Preview only show first 10 pages with watermark. For full document please download

Ceilair®

   EMBED


Share

Transcript

CEILAiR ® Engineering Manual Precision Air Conditioning 1 to 10 Tons (60 Hz Data) Ceiling Mounted Full line of DX & CW Systems Air Technology Systems, Inc. Air Technology Systems, Inc. Stulz Air Technology Systems, Inc. SATS is dedicated to providing innovative solutions for critical temperature and humidity control needs. SATS designs and manufactures specialized environmental control equipment for commercial, industrial and custom military applications. SATS serves a diverse marketplace - including telecommunications, information technology, medical, financial, educational, industrial process and government contracts - utilizing world-class “island” manufacturing processes in a modern, 150,000 ft2 facility. The addition of SATS to the STULZ family of companies solidifies STULZ as a global leader in the precision air conditioning marketplace. SATS combines a global network of sales and service companies with an extensive factory engineering staff and highly flexible manufacturing resources dedicated to providing world-class quality, innovation and customer service. CeilAiR ceiling mounted air conditioning units provide temperature and/or humidity control for those hot spot areas in the building which exceed the central system capacity. They are an economical solution to such demands which may, in fact, be temporary until the next offices are carved out of an existing plant area, another laboratory added to a school or new medical equipment installed at a hospital. No floor space is required by the CeilAiR ceiling mounted units. The units are designed with a wide range of options to handle both comfort and precision cooling applications. Typical applications include: Air Technology Systems, Inc COMFORT ISO-9001:2001Quality Registered Stulz-ATS is committed to satisfying customer expectations by meeting and exceeding requirements. Our Quality Policy ensures that every Employee is committed to Customer Satisfaction, Teamwork and utilizing Continuous Process Improvement methods in order to deliver an exceptional product. We will continually measure our performance to improve the effectiveness of our quality management system Precision A/C Applications Stulz-ATS is dedicated to the manufacturing of supplemental and precision air ­conditioning products. With an extensive installation base, SATS has earned a solid ­reputation as a quality supplier and leader in its field. 1-1 Air Technology Systems, Inc. ■ Conference Rooms ■ General Office Spaces ■ Modular Offices CRITICAL / PRECISION ■ Telecommunications Rooms ■ Telephone Switch-Gear Rooms ■ Computer / LAN Rooms ■ Copier / Fax Rooms ■ ATM Bank Centers ■ Elevator Equipment Rooms ■ CAT SCAN / MRI Facilities ■ Hospital Operating & Isolation Rooms ■ Clean Rooms ■ Laboratories PERFECT FOR TENANT RENOVATIONS! Table of Contents Table of Contents SECTION - 5 SECTION - 1 Introduction to Stulz-ATS...................................................... 1-1 Table of Contents................................................................. 1-2 SECTION - 2 ELECTRICAL DATA: (FLA / MCA / MFS) Electrical Data Index............................................................. 5-1 DX - Compressorized Systems: CeilAiR SYSTEMS: Outstanding Advantages...................................................... 2-1 User Oriented Features & Options......................................... 2-2 Available Configurations................................................... 2-3/4 Air Cooled, Self-Contained Systems...................................... 5-2 Air Cooled, Split Systems................................................... 5-2/4 Water Cooled Systems...................................................... 5-2/4 Glycol Cooled Systems...................................................... 5-2/4 MODEL NOMENCLATURE: Nomenclature Chart............................................................. 2-5 Model Nomenclature Specifications...................................... 2-6 SECTION - 3 GUIDE SPECIFICATIONS: Standard Features Index....................................................... 3-1 Standard Guide Specifications........................................... 3-2/4 DX - Air Handling & Remote Condensing Units: DX - Air Handling Units..................................................... 5-5/6 Free-Cooling & Alternate Water Source: DX with Free-Cooling........................................................ 5-7/8 DX with Alternate Water Source........................................ 5-7/8 Chilled Water Air Handling Systems: Optional Features Index........................................................ 3-5 Optional Features Guide Specifications............................ 3-6/14 Chilled Water Systems.......................................................... 5-9 SECTION - 4 SECTION - 6 PERFORMANCE / CAPACITY SPECIFICATIONS: DIMENSIONAL / INSTALLATION DRAWINGS: Performance Data Index....................................................... 4-1 Dimensional Drawing "Quick Find" Index............................. 6-1 DX - Air Cooled Systems.................................................... 4-2/6 Physical Data - Unit Weights (lbs).......................................... 6-2 Connection Sizes - DX Refrigerant........................................ 6-3 DX - Water Cooled Systems............................................... 4-7/8 DX - Glycol Cooled Systems............................................. 4-9/10 Air Cooled Systems........................................................... 6-4/9 Water / Glycol Cooled Systems...................................... 6-10/13 Chilled Water Systems................................................... 6-14/15 Chilled Water Systems................................................... 4-11/16 Free-Cooling & Alternate Water Source Systems............ 4-17/28 Air Technology Systems, Inc. 1-2 CeilAiR Systems CeilAiR ceiling A/C's are designed as the ultimate space saver. They easily mount in a standard 2' x 4' grid of a dropped ceiling plenum and are available with high static blowers (up to 2.0" e.s.p. available) for connection to ceiling plenum ducts. CeilAiR units are especially useful where there is no floor or wall space available for cooling units or where aesthetics demand out-of-sight installation. { CeilAiR Systems Offer Outstanding Advantages Flexibility Microprocessor Controls A wide variety of types are available to meet your unique requirements. Precision temperature and/or humidity control with unrivaled, user-friendly controls, offer a wide range of functions and alarms. • DX - Air Cooled • DX - Water Cooled • DX - Glycol Cooled (w/ Remote Drycoolers & Pump Packages • DX - Air Handling Units • Chilled Water Air Handling Units Air Technology Systems, Inc Versatility • Spot Cooling & Ducted systems • Self-Contained & Split systems A-Tech-1.1/.2 Space Saving Design Complete Temperature & Humidity Control Compact, in-the-ceiling design saves valuable floor space. Wide Size Range 1 to 10 tons capacity in eleven incremental sizes meets any supplemental cooling requirement. C-Tech-10 A-Tech-20 • Steam Canister Humidification (Optional) • Dehumidification Mode (Optional) with - Electric Reheat/Heat - Hot Gas Reheat (Energy $aver) - Hot Water & Steam Reheat/Heat Capacity Modulation Options Non-Proprietary Parts All CeilAiR systems incorporate non-proprietary components where possible. Most major HVAC, refrigeration and electrical distributors stock an exact model cross reference or an alternate to most factory provided components. • Single & Dual Compressor Systems • Hot Gas Bypass Systems • Multistage Reheat/Heat Code Conformance Complies With L LISTED NRT UL 1995 C Listing E112043 R CSA C22.2 No. 236� Heating & Cooling Equipment - NYC MEA Approved (MEA-163-88-E) - Chicago Code Approved - MET-C recognized by Standards Council of Canada 2-1 Air Technology Systems, Inc. User Oriented Features & Options Scroll Compressors Variety of Air Patterns CeilAiR DX air conditioners incorporate Scroll Compressor Technology (unless specified otherwise). Scroll Compressors provide higher efficiency, higher reliability and lower sound power than other compressor technologies. Spot Cooler EVAPORATOR AIR IN Year Round Operation Option offerings available with CeilAiR air conditioners allow for year-round, 24/7 continuous on-line system operation in any environment in the world: EVAPORATOR AIR OUT Ducted Low Ambient Control (DX - Air Cooled) • 0°F Fan Cycling / Fan Speed • -20°F Variable Fan Speed • -30°F Flooded Head Pressure EVAPORATOR AIR IN EVAPORATOR AIR IN Quiet Operation EVAPORATOR AIR OUT Low sound power Scroll compressors coupled with low RPM blowers, acoustically lined cabinets and low velocity grilles provide the optimum in quiet operation. Fast Delivery • Stock units complete and ready for shipment • "Rapid-Fire", 5 day Ship Program Warranty - 2 Year Parts Standard - Optional 5 Year Compressor EVAPORATOR AIR OUT Straight-Thru 90° / Right-Angle Other Available Options - Condensate Pumps - Electrical Service Switches - Firestats - Smoke Detectors - Water Leak Detectors - Special High Efficiency Filtration (2" & 4" Filters up-to 60% Dust Spot) - High Pressure DX - Water/Glycol Cooled Condenser Regulating Valves - Free-Cooling & Alternate Water Source Units - Many more options available (see page 3-5)! Light weight ALL ALUMINUM cabinet and chassis prevents rust & corrosion Selected Standard Features: • Acoustical / Thermal Insulation • Aluminum Fin / Copper Tube Coils • Thermal Expansion Valve • Refrigerant Sight Glass • Filter / Drier Strainer • Liquid Refrigerant Reclaim Valves • Insulated SS or Polymer Drain Pans • Condensate Overflow Safety Switch • High / Low Pressure Switches CeilAiR Ceiling AC Systems (Model OHS-( )-AS Shown) Air Technology Systems, Inc. 2-2 Space Saving Configuration Choices AIR COOLED SYSTEMS SELF-CONTAINED AIR COOLED - with INTEGRAL Air Cooled Condenser OHS-012/040-AS OHS-012/040-AS (Self-Contained, Ducted Evaporator) (Self-Contained, "Ductless" Spot Cooler) SPLIT AIR COOLED - with REMOTE OUTDOOR or INDOOR Air Cooled Condenser (compressor located with Evaporator Section) Please refer to the SATS Heat Rejection Engineering Manual for specification and performance data on SATS Remote Condensers & Condensing Units SATS Remote Outdoor Propeller Condenser SATS Remote Outdoor Propeller Condenser SATS Remote Indoor Centrifugal Condenser { { SATS Remote Indoor Centrifugal Condenser OHS-012/040-HAR & OHS-048/060-AR (Single Compressor - Split Evaporator) (Ducted Only) OHS-012/040-AR SATS Remote Outdoor Propeller Condenser (Split Evaporator, "Ductless" Spot Cooler) Air Technology Systems, Inc SATS Remote Outdoor Propeller Condenser { { SATS Remote Indoor Centrifugal Condenser OHS-040/120-(D)AR OHS-012/032-AR (Dual Compressors - Split Evaporator) (Ducted Only) (Split Evaporator, Ducted Evaporator) SPLIT AIR COOLED - AIR HANDLING UNIT w/ INDOOR or OUTDOOR REMOTE CONDENSING UNIT (compressor located with Condensing Section) SATS Outdoor Propeller Remote Condensing Unit SATS Outdoor Propeller Remote Condensing Unit { { SATS Indoor Centrifugal Remote Condensing Unit SATS Indoor Centrifugal Remote Condensing Unit OHS-012/040-AHU (Split , DX - Air Handling Unit) ("Ductless" Spot Cooler) OHS-048/060-AHU (Split , DX - Air Handling Unit) (Ducted Only) SATS Outdoor Propeller Remote Condensing Unit OHS-048/120-DAHU { SATS Indoor Centrifugal Remote Condensing Unit (Split , DX - Air Handling Unit) (Ducted Evaporator) 2-3 SATS Outdoor Propeller Remote Condensing Unit (Dual Circuit, Split, DX - Air Handling Unit) (Ducted Only) { OHS-012/040-AHU & HAHU SATS Remote Indoor Centrifugal Condenser Air Technology Systems, Inc. SATS Indoor Centrifugal Remote Condensing Unit More Space Saving Configuration Choices WATER COOLED SYSTEMS SELF-CONTAINED WATER COOLED SYSTEMS Remote Water Source (supplied by others) Remote Water Source (supplied by others) OHS-012/040-W OHS-012/032-W (Self-Contained, "Ductless" Spot Cooler) (Self-Contained, Ducted Evaporator) Remote Water Source (supplied by others) OHS-012/040-HW & OHS-048/060-W Remote Water Source (supplied by others) OHS-048/120-DW (Single Compressor, Self-Contained, Ducted Only) (Dual Compressors, Self-Contained, Ducted Only) GLYCOL COOLED SYSTEMS SELF-CONTAINED GLYCOL COOLED SYSTEMS Please refer to the SATS Glycol Systems Engineering Manual for specification and performance data on SATS Glycol Pump Packages and Drycoolers OHS-012/040-HG & OHS-048/060-G with SATS DRYCOOLER & PUMP PACKAGE (Single Compressor, Self-Contained, Ducted Only with Outdoor Propeller Drycooler & Pump Package) OHS-012/040-G with SATS DRYCOOLER & PUMP PACKAGE (Self-Contained, "Ductless" Spot Cooler with Outdoor Propeller Drycooler & Pump Package) OHS-048/120-DG with SATS DRYCOOLER & PUMP PACKAGE OHS-012/040-G with SATS DRYCOOLER & PUMP PACKAGE (Dual Compressors, Self-Contained, Ducted Only with Outdoor Propeller Drycooler & Pump Package) (Self-Contained, Ducted Evaporator with Outdoor Propeller Drycooler & Pump Package) CHILLED WATER SYSTEMS Remote Liquid Chiller (supplied by others) Remote Liquid Chiller (supplied by others) OHS-012/040-C (Self-Contained Air Handler) ("Ductless" Spot Cooler Evaporator) Remote Liquid Chiller (supplied by others) OHS-012/040-C (Self-Contained Air Handler) (Ducted Evaporator) Air Technology Systems, Inc. OHS-048/120-C (Self-Contained Air Handler) (Ducted Only) 2-4 Model Nomenclature - "OHS" Systems Nomenclature CeilAiR® - Ceiling Mounted A/C's OHS-040-G-FC AWS FC LP OA SF SP OHS = OverHead System COS = CyberONE System MCS = Modular Cyber System VFS = Vertical Floor System FCS = Floor Console System SCS = STULZ Condensing Section* GPS = Glycol Pump System* - CeilAiR® Systems AHU AR AS C CAA D( ) G H( ) ( )AA ( )SA ( )AA EC RCU-I RCU-O W Nominal Capacity in 1,000's of BTU/H = = = = = = = = = = = = = = = = = = = = = "Alternate Water Source" "Free-Cooling" "Low Profile Configuration" "Outside Air"* "Same-Face" Air Pattern "Special Configuration" Air Handling Unit Remote (Split) Air Cooled Self-Contained Air Cooled Chilled Water System Indoor Centrifugal Condenser* Dual (Two) Circuit System Glycol Cooled Horizontal Discharge, "H- Series" Configuration (e.g.: HAHU, HAR, HW, HG, & HC) Outdoor Prop Fan Condenser for 0° F* Outdoor Prop Fan Condenser for -20° F* Outdoor Prop Fan Condenser for -30° F* Outdoor Prop Fan Condenser for -20° F* w/ EC Fans Indoor Centrifugal Remote Condensing Unit* Outdoor Remote Condensing Unit* Water Cooled Air Technology Systems, Inc * SATS Condensers & Condensing Units can be found in our "Heat Rejection" engineering manual. * SATS OHS Oustide Air Units can be found in our "CeilAiR® Outide Air" engineering manual. * SATS Pump Packages and Drycoolers can be found in our "Glycol Systems" engineering manual. 2-5 Air Technology Systems, Inc. Model Nomenclature Specifications AIR COOLED SELF-CONTAINED Integral Self-Contained (Models OHS-012/040-AS) The system shall be a self-contained, ceiling mounted supplemental air conditioner with factory mounted integral air cooled condenser with centrifugal blower. The system shall require only single point supply power connection and the system shall ship from the SATS factory with a full operating refrigerant charge. DX - EVAPORATOR SECTIONS Air Cooled Remote Evaporator (Models OHS-( )-()AR) The system shall be a remote (split) air cooled, ceiling mounted supplemental air conditioner evaporator. The evaporator section shall house, as a minimum, the evaporator coil, expansion valve, compressor, evaporator blower/motor and associated electrical and refrigeration components. The OHS-( )-()AR evaporator section shall be located at some distance from its corresponding CeilAiR model HES-( )-()CAA indoor or WCS-( ) outdoor air cooled condenser. (Note: SATS Condensers & Condensing Units can be found in our "Heat Rejection" engineering manual.) DX - WATER COOLED SYSTEMS Integral Self-Contained (Models OHS-( )-W / DW) The system shall be a self-contained, ceiling mounted supplemental air conditioner to include integral water cooled, coaxial condenser with factory installed head pressure water regulating control valve(s). Condenser (source) water shall be provided by a cooling tower or some other remote water source. The system shall require only single point supply power connection and shall ship from the SATS factory with a full operating refrigerant charge. Water Regulating Valves: Head pressure shall be automatically controlled by a factory installed 2-way water regulating valve rated for 150 psig w.w.p. (Note: 3-way and high pressure 300 to 400 psig rated valves are available as options, page 3-9.) DX - GLYCOL COOLED SYSTEMS Integral Self-Contained (Models OHS-( )-G / DG) mental air conditioner to include integral glycol cooled, coaxial condenser with factory installed head pressure glycol regulating control valve(s). Condenser (source) glycol solution shall be provided via a CeilAiR model GPS-( )-( ) / HES-( )-LGA remote glycol pump package and drycooler system. The system shall require only single point supply power connection and shall ship from the SATS factory with a full operating refrigerant charge. Glycol Regulating Valves: Head pressure shall be automatically controlled by a factory installed 2-way glycol regulating valve rated for 150 psig w.w.p. (Note: 3-way and high pressure 300 to 450 psig rated valves are available as options, page 3-9.) CHILLED WATER AIR HANDLERS CHILLED WATER SYSTEM (Models OHS-( )-C) - CeilAiR® Systems The condenser shall be sized to provide the total heat of rejection of the system at a 95°F DB ambient temperature. The evaporator system shall require only single point main power supply connection and the ystem shall ship from the SATS factory with a dry nitrogen holding charge ready for field refrigerant (R-22) charging. Nomenclature "CeilAiR" Model Nomenclature Guide Specifications The system shall be a ceiling mounted chilled water supplemental air conditioner to include chilled water cooling coil, evaporator blower and motor and chilled water control valve. Chilled water shall be provided by a remote liquid chiller system. Chilled Water Control Valve: Cooling capacity shall be controlled with a slowly opening and slowly closing 2-way motorized control valve rated for 300 psig w.w.p. (Note: 3-way 300 psig motorized valves and 2 or 3-way modulating valves are available as options .) The system shall be a self-contained, ceiling mounted supple- Air Technology Systems, Inc. 2-6 Selected Standard Features Guide Spec's "OHS" Model 012/040-( ) "OHS" Series 012/040-H( ) 048/060-( ) 048/120-D( ) Std Opt Std Opt Std Opt Std Opt Opt Opt Opt Opt Opt Opt Opt Opt Std Opt Opt Std Opt Opt Std Opt Opt N/A Std Opt Std Std Std Std Std Std Std Std Std Std Std Std Std Std Std Std Std Opt N/A Std N/A Std N/A Std Std Opt Std Std Std Std Std Std Opt Std Std Std Std Std Std Opt Std Std Std Std Std Std Opt Std Std Std Std Std Std N/A N/A Std N/A Std N/A Std SELECTED STANDARD FEATURES: TEMPERATURE CONTROL • Cooling Only • Heating / Reheating Control HUMIDITY CONTROL • Electrode Canister Steam Humidifier • Dehumidification Mode with Reheat CONTROLS • A-Tech-1.1 single stage controls • A-Tech-1.2 two stage controls • C-Tech-10, A-Tech-20, C6000 T/H Microprocessor Controls CABINET • • • • All Aluminum Construction Insulated SS or Polymer Condensate Drain Pan 1/2", 2 lb Density Thermal & Sound Insulation Rubber Hanging Vibration Isolators - Standard Features "Quick-Reference" Table FILTERS / GRILLES • Spot Coolers with bottom supply / return filter grille • Ducted Units with flanged ducted connections DX-REFRIGERATION CIRCUIT • • • • • • • R22 Refrigerant R407C Refrigerant Scroll Type Compressor(s), (unless otherwise noted) High Efficiency, Aluminum Fin / Copper Tube Coils Thermal Expansion Valve Refrigerant Sight Glass & Filter/Drier Strainer Refrigerant Service Valves Air Technology Systems, Inc BLOWERS / MOTORS • Direct-Drive Evaporator Motors • Belt-Drive Evaporator Motors ELECTRICAL • Power Supply • Multi-Voltage Control Transformer (24V Class II) • Individual Motor Starter(s) / Contactor(s) ------------------------- See Electrical Tables Section 5 ------------------------Std Std Std Std Std Std Std Std SAFETY FEATURES • Condensate Pan Overflow Safety Switch(es) • High / Low Refrigerant Pressure Switches (DX units) • Motor Overcurrent and Overload Protection Per UL 1995 Std Std Std Std Std Std Std Std Std Std Std Std SPECIFIC MODEL STANDARD FEATURES: AIR COOLED • Low Ambient Head Pressure Control • Integral (model OHS-()-AS) or Remote Air Cooled Condenser ------------------- Three types available 0°F, -20°F or -30°F ------------------Std Std Std Std WATER / GLYCOL COOLED • 2-way, 150 psig Water/Glycol Regulating Valves • High Pressure & 3-way Valves • Coaxial, Tube-in-Tube Heat Exchanger Std Opt Std Std Opt Std Std Opt Std Std Opt Std Std Std Std Std N/A N/A N/A N/A N/A N/A N/A N/A N/A Std Std Std Std Opt Std Opt Std Opt Std Opt Std Std Std Std Std Std Std Std ALL SPLIT DX SYSTEMS • Liquid Line Solenoid Valve to Prevent Liquid Slugging DUAL CIRCUIT DX SYSTEMS • Two(2) Independent Refrigerant Circuits • Two(2) Equal Horsepower Scroll Compressors (1 per circuit) • A-Tech-1.2 two stage controls CHILLED WATER SYSTEMS • 2-way, 300 psig Motorized Valve • Modulating, High Pressure & 3-way Valves CODE CONFORMANCE • NRTL Conformance Compliance to UL 1995 Standard • NYC MEA-163-88-E / Chicago Code Approval 3-1 Air Technology Systems, Inc. Guide Specifications (ISO-9001:2001 Registered) Electrical System SATS operates in an ISO-9001:2001 registered quality control environment. Each SATS employee is committed to satisfying his or her customer expectations with the highest level of consistent, measurable and continuous quality improvement. GENERAL GUIDE SPECIFICATION General Description The system shall be manufactured by ISO-9001 Quality Registered Stulz Air Technology Systems, Inc. in Frederick, Maryland, USA. Component Access The air conditioner shall be fully accessible in-place through easily removable side access panels. Cabinet Construction The cabinet and access panels shall be fabricated from aluminum for corrosion protection and to minimize the system’s weight. The panels shall be lined with 2 lb/ft2 high density sound and thermal insulation and sealed with self-extinguishing gasketing conforming to NFPA 90A and 90B. The evaporator coil shall be mounted in an insulated stainless steel condensate pan. DX- Refrigeration System Thermal Expansion Valves The system shall incorporate overcurrent and overload protection in accordance with UL 1995 requirements. Each blower motor, compressor, electric heater stage and humidifier (if applicable) shall be provided with a factory mounted and wired starter / contactor. The control circuit shall be a 24 VAC Class 2 low voltage circuit including a circuit breaker for protection. Low voltage, high voltage and grounding wires shall be color coded and shall be individually numbered at each end for ease of service tracing. All wiring shall be in accordance with the National Electric Code (NEC). Overflow Safety Float Switch A condensate pan water level switch shall be incorporated to shut the system down if a condensate overflow condition is sensed. Filter Drier/ Strainers Sight Glasses All refrigeration piping shall be refrigerant grade tubing. Each refrigerant circuit shall include, as a minimum, refrigerant drier/strainer, sight glass with moisture detector, thermal expansion valve with rapid bleed port feature and external equalizer, evaporator coil, compressor, high pressure switch with manual reset and a low pressure switch with automatic reset. Split / Remote systems shall have a liquid line solenoid for refrigerant isolation to prevent liquid slugging. All high pressure joints shall be brazed, and the entire system shall be pressure tested at the factory with dry nitrogen, evacuated to at least 50 microns and fully charged with refrigerant. - Standard Equipment The system shall be a ceiling mounted supplemental air conditioner designed and built to the highest of industry standards. The system shall be complete and factory run-tested before shipment. The system shall be listed and labeled in compliance with UL 1995 (# SATS-1995) by an approved Nationally Recognized Testing Laboratory (NRTL). The system shall be MEA NYC (MEA-163-88-E) and Chicago Code approved. pered aluminum fins with a raisedlanced fin design for maximum heat transfer. Coil end plates shall be hot dipped galvanized. Guide Spec's QUALITY ASSURANCE Standard Equipment Note: All split / remote DX systems ship with a dry nitrogen holding charge. All self-contained DX systems ship with a full refrigerant (R-22) operating charge. Remote Stop / Start Included in the system's electrical control circuit shall be a 2-pin terminal connection for remote stop / start of the CeilAiR air conditioner by a remote source. Scroll Compressors Coils Evaporator systems shall be configured for a draw-thru air pattern to provide uniform air distribution over the evaporator coil face. The coils shall be seamless drawn copper tubes, mechanically bonded to tem- Air Technology Systems, Inc. Each compressor shall be a high efficiency, high reliability and low sound Scroll Compressor, unless specifically noted otherwise. 