG1KT)
Gas and Powder-Actuated Fastening Systems
C-SAS-2012 © 2012 Simpson Strong-Tie Company Inc.
• • • •
The GCN-MEP Gas-Actuated Concrete Nailer Kit includes: • • • • • • •
GCN-MEP nailer or GCN-MEPMAG 2 batteries Battery charger Allen wrenches Safety glasses and ear plugs Operator’s manual/tool schematic Rugged tool box
Replacement Parts Model
Description
GCN-APP012 GCN-CHG007 GCN-PPA020
Adaptor Charger (U.S.) Battery (U.S.)
GCN-MEPKT or GCN-MEPMAGKT (with magazine)
179
Simpson Strong-Tie ® Anchoring and Fastening Systems for Concrete and Masonry
GCN-MEP Fasteners and Accessories GCN-MEP Gas-Actuated Pins and Assemblies for Mechanical, Electrical and Plumbing (MEP) Applications New, pre-assembled MEP fasteners are available for use with the GCN-MEP gas-actuated concrete nailer designed for high-volume applications such as affixing conduit clips, rod hangers, cable ties and drywall track. With their .300" heads, these versatile pins and assemblies can also be used with common powderactuated tools when fastening into harder substrates (structural steel or extra hard concrete) when required. Codes: ICC-ES ESR-2811 Mechanical, Electrical and Plumbing Pins
GCC
Model No. GRH25-R100 GRH37-R100
Description ⁄4" Rod Hanger w/ .125" Dia. x 1" Length Pin 3 ⁄8" rod hanger w/ .125" Dia. Shank x 1" Length Pin
Pack Qty. 100 100
Compatible Gas-Actuated Nailer GCN-MEP, T3 GCN-MEP, T3
Model No. GCC50-R100 GCC75-R100 GCC100-R100
Description 1 ⁄2" Conduit Clip w/ .125" Dia. x 1" Length Pin 3 ⁄4" Conduit Clip w/ .125" Dia. x 1" Length Pin 1" Conduit Clip w/ .125" Dia. x 1" Length Pin 1" Conduit Clip (13 Gauge Steel) w/ .125" Dia. x 1" Length Pin
Pack Qty. 100 100 100
Compatible Gas-Actuated Nailer GCN-MEP, T3 GCN-MEP, T3 GCN-MEP, T3
50
GCN-MEP, T3
Description ⁄2" Conduit Clamp w/ .125" Dia. x 1" Length Pin 3 ⁄4" Conduit Clamp w/ .125" Dia. x 1" Length Pin
Pack Qty. 50 25
Compatible Gas-Actuated Nailer GCN-MEP, T3 GCN-MEP, T3
Model No. GAC-R100
Description Angle Clip w/ .125" Dia. x 1" Length Pin
Pack Qty. 100
Compatible Gas-Actuated Nailer GCN-MEP, T3
Model No. GCT-R50
Description Tie Strap Holder w/ .125" Dia x 1" Length Pin
Pack Qty. 50
Compatible Gas-Actuated Nailer GCN-MEP, T3
Model No.
Description ⁄2" Dome Washer w/ .111"/ .125" Dia. x 1⁄2" Length Pin (Step Shank Pin) 1 ⁄2" Dome Washer w/ .125" Dia. x 3⁄4" Length Pin
Pack Qty.
Compatible Gas-Actuated Nailer
200
GCN-MEP, T3
200
GCN-MEP, T3
⁄2" Dome Washer w/ .125" Dia. x 1" Length Pin
200
GCN-MEP, T3
Description ⁄4-20 thread, 1⁄2" length thread, 3⁄4" length shank (.125" dia shank)
Pack Qty.
Compatible Gas-Actuated Nailer
200
GCN-MEP, T3
Model No.
Description
Pack Qty.
Compatible Gas-Actuated Nailer
GBR2-R25
2" Dia. Ring, w/ .125" Dia. x 1" Length Pin
25
GCN-MEP, T3
Model No.
Description
Pack Qty.