3-2 Guide Specifications Guide Spec's The compressor shall be complete with charging and service schraeder ports, internal vibration isolation, internal thermal overloads, internal pressure relief valve, internal discharge gas vibration eliminator and external vibration mounting isolation. Chilled Water Systems (Models OHS-()-C) Standard Equipment motor shall be factory wired for the correct speed to produce the specified air quantity. The motor(s) shall have internal overload protection. (277V & 460V direct-drive motors shall be 2-speed.) Belt Driven Systems Cooling Coil: The chilled water coil shall be constructed of seamless drawn copper tubes, mechanically bonded to tempered aluminum fins for maximum heat transfer. Coil end plates shall be hot dipped galvanized. - Standard Equipment The cooling coil shall be mounted in an insulated stainless steel condensate drain pan. Control Valve: Temp & Humid Control The standard CeilAiR system is configured as a "cooling only" system. Heating, reheating and/or humidity control can be optionally added to provide total space ­temperature and humidity control. (Please see pages 3-5 thru 3-7 for more details.) A-Tech-1.1 The blower(s) shall be belt driven with double width, double inlet housing and forward curved blades and permanently lubricated ball bearings sized for an average 100,000 hours of service life. The blowers shall be dynamically and statically balanced to minimize vibration and operate in the Class I range. Standard single stage DX and nonproportional CW Heat/Cool programmable digital thermostat. A-Tech-1.2 Standard dual stage DX Heat/ Cool programmable digital thermostat. Air Technology Systems, Inc Cooling capacity shall be controlled by a factory installed slowly opening and slowly closing 2-way motorized control valve rated for a maximum 300 psig w.w.p. The blower(s) shall have an adjustable base for belt tensioning and a locking system to prevent the motors from moving. The motors’ drive sheaves shall have an adjustable pitch to change the speed of the blowers. The motor(s) shall be 1725 RPM and shall have overload protection and a minimum NEMA service factor of 1.15. (Note: Please refer to page 3-10 for additional chilled water valve options.) Optional single or dual stage DX or non-proportional CW Temperature and Humidity Microprocessor Controller with alarms. Blowers / Motors A-Tech-20 & C6000 Optional all purpose Advanced Temperature and Humidity Microprocessor Controllers with alarms and optional remote BMS communications connections. Direct Drive Systems The blower(s) shall be direct driven with double width, double inlet housing and forward curved blades. The blower(s) shall be dynamically and statically balanced to minimize vibration and operate in the Class I range. The blower(s) shall be corrosion protected with a painted housing and impeller wheel. (NOTE: Please refer to pages 3-6 & 3-7 for additional specification details on all CeilAiR ceiling AC control options.) The three speed (208V) evaporator 3-3 C-Tech-10 Air Technology Systems, Inc. Guide Specifications - Standard Equipment DX - Heat Rejection "Ductless" Spot Cooler AIR COOLED (Models OHS-012 thru 040-( ) only.) The air conditioner shall be designed for installation in a standard 2' x 4' ceiling grid for ductless supply and return evaporator air through a factory provided bottom supply & return filter grille. Please refer to the SATS Heat Rejection Engineering Manual for specification details of air cooled condensers and condensing units. WATER / GLYCOL COOLED Guide Spec's Evaporator Air Patterns & Filtration Water/Glycol Cooled Condensers Coaxial Tube-In-Tube: (Available on all model sizes) The air conditioner shall be provided with evaporator supply and return air duct connections. EVAPORATOR AIR IN EVAPORATOR AIR IN EVAPORATOR AIR OUT EVAPORATOR AIR OUT The unit shall have slide out, 1" deep Class 2 (per U.L. Standard 900) filter(s) easily accessed through a side access panel. The filter shall have a rating of at least 80% average arrestance as measured by ASHRAE Standard 52-76 test method. Each evaporator refrigerant circuit shall be provided with a factory installed single pass, counterflow configured, tube-in-tube coaxial condenser; designed and tested for a 450 psig. w.w.p. 2-Way, 150 psig Regulating Valve (Standard on all OHS-( )-()W/G) Each refrigerant circuit's head pressure shall be controlled by a factory installed 2-way water / glycol regulating valve rated for 150 psig. w.w.p. (Note: 3-way and high pressure water/ glycol regulating valves are optionally available, page 3-9.) Standard Equipment Ducted Evaporator (Models OHS-012/120-()W/G) - The air conditioning unit shall have a drop out, 1" deep, class 2 (per U.L. Standard 900) filter easily accessed through the hinged return grille. The filter shall have a rating of at least 80% average arrestance as measured by ASHRAE Standard 52-76 test method. (Note: Please refer to Section 6 for standard CeilAiR cabinet configurations. Consult your local SATS sales representative for special applications.) Air Technology Systems, Inc. 3-4 Optional Features - Guide Specifications Optional Features Optional Features Index OPTION . ............................................. page Microprocessor Controls • A-Tech-1.1 • A-Tech-1.2 • C-Tech-10 • A-Tech-20 • A-Tech-20 • C6000 • C6000 (Digital Thermostat, 1-stage)................. 3-6 (Digital Thermostat, 2-stage)................. 3-6 (Micro Temp/Humid w/ Alarms)............. 3-6 Advanced Microprocessor..................... 3-7 Remote Communications...................... 3-7 Advanced Microprocessor..................... 3-8 Remote Communications...................... 3-9 Humidity Control Options Free Cooling - Valve Combinations • 150 psig Rated System: (standard)....................... 3-11 - 3-way, 150 psig, DX Condenser Valve(s) - 3-way, 300/400 psig, FC Coil Valve • 300 psig Rated System: (optional)........................ 3-11 - 3-way, 350 psig, DX Condenser Valve(s) - 3-way, 300/400 psig, FC Coil Valve • 400 psig Rated System: (optional)........................ 3-11 - 3-way, 450 psig, DX Condenser Valves - 3-way, 400 psig, FC Coil Valve • Steam Humidifier.................................................... 3-10 Capacity Modulation Options - • Dehumidification Cycle Index - Electric Reheat / Heat....................................... 3-10 - Hot Gas Reheat................................................ 3-10 - Hot Water Reheat / Heat.................................. 3-10 - Steam Reheat / Heat........................................ 3-10 - SCR Fired (0-10 Vdc) Electric Reheat................. 3-10 • Snap-Acting, Hot Gas Bypass.................................. 3-11 • Full-Floating, Hot Gas Bypass.................................. 3-12 • Dual Compressor / 2-Stage Systems........................ 3-12 • Modulating Chilled Water Control Valves................ 3-12 Air Technology Systems, Inc ACCESSORIES High Static Pressure Blowers • High Static Belt-Drive Blower Upgrade............... 3-10/11 (Up to 2.0" ext. static pressure) • 3-Phase Power Supply............................................ 3-12 • 277/1/60 Power Supply.......................................... 3-12 • Condensate Pump............................................. 3-12/13 High Efficiency Filtration (IAQ) • Smoke Detector...................................................... 3-13 • IAQ High Efficiency Filters...................................... 3-11 . ......................................................... 3-13 • Remote Water / Leak Detector................................ 3-13 • Acoustical Compressor Sound Jackets..................... 3-13 Head Pressure Control Options Air Cooled - Low Ambient Control • 0°F Ambient..................................................... 3-11 • -20°F Ambient................................................. 3-11 • -30°F Ambient................................................. 3-11 Water/Glycol Cooled - Regulating Valves • 2-way, 150 psig (Standard)............................... 3-11 • 2-way, 350 psig................................................ 3-11 • 2-way, 450 psig................................................ 3-11 • 3-way, 150 psig................................................ 3-11 • 3-way, 350 psig................................................ 3-11 • 3-way, 450 psig................................................ 3-11 3-5 • Firestat • Low Entering Condenser Water.............................. 3-14 • Main Power - Non-Fused Service Switch.................. 3-14 • Refrigerant Lines with Quick Disconnect Couplings................................... 3-14 Energy $aving Cooling Options • Free-Cooling Cycle.................................................. 3-14 • Alternate Water Source Cycle................................. 3-14 Air Technology Systems, Inc. Optional Features - A-Tech-1.1 5-Levels of microprocessor control offerings allow you the flexibility of selecting the best control scheme for their unique requirements: A-Tech-1.1 Standard single stage DX and non-proportional CW Heat/Cool programmable digital thermostat. Standard dual stage DX Heat/ Cool programmable digital thermostat. C-Tech-10 The CeilAiR ceiling air conditioner shall be provided with SATS' "slimline", ultra-thin profile, 1stage cool / 1-stage heat, remote wall mounted programmable digital microprocessor based controller. Note: The A-Tech-1.1 thermostat is standard on all single stage DX and non-proportional chilled water systems. A-Tech-1.2 C-Tech-10 Optional single or dual stage DX or non-proportional CW Temperature and Humidity Microprocessor Controller with alarms. A-Tech-20 Optional all purpose Advanced Temperature and Humidity Microprocessor Controller with alarms and optional remote BMS communications connections. C6000 Optional all purpose Advanced Temperature and Humidity Microprocessor Controller with alarms and optional remote BMS communications connections. Temperature & Humidity Microprocessor Controller The CeilAiR ceiling mounted air conditioner shall be provided with SATS' C-Tech-10 Microprocessor based Temperature and Humidity controller with Alarms. The controller shall incorporate a userfriendly operating environment with backlit graphic LCD display. Standard Features: The CeilAiR ceiling air conditioner shall be provided with SATS' "slimline", ultra-thin profile, 2-stage cool / 2-stage heat, remote wall mounted programmable digital microprocessor based controller. Note: The A-Tech-1.2 thermostat is standard on all dual stage DX systems. Common A-Tech-1.1/1.2 Features: • Auto changeover for Heat/Cool Modes • Selectable °F or degrees C display • Fan selector for continuous fan operation • Built-in short cycle protection • Internal switch to lock-out the keypad to prevent unauthorized tampering • Electronic calibration • 45 second fan purge after heating and cooling call • Day/Night button for user selectable alternate setpoint manual setback Air Technology Systems, Inc. Display / Keypad: • Backlit LCD graphic display with characters to show the operating mode, time, set points and actual readings • Internal Temperature and Humidity Sensor • 3 Set Point Programmable (Normal, Temporary, Night) per day, 7 days per week • Summary Alarm Contact - Microprocessor Control Options A-Tech-1.2 • 12 hour or 24 hour clock • Daylight Savings Time button to adjust the clock +/- 1 hour • Copy button to allow one program to be copied to subsequent days • Override feature • Does not require a battery • Solid state electronic output Optional Features CeilAiR Control Options Microprocessor Control Options Visual/Audible Alarm Indication: ■ High Temp (HI T) ■ Low Temp (LO T) ■ High Humid (HI H) ■ Low Humid (LO H) ■ Dirty Filter (E FL) ■ Sensor Failure ■ Comm. Failure ■ Summary (E ID) • Summary Alarm (E ID): condensate overflow/water detection; smoke detec- tion; firestat (if applicable) • Maintenace Alarms: based on user defined component run-times schedules (compressor 1 (HR 1) & 2 (HR 2); evap blower (HR F). 3-6 Optional Features Optional Features System Operation: • Fan Continuous or on Demand • Auto-Restart Upon Power Loss • Remote Stop/Start Connection • Short Cycle Protection • Cold Start Time Delay • Pump-Down Cycle Optional Features: Remote Temp/Humid Sensor: • Optional remote wall mounted temperature and humidity sensor Remote Sensor Cable Options: • 75 ft. cable length (standard option) • 150 ft. cable length A-Tech-20 • • • • • • • • • • • Microprocessor Control Options Remote Stop / Start Connection Selectable Automatic or Manual Restart Upon Power Loss Sequential Load Activation Upon Power Loss Restart Alarm Delay for Space T/H Recovery Upon Power Loss Restart Multi-Level Password Security Protection Short Cycle Protection Cold Start Time Delay Pump-Down Cycle Service Mode Time-Clock with Override Night-Setback with Override three methods: 1) 2) 3) Manual ChangeOver Automatic Timed (1-30 days) Automatic ChangeOver on Unit Failure (if applicable): Interconnect Cable Options: • 75 ft. cable length (standard option) • 150 ft. cable length Capacity Assist-Mode: ­(Additionally Optional) - Microprocessor Control Options • 30 ft. cable length (standard) • 75 ft. cable length • 150 ft. cable length In addition to switchover via manual, automatic timed or failure, the CyberLAN Multi-Unit Sequencing “Capacity AssistMode” can initiate switchover to standby unit operation to assist in the temperature and/or humidity control of the space. Remote Sensor Cable Options: Capacity Assist Sensor Cable Opts: • 75 ft. cable length (standard option) • 150 ft. cable length • 75 ft. cable length (standard option) • 150 ft. cable length Display/Sensor Options: Remote Display Cable Options: Air Technology Systems, Inc ALARM CONDITIONS: Advanced Microprocessor Temperature & Humidity Controller with Alarms The CeilAiR ceiling mounted air conditioner shall be provided with SATS' A-Tech-20 Advanced Microprocessor based Temperature and Humidity controller with Alarms. The controller shall incorporate a "user-friendly" operating environment, to allow easy system setup and operation. Standard Features: • • • • • • • • • 3-7 4 x 20 character liquid-crystal alpha-numerical display Field Configurable 30 Ft. Remote Display Cable Unit Mounted T/H Sensor Current Unit Status Component Run-Time History Visual & Audible Alarm Indication Summary Alarm Contacts Alarm History The A-Tech-20 alerts to the following alarm conditions (if applicable): ■ High Temperature ■ Low Temperature ■ High Humidity ■ Low Humidity ■ High Head Press ■ Low Suction Press ■ Loss of Air Flow ■ Loss of Power ■ Dirty Filter ■ Smoke Detection ■ Firestat ■ Leak Detection ■ GC Pump Failure ■ Sensor Failure ■ Comm. Failure CyberLAN w/ A-Tech 20 Remote Communications (Optional) REMOTE BMS CONNECTION (ModBus Gateway) The operator may select which alarms are active or inactive. CyberLAN Networking Options: Multi-Unit Sequencing: Multiple CyberAiR air conditioners incorporating A-Tech-20 controls can be configured in groups of up to 6 (six) units to allow for "N+1" redundancy/backup critical application operation. The A-Tech-20 is programmed to automatically change from current primary unit operation to secondary standby unit operation via Air Technology Systems, Inc. A-Tech-20 Inputs & Outputs can be remotely monitored (address readable) and remotely controlled (address writable) via any building management system (BMS) / local area network (LAN) control system that can communicate via a ModBus protocol. 16 Units Per CyberLAN ModBus: Each ModBus Gateway can accommodate up to 16 (sixteen) A/C units in a group. Optional Features The CeilAiR ceiling-mounted air conditioner shall be provided with SATS’ C6000 Microprocessor based Temperature and Humidity controller with Alarms. The controller shall incorporate a “user-friendly” operating environment, to allow easy system setup and operation. The C6000 is a complete microprocessor based control system designed for operating, controlling and monitoring the precision air conditioning unit. The controller shall be mounted in an indoor rated steel box. The box shall be powder coated to match the environmental control unit. The box shall contain the controller board, the IO board, and all necessary transformers and internal wiring. The control box shall be wall mounted and field wired to the environmental control unit. Display Key Pad The Display Key Pad shall feature an easy to read, liquid-crystal alpha-numerical display. The keypad/display allows the operator to visually monitor and customize unit functions and settings. The self-explanatory, keypad nomenclature shall aid in the ease of location of system programming features. Sensor Location Options As a standard, the C6000 temperature and humidity sensor shall be factory unit mounted in the return air stream of the Precision AC unit, after the return air filter(s). System Setup & Adjustments The C6000 shall be completely factory preprogrammed, and therefore, most applications will require no field setup. However, the “default” set points and their ranges are easily adjusted from C6000 keypad/display. Unit Status Display The C6000 keypad displays current unit functions and room status: • Current Dry Bulb Temp Set Point • Current Relative Humidity Set Point Current Unit Status • System ON/OFF • Cooling • Heating • Humidifying • Dehumidifying • Standby Mode • Reheating • Manual Mode • Actual Room DB Temperature • Actual Room Relative Humidity Run Times The historical run-time in hours of the following major components shall be available directly from the C6000 keypad/display: (if applicable) • Blower Motor(s) • Humidifier Air Technology Systems, Inc. • Chilled Water Valve Alarm Conditions Alarm conditions activate an audible and visual indicator. An alarm shall be acknowledged through a Reset button located on the keypad display. The C6000 alerts to the following alarm conditions (if applicable): • High Temperature • Low Temperature • High Humidity • Low Humidity • Smoke Detection • Firestat • Leak Detection • Sensor Failure • Dirty Filter • Loss of Air Flow Summary Alarm Contact A summary alarm dry-contact (n/o) connection shall be available for remote annunciation of an alarm condition. An additional user-defined custom alarm dry-contact shall also be available on most system configurations. Alarm History The C6000 controller provides users with a recorded history of the last 80 alarms, including the time and date of the alarm occurance. Control Inputs/Outputs The C6000 is capable of both digital (on/off) and analog input and output device control. Prior to shipment, each Precision AC unit’s C6000 is factory program configured to match the unit’s system operational requirements. - Microprocessor Control Options The C 6000 controller shall include a full-featured LED display for visual indication of the units operating conditions. Field Configurable The C6000 controller is field program configurable and capable of matching the unique needs of any data center, telecommunication or other critical area. Optional Features C6000 Microprocessor Control Options Temperature Anticipation The C6000 shall incorporate a self-calibrating and self-adjusting control logic that adjusts the re- 3-8 Optional Features Optional Features sponse of the SATS air conditioner to changes in temperature and humidity. The system shall provide premium setpoint accuracy while controlling the room condition’s rate of change, minimizing the equipment energy consumption and maximizing the system’s operating life and reliability. - Microprocessor Control Options Power Loss Restart In the event of a loss of power to the system, the C6000 can be configured for Automatic or Manual Restart. The C6000’s non-volatile memory enables the system to restart when power is restored, without the loss of the “last” stored set points and other system configuration settings. Sequential Load Activation To minimize the total in rush current loads during system startup/restart, the C6000 controller shall be configured for time-delay sequence startup. The user can designate specific unit restart time-delays, as well as, each unit’s respective electric heater and/or humidifier. Unit restart delay can be adjusted from 0 to 10 minutes. Microprocessor Control Options Diagnostic & Service Mode The C6000 shall incorporate a unique self-diagnostics algorithm that continually tests systems functions and hardware operation. In the event of such a failure, the user will be alerted to the condition via a visual and audible alarm. Control Board The Control Board shall initiate a self-test of the control system. Input Diagnostics All system inputs and output devices shall be continuously monitored for proper operation. Night Set-back The C6000 shall include Night SetBack occupied/non-occupied energy saving modes. This feature enables the user to customize each unit’s daily 5-day/weekly and 2-day/weekend operational schedule. MIB GATEWAY (Optional) C-6000 Inputs & Outputs shall be remotely monitored (address readable) and remotely controlled (address writable) via any building management system (BMS)/local area network (LAN) control system that can communicate via a ModBus protocol. Each C-6000 configured for BMS communication shall incorporate an RS-485 Serial Communication Port that is field connected to a factory provided wall mounted MIB Gateway. MIB-FS GATEWAY (Optional) C-6000 Inputs & Outputs shall be remotely monitored (address readable) and remotely controlled (address writable) via a building management system (BMS)/local area network (LAN) control system. Available Protocols, Modbus RTU, Modbus TCP/IP, Bacnet IP, Bacnet MSTP, Bacnet Ethernet, Metasys N-2, and Lonworks. Air Technology Systems, Inc Each C-6000 configured for BMS communication shall incorporate an RS485 Serial Communication Port that is field connected to a factory provided wall mounted MIB Gateway. The MIB-FS requires field configuration. Number of units, type of protocol employed, and individual data-points monitored must be configured in the MIB-FS prior to use. Recovery Delay After a power loss, the C6000’s Recovery Delay feature allows the system to operate without initiating any high or low temperature or humidity alarms for a delayed period. This feature allows time (15 to 60 minutes adj.) to “pull-down” the conditioned space’s load without nuisance alarms during initial startup or power loss restart. Security Multiple security levels prevent unauthorized adjustment of critical system control parameters. 3-9 Remote BMS Connection Air Technology Systems, Inc. Optional Features - Hot Water Reheat/Heat Electric Reheat/Heat A factory installed copper tube, aluminum fin heat/reheat coil and 2-way control valve shall be provided to control the flow of hot water for automatic sensible reheating mode during the dehumidification cycle and automatic heating mode as required. Humidity Control Dehumidification Cycle The ceiling air conditioner shall be provided with a refrigeration based dehumidification mode. Moisture shall be condensed on the cooling coil and discharged through the condensate drain. Reheat (electric, hot gas, hot water or steam) shall be provided to offset sensible cooling during the dehumidification cycle. Hot Gas Reheat: (Models OHS-()-AS, AR, W & G only) Scroll Compressor Hot Gas Reheat Valve Flooded Head Pressure Control Valve Relief Valve Refrigerant Reclaim Port Liquid Refrigerant Receiver Equalizer Line Remote Air Cooled Condenser LP HP Sight Glass Hot Gas Evaporator Cooling Coil Reheat Coil Feeler Bulb Air Flow Steam Reheat/Heat A factory installed copper tube, aluminum fin heat/reheat coil and 2-way control valve shall be provided to control the flow of steam for automatic sensible reheating mode during the dehumidification cycle and automatic heating mode as required. (Note: Steam trap and steam piping specialities shall be provided by others not SATS.) SCR Fired Reheat/Heat The electric heat/reheat shall be controlled through a “Zero Firing” Silicon Controlled Rectifier (SCR) with an extruded aluminum heat sink and solid state logic system to provide close dry bulb temperature control of the conditioned air. A-Tech-20 proportional (0-10 Vdc) microprocessor controls shall be provided with the SCR Fired Electric Reheat option. High Static Pressure Belt-Drive Blowers - Guide Specifications The humidifier shall be an electrode steam canister type and shall have an adjustable humidity output setting from 25 to 100% of the full rated humidifier capacity, an automatic flush cycle that senses the current consumption of the humidifier and controls mineral concentration of the water. A “Change Cylinder” light shall notify service personnel when the humidification output is below rated requirements and when maintenance is due. Heaters shall use fast reacting nichrome wire heater elements which cool quickly when turned off eliminating residual heat problems. Equalizer Line Canister Steam Humidification A factory mounted and wired electric resistance heater shall be included to provide automatic sensible reheating mode during the dehumidification cycle and automatic heating mode as required. Electric heaters shall be provided with thermal / magnetic circuit breakers which shall protect each conductor. The heater elements shall be housed within a stainless steel frame with mounted supports. Included shall be one automatic resetting over-temperature safety device (pilot duty), and a non-resettable over-temperature safety device (located in main power line). Optional Features SELECTED OPTIONS Guide Specifications Solenoid Valve Refrigerant Drier / Strainer Thermal Expansion Valve A factory installed copper tube, alumninum fin hot gas reheat coil and valve shall be provided for automatic sensible reheating mode during dehumidification cycle. Hot compressor discharge gas shall be diverted from the condenser to the hot gas reheat coil providing energy free sensible reheating. (Note: Hot Gas Reheat is not available on systems incorporating Free-Cooling or Alternate Water Source, because no method of reheat would be available during non-compressorized FC or AWS operation.) Air Technology Systems, Inc. The CeilAiR ceiling air conditioner shall be provided with a high static pressure belt-driven evaporator blower to provide standard unit CFM @ ____ " e.s.p. (Note: Due to the probable change in standard unit blower motor horsepower for the High Static Belt-Drive Blower 3-10 Optional Features Optional Features option, please consult your local SATS sales representative for the following unit specification changes: • • • • Blower Motor Horsepower Net Cooling Capacity Electrical Data Discharge Blower Data Unit AIr Flow Rate (CFM) will match the standard data as shown in Section 4 of this manual for each respective unit model.) Filtration Guide Specifications fan speed head pressure control for year-round air conditioning system operation down to 0°F DB minimum ambient air temperature. (Note: 0°F fan cycling head pressure control is a standard feature for all CeilAiR air cooled condensers and condensing units incorporating direct drive condenser fans.) FREE-COOLING SYSTEMS -20°F, Variable Speed Control (Model WCS-( ) Condensers) The air cooled system shall incorporate a low ambient variable speed fan head pressure control for year-round system operation down to -20°F DB minimum ambient air temperature. -30°F, Flooded Control Remote Air Cooled Condenser (Optional) Flooded Head Pressure Control Valve Relief Valve Liquid Refrigerant Receiver HP Evaporator Cooling Coil LP Sight Glass Refrigerant Reclaim Port Low Pressure Switch Liquid Line Solenoid Valve Refrigerant Drier / Strainer Feeler Bulb Equalizer Line - Guide Specifications High Pressure Switch DX Water/Glycol Cooled systems with Free-Cooling are available with the following standard and optional DX head pressure and Free-Cooling valve combinations: 150 psig Rated System: (standard) Scroll Compressor CeilAiR ceiling A/C's are available with the following standard (F1) and optional (F2, F3 & F4) high efficiency IAQ conscious filtration: Each refrigerant circuit's head pressure shall be controlled by a factory (or field) installed ____-way water / glycol regulating valve rated for ____ psig. w.w.p. Thermal Expansion Valve • DX Valves = 3-way, 150 psig • FC Valve = 3-way, 300/400 psig 300 psig Rated System: (optional) • DX Valves = 3-way, 350 psig • FC Valve = 3-way, 300/400 psig Air Technology Systems, Inc F1: F2: F3: F4: 1", 20% Eff. Filters (standard) 2", 30% Eff. Filters 4", 60% Eff. Filters 2", 30% Pre / 4", 60% Eff. Final Filters Air Pattern Type Filters Avail. Direct Drive 012/040: w/ Spot Cooler: w/ Ducted Return: F1 F1, F2 (n/a 024) Belt-Drive Units: w/ Ducted Return: F1, F2, F3 & F4 The air cooled system shall incorporate a low ambient flooded head pressure control for year-round system operation down to -30°F DB minimum ambient air temperature. This option shall include a factory installed crankcase heater, cold-start relay, liquid refrigerant receiver with receiver liquid level sight glass and head pressure regulating valve for flooded condenser operation. Filter ratings are based on dust spot efficiency ratings per ASHRAE Test Standard 52-76. (Note: F2, F3 & F4 optional filters create additional static pressure and may require the High Static Pressure Belt-Drive Option. Please consult your local Sales Representative for details.) Head Pressure Control AIR COOLED - Low Ambient 0°F, Fan Cycling / Fan Speed The air cooled system shall incorporate a low ambient fan cycling / 3-11 400 psig Rated System: (optional) • DX Valves = 3-way, 450 psig • FC Valve = 3-way, 400 psig Each refrigerant circuit's head pressure shall be controlled by a field installed 3-way water / glycol regulating valve rated for ____ psig w.w.p. Free-Cooling mode cooling shall be controlled by a factory installed 3-way motorized (on/off) control valve rated for ____ psig. w.w.p. Note: Modulating (0-10 Vdc) Free-Cooling mode cooling control is optionally available via A-Tech-20 controls and modulating 3-way FC control valve. DX Water Cooled and Glycol Cooled systems are available with following standard (V1) and optional (V2-V6) head pressure regulating control valves: V1: 2-way, 150 psig (standard) V2: 2-way, 350 psig V3: 2-way, 450 psig V4: 3-way, 150 psig V5: 3-way, 350 psig V6: 3-way, 450 psig } Air Technology Systems, Inc. 3-way valves ship loose for field installation. DX - Capacity Modulation / Freeze-Protection SNAP-ACTING, Hot Gas Bypass (Models OHS-()-AS, AR, W & G only) The CeilAiR ceiling A/C shall incorporate a snap acting hot gas bypass system to provide modulation of the unit’s cooling capacity and evaporator coil freeze protection under low load conditions. Optional Features - Guide Specifications Scroll Compressor HP LP Low Pressure Switch Flooded Head Pressure Control Valve Feeler Bulb Equalizer Line High Pressure Switch Evaporator Cooling Coil Hot Gas Regulator Valve (Optional) Relief Valve Liquid Line Solenoid Valve Sight Glass Refrigerant Liquid Refrigerant Reclaim Port Receiver Refrigerant Drier / Strainer Thermal Expansion Valve FULL-FLOATING, Hot Gas Bypass (Models OHS-( )-()AHU/SCO only) DUAL COMPRESSOR SYSTEMS (Models OHS-( )-D()) V6: 3-way, 400 psig Standard (On/Off) Valve Control : A ____-way motorized (On/Off) CW or AWS cooling control valve rated for a maximum ____ psig w.w.p. shall be factory unit installed. Precision cooling control shall be accomplished via a spring return slow open and close valve design. Optional (0-10 Vdc) Valve Control: A ____-way modulating CW or AWS cooling control valve rated for a maximum ____ psig w.w.p. shall be factory installed. Precision cooling control shall be accomplished via a 0-10 Vdc A-Tech-20 analog control signal to the proportional actuating control valve. ACCESSORIES The air conditioner shall be provided with a 2-Stage temperature controller with microprocessor based control logic for automatic staging. Chilled Water & AWS Control Valves Chilled Water and Alternate Water Source cooling shall be controlled by the following standard and optional control valves: Remote Air Cooled Condenser (Optional) Scroll Compressor High Pressure Switch Flooded Head Pressure Control Valve Relief Valve Liquid Refrigerant Receiver HP Evaporator Cooling Coil LP Sight Glass Refrigerant Reclaim Port Low Pressure Switch Liquid Line Solenoid Valve Refrigerant Drier / Strainer Thermal Expansion Valve Three phase power supply is available, as an option, on OHS-024, 032 & 040-() units. Compressor, (belt-drive blower motor(s) and electric heat/reheat if applicable) shall be three phase in lieu of standard single phase. All other components (5/10 lb humidifier and direct drive motor(s)) shall be single phase, with each leg of power supply balanced as closely as possible. (Note: Three phase power supply is a standard feature on models OHS-048 and larger units.) Models OHS-012/060-C / AWS: V1: V2: V3: V4: Feeler Bulb Equalizer Line The air conditioner shall be a dual scroll compressor system with two independent refrigeration circuits to provide 50% capacity unloading, as well as component redundancy. Note-1: Fast delivery orders sometimes require that the OHS system be shipped from stock as 208/1/60. In those cases, 277/1/60 applications are provided with a field installed 277 to 208 step-down transformer. Condensate Pump 3 Phase Power Supply A main power distribution block shall be located in the air conditioner's electric box for single point power connection to a 277/1/60 power supply source. All system components (motor, heater & humidifier, if applicable) shall be rated for operation with a 277/1/60 power supply. 277V to 208V main power step-down transformers shall not be required. 2-way, 300 psig (standard) 2-way, 400 psig 3-way, 300 psig 3-way, 400 psig Air Technology Systems, Inc. A Low-Profile condensate pump designed for limited height ceiling plenum installation shall be factory provided for automatic removal of condensate and humidifier flush water (if applicable). The condensate pump shall be field installed as a standard. - Guide Specifications The CeilAiR ceiling A/C shall incorporate a full floating hot gas bypass system to provide modulation of the unit’s cooling capacity and evaporator coil freeze protection under low load conditions. (Models OHS-012 thru-040) V5: 2-way, 400 psig (standard) Optional Features 277/1/60 Power Supply Models OHS-072/120-C / AWS: Remote Air Cooled Condenser (Optional) A heavy duty All-Metal condensate pump shall be provided for automatic removal of condensate and humidifier flush water (if applicable). The pump shall be constructed with a cast aluminum reservoir and impeller; aluminum reservoir cover and impeller chamber cover; stainless steel fasteners and a stainless steel motor shaft. The condensate pump meets most local codes for certification as a "plenum rated" pump. The condensate pump shall be field installed only. 3-12 Optional Features Optional Features The condensate pump shall be specifically designed to operate with the higher condensate temperatures caused by the flush and drain cycle of the electrode canister humidifiers. Dual Overflow Safety Switches: In addition to the standard condensate pan overflow safety float(s), the condensate pump shall include an internal overflow safety float switch which, when wired to the A/C's remote stop/start terminals, shall open the A/C's control circuit, thereby shutting the A/C down in the event of a condensate overflow. Guide Specifications 1 to 3 Ton Models: OHS-012/040-HAS, HAR, HAHU, HW, HG & HC 4 to 10 Ton Models: OHS-048/120-()AR, AHU, W, G & C Factory Installed In-Pan Condensate Pump (Not Available w/ Humidifier) Smoke Detector water/leak detector per CeilAiR A/C unit shall be factory provided for remote field installation. Upon sensing a water leak, the normally closed water detector control circuit shall open, thereby shutting down the air conditioner's water producing operations. - Guide Specifications Dual (two) - Spot Type Detectors: Quantity 2(two) remote spot type water/leak detectors per CeilAiR A/C unit shall be factory provided for remote field installation. Upon sensing a water leak, the normally closed water detector control circuit shall open, thereby shutting down the air conditioner's water producing operations. 20 Ft. - Strip/Cable Type Detector: Air Technology Systems, Inc Factory Installed - Optional A photo-electric smoke detector shall be factory installed in the CeilAiR evaporator section on the suction side of the evaporator blower. Low-Profile Condensate Pump The CeilAiR Low-Profile condensate pump can be factory installed as an option on the following models: The smoke detector shall be rated for high air velocity applications, and shall shut down the air conditioner upon sensing smoke in the return air stream. OHS-012/040-AS, AHU, AR, W, G & C Firestat Factory Installed Low-Profile Condensate Pump In-Pan Condensate Pump The CeilAiR In-Pan condensate pump can be factory installed as an option in the following models: The air conditioner shall be provided with a factory wired and mounted firestat. The firestat shall shut down the air conditioner upon sensing a high return air temperature. Compressor Sound Jackets (Air Cooled 0°F OHS-()-AS, and Water/Glycol Cooled Only!) Remote Water Detectors Single (one) - Spot Type Detector: Quantity 1(one) remote spot type 3-13 A 20 Ft. in length remote strip/cable type water/leak detector shall be factory provided for remote field installation. In addition to the 20 ft. cable, a 24V power water detector power module shall require field mounting and wiring to factory provided terminal connection. Upon sensing a water leak, the normally closed water detector control circuit shall open, thereby shutting down the air conditioner's water producing operations. Air Technology Systems, Inc. Each compressor shall be provided with a factory installed acoustical sound jacket. Each sound jacket shall have a snap closure system for ease of removing and reinstallation during Optional Features - Main Power - Electric Non-Fused Service Switch The main power service switch shall be the NEMA 3R or NEMA-12 nonfused type, depending on the OHS model selected. The disconnect switch shall have a lockable handle. (Note: Field installed main power service switches shall be the standard option, however, switches can be optionally factory mounted on select CeilAiR systems. Factory mounting of disconnect switches is not available on models OHS-012, 018, 024 & 032-AS incorporating the "Ducted" Evaporator Connection option.) Refrigerant Lines w/ Quick Disconnects (AHU/RCU-O Systems Only!) Each refrigerant circuit shall be supplied with factory assembled, soft-copper refrigerant line set 50 ft. in length complete with quick disconnect couplings and schraeder service ports. The quick disconnect couples shall be industrial grade, self-sealing, reusable type couplings. Suction lines shall be insulated, liquid lines shall be uninsulated. 2) A backup DX compressorized refrigerant circuit. Remote Liquid Chiller (by others) A Free-Cooling cycle shall be provided to take advantage of low ambient air temperature conditions to provide compressor-less cooling. Alternate Water Source Cooling Coil Pump (by others) Flow Switch AWS Control Valve FS Alternate Water Source Aqua-Stat T Remote Air Cooled Condenser Scroll Compressor Flooded Head Pressure Control Valve Relief Valve Refrigerant Reclaim Port Receiver When outdoor temperatures are sufficiently low (setpoint adjustable), source coolant shall be diverted from the DX - Water or Glycol Cooled refrigerant condenser to a chilled water/glycol coil (free-cooling coil & control valve). The drycooler capacity shall be increased by reversing the typical drycooler fan(s) cycling sequence of operation to provide the maximum cooling effect for the coolant solution. The free-cooling coil shall be closely sized to match the refrigerant cooling capacity to increase the number of hours that the system can operate in the free-cooling mode, thereby increasing the operating savings of the installation. LP HP Sight Glass DX - Cooling Coil Feeler Bulb Solenoid Valve Refrigerant Drier / Strainer Expansion Valve When chilled water is available, the system shall operate as a chilled water unit, without the compressor operating. When the water temperature is too high, or the water flow rate is not sufficient, the air conditioner shall automatically switch to the DX compressorized refrigerant operation. - Guide Specifications For Water/Glycol systems that require entering condenser water temperatures from 65°F to 45°F, the system shall be provided with a factory installed in-line liquid refrigerant receiver to help reduce the negative effect the low condenser source can have on the evaporator. A compressor crankcase heater shall also be provided standard with this option. (Compressor Sound Jackets are not available with this option due to the crankcase heater). Free-Cooling Option (Water/Glycol Economizer Coil) 1) A chilled water / glycol circuit (AWS coil & control valve); Equalizer Line Low Entering Condenser Water Kit ENERGY $AVING COOLING OPTIONS Optional Features maintenance. Each sound jacket shall have a Noise Reduction Coefficient NRC of 85 per ASTM C-423 and a Sound Transmission Loss STC of 11 per ASTM E-90. Guide Specifications Alternate Water Source (Chilled Water by "Day" and DX-Backup by "Night") An Alternate Water Source cooling cycle shall be provided to utilize building chilled water supply when available as the primary cooling cycle with DX - Air Cooled refrigerant cooling as a backup. The air conditioner shall have two cooling systems: Air Technology Systems, Inc. 3-14 Performance Data - Equipment Schedule Data Performance Data Performance Data Index MODEL TYPE ........................................... page DX - Air Cooled DX with Free-Cooling Self-Contained Air Cooled: Self-Contained Glycol Cooled w/ FC: • 1-3 Ton, models OHS-012/040-AS.................................... 4-2/3 • 1-5 Ton, models OHS-012/060-G-FC............................ 4-17/19 • 4-10 Ton, models OHS-048/120-DG-FC........................ 4-20/21 Split Air Cooled Remote w/ Condenser: - • 1-5 Ton, models OHS-012/060-AR.................................... 4-2/3 • 4-10 Ton, models OHS-048/120-DAR.................................. 4-4 Self-Contained Water Cooled w/ FC: • 1-5 Ton, models OHS-012/060-W-FC............................ 4-22/23 • 4-10 Ton, models OHS-048/120-DW-FC....................... 4-24/25 Index Split Air Cooled Air Handling w/ Condensing Unit: • 1-5 Ton, models OHS-012/060-AHU.................................... 4-5 • 4-10 Ton, models OHS-048/120-DAHU................................ 4-6 DX with Alternate Water Source Air Technology Systems, Inc DX - Water Cooled Alternate Water Source: Self-Contained Water Cooled: • 1-5 Ton, models OHS-012/060-W........................................ 4-7 • 4-10 Ton, models OHS-048/120-DW................................... 4-8 • 1-5 Ton, models OHS-012/060-( )-AWS............................. 4-26 • 4-10 Ton, models OHS-048/120-D()-AWS.......................... 4-27 • 42°F / 50°F EWT Performance Data................................... 4-28 DX - Glycol Cooled Self-Contained Glycol Cooled: • 1-5 Ton, models OHS-012/060-G......................................... 4-9 • 4-10 Ton, models OHS-048/120-DG.................................. 4-10 Chilled Water Chilled Water Air Handlers: • 1-3 Ton, models OHS-012/040-C.................................. 4-11/12 • 4-10 Ton, models OHS-048/120-C................................ 4-13/14 • 42°F EWT Performance Data............................................. 4-15 • 50°F EWT Performance Data............................................. 4-16 4-1 Air Technology Systems, Inc. Air Cooled - 012-AS/AR 018-AS/AR 024-AS/AR 032-AS/AR 040-AS/AR 048-AR 060-AR NET DX COOLING CAPACITY - BTU/H, (includes standard DX evaporator motor heat @ std CFM & e.s.p. ratings) 80°FDB/67°FWB, 50% RH 13,985 19,465 25,740 32,770 35,800 59,970 65,975 10,585 15,235 19,470 23,430 27,950 47,685 52,435 Total 12,710 18,000 23,600 30,000 32,650 55,010 60,470 Sensible 10,645 15,400 19,025 22,920 27,430 46,960 51,630 Total 12,000 17,160 22,465 28,500 31,050 52,400 57,580 Sensible 10,405 15,100 18,580 22,400 26,690 46,020 50,590 Total 13,425 18,860 24,600 31,320 34,700 57,680 63,350 Sensible 11,840 16,990 20,900 24,905 30,900 52,080 57,325 Total 12,270 17,490 23,030 28,895 32,080 53,415 58,620 Sensible 11,385 16,400 20,500 23,940 29,650 50,250 55,285 Total 11,585 16,665 22,000 27,400 30,530 50,875 55,790 Sensible 11,110 16,065 20,060 23,600 28,990 49,180 54,080 75°FDB/62.5°FWB, 50% RH 72°FDB/60°FWB, 50% RH 80°FDB/65°FWB, 45% RH 75°FDB/61°FWB, 45% RH 72°FDB/58.5°FWB, 45% RH Reheat/Heat - Performance Capacities Include Motor Heat, (Optional) ELECTRIC REHEAT / HEAT - BTU/H (Kw) @ 208V 17,135 (5.0) 17,135 (5.0) 17,135 (5.0) 17,425 (5.1) 17,955 (5.3) 37,350 (10.9) 38,900 (11.4) @ 230V 18,840 (5.5) 18,840 (5.5) 18,840 (5.5) 19,130 (5.6) 19,660 (5.8) 43,140 (12.6) 44,690 (13.1) @ 460V 17,355 (5.1) 17,355 (5.1) 17,355 (5.1) 17,645 (5.2) 18,175 (5.3) 37,350 (10.9) 38,900 (11.4) @ 277/480V 18,065 (5.3) 18,065 (5.3) 18,065 (5.3) 18,355 (5.4) 18,885 (5.5) 38,835 (11.4) 40,385 (11.8) 11,390 17,030 21,190 25,650 30,920 49,310 54,210 HOT GAS REHEAT BTU/H HOT WATER REHEAT / HEAT - Reheat rated @ 180°F Entering Water Temperature, EAT = 72°F DB BTU/H 20,690 32,420 34,880 50,360 55,320 97,140 111,220 GPM 1 2 2 3 3 4 5 Pressure Drop, ft. wg Control 0.1 0.3 0.3 0.3 0.3 0.4 0.6 Motorized Motorized Motorized Motorized Motorized Motorized Motorized 60,000 STEAM REHEAT / HEAT - nominally Reheat rated @ 5 psig Steam, EAT = 72°F DB BTU/H (nominal) Condensate (lb/hr) Control 12,000 18,000 24,000 32,000 40,000 48,000 13 19 25 34 42 50 63 Motorized Motorized Motorized Motorized Motorized Motorized Motorized Humidification - Electrode Steam Canister Humidifier with Adjustable Output, (Optional) Lbs/Hr, (Kw Input) Std Control 2-5, (1.7) 2-5, (1.7) 2-5, (1.7) 2-5, (1.7) 2-5, (1.7) 4-10, (3.4) 4-10, (3.4) Cycling Cycling Cycling Cycling Cycling Cycling Cycling 1/4 Hp 1/4 Hp 1/3 Hp 1/2 Hp 1 Hp 1-1/2 Hp - Air Cooled (1 to 5 ton Systems) Total Sensible Performance Data OHS Model 1 to 5 Ton "OHS" (Single Compressor), Self-Contained & Split Evaporator Blower / Motor - DWDI Centrifugal Horsepower 1/4 Hp CFM @ ext. st. press. 500 @ 0.3" 750 @ 0.3" 900 @ 0.3" 1,000 @ 0.3" 1,415 @ 0.3" 2,200 @ 0.5" 2,500 @ 0.5" Std. Drive Method Direct Driven Direct Driven Direct Driven Direct Driven Direct Driven Belt Driven Belt Driven Continued on next page Air Technology Systems, Inc. 4-2 Air Cooled Performance Data OHS Model 1 to 5 Ton "OHS" (Single Compressor), Self-Contained & Split 012-AS/AR 018-AS/AR 024-AS/AR 032-AS/AR 040-AS/AR 048-AR 060-AR NET DX COOLING CAPACITY - BTU/H, (includes standard DX evaporator motor heat @ std CFM & e.s.p. ratings) Evaporator Coil - Aluminum Fin, Copper Tube Rows/Face Area (Ft2) 3/ 2.1 3/ 2.1 3/ 2.1 3/ 2.8 3/ 2.8 4/ 5.0 4/ 5.0 Scroll, (1) Compressor - Heat pump duty rated, HCFC Ozone Safe R-22 Recip., (1) Scroll, (1) Scroll, (1) Scroll, (1) Scroll, (1) Scroll, (1) Watts - Input Type, (Qty.) 1,405 1,614 2,092 2,711 2,842 4,415 4,959 Tot. Heat of Rej. (BTU/H) 17,595 24,260 31,480 40,500 43,830 70,080 77,395 20x20, (1) 20x20, (1) 20x20, (1) 20x20, (1) 20x20, (1) 20x16, (2) 20x16, (2) Filters - 1" deep throwaway Nom. Size (in.), (Qty.) Connection Sizes - Copper, (Please refer to CeilAiR IOM Manual for proper interconnecting refrigerant line sizing.) Refrigerant: (OHS-012/060-()AR only) - Air Cooled (1 to 5 ton Systems) Liquid Line, (Qty.) 3/8" OD, (1) 3/8" OD, (1) 3/8" OD, (1) 1/2" OD (1) 1/2" OD (1) 1/2" OD (1) 1/2" OD (1) Hot Gas Line, (Qty.) 1/2" OD, (1) 1/2" OD, (1) 5/8" OD, (1) 5/8" OD (1) 7/8" OD (1) 7/8" OD (1) 7/8" OD (1) Condensate Drain 7/8" OD 7/8" OD 7/8" OD 7/8" OD 7/8" OD 3/4" FPT 3/4" FPT Humidifier Inlet 1/4" OD 1/4" OD 1/4" OD 1/4" OD 1/4" OD 1/4" OD 1/4" OD Physical Size - (Please refer to Section 6 for detailed dimensional data.) Approx. Wt. (OHS-()-AS) 210 lbs 215 lbs 220 lbs 255 lbs 265 lbs N/A N/A Approx. Wt. (OHS-()-AR) 160 lbs 165 lbs 170 lbs 205 lbs 215 lbs 370 lbs 380 lbs Air Cooled Condenser Data - (Self Contained) Air Technology Systems, Inc OHS Model @ 95°F Amb. 012-AS 018-AS 024-AS 032-AS 040-AS 048 060 Integral Centrifugal Blower, Air Cooled Condenser Data for Self-Contained Model OHS-( )-AS Condenser Blower Data 750 @ 0.3" 1,400 @ 0.3" 1,400 @ 0.3" 2,000 @ 0.3" 2,000 @ 0.3" N/A N/A Motor Horsepower CFM @ e.s.p 1/3 Hp. 1/2 Hp. 1/2 Hp. 1/2 Hp. 1/2 Hp. N/A N/A Drive Method Direct Direct Direct Direct Direct N/A N/A 4 / 2.1 4 / 2.1 4 / 2.1 4 / 2.8 4 / 2.8 N/A N/A 0°F 0°F 0°F 0°F 0°F N/A N/A MotorSpeed MotorSpeed MotorSpeed MotorSpeed MotorSpeed N/A N/A Condenser Coil Rows/Face Area (ft2) Low Ambient Control Std. Minimum Op. Amb. Head Pressure Method Note: Compressor is integral to the OHS-( )-AS Self-Contained Unit. Please refer to the SATS Heat Rejection Engineering Manual for specification and performance data on Remote Outdoor and Indoor Air Cooled Condensers used with OHS-( )-()AR Split Systems. 4-3 Air Technology Systems, Inc. Air Cooled - 4 to 10 Ton "OHS" (Dual Compressors) ( )-048-DAR ( )-072-DAR ( )-084-DAR ( )-120-DAR NET DX COOLING CAPACITY - BTU/H, (includes standard DX evaporator motor heat @ std CFM & e.s.p. ratings) 80°FDB/67°FWB, 50% RH Total 53,740 73,870 92,065 130,435 Sensible 40,860 62,110 71,070 98,030 75°FDB/62.5°FWB, 50% RH Total 49,250 67,550 83,980 119,590 Sensible 40,290 61,525 70,840 96,230 72°FDB/60°FWB, 50% RH Total 46,950 64,275 79,760 113,380 Sensible 39,480 60,215 69,565 94,580 80°FDB/65°FWB, 45% RH Total 51,610 70,730 87,660 124,890 Sensible 44,310 68,085 79,060 106,480 75°FDB/61°FWB, 45% RH Total 47,860 65,590 80,770 115,540 Sensible 42,830 64,070 76,215 102,850 Total 45,620 62,750 76,660 109,955 Sensible 42,040 61,910 73,710 100,920 72°FDB/58.5°FWB, 45% RH ELECTRIC REHEAT / HEAT - BTU/H (Kw) @ 208V/460V 36,810 (10.9) 38,900 (11.4) 40,510 (11.9) 43,580 (12.8) @ 230V 42,600 (12.5) 44,690 (13.1) 46,300 (13.6) 49,370 (14.5) @ 480V 38,295 (11.2) 40,385 (11.8) 41,995 (12.3) 45,065 (13.2) 21,150 32,300 37,190 50,520 130,500 HOT GAS REHEAT BTU/H HOT WATER REHEAT / HEAT - Reheat rated @ 180°F Entering Water Temperature, EAT = 72°F DB BTU/H 50,360 97,880 99,830 GPM 3 3 3 10 0.3 0.3 0.3 2.2 Motorized Motorized Motorized Motorized 48,000 72,000 90,000 120,000 50 75 94 125 Motorized Motorized Motorized Motorized Pressure Drop, ft. wg Control STEAM REHEAT / HEAT - nominally Reheat rated @ 5 psig Steam, EAT = 72°F DB BTU/H (nominal) Condensate (lbs/hr) Control Humidification - Electrode Steam Canister Humidifier with Adjustable Output, (Optional) Lbs/Hr, (Kw Input) Std Control 4-10, (3.4) 4-15, (5.1) 4-15, (5.1) 4-15, (5.1) Cycling Cycling Cycling Cycling Evaporator Blower / Motor - DWDI Centrifugal - Belt Driven, Variable Pitch Pulleys Horsepower CFM @ ext. st. press. Drive Method 3/4 Hp 1-1/2 Hp 2 Hp 3 Hp 1,800 @ 0.5" 3,000 @ 0.5" 3,350 @ 0.5" 4,400 @ 0.5" Belt Driven Belt Driven Belt Driven Belt Driven Evaporator Coil - Aluminum Fin, Copper Tube Rows Face Area (Ft2) 3 4 4 4 4.1 6.7 6.7 10 Scroll, (2) Compressor - Heat pump duty rated, HCFC Ozone Safe R-22 Scroll, (2) Scroll, (2) Scroll, (2) Watts Input (per compressor) Type, (Qty.) 2,054 2,797 3,848 4,959 Total Heat of Rejection, (BTU/H) 63,270 86,645 110,250 153,440 16x20, (2) 20x20, (2) 20x20, (2) 24x24, (2) 1/2" OD, (2) Filters - 1" deep throwaway Nominal Size (in.), (Qty.) Connection Sizes - Copper, (Please refer to CeilAiR IOM Manual for proper interconnecting refrigerant line sizing.) Refrigerant: Liquid Line, (Qty.) 3/8" OD, (2) 1/2" OD, (2) 1/2" OD, (2) Hot Gas Line, (Qty.) 5/8" OD, (2) 5/8" OD, (2) 7/8" OD, (2) 7/8" OD, (2) 3/4" FPT, (1/2"OD) 3/4" FPT, (1/2"OD) 3/4" FPT, (1/2"OD) 3/4" FPT, (1/2"OD) 1/4" OD 1/4" OD 1/4" OD 1/4" OD 450 lbs 510 lbs 580 lbs Condensate Drain, (w/ In-Pan Pump) Humidifier Inlet - Air Cooled (4 to 10 Ton, DUAL Compressor) Reheat/Heat - Performance Capacities Include Motor Heat, (Optional) Performance Data OHS Model Physical Size - (Please refer to Section 6 for detailed dimensional data.) Approx. Weight 420 lbs Air Technology Systems, Inc. 4-4 Air Cooled AHU/RCU Performance Data OHS Model 012-AHU 018-AHU 1 to 5 Ton "OHS" 024-AHU 032-AHU 040-AHU 048-AHU 060-AHU NET DX COOLING CAPACITY - BTU/H, (includes standard DX evaporator motor heat @ std CFM & e.s.p. ratings) 80°FDB/67°FWB, 50% RH Total 13,985 19,465 25,740 32,940 36,505 59,970 65,975 Sensible 10,585 15,235 19,470 24,595 30,065 47,685 52,435 Total 12,710 18,000 23,600 30,355 33,750 55,010 60,470 Sensible 10,645 15,400 19,025 24,235 29,300 46,960 51,630 Total 12,000 17,160 22,465 29,035 32,320 52,400 57,580 Sensible 10,405 15,100 18,580 23,680 28,500 46,020 50,590 Total 13,425 18,860 24,600 31,670 35,120 57,680 63,350 Sensible 11,840 16,990 20,900 27,560 33,385 52,080 57,325 Total 12,270 17,490 23,030 29,500 32,790 53,415 58,620 Sensible 11,385 16,400 20,500 26,251 31,530 50,250 55,285 Total 11,585 16,665 22,000 28,220 31,410 50,875 55,790 Sensible 11,110 16,065 20,060 25,570 30,525 49,180 54,080 75°FDB/62.5°FWB, 50% RH 72°FDB/60°FWB, 50% RH 80°FDB/65°FWB, 45% RH 75°FDB/61°FWB, 45% RH 72°FDB/58.5°FWB, 45% RH Air Cooled AHU/RCU (1 to 5 ton Systems) Reheat/Heat - Performance Capacities Include Motor Heat, (Optional) ELECTRIC REHEAT / HEAT - BTU/H (Kw) @ 208V 17,135 (5.0) 17,135 (5.0) 17,135 (5.0) 17,425 (5.1) 17,955 (5.3) 37,350 (10.9) 38,900 (11.4) @ 230V 18,840 (5.5) 18,840 (5.5) 18,840 (5.5) 19,130 (5.6) 19,660 (5.8) 43,140 (12.6) 44,690 (13.1) Air Technology Systems, Inc @ 460V 17,355 (5.1) 17,355 (5.1) 17,355 (5.1) 17,645 (5.2) 18,175 (5.3) 37,350 (10.9) 38,900 (11.4) @ 277/480V 18,065 (5.3) 18,065 (5.3) 18,065 (5.3) 18,355 (5.4) 18,885 (5.5) 38,835 (11.4) 40,385 (11.8) 111,220 HOT WATER REHEAT / HEAT - Reheat rated @ 180°F Entering Water Temperature, EAT = 72°F DB BTU/H 20,690 32,420 34,880 50,360 55,320 97,140 GPM 1 2 2 3 3 4 5 0.1 0.3 0.3 0.3 0.3 0.4 0.6 Motorized Motorized Motorized Motorized Motorized Motorized Motorized 60,000 Pressure Drop, ft. wg Control STEAM REHEAT / HEAT - nominally Reheat rated @ 5 psig Steam, EAT = 72°F DB BTU/H (nominal) Condensate (lb/hr) Control 12,000 18,000 24,000 32,000 40,000 48,000 13 19 25 34 42 50 63 Motorized Motorized Motorized Motorized Motorized Motorized Motorized Humidification - Electrode Steam Canister Humidifier with Adjustable Output, (Optional) Lbs/Hr, (Kw Input) Std Control 2-5, (1.7) 2-5, (1.7) 2-5, (1.7) 2-5, (1.7) 2-5, (1.7) 4-10, (3.4) 4-10, (3.4) Cycling Cycling Cycling Cycling Cycling Cycling Cycling Evaporator Blower / Motor - DWDI Centrifugal 1/4 Hp 1/4 Hp 1/4 Hp 1/3 Hp 1/2 Hp 1 Hp 1-1/2 Hp CFM @ ext. st. press. Horsepower 500 @ 0.3" 750 @ 0.3" 900 @ 0.3" 1,000 @ 0.3" 1,415 @ 0.3" 2,200 @ 0.5" 2,500 @ 0.5" Std. Drive Method Direct Driven Direct Driven Direct Driven Direct Driven Direct Driven Belt Driven Belt Driven Opt. Drive Method Belt-Driven Belt-Driven Belt-Driven Belt-Driven Belt-Driven N/A N/A 3/ 2.1 3/ 2.1 3/ 2.1 3/ 2.8 3/ 2.8 4/ 5.0 4/ 5.0 20x20, (1) 20x20, (1) 20x20, (1) 20x20, (1) 20x20, (1) 20x16, (2) 20x16, (2) Evaporator Coil - Aluminum Fin, Copper Tube Rows/Face Area (Ft2) Filters - 1" deep throwaway Nom. Size (in.), (Qty.) Connection Sizes - Copper, (Please refer to CeilAiR IOM Manual for proper interconnecting refrigerant line sizing.) Refrigerant: Suction, (Qty.) 5/8" OD, (1) 3/4" OD, (1) 3/4" OD, (1) 3/4" OD (1) 7/8" OD (1) 7/8" OD (1) 7/8" OD (1) Liquid Line, (Qty.) 3/8" OD, (1) 3/8" OD, (1) 3/8" OD, (1) 1/2" OD (1) 1/2" OD (1) 1/2" OD (1) 1/2" OD (1) Condensate Drain 7/8" OD 7/8" OD 7/8" OD 7/8" OD 7/8" OD 3/4" FPT 3/4" FPT Humidifier Inlet 1/4" OD 1/4" OD 1/4" OD 1/4" OD 1/4" OD 1/4" OD 1/4" OD 120 lbs 155 lbs 165 lbs 270 lbs 280 lbs Physical Size - (Please refer to Section 6 for detailed dimensional data.) Approx. Wt. 120 lbs 120 lbs Please refer to the SATS Heat Rejection Engineering Manual for specification and performance data on Remote Outdoor and Indoor Air Cooled Condensers 4-5 Air Technology Systems, Inc. Air Cooled DAHU/DRCU - 4 to 10 Ton "OHS" (Dual) ( )-048-DAHU ( )-072-DAHU ( )-084-DAHU ( )-120-DAHU NET DX COOLING CAPACITY - BTU/H, (includes standard DX evaporator motor heat @ std CFM & e.s.p. ratings) 80°FDB/67°FWB, 50% RH Total 53,740 73,870 92,065 130,435 Sensible 40,860 62,110 71,070 98,030 75°FDB/62.5°FWB, 50% RH Total 49,250 67,550 83,980 119,590 Sensible 40,290 61,525 70,840 96,230 Total 46,950 64,275 79,760 113,380 Sensible 39,480 60,215 69,565 94,580 72°FDB/60°FWB, 50% RH 80°FDB/65°FWB, 45% RH 51,610 70,730 87,660 124,890 44,310 68,085 79,060 106,480 Total 47,860 65,590 80,770 115,540 Sensible 42,830 64,070 76,215 102,850 Total 45,620 62,750 76,660 109,955 Sensible 42,040 61,910 73,710 100,920 75°FDB/61°FWB, 45% RH 72°FDB/58.5°FWB, 45% RH Reheat/Heat - Performance Capacities Include Motor Heat, (Optional) ELECTRIC REHEAT / HEAT - BTU/H (Kw) @ 208V/460V 36,810 (10.9) 38,900 (11.4) 40,510 (11.9) 43,580 (12.8) @ 230V 42,600 (12.5) 44,690 (13.1) 46,300 (13.6) 49,370 (14.5) @ 480V 38,295 (11.2) 40,385 (11.8) 41,995 (12.3) 45,065 (13.2) 130,500 HOT WATER REHEAT / HEAT - Reheat rated @ 180°F Entering Water Temperature, EAT = 72°F DB BTU/H 50,360 97,880 99,830 GPM 3 3 3 10 0.3 0.3 0.3 2.2 Motorized Motorized Motorized Motorized 120,000 Pressure Drop, ft. wg Control STEAM REHEAT / HEAT - nominally Reheat rated @ 5 psig Steam, EAT = 72°F DB BTU/H (nominal) 48,000 72,000 90,000 50 75 94 125 Motorized Motorized Motorized Motorized Condensate (lbs/hr) Control Humidification - Electrode Steam Canister Humidifier with Adjustable Output, (Optional) Lbs/Hr, (Kw Input) Std Control 4-10, (3.4) 4-15, (5.1) 4-15, (5.1) 4-15, (5.1) Cycling Cycling Cycling Cycling Evaporator Blower / Motor - DWDI Centrifugal - Belt Driven, Variable Pitch Pulleys Horsepower CFM @ ext. st. press. Drive Method 3/4 Hp 1-1/2 Hp 2 Hp 3 Hp 1,800 @ 0.5" 3,000 @ 0.5" 3,350 @ 0.5" 4,400 @ 0.5" Belt Driven Belt Driven Belt Driven Belt Driven 3/ 4.1 4/ 6.7 4/ 6.7 4/ 10.0 16x20, (2) 20x20, (2) 20x20, (2) 24x24, (2) Evaporator Coil - Aluminum Fin, Copper Tube Rows/Face Area (Ft2) Filters - 1" deep throwaway Nominal Size (in.), (Qty.) Connection Sizes - Copper, (Please refer to CeilAiR IOM Manual for proper interconnecting refrigerant line sizing.) Refrigerant: Suction Line, (Qty.) 3/4" OD, (2) 7/8" OD, (2) 7/8" OD, (2) 7/8" OD, (2) Liquid Line, (Qty.) 3/8" OD, (2) 1/2" OD, (2) 1/2" OD, (2) 1/2" OD, (2) 3/4" FPT, (1/2"OD) 3/4" FPT, (1/2"OD) 3/4" FPT, (1/2"OD) 3/4" FPT, (1/2"OD) 1/4" OD 1/4" OD 1/4" OD 1/4" OD 350 lbs 410 lbs 480 lbs Condensate Drain, (w/ In-Pan Pump) Humidifier Inlet Physical Size - (Please refer to Section 6 for detailed dimensional data.) Approx. Weight 320 lbs - Air Cooled DAHU/DRCU (4-10 Ton, DUAL Compressor) Total Sensible Performance Data OHS Model Please refer to the SATS Heat Rejection Engineering Manual for specification and performance data on Remote Outdoor and Indoor Air Cooled Condensing Units Air Technology Systems, Inc. 4-6 Water Cooled Performance Data OHS Model ( )-012-W 1 to 5 Ton "OHS" ( )-018-W ( )-024-W ( )-032-W ( )-040-W ( )-048-W ( )-060-W NET DX COOLING CAPACITY - BTU/H, (includes standard DX evaporator motor heat @ std CFM & e.s.p. ratings) 80°FDB/67°FWB, 50% RH Total 16,394 21,125 27,990 35,550 39,115 64,250 70,665 Sensible 11,675 16,000 20,455 24,575 29,500 49,240 54,100 Total 14,850 19,345 25,750 32,700 35,830 58,820 64,690 Sensible 11,340 15,625 20,100 24,265 28,800 48,580 53,445 Total 14,000 18,380 24,560 31,150 34,109 56,070 61,650 Sensible 11,050 16,400 19,680 23,775 28,093 47,600 52,345 Total 15,570 20,430 26,840 34,170 37,355 61,635 67,730 Sensible 12,440 17,645 21,825 26,300 31,600 53,560 58,955 Total 14,380 18,950 24,920 31,600 35,120 57,130 62,760 Sensible 12,250 17,040 21,075 25,360 30,560 51,780 56,975 Total 13,620 18,065 23,685 30,060 33,460 54,460 59,795 Sensible 12,010 16,710 20,700 24,820 30,470 50,820 55,910 75°FDB/62.5°FWB, 50% RH 72°FDB/60°FWB, 50% RH 80°FDB/65°FWB, 45% RH 75°FDB/61°FWB, 45% RH 72°FDB/58.5°FWB, 45% RH Reheat/Heat - Performance Capacities Include Motor Heat, (Optional) ELECTRIC REHEAT / HEAT - BTU/H (Kw) - Water Cooled (1 to 5 Ton Systems) @ 208V 17,135 (5.0) 17,135 (5.0) 17,135 (5.0) 17,425 (5.1) 17,955 (5.3) 37,350 (10.9) 38,900 (11.4) @ 230V 18,840 (5.5) 18,840 (5.5) 18,840 (5.5) 19,130 (5.6) 19,660 (5.8) 43,140 (12.6) 44,690 (13.1) @ 460V 17,355 (5.1) 17,355 (5.1) 17,355 (5.1) 17,645 (5.2) 18,175 (5.3) 37,350 (10.9) 38,900 (11.4) @ 277/480V 18,065 (5.3) 18,065 (5.3) 18,065 (5.3) 18,355 (5.4) 18,885 (5.5) 38,835 (11.4) 40,385 (11.8) 12,440 17,690 22,150 27,045 32,425 51,010 56,120 HOT GAS REHEAT BTU/H HOT WATER REHEAT / HEAT - Reheat rated @ 180°F Entering Water Temperature, EAT = 72°F DB Air Technology Systems, Inc BTU/H 20,690 32,420 34,880 50,360 55,320 97,140 GPM 1 2 2 3 3 4 5 0.1 0.3 0.3 0.3 0.3 0.4 0.6 Motorized Motorized Motorized Motorized Motorized Motorized Motorized 60,000 Pressure Drop, ft. wg Control 111,220 STEAM REHEAT / HEAT - nominally Reheat rated @ 5 psig Steam, EAT = 72°F DB BTU/H (nominal) Condensate (lb/hr) Control 12,000 18,000 24,000 32,000 40,000 48,000 13 19 25 34 42 50 63 Motorized Motorized Motorized Motorized Motorized Motorized Motorized Humidification - Electrode Steam Canister Humidifier with Adjustable Output, (Optional) Lbs/Hr, (Kw Input) Std Control 2-5, (1.7) 2-5, (1.7) 2-5, (1.7) 2-5, (1.7) 2-5, (1.7) 4-10, (3.4) 4-10, (3.4) Cycling Cycling Cycling Cycling Cycling Cycling Cycling Evaporator Blower / Motor - DWDI Centrifugal 1/4 Hp 1/4 Hp 1/4 Hp 1/3 Hp 1/2 Hp 1 Hp 1-1/2 Hp CFM @ ext. st. press. Horsepower 500 @ 0.3" 750 @ 0.3" 900 @ 0.3" 1,000 @ 0.3" 1,415 @ 0.3" 2,200 @ 0.5" 2,500 @ 0.5" Std. Drive Method Direct Driven Direct Driven Direct Driven Direct Driven Direct Driven Belt Driven Belt Driven Opt. Drive Method Belt-Driven Belt-Driven Belt-Driven Belt-Driven Belt-Driven N/A N/A 3/ 2.1 3/ 2.1 3/ 2.8 3/ 2.8 4/ 5.0 4/ 5.0 Evaporator Coil - Aluminum Fin, Copper Tube Rows/Face Area (Ft2) 3/ 2.1 Compressor - Heat pump duty rated, HCFC Ozone Safe R-22 Type, (Qty.) Recip., (1) Scroll, (1) Scroll, (1) Scroll, (1) Scroll, (1) Scroll, (1) Scroll, (1) Watts Input 1,245 1,239 1,633 2,118 2,222 3,451 3,867 Water Cooled Condenser Data - Based on 0% glycol solution Tot Heat of Reject. 18,900 Btu/h 24,350 Btu/h 32,145 Btu/h 41,325 Btu/h 44,865 Btu/h 70,600 Btu/h 77,890 Btu/h GPM @ 85°F EWT 3.8 GPM 4.9 GPM 6.4 GPM 8.3 GPM 9.0 GPM 14.1 GPM 15.6 GPM Total Unit PD (Ft. of H2O) 10.0 Ft. 6.5 Ft. 11.0 Ft. 11.7 Ft. 13.9 Ft. 16.5 Ft. 22.7 Ft. Type Coaxial Coaxial Coaxial Coaxial Coaxial Coaxial Coaxial 3/4" FPT Head Pressure Control Standard Control - 2-way, 150 psig Water Regulating Valve, (factory installed) Optional Control - Refer to the Optional Guide Specifications Section for High Pressure and 3-way Valve Options! Connection Sizes - Copper Condensate Drain 7/8" OD 7/8" OD 7/8" OD 7/8" OD 7/8" OD 3/4" FPT Humidifier Inlet 1/4" OD 1/4" OD 1/4" OD 1/4" OD 1/4" OD 1/4" OD 1/4" OD Source Water In/Out 5/8" OD 7/8" OD 7/8" OD 7/8" OD 7/8" OD 1-1/8" OD 1-1/8" OD 20x20 (1) 20x20, (1) 20x20, (1) 20x20, (1) 20x20, (1) 20x16, (2) 20x16, (2) 210 lbs 245 lbs 260 lbs 395 lbs 405 lbs Filters - 1" deep throwaway Nom. Size (in.), (Qty.) Physical Size - (Please refer to Section 6 for detailed dimensional data.) Approx. Weight 180 lbs 200 lbs Please refer to the SATS Heat Rejection Engineering Manual for specification and performance data on Remote Outdoor and Indoor Air Cooled Condensing Units 4-7 Air Technology Systems, Inc. Water Cooled - OHS-048-DW OHS-072-DW OHS-084-DW OHS-120-DW NET DX COOLING CAPACITY - BTU/H, (includes standard DX evaporator motor heat @ std CFM & e.s.p. ratings) 80°FDB/67°FWB, 50% RH Total 57,200 79,165 98,760 139,210 Sensible 42,320 63,770 73,735 101,715 Total 52,580 72,510 90,475 127,660 Sensible 41,620 63,225 72,760 100,040 75°FDB/62.5°FWB, 50% RH 72°FDB/60°FWB, 50% RH Total 50,100 69,035 86,090 121,610 Sensible 40,820 62,045 71,400 98,010 80°FDB/65°FWB, 45% RH Total 54,890 75,840 94,300 133,265 Sensible 45,740 70,425 81,160 110,080 Total 50,960 70,200 87,050 123,460 Sensible 44,180 67,685 78,670 106,285 75°FDB/61°FWB, 45% RH 72°FDB/58.5°FWB, 45% RH Total 48,620 66,785 82,760 117,645 Sensible 43,390 65,220 77,320 104,340 Performance Data OHS Model 4 to 10 Ton "OHS" (Dual) Reheat/Heat - Performance Capacities Include Motor Heat, (Optional) @ 208V/460V 36,810 (10.9) 38,900 (11.4) 40,510 (11.9) 43,580 (12.8) @ 230V 42,600 (12.5) 44,690 (13.1) 46,300 (13.6) 49,370 (14.5) @ 480V 38,295 (11.2) 40,385 (11.8) 41,995 (12.3) 45,065 (13.2) 21,850 33,195 38,200 52,520 130,500 HOT GAS REHEAT BTU/H HOT WATER REHEAT / HEAT - Reheat rated @ 180°F Entering Water Temperature, EAT = 72°F DB BTU/H 50,360 97,880 99,830 GPM 3 3 3 10 0.3 0.3 0.3 2.2 Motorized Motorized Motorized Motorized 48,000 72,000 90,000 120,000 50 75 94 125 Motorized Motorized Motorized Motorized 4-10, (3.4) 4-15, (5.1) 4-15, (5.1) 4-15, (5.1) Cycling Cycling Cycling Cycling Pressure Drop, ft. wg Control STEAM REHEAT / HEAT - nominally Reheat rated @ 5 psig Steam, EAT = 72°F DB BTU/H (nominal) Condensate (lbs/hr) Control Humidification - Electrode Steam Canister Humidifier with Adjustable Output, (Optional) Lbs/Hr, (Kw Input) Std Control Evaporator Blower / Motor - DWDI Centrifugal - Belt Driven, Variable Pitch Pulleys Horsepower 3/4 Hp 1-1/2 Hp 2 Hp 3 Hp 1,800 @ 0.5" 3,000 @ 0.5" 3,350 @ 0.5" 4,400 @ 0.5" Belt Driven Belt Driven Belt Driven Belt Driven 3/ 4.1 4/ 6.7 4/ 6.7 4/ 10.0 Scroll, (2) Scroll, (2) Scroll, (2) Scroll, (2) 1,603 2,182 2,973 3,867 63,525 Btu/h 87,405 Btu/h 110,770 Btu/h 154,060 Btu/h 12.7 GPM 17.5 GPM 22.2 GPM 30.8 GPM Total Unit Pressure Drop (Ft. of H2O) 12.4 Ft. 17.9 Ft. 12.4 Ft. 25.7 Ft. Type Coaxial Coaxial Coaxial Coaxial 3/4" FPT, (1/2"OD) CFM @ ext. st. press. Drive Method Evaporator Coil - Aluminum Fin, Copper Tube Rows/Face Area (Ft2) Compressor - Heat pump duty rated, HCFC Ozone Safe R-22 Type, (Qty.) Watt Input (per compressor) Water Cooled Condenser Data - Based on 0% glycol solution Total Heat of Reject. GPM @ 85°F EWT - Water Cooled (4 to 10 Ton Systems) ELECTRIC REHEAT / HEAT - BTU/H (Kw) Head Pressure Control Standard Control - 2-way, 150 psig Water Regulating Valve, (factory installed) Optional Control - Refer to the Optional Guide Specifications Section for High Pressure and 3-way Valve Options! Connection Sizes - Copper Condensate Drain, (w/ In-Pan Pump) Humidifier Inlet Source Water Inlet/Outlet 3/4" FPT, (1/2"OD) 3/4" FPT, (1/2"OD) 3/4" FPT, (1/2"OD) 1/4" OD 1/4" OD 1/4" OD 1/4" OD 1-1/8" OD 1-1/8" OD 1-3/8" OD 1-3/8" OD 16x20, (2) 20x20, (2) 20x20, (2) 24x24, (2) 470 lbs 550 lbs 625 lbs Filters - 1" deep throwaway Nominal Size (in.), (Qty.) Physical Size - (Please refer to Section 6 for detailed dimensional data.) Approx. Weight 440 lbs Air Technology Systems, Inc. 4-8 Glycol Cooled Performance Data OHS Model ( )-012-G 1 to 5 Ton "OHS" ( )-018-G ( )-024-G ( )-032-G ( )-040-G ( )-048-G ( )-060-G NET DX COOLING CAPACITY - BTU/H, (includes standard DX evaporator motor heat @ std CFM & e.s.p. ratings) 80°FDB/67°FWB, 50% RH Total 13,390 18,960 25,090 32,000 34,910 57,150 62,670 Sensible 10,435 15,060 19,160 23,085 27,500 46,565 51,120 Total 12,200 17,541 22,975 28,175 31,855 52,325 57,335 Sensible 10,450 15,194 18,710 23,700 26,975 45,920 50,410 Total 11,510 16,720 21,900 27,800 30,540 49,770 54,525 Sensible 10,210 14,880 18,275 22,045 26,455 44,970 49,370 Total 12,900 18,375 23,990 30,580 33,840 54,920 60,120 Sensible 11,650 16,800 20,535 24,540 30,475 51,075 56,140 Total 11,780 17,035 22,430 28,175 31,290 50,785 55,550 Sensible 11,171 16,200 20,195 23,700 29,270 49,080 53,900 Total 11,120 16,235 21,355 27,065 29,770 48,360 52,680 Sensible 10,875 15,855 19,760 23,375 28,610 47,710 51,930 75°FDB/62.5°FWB, 50% RH 72°FDB/60°FWB, 50% RH 80°FDB/65°FWB, 45% RH 75°FDB/61°FWB, 45% RH 72°FDB/58.5°FWB, 45% RH Reheat/Heat - Performance Capacities Include Motor Heat, (Optional) - Glycol Cooled (1 to 5 Ton Systems) ELECTRIC REHEAT / HEAT - BTU/H (Kw) @ 208V 17,135 (5.0) 17,135 (5.0) 17,135 (5.0) 17,425 (5.1) 17,955 (5.3) 37,350 (10.9) 38,900 (11.4) @ 230V 18,840 (5.5) 18,840 (5.5) 18,840 (5.5) 19,130 (5.6) 19,660 (5.8) 43,140 (12.6) 44,690 (13.1) @ 460V 17,355 (5.1) 17,355 (5.1) 17,355 (5.1) 17,645 (5.2) 18,175 (5.3) 37,350 (10.9) 38,900 (11.4) @ 277/480V 18,065 (5.3) 18,065 (5.3) 18,065 (5.3) 18,355 (5.4) 18,885 (5.5) 38,835 (11.4) 40,385 (11.8) 11,290 16,845 20,895 25,295 30,555 48,220 52,930 HOT GAS REHEAT BTU/H Air Technology Systems, Inc HOT WATER REHEAT / HEAT - Reheat rated @ 180°F Entering Water Temperature, EAT = 72°F DB BTU/H 20,690 32,420 34,880 50,360 55,320 97,140 GPM 1 2 2 3 3 4 5 0.1 0.3 0.3 0.3 0.3 0.4 0.6 Motorized Motorized Motorized Motorized Motorized Motorized Motorized 60,000 Pressure Drop, ft. wg Control 111,220 STEAM REHEAT / HEAT - nominally Reheat rated @ 5 psig Steam, EAT = 72°F DB BTU/H (nominal) Condensate (lb/hr) Control 12,000 18,000 24,000 32,000 40,000 48,000 13 19 25 34 42 50 63 Motorized Motorized Motorized Motorized Motorized Motorized Motorized Humidification - Electrode Steam Canister Humidifier with Adjustable Output, (Optional) Lbs/Hr, (Kw Input) Std Control 2-5, (1.7) 2-5, (1.7) 2-5, (1.7) 2-5, (1.7) 2-5, (1.7) 4-10, (3.4) 4-10, (3.4) Cycling Cycling Cycling Cycling Cycling Cycling Cycling Evaporator Blower / Motor - DWDI Centrifugal 1/4 Hp 1/4 Hp 1/4 Hp 1/3 Hp 1/2 Hp 1 Hp 1-1/2 Hp CFM @ ext. st. press. Horsepower 500 @ 0.3" 750 @ 0.3" 900 @ 0.3" 1,000 @ 0.3" 1,415 @ 0.3" 2,200 @ 0.5" 2,500 @ 0.5" Std. Drive Method Direct Driven Direct Driven Direct Driven Direct Driven Direct Driven Belt Driven Belt Driven Opt. Drive Method Belt-Driven Belt-Driven Belt-Driven Belt-Driven Belt-Driven N/A N/A 3/ 2.1 3/ 2.1 3/ 2.8 3/ 2.8 4/ 5.0 4/ 5.0 Evaporator Coil - Aluminum Fin, Copper Tube Rows/Face Area (Ft2) 3/ 2.1 Compressor - Heat pump duty rated, HCFC Ozone Safe R-22 Type, (Qty.) Recip., (1) Scroll, (1) Scroll, (1) Scroll, (1) Scroll, (1) Scroll, (1) Scroll, (1) Watts Input 1,442 1,729 2,227 2,882 3,027 4,699 5,290 Glycol Condenser Data - Based on 40% ethylene glycol solution Tot. Heat of Reject. 17,270 Btu/h 23,990 Btu/h 31,305 Btu/h 40,340 Btu/h 43,625 Btu/h 68,360 Btu/h 75,390 Btu/h GPM @ 110°F EGT 3.8 GPM 5.3 GPM 6.9 GPM 8.9 GPM 9.7 GPM 15.1 GPM 16.7 GPM Total Unit PD (Ft. of H2O) 10.1 Ft. 7.0 Ft. 11.8 Ft. 12.8 Ft. 15.2 Ft. 18.0 Ft. 24.5 Ft. Type Coaxial Coaxial Coaxial Coaxial Coaxial Coaxial Coaxial 3/4" FPT Head Pressure Control Standard Control - 2-way, 150 psig Glycol Regulating Valve, (factory installed) Optional Control - Refer to the Optional Guide Specifications Section for High Pressure and 3-way Valve Options! Connection Sizes - Copper Condensate Drain 7/8" OD 7/8" OD 7/8" OD 7/8" OD 7/8" OD 3/4" FPT Humidifier Inlet 1/4" OD 1/4" OD 1/4" OD 1/4" OD 1/4" OD 1/4" OD 1/4" OD Source Glycol In/Out 5/8" OD 7/8" OD 7/8" OD 7/8" OD 7/8" OD 1-1/8" OD 1-1/8" OD 20x20, (1) 20x20, (1) 20x20, (1) 20x20, (1) 20x20, (1) 20x16, (2) 20x16, (2) 210 lbs 245 lbs 260 lbs 395 lbs 405 lbs Filters - 1" deep throwaway Nom. Size (in.), (Qty.) Physical Size - (Please refer to Section 6 for detailed dimensional data.) Approx. Weight 4-9 180 lbs 200 lbs Air Technology Systems, Inc. Glycol Cooled OHS-048-DG OHS-072-DG OHS-084-DG OHS-120-DG NET DX COOLING CAPACITY - BTU/H, (includes standard DX evaporator motor heat @ std CFM & e.s.p. ratings) 80°FDB/67°FWB, 50% RH Total 51,260 70,230 87,445 123,970 Sensible 39,730 61,010 69,465 95,280 75°FDB/62.5°FWB, 50% RH Total 46,840 64,090 79,565 113,045 Sensible 39,230 60,180 69,420 93,920 72°FDB/60°FWB, 50% RH Total 44,600 60,990 75,580 107,490 Sensible 38,400 58,520 68,115 91,925 80°FDB/65°FWB, 45% RH Total 49,150 67,340 83,055 118,680 Sensible 43,340 65,360 77,390 104,065 75°FDB/61°FWB, 45% RH Total 45,500 62,635 76,640 109,590 Sensible 41,840 61,750 73,350 100,420 Total 43,320 59,880 73,150 104,185 Sensible 41,000 59,635 71,130 98,400 72°FDB/58.5°FWB, 45% RH Performance Data OHS Model 4 to 10 Ton "OHS" (Dual) Reheat/Heat - Performance Capacities Include Motor Heat, (Optional) @ 208V/460V 36,810 (10.9) 38,900 (11.4) 40,510 (11.9) 43,580 (12.8) @ 230V 42,600 (12.5) 44,690 (13.1) 46,300 (13.6) 49,370 (14.5) @ 480V 38,295 (11.2) 40,385 (11.8) 41,995 (12.3) 45,065 (13.2) 20,595 31,595 36,445 49,310 130,500 HOT GAS REHEAT BTU/H HOT WATER REHEAT / HEAT - Reheat rated @ 180°F Entering Water Temperature, EAT = 72°F DB BTU/H 50,360 97,880 99,830 GPM 3 3 3 10 0.3 0.3 0.3 2.2 Motorized Motorized Motorized Motorized 48,000 72,000 90,000 120,000 50 75 94 125 Motorized Motorized Motorized Motorized Pressure Drop, ft. wg Control STEAM REHEAT / HEAT - nominally Reheat rated @ 5 psig Steam, EAT = 72°F DB BTU/H (nominal) Condensate (lbs/hr) Control Humidification - Electrode Steam Canister Humidifier with Adjustable Output, (Optional) Lbs/Hr, (Kw Input) Std Control 4-10, (3.4) 4-15, (5.1) 4-15, (5.1) 4-15, (5.1) Cycling Cycling Cycling Cycling Evaporator Blower / Motor - DWDI Centrifugal - Belt Driven, Variable Pitch Pulleys Horsepower 3/4 Hp 1-1/2 Hp 2 Hp 3 Hp 1,800 @ 0.5" 3,000 @ 0.5" 3,350 @ 0.5" 4,400 @ 0.5" Belt Driven Belt Driven Belt Driven Belt Driven 3/ 4.1 4/ 6.7 4/ 6.7 4/ 10.0 Scroll, (2) Scroll, (2) Scroll, (2) Scroll, (2) 2,188 2,973 4,103 5,290 61,775 Btu/h 84,385 Btu/h 107,570 Btu/h 149,155 Btu/h 13.7 GPM 18.7 GPM 23.8 GPM 33.0 GPM Total Unit Pressure Drop (Ft. of H2O) 13.6 Ft. 20.0 Ft. 13.9 Ft. 28.1 Ft. Type Coaxial Coaxial Coaxial Coaxial 3/4" FPT, (1/2"OD) CFM @ ext. st. press. Drive Method Evaporator Coil - Aluminum Fin, Copper Tube Rows/Face Area (Ft2) Compressor - Heat pump duty rated, HCFC Ozone Safe R-22 Type, (Qty.) Watt Input (per compressor) Glycol Condenser Data - Based on 40% ethylene glycol solution Total Heat of Rejection GPM @ 110°F EGT - Glycol Cooled (4 to 10 Ton Systems) ELECTRIC REHEAT / HEAT - BTU/H (Kw) Head Pressure Control Standard Control - 2-way, 150 psig Glycol Regulating Valves, (factory installed) Optional Control - Refer to the Optional Guide Specifications Section for High Pressure and 3-way Valve Options! Connection Sizes - Copper Condensate Drain, (w/ In-Pan Pump) Humidifier Inlet Source Glycol Inlet/Outlet 3/4" FPT, (1/2"OD) 3/4" FPT, (1/2"OD) 3/4" FPT, (1/2"OD) 1/4" OD 1/4" OD 1/4" OD 1/4" OD 1-1/8" OD 1-1/8" OD 1-3/8" OD 1-3/8" OD 16x20, (2) 20x20, (2) 20x20, (2) 24x24, (2) 470 lbs 550 lbs 625 lbs Filters - 1" deep throwaway Nominal Size (in.), (Qty.) Physical Size - (Please refer to Section 6 for detailed dimensional data.) Approx. Weight 440 lbs Air Technology Systems, Inc. 4-10 Chilled Water Performance Data OHS Model - 1 to 3 Tons "OHS" OHS-012-C OHS-018-C OHS-024-C OHS-032-C OHS-040-C 51,990 COOLING CAPACITY - BTU/H @ 45°F EWT, 0% Glycol Solution (@ std CFM & e.s.p. ratings) 80°FDB/67°FWB, 50% RH High Flow Total 22,970 31,090 35,410 40,800 (8°F ∆Tw) Sens. 15,340 21,440 24,820 28,730 37,670 5.8 / (19.6) 7.8 / (34.0) 8.8 / (43.1) 10.2 / (23.3) 13.0 / (36.8) 48,680 GPM / (pd. Ft.) Med. Flow Total 21,200 29,050 33,090 38,030 (10°F ∆Tw) Sens. 14,560 20,520 23,770 27,430 36,100 4.3 / (11.2) 5.8 / (19.8) 6.6 / (25.1) 7.6 / (13.6) 9.7 / (21.5) 45,440 GPM / (pd. Ft.) Low Flow Total 19,390 26,830 30,910 34,950 (12°F ∆Tw) Sens. 13,760 19,530 22,770 25,990 34,520 3.3 / (6.8) 4.5 / (12.2) 5.2 / (15.8) 5.8 / (8.3) 7.6 / (13.4) 38,890 GPM / (pd. Ft.) 75°FDB/62.5°FWB, 50% RH High Flow Total 16,460 22,840 26,110 30,170 (8°F ∆Tw) Sens. 13,000 18,510 21,500 24,720 32,720 4.2 / (10.7) 5.7 / (19.4) 6.5 / (24.6) 7.6 / (13.4) 9.7 / (21.5) 36,190 GPM / (pd. Ft.) Med. Flow Total 15,110 21,080 24,380 27,720 (10°F ∆Tw) Sens. 12,340 17,610 20,590 23,420 31,210 3.1 / (6.0) 4.2 / (11.1) 4.9 / (14.5) 5.6 / (7.6) 7.3 / (12.5) 33,310 GPM / (pd. Ft.) - Chilled Water (1-3 ton) Systems Low Flow Total 13,840 19,420 22,490 25,470 (12°F ∆Tw) Sens. 11,690 16,700 19,510 22,170 29,510 2.3 / (3.7) 3.3 / (6.8) 3.8 / (8.9) 4.3 / (4.7) 5.6 / (7.6) 32,490 GPM / (pd. Ft.) 72°FDB/60°FWB, 50% RH High Flow Total 13,510 18,810 21,750 24,930 (8°F ∆Tw) Sens. 11,700 16,680 19,500 22,240 29,600 3.4 / (7.5) 4.7 / (13.6) 5.5 / (17.8) 6.3 / (9.5) 8.1 / (15.4) 29,590 GPM / (pd. Ft.) Med. Flow Total 12,390 17,240 19,910 22,830 (10°F ∆Tw) Sens. 11,080 15,740 18,360 20,970 27,750 2.5 / (4.2) 3.5 / (7.7) 4.0 / (10.0) 4.6 / (5.4) 6.0 / (8.6) 25,970 Air Technology Systems, Inc GPM / (pd. Ft.) Low Flow Total 11,120 15,380 17,680 20,240 (12°F ∆Tw) Sens. 10,300 14,520 16,850 19,280 25,270 1.9 / (2.2) 2.6 / (4.5) 3.0 / (5.7) 3.4 / (3.1) 4.4 / (4.9) 47,370 GPM / (pd. Ft.) 80°FDB/65°FWB, 45% RH High Flow Total 20,300 27,780 31,800 36,940 (8°F ∆Tw) Sens. 15,640 22,090 25,710 29,660 39,180 5.1 / (15.7) 6.9 / (27.5) 8.0 / (35.4) 9.2 / (19.5) 11.8 / (30.8) 44,850 GPM / (pd. Ft.) Med. Flow Total 18,880 26,180 30,070 34,620 (10°F ∆Tw) Sens. 14,970 21,310 24,830 28,480 37,830 3.8 / (9.1) 5.2 / (16.3) 6.0 / (21.1) 6.9 / (11.5) 9.0 / (18.5) 42,110 GPM / (pd. Ft.) Low Flow Total 17,570 24,520 28,250 32,270 (12°F ∆Tw) Sens. 14,340 20,460 23,870 27,250 36,300 2.9 / (5.7) 4.1 / (10.4) 4.7 / (13.4) 5.4 / (7.2) 7.0 / (11.7) 36,630 GPM / (pd. Ft.) 75°FDB/61°FWB, 45% RH High Flow Total 15,230 21,220 24,400 28,210 (8°F ∆Tw) Sens. 13,420 19,160 22,330 25,550 33,970 3.8 / (9.3) 5.4 / (17.0) 6.1 / (21.9) 7.0 / (11.8) 9.2 / (19.3) 33,910 GPM / (pd. Ft.) Med. Flow Total 14,210 19,750 22,720 26,220 (10°F ∆Tw) Sens. 12,850 18,270 21,260 24,340 32,200 2.9 / (5.4) 4.0 / (9.9) 4.6 / (12.7) 5.3 / (6.9) 6.8 / (11.0) 27,460 GPM / (pd. Ft.) Low Flow Total 13,040 17,980 20,610 23,830 (12°F ∆Tw) Sens. 12,130 17,110 19,850 22,790 27,460 2.2 / (3.2) 3.0 / (5.9) 3.5 / (7.6) 4.0 / (4.2) 4.6 / (5.4) 28,360 GPM / (pd. Ft.) 72°FDB/58.5°FWB, 45% RH High Flow Total 12,650 17,360 19,380 23,310 (8°F ∆Tw) Sens. 12,140 17,120 19,380 22,900 28,360 3.2 / (6.6) 4.4 / (11.8) 4.9 / (14.4) 5.9 / (8.5) 7.1 / (12.1) 25,700 GPM / (pd. Ft.) Med. Flow Total 10,780 15,310 17,820 19,440 (10°F ∆Tw) Sens. 10,780 15,310 17,820 19,440 25,700 2.2 / (3.1) 3.1 / (6.2) 3.6 / (8.1) 3.9 / (4.0) 5.2 / (6.7) 22,870 GPM / (pd. Ft.) Low Flow Total 9,740 13,810 16,080 17,240 (12°F ∆Tw) Sens. 9,740 13,810 16,080 17,240 22,870 1.7 / (1.6) 2.3 / (3.7) 2.7 / (4.8) 2.9 / (2.1) 3.9 / (3.9) GPM / (pd. Ft.) 4-11 Air Technology Systems, Inc. Chilled Water OHS-012-C OHS-018-C OHS-024-C OHS-032-C OHS-040-C Chilled Water Control Valve - Sized for Medium Flow @ 75°FDB/62.5°FWB EAT Conditions 2-way (standard) - Spring Actuated (Open/Close) Size / (Cv) Valve Pressure Rating Total Unit Pressure Drop 1/2" / (3.5 Cv) 3/4" / (3.5 Cv) 3/4" / (3.7 Cv) 3/4" / (3.7 Cv) 3/4" / (3.7 Cv) 300 psig 300 psig 300 psig 300 psig 300 psig 8.0 Ft. 14.6 Ft. 19.4 Ft. 14.2 Ft. 22.6 Ft. 1/2" / (5.0 Cv) 3/4" / (5.0 Cv) 3/4" / (5.0 Cv) 3/4" / (5.0 Cv) 3/4" / (5.0 Cv) 300 psig 300 psig 300 psig 300 psig 300 psig 7.1 Ft. 12.9 Ft. 17.0 Ft. 11.2 Ft. 17.5 Ft. 4 / 2.1 4 / 2.1 4 / 2.8 4 / 2.8 3-way (optional) - Spring Actuated (Open/Close) Size / (Cv) Valve Pressure Rating Total Unit Pressure Drop Chilled Water Coil - Aluminum Fin, Copper Tube Rows/Face Area (Ft2) 4 / 2.1 Evaporator Blower / Motor - DWDI Centrifugal Horsepower 1/4 Hp 1/4 Hp 1/3 Hp 1/2 Hp 500 @ 0.3" 750 @ 0.3" 900 @ 0.3" 1,000 @ 0.3" 1,415 @ 0.3" Std. Drive Method Direct Driven Direct Driven Direct Driven Direct Driven Direct Driven Opt. Drive Method Belt-Driven Belt-Driven Belt-Driven Belt-Driven Belt-Driven Reheat/Heat - Performance Capacities Include Motor Heat, (Optional) ELECTRIC REHEAT / HEAT - BTU/H (Kw) @ 208V 17,135 (5.0) 17,135 (5.0) 17,135 (5.0) 17,425 (5.1) 17,955 (5.3) @ 230V 18,840 (5.5) 18,840 (5.5) 18,840 (5.5) 19,130 (5.6) 19,660 (5.8) @ 460V 17,355 (5.1) 17,355 (5.1) 17,355 (5.1) 17,645 (5.2) 18,175 (5.3) @ 277/480V 18,065 (5.3) 18,065 (5.3) 18,065 (5.3) 18,355 (5.4) 18,885 (5.5) 50,360 55,320 HOT WATER REHEAT / HEAT - Reheat rated @ 180°F Entering Water Temperature, EAT = 72°F DB BTU/H GPM Pressure Drop, ft. wg Control 20,690 32,420 34,880 1 2 2 3 3 0.1 0.3 0.3 0.3 0.3 Motorized Motorized Motorized Motorized Motorized STEAM REHEAT / HEAT - nominally Reheat rated @ 5 psig Steam, EAT = 72°F DB BTU/H (nominal) Condensate (lb/hr) Control 12,000 18,000 24,000 32,000 40,000 13 19 25 34 42 Motorized Motorized Motorized Motorized Motorized Humidification - Electrode Steam Canister Humidifier with Adjustable Output, (Optional) Lbs/Hr, (Kw Input) Std Control 2-5, (1.7) 2-5, (1.7) 2-5, (1.7) 2-5, (1.7) 2-5, (1.7) Cycling Cycling Cycling Cycling Cycling 20x20, (1) 20x20, (1) 20x20, (1) 20x20, (1) 20x20, (1) 7/8" OD 7/8" OD 7/8" OD 7/8" OD 7/8" OD Filters - 1" deep throwaway Nom. Size (in.), (Qty.) - Chilled Water (1-3 ton) Systems 1/4 Hp CFM @ ext. st. press. Performance Data OHS Model - 1 to 3 Tons "OHS" Connection Sizes - Copper Condensate Drain Humidifier Inlet 1/4" OD 1/4" OD 1/4" OD 1/4" OD 1/4" OD Chilled Water In/Out 5/8" OD 7/8" OD 7/8" OD 7/8" OD 7/8" OD 125 lbs 160 lbs 170 lbs Physical Size - (Please refer to Section 6 for detailed dimensional data.) Approx. Wt. 120 lbs 125 lbs Air Technology Systems, Inc. 4-12 Chilled Water Performance Data OHS Model OHS-048-C 4 to 10 Ton "OHS" OHS-060-C OHS-072-C OHS-084-C OHS-120-C 166,850 COOLING CAPACITY - BTU/H @ 45°F EWT, 0% Glycol Solution (@ std CFM & e.s.p. ratings) 80°FDB/67°FWB, 50% RH High Flow Total 83,770 91,130 134,100 144,440 (8°F ∆Tw) Sensible 59,280 65,250 90,760 98,710 117,880 20.9 / (18.6) 22.8 / (21.9) 33.5 / (46.3) 36.1 / (53.2) 41.8 / (18.6) 154,030 GPM / (pd. Ft.) Med. Flow Total 77,350 84,830 125,560 135,080 (10°F ∆Tw) Sensible 56,410 62,390 87,010 94,600 112,150 15.5 / (10.7) 17.1 / (12.7) 25.2 / (27.5) 27.1 / (31.5) 31.0 / (10.7) 139,290 GPM / (pd. Ft.) Low Flow Total 69,980 77,170 117,370 126,560 (12°F ∆Tw) Sensible 53,070 58,870 83,420 90,820 105,460 11.7 / (6.4) 13.0 / (7.7) 19.6 / (17.4) 21.2 / (20.1) 23.4 / (6.4) 121,940 GPM / (pd. Ft.) 75°FDB/62.5°FWB, 50% RH High Flow Total 61,310 67,460 99,080 106,720 (8°F ∆Tw) Sensible 51,210 56,760 78,510 85,490 101,740 15.4 / (10.6) 17.0 / (12.7) 24.8 / (26.9) 26.8 / (30.8) 30.8 / (10.6) 109,650 GPM / (pd. Ft.) Med. Flow Total 55,160 61,100 93,260 100,560 (10°F ∆Tw) Sensible 47,960 53,340 75,670 82,420 95,250 11.1 / (5.8) 12.4 / (7.1) 18.8 / (16.1) 20.3 / (18.5) 22.2 / (5.8) 97,640 GPM / (pd. Ft.) - Chilled Water (4-10 ton) Systems Low Flow Total 49,160 54,360 87,270 94,830 (12°F ∆Tw) Sensible 44,430 49,290 72,610 79,360 88,190 8.3 / (3.4) 9.2 / (4.1) 14.6 / (10.2) 15.9 / (11.9) 16.6 / (3.4) 99,540 GPM / (pd. Ft.) 72°FDB/60°FWB, 50% RH High Flow Total 50,110 55,070 83,050 89,560 (8°F ∆Tw) Sensible 45,920 50,810 71,570 77,990 91,150 12.6 / (7.4) 13.9 / (8.8) 20.9 / (19.6) 22.5 / (22.6) 25.2 / (7.4) 85,960 GPM / (pd. Ft.) Med. Flow Total 43,320 47,530 78,610 84,870 (10°F ∆Tw) Sensible 41,670 46,000 69,090 75,240 82,660 8.7 / (3.7) 9.6 / (4.5) 15.8 / (11.9) 17.2 / (13.7) 17.4 / (3.7) 67,580 Air Technology Systems, Inc GPM / (pd. Ft.) Low Flow Total 34,130 37,920 71,630 77,770 (12°F ∆Tw) Sensible 34,130 37,920 64,930 70,840 67,580 5.8 / (1.6) 6.4 / (2.1) 12.0 / (7.2) 13.1 / (8.4) 11.6 / (1.6) 150,470 GPM / (pd. Ft.) 80°FDB/65°FWB, 45% RH High Flow Total 75,570 82,490 120,390 130,020 (8°F ∆Tw) Sens. 61,670 68,110 93,640 102,180 122,660 18.9 / (15.5) 20.7 / (18.3) 30.2 / (38.4) 32.6 / (44.1) 37.8 / (15.5) 139,440 GPM / (pd. Ft.) Med. Flow Total 70,060 77,190 114,230 123,240 (10°F ∆Tw) Sens. 58,910 65,370 90,740 98,940 117,150 14.1 / (8.9) 15.5 / (10.7) 23.0 / (23.3) 24.8 / (26.7) 28.2 / (8.9) 128,090 GPM / (pd. Ft.) Low Flow Total 64,380 76,080 108,620 117,210 (12°F ∆Tw) Sens. 55,910 62,060 88,020 95,950 111,140 10.8 / (5.5) 11.9 / (6.6) 18.2 / (15.1) 19.6 / (17.4) 21.6 / (5.5) 113,800 GPM / (pd. Ft.) 75°FDB/61°FWB, 45% RH High Flow Total 57,240 62,820 93,130 100,510 (8°F ∆Tw) Sens. 53,140 58,810 81,850 89,260 105,610 14.4 / (9.4) 15.9 / (11.2) 23.4 / (24.1) 25.3 / (27.8) 28.8 / (9.4) 101,000 GPM / (pd. Ft.) Med. Flow Total 50,840 55,860 89,310 96,130 (10°F ∆Tw) Sens. 49,150 54,370 79,650 86,670 97,630 10.2 / (5.0) 11.3 / (6.0) 18.0 / (14.9) 19.4 / (17.2) 20.4 / (5.0) 83,850 GPM / (pd. Ft.) Low Flow Total 42,260 46,900 84,180 91,060 (12°F ∆Tw) Sens. 42,260 46,900 76,530 83,390 83,850 7.1 / (2.6) 7.9 / (3.1) 14.1 / (9.6) 15.3 / (11.1) 14.2 / (2.6) 89,130 GPM / (pd. Ft.) 72°FDB/58.5°FWB, 45% RH High Flow Total 44,900 49,650 79,680 85,280 (8°F ∆Tw) Sens. 44,900 49,650 75,350 81,670 89,130 11.3 / (6.0) 12.5 / (7.3) 20.0 / (18.2) 21.4 / (20.6) 22.6 / (6.0) 79,120 GPM / (pd. Ft.) Med. Flow Total 39,900 44,230 66,750 72,960 (10°F ∆Tw) Sens. 