Compatible Gas-Actuated Nailer
GTH-R200
.125" Dia. x 1" Length Pin
200
GCN-MEP, T3
GCC125-R50
Gas and Powder-Actuated Fastening Systems
Model No. GCL50-R50 GCL75-R25
GW50-R200 GW75-R200 GW100-R200
1
1
1
Model No. GTS-45075-R200
1
GCL
GAC
GCT
GW
GTS
GBR
GTH
GDP Strip Pins (with GCN-MEP MAGKT and 1 fuel cell)
180
NEW
Model No.
Description
Qty. Pins/Pack Compatible Gas-Actuated Nailer + 1 Fuel Cell 1,000 GCN150, GCN-MEP, TF1100, C3
GDP-50KT
.106" dia. x ½" pin
GDP-562KT
.106" dia. x 5⁄8" pin
1,000
GCN150, GCN-MEP, TF1100, C3
GDP-75KT
.106" dia. x ¾" pin
1,000
GCN150, GCN-MEP, TF1100, C3
GDP-100KT
.106" dia. x 1" pin
1,000
GCN150, GCN-MEP, TF1100, C3
GDP-125KT
.106" dia. x 1¼" pin
1,000
GCN150, GCN-MEP, TF1100, C3
GDP-150KT
.106" dia. x 1½" pin
1,000
GCN150, GCN-MEP, TF1100, C3
Model No.
Description
Pack Qty.
Compatible Gas-Actuated Nailer
GDPS-50
1.09"/1.11" dia. x ½" pin
1,000
GCN150, GCN-MEP, TF1100, C3
GDPS-62
1.09"/1.11" dia. x 5⁄8" pin
1,000
GCN150, GCN-MEP, TF1100, C3
GDPS-75
1.09"/1.11" dia. x ¾" pin
1,000
GCN150, GCN-MEP, TF1100, C3
Model No.
Description
Pack Qty.
Compatible Gas-Actuated Nailer
GDPSK-137KT
.110" dia. X 13⁄8" spiral knurled pin
1,000
GCN150, GCN-MEP, F100, C3
GDP
GDPS
GDPSK
C-SAS-2012 © 2012 Simpson Strong-Tie Company Inc.
All single-shot pins are .125" diameter x 1" except where specified. 1
GRH
Simpson Strong-Tie ® Anchoring and Fastening Systems for Concrete and Masonry
GCN-MEP Gas-Actuated Concrete Nailer *
GCN-MEP Fasteners - Tension and Shear Loads in Normal-Weight Concrete
Model No.
GW-75, GW-100, GTH
Shank Minimum Diameter Penetration In. In. (mm) (mm)
0.125 (3.2)
Allowable Tension Load - lbs. (kN) Allowable Shear Load - lbs. (kN) Minimum Spacing f'c ≥ 2,000 psi f'c ≥ 3,000 psi f'c ≥ 4,000 psi f'c ≥ 2,000 psi f'c ≥ 3,000 psi f'c ≥ 4,000 psi In. (13.8 MPa) (20.7 MPa) (27.6 MPa) (13.8 MPa) (20.7 MPa) (27.6 MPa) (mm) Concrete Concrete Concrete Concrete Concrete Concrete
Minimum Edge Distance In. (mm)
5 ⁄8 (15.9)
3 (76.2)
4 (101.6)
60 (0.27)
70 (0.31)
95 (0.42)
55 (0.27)
65 (0.29)
95 (0.42)
3 ⁄4 (19.1)
3 (76.2)
4 (101.6)
85 (0.38)
105 (0.47)
190 (0.85)
120 (0.53)
145 (0.65)
215 (0.96)
1. The fasteners must not be driven until the concrete has reached the designated minimum compressive strength. 2. Minimum concrete thickness must be three times the fastener embedment into the concrete. 3. The allowable tension and shear values are only for the fastener in the concrete. Members connected to the concrete must be investigated in accordance with accepted design criteria.