39,900 44,230 66,750 72,960 79,120 8.1 / (3.2) 9.0 / (3.9) 13.4 / (8.8) 14.8 / (10.5) 16.2 / (3.2) 67,330 GPM / (pd. Ft.) Low Flow Total 34,000 37,780 60,390 65,910 (12°F ∆Tw) Sens. 34,000 37,780 60,390 65,910 67,330 5.7 / (1.6) 6.4 / (2.0) 10.2 / (5.3) 11.1 / (6.3) 11.4 / (1.6) GPM / (pd. Ft.) 4-13 Air Technology Systems, Inc. Chilled Water OHS-048-C OHS-060-C OHS-072-C OHS-084-C OHS-120-C Chilled Water Control Valve - Sized for Medium Flow @ 75°FDB/62.5°FWB EAT Conditions 2-way (standard) - Spring Actuated (Open/Close) 1" / (8.0 Cv) 1" / (8.0 Cv) 1" / (14.0 Cv) 1" / (14.0 Cv) 1" / (14.0 Cv) Valve Pressure Rating Size / (Cv) 300 psig 300 psig 400 psig 400 psig 400 psig Total Unit Pressure Drop 10.4 Ft. 12.7 Ft. 20.7 Ft. 24.1 Ft. 12.5 Ft. 3-way (optional) - Spring Actuated (Open/Close) 1" / (7.0 Cv) 1" / (7.0 Cv) 1" / (14.0 Cv) 1" / (14.0 Cv) 1" / (14.0 Cv) Valve Pressure Rating Size / (Cv) 300 psig 300 psig 400 psig 400 psig 400 psig Total Unit Pressure Drop 11.8 Ft. 14.4 Ft. 20.7 Ft. 24.1 Ft. 12.5 Ft. 4/ 5.0 4/ 6.7 4/ 6.7 4/ 10.0 Chilled Water Coil - Aluminum Fin, Copper Tube Rows/Face Area (Ft2) 4/ 5.0 Evaporator Blower / Motor - DWDI Centrifugal - Belt Driven, Variable Pitch Pulleys Horsepower CFM @ ext. st. press. Drive Method 1-1/2 Hp 1-1/2 Hp 2 Hp 3 Hp 2,500 @ 0.5" 3,000 @ 0.5" 3,350 @ 0.5" 4,400 @ 0.5" Belt Driven Belt Driven Belt Driven Belt Driven Belt Driven 38,900 (11.4) 40,510 (11.9) 43,580 (12.8) Reheat/Heat - Performance Capacities Include Motor Heat, (Optional) ELECTRIC REHEAT / HEAT - BTU/H (Kw) @ 208V/460V 37,350 (10.9) 38,900 (11.4) @ 230V 43,140 (12.6) 44,690 (13.1) 44,690 (13.1) 46,300 (13.6) 49,370 (14.5) @ 480V 38,835 (11.4) 40,385 (11.8) 40,385 (11.8) 41,995 (12.3) 45,065 (13.2) 99,830 130,500 HOT WATER REHEAT / HEAT - Reheat rated @ 180°F Entering Water Temperature, EAT = 72°F DB BTU/H 97,140 111,220 97,880 GPM / Press. Drop (ft.wg) 4.0 / (0.4) 5.0 / (0.6) 3.0 / (0.3) 3.0 / (0.3) 10.0 / (2.2) Control Motorized Motorized Motorized Motorized Motorized 90,000 120,000 STEAM REHEAT / HEAT - nominally Reheat rated @ 5 psig Steam, EAT = 72°F DB BTU/H (nominal) Condensate (lb/hr) Control 48,000 60,000 72,000 50 63 75 94 125 Motorized Motorized Motorized Motorized Motorized Humidification - Electrode Steam Canister Humidifier with Adjustable Output, (Optional) Lbs/Hr, (Kw Input) Std Control 4-10, (3.4) 4-10, (3.4) 4-15, (5.1) 4-15, (5.1) 4-15, (5.1) Cycling Cycling Cycling Cycling Cycling 20x16, (2) 20x16, (2) 20x20, (2) 20x20, (2) 24x24, (2) Filters - 1" deep throwaway Nominal Size (in.), (Qty) Connection Sizes - Copper, (Water In/Out connections are sized for flow rates at 75°FDB/62.5°FWB EAT conditions.) Cond. Drain, (w/ In-Pan Pump) Humidifier Inlet Chilled Water In/Out 3/4" FPT, (1/2"OD) 3/4" FPT, (1/2"OD) 3/4" FPT, (1/2"OD) 3/4" FPT, (1/2"OD) 3/4" FPT, (1/2"OD) 1/4" OD 1/4" OD 1/4" OD 1/4" OD 1/4" OD 1-1/8" OD 1-1/8" OD 1-1/8" OD 1-1/8" OD 1-3/8" OD 365 lbs 415 lbs 495 lbs - Chilled Water (4-10 ton) Systems 1 Hp 2,200 @ 0.5" Performance Data OHS Model 4 to 10 Ton "OHS" Physical Size - (Please refer to Section 6 for detailed dimensional data.) Approx. Weight 280 lbs 290 lbs Air Technology Systems, Inc. 4-14 Chilled Water - 42°F Entering Water Temperature Cooling Capacities (BTU/H) for 42°F Chilled Water Entering the Cooling Coil 80°FDB/67°FWB OHS-012C OHS-018C OHS-024C OHS-032C OHS-040C OHS-048C OHS-060C OHS-072C OHS-084C OHS-120C High Flow Total 26,260 35,660 40,630 46,540 59,330 96,270 104,840 153,410 165,430 191,860 (8°F ∆Tw) Sensible 16,820 23,440 27,080 31,360 40,970 64,660 71,110 99,310 107,930 128,640 GPM/(Ft.) 6.6/(25.0) 8.9/(43.9) 10.1/(55.8) 11.6/(29.8) 14.8/(47.2) 24.0/(24.2) 26.2/(28.4) 38.3/(59.6) 41.3/(68.6) 42.0/(24.2) Med Flow Total 24,550 33,500 38,180 43,710 55,750 89,650 97,830 144,620 155,710 178,610 (10°F ∆Tw) Sensible 16,030 22,450 25,960 30,010 39,270 61,650 67,920 95,310 103,520 122,630 GPM/(Ft.) 4.9/(14.8) 6.7/(25.8) 7.6/(32.9) 8.7/(17.6) 11.1/(27.7) 17.9/(14.1) 19.6/(16.6) 28.9/(35.7) 31.2/(41.0) 35.8/(14.1) Low Flow Total 22,660 31,170 35,790 40,430 52,300 81,320 59,560 135,610 146,250 161,960 (12°F ∆Tw) Sensible 15,180 21,390 24,860 28,450 37,600 57,910 64,180 91,260 99,260 115,150 GPM/(Ft.) 3.8/(9.1) 5.2/(16.1) 6.0/(20.8) 6.7/(10.9) 8.7/(17.6) 13.6/(8.4) 15.0/(10.1) 22.6/(22.7) 24.5/(26.3) 27.2/(8.4) OHS-012C OHS-018C OHS-024C OHS-032C OHS-040C OHS-048C OHS-060C OHS-072C OHS-084C OHS-120C 75°FDB/62.5°FWB High Flow Total 19,450 26,760 30,590 35,200 45,190 72,100 79,070 115,660 124,650 143,530 (8°F ∆Tw) Sensible 14,380 20,310 23,570 27,140 35,750 56,180 62,130 86,120 93,710 111,680 Air Technology Systems, Inc GPM/(Ft.) 4.9/(14.5) 6.7/(25.9) 7.6/(33.2) 8.8/(17.9) 11.3/(28.4) 18.1/(14.3) 19.9/(17.1) 28.9/(35.8) 31.2/(41.1) 36.2/(14.3) Med Flow Total 17,880 24,830 28,560 32,460 42,280 65,300 72,010 108,750 117,090 129,920 (10°F ∆Tw) Sensible 13,620 19,360 22,540 25,730 34,220 52,790 58,560 82,780 90,030 104,910 GPM/(Ft.) 3.6/(8.2) 5.0/(15.1) 5.7/(19.3) 6.5/(10.2) 8.5/(16.7) 13.1/(7.9) 14.5/(9.6) 21.8/(21.4) 23.5/(24.5) 26.2/(7.9) Low Flow Total 16,370 22,860 26,690 29,890 39,060 58,870 65,240 101,470 110,240 117,060 (12°F ∆Tw) Sensible 12,880 18,360 21,440 24,390 32,470 49,420 54,950 79,230 86,610 98,170 GPM/(Ft.) 2.8/(5.0) 3.8/(9.2) 4.4/(11.9) 5.0/(6.3) 6.5/(10.2) 9.9/(4.7) 11.0/(5.7) 17.0/(13.6) 18.5/(15.8) 19.8/(4.7) OHS-012C OHS-018C OHS-024C OHS-032C OHS-040C OHS-048C OHS-060C OHS-072C OHS-084C OHS-120C 72°FDB/60°FWB High Flow Total 16,130 22,430 25,760 29,550 38,380 59,940 65,890 97,760 105,340 119,190 (8°F ∆Tw) Sensible 12,960 18,450 21,470 24,590 32,650 50,840 56,300 78,590 85,540 100,990 GPM/(Ft.) 4.1/(10.4) 5.7/(19.0) 6.4/(24.0) 7.4/(13.0) 9.6/(21.0) 15.1/(10.2) 16.6/(12.3) 24.5/(26.4) 26.4/(30.3) 30.2/(10.2) Med Flow Total 14,790 20,650 23,870 27,110 35,430 53,890 59,500 91,990 99,230 107,110 (10°F ∆Tw) Sensible 12,270 17,500 20,430 23,230 30,950 47,500 52,690 75,630 82,350 94,310 GPM/(Ft.) 3.0/(5.9) 4.2/(10.8) 4.8/(14.0) 5.4/(7.4) 7.1/(12.1) 10.8/(5.6) 12.0/(6.8) 18.5/(15.8) 20.0/(18.2) 21.6/(5.6) Low Flow Total 13,530 18,980 21,970 24,850 32,490 47,370 52,240 84,910 92,170 94,070 (12°F ∆Tw) Sensible 11,590 16,540 19,310 21,920 29,140 43,510 48,160 71,880 78,490 86,340 GPM/(Ft.) 2.3/(3.4) 3.2/(6.6) 3.7/(8.6) 4.2/(4.5) 5.4/(7.3) 8.0/(3.2) 8.8/(3.8) 14.2/(9.9) 15.5/(11.4) 16.0/(3.2) (Note: The above Cooling capacities @ standard CFM/e.s.p. as shown on page 4-19 & 4-21, Evaporator Blower/Motor.) 4-19 4-15 Air Technology Systems, Inc. Chilled Water - 50°F Entering Water Temperature Cooling Capacities (BTU/H) for 50°F Chilled Water Entering the Cooling Coil 80°FDB/67°FWB OHS-012C OHS-018C OHS-024C OHS-032C OHS-040C OHS-048C OHS-060C OHS-072C OHS-084C OHS-120C High Flow Total 17,340 23,720 27,070 31,550 40,300 64,160 69,840 102,640 110,880 127,640 (8°F ∆Tw) Sensible 12,970 18,360 21,350 24,670 32,580 51,150 56,420 77,640 84,770 101,610 GPM/(Ft.) 4.4/(11.6) 6.0/(20.6) 6.8/(26.0) 7.9/(14.5) 10.1/(22.7) 16.1/(11.4) 17.6/(13.4) 25.7/(28.3) 27.9/(32.7) 32.2/(11.4) Med Flow Total 15,870 22,110 25,390 29,130 36,840 58,670 64,760 96,430 103,990 116,670 (10°F ∆Tw) Sensible 12,330 17,620 20,530 23,520 31,310 48,530 53,880 74,920 81,700 96,380 GPM/(Ft.) 3.2/(6.5) 4.5/(12.0) 5.1/(15.3) 5.8/(8.2) 7.6/(13.4) 11.8/(6.4) 13.1/(7.8) 19.4/(16.9) 21.0/(19.5) 23.6/(6.4) Low Flow Total 14,570 20,410 23,660 26,770 35,130 52,860 58,460 91,030 97,870 105,040 (12°F ∆Tw) Sensible 11,730 16,780 19,640 22,320 29,840 45,480 50,480 72,410 78,760 90,280 GPM/(Ft.) 2.5/(4.0) 3.4/(7.4) 4.0/(9.7) 4.5/(5.1) 5.9/(8.3) 8.9/(3.8) 9.9/(4.6) 15.3/(10.9) 16.4/(12.5) 17.8/(3.8) OHS-012C OHS-018C OHS-024C OHS-032C OHS-040C OHS-048C OHS-060C OHS-072C OHS-084C OHS-120C 75°FDB/62.5°FWB High Flow Total 12,100 16,730 19,200 22,380 28,770 43,580 45,430 75,480 80,860 86,480 (8°F ∆Tw) Sensible 10,990 15,610 18,170 20,880 27,580 42,410 45,430 67,760 73,570 84,150 GPM/(Ft.) 3.1/(6.1) 4.2/(10.9) 4.8/(14.0) 5.7/(7.8) 7.2/(12.3) 11.0/(5.6) 11.5/(6.1) 19.0/(16.3) 20.4/(18.6) 22.0/(5.6) Med Flow Total 10,900 14,880 16,960 19,860 23,400 36,050 39,970 71,720 76,250 71,430 (10°F ∆Tw) Sensible 10,270 14,430 16,690 19,290 23,400 36,050 39,970 65,350 70,550 71,430 GPM/(Ft.) 2.2/(3.3) 3.0/(5.8) 3.4/(7.4) 4.0/(4.2) 4.8/(5.7) 7.3/(2.7) 8.2/(3.3) 14.4/(9.9) 15.4/(11.2) 14.6/(2.7) Low Flow Total 8,710 12,380 14,420 15,370 20,380 30,000 33,350 54,330 59,290 59,330 (12°F ∆Tw) Sensible 8,710 12,380 14,420 15,370 20,380 30,000 33,350 54,330 59,290 59,330 GPM/(Ft.) 1.5/(1.3) 2.1/(2.9) 2.4/(3.9) 2.6/(1.7) 3.5/(3.1) 5.1/(1.2) 5.7/(1.6) 9.2/(4.4) 10.0/(5.1) 10.2/(1.2) OHS-012C OHS-018C OHS-024C OHS-032C OHS-040C OHS-048C OHS-060C OHS-072C OHS-084C OHS-120C 72°FDB/60°FWB High Flow Total 8,950 12,720 14,820 16,220 21,520 33,560 37,150 55,560 60,470 66,440 (8°F ∆Tw) Sensible 8,950 12,720 14,820 16,220 21,520 33,560 37,150 55,560 60,470 66,440 GPM/(Ft.) 2.3/(3.5) 3.2/(6.6) 3.7/(8.7) 4.1/(4.3) 5.5/(7.3) 8.5/(3.5) 9.5/(4.3) 14.1/(9.5) 15.4/(11.1) 17.0/(3.5) Med Flow Total 7,930 11,260 13,120 14,070 18,640 27,890 30,910 49,330 53,790 55,100 (10°F ∆Tw) Sensible 7,930 11,260 13,120 14,070 18,640 27,890 30,910 49,330 53,790 55,100 GPM/(Ft.) 1.6/(1.6) 2.3/(3.5) 2.7/(4.6) 2.9/(2.1) 3.8/(3.7) 5.7/(1.6) 6.4/(2.0) 10.0/(5.1) 11.0/(6.0) 11.4/(1.6) Low Flow Total 6,690 9,550 11,140 11,500 15,340 20,870 23,350 41,390 45,320 41,060 (12°F ∆Tw) Sensible 6,690 9,550 11,140 11,500 15,340 20,870 23,350 41,390 45,320 41,060 GPM/(Ft.) 1.1/(0.7) 1.6/(1.6) 1.9/(2.3) 2.0/(0.8) 2.6/(1.7) 3.6/(0.5) 4.1/(0.7) 7.0/(2.7) 7.7/(3.2) 7.2/(0.5) (Note: The above Cooling capacities @ standard CFM/e.s.p. as shown on page 4-19 & 4-21, Evaporator Blower/Motor.) Air Technology Systems, Inc. 4-16 Free-Cooling & Alternate Water Source Free-Cooling MODEL TYPE ........................................... page DX with Free-Cooling Self-Contained Glycol Cooled w/ FC: • 1-5 Ton, models OHS-012/060-G-FC............................ 4-17/19 • 4-10 Ton, models OHS-048/120-DG-FC........................ 4-20/21 Self-Contained Water Cooled w/ FC: - Free-Cooling & Alternate Water Source Systems • 1-5 Ton, models OHS-012/060-W-FC............................ 4-22/23 • 4-10 Ton, models OHS-048/120-DW-FC....................... 4-24/25 DX with Alternate Water Source Air Technology Systems, Inc Alternate Water Source: • 1-5 Ton, models OHS-012/060-( )-AWS............................. 4-26 • 4-10 Ton, models OHS-048/120-D()-AWS.......................... 4-27 • 42°F / 50°F EWT Performance Data................................... 4-28 Alternate Water Source Remote Liquid Chiller (by others) Alternate Water Source Cooling Coil Pump (by others) Flow Switch Alternate Water Source Aqua-Stat T Remote Air Cooled Condenser Scroll Compressor Flooded Head Pressure Control Valve Relief Valve Receiver Air Technology Systems, Inc. DX - Cooling Coil LP HP Sight Glass Refrigerant Reclaim Port 4-17 AWS Control Valve FS Equalizer Line Performance Data Free-Cooling / Alternate Water Source Feeler Bulb Solenoid Valve Refrigerant Drier / Strainer Expansion Valve DX Glycol Cooled w/ Free-Cooling - 1 to 5 Ton "OHS" 012-HG-FC 018-HG-FC 024-HG-FC 032-HG-FC 040-HG-FC 048-G-FC 060-G-FC NET DX COOLING CAPACITY - BTU/H, (includes standard DX w/ FC evaporator motor heat @ std CFM & e.s.p. ratings) 80°FDB/67°FWB, 50% RH 13,390 18,960 25,090 32,000 34,910 57,150 62,670 Sensible 10,435 15,060 19,160 23,085 27,500 46,565 51,120 Total 12,200 17,541 22,975 28,175 31,855 52,325 57,335 Sensible 10,450 15,194 18,710 23,700 26,975 45,920 50,410 Total 11,510 16,720 21,900 27,800 30,540 49,770 54,525 Sensible 10,210 14,880 18,275 22,045 26,455 44,970 49,370 Total 12,900 18,375 23,990 30,580 33,840 54,920 60,120 Sensible 11,650 16,800 20,535 24,540 30,475 51,075 56,140 Total 11,780 17,035 22,430 28,175 31,290 50,785 55,550 Sensible 11,171 16,200 20,195 23,700 29,270 49,080 53,900 Total 11,120 16,235 21,355 27,065 29,770 48,360 52,680 Sensible 10,875 15,855 19,760 23,375 28,610 47,710 51,930 75°FDB/62.5°FWB, 50% RH 72°FDB/60°FWB, 50% RH 80°FDB/65°FWB, 45% RH 75°FDB/61°FWB, 45% RH 72°FDB/58.5°FWB, 45% RH FREE-COOLING CAPACITY - BTU/H @ 45°F Entering Glycol Temperature, 40% Ethylene Glycol Solution 80°FDB/67°FWB, 50% RH Total 16,040 22,685 27,755 32,355 39,420 57,050 63,700 Sensible 12,500 17,960 21,670 25,080 32,180 48,450 54,265 Total 12,880 18,190 22,170 25,910 31,670 45,395 50,560 Sensible 11,460 16,440 19,800 22,795 29,290 44,130 49,325 Total 11,160 15,670 19,125 22,455 27,265 39,955 44,570 Sensible 10,665 15,235 18,370 21,150 27,025 39,955 44,570 Total 15,110 21,330 25,990 30,380 37,140 53,235 59,270 Sensible 13,400 19,225 23,140 26,640 34,270 51,680 57,765 Total 12,200 16,815 20,840 24,630 29,405 44,500 49,635 Sensible 12,000 16,815 20,630 23,820 29,405 44,500 49,635 Total 10,740 15,260 18,465 21,010 26,380 39,890 44,490 Sensible 10,740 15,260 18,465 21,010 26,380 39,890 44,490 5.3 GPM 6.9 GPM 8.9 GPM 9.7 GPM 15.1 GPM 16.7 GPM 75°FDB/62.5°FWB, 50% RH 72°FDB/60°FWB, 50% RH 80°FDB/65°FWB, 45% RH 75°FDB/61°FWB, 45% RH 72°FDB/58.5°FWB, 45% RH Flow Rates, Free-Cooling Coil Flow Rate 3.8 GPM Evaporator Blower / Motor, DX w/ Free-Cooling - DWDI Centrifugal - Belt Driven, Variable Pitch Pulleys 1/4 Hp 1/3 Hp 1/2 Hp 1/2 Hp 3/4 Hp 1-1/2 Hp 2 Hp CFM @ ext. st. press. Horsepower 500 @ 0.5" 750 @ 0.5" 900 @ 0.5" 1,000 @ 0.5" 1,415 @ 0.5" 2,200 @ 0.5" 2,500 @ 0.5" Drive Method Belt Driven Belt Driven Belt Driven Belt Driven Belt Driven Belt Driven Belt Driven Evaporator Coils, (Both DX & Free-Cooling Respectively) - Aluminum Fin, Copper Tube - DX Glycol Cooled w/ FC (1 to 5 Ton Systems) Total Performance Data OHS Model DX Coil: Rows/ Face Area (Ft2) 3/ 2.1 3/ 2.1 3/ 2.1 3/ 2.8 3/ 2.8 4/ 5.0 4/ 5.0 4/ 2.1 4/ 2.1 4/ 2.1 4/ 2.8 4/ 2.8 4/ 5.0 4/ 5.0 FC Coil: Rows/Face Area (Ft2) Air Technology Systems, Inc. 4-18 DX Glycol Cooled w/ Free-Cooling - 1 to 5 Ton "OHS" Performance Data OHS Model 012-HG-FC 018-HG-FC 024-HG-FC 032-HG-FC 040-HG-FC 048-G-FC 060-G-FC Reheat/Heat - Performance Capacities Include Motor Heat, (Optional) ELECTRIC REHEAT / HEAT - BTU/H (Kw) @ 208V 17,135 (5.0) 17,135 (5.0) 17,135 (5.0) 17,425 (5.1) 17,955 (5.3) 37,350 (10.9) 38,900 (11.4) @ 230V 18,840 (5.5) 18,840 (5.5) 18,840 (5.5) 19,130 (5.6) 19,660 (5.8) 43,140 (12.6) 44,690 (13.1) @ 460V 17,355 (5.1) 17,355 (5.1) 17,355 (5.1) 17,645 (5.2) 18,175 (5.3) 37,350 (10.9) 38,900 (11.4) @ 277/480V 18,065 (5.3) 18,065 (5.3) 18,065 (5.3) 18,355 (5.4) 18,885 (5.5) 38,835 (11.4) 40,385 (11.8) Humidification - Electrode Steam Canister Humidifier with Adjustable Output, (Optional) Lbs/Hr, (Kw Input) 2-5, (1.7) 2-5, (1.7) 2-5, (1.7) 2-5, (1.7) 2-5, (1.7) 4-10, (3.4) 4-10, (3.4) Cycling Cycling Cycling Cycling Cycling Cycling Cycling Std Control Compressor - Heat pump duty rated, HCFC Ozone Safe R-22 Type, (Qty.) Recip., (1) Scroll, (1) Scroll, (1) Scroll, (1) Scroll, (1) Scroll, (1) Scroll, (1) Watts Input 1,442 1,729 2,227 2,882 3,027 4,699 5,290 DX Glycol Condenser Data - Based on 40% ethylene glycol solution Tot. Heat of Reject. 17,270 Btu/h 23,990 Btu/h 31,305 Btu/h 40,340 Btu/h 43,625 Btu/h 68,360 Btu/h 75,390 Btu/h - DX Glycol Cooled w/ FC (1 to 5 Ton Systems) GPM @ 110°F EGT 3.8 GPM 5.3 GPM 6.9 GPM 8.9 GPM 9.7 GPM 15.1 GPM 16.7 GPM Total Unit PD (Ft. of H2O) 11.8 Ft. 21.1 Ft. 38.4 Ft. 28.1 Ft. 34.3 Ft. 20.1 Ft. 24.9 Ft. Type Coaxial Coaxial Coaxial Coaxial Coaxial Coaxial Coaxial DX-Head Pressure & Free-Cooling Coil Control Valve Combinations DX Hd Pr. Valve Type - - - - - - - - 3-way, 150 psig DX Condenser Source Regulating Valve - field installed - - - - - - - Free-Cooling Valve - 3-way, Spring Actuated (Open/Close): Air Technology Systems, Inc 4-19 FC Valve Size / (Cv) 1/2" / (5.0 Cv) 3/4" / (5.0 Cv) 3/4" / (5.0 Cv) 3/4" / (5.0 Cv) 3/4" / (5.0 Cv) 1" / (7.0 Cv) 1" / (7.0 Cv) 300 psig 300 psig 300 psig 300 psig 300 psig 300 psig 300 psig Valve Pressure Rating Optional Valve Combinations - Please refer to page 3-9 for Higher Pressure Rated and Modulating (0-10 Vdc) Valve Combination Options! Connection Sizes - Copper Condensate Drain 3/4" FPT 3/4" FPT 3/4" FPT 3/4" FPT 3/4" FPT 3/4" FPT 3/4" FPT Humidifier Inlet 1/4" OD 1/4" OD 1/4" OD 1/4" OD 1/4" OD 1/4" OD 1/4" OD Source Glycol In/Out 5/8" OD 7/8" OD 7/8" OD 7/8" OD 7/8" OD 1-1/8" OD 1-1/8" OD 20x20, (1) 20x20, (1) 20x20, (1) 20x20, (1) 20x16, (2) 20x16, (2) 300 lbs 310 lbs 500 lbs 510 lbs Filters - 1" deep throwaway Nom. Size (in.), (Qty.) 20x20, (1) Physical Size - (Please refer to Section 6 for detailed dimensional data.) Approx. Weight 245 lbs 265 lbs 275 lbs DRYCOOLER DATA - Please refer to Glycol Pump / Drycooler Engineering Manual 105°F Amb. Selections - Optional - Please refer to Glycol Pump / Drycooler Engineering Manual Glycol Pump Packages - Optional - Please refer to Glycol Pump / Drycooler Engineering Manual Air Technology Systems, Inc. DX Glycol Cooled w/ Free-Cooling - 4 to 10 Ton "OHS" (Dual) 048-DG-FC 072-DG-FC 084-DG-FC 120-DG-FC NET DX COOLING CAPACITY - BTU/H, (includes standard DX w/ FC evaporator motor heat @ std CFM & e.s.p. ratings) 80°FDB/67°FWB, 50% RH 51,260 70,230 87,445 123,970 Sensible 39,730 61,010 69,465 95,280 Total 46,840 64,090 79,565 113,045 Sensible 39,230 60,180 69,420 93,920 Total 44,600 60,990 75,580 107,490 Sensible 38,400 58,520 68,115 91,925 Total 49,150 67,340 83,055 118,680 Sensible 43,340 65,360 77,390 104,065 Total 45,500 62,635 76,640 109,590 Sensible 41,840 61,750 73,350 100,420 Total 43,320 59,880 73,150 104,185 Sensible 41,000 59,635 71,130 98,400 75°FDB/62.5°FWB, 50% RH 72°FDB/60°FWB, 50% RH 80°FDB/65°FWB, 45% RH 75°FDB/61°FWB, 45% RH 72°FDB/58.5°FWB, 45% RH FREE-COOLING CAPACITY - BTU/H @ 45°F Entering Glycol Temperature, 40% Ethylene Glycol Solution 80°FDB/67°FWB, 50% RH Total 54,105 89,015 105,970 119,730 Sensible 42,715 72,360 83,255 99,390 Total 43,290 72,275 85,820 95,730 Sensible 39,055 66,680 76,665 90,850 Total 37,290 62,365 74,595 82,130 Sensible 36,180 61,770 71,425 82,130 Total 50,780 84,960 100,770 112,260 Sensible 45,670 78,090 89,680 106,340 Total 39,925 68,360 81,685 92,370 Sensible 39,925 68,360 81,685 92,370 Total 36,260 61,260 71,495 82,820 Sensible 36,260 61,260 71,495 82,820 13.7 GPM 18.7 GPM 23.8 GPM 33.0 GPM 75°FDB/62.5°FWB, 50% RH 72°FDB/60°FWB, 50% RH 80°FDB/65°FWB, 45% RH 75°FDB/61°FWB, 45% RH 72°FDB/58.5°FWB, 45% RH Flow Rates, Free-Cooling Coil Flow Rate Evaporator Blower / Motor, DX w/ Free-Cooling - DWDI Centrifugal - Belt Driven, Variable Pitch Pulleys Horsepower CFM @ ext. st. press. Drive Method 1 Hp 1-1/2 Hp 2 Hp 3 Hp 1,800 @ 0.5" 3,000 @ 0.5" 3,350 @ 0.5" 4,400 @ 0.5" Belt Driven Belt Driven Belt Driven Belt Driven Evaporator Coils, (Both DX & Free-Cooling Respectively) - Aluminum Fin, Copper Tube - DX Glycol Cooled w/ FC (4 to 10 Ton Dual Systems) Total Performance Data OHS Model DX Coil: Rows/ Face Area (ft2) 4/ 4.1 ft2 4/ 6.7 ft2 4/ 6.7 ft2 4/ 10.0 ft2 Rows/Face Area (ft2) 4/ 4.1 ft2 4/ 6.7 ft2 4/ 6.7 ft2 4/ 10.0 ft2 FC Coil: Air Technology Systems, Inc. 4-20 DX Glycol Cooled w/ Free-Cooling - 4 to 10 Ton "OHS" (Dual) Performance Data OHS Model 048-DG-FC 072-DG-FC 084-DG-FC 120-DG-FC Reheat/Heat - Performance Capacities Include Motor Heat, (Optional) ELECTRIC REHEAT / HEAT - BTU/H (Kw) @ 208V/460V 36,810 (10.9) 38,900 (11.4) 40,510 (11.9) 43,580 (12.8) @ 230V 42,600 (12.5) 44,690 (13.1) 46,300 (13.6) 49,370 (14.5) @ 480V 38,295 (11.2) 40,385 (11.8) 41,995 (12.3) 45,065 (13.2) Humidification - Electrode Steam Canister Humidifier with Adjustable Output, (Optional) Lbs/Hr, (Kw Input) - DX Glycol Cooled w/ FC (4 to 10 Ton Dual Systems) 4-10, (3.4) 4-15, (5.1) 4-15, (5.1) 4-15, (5.1) Cycling Cycling Cycling Cycling Scroll, (2) Scroll, (2) Scroll, (2) Scroll, (2) 2,188 2,973 4,103 5,290 61,775 Btu/h 84,385 Btu/h 107,570 Btu/h 149,155 Btu/h 13.7 GPM 18.7 GPM 23.8 GPM 33.0 GPM Total Unit Pressure Drop (Ft. of H2O) 37.8 Ft. 34.8 Ft. 41.0 Ft. 29.5 Ft. Type Coaxial Coaxial Coaxial Coaxial Std Control Compressor - Heat pump duty rated, HCFC Ozone Safe R-22 Type, (Qty.) Watt Input (per compressor) DX Glycol Condenser Data - Based on 40% ethylene glycol solution Total Heat of Rejection GPM @ 110°F EGT DX-Head Pressure & Free-Cooling Coil Control Valve Combinations DX Head Pressure Regulating Valves: DX Hd Pr. Valve Type - - - - - - - - - - -3-way, 150 psig DX Condenser Source Regulating Valve - factory installed - - - - - - - - - - - Free-Cooling Valve - 3-way, Spring Actuated (Open/Close): Air Technology Systems, Inc 4-21 FC Valve Size / (Cv) Valve Pressure Rating 1" / (7.0 Cv) 1" / (14.0 Cv) 1" / (14.0 Cv) 1" / (14.0 Cv) 300 psig 400 psig 400 psig 400 psig Optional Valve Combos - Please refer to page 3-9 for Higher Pressure Rated and Modulating (0-10 Vdc) Valve Combination Options! Connection Sizes - Copper Condensate Drain, (w/ In-Pan Pump) Humidifier Inlet Source Glycol In/Out 3/4" FPT, (1/2"OD) 3/4" FPT, (1/2"OD) 3/4" FPT, (1/2"OD) 3/4" FPT, (1/2"OD) 1/4" OD 1/4" OD 1/4" OD 1/4" OD 1-1/8" OD 1-1/8" OD 1-3/8" OD 1-3/8" OD 16x20, (2) 20x20, (2) 20x20, (2) 24x24, (2) 660 lbs 745 lbs Filters - 1" deep throwaway Nominal Size (in.), (Qty.) Physical Size - (Please refer to Section 6 for detailed dimensional data.) Approx. Weight 550 lbs 570 lbs DRYCOOLER DATA - Please refer to Glycol Pump / Drycooler Engineering Manual 105°F Amb. Selections - Optional - Please refer to Glycol Pump / Drycooler Engineering Manual Glycol Pump Packages - Optional - Please refer to Glycol Pump / Drycooler Engineering Manual Air Technology Systems, Inc. DX Water Cooled w/ Free-Cooling - 1 to 5 Ton "OHS" 012-HW-FC 018-HW-FC 024-HW-FC 032-HW-FC 040-HW-FC 048-W-FC 060-W-FC DX COOLING CAPACITY - BTU/H, (includes standard DX w/ FC evaporator motor heat @ std CFM & e.s.p. ratings) 80°FDB/67°FWB, 50% RH 16,394 21,125 27,990 35,550 39,115 64,250 70,665 Sensible 11,675 16,000 20,455 24,575 29,500 49,240 54,100 Total 14,850 19,345 25,750 32,700 35,830 58,820 64,690 Sensible 11,340 15,625 20,100 24,265 28,800 48,580 53,445 Total 14,000 18,380 24,560 31,150 34,109 56,070 61,650 Sensible 11,050 16,400 19,680 23,775 28,093 47,600 52,345 Total 15,570 20,430 26,840 34,170 37,355 61,635 67,730 Sensible 12,440 17,645 21,825 26,300 31,600 53,560 58,955 Total 14,380 18,950 24,920 31,600 35,120 57,130 62,760 Sensible 12,250 17,040 21,075 25,360 30,560 51,780 56,975 Total 13,620 18,065 23,685 30,060 33,460 54,460 59,795 Sensible 12,010 16,710 20,700 24,820 30,470 50,820 55,910 75°FDB/62.5°FWB, 50% RH 72°FDB/60°FWB, 50% RH 80°FDB/65°FWB, 45% RH 75°FDB/61°FWB, 45% RH 72°FDB/58.5°FWB, 45% RH FREE-COOLING CAPACITY - BTU/H @ 45°F Entering Water Temperature, 0% Glycol Solution 80°FDB/67°FWB, 50% RH Total 20,595 27,790 32,980 39,210 48,040 75,585 83,475 Sensible 14,380 20,050 23,810 28,095 35,960 55,990 62,325 Total 16,240 22,100 26,160 31,060 38,605 60,370 66,790 Sensible 12,975 18,215 21,605 25,280 32,710 51,050 56,895 Total 14,010 19,125 22,600 26,820 33,565 52,360 57,970 Sensible 12,040 16,935 20,075 23,400 30,390 47,520 52,960 Total 19,030 25,895 30,615 36,395 45,190 70,785 78,305 Sensible 15,130 21,250 25,190 29,490 38,160 59,610 66,435 Total 15,350 20,985 24,750 29,390 36,840 57,550 63,570 Sensible 13,565 19,090 22,605 26,325 34,220 53,600 59,650 Total 13,295 18,050 21,240 25,440 30,250 48,250 53,590 Sensible 12,620 17,640 20,880 24,400 30,250 48,250 53,590 4.9 GPM 6.4 GPM 8.3 GPM 9.0 GPM 14.1 GPM 15.6 GPM 75°FDB/62.5°FWB, 50% RH 72°FDB/60°FWB, 50% RH 80°FDB/65°FWB, 45% RH 75°FDB/61°FWB, 45% RH 72°FDB/58.5°FWB, 45% RH Flow Rates, Free-Cooling Coil Flow Rate 3.8 GPM Evaporator Blower / Motor, DX w/ Free-Cooling - DWDI Centrifugal - Belt Driven, Variable Pitch Pulleys 1/4 Hp 1/3 Hp 1/2 Hp 1/2 Hp 3/4 Hp 1-1/2 Hp 2 Hp CFM @ ext. st. press. Horsepower 500 @ 0.5" 750 @ 0.5" 900 @ 0.5" 1,000 @ 0.5" 1,415 @ 0.5" 2,200 @ 0.5" 2,500 @ 0.5" Drive Method Belt Driven Belt Driven Belt Driven Belt Driven Belt Driven Belt Driven Belt Driven - DX Water Cooled w/ FC (1 to 5 Ton Systems) Total Performance Data OHS Model Evaporator Coils, (Both DX & Free-Cooling Respectively) - Aluminum Fin, Copper Tube DX Coil: Rows/ Face Area (ft2) 3/ 2.1 3/ 2.1 3/ 2.1 3/ 2.8 3/ 2.8 4/ 5.0 4/ 5.0 4/ 2.1 4/ 2.1 4/ 2.1 4/ 2.8 4/ 2.8 4/ 5.0 4/ 5.0 FC Coil: Rows/Face Area (ft2) Air Technology Systems, Inc. 4-22 DX Water Cooled w/ Free-Cooling - 1 to 5 Ton "OHS" Performance Data OHS Model 012-HW-FC 018-HW-FC 024-HW-FC 032-HW-FC 040-HW-FC 048-W-FC 060-W-FC Reheat/Heat - Performance Capacities Include Motor Heat, (Optional) ELECTRIC REHEAT / HEAT - BTU/H (Kw) @ 208V 17,135 (5.0) 17,135 (5.0) 17,135 (5.0) 17,425 (5.1) 17,955 (5.3) 37,350 (10.9) 38,900 (11.4) @ 230V 18,840 (5.5) 18,840 (5.5) 18,840 (5.5) 19,130 (5.6) 19,660 (5.8) 43,140 (12.6) 44,690 (13.1) @ 460V 17,355 (5.1) 17,355 (5.1) 17,355 (5.1) 17,645 (5.2) 18,175 (5.3) 37,350 (10.9) 38,900 (11.4) @ 277/480V 18,065 (5.3) 18,065 (5.3) 18,065 (5.3) 18,355 (5.4) 18,885 (5.5) 38,835 (11.4) 40,385 (11.8) Humidification - Electrode Steam Canister Humidifier with Adjustable Output, (Optional) Lbs/Hr, (Kw Input) Std Control 2-5, (1.7) 2-5, (1.7) 2-5, (1.7) 2-5, (1.7) 2-5, (1.7) 4-10, (3.4) 4-10, (3.4) Cycling Cycling Cycling Cycling Cycling Cycling Cycling Compressor - Heat pump duty rated, HCFC Ozone Safe R-22 Type, (Qty.) Recip., (1) Scroll, (1) Scroll, (1) Scroll, (1) Scroll, (1) Scroll, (1) Scroll, (1) Watts Input 1,245 1,239 1,633 2,118 2,222 3,451 3,867 DX Water Cooled Condenser Data - Based on 0% glycol solution - DX Water Cooled w/ FC (1 to 5 Ton Systems) Tot Heat of Reject. 18,900 Btu/h 24,350 Btu/h 32,145 Btu/h 41,325 Btu/h 44,865 Btu/h 70,600 Btu/h 77,890 Btu/h GPM @ 85°F EWT 3.8 GPM 4.9 GPM 6.4 GPM 8.3 GPM 9.0 GPM 14.1 GPM 15.6 GPM Total Unit PD (Ft. of H2O) 12.1 Ft. 16.3 Ft. 26.9 Ft. 21.6 Ft. 25.1 Ft. 16.5 Ft. 22.7 Ft. Type Coaxial Coaxial Coaxial Coaxial Coaxial Coaxial Coaxial DX-Head Pressure & Free-Cooling Coil Control Valve Combinations DX Head Pressure Control Valve Type - - - - - - - - 3-way, 150 psig DX Condenser Source Regulating Valve - field installed - - - - - - - Free-Cooling Valve - 3-way, Spring Actuated (Open/Close): FC Valve Size / (Cv) 1/2" / (5.0 Cv) 3/4" / (5.0 Cv) 3/4" / (5.0 Cv) 3/4" / (5.0 Cv) 3/4" / (5.0 Cv) 1" / (7.0 Cv) 1" / (7.0 Cv) Air Technology Systems, Inc 4-23 Valve Pressure Rating 300 psig 300 psig 300 psig 300 psig 300 psig 300 psig 300 psig Optional Valve Combinations - Please refer to page 3-9 for Higher Pressure Rated and Modulating (0-10 Vdc) Valve Combination Options! Connection Sizes - Copper Condensate Drain 3/4" FPT 3/4" FPT 3/4" FPT 3/4" FPT 3/4" FPT 3/4" FPT 3/4" FPT Humidifier Inlet 1/4" OD 1/4" OD 1/4" OD 1/4" OD 1/4" OD 1/4" OD 1/4" OD Source Water In/Out 5/8" OD 7/8" OD 7/8" OD 7/8" OD 7/8" OD 1-1/8" OD 1-1/8" OD 20x20, (1) 20x20, (1) 20x20, (1) 20x20, (1) 20x20, (1) 20x16, (2) 20x16, (2) 300 lbs 310 lbs 500 lbs 510 lbs Filters - 1" deep throwaway Nom. Size (in.), (Qty.) Physical Size - (Please refer to Section 6 for detailed dimensional data.) Approx. Weight 245 lbs 265 lbs 275 lbs Air Technology Systems, Inc. DX Water Cooled w/ Free-Cooling - 4 to 10 Ton (Dual) "OHS" 048-DW-FC 072-DW-FC 084-DW-FC 120-DW-FC NET DX COOLING CAPACITY - BTU/H, (includes standard DX w/ FC evaporator motor heat @ std CFM & e.s.p. ratings) 80°FDB/67°FWB, 50% RH 57,200 79,165 98,760 139,210 Sensible 42,320 63,770 73,735 101,715 Total 52,580 72,510 90,475 127,660 Sensible 41,620 63,225 72,760 100,040 Total 50,100 69,035 86,090 121,610 Sensible 40,820 62,045 71,400 98,010 Total 54,890 75,840 94,300 133,265 Sensible 45,740 70,425 81,160 110,080 Total 50,960 70,200 87,050 123,460 Sensible 44,180 67,685 78,670 106,285 Total 48,620 66,785 82,760 117,645 Sensible 43,390 65,220 77,320 104,340 75°FDB/62.5°FWB, 50% RH 72°FDB/60°FWB, 50% RH 80°FDB/65°FWB, 45% RH 75°FDB/61°FWB, 45% RH 72°FDB/58.5°FWB, 45% RH FREE-COOLING CAPACITY - BTU/H @ 45°F Entering Water Temperature, 0% Glycol Solution 80°FDB/67°FWB, 50% RH Total 65,040 114,520 129,450 155,760 Sensible 47,200 82,710 92,855 114,040 Total 51,715 92,810 103,815 124,035 Sensible 42,900 75,940 84,740 103,790 Total 44,720 81,270 90,630 107,260 Sensible 39,870 71,045 79,175 96,470 Total 60,530 108,660 121,700 145,395 Sensible 50,020 88,545 98,880 121,150 Total 49,015 89,840 99,690 117,850 Sensible 44,910 80,380 89,360 108,830 Total 42,040 78,890 87,155 100,940 Sensible 41,440 75,090 83,385 100,300 12.7 GPM 17.5 GPM 22.2 GPM 30.8 GPM 75°FDB/62.5°FWB, 50% RH 72°FDB/60°FWB, 50% RH 80°FDB/65°FWB, 45% RH 75°FDB/61°FWB, 45% RH 72°FDB/58.5°FWB, 45% RH Flow Rates, Free-Cooling Coil Flow Rate Evaporator Blower / Motor, DX w/ Free-Cooling - DWDI Centrifugal - Belt Driven, Variable Pitch Pulleys Horsepower CFM @ ext. st. press. Drive Method 1 Hp 1-1/2 Hp 2 Hp 3 Hp 1,800 @ 0.5" 3,000 @ 0.5" 3,350 @ 0.5" 4,400 @ 0.5" Belt Driven Belt Driven Belt Driven Belt Driven Evaporator Coils, (Both DX & Free-Cooling Respectively) - Aluminum Fin, Copper Tube - DX Water Cooled w/ FC (4 to 10 Ton Dual Systems) Total Performance Data OHS Model DX Coil: Rows/ Face Area (ft2) 4/ 4.1 4/ 6.7 4/ 6.7 4/ 10.0 Rows/Face Area (ft2) 4/ 4.1 4/ 6.7 4/ 6.7 4/ 10.0 FC Coil: Air Technology Systems, Inc. 4-24 DX Water Cooled w/ Free-Cooling - 4 to 10 Ton (Dual) "OHS" Performance Data OHS Model 048-DW-FC 072-DW-FC 084-DW-FC 120-DW-FC Reheat/Heat - Performance Capacities Include Motor Heat, (Optional) ELECTRIC REHEAT / HEAT - BTU/H (Kw) @ 208V/460V 36,810 (10.9) 38,900 (11.4) 40,510 (11.9) 43,580 (12.8) @ 230V 42,600 (12.5) 44,690 (13.1) 46,300 (13.6) 49,370 (14.5) @ 480V 38,295 (11.2) 40,385 (11.8) 41,995 (12.3) 45,065 (13.2) Humidification - Electrode Steam Canister Humidifier with Adjustable Output, (Optional) Lbs/Hr, (Kw Input) - DX Water Cooled w/ FC (4 to 10 Ton Dual Systems) 4-10, (3.4) 4-15, (5.1) 4-15, (5.1) 4-15, (5.1) Cycling Cycling Cycling Cycling Scroll, (2) Scroll, (2) Scroll, (2) Scroll, (2) 2,188 2,973 4,103 5,290 63,525 Btu/h 87,405 Btu/h 110,770 Btu/h 154,060 Btu/h 12.7 GPM 17.5 GPM 22.2 GPM 30.8 GPM Press. Drop (Ft. of H2O) 26.8 Ft. 25.2 Ft. 28.3 Ft. 25.7 Ft. Type Coaxial Coaxial Coaxial Coaxial Std Control Compressor - Heat pump duty rated, HCFC Ozone Safe R-22 Type, (Qty.) Watt Input (per compressor) DX Water Cooled Condenser Data - Based on 0% glycol solution Total Heat of Reject. GPM @ 85°F EWT DX-Head Pressure & Free-Cooling Coil Control Valve Combinations DX Hd Pr. Valve Type - - - - - - - - - - 3-way, 150 psig DX Condenser Source Regulating Valve - factory installed - - - - - - - - - Free-Cooling Valve - 3-way, Spring Actuated (Open/Close): FC Valve Size / (Cv) 1" / (7.0 Cv) 1" / (14.0 Cv) 1" / (14.0 Cv) 1" / (14.0 Cv) 300 psig 400 psig 400 psig 400 psig Air Technology Systems, Inc Valve Pressure Rating Optional Valve Combos - Please refer to page 3-9 for Higher Pressure Rated and Modulating (0-10 Vdc) Valve Combination Options! Connection Sizes - Copper Condensate Drain, (w/ In-Pan Pump) Humidifier Inlet Source Water In/Out 3/4" FPT, (1/2"OD) 3/4" FPT, (1/2"OD) 3/4" FPT, (1/2"OD) 3/4" FPT, (1/2"OD) 1/4" OD 1/4" OD 1/4" OD 1/4" OD 1-1/8" OD 1-1/8" OD 1-3/8" OD 1-3/8" OD 16x20, (2) 20x20, (2) 20x20, (2) 24x24, (2) 660 lbs 745 lbs Filters - 1" deep throwaway Nominal Size (in.), (Qty.) Physical Size - (Please refer to Section 6 for detailed dimensional data.) Approx. Weight 4-25 550 lbs 570 lbs Air Technology Systems, Inc. Alternate Water Source 012-AWS 018-AWS 024-AWS 032-AWS 040-AWS (45°F EWT) 048-AWS 060-AWS 83,430 90,800 COOLING CAPACITY - BTU/H @ 45°F EWT, 0% Glycol Solution (includes motor heat @ std CFM & e.s.p. ratings) 80°FDB/67°FWB, 50% RH High Flow (8°F ∆Tw) Total Sens. GPM / (pd. Ft.) 22,970 31,040 35,250 40,690 51,820 15,340 21,380 24,650 28,610 37,500 58,940 64,920 5.8 / (19.6) 7.8 / (34.0) 8.8 / (43.1) 10.2 / (23.3) 13.0 / (36.8) 20.9 / (18.6) 22.8 / (21.9) 84,490 Med. Flow Total 21,200 29,000 32,920 37,920 48,510 77,020 (10°F ∆Tw) Sens. 14,560 20,470 23,600 27,310 35,930 56,080 62,060 4.3 / (11.2) 5.8 / (19.8) 6.6 / (25.1) 7.6 / (13.6) 9.7 / (21.5) 15.5 / (10.7) 17.1 / (12.7) GPM / (pd. Ft.) Low Flow Total 19,390 26,780 30,740 34,840 45,270 69,650 76,840 (12°F ∆Tw) Sens. 13,760 19,470 22,600 25,870 34,360 52,730 58,530 3.3 / (6.8) 4.5 / (12.2) 5.2 / (15.8) 5.8 / (8.3) 7.6 / (13.4) 11.7 / (6.4) 13.0 / (7.7) 16,460 22,790 25,940 30,060 38,720 60,970 67,120 GPM / (pd. Ft.) 75°FDB/62.5°FWB, 50% RH High Flow (8°F ∆Tw) Total Sens. GPM / (pd. Ft.) 18,450 21,330 24,610 32,550 50,870 56,430 5.7 / (19.4) 6.5 / (24.6) 7.6 / (13.4) 9.7 / (21.5) 15.4 / (10.6) 17.0 / (12.7) 60,770 Med. Flow Total 15,110 21,030 24,210 27,600 36,030 54,830 (10°F ∆Tw) Sens. 12,340 17,550 20,420 23,310 31,050 47,630 53,000 3.1 / (6.0) 4.2 / (11.1) 4.9 / (14.5) 5.6 / (7.6) 7.3 / (12.5) 11.1 / (5.8) 12.4 / (7.1) GPM / (pd. Ft.) Low Flow Total 13,840 19,360 22,320 25,360 33,140 48,820 54,020 (12°F ∆Tw) Sens. 11,690 16,640 19,340 22,060 29,340 44,100 48,950 2.3 / (3.7) 3.3 / (6.8) 3.8 / (8.9) 4.3 / (4.7) 5.6 / (7.6) 8.3 / (3.4) 9.2 / (4.1) 13,510 18,750 21,580 24,820 32,320 49,770 54,740 GPM / (pd. Ft.) 72°FDB/60°FWB, 50% RH High Flow (8°F ∆Tw) Total Sens. GPM / (pd. Ft.) 11,700 16,630 19,340 22,120 29,440 45,580 50,480 3.4 / (7.5) 4.7 / (13.6) 5.5 / (17.8) 6.3 / (9.5) 8.1 / (15.4) 12.6 / (7.4) 13.9 / (8.8) Med. Flow Total 12,390 17,180 19,740 22,710 29,420 42,980 47,200 (10°F ∆Tw) Sens. 11,080 15,690 18,190 20,860 27,580 41,330 45,670 2.5 / (4.2) 3.5 / (7.7) 4.0 / (10.0) 4.6 / (5.4) 6.0 / (8.6) 8.7 / (3.7) 9.6 / (4.5) Low Flow GPM / (pd. Ft.) Total 11,120 15,320 17,510 20,120 25,810 33,790 37,580 (12°F ∆Tw) Sens. 10,300 14,460 16,680 19,170 25,100 33,790 37,580 1.9 / (2.2) 2.6 / (4.5) 3.0 / (5.7) 3.4 / (3.1) 4.4 / (4.9) 5.8 / (1.6) 6.4 / (2.1) GPM / (pd. Ft.) Alternate Water Source Control Valve - Sized for Medium Flow @ 75°FDB/62.5°FWB EAT Conditions 2-way (standard) - Spring Actuated (Open/Close) Size / (Cv) Pressure Rating Total Unit PD 1/2" / (3.5) 3/4" / (3.5) 3/4" / (3.7) 3/4" / (3.7) 3/4" / (3.7) 1.0" / (8.0) 1.0" / (8.0) 300 psig 300 psig 300 psig 300 psig 300 psig 300 psig 300 psig 8.0 Ft. 14.6 Ft. 19.4 Ft. 14.2 Ft. 22.6 Ft. 10.4 Ft. 12.7 Ft. 1/2" / (5.0) 3/4" / (5.0) 3/4" / (5.0) 3/4" / (5.0) 3/4" / (5.0) 1.0" / (7.0) 1.0" / (7.0) 300 psig 300 psig 300 psig 300 psig 300 psig 300 psig 300 psig 7.1 Ft. 12.9 Ft. 17.0 Ft. 11.2 Ft. 17.5 Ft. 11.8 Ft. 14.4 Ft. 4 / 2.8 ft2 4 / 2.8 ft2 4/ 5.0 ft2 4/ 5.0 ft2 3-way (optional) - Spring Actuated (Open/Close) Size / (Cv) Pressure Rating Total Unit PD - Alternate Water Source (45°F EWT) 13,000 4.2 / (10.7) Performance Data OHS Model - 1 to 5 Ton "OHS" Evaporator Coil, Alternate Water Source - Aluminum Fin, Copper Tube Rows/Face Area (ft2) 4 / 2.1 ft2 4 / 2.1 ft2 4 / 2.1 ft2 Evaporator Blower / Motor, Alternate Water Source - DWDI Centrifugal - Belt Driven, Variable Pitch Pulleys 1/4 Hp 1/3 Hp 1/2 Hp 1/2 Hp 3/4 Hp 1-1/2 Hp 2 Hp CFM @ ext. st. press. Horsepower 500 @ 0.5" 750 @ 0.5" 900 @ 0.5" 1,000 @ 0.5" 1,415 @ 0.5" 2,200 @ 0.5" 2,500 @ 0.5" Drive Method Belt Driven Belt Driven Belt Driven Belt Driven Belt Driven Belt Driven Belt Driven 1-1/8" OD 1-1/8" OD Connection Sizes, Alternate Water Source - Copper, (@ 75°FDB/62.5°FWB EAT flow rate conditions.) Chilled Water In/Out 5/8" OD 7/8" OD 7/8" OD Air Technology Systems, Inc. 7/8" OD 7/8" OD 4-26 Alternate Water Source Performance Data OHS Model 048D()-AWS - 4 to 10 Ton "OHS" 072D()-AWS 084D()-AWS (45°F EWT) 120D()-AWS NET COOLING CAPACITY - BTU/H @ 45°F EWT, 0% Glycol Solution (includes motor heat @ std CFM & e.s.p. ratings) 80°FDB/67°FWB, 50% RH High Flow Total (8°F ∆Tw) Sensible GPM / (pd. Ft.) 70,490 134,100 144,440 166,850 49,290 90,760 98,710 117,880 17.6 / (43.1) 33.5 / (46.3) 36.1 / (53.2) 41.8 / (18.6) Med. Flow Total 65,830 125,560 135,080 154,030 (10°F ∆Tw) Sensible 47,200 87,010 94,600 112,150 13.2 / (25.1) 25.2 / (27.5) 27.1 / (31.5) 31.0 / (10.7) 61,480 117,370 126,560 139,290 GPM / (pd. Ft.) Low Flow Total (12°F ∆Tw) Sensible GPM / (pd. Ft.) 45,200 83,420 90,820 105,460 10.4 / (15.8) 19.6 / (17.4) 21.2 / (20.1) 23.4 / (6.4) 51,880 99,080 106,720 121,940 75°FDB/62.5°FWB, 50% RH High Flow Total (8°F ∆Tw) Sensible GPM / (pd. Ft.) 42,660 78,510 85,490 101,740 13.0/ (24.6) 24.8 / (26.9) 26.8 / (30.8) 30.8 / (10.6) - Alternate Water Source (45°F EWT) Med. Flow Total 48,420 93,260 100,560 109,650 (10°F ∆Tw) Sensible 40,30 75,670 82,420 95,250 9.8 / (14.5) 18.8 / (16.1) 20.3 / (18.5) 22.2 / (5.8) 44,630 87,270 94,830 97,640 GPM / (pd. Ft.) Low Flow Total (12°F ∆Tw) Sensible 38,670 72,610 79,360 88,190 7.6 / (8.9) 14.6 / (10.2) 15.9 / (11.9) 16.6 / (3.4) 43,150 83,050 89,560 99,540 Air Technology Systems, Inc GPM / (pd. Ft.) 72°FDB/60°FWB, 50% RH Total High Flow (8°F ∆Tw) Sensible GPM / (pd. Ft.) 38,670 71,570 77,990 91,150 11.0 / (17.8) 20.9 / (19.6) 22.5 / (22.6) 25.2 / (7.4) Med. Flow Total 39,480 78,610 84,870 85,960 (10°F ∆Tw) Sensible 36,380 69,090 75,240 82,660 8.0 / (10.0) 15.8 / (11.9) 17.2 / (13.7) 17.4 / (3.7) Low Flow GPM / (pd. Ft.) Total 35,020 71,630 77,770 67,580 (12°F ∆Tw) Sensible 33,360 64,930 70,840 67,580 6.0 / (5.7) 12.0 / (7.2) 13.1 / (8.4) 11.6 / (1.6) GPM / (pd. Ft.) Alternate Water Source Control Valve - Sized for Medium Flow @ 75°FDB/62.5°FWB EAT Conditions 2-way (standard) - Spring Actuated (Open/Close) Size / (Cv) 1" / (8.0) 1" / (14.0) 1" / (14.0) 1" / (14.0) Pressure Rating 300 psig 400 psig 400 psig 400 psig Total Unit Pressure Drop 19.4 Ft. 20.7 Ft. 24.1 Ft. 12.5 Ft. 3-way (optional) - Spring Actuated (Open/Close) Size / (Cv) 1" / (7.0) 1" / (14.0) 1" / (14.0) 1" / (14.0) Valve Pressure Rating 300 psig 400 psig 400 psig 400 psig Total Unit Pressure Drop 17.0 Ft. 20.7 Ft. 24.1 Ft. 12.5 Ft. 4/ 6.7 ft2 4/ 6.7 ft2 4/ 10.0 ft2 Evaporator Coil, Alternate Water Source - Aluminum Fin, Copper Tube Rows/Face Area (ft2) 4/ 4.1 ft2 Evaporator Blower / Motor, Alternate Water Source - DWDI Centrifugal - Belt Driven, Variable Pitch Pulleys Horsepower CFM @ ext. st. press. Drive Method 1 Hp 1-1/2 Hp 2 Hp 3 Hp 1,800 @ 0.5" 3,000 @ 0.5" 3,350 @ 0.5" 4,400 @ 0.5" Belt Driven Belt Driven Belt Driven Belt Driven Connection Sizes, Alternate Water Source - Copper, (@ 75°FDB/62.5°FWB EAT flow rate conditions.) Chilled Water In/Out 4-27 1-1/8" OD 1-1/8" OD Air Technology Systems, Inc. 1-1/8" OD 1-3/8" OD Alternate Water Source - 42°F/50°F EWT 012-AWS 018-AWS 024-AWS 032-AWS 040-AWS 048-AWS 060-AWS 072-AWS 084-AWS 120-AWS High Flow Total 26,260 35,660 40,630 46,540 59,330 96,270 104,840 153,410 165,430 191,860 (8°F ∆Tw) Sensible 16,820 23,440 27,080 31,360 40,970 64,660 71,110 99,310 107,930 128,640 GPM/(Ft.) 6.6/(25.0) 8.9/(43.9) 10.1/(55.8) 11.6/(29.8) 14.8/(47.2) 24.0/(24.2) 26.2/(28.4) 38.3/(59.6) 41.3/(68.6) 42.0/(24.2) Med Flow Total 24,550 33,500 38,180 43,710 55,750 89,650 97,830 144,620 155,710 178,610 (10°F ∆Tw) Sensible 16,030 22,450 25,960 30,010 39,270 61,650 67,920 95,310 103,520 122,630 GPM/(Ft.) 4.9/(14.8) 6.7/(25.8) 7.6/(32.9) 8.7/(17.6) 11.1/(27.7) 17.9/(14.1) 19.6/(16.6) 28.9/(35.7) 31.2/(41.0) 35.8/(14.1) Low Flow Total 22,660 31,170 35,790 40,430 52,300 81,320 59,560 135,610 146,250 161,960 (12°F ∆Tw) Sensible 15,180 21,390 24,860 28,450 37,600 57,910 64,180 91,260 99,260 115,150 GPM/(Ft.) 3.8/(9.1) 5.2/(16.1) 6.0/(20.8) 6.7/(10.9) 8.7/(17.6) 13.6/(8.4) 15.0/(10.1) 22.6/(22.7) 24.5/(26.3) 27.2/(8.4) 012-AWS 018-AWS 024-AWS 032-AWS 040-AWS 048-AWS 060-AWS 072-AWS 084-AWS 120-AWS 75°FDB/62.5°FWB Total 19,450 26,760 30,590 35,200 45,190 72,100 79,070 115,660 124,650 143,530 (8°F ∆Tw) Sensible 14,380 20,310 23,570 27,140 35,750 56,180 62,130 86,120 93,710 111,680 GPM/(Ft.) 4.9/(14.5) 6.7/(25.9) 7.6/(33.2) 8.8/(17.9) 11.3/(28.4) 18.1/(14.3) 19.9/(17.1) 28.9/(35.8) 31.2/(41.1) Total 17,880 24,830 28,560 32,460 42,280 65,300 72,010 108,750 117,090 129,920 Sensible 13,620 19,360 22,540 25,730 24,220 52,790 58,560 82,780 90,030 104,910 GPM/(Ft.) 3.6/(8.2) 5.0/(15.1) 5.7/(19.3) 6.5/(10.2) 8.5/(16.7) 13.1/(7.9) 14.5/(9.6) 21.8/(21.4) 23.5/(24.5) 26.2/(7.9) Total 16,370 22,860 26,690 29,890 39,060 58,870 65,240 101,470 110,240 117,060 Sensible 12,880 18,360 21,440 24,390 32,470 49,420 54,950 79,230 86,610 98,170 GPM/(Ft.) 2.8/(5.0) 3.8/(9.2) 4.4/(11.9) 5.0/(6.3) 6.5/(10.2) 9.9/(4.7) 11.0/(5.7) 17.0/(13.6) 18.5/(15.8) 19.8/(4.7) 012-AWS 018-AWS 024-AWS 032-AWS 040-AWS 048-AWS 060-AWS 072-AWS 084-AWS 120-AWS Med Flow (10°F ∆Tw) Low Flow (12°F ∆Tw) 72°FDB/60°FWB 36.2/(14.3) High Flow Total 16,130 22,430 25,760 29,550 38,380 59,940 65,890 97,760 105,340 119,190 (8°F ∆Tw) Sensible 12,960 18,450 21,470 24,590 32,650 50,840 56,300 78,590 85,540 100,990 GPM/(Ft.) 4.1/(10.4) 5.7/(19.0) 6.4/(24.0) 7.4/(13.0) 9.6/(21.0) 15.1/(10.2) 16.6/(12.3) 24.5/(26.4) 26.4/(30.3) 30.2/(10.2) Med Flow Total 14,790 20,650 23,870 27,110 35,430 53,890 59,500 91,990 99,230 107,110 (10°F ∆Tw) Sensible 12,270 17,500 20,430 23,230 30,950 47,500 52,690 75,630 82,350 94,310 GPM/(Ft.) 3.0/(5.9) 4.2/(10.8) 4.8/(14.0) 5.4/(7.4) 7.1/(12.1) 10.8/(5.6) 12.0/(6.8) 18.5/(15.8) 20.0/(18.2) Low Flow Total 13,530 18,980 21,970 24,850 32,490 47,370 52,240 84,910 92,170 94,070 (12°F ∆Tw) Sensible 11,590 16,540 19,310 21,920 29,140 43,510 48,160 71,880 78,490 86,340 GPM/(Ft.) 2.3/(3.4) 3.2/(6.6) 3.7/(8.6) 4.2/(4.5) 5.4/(7.3) 8.0/(3.2) 8.8/(3.8) 14.2/(9.9) 15.5/(11.4) 16.0/(3.2) 21.6/(5.6) Cooling Capacities (BTU/H) for 50°F Chilled Water Entering the Cooling Coil 80°FDB/67°FWB 012-AWS 018-AWS 024-AWS 032-AWS 040-AWS 048-AWS 060-AWS 072-AWS 084-AWS 120-AWS High Flow Total 17,340 23,720 27,070 31,550 40,300 64,160 69,840 102,640 110,880 127,640 (8°F ∆Tw) Sensible 12,970 18,360 21,350 24,670 32,580 51,150 56,420 77,640 84,770 101,610 GPM/(Ft.) 4.4/(11.6) 6.0/(20.6) 6.8/(26.0) 7.9/(14.5) 10.1/(22.7) 16.1/(11.4) 17.6/(13.4) 25.7/(28.3) 27.9/(32.7) 32.2/(11.4) Med Flow Total 15,870 22,110 25,390 29,130 36,840 58,670 64,760 96,430 103,990 116,670 (10°F ∆Tw) Sensible 12,330 17,620 20,530 23,520 31,310 48,530 53,880 74,920 81,700 96,380 GPM/(Ft.) 3.2/(6.5) 4.5/(12.0) 5.1/(15.3) 5.8/(8.2) 7.6/(13.4) 11.8/(6.4) 13.1/(7.8) 19.4/(16.9) 21.0/(19.5) 23.6/(6.4) Low Flow Total 14,570 20,410 23,660 26,770 35,130 52,860 58,460 91,030 97,870 105,040 (12°F ∆Tw) Sensible 11,730 16,780 19,640 22,320 29,840 45,480 50,480 72,410 78,760 90,280 GPM/(Ft.) 2.5/(4.0) 3.4/(7.4) 4.0/(9.7) 4.5/(5.1) 5.9/(8.3) 8.9/(3.8) 9.9/(4.6) 15.3/(10.9) 16.4/(12.5) 17.8/(3.8) 012-AWS 018-AWS 024-AWS 032-AWS 040-AWS 048-AWS 060-AWS 072-AWS 084-AWS 120-AWS 75°FDB/62.5°FWB High Flow Total 12,100 16,730 19,200 22,380 28,770 43,580 45,430 75,480 80,860 86,480 (8°F ∆Tw) Sensible 10,990 15,610 18,170 20,880 27,580 42,410 45,430 67,760 73,570 84,150 GPM/(Ft.) 3.1/(6.1) 4.2/(10.9) 4.8/(14.0) 5.7/(7.8) 7.2/(12.3) 11.0/(5.6) 11.5/(6.1) 19.0/(16.3) 20.4/(18.6) Med Flow Total 10,900 14,880 16,960 19,860 23,400 36,050 39,970 71,720 76,250 71,430 (10°F ∆Tw) Sensible 10,270 14,430 16,690 19,290 23,400 36,050 39,970 65,350 70,550 71,430 GPM/(Ft.) 2.2/(3.3) 3.0/(5.8) 3.4/(7.4) 4.0/(4.2) 4.8/(5.7) 7.3/(2.7) 8.2/(3.3) 14.4/(9.9) 15.4/(11.2) 22.0/(5.6) 14.6/(2.7) Low Flow Total 8,710 12,380 14,420 15,370 20,380 30,000 33,350 54,330 59,290 59,330 (12°F ∆Tw) Sensible 8,710 12,380 14,420 15,370 20,380 30,000 33,350 54,330 59,290 59,330 GPM/(Ft.) 1.5/(1.3) 2.1/(2.9) 2.4/(3.9) 2.6/(1.7) 3.5/(3.1) 5.1/(1.2) 5.7/(1.6) 9.2/(4.4) 10.0/(5.1) 10.2/(1.2) 012-AWS 018-AWS 024-AWS 032-AWS 040-AWS 048-AWS 060-AWS 072-AWS 084-AWS 120-AWS 72°FDB/60°FWB High Flow Total 8,950 12,720 14,820 16,220 21,520 33,560 37,150 55,560 60,470 66,440 (8°F ∆Tw) Sensible 8,950 12,720 14,820 16,220 21,520 33,560 37,150 55,560 60,470 66,440 GPM/(Ft.) 2.3/(3.5) 3.2/(6.6) 3.7/(8.7) 4.1/(4.3) 5.5/(7.3) 8.5/(3.5) 9.5/(4.3) 14.1/(9.5) 15.4/(11.1) 17.0/(3.5) Med Flow Total 7,930 11,260 13,120 14,070 18,640 27,890 30,910 49,330 53,790 55,100 (10°F ∆Tw) Sensible 7,930 11,260 13,120 14,070 18,640 27,890 30,910 49,330 53,790 55,100 GPM/(Ft.) 1.6/(1.6) 2.3/(3.5) 2.7/(4.6) 2.9/(2.1) 3.8/(3.7) 5.7/(1.6) 6.4/(2.0) 10.0/(5.1) 11.0/(6.0) - Alternate Water Source @ 42°F / 50°F EWT High Flow Performance Data Cooling Capacities (BTU/H) for 42°F Chilled Water Entering the Cooling Coil 80°FDB/67°FWB 11.4/(1.6) Low Flow Total 6,690 9,550 11,140 11,500 15,340 20,870 23,350 41,390 45,320 41,060 (12°F ∆Tw) Sensible 6,690 9,550 11,140 11,500 15,340 20,870 23,350 41,390 45,320 41,060 GPM/(Ft.) 1.1/(0.7) 1.6/(1.6) 1.9/(2.3) 2.0/(0.8) 2.6/(1.7) 3.6/(0.5) 4.1/(0.7) 7.0/(2.7) 7.7/(3.2) 7.2/(0.5) (Note: The above Net Cooling capacities include standard motor heat @ standard CFM/e.s.p. as shown on page 4-24 & 4-25, Evaporator Blower/Motor.) Air Technology Systems, Inc. 4-28 Electrical Data - Index Electrical Data CeilAiR Ceiling AC's FLA / MCA / MFS INDEX MODEL TYPE ...........................................page DX - Compressorized Systems Free-Cooling & Alternate Water Source - Index Single Compressor Systems: Single Circuit Systems: • OHS-012 thru 040-AS........................................................ 5-2 • OHS-012 thru 040-HAR, HW, HG-FC/AWS......................... 5-7 • OHS-048 thru 060-AR, W, G-FC/AWS................................. 5-7 • OHS-012 thru 024-AR, W & G............................................ 5-2 • OHS-032 thru 060-AR, W & G............................................ 5-3 Dual Compressor Systems: Dual Circuit Systems: • OHS-048 thru 120-DAR, DW, DG-FC/AWS......................... 5-8 • OHS-048 thru 120-DAR, DW & DG.................................... 5-4 Air Technology Systems, Inc DX - Air Handling Units Chilled Water Systems Single Circuit Systems: • OHS-012 thru 120-C.......................................................... 5-9 • OHS-012 thru 060-AHU..................................................... 5-5 Dual Circuit Systems: • OHS-048 thru 120-DAHU................................................... 5-6 << Electrical Data Notes >> 1) Electrical Data is based on standard performance and component selection per Section 4 of this brochure. Please consult your local Sales Representative for "special" equipment electrical data. 2) High Static Pressure Belt-Drive Option - Electrical Data in the pages to follow are based on Standard CFM's and External Static Pressures. Please Consult your local Sales Representative for component and electrical rating data for this Option. 5-1 Air Technology Systems, Inc. Electrical Data OHS-012-AS FLA MCA MFS OHS-018-AS FLA MCA OHS-024-AS MFS FLA MCA OHS-032-AS MFS OHS-040-AS FLA MCA MFS FLA MCA MFS OHS-048-AS OHS-060-AS FLA FLA MCA MFS MCA COOLING ONLY, with or without Hot Gas, Hot Water or Steam Reheat 208/1/60 11.7 14.4 20 13.2 17.6 25 15.4 23.0 30 19.2 27.2 35 20.0 29.5 40 N/A N/A 277/1/60 9.8 12.2 15 11.0 14.7 20 13.7 20.2 25 16.5 24.0 30 18.0 25.2 35 N/A N/A 208/3/60 N/A N/A 12.5 16.8 25 15.0 20.1 30 15.8 21.4 30 N/A N/A 460/3/60 N/A N/A 7.4 9.5 15 8.3 10.9 15 9.9 12.6 15 N/A N/A COOLING and ELECTRIC REHEAT/HEAT, with or without Humidifier 208/1/60 34.4 42.8 45 35.9 46.0 50 38.1 51.4 60 41.9 55.6 60 42.7 57.9 70 N/A N/A 277/1/60 27.8 34.8 35 29.9 38.3 40 31.8 42.7 45 34.5 46.5 50 36.1 47.7 50 N/A N/A 208/3/60 N/A N/A 25.6 33.2 35 28.1 36.5 40 28.9 37.8 45 N/A N/A 460/3/60 N/A N/A 13.6 17.3 20 14.5 18.7 20 16.1 20.5 25 N/A N/A COOLING and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat) 208/1/60 19.9 22.6 25 21.4 25.8 35 23.6 31.2 45 27.4 35.4 50 28.2 37.7 50 N/A N/A 277/1/60 16.0 18.4 20 17.9 21.5 25 19.9 26.4 35 22.7 30.2 40 24.2 31.4 45 N/A N/A 208/3/60 N/A N/A 20.7 25.0 30 23.2 28.3 35 24.0 29.6 40 N/A N/A 460/3/60 N/A N/A 11.1 13.2 15 12.0 14.6 20 13.6 16.3 20 N/A N/A 208/1/60 25.4 31.8 35 25.4 31.8 35 25.4 31.8 35 26.1 32.7 35 26.5 33.2 35 N/A N/A 277/1/60 20.6 25.7 30 21.2 26.5 30 20.6 25.7 30 20.8 25.9 30 22.0 27.4 30 N/A N/A 208/3/60 N/A N/A 15.8 19.8 20 16.5 20.7 20 16.9 21.4 25 N/A N/A 460/3/60 N/A N/A 7.9 9.8 15 8.3 10.9 15 9.9 12.6 15 N/A N/A Model FLA (OEM Rated) OHS-012-AR, W, & G AR W G MCA OHS-018-AR, W, & G MFS FLA (OEM Rated) AR W G OHS-024-AR, W, & G MCA MFS FLA (OEM Rated) AR W G MCA MFS COOLING ONLY, with or without Hot Gas, Hot Water or Steam Reheat 208/1/60 8.8 8.0 9.0 11.5 15 9.9 8.3 10.4 14.3 20 12.1 10.1 12.7 19.7 30 277/1/60 7.6 6.9 7.7 10.0 15 8.3 7.0 8.7 12.0 15 10.3 8.6 10.8 16.8 25 208/3/60 N/A N/A 9.3 8.2 9.6 13.5 20 460/3/60 N/A N/A 4.9 4.4 5.1 7.0 15 COOLING and ELECTRIC REHEAT/HEAT only, (No Humidifier) 208/1/60 31.5 30.7 31.7 39.9 40 32.6 31.0 33.1 42.7 45 34.8 32.8 35.4 48.1 50 277/1/60 25.6 24.9 25.8 32.6 35 27.2 25.8 27.6 35.6 40 28.4 26.7 28.9 39.3 45 208/3/60 N/A N/A 22.4 21.3 22.7 29.9 35 460/3/60 N/A N/A 11.2 10.6 11.3 14.8 15 COOLING and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat) 208/1/60 17.0 16.2 17.2 19.7 25 18.1 16.5 18.6 22.5 30 20.3 18.3 20.9 27.9 277/1/60 13.8 13.1 13.9 16.2 20 15.1 13.8 15.5 18.8 25 16.5 14.8 17.0 23.0 40 30 208/3/60 N/A N/A 17.5 16.4 17.8 21.7 30 460/3/60 N/A N/A 8.6 8.1 8.8 10.7 15 - DX Compressorized Systems COOLING and ELECTRIC HEAT only, (No Electric Reheat or Humidifier) MFS Electrical Data Model - DX Compressorized Systems COOLING and ELECTRIC HEAT only, (No Electric Reheat or Humidifier) 208/1/60 25.4 25.4 25.4 31.8 35 25.4 25.4 25.4 31.8 35 25.4 25.4 25.4 31.8 35 277/1/60 20.6 20.6 20.6 25.7 30 21.2 21.2 21.2 26.5 30 20.6 20.6 20.6 25.7 30 208/3/60 N/A N/A 15.8 15.8 15.8 19.8 20 460/3/60 N/A N/A 7.9 7.9 7.9 9.8 15 34.8 33.6 35.4 48.1 50 COOLING and ELECTRIC REHEAT/HEAT and HUMIDIFIER 208/1/60 33.6 33.6 33.6 42.0 45 33.6 33.6 33.6 42.7 45 277/1/60 26.8 26.8 26.8 33.4 35 28.0 28.0 28.0 35.6 40 28.4 26.8 28.9 39.3 45 208/3/60 N/A N/A 24.0 24.0 24.0 30.0 35 460/3/60 N/A N/A 11.6 11.6 11.6 14.8 15 Air Technology Systems, Inc. (*) Current Draws are given in the following order: FLA MCA MFS FLA = Full Load Amps MCA = Minimum Circuit Amps (wire size amps) MFS = Maximum Fuse Size 5-2 Electrical Data Electrical Data Model - DX Compressorized Systems  OHS-032-AR, W, & G FLA (OEM Rated) AR W G MCA OHS-040-AR, W, & G MFS FLA (OEM Rated) AR W G OHS-048-AR, W, & G MCA MFS FLA (OEM Rated) AR W G MCA OHS-060-AR, W, & G MFS FLA (OEM Rated) AR W G MCA MFS COOLING ONLY, with or without Hot Gas, Hot Water or Steam Reheat 208/1/60 15.9 13.4 16.6 23.9 35 16.7 14.1 17.5 26.2 40 N/A 277/1/60 13.1 11.0 13.7 20.6 30 14.6 12.4 15.3 21.8 30 N/A N/A 208/3/60 11.7 10.5 12.1 16.8 25 12.5 11.3 12.9 18.1 25 17.1 15.0 17.8 24.4 45 19.9 17.5 20.7 31.2 45 460/3/60 5.8 5.2 6.0 8.4 15 7.4 6.8 7.6 10.1 15 8.7 7.4 9.1 12.5 15 10.2 9.0 10.6 15.4 25 N/A COOLING and ELECTRIC REHEAT/HEAT only, (No Humidifier) 208/1/60 38.6 36.1 39.3 52.3 60 39.4 36.8 40.2 54.6 60 N/A 277/1/60 31.1 29.1 31.7 43.1 50 32.7 30.5 33.3 44.3 50 N/A N/A 208/3/60 24.8 23.6 25.2 33.2 40 25.6 24.4 26.0 34.5 40 43.3 41.2 44.0 57.2 70 46.1 43.7 46.9 64.0 70 460/3/60 12.0 11.4 12.2 16.2 20 13.6 13.0 13.8 18.0 20 21.3 20.0 21.7 28.1 30 22.8 21.6 23.2 31.1 35 N/A COOLING and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat) 208/1/60 24.1 21.6 24.8 32.1 45 24.9 22.3 25.7 34.4 50 N/A 277/1/60 19.3 17.2 19.9 26.8 40 20.8 18.6 21.5 28.0 40 N/A N/A 208/3/60 19.9 18.7 20.3 25.0 35 20.7 19.5 21.1 26.3 35 33.5 31.4 34.2 40.8 60 36.3 33.9 37.1 47.6 60 460/3/60 9.5 8.9 9.7 12.1 15 11.1 10.5 11.3 13.8 15 16.1 14.8 16.5 19.9 25 17.6 16.4 18.0 22.8 30 N/A - DX Compressorized Systems COOLING and ELECTRIC HEAT only, (No Electric Reheat or Humidifier) 208/1/60 26.1 26.1 26.1 32.7 35 26.5 26.5 26.5 33.2 35 N/A 277/1/60 20.8 20.8 20.8 25.9 30 22.0 22.0 22.0 27.4 30 N/A N/A 208/3/60 16.5 16.5 16.5 20.7 25 16.9 16.9 16.9 21.2 25 30.1 30.1 30.1 37.7 40 31.5 31.5 31.5 39.4 40 460/3/60 7.9 7.9 7.9 9.8 15 9.3 9.3 9.3 11.6 15 14.8 14.8 14.8 18.4 20 15.5 15.5 15.5 19.3 20 N/A COOLING and ELECTRIC REHEAT/HEAT and HUMIDIFIER 208/1/60 38.6 36.1 39.3 52.3 60 39.4 36.8 40.2 54.6 60 N/A 277/1/60 31.1 29.1 31.7 43.1 50 32.7 30.5 33.3 44.3 50 N/A N/A 208/3/60 24.8 24.7 25.2 33.2 40 25.6 25.1 26.0 34.5 40 46.5 46.5 46.5 58.2 70 47.9 47.9 47.9 64.0 70 460/3/60 12.0 11.6 12.2 16.2 20 13.6 13.0 13.8 18.0 20 22.2 22.2 22.2 28.1 30 22.9 22.9 23.2 31.1 35 Air Technology Systems, Inc 5-3 Air Technology Systems, Inc. N/A Electrical Data - DUAL DX FLA (OEM rated) DAR DW DG MCA OHS-072-DAR, DW, & DG MFS FLA (OEM rated) DAR DW DG MCA OHS-084-DAR, DW, & DG MFS FLA (OEM rated) DAR DW DG MCA OHS-120-DAR, DW, & DG MFS FLA (OEM rated) DAR DW DG MCA MFS Electrical Data OHS-048-DAR, DW, & DG Model COOLING ONLY, with or without Hot Gas, Hot Water or Steam Reheat 208/1/60 N/A N/A N/A 277/1/60 N/A N/A N/A N/A N/A 208/3/60 16.7 14.5 17.3 22.9 30 22.7 20.3 23.5 31.0 40 29.3 25.7 30.5 40.7 50 37.9 33.1 39.5 55.3 70 460/3/60 8.6 7.5 8.9 11.7 15 11.6 10.4 12.0 15.7 20 14.9 13.1 15.5 20.6 30 19.2 16.8 20.0 27.1 35 COOLING and ELECTRIC REHEAT/HEAT only, (No Humidifier) 208/1/60 N/A N/A N/A 277/1/60 N/A N/A N/A N/A N/A 208/3/60 36.3 35.2 36.6 47.1 50 40.2 39.0 40.6 52.4 60 44.3 42.5 44.9 58.5 70 49.5 47.1 50.3 67.4 80 460/3/60 17.9 17.3 18.0 23.1 25 19.8 19.2 20.0 25.7 30 21.9 21.0 22.2 28.8 35 24.5 23.3 24.9 32.8 40 COOLING and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat) 208/1/60 N/A N/A N/A 277/1/60 N/A N/A N/A N/A N/A 208/3/60 33.1 30.9 33.7 39.3 45 36.9 34.5 37.7 45.2 50 43.5 39.9 44.7 54.9 60 52.1 47.3 53.7 69.5 80 460/3/60 16.0 14.9 16.3 19.1 20 18.0 16.8 18.4 22.1 25 21.3 19.5 21.9 27.0 35 25.6 23.2 26.4 33.5 40 208/1/60 N/A N/A N/A 277/1/60 N/A N/A N/A N/A N/A 208/3/60 29.7 29.7 29.7 37.2 40 31.5 31.5 31.5 39.4 45 33.1 33.1 33.1 41.4 45 37.9 34.9 39.5 55.3 70 460/3/60 14.6 14.6 14.6 18.2 20 15.5 15.5 15.5 19.3 25 16.3 16.3 16.3 20.6 25 19.2 17.2 20.0 27.1 35 COOLING and ELECTRIC REHEAT/HEAT and HUMIDIFIER 208/1/60 N/A N/A N/A 277/1/60 N/A N/A N/A N/A N/A 208/3/60 46.1 46.1 46.1 57.7 60 45.7 45.7 45.7 57.2 60 47.3 47.3 47.3 59.2 70 52.1 49.1 53.7 69.5 80 460/3/60 22.0 22.0 22.0 27.4 30 21.9 21.9 21.9 27.3 30 22.7 22.7 22.7 26.7 35 25.6 23.6 26.4 33.5 40 Dual Compressor Systems with C-Tech-10 Microprocessor (see Note-1) OHS-048-DAR, DW, & DG Model FLA (OEM rated) DAR DW DG MCA OHS-072-DAR, DW, & DG MFS FLA (OEM rated) DAR DW DG MCA OHS-084-DAR, DW, & DG MFS FLA (OEM rated) DAR DW DG MCA OHS-120-DAR, DW, & DG MFS FLA (OEM rated) DAR DW DG MCA MFS COOLING and ELECTRIC REHEAT/HEAT only, (No Humidifier) 208/1/60 N/A N/A N/A 277/1/60 N/A N/A N/A N/A N/A 208/3/60 42.9 40.7 43.5 55.7 60 48.9 46.5 49.7 63.8 70 55.5 51.9 56.7 73.5 80 64.1 59.3 65.7 88.1 100 460/3/60 21.2 20.1 21.5 27.4 30 24.2 23.0 24.6 31.4 35 27.5 25.7 28.1 36.3 40 31.8 29.4 32.6 42.8 45 COOLING and ELECTRIC REHEAT/HEAT and HUMIDIFIER 208/1/60 N/A N/A N/A 277/1/60 N/A N/A N/A N/A N/A 208/3/60 46.1 46.1 46.1 57.7 60 48.9 46.5 49.7 63.8 70 55.5 51.9 56.7 73.5 80 64.1 59.3 65.7 88.1 100 460/3/60 22.0 22.0 22.0 27.4 30 24.2 23.0 24.6 31.4 35 27.5 25.7 28.1 36.3 40 31.8 29.4 32.6 42.8 45 Note-1: Dual compressor systems incorporating C-Tech-10 controls provide 2(two) compressor stages of Cooling and 2(two) compressor stages of Dehumidification. The A-Tech-1.2 and A-Tech-20 controls provide 2(two) compressor stages of Cooling and 1(one) compressor stage of Dehumidification. Therefore, electrical data for dual compressor systems with dehumidification mode (reheat) is controller dependent as shown above. Air Technology Systems, Inc. (*) Current Draws are given in the following order: FLA MCA - Dual