*
GCN-MEP Fasteners - Tension and Shear Loads in Sand-Lightweight Concrete over Metal Deck Shank Diameter In. (mm)
GW-75, GW-100, GTH
0.125 (3.2)
Minimum Penetration In. (mm)
Minimum Spacing In. (mm)
5 ⁄8 (15.9)
3 (76.2)
3 ⁄4 (19.1)
3 (76.2)
Installed in Concrete
Installed Thru. 3-inch "w" deck
Allow. Tension Load lbs. (kN)
Allow. Shear Load lbs. (kN)
Allow. Tension Load lbs. (kN)
Allow. Shear Load lbs. (kN)
4 (101.6)
60 (0.27)
110 (0.49)
35 (0.16)
215 (0.96)
4 (101.6)
115 (0.51)
130 (0.58)
55 (0.24)
235 (1.05)
*See page 13 for an explanation of the load table icons
1. The fasteners must not be driven through the steel deck and into the light3. The steel deck must have a minimum thickness of 20 gauge and a minimum weight concrete until the lightweight concrete has reached the designated yield strength of 38 ksi. minimum compressive strength. 4. The fasteners must be installed through the steel deck and into the concrete 2. The allowable tension and shear values are only for the fasteners driven at the lower flute. The fastener must be a minimum of 11⁄8" from the edge of the lower flute and 3 inches from the end of the deck. through the steel deck and into the lightweight concrete. Members connected by the fastener, driven through the steel deck and into the lightweight concrete, must be investigated in accordance with accepted design criteria.
*
C-SAS-2012 © 2012 Simpson Strong-Tie Company Inc.
GCN-MEP Fasteners - Tension and Shear Loads in Hollow CMU Installed in CMU Face Shell
Model No.
Shank Diameter In. (mm)
Minimum Penetration In. (mm)
Minimum Edge Distance In. (mm)
Minimum Spacing In. (mm)
Allow. Tension Load – lbs. (kN)
Allow. Shear Load – lbs. (kN)
GW-75, GW-100, GTH
0.125 (3.2)
5 ⁄8 (15.9)
3 (76.2)
8 (203.2)
55 (0.24)
65 (0.29)
GAS ACTUATED FASTENER STEEL THICKNESS
1. The tabulated allowable load values are for the fasteners only. Members connected to the CMU receiving elements shall be designed in accordance with the applicable code and accepted design criteria. 2. The tabulated allowable load values are for fasteners installed in hollow CMUs conforming to ASTM C 90. The minimum allowable nominal size of the CMU must be 8 inches high by 8 inches wide by 16 inches long, with a minimum,1¼"-thick face shell thickness, medium-weight and normal-weight concrete masonry units. 3. The tabulated allowable load values are for fasteners installed in the center of a hollow CMU face shell.
Gas and Powder-Actuated Fastening Systems
Model No.
Minimum Edge Distance In. (mm)
ENTIRE POINTED PORTION OF THE FASTENER MUST PENETRATE THROUGH THE STEEL
Detail A
*
GCN-MEP Fasteners - Tension and Shear Loads in Steel
Steel Thickness - (In.) Minimum 3 1 3 Minimum ⁄ 16 ⁄4 ⁄8 Edge Spacing Distance Allow. Tension Allow. Shear Allow. Tension Allow. Shear Allow. Tension Allow. Shear In. In. Load – lbs. Load – lbs. Load – lbs. Load – lbs. Load – lbs. Load – lbs. (mm) (mm) (kN) (kN) (kN) (kN) (kN) (kN)
Model No.
Shank Diameter In. (mm)
GW-50, GTH-50
0.111/0.125 (2.8/3.2)
⁄2 (12.7)
GW-50, GTH-50
0.111/0.125 (2.8/3.2)
⁄2 (12.7)
ASTM A36 1
1 (25.4)
225 (1.00)
400 (1.78)
275 (1.22)
345 (1.53)
2454 (1.09)
3104 (1.38)
3254 (1.45)4
2804 (1.25)4
3504 (1.56)4
ASTM A572 Grade 50 or A992 1
1 (25.4)
240 (1.07)
1. The entire pointed portion of the fastener must penetrate through the steel to obtain the tabulated values, see Detail A, except as noted in footnote 4. 2. The allowable tension and shear values are for the fastener only. Members connected to the steel must be separately in accordance with accepted design criteria.investigated.
380 (1.69)
2154 (0.96)4
3. Steel must conform to ASTM A36 (Fy = 36 ksi, F4 = 58 ksi), ASTM A572 Grade 50 (Fy = 50 ksi, F4 = 65 ksi), or ASTM A992 (Fy = 50 ksi, F4 = 65 ksi). 4. Tabulated values are based on minimum penetration of the fastener point into steel of 0.25 inch (6.4mm).
181