DX & Remote Air Cooled Condensers COOLING and ELECTRIC HEAT only, (No Electric Reheat or Humidifier) MFS FLA = Full Load Amps MCA = Minimum Circuit Amps (wire size amps) MFS = Maximum Fuse Size 5-4 Electrical Data Electrical Data Model OHS-012-AHU FLA MCA - Air Cooled "AHU / RCU" OHS-018-AHU MFS FLA MCA OHS-024-AHU MFS OHS-032-AHU FLA MCA MFS FLA MCA MFS COOLING ONLY, with or without Hot Gas, Hot Water or Steam Reheat 208/1/60 2.7 3.4 15 2.7 3.4 15 2.7 3.4 15 3.4 4.3 15 277/1/60 2.5 3.1 15 2.5 3.1 15 2.5 3.1 15 2.7 3.4 15 208/3/60 2.7 3.4 15 2.7 3.4 15 2.7 3.4 15 3.4 4.3 15 460/3/60 1.6 2.0 15 1.6 2.0 15 1.6 2.0 15 1.6 2.0 15 COOLING and ELECTRIC REHEAT/HEAT only, (No Humidifier) 208/1/60 25.4 31.8 35 25.4 31.8 35 25.4 31.8 35 26.1 32.7 35 277/1/60 20.6 25.7 30 20.6 25.7 30 20.6 25.7 30 20.8 25.9 30 208/3/60 15.8 19.8 20 15.8 19.8 20 15.8 19.8 20 16.5 20.7 25 460/3/60 7.9 9.8 15 7.9 9.8 15 7.9 9.8 15 7.9 9.8 15 COOLING and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat) 208/1/60 10.9 13.6 15 10.9 13.6 15 10.9 13.6 15 11.6 14.5 15 277/1/60 8.7 10.9 15 8.7 10.9 15 8.7 10.9 15 8.9 11.1 15 208/3/60 10.9 13.6 15 10.9 13.6 15 10.9 13.6 15 11.6 14.5 15 460/3/60 5.3 6.6 15 5.3 6.6 15 5.3 6.6 15 5.3 6.6 15 COOLING and ELECTRIC HEAT only, (No Electric Reheat or Humidifier) - Air Cooled ("AHU / RCU") 208/1/60 25.4 31.8 35 25.4 31.8 35 25.4 31.8 35 26.1 32.7 35 277/1/60 20.6 35.7 30 20.6 25.7 30 20.6 25.7 30 20.8 25.9 30 208/3/60 15.8 19.8 20 15.8 19.8 20 15.8 19.8 20 16.5 20.7 25 460/3/60 7.9 9.8 15 7.9 9.8 15 7.9 9.8 15 7.9 9.8 15 COOLING with ELECTRIC REHEAT/HEAT and HUMIDIFIER 208/1/60 33.6 42.0 45 33.6 42.0 45 33.6 42.0 45 34.3 42.9 45 277/1/60 26.8 33.4 35 26.8 33.4 35 26.8 33.4 35 27.7 33.7 35 208/3/60 24.0 30.0 30 24.0 30.0 30 24.0 30.0 30 24.7 30.9 35 460/3/60 11.6 14.5 15 11.6 14.5 15 11.6 14.5 15 11.6 14.5 15 Air Technology Systems, Inc Model OHS-040-AHU FLA MCA OHS-048-AHU MFS FLA MCA OHS-060-AHU MFS FLA MCA MFS COOLING ONLY, with or without Hot Gas, Hot Water or Steam Reheat 208/1/60 3.8 4.8 15 N/A 277/1/60 3.9 4.9 15 N/A N/A 208/3/60 3.8 4.8 15 3.9 4.9 15 5.3 6.6 15 460/3/60 3.0 3.8 15 2.2 2.8 15 2.9 3.6 15 N/A COOLING and ELECTRIC REHEAT/HEAT only, (No Humidifier) 208/1/60 26.5 33.2 35 N/A N/A 277/1/60 22.0 27.4 30 N/A N/A 208/3/60 16.9 21.2 25 30.1 37.7 40 31.5 39.4 40 460/3/60 9.3 11.6 15 14.8 18.4 20 15.5 19.3 20 COOLING and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat) 208/1/60 12.0 15.0 20 N/A N/A 277/1/60 10.1 12.6 15 N/A N/A 208/3/60 12.0 15.0 20 20.3 25.4 30 21.7 27.1 30 460/3/60 6.7 8.4 15 9.6 12.0 15 10.3 12.9 15 (*) Current Draws are given in the following order: COOLING and ELECTRIC HEAT only, (No Electric Reheat or Humidifier) N/A 26.5 33.2 35 N/A 277/1/60 22.0 27.4 30 208/3/60 16.9 21.2 25 30.1 37.7 40 31.5 39.4 40 460/3/60 9.3 11.6 15 14.8 18.4 20 15.5 19.3 20 N/A COOLING with ELECTRIC REHEAT/HEAT and HUMIDIFIER 5-5 208/1/60 34.7 43.4 45 N/A 277/1/60 28.2 35.2 40 N/A N/A 208/3/60 25.1 31.4 35 46.5 58.2 60 47.9 59.9 60 460/3/60 13.0 16.2 20 22.2 27.7 30 22.9 28.6 30 N/A Air Technology Systems, Inc. MCA MFS FLA = Full Load Amps MCA = Minimum Circuit Amps (wire size amps) MFS = Maximum Fuse Size 208/1/60 N/A FLA Electrical Data OHS-048-DAHU FLA MCA OHS-072-DAHU MFS FLA MCA OHS-084-DAHU MFS FLA MCA OHS-120-DAHU MFS FLA MCA Electrical Data Model - Air Cooled "DAHU / DRCU MFS COOLING ONLY, with or without Hot Gas, Hot Water or Steam Reheat 208/1/60 N/A N/A N/A N/A 277/1/60 N/A N/A N/A N/A 208/3/60 3.5 4.4 15 5.3 6.6 15 6.9 8.6 15 8.7 10.9 15 460/3/60 2.0 2.5 15 2.9 3.6 15 3.7 4.6 15 4.6 5.8 15 COOLING and ELECTRIC REHEAT/HEAT only, (No Humidifier) 208/1/60 N/A 277/1/60 N/A N/A N/A N/A N/A N/A N/A 208/3/60 29.7 37.2 40 31.5 39.4 45 33.1 41.4 45 34.9 43.7 45 460/3/60 14.6 18.2 20 15.5 19.3 25 16.3 20.3 25 17.2 21.4 25 COOLING and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat) 208/1/60 N/A N/A N/A N/A 277/1/60 N/A N/A N/A N/A 19.9 24.9 25 19.5 24.4 30 21.1 26.4 30 22.9 28.6 30 460/3/60 9.4 11.8 15 9.3 11.6 15 10.1 12.6 15 11.0 13.8 15 - Air Cooled ("DAHU / DRCU") 208/3/60 COOLING and ELECTRIC HEAT only, (No Electric Reheat or Humidifier) 208/1/60 N/A 277/1/60 N/A N/A N/A N/A N/A N/A N/A 208/3/60 29.7 37.2 40 31.5 39.4 45 33.1 41.4 45 34.9 43.7 45 460/3/60 14.6 18.2 20 15.5 19.3 25 16.3 20.3 25 17.2 21.4 25 COOLING with ELECTRIC REHEAT/HEAT and HUMIDIFIER 208/1/60 N/A N/A N/A N/A 277/1/60 N/A N/A N/A N/A 208/3/60 46.1 57.7 60 45.7 57.2 60 47.3 59.2 60 49.1 61.4 70 460/3/60 22.0 27.4 30 21.9 27.3 30 22.7 28.3 30 23.6 29.4 30 (*) Current Draws are given in the following order: FLA MCA MFS FLA = Full Load Amps MCA = Minimum Circuit Amps (wire size amps) MFS = Maximum Fuse Size Air Technology Systems, Inc. 5-6 Electrical Data - Free-Cooling & Alternate Water Source Electrical Data OHS-012-HAR, HW, & HG AWS or FC Model FLA (OEM rated) HAR HW HG MCA OHS-018-HAR, HW, & HG AWS or FC MFS FLA (OEM rated) HAR HW HG 9.1 11.2 OHS-024-HAR, HW, & HG AWS or FC MCA MFS 15.1 20 FLA (OEM rated) HAR HW HG 14.1 12.1 14.7 MCA MFS 21.7 30 COOLING ONLY, with or without Hot Water or Steam Reheat 208/1/60 9.1 8.3 9.3 11.8 15 10.7 277/1/60 N/A N/A N/A 208/3/60 N/A N/A 8.7 7.6 9.0 12.9 20 460/3/60 N/A N/A 4.6 4.1 4.8 6.7 15 36.8 34.8 37.4 50.1 60 COOLING and ELECTRIC REHEAT/HEAT only, (No Humidifier) 208/1/60 31.8 31.0 32.0 40.2 45 33.4 31.8 33.9 43.5 45 277/1/60 N/A N/A N/A 208/3/60 N/A N/A 21.8 20.7 22.1 29.3 30 460/3/60 N/A N/A 10.9 10.3 11.0 14.5 15 COOLING and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat) 208/1/60 17.3 16.5 17.5 20.0 25 18.9 17.3 19.4 23.3 30 22.3 20.3 - Free-Cooling & Alternate Water Source 277/1/60 N/A N/A 208/3/60 N/A N/A 16.9 15.8 460/3/60 N/A N/A 8.3 7.8 27.4 27.4 22.9 29.9 40 17.2 21.1 25 8.5 10.4 15 27.4 34.3 35 N/A COOLING and ELECTRIC HEAT only, (No Electric Reheat or Humidifier) 208/1/60 25.7 25.7 25.7 32.2 35 26.2 26.2 26.2 32.8 35 277/1/60 N/A N/A N/A 208/3/60 N/A N/A 15.2 15.2 15.2 19 20 460/3/60 N/A N/A 7.6 7.6 7.6 9.5 15 (*) Current Draws are given in the following order: COOLING and ELECTRIC REHEAT/HEAT and HUMIDIFIER FLA MCA MFS Air Technology Systems, Inc 208/1/60 33.9 33.9 33.9 42.4 45 34.4 34.4 34.4 43.5 45 36.8 35.6 277/1/60 N/A N/A 208/3/60 N/A N/A 23.4 23.4 460/3/60 N/A N/A 11.3 11.3 Model OHS-032-HAR, HW, & HG AWS or FC FLA (OEM rated) HAR HW HG MCA FLA (OEM rated) HAR HW HG 50.1 60 23.4 29.3 30 11.3 14.5 15 N/A OHS-040-HAR, HW, & HG AWS or FC MFS 37.4 FLA = Full Load Amps MCA = Minimum Circuit Amps (wire size amps) MFS = Maximum Fuse Size OHS-048-AR, W, & G AWS or FC MCA MFS 28.0 45 FLA (OEM rated) AR W G MCA OHS-060 AR, W, & G AWS or FC MFS FLA (OEM rated) AR W G MCA MFS COOLING ONLY, with or without Hot Water or Steam Reheat 208/1/60 17.2 14.7 277/1/60 17.9 25.2 40 18.5 15.9 N/A 19.3 N/A N/A N/A N/A N/A 208/3/60 10.4 9.2 10.8 15.5 25 12.2 11.0 12.6 17.8 25 18.5 16.4 19.2 25.8 40 21.5 19.1 22.3 32.8 50 460/3/60 5.5 4.9 5.7 8.1 15 6.4 5.8 6.6 9.1 15 9.4 8.1 9.8 13.5 20 11.0 9.8 11.4 16.2 25 42.0 56.4 60 COOLING and ELECTRIC REHEAT/HEAT only, (No Humidifier) 208/1/60 39.9 37.4 277/1/60 40.6 53.6 60 41.2 38.6 N/A N/A N/A N/A N/A N/A 208/3/60 23.5 22.3 23.9 31.9 35 25.3 24.1 25.7 34.2 40 44.7 42.6 45.4 58.6 60 47.7 45.3 48.5 65.6 70 460/3/60 11.7 11.1 11.9 15.9 20 12.6 12.0 12.8 17.0 20 22.0 20.7 22.4 28.8 30 23.6 22.4 24.0 31.9 35 COOLING and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat) 208/1/60 25.4 22.9 277/1/60 26.1 33.4 45 26.7 24.1 N/A 27.5 36.2 50 N/A N/A N/A N/A N/A 208/3/60 18.6 17.4 19.0 23.7 30 20.4 19.2 20.8 26.0 35 34.9 32.8 35.6 42.2 50 37.9 35.5 38.7 49.2 60 460/3/60 9.2 8.6 9.4 11.8 15 10.1 9.5 10.3 12.8 15 16.8 15.5 17.2 20.6 25 18.4 17.2 18.8 23.6 30 35.4 45 COOLING and ELECTRIC HEAT only, (No Electric Reheat or Humidifier) 208/1/60 27.4 27.4 277/1/60 27.4 34.3 40 28.3 28.3 N/A 28.3 N/A N/A N/A N/A N/A 208/3/60 15.2 15.2 15.2 19.0 25 16.6 16.6 16.6 20.8 25 31.5 31.5 31.5 39.4 40 33.1 33.1 33.1 41.4 50 460/3/60 7.6 7.6 7.6 9.5 15 8.3 8.3 8.3 10.3 15 15.5 15.5 15.5 19.3 20 16.3 16.3 16.3 20.3 25 38.6 42.0 56.4 60 COOLING and ELECTRIC REHEAT/HEAT and HUMIDIFIER 208/1/60 39.9 37.4 277/1/60 5-7 40.6 53.6 60 41.2 N/A N/A N/A N/A N/A N/A 208/3/60 23.5 23.4 23.9 31.9 35 25.3 24.8 25.7 34.2 40 47.9 47.9 47.9 59.9 60 49.5 49.5 49.5 65.6 70 460/3/60 11.7 11.3 11.9 15.9 20 12.6 12.0 12.8 17.0 20 22.9 22.9 22.9 28.8 30 23.7 23.7 24.0 31.9 35 Air Technology Systems, Inc. Electrical Data OHS-048-DAR, DW, & DG AWS or FC FLA (OEM rated) DAR DW DG MCA OHS-072-DAR, DW, & DG AWS or FC MFS FLA (OEM rated) DAR DW DG MCA OHS-084-DAR, DW, & DG AWS or FC MFS FLA (OEM rated) DAR DW DG MCA OHS-120-DAR, DW, & DG AWS or FC MFS FLA (OEM rated) DAR DW DG MCA MFS COOLING ONLY, with or without Hot Water or Steam Reheat 208/1/60 N/A N/A N/A 277/1/60 N/A N/A N/A N/A N/A 208/3/60 17.1 14.9 17.7 23.3 30 22.7 20.3 23.5 31.0 40 29.3 25.7 30.5 40.7 50 37.9 33.1 39.5 55.3 70 460/3/60 8.8 7.7 9.1 11.9 15 11.6 10.4 12.0 15.7 20 14.9 13.1 15.5 20.6 25 19.2 16.8 20.0 27.1 35 COOLING and ELECTRIC REHEAT/HEAT only, (No Humidifier) 208/1/60 N/A N/A N/A 277/1/60 N/A N/A N/A N/A N/A 208/3/60 36.7 35.6 37.0 47.5 50 40.2 39.0 40.6 52.4 60 44.3 42.5 44.9 58.5 60 49.5 47.1 50.3 67.4 80 460/3/60 18.1 17.5 18.2 23.3 25 19.8 19.2 20.0 25.7 30 21.9 21.0 22.2 28.8 30 24.5 23.3 24.9 32.8 35 COOLING and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat) 208/1/60 N/A N/A N/A 277/1/60 N/A N/A N/A N/A N/A 208/3/60 33.5 31.3 34.1 39.7 40 36.9 34.5 37.7 45.2 50 43.5 39.9 44.7 54.9 60 52.1 47.3 53.7 69.5 90 460/3/60 16.2 15.1 16.5 19.3 20 18.0 16.8 18.4 22.1 25 21.3 19.5 21.9 27.0 30 25.6 23.2 26.4 33.5 40 N/A N/A N/A 277/1/60 N/A N/A N/A N/A N/A 208/3/60 30.1 30.1 34.4 37.7 40 31.5 31.5 42.4 39.4 40 33.1 33.1 33.1 41.4 50 37.9 34.9 39.5 55.3 70 460/3/60 14.8 14.8 16.9 18.4 20 15.5 15.5 21.4 19.3 20 16.3 16.3 16.3 20.6 25 19.2 17.2 20.0 27.1 35 COOLING and ELECTRIC REHEAT/HEAT and HUMIDIFIER 208/1/60 N/A N/A N/A 277/1/60 N/A N/A N/A N/A N/A 208/3/60 46.5 46.5 46.5 58.2 60 45.7 45.7 57.2 57.2 60 47.3 47.3 47.3 59.2 60 52.1 49.1 53.7 69.5 90 460/3/60 22.2 22.2 22.2 27.7 30 21.9 21.9 28.3 27.3 30 22.7 22.7 22.7 28.8 30 25.6 23.6 26.4 33.5 40 Dual Compressor Systems with C-Tech-10 Microprocessor (see Note-1) Model OHS-048-DAR, DW, & DG AWS or FC FLA (OEM rated) DAR DW DG MCA OHS-072-DAR, DW, & DG AWS or FC MFS FLA (OEM rated) DAR DW DG MCA OHS-084-DAR, DW, & DG AWS or FC MFS FLA (OEM rated) DAR DW DG MCA OHS-120-DAR, DW, & DG -AWS or FC MFS FLA (OEM rated) DAR DW DG MCA MFS COOLING and ELECTRIC REHEAT/HEAT only, (No Humidifier) 208/1/60 N/A N/A N/A 277/1/60 N/A N/A N/A N/A N/A 208/3/60 43.3 41.1 43.9 56.1 60 48.9 46.5 49.7 63.8 70 55.5 51.9 56.7 73.5 80 64.1 59.3 65.7 88.1 100 460/3/60 21.4 20.3 21.7 27.6 30 24.2 23.0 24.6 31.4 35 27.5 25.7 28.1 36.3 40 31.8 29.4 32.6 42.8 45 COOLING and ELECTRIC REHEAT/HEAT and HUMIDIFIER 208/1/60 N/A N/A N/A N/A 277/1/60 N/A N/A N/A N/A 208/3/60 46.5 46.5 46.5 58.2 60 48.9 46.5 68.6 63.8 70 55.5 51.9 56.7 73.5 80 64.1 59.3 65.7 88.1 100 460/3/60 22.2 22.2 22.2 27.7 30 24.2 23.0 34.0 31.4 35 27.5 25.7 58.1 36.3 40 31.8 29.4 32.6 42.8 45 Note-1: Dual compressor systems incorporating C-Tech-10 controls provide 2(two) compressor stages of Cooling and 2(two) compressor stages of Dehumidification. The A-Tech-1.2 and A-Tech-20 controls provide 2(two) compressor stages of Cooling and 1(one) compressor stage of Dehumidification. Therefore, electrical data for dual compressor systems with dehumidification mode (reheat) is controller dependent as shown above. Air Technology Systems, Inc. - Free-Cooling & Alternate Water Source COOLING and ELECTRIC HEAT only, (No Electric Reheat or Humidifier) 208/1/60 Electrical Data Model - Free-Cooling & Alternate Water Source (*) Current Draws are given in the following order: FLA MCA MFS FLA = Full Load Amps MCA = Minimum Circuit Amps (wire size amps) MFS = Maximum Fuse Size 5-8 Electrical Data Electrical Data Model OHS-012-C FLA MCA - Chilled Water Systems OHS-018-C MFS FLA MCA OHS-024-C MFS FLA MCA OHS-032-C OHS-040-C MFS FLA MCA MFS FLA MCA MFS COOLING ONLY, with or without Hot Gas, Hot Water or Steam Reheat 208/1/60 2.7 3.4 15 2.7 3.4 15 2.7 3.4 15 3.4 4.3 15 3.8 4.8 15 277/1/60 2.5 3.1 15 2.5 3.1 15 2.5 3.1 15 2.7 3.4 15 3.9 4.9 15 208/3/60 2.7 3.4 15 2.7 3.4 15 2.7 3.4 15 3.4 4.3 15 3.8 4.8 15 460/3/60 1.6 2.0 15 1.6 2.0 15 1.6 2.0 15 1.6 2.0 15 3.0 3.8 15 COOLING and ELECTRIC REHEAT/HEAT only, (No Humidifier) 208/1/60 25.4 31.8 35 25.4 31.8 35 25.4 31.8 35 26.1 32.7 35 26.5 33.2 35 277/1/60 20.6 25.7 30 20.6 25.7 30 20.6 25.7 30 20.8 25.9 30 22.0 27.4 30 208/3/60 15.8 19.8 20 15.8 19.8 20 15.8 19.8 20 16.5 20.7 25 16.9 21.2 25 460/3/60 7.9 9.8 15 7.9 9.8 15 7.9 9.8 15 7.9 9.8 15 9.3 11.6 15 COOLING and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat) 208/1/60 10.9 13.6 15 10.8 13.6 15 10.9 13.6 15 11.6 14.5 15 12.0 15.0 20 277/1/60 8.7 10.9 15 8.7 10.9 15 8.7 10.9 15 8.9 11.1 15 10.1 12.6 15 208/3/60 10.9 13.6 15 10.9 13.6 15 10.9 13.6 15 11.6 14.5 15 12.0 15.0 20 460/3/60 5.3 6.6 15 5.3 6.6 15 5.3 6.6 15 5.3 6.6 15 6.7 8.4 15 COOLING and ELECTRIC HEAT only, (No Electric Reheat or Humidifier) - Chilled Water Sysetms 208/1/60 25.4 31.8 35 25.4 31.8 35 25.4 31.8 35 26.1 32.7 35 26.5 33.2 35 277/1/60 20.6 25.7 30 20.6 25.7 30 20.6 25.7 30 20.8 25.9 30 22.0 27.4 30 208/3/60 15.8 19.8 20 15.8 19.8 20 15.8 19.8 20 16.5 20.7 25 16.9 21.2 25 460/3/60 7.9 9.8 15 7.9 9.8 15 7.9 9.8 15 7.9 9.8 15 9.3 11.6 15 33.6 42.0 45 34.3 42.9 45 34.7 43.4 45 COOLING with ELECTRIC REHEAT/HEAT and HUMIDIFIER 208/1/60 33.6 42.0 45 33.6 42.0 45 Air Technology Systems, Inc 277/1/60 26.8 33.4 35 26.8 33.4 35 26.8 33.4 35 27.0 33.7 35 28.2 35.2 40 208/3/60 24.0 30.0 30 24.0 30.0 30 24.0 30.0 30 24.7 30.9 35 25.1 31.4 35 460/3/60 11.6 14.5 15 11.6 14.5 15 11.6 14.5 15 11.6 14.5 15 13.0 16.2 20 MFS FLA MFS FLA MFS FLA MFS FLA Model OHS-048-C FLA MCA OHS-060-C MCA OHS-072-C MCA OHS-084-C MCA OHS-120-C MCA MFS COOLING ONLY, with or without Hot Gas, Hot Water or Steam Reheat 208/1/60 N/A N/A N/A N/A 277/1/60 N/A N/A N/A N/A N/A N/A 208/3/60 3.9 4.9 15 5.3 6.6 15 5.3 6.6 15 6.9 8.6 15 8.7 10.9 15 460/3/60 2.2 2.8 15 2.9 3.6 15 2.9 3.6 15 3.7 4.6 15 4.6 5.8 15 COOLING and ELECTRIC REHEAT/HEAT only, (No Humidifier) 208/1/60 N/A N/A N/A N/A 277/1/60 N/A N/A N/A N/A N/A N/A 208/3/60 30.1 37.7 40 31.5 39.4 40 31.5 39.4 45 33.1 41.4 45 34.9 43.7 45 460/3/60 14.8 18.4 20 15.5 19.3 20 15.5 19.3 25 16.3 20.3 25 17.2 21.4 25 COOLING and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat) 208/1/60 N/A N/A N/A N/A 277/1/60 N/A N/A N/A N/A N/A N/A 208/3/60 20.3 25.4 30 21.7 27.1 30 19.5 24.4 30 21.1 26.4 30 22.9 28.6 30 460/3/60 9.6 12.0 15 10.3 12.9 15 9.3 11.6 15 10.1 12.6 15 11.0 13.8 15 COOLING and ELECTRIC HEAT only, (No Electric Reheat or Humidifier) 208/1/60 N/A N/A N/A N/A 277/1/60 N/A N/A N/A N/A N/A N/A 208/3/60 30.1 37.7 40 31.5 39.4 40 31.5 39.4 45 33.1 41.4 45 34.9 43.7 45 460/3/60 14.8 18.4 20 15.5 19.3 20 15.5 19.3 25 16.3 20.3 25 17.2 21.4 25 COOLING with ELECTRIC REHEAT/HEAT and HUMIDIFIER 5-9 208/1/60 N/A N/A N/A N/A 277/1/60 N/A N/A N/A N/A N/A N/A 208/3/60 46.5 58.2 60 47.9 59.9 60 45.7 57.2 60 47.3 59.2 60 49.1 61.4 70 460/3/60 22.2 27.7 30 22.9 28.6 30 21.9 27.3 30 22.7 28.3 30 23.6 29.4 30 Air Technology Systems, Inc. (*) Current Draws are given in the following order: FLA MCA MFS FLA = Full Load Amps MCA = Minimum Circuit Amps (wire size amps) MFS = Maximum Fuse Size Dimensional Data - Standard "OHS" Configurations (Drwg. #) MODEL TYPE .................page Physical Data / Connection Sizes Water / Glycol Cooled Systems Unit Net Weights (lbs) Table ......................................... 6-2 DX - Refrigerant Connection Sizes ............................... 6-3 Source Water/Glycol Connection Sizes ......................... 6-3 Chilled Water Connection Sizes . .................................. 6-3 Air Cooled Systems OHS-012/032-AS "Spot Cooler Configuration"................................ 6-4 "Ducted Configuration"....................................... 6-4 OHS-040-AS "Spot Cooler Configuration"................................ 6-4 "Ducted Configuration"....................................... 6-5 OHS-012/032-AR "Spot Cooler Configuration"................................ 6-5 "Ducted Configuration"....................................... 6-5 OHS-040-AR "Spot Cooler Configuration"................................ 6-6 "Ducted Configuration (direct-drive)"................... 6-6 (8) (9) OHS-012/040-HAR (Ducted, belt-drive).................... 6-6 OHS-040/060-AR ..................................................... 6-6 (10) (11) OHS-048/084-DAR . ................................................. 6-7 OHS-120-DAR . ........................................................ 6-7 OHS-012/032-W/G "Spot Cooler Configuration"................................ 6-10 "Ducted Configuration"....................................... 6-10 OHS-040-W/G "Spot Cooler Configuration"................................ 6-10 "Ducted Configuration (direct-drive)"................... 6-11 OHS-012/040-HW/HG & FC "Ducted Configuration (belt-drive)"...................... 6-11 (22) OHS-048/060-W/G & FC .......................................... 6-11 (23) (24) OHS-048/084-DW/DG & FC ..................................... 6-12 OHS-120-DW/DG . ................................................... 6-12 (25) OHS-120-DW/DG-FC ............................................... 6-13 Chilled Water Systems (26) (27) (28) OHS-012/040-C "Spot Cooler Configuration"................................ 6-14 "Ducted Configuration"....................................... 6-14 OHS-012/040-HC "Belt-Driven Ducted Configuration"..................... 6-14 (29) (30) (31) OHS-048/060-C ........................................................ 6-15 OHS-072/084-C ........................................................ 6-15 OHS-120-C ............................................................... 6-15 - Index (1) (2) (3) (4) (5) (6) (7) (8) (18) (19) (20) (21) (21) Dimensional Data "Index" DX - Air Handling Units (12) (13) (14) OHS-012/040-AHU "Spot Cooler Configuration"................................ 6-8 "Ducted Configuration"....................................... 6-8 OHS-012/040-HAHU "Belt-Driven Ducted Configuration"..................... 6-8 (15) OHS-048/060-AHU ................................................ 6-9 (16) (17) OHS-048/084-DAHU . .............................................. 6-9 OHS-120-DAHU . ..................................................... 6-9 Air Technology Systems, Inc. 6-1 Physical Data Dimensional Data - Physical Data (Unit Weight lbs.) OHS-( )-( ) OHS-( )-AS OHS-( )-AR OHS-( )-HAR OHS-( )-AHU OHS-( )-HAHU OHS-( )-DAR OHS-( )-DAHU OHS-( )-W OHS-( )-HW OHS-( )-DW OHS-( )-G OHS-( )-HG OHS-( )-DG OHS-( )-C OHS-( )-HC OHS-( )-( )-FC OHS-( )-( )-AWS Unit Weights (lbs.) Approximate Unit Physical Weight (Cooling Only! Please see notes, given in lbs.) 012 018 024 032 040 048 060 210 215 220 255 265 160 165 170 205 215 370 380 185 190 195 230 240 120 120 120 155 165 270 280 135 140 145 180 190 420 320 180 200 210 245 260 395 405 205 225 235 265 285 440 180 200 210 245 260 395 405 205 225 235 265 285 440 120 125 125 160 170 280 290 140 145 150 185 190 245 265 275 300 310 500 510 225 230 235 270 280 460 470 072 450 350 470 470 365 570 550 084 510 410 550 550 415 660 610 120 580 480 625 625 495 745 705 Air Technology Systems, Inc 6-2 Table Legend: Note-1: ----- means unit not available in this configuration and/or size. Note-2: Model "OHS" weights shown above are for Cooling Only Evaporator units without receivers. If Humidity Options (steam humidifier; electric, hot gas, hot water or steam reheat) and/or -30°F flooded receiver(s) are applicable, please add the following approximate weights to the Cooling Only model "OHS" weights shown above: Features/Options Model Sizes 012/040 048/060 048/120-D( ) Adding Features: Net Additions Steam Humidifier + 20 lbs + 25 lbs + 25 lbs Electric Reheat Hot Gas Reheat Hot Water Reheat Steam Reheat + 15 lbs + 30 lbs + 30 lbs + 30 lbs + 25 lbs + 35 lbs + 35 lbs + 35 lbs + 25 lbs + 45 lbs + 45 lbs + 45 lbs -30 Flooded Condensate Pump + 30 lbs + 10 lbs + 50 lbs + 10 lbs + 100 lbs + 10 lbs Air Technology Systems, Inc. Piping Connection Sizes Model OHS-018-( ) OHS-024-( ) OHS-032-( ) OHS-040-( ) OHS-048-( ) OHS-060-( ) "A" "B' "C" "A" "B' "C" "A" "B' "C" "A" "B' "C" "A" "B' "C" "A" "B' "C" "A" "B' "C" OHS-( )-AR ---- 3/8 1/2 ---- 3/8 1/2 ---- 3/8 5/8 ---- 1/2 5/8 ---- 1/2 7/8 ---- 1/2 7/8 ---- 1/2 7/8 OHS-( )-AHU 5/8 3/8 ---- 3/4 3/8 ---- 3/4 3/8 ---- 3/4 1/2 ---- 7/8 1/2 ---- 7/8 1/2 ---- 7/8 1/2 ---- Legend: Refrigerant Piping connection Sizes Dual Compressor / Circuit Systems Sizes giver are per circuit OD Model OHS-048-( ) OHS-072-( ) OHS-084-( ) OHS-120-( ) "A" "B' "C" "A" "B' "C" "A" "B' "C" "A" "B' "C" OHS-( )-DAR ---- 3/8 5/8 ---- 1/2 5/8 ---- 1/2 7/8 ---- 1/2 7/8 OHS-( )-DAHU 3/4 3/8 ---- 7/8 1/2 ---- 7/8 1/2 ---- 7/8 1/2 ---- "A" "B" "C" = Suction Line, inches OD Copper = Liquid Line, inches OD Copper = Hot Gas, inches OD Copper Notes: Note-1: ----- means connection type not applicable to this unit configuration. Note-2: Dimensions shown represent the "pipe connection size" only! For information detailing the sizing of the interconnecting refrigerant and water lines, please refer to the CeilAiR Installations, Operations and Maintenance Manual. (Single Compressor / Single Circuit Systems) 012 018 024 032 040 048 060 IN/OUT IN/OUT IN/OUT IN/OUT IN/OUT IN/OUT IN/OUT OHS-( )-W/G 5/8 7/8 7/8 7/8 7/8 1-1/8 1-1/8 OHS-( )-W/G-FC 5/8 5/8 5/8 7/8 7/8 1-1/8 1-1/8 Model Chilled Water / Alternate Water Souce Piping Connection Sizes Model OHS-( )-C & AWS Model OHS-( )-C & AWS 012 018 024 032 040 048 060 IN/OUT IN/OUT IN/OUT IN/OUT IN/OUT IN/OUT IN/OUT 5/8 7/8 7/8 7/8 7/8 1-1/8 1-1/8 048 072 084 120 IN/OUT IN/OUT IN/OUT IN/OUT 1-1/8 1-1/8 1-1/8 1-3/8 - Piping Connection Sizes Source Water / Glycol Piping Connection Sizes Dimensional Data Refrigerant Piping Connection Sizes - Single Compressor / Circuit Systems OHS-012-( ) Legend: IN OUT = Inlet Connection, inches OD Copper = Outlet Connection, inches OD Copper Air Technology Systems, Inc. 6-3 Air Cooled - SINGLE Compressor Systems DIMENSIONAL DATA Dimensional Data (1) OHS-012 thru 032-AS Self-Contained, Air Cooled ("Ductless" Spot Cooler) - Air Cooled (SINGLE Compressor Systems) DIMENSIONAL DATA "C" "D" "E" "F" 15.5" 5.75" 18.0" 19.75" 16.13" 21.5" 10.88" 23.0" 15.63" 19.75" MODEL "A" "B" OHS-012, 018,& 024-AS 20.38" OHS-032-AS 26.38" MODEL "A" "B" "C" "D" OHS-012, 018,& 024-AS 20.38" 15.5" 5.50" 18.0" OHS-032-AS 26.38" 21.5" 10.50" 23.0" (2) OHS-012 thru 032-AS Self-Contained, Air Cooled ("Ducted" Evap - Direct Driven) Air Technology Systems, Inc 6-4 (3) OHS-040-AS Self-Contained, Air Cooled ("Ductless" Spot Cooler) Air Technology Systems, Inc. Air Cooled - SINGLE Compressor Systems Dimensional Data (4) OHS-040-HAS Self-Contained, Air Cooled ("Ducted" Version - Direct Driven) MODEL "A" OHS-012, 018,& 024-AR 20.38" OHS-032-AR 26.38" (5) OHS-012 thru 032-AR Remote Air Cooled, Evaporator ("Ductless" Spot Cooler) (6) OHS-012 thru 032-AR DIMENSIONAL DATA Remote Air Cooled, Evaporator ("Ducted" Version - Direct Driven) Air Technology Systems, Inc. MODEL "A" "B" "D" "F" OHS-012, 018,& 024-AR 20.38" 15.5" 19.75" 16.13" OHS-032-AR 26.38" 21.5" 15.63" 19.75" - Air Cooled (SINGLE Compressor Systems) DIMENSIONAL DATA 6-5 Air Cooled - SINGLE Compressor Systems Dimensional Data (7) OHS-040-AR Remote Air Cooled, Evaporator ("Ductless" Spot Cooler) DIMENSIONAL DATA - Air Cooled (SINGLE Compressor Systems) MODEL "A" "B" "C" "L" "M" OHS-012, 018, & 024-HAR 20.0" 16.0" see note see note see note OHS-032- & 040-HAR 24.0" 20.0" see note see note see note OHS-040-HAR @ 0.3" esp (direct drive blower) 24.0" (8) OHS-012 thru 040-HAR Remote Air Cooled, Evaporator "H-Series Ducted Version" (040 - Direct Driven) & (012/040 - Belt Driven) Air Technology Systems, Inc 6-6 20.0" 6.62" 11.38" 10.5" Note: Consult your local Sales Representative for blower outlet dimensional data for "High-Static Pressure Blower Option". DIMENSIONAL DATA (9) OHS-040 thru 060-AR MODEL Remote Air Cooled, Evaporator (Ducted Only!) OHS-040 & 060-AR Air Technology Systems, Inc. "C" "L" "M" 6.62" 11.38" 13.12" Air Cooled - DUAL Compressor Systems DIMENSIONAL DATA Remote Air Cooled, Evaporator (DUAL Compressors) MODEL "M" 11.38" 13.12" OHS-072 & 084-DAR 7.62" 13.44" 15.62" "C" "L" "M" 7.25" 13.44" 15.62" Remote Air Cooled, Evaporator (DUAL Compressors) Air Technology Systems, Inc. - Air Cooled (DUAL Compressor Systems) MODEL "L" 6.62" (11) OHS-120-DAR DIMENSIONAL DATA OHS-120-DAR "C" OHS-048-DAR Dimensional Data (10) OHS-048 thru 084-DAR 6-7 DX - Air Handling Units DIMENSIONAL DATA Dimensional Data (12) OHS-012 thru 040-AHU MODEL DX - Air Handling Unit ("Ductless" Spot Cooler) 20.7" OHS-032 & 040-AR 26.7" - DX - Air Handling Units (13) OHS-012 thru 040-AHU DIMENSIONAL DATA MODEL "A" OHS-012, 018, & 024-AHU "A" "B" "E" "F" OHS-012, 018, & 024-AHU 20.7" 15.5" 19.88" 15.75" OHS-032 & 040-AHU 26.7" 21.5" 15.75" 19.88" DX - Air Handling Unit ("Ducted Version" - Direct Driven) Air Technology Systems, Inc DIMENSIONAL DATA (14) OHS-012 thru 040-HAHU DX - "H-Series", Air Handling Unit ("Ducted Version" - Belt Driven) MODEL "A" "E" "F" "C" "L" "M" OHS-012, 018, & 024-AHU 20.0" 19.75" 15.63" see note see note see note OHS-032 & 040-AHU 24.0" 19.75" 19.75" see note see note see note Note: Consult your local Sales Representative for blower outlet dimensional data for "High-Static Pressure Blower Option". 6-8 Air Technology Systems, Inc. DX - Air Handling Units MODEL DX - Air Handling Unit (Ducted Only!) OHS-048 & 060-AHU MODEL "C" "L" "M" 6.62" 11.38" 13.12" OHS-072 & 084-AHU 7.62" 13.44" 15.62" "M" 11.38" 13.12" (16) OHS-048 thru 084-DAHU Std CFM @ 0.5" esp OHS-048-DAHU "L" 6.62" DUAL Circuit, DX - Air Handling Unit (Ducted Only!) - DX - Air Handling Units DIMENSIONAL DATA Std CFM @ 0.5" esp "C" Dimensional Data DIMENSIONAL DATA (15) OHS-048 thru 060-AHU DIMENSIONAL DATA (17) OHS-120-DAHU MODEL DUAL Circuit, DX - Air Handling Unit (Ducted Only!) OHS-120-DAHU Air Technology Systems, Inc. Std CFM @ 0.5" esp "C" "L" "M" 7.38" 13.5" 15.69" 6-9 Water / Glycol Cooled - SINGLE Compressor Systems Dimensional Data DIMENSIONAL DATA (18) OHS-012 thru 032-W / G Self-Contained, Water/Glycol Cooled ("Ductless" Spot Cooler) - Water / Glycol Cooled (SINGLE Compressor Systems) DIMENSIONAL DATA MODEL "A" "B" "E" "F" OHS-012, 018, & 024-W/G 20.4" 15.5" 19.75" 16.13" OHS-032-W/G 26.4" 21.5" 15.63" 19.75" MODEL "A" OHS-012, 018, & 024 W/G 20.4" OHS-032-W/G 26.4" (19) OHS-012 thru 032-W / G Self-Contained, Water/Glycol Cooled ("Ducted Version" - Direct Drive) Air Technology Systems, Inc 6-10 (20) OHS-040-W / G Self-Contained, Water/Glycol Cooled ("Ductless" Spot Cooler) Air Technology Systems, Inc. Water / Glycol Cooled - SINGLE Compressor Systems DIMENSIONAL DATA & optional OHS-012 thru 040-HW/HG-FC "H-Series Ducted Version" (040 - Direct Driven) & (012/040 - Belt Driven) MODEL "A" "B" "C" "L" "M" OHS-012, 018, & 024-HW/HG (& HW/HG-FC) 20.0" 16.0" see note see note see note OHS-032, & 040-HW/HG (& HW/HG-FC) 24.0" 20.0" see note see note see note OHS-040-HW/G @ 0.3" esp (Direct-Drive Blower) 24.0" 20.0" 6.62" 11.38" 10.5" Note: Consult your local Sales Representative for blower outlet dimensional data for "High-Static Pressure Blower Option". MODEL & optional Std CFS @ 0.5" esp "C" "L" "M" OHS-048, & 060-W/G 6.62" 11.38" 13.12" OHS-048, & 060-W/G-FC see note see note see note OHS-048 thru 060-W/G-FC Self-Contained, Water/Glycol Cooled (Ducted Only!) Note: Consult your local Sales Representative for blower outlet dimensional data for "High-Static Pressure Blower Option". Air Technology Systems, Inc. - Water / Glycol Cooled (SINGLE Compressor Systems) (22) OHS-048 thru 060-W / G DIMENSIONAL DATA Dimensional Data (21) OHS-012 thru 040-HW / HG 6-11 Water / Glycol Cooled - DUAL Compressor Systems Dimensional Data (23) OHS-048 thru 084-DW / DG DIMENSIONAL DATA & optional OHS-048 thru 084-DW/DG-FC MODEL Self-Contained, Water/Glycol Cooled (DUAL Compressors) Std CFS @ 0.5" esp "C" "L" "M" OHS-048-DW/DG 6.62" 11.38" 13.19" OHS-072-084-DW/DG 7.62" 13.5" 15.69" OHS-048/084-DW/DG-FC see note see note see note Note: Consult your local Sales Representative for blower outlet dimensional data for "High-Static Pressure Blower Option". - Water / Glycol Cooled (DUAL Compressor Systems) Air Technology Systems, Inc (24) OHS-120-DW / DG DIMENSIONAL DATA MODEL OHS-120-DW/DG 6-12 Std CFS @ 0.5" esp "C" "L" "M" 7.25" 13.5" 15.69" Self-Contained, Water/Glycol Cooled (DUAL Compressors) Air Technology Systems, Inc. Water / Glycol Cooled - "10-ton Free-Cooling Version" MODEL "FREE-COOLING Version" Self-Contained, Water/Glycol Cooled (DUAL Compressors) OHS-120-DW/DG-FC Std CFS @ 0.5" esp "C" "L" "M" 7.62" 13.5" 15.69" Dimensional Data DIMENSIONAL DATA (25) OHS-120-DW / DG-FC - Water/Glycol Cooled (Optional "Free-Cooling") Air Technology Systems, Inc. 6-13 Chilled Water Systems - 1 thru 3 Ton Systems DIMENSIONAL DATA Dimensional Data (26) OHS-012 thru 040-C MODEL Chilled Water System ("Ductless" Spot Cooler) DIMENSIONAL DATA - Chilled Water Systems (1 to 3 Ton Systems) MODEL "A" "B" "E" "F" OHS-012, 018, & 024-C 20.4" 15.5" 19.75" 15.63" OHS-032, & 040-C 26.4" 21.5" 15.63" 19.75" "A" OHS-012-, 018, & 024-C 20.7" OHS-032 & 040-C 26.7" (27) OHS-012 thru 040-C Chilled Water System ("Ducted Version" - Direct Driven) Air Technology Systems, Inc 6-14 (28) OHS-012 thru 040-HC DIMENSIONAL DATA MODEL "H-Series", Chilled Water System ("Ducted Version" - Belt Driven) OHS-012, 018, & 024-HC OHS-032, & 040-HC "A" "E" "F" "C" "L" "M" 20.0" 19.75" 15.63" SEE NOTE SEE NOTE SEE NOTE 24.0" 19.75" 19.75" SEE NOTE SEE NOTE SEE NOTE Note: Consult your local Sales Representative for blower outlet dimensional data for "High-Static Pressure Blower Option". Air Technology Systems, Inc. Chilled Water Systems - 4 thru 10 Ton Systems MODEL Chilled Water System ("Ducted" - Belt Driven) OHS-048 & 060-C MODEL OHS-072 & 084-C "C" "L" "M" 13.5" 15.69" "M" 11.38" 13.12" (30) OHS-072 thru 084-C Std CFS @ 0.5" esp 7.62" "L" 6.62" Chilled Water System ("Ducted" - Belt Driven) DIMENSIONAL DATA (31) OHS-120-C MODEL Chilled Water System ("Ducted" - Belt Driven) OHS-120-C Air Technology Systems, Inc. Std CFS @ 0.5" esp "C" "L" "M" 7.38" 13.5" 15.7" - Chilled Water Systems (4 to 10 Ton Systems) DIMENSIONAL DATA Std CFS @ 0.5" esp "C" Dimensional Data DIMENSIONAL DATA (29) OHS-048 thru 060-C 6-15 www.stulz-ats.com Air Technology Systems, Inc the greener way of cooling your data center. 1572 Tilco Drive, Frederick, Maryland 21704 Phone: 301.620.2033, Fax: 301.662.5487 E-mail: [email protected] Air Technology Systems, Inc. Registered ISO9001 Quality System ISO-9001:2001 Quality Registered Copyright, September 2008 QE-OHS0023 Rev Specifications subject to change without notice. This document was printed on recycled paper, with ecosmarttm environmentally responsible ink products. Air Technology Systems, Inc. Technical Bulletin Addendum to QE-OHS0023 CeilAiR (OHS) Engineering Manual Table of Contents Electrical Data DX Single Circuit Systems...................................................................................................2-3 DX Dual Circuit Systems.....................................................................................................4-5 Single Circuit AHU Systems................................................................................................6 Dual Circuit DAHU Systems................................................................................................7 DX Single Circuit Systems with Free Cooling or Alternate Water Source.......................8 DX Single Circuit Systems with Free Cooling or Alternate Water Source.......................9 Chilled Water Systems........................................................................................................10-11 << Electrical Data Notes >> 1) Electrical Data is based on standard performance and component selection per QE-OHS0023. Please consult your local Sales Representative for "special" equipment electrical data. 2) High Static Pressure Belt-Drive Option - Electrical Data in the pages to follow are based on Standard CFM's and External Static Pressures. Please Consult your local Sales Representative for component and electrical rating data for this Option. Addendum to QE-OHS0023- OHS Eng. Manual QECH013-, November, 2013 Page 1 of 11 Technical Bulletin Electrical Data - DX Single Compressor Systems Model OHS-012-AS FLA MCA MFS OHS-018-AS FLA MCA OHS-024-AS MFS FLA MCA OHS-032-AS MFS FLA OHS-040-AS MCA MFS FLA MCA MFS OHS-048-AS OHS-060-AS FLA FLA MCA MFS MCA MFS COOLING ONLY, with or without Hot Gas, Hot Water or Steam Reheat 208/1/60 11.7 17.2 25 14.8 20.3 30 17.5 25.6 40 19.9 29 45 21.2 30.3 45 N/A N/A 277/1/60 9.2 14.7 20 11 15.8 20 12.9 19.8 30 15.8 23.1 35 16.9 24.2 35 N/A N/A 208/3/60 N/A N/A 14.3 18 25 15.9 22.6 30 17.2 23.9 35 N/A N/A 460/3/60 N/A N/A 6.5 8.8 15 7.3 11.1 15 7.9 11.7 15 N/A N/A COOLING and ELECTRIC REHEAT/HEAT, with or without Humidifier 208/1/60 33.1 44 45 36.2 47 50 38.9 52.4 60 41.3 55.7 60 42.6 57 60 N/A N/A 277/1/60 27.3 37.3 40 29.1 38.5 40 31 42.5 50 33.9 45.7 50 35 46.8 50 N/A N/A 208/3/60 N/A N/A 26.7 33.5 35 28.3 38.1 45 29.6 39.4 45 N/A N/A 460/3/60 N/A N/A 12.8 16.7 20 13.6 19 20 14.2 19.6 20 N/A N/A COOLING and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat) 208/1/60 19.9 25.4 30 23 28.5 35 277/1/60 15.3 20.8 25 17.1 21.9 30 25.7 33.8 45 28.1 37.2 50 29.4 38.5 50 N/A N/A 19 25.9 35 21.9 29.2 40 23 30.3 40 N/A N/A 208/3/60 N/A N/A 22.5 26.2 35 24.1 30.8 40 25.4 32.1 40 N/A N/A 460/3/60 N/A N/A 10.2 12.6 15 11 14.8 20 11.6 15.4 20 N/A N/A COOLING and ELECTRIC HEAT only, (No Electric Reheat or Humidifier) 208/1/60 27 33.8 35 28.3 35.4 40 28.3 35.4 40 29 36.3 40 30.3 37.9 40 N/A N/A 277/1/60 21.7 27.1 30 22.8 28.5 30 22.8 28.5 30 23.3 29.1 30 24.4 30.5 35 N/A N/A 208/3/60 N/A N/A 19.3 24.1 25 20 25.0 30 21.3 26.6 30 N/A N/A 460/3/60 N/A N/A 9.4 11.8 15 9.4 11.8 15 10 12.5 15 N/A N/A Model FLA (OEM Rated) OHS-012-AR, W, & G AR W G MCA OHS-018-AR, W, & G MFS FLA (OEM Rated) AR W G OHS-024-AR, W, & G MCA MFS FLA (OEM Rated) AR W G MCA MFS COOLING ONLY, with or without Hot Gas, Hot Water or Steam Reheat 208/1/60 8.8 7.4 9.2 14.3 20 10.6 8.9 11.1 16.1 25 13.3 10.7 14.2 21.5 35 277/1/60 7.4 6.4 7.7 12.9 20 8.1 6.8 8.5 12.9 20 10 8.1 10.6 16.9 25 208/3/60 N/A N/A 10.1 8.7 10.6 13.8 20 460/3/60 N/A N/A 4.9 4.3 5.1 7.3 15 COOLING and ELECTRIC REHEAT/HEAT only, (No Humidifier) 208/1/60 30.2 28.8 30.6 41.1 45 32 30.3 32.5 42.8 45 34.7 32.1 35.6 48.2 50 277/1/60 25.5 24.5 25.8 35.5 40 26.2 24.9 26.6 35.5 40 28.1 26.2 28.7 39.5 45 208/3/60 N/A N/A 22.5 21.1 23 29.3 35 460/3/60 N/A N/A 11.2 10.6 11.4 15.1 20 COOLING and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat) 208/1/60 17 15.6 17.4 22.5 30 18.8 17.1 19.3 24.3 30 21.5 18.9 22.4 29.6 40 277/1/60 13.5 12.5 13.8 19 25 14.2 12.9 14.6 19 25 16.1 14.2 16.7 23 35 208/3/60 N/A N/A 18.3 16.9 18.8 22 30 460/3/60 N/A N/A 8.6 8 8.8 10.9 15 COOLING and ELECTRIC HEAT only, (No Electric Reheat or Humidifier) 208/1/60 24.1 24.1 24.1 30.1 35 24.1 24.1 24.1 30.1 35 24.1 24.1 24.1 30.1 35 277/1/60 19.9 19.9 19.9 24.9 25 19.9 19.9 19.9 24.9 25 19.9 19.9 19.9 24.9 25 208/3/60 N/A N/A 15.1 15.1 15.1 18.9 20 460/3/60 N/A N/A 7.8 7.8 7.8 9.8 15 COOLING and ELECTRIC REHEAT/HEAT and HUMIDIFIER 208/1/60 30.2 28.8 30.6 41.1 45 32 30.3 32.5 42.8 45 34.7 32.1 35.6 48.2 50 277/1/60 25.5 24.5 25.8 35.5 40 26.2 24.9 26.6 35.5 40 28.1 26.2 28.7 39.5 45 208/3/60 N/A N/A 22.5 21.1 23 29.3 35 460/3/60 N/A N/A 11.2 10.6 11.4 15.1 20 Addendum to QE-OHS0023- OHS Eng. Manual QECH013-, November, 2013 Page 2 of 11 (*) Current Draws are given in the following order: FLA MCA MFS FLA = Full Load Amps MCA = Minimum Circuit Amps (wire size amps) MFS = Maximum Fuse Size Technical Bulletin Electrical Data - DX Single Compressor Systems Model OHS-032-AR, W, & G FLA (OEM Rated) AR W G MCA OHS-040-AR, W, & G MFS FLA (OEM Rated) AR W G OHS-048-AR, W, & G MCA MFS FLA (OEM Rated) AR W G MCA OHS-060-AR, W, & G MFS FLA (OEM Rated) AR W G MCA MFS COOLING ONLY, with or without Hot Gas, Hot Water or Steam Reheat 208/1/60 15.7 13 16.5 24.8 40 17 14.3 17.8 26.1 40 N/A 277/1/60 12.9 10.6 13.6 20.2 30 14 11.7 14.7 21.3 35 N/A N/A 208/3/60 11.7 10.3 12.1 18.4 30 13 11.6 13.4 19.7 30 16.9 14.4 17.7 25.3 40 22.6 19.3 23.6 29.2 45 460/3/60 5.7 5 5.9 9.5 15 6.3 5.6 6.5 10.1 15 8.7 7.5 9.1 12.1 15 10.4 9 10.8 14.3 20 N/A COOLING and ELECTRIC REHEAT/HEAT only, (No Humidifier) 208/1/60 37.1 34.4 37.9 51.5 60 38.4 35.7 39.2 52.8 60 N/A 277/1/60 31 28.7 31.7 42.8 50 32.1 29.8 32.8 43.9 50 N/A N/A 208/3/60 24.1 22.7 24.5 33.9 40 25.4 24 25.8 35.2 40 41.6 39.1 42.4 56.2 60 47.3 44 48.3 60.1 70 460/3/60 12 11.3 12.2 17.4 20 12.6 11.9 12.8 18 20 21.3 20.1 21.7 27.8 30 23 21.6 23.4 30 35 N/A COOLING and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat) 208/1/60 23.9 21.2 24.7 33 50 25.2 22.5 26 34.3 50 N/A 277/1/60 19 16.7 19.7 26.3 40 20.1 17.8 20.8 27.4 40 N/A N/A 208/3/60 19.9 18.5 20.3 26.6 35 21.2 19.8 21.6 27.9 35 33.2 30.7 34 41.6 50 38.9 35.6 39.9 45.5 60 460/3/60 9.4 8.7 9.6 13.2 15 10 9.3 10.2 13.8 20 16.1 14.9 16.5 19.5 25 17.8 16.4 18.2 21.7 30 N/A COOLING and ELECTRIC HEAT only, (No Electric Reheat or Humidifier) 208/1/60 24.8 24.8 24.8 31.0 35 26.1 26.1 26.1 32.6 35 N/A 277/1/60 20.4 20.4 20.4 25.5 30 21.5 21.5 21.5 26.9 30 N/A N/A 208/3/60 15.8 15.8 15.8 19.8 20 17.1 17.1 17.1 21.4 25 28.6 28.6 28.6 35.8 40 29.8 29.8 29.8 37.3 40 460/3/60 7.8 7.8 7.8 9.8 15 8.4 8.4 8.4 10.5 15 14.8 14.8 14.8 18.5 20 15.5 15.5 15.5 19.4 20 N/A COOLING and ELECTRIC REHEAT/HEAT and HUMIDIFIER 208/1/60 37.1 34.4 37.9 51.5 60 38.4 35.7 39.2 52.8 60 N/A 277/1/60 31 28.7 31.7 42.8 50 32.1 29.8 32.8 43.9 50 N/A N/A 208/3/60 24.1 22.7 24.5 33.9 40 25.4 24 25.8 35.2 40 41.6 39.1 42.4 56.2 60 47.3 44 48.3 60.1 70 460/3/60 12 11.3 12.2 17.4 20 12.6 11.9 12.8 18 20 21.3 20.1 21.7 27.8 30 23 21.6 23.4 30 35 N/A (*) Current Draws are given in the following order: FLA MCA MFS FLA = Full Load Amps MCA = Minimum Circuit Amps (wire size amps) MFS = Maximum Fuse Size Addendum to QE-OHS0023- OHS Eng. Manual QECH013-, November, 2013 Page 3 of 11 Technical Bulletin Electrical Data - DX Dual Compressor Systems OHS-048-DAR, DW, & DG Model FLA (OEM rated) DAR DW DG MCA OHS-072-DAR, DW, & DG MFS FLA (OEM rated) DAR DW MCA DG OHS-084-DAR, DW, & DG MFS FLA (OEM rated) DAR DW DG MCA OHS-120-DAR, DW, & DG MFS FLA (OEM rated) DAR DW DG MCA MFS COOLING ONLY, with or without Hot Gas, Hot Water or Steam Reheat 208/1/60 N/A N/A N/A 277/1/60 N/A N/A N/A N/A N/A 208/3/60 18.9 16.1 19.9 24.1 30 21.7 18.9 22.5 32.1 40 30.2 26.2 31.4 45.5 60 44.3 37.7 46.3 52.7 70 460/3/60 8.7 7.5 9.1 12.3 15 11.3 9.9 11.7 17.3 20 15.4 13.4 16 21.2 25 19.8 17 20.6 25.3 30 COOLING and ELECTRIC REHEAT/HEAT only, (No Humidifier) 208/1/60 N/A N/A N/A 277/1/60 N/A N/A N/A N/A N/A 208/3/60 36.2 34.8 36.7 46.1 50 38.1 36.7 38.5 51 60 43.3 41.3 43.9 59.3 70 51.5 48.2 52.5 64.3 70 460/3/60 17.9 17.3 18.1 23.4 25 19.7 19 19.9 26.7 30 22 21 22.3 29 30 24.9 23.5 25.3 31.9 35 COOLING and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat) 208/1/60 N/A N/A N/A 277/1/60 N/A N/A N/A N/A N/A 208/3/60 35.2 32.4 36.2 40.4 45 35.9 33.1 36.7 46.3 50 44.4 40.4 45.6 59.7 70 58.5 51.9 60.5 66.9 80 460/3/60 16.1 14.9 16.5 19.6 20 17.7 16.3 18.1 23.7 30 21.8 19.8 22.4 27.6 35 26.2 23.4 27 31.7 40 COOLING and ELECTRIC HEAT only, (No Electric Reheat or Humidifier) 208/1/60 N/A N/A N/A 277/1/60 N/A N/A N/A N/A N/A 208/3/60 28.6 28.6 28.6 35.8 40 29.8 29.8 29.8 37.3 40 31.7 31.7 31.7 39.6 40 34 34 34 42.5 45 460/3/60 14.8 14.8 14.8 18.5 20 15.5 15.5 15.5 19.4 20 16 16 16 20 25 17.4 17.4 17.4 21.8 25 COOLING and ELECTRIC REHEAT/HEAT and HUMIDIFIER 208/1/60 N/A N/A N/A 277/1/60 N/A N/A N/A N/A N/A 208/3/60 36.2 34.8 36.7 46.1 50 38.1 36.7 38.5 51 60 44.4 41.3 45.6 59.7 70 58.5 51.9 60.5 66.9 80 460/3/60 17.9 17.3 18.1 23.4 25 19.7 19 19.9 26.7 30 22 21 22.4 29 35 26.2 23.5 27 31.9 40 (*) Current Draws are given in the following order: FLA MCA MFS FLA = Full Load Amps MCA = Minimum Circuit Amps (wire size amps) MFS = Maximum Fuse Size Addendum to QE-OHS0023- OHS Eng. Manual QECH013-, November, 2013 Page 4 of 11 Technical Bulletin Electrical Data - Single Circuit AHU Systems Model OHS-012-AHU FLA MCA OHS-018-AHU MFS FLA MCA OHS-024-AHU MFS OHS-032-AHU FLA MCA MFS FLA MCA MFS COOLING ONLY, with or without Hot Gas, Hot Water or Steam Reheat 208/1/60 2.7 3.4 15 2.7 3.4 15 2.7 3.4 15 3.4 4.3 15 277/1/60 1.8 2.3 15 1.8 2.3 15 1.8 2.3 15 2.3 2.9 15 208/3/60 2.7 3.4 15 2.7 3.4 15 2.7 3.4 15 3.4 4.3 15 460/3/60 1.5 1.9 15 1.5 1.9 15 1.5 1.9 15 1.5 1.9 15 COOLING and ELECTRIC REHEAT/HEAT only, (No Humidifier) 208/1/60 24.1 30.1 35 24.1 30.1 35 24.1 30.1 35 24.8 31 35 277/1/60 19.9 24.9 25 19.9 24.9 25 19.9 24.9 25 20.4 25.5 30 208/3/60 15.1 18.9 20 15.1 18.9 20 15.1 18.9 20 15.8 19.8 20 460/3/60 7.8 9.8 15 7.8 9.8 15 7.8 9.8 15 7.8 9.8 15 COOLING and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat) 208/1/60 10.9 13.6 15 10.9 13.6 15 10.9 13.6 15 11.6 14.5 15 277/1/60 7.9 9.9 15 7.9 9.9 15 7.9 9.9 15 8.4 10.5 15 208/3/60 10.9 13.6 15 10.9 13.6 15 10.9 13.6 15 11.6 14.5 15 460/3/60 5.2 6.5 15 5.2 6.5 15 5.2 6.5 15 5.2 6.5 15 COOLING and ELECTRIC HEAT only, (No Electric Reheat or Humidifier) 208/1/60 24.1 30.1 35 24.1 30.1 35 24.1 30.1 35 24.8 31 35 277/1/60 19.9 24.9 25 19.9 24.9 25 19.9 24.9 25 20.4 25.5 30 208/3/60 15.1 18.9 20 15.1 18.9 20 15.1 18.9 20 15.8 19.8 20 460/3/60 7.8 9.8 15 7.8 9.8 15 7.8 9.8 15 7.8 9.8 15 COOLING with ELECTRIC REHEAT/HEAT and HUMIDIFIER 208/1/60 32.3 40.4 45 32.3 40.4 45 32.3 40.4 45 33 41.3 45 277/1/60 26 32.5 35 26 32.5 35 26 32.5 35 26.5 33.1 35 208/3/60 23.3 29.1 30 23.3 29.1 30 23.3 29.1 30 24 30 35 460/3/60 11.5 14.4 15 11.5 14.4 15 11.5 14.4 15 11.5 14.4 15 MFS FLA MFS FLA Model OHS-040-AHU FLA MCA OHS-048-AHU MCA OHS-060-AHU MCA MFS COOLING ONLY, with or without Hot Gas, Hot Water or Steam Reheat 208/1/60 4.7 5.9 15 N/A 277/1/60 3.4 4.3 15 N/A N/A 208/3/60 4.7 5.9 15 3.9 4.9 15 5.1 6.4 15 460/3/60 2.1 2.6 15 2.2 2.8 15 2.9 3.6 15 N/A COOLING and ELECTRIC REHEAT/HEAT only, (No Humidifier) 208/1/60 26.1 32.6 35 N/A 277/1/60 21.5 26.9 30 N/A N/A 208/3/60 17.1 21.4 25 28.6 35.8 40 29.8 37.3 40 460/3/60 8.4 10.5 15 14.8 18.5 20 15.5 19.4 20 N/A COOLING and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat 208/1/60 12.9 16.1 20 N/A 277/1/60 9.5 11.9 15 N/A N/A 208/3/60 12.9 16.1 20 20.2 25.2 30 21.4 26.8 30 460/3/60 5.8 7.3 15 9.6 12 15 10.3 12.9 15 N/A COOLING and ELECTRIC HEAT only, (No Electric Reheat or Humidifier) 208/1/60 26.1 32.6 35 N/A 277/1/60 21.5 26.9 30 N/A N/A 208/3/60 17.1 21.4 25 28.6 35.8 40 29.8 37.3 40 460/3/60 8.4 10.5 15 14.8 18.5 20 15.5 19.4 20 N/A COOLING with ELECTRIC REHEAT/HEAT and HUMIDIFIER FLA 208/1/60 34.3 42.9 45 N/A N/A 277/1/60 27.6 34.5 35 N/A N/A 208/3/60 25.3 31.6 35 44.9 56.1 60 46.1 57.6 60 460/3/60 12.1 15.1 20 22.2 27.8 30 22.9 28.6 30 Addendum to QE-OHS0023- OHS Eng. Manual QECH013-, November, 2013 Page 5 of 11 (*) Current Draws are given in the following order: MCA MFS FLA = Full Load Amps MCA = Minimum Circuit Amps (wire size amps) MFS = Maximum Fuse Size Technical Bulletin Electrical Data - Dual Circuit DAHU Systems Model OHS-048-DAHU FLA MCA OHS-072-DAHU MFS FLA MCA OHS-084-DAHU MFS FLA MCA OHS-120-DAHU MFS FLA MCA MFS COOLING ONLY, with or without Hot Gas, Hot Water or Steam Reheat 208/1/60 N/A N/A N/A N/A 277/1/60 N/A N/A N/A N/A 208/3/60 4.1 5.1 15 5.1 6.4 15 7 8.8 15 9.3 11.6 20 460/3/60 1.9 2.4 15 2.9 3.6 15 3.4 4.3 15 4.8 6 15 COOLING and ELECTRIC REHEAT/HEAT only, (No Humidifier) 208/1/60 N/A 277/1/60 N/A N/A N/A N/A N/A N/A N/A 208/3/60 28.8 36 40 29.8 37.3 40 31.7 39.6 40 34 42.5 45 460/3/60 14.5 18.1 20 15.5 19.4 20 16 20 25 17.4 21.8 25 COOLING and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat) 208/1/60 N/A N/A N/A N/A 277/1/60 N/A N/A N/A N/A 208/3/60 20.4 25.5 30 19.3 24.1 25 21.2 26.5 30 23.5 29.4 30 460/3/60 9.3 11.6 15 9.3 11.6 15 9.8 12.3 15 11.2 14 15 COOLING and ELECTRIC HEAT only, (No Electric Reheat or Humidifier) 208/1/60 N/A 277/1/60 N/A N/A N/A N/A N/A N/A N/A 208/3/60 28.8 36 40 29.8 37.3 40 31.7 39.6 40 34 42.5 45 460/3/60 14.5 18.1 20 15.5 19.4 20 16 20 25 17.4 21.8 25 COOLING with ELECTRIC REHEAT/HEAT and HUMIDIFIER 208/1/60 N/A N/A N/A N/A 277/1/60 N/A N/A N/A N/A 208/3/60 45.1 56.4 60 44 55 60 45.9 57.4 60 48.2 60.3 70 460/3/60 21.9 27.4 30 21.9 27.4 30 22.4 28 30 23.8 29.8 30 (*) Current Draws are given in the following order: FLA MCA MFS FLA = Full Load Amps MCA = Minimum Circuit Amps (wire size amps) MFS = Maximum Fuse Size Addendum to QE-OHS0023- OHS Eng. Manual QECH013-, November, 2013 Page 6 of 11 Technical Bulletin Electrical Data - DX Single Circuit Systems with Free Cooling or Alternate Water Source Model OHS-012-HAR, HW, & HG AWS or FC FLA (OEM rated) HAR HW HG MCA OHS-018-HAR, HW, & HG AWS or FC MFS FLA (OEM rated) HAR HW HG OHS-024-HAR, HW, & HG AWS or FC MCA MFS FLA (OEM rated) HAR HW HG MCA MFS COOLING ONLY, with or without Hot Water or Steam Reheat 208/1/60 9.1 7.7 9.5 14.6 20 12 10.3 12.5 17.5 25 15.4 12.8 16.3 23.5 35 277/1/60 8.2 7.2 8.5 13.7 20 9.6 8.3 10 14.4 20 12.5 10.6 13.1 19.4 30 208/3/60 N/A N/A 8.7 7.6 9.0 12.9 20 460/3/60 N/A N/A 4.6 4.1 4.8 6.7 15 COOLING and ELECTRIC REHEAT/HEAT only, (No Humidifier) 208/1/60 30.5 29.1 30.9 41.4 45 33.4 31.7 33.9 44.2 45 36.8 34.2 37.7 50.3 60 277/1/60 26.3 25.3 26.6 36.3 40 27.7 26.4 28.1 37 40 30.6 28.7 31.2 42 45 208/3/60 N/A N/A 22.8 21.4 23.3 29.6 35 460/3/60 N/A N/A 11.2 10.6 11.4 15.1 20 COOLING and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat) 208/1/60 17.3 15.9 17.7 22.8 30 20.2 18.5 20.7 25.7 35 23.6 21 24.5 31.8 45 277/1/60 14.3 13.3 14.6 19.8 25 15.7 14.4 16.1 20.5 25 18.6 16.7 19.2 25.5 35 208/3/60 N/A N/A 18.6 17.2 19.1 22.3 30 460/3/60 N/A N/A 8.6 8 8.8 10.9 15 COOLING and ELECTRIC HEAT only, (No Electric Reheat or Humidifier) 208/1/60 24.4 24.4 24.4 30.5 35 25.5 25.5 25.5 31.9 35 26.2 26.2 26.2 32.8 35 277/1/60 20.7 20.7 20.7 25.9 30 21.4 21.4 21.4 26.8 30 22.4 22.4 22.4 28 30 208/3/60 N/A N/A 15.4 15.4 15.4 19.3 20 460/3/60 N/A N/A 7.8 7.8 7.8 9.8 15 COOLING and ELECTRIC REHEAT/HEAT and HUMIDIFIER 208/1/60 30.5 29.1 30.9 41.4 45 33.4 31.7 33.9 44.2 45 36.8 277/1/60 26.3 25.3 26.6 36.3 40 27.7 26.4 28.1 37 40 30.6 34.2 28.7 37.7 31.2 50.3 42 60 45 208/3/60 N/A N/A 22.8 21.4 23.3 29.6 35 460/3/60 N/A N/A 11.2 10.6 11.4 15.1 20 (*) Current Draws are given in the following order: FLA MCA MFS FLA = Full Load Amps MCA = Minimum Circuit Amps (wire size amps) MFS = Maximum Fuse Size Addendum to QE-OHS0023- OHS Eng. Manual QECH013-, November, 2013 Page 7 of 11 Technical Bulletin Electrical Data - DX Single Circuit Systems with Free Cooling or Alternate Water Source Model OHS-032-HAR, HW, & HG AWS or FC FLA (OEM rated) HAR HW HG MCA OHS-040-HAR, HW, & HG AWS or FC MFS FLA (OEM rated) HAR HW HG OHS-048-AR, W, & G AWS or FC MCA MFS FLA (OEM rated) AR W G MCA OHS-060 AR, W, & G AWS or FC MFS FLA (OEM rated) AR W G MCA MFS COOLING ONLY, with or without Hot Water or Steam Reheat 208/1/60 20.2 17.5 21 29.3 45 20.2 17.5 21 29.3 45 N/A 277/1/60 16.9 14.6 17.6 24.2 35 16.9 14.6 17.6 24.2 35 N/A N/A 208/3/60 12.2 10.8 12.6 18.9 30 12.2 10.8 12.6 18.9 30 18.1 15.6 18.9 26.5 40 24.5 21.2 25.5 31.1 50 460/3/60 6.4 5.7 6.6 10.2 15 6.4 5.7 6.6 10.2 15 9.4 8.2 9.8 12.8 20 10.9 9.5 11.3 14.8 20 N/A COOLING and ELECTRIC REHEAT/HEAT only, (No Humidifier) 208/1/60 41.6 38.9 42.4 56 60 41.6 38.9 42.4 56 60 N/A 277/1/60 35 32.7 35.7 46.8 50 35 32.7 35.7 46.8 50 N/A N/A 208/3/60 24.6 23.2 25 34.4 40 24.6 23.2 25 34.4 40 42.8 40.3 43.6 57.4 60 49.2 45.9 50.2 62 70 460/3/60 12.7 12 12.9 18.1 20 12.7 12 12.9 18.1 20 22 20.8 22.4 28.5 30 23.5 22.1 23.9 30.5 35 N/A COOLING and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat) 208/1/60 28.4 25.7 29.2 37.5 50 28.4 25.7 29.2 37.5 50 N/A 277/1/60 23 20.7 23.7 30.3 40 23 20.7 23.7 30.3 40 N/A N/A 208/3/60 20.4 19 20.8 27.1 35 20.4 19 20.8 27.1 35 34.4 31.9 35.2 42.8 50 40.8 37.5 41.8 47.4 60 460/3/60 10.1 9.4 10.3 13.9 20 10.1 9.4 10.3 13.9 20 16.8 15.6 17.2 20.2 25 18.3 16.9 18.7 22.2 30 N/A COOLING and ELECTRIC HEAT only, (No Electric Reheat or Humidifier) 208/1/60 29.3 29.3 29.3 36.6 40 29.3 29.3 29.3 36.6 40 N/A 277/1/60 24.4 24.4 24.4 30.5 35 24.4 24.4 24.4 30.5 35 N/A N/A 208/3/60 16.3 16.3 16.3 20.4 25 16.3 16.3 16.3 20.4 25 29.8 29.8 29.8 37.3 40 31.7 31.7 31.7 39.6 40 460/3/60 8.5 8.5 8.5 10.6 15 8.5 8.5 8.5 10.6 15 15.5 15.5 15.5 19.4 20 16 16 16 20 25 N/A COOLING and ELECTRIC REHEAT/HEAT and HUMIDIFIER 208/1/60 41.6 38.9 42.4 56 60 41.6 38.9 42.4 56 60 N/A 277/1/60 35 32.7 35.7 46.8 50 35 32.7 35.7 46.8 50 N/A 208/3/60 24.6 23.2 25 34.4 40 24.6 23.2 25 34.4 40 42.8 40.3 43.6 57.4 60 49.2 45.9 50.2 62 70 460/3/60 12.7 12 12.9 18.1 20 12.7 12 12.9 18.1 20 22 20.8 22.4 28.5 30 23.5 22.1 23.9 30.5 35 Addendum to QE-OHS0023- OHS Eng. Manual QECH013-, November, 2013 Page 8 of 11 N/A N/A Technical Bulletin Electrical Data - DX Dual Circuit Systems with Free Cooling or Alternate Water Source Model OHS-048-DAR, DW, & DG AWS or FC FLA (OEM rated) DAR DW DG MCA OHS-072-DAR, DW, & DG AWS or FC MFS FLA (OEM rated) DAR DW DG MCA OHS-084-DAR, DW, & DG AWS or FC MFS FLA (OEM rated) DAR DW DG MCA OHS-120-DAR, DW, & DG AWS or FC MFS FLA (OEM rated) DAR DW DG MCA MFS COOLING ONLY, with or without Hot Water or Steam Reheat 208/1/60 N/A N/A N/A 277/1/60 N/A N/A N/A N/A N/A 208/3/60 18.7 15.9 19.7 23.9 30 23.6 20.8 24.4 34 45 32.5 28.5 33.7 47.8 60 49.1 42.5 51.1 57.5 70 460/3/60 9 7.8 9.4 12.6 15 11.8 10.4 12.2 17.8 20 16.8 14.8 17.4 22.6 30 21.7 18.9 22.5 27.2 35 COOLING and ELECTRIC REHEAT/HEAT only, (No Humidifier) 208/1/60 N/A N/A N/A 277/1/60 N/A N/A N/A N/A N/A 208/3/60 36 34.6 36.5 45.9 50 40 38.6 40.4 52.9 60 45.6 43.6 46.2 61.6 70 56.3 53 57.3 69.1 80 460/3/60 18.2 17.6 18.4 23.7 25 20.2 19.5 20.4 27.2 30 23.4 22.4 23.7 30.4 35 26.8 25.4 27.2 33.8 35 COOLING and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat) 208/1/60 N/A N/A N/A 277/1/60 N/A N/A N/A N/A N/A 208/3/60 35 32.2 36 40.2 45 37.8 35 38.6 48.2 60 46.7 42.7 47.9 62 70 63.3 56.7 65.3 71.7 90 460/3/60 16.4 15.2 16.8 20 25 18.2 16.8 18.6 24.2 30 23.2 21.2 23.8 29 35 28.1 25.3 28.9 33.6 40 COOLING and ELECTRIC HEAT only, (No Electric Reheat or Humidifier) 208/1/60 N/A N/A N/A 277/1/60 N/A N/A N/A N/A N/A 208/3/60 28.6 28.6 28.6 35.8 40 31.7 31.7 31.7 39.6 40 34 34 34 42.5 45 38.8 38.8 38.8 48.5 50 460/3/60 14.8 14.8 14.8 18.5 20 16 16 16 20 25 17.4 17.4 17.4 21.8 25 19.3 19.3 19.3 24.1 25 COOLING and ELECTRIC REHEAT/HEAT and HUMIDIFIER 208/1/60 N/A N/A N/A 277/1/60 N/A N/A N/A N/A N/A 208/3/60 36 34.6 36.5 45.9 50 40 38.6 40.4 52.9 60 46.7 43.6 47.9 62 70 63.3 56.7 65.3 71.7 90 460/3/60 18.2 17.6 18.4 23.7 25 20.2 19.5 20.4 27.2 30 23.4 22.4 23.8 30.4 35 28.1 25.4 28.9 33.8 40 (*) Current Draws are given in the following order: FLA MCA MFS FLA = Full Load Amps MCA = Minimum Circuit Amps (wire size amps) MFS = Maximum Fuse Size Addendum to QE-OHS0023- OHS Eng. Manual QECH013-, November, 2013 Page 9 of 11 Technical Bulletin Electrical Data - Chilled Water Systems Model OHS-012-C FLA MCA OHS-018-C MFS FLA MCA OHS-024-C MFS FLA MCA OHS-032-C OHS-040-C MFS FLA MCA MFS FLA MCA MFS COOLING ONLY, with or without Hot Gas, Hot Water or Steam Reheat 208/1/60 2.7 3.4 15 2.7 3.4 15 2.7 3.4 15 3.4 4.3 15 4.7 5.9 15 277/1/60 1.8 2.3 15 1.8 2.3 15 1.8 2.3 15 2.3 2.9 15 3.4 4.3 15 208/3/60 2.7 3.4 15 2.7 3.4 15 2.7 3.4 15 3.4 4.3 15 4.7 5.9 15 460/3/60 1.5 1.9 15 1.5 1.9 15 1.5 1.9 15 1.5 1.9 15 2.1 2.6 15 COOLING and ELECTRIC REHEAT/HEAT only, (No Humidifier) 208/1/60 24.1 30.1 35 24.1 30.1 35 24.1 30.1 35 24.8 31 35 26.1 32.6 35 277/1/60 19.9 24.9 25 19.9 24.9 25 19.9 24.9 25 20.4 25.5 30 21.5 26.9 30 208/3/60 15.1 18.9 20 15.1 18.9 20 15.1 18.9 20 15.8 19.8 20 17.1 21.4 25 460/3/60 7.8 9.8 15 7.8 9.8 15 7.8 9.8 15 7.8 9.8 15 8.4 10.5 15 COOLING and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat) 208/1/60 10.9 13.6 15 10.9 13.6 15 10.9 13.6 15 11.6 14.5 15 12.9 16.1 20 277/1/60 7.9 9.9 15 7.9 9.9 15 7.9 9.9 15 8.4 10.5 15 9.5 11.9 15 208/3/60 10.9 13.6 15 10.9 13.6 15 10.9 13.6 15 11.6 14.5 15 12.9 16.1 20 460/3/60 5.2 6.5 15 5.2 6.5 15 5.2 6.5 15 5.2 6.5 15 5.8 7.3 15 COOLING and ELECTRIC HEAT only, (No Electric Reheat or Humidifier) 208/1/60 24.1 30.1 35 24.1 30.1 35 24.1 30.1 35 24.8 31 35 26.1 32.6 35 277/1/60 19.9 24.9 25 19.9 24.9 25 19.9 24.9 25 20.4 25.5 30 21.5 26.9 30 208/3/60 15.1 18.9 20 15.1 18.9 20 15.1 18.9 20 15.8 19.8 20 17.1 21.4 25 460/3/60 7.8 9.8 15 7.8 9.8 15 7.8 9.8 15 7.8 9.8 15 8.4 10.5 15 COOLING with ELECTRIC REHEAT/HEAT and HUMIDIFIER 208/1/60 32.3 40.4 45 32.3 40.4 45 32.3 40.4 45 33 41.3 45 34.3 42.9 45 277/1/60 26.0 32.5 35 26.0 32.5 35 26.0 32.5 35 26.5 33.1 35 27.6 34.5 35 208/3/60 23.3 29.1 30 23.3 29.1 30 23.3 29.1 30 24 30 35 25.3 31.6 35 460/3/60 11.5 14.4 15 11.5 14.4 15 11.5 14.4 15 11.5 14.4 15 12.1 15.1 20 (*) Current Draws are given in the following order: FLA MCA MFS FLA = Full Load Amps MCA = Minimum Circuit Amps (wire size amps) MFS = Maximum Fuse Size Addendum to QE-OHS0023- OHS Eng. Manual QECH013-, November, 2013 Page 10 of 11 Technical Bulletin Electrical Data - Chilled Water Systems Model OHS-048-C FLA MCA OHS-060-C MFS FLA MCA OHS-072-C MFS FLA MCA OHS-084-C MFS FLA MCA OHS-120-C MFS FLA MCA MFS COOLING ONLY, with or without Hot Gas, Hot Water or Steam Reheat 208/1/60 N/A N/A N/A N/A 277/1/60 N/A N/A N/A N/A N/A N/A 208/3/60 3.9 4.9 15 5.1 6.4 15 5.1 6.4 15 7 8.8 15 9.3 11.6 20 460/3/60 2.2 2.8 15 2.9 3.6 15 2.9 3.6 15 3.4 4.3 15 4.8 6 15 COOLING and ELECTRIC REHEAT/HEAT only, (No Humidifier) 208/1/60 N/A N/A N/A N/A 277/1/60 N/A N/A N/A N/A N/A N/A 208/3/60 28.6 35.8 40 29.8 37.3 40 29.8 37.3 40 31.7 39.6 40 34 42.5 45 460/3/60 14.8 18.5 20 15.5 19.4 20 15.5 19.4 20 16 20 25 17.4 21.8 25 COOLING and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat) 208/1/60 N/A N/A N/A N/A 277/1/60 N/A N/A N/A N/A N/A N/A 208/3/60 20.2 25.2 30 21.4 26.8 30 19.3 24.1 25 21.2 26.5 30 23.5 29.4 30 460/3/60 9.6 12 15 10.3 12.9 15 9.3 11.6 15 9.8 12.3 15 11.2 14 15 COOLING and ELECTRIC HEAT only, (No Electric Reheat or Humidifier) 208/1/60 N/A N/A N/A N/A 277/1/60 N/A N/A N/A N/A N/A N/A 208/3/60 28.6 35.8 40 29.8 37.3 40 29.8 37.3 40 31.7 39.6 40 34 42.5 45 460/3/60 14.8 18.5 20 15.5 19.4 20 15.5 19.4 20 16 20 25 17.4 21.8 25 COOLING with ELECTRIC REHEAT/HEAT and HUMIDIFIER 208/1/60 N/A N/A N/A N/A 277/1/60 N/A N/A N/A N/A N/A N/A 208/3/60 44.9 56.1 60 46.1 57.6 60 44 55 60 45.9 57.4 60 48.2 60.3 70 460/3/60 22.2 27.8 30 22.9 28.6 30 21.9 27.4 30 22.4 28 30 23.8 29.8 30 (*) Current Draws are given in the following order: FLA MCA MFS FLA = Full Load Amps MCA = Minimum Circuit Amps (wire size amps) MFS = Maximum Fuse Size Addendum to QE-OHS0023- OHS Eng. Manual QECH013-, November, 2013 Page 11 of 11