Transcript
Console & Ceiling Type
Simple yet Functional Ceiling type indoor unit has two way installation options for the ceiling and floor, enabling you to use your available space more efficiently. You can enjoy crisp, powerful air spreading throughout your entire space from the compact unit in your ceiling or floor.
Slim and Elegant Console 2Way Installation
Features
Depending on the available space and the purpose of the air conditioner, the indoor unit can be installed under the ceiling or on the floor.
Indoor units
Under Ceiling
Floor Standing
Compact but Powerful 200%
Samsung Ceiling type air conditioner boasts a slim, compact design - half the size of our competitor’s with cooling power comparable to our competitor’s larger products.
136% Smaller
123%
Lighter
118% 100%
100%
SAMSUNG
Company B
Company A
SAMSUNG
Company B
Company A
7.1kW Model
Size
78
Weight
2013 SAMSUNG System Air Conditioners
79
9
Ceiling 9-1. Specifications 1) Technical specifications Model Power Supply Mode*1) Capacity Performance (Nominal)
Power
Cooling*2) Heating*3)
*2) Power Input Cooling (Nominal) Heating*3) *2) Current Input Cooling (Nominal) Heating*3)
Fan
7.1
Btu/h
19,100
24,200
kW
6.3
8.0
Btu/h
21,500
27,300
72
80
W A
72
77
0.33
0.35
Output
W
60
120
Number of unit
EA
1
1
CMM
14.00/13.00/12.00
18.00/16.50/15.00
Min / Std / Max
l/s
233.33/216.67/200.00
300.00/275.00/250.00
mmAq
-
-
Pa
-
-
WG
-
-
-
013054-105000-203838-330010
013054-105000-204747-330010 9.52
Ø, mm
6.35
Ø, inch
1/4
3/8
Ø, mm
12.70
15.88
Ø, inch
1/2
5/8
Ø, mm
ID 18 HOSE
ID 18 HOSE
Power Below 20m / Source Wire over 20m
mm2
1.5 / 2.5
1.5 / 2.5
Transmission Cable
mm2
0.75~1.5
0.75~1.5
Type
-
R410A
R410A
Control Method
-
EEV NOT INCLUDED
EEV NOT INCLUDED
Drain Pipe
Sound Pressure
High / Mid / Low*4)
dBA
40 / 37 / 34
44 / 42 / 40
Net Weight
kg
21.00
21.00
Shipping Weight
kg
25.50
25.50
mm
1000 x 650 x 200
1000 x 650 x 200
mm
1080 x 730 x 300
1080 x 730 x 300
-
-
-
Panel Net Weight
kg
-
-
Shipping Weight
kg
-
-
Net Dimensions (W×H×D)
mm
-
-
Shipping Dimensions (W×H×D)
mm
-
-
- / Model
-
-
mm/liter/h
-
-
-
Long life filter
Long life filter
Dimensions Net Dimensions (W×H×D) Shipping Dimensions (W×H×D) Panel model
Panel Size
5.6
0.29
Piping Connections Gas Pipe
Sound
HP/HR
kW
Sirocco Fan
Liquid Pipe
Refrigerant
HP/HR
0.28
Option Code
Field Wiring
1, 2, 220~240, 50
-
Sirocco Fan
Air Flow Rate H/M/L (UL) External Pressure
AM071FNCDEH✴✴✴
1, 2, 220~240, 50
-
Type Motor
AM056FNCDEH✴✴✴ Ø, #, V, Hz
Drain pump Drain pump Additional Accessories Air Filter
Max. lifting Height / Displacement
* Specifications may be subject to change without prior notice for product improvement. *1) Mode - HP : Heat Pump, HR : Heat Recovery *2) Nominal cooling capacities are based on; - Indoor temperature : 27°C DB, 19°C WB - Outdoor temperature : 35°C DB, 24°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m *3) Nominal heating capacities are based on; - Indoor temperature : 20°C DB, 15°C WB - Outdoor temperature : 7°C DB, 6°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m *4) Sound pressure was acquired in an anechoic room. Thus actual noise level may be different depending on the installation conditions.
112
9-2. Capacity tables 1) Cooling Model
056
Outdoor temperature (ºC, DB) 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39
20 (ºC, DB) 14 (ºC, WB) TC SHC
3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9
3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0
23 (ºC, DB) 16 (ºC, WB) TC SHC
4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8
3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4
26 (ºC, DB) 18 (ºC, WB) TC SHC
3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8
5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7
5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1
3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9
28 (ºC, DB) 20 (ºC, WB) TC SHC
5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.3 7.3
3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.8 4.8
2) Heating Model
056
071
30 (ºC, DB) 22 (ºC, WB) TC SHC
6.3 6.3 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.1 6.1 8.0 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.8 7.7
3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.7 4.9 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.7 4.6
32 (ºC, DB) 24 (ºC, WB) TC SHC
6.7 6.7 6.7 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.5 6.4 8.5 8.5 8.5 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.2 8.1
3.7 3.7 3.7 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.5 3.4 4.7 4.7 4.7 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.5 4.4
TC : Total Capacity(kW) Outdoor temperature (ºC) DB -20 -17 -15 -12 -10 -7 -5 -3 0 3 5 7 9 11 13 15 -20 -17 -15 -12 -10 -7 -5 -3 0 3 5 7 9 11 13 15
WB -21 -18 -16 -13 -11 -8 -6 -4 -1 2.2 4.1 6 7.9 9.8 12 14 -21 -18 -16 -13 -11 -8 -6 -4 -1 2.2 4.1 6 7.9 9.8 12 14
Indoor temperature (ºC, DB) 16.0 TC kW 3.9 4.0 4.2 4.4 4.6 4.9 5.2 5.4 5.7 5.9 6.2 6.5 6.7 6.9 7.1 7.3 4.9 5.1 5.3 5.6 5.9 6.2 6.5 6.9 7.2 7.6 7.9 8.2 8.5 8.7 9.0 9.2
18.0 TC kW 3.8 4.0 4.1 4.3 4.6 4.8 5.1 5.3 5.6 5.9 6.1 6.4 6.5 6.6 6.7 6.8 4.9 5.0 5.2 5.5 5.8 6.1 6.5 6.8 7.1 7.5 7.8 8.1 8.2 8.4 8.5 8.6
20.0 TC kW 3.8 3.9 4.0 4.2 4.5 4.8 5.0 5.3 5.5 5.8 6.0 6.3 6.3 6.3 6.3 6.3 4.8 4.9 5.1 5.4 5.7 6.0 6.4 6.7 7.0 7.3 7.7 8.0 8.0 8.0 8.0 8.0
22.0 TC kW 3.7 3.8 3.9 4.2 4.4 4.7 4.9 5.1 5.3 5.6 5.7 5.8 5.8 5.8 5.8 5.8 4.7 4.8 4.9 5.3 5.6 5.9 6.2 6.4 6.7 7.1 7.2 7.4 7.4 7.4 7.4 7.4
24.0 TC kW 3.7 3.8 3.8 4.1 4.4 4.5 4.7 4.9 5.0 5.3 5.3 5.3 5.3 5.3 5.3 5.3 4.7 4.8 4.8 5.2 5.6 5.8 6.0 6.2 6.4 6.8 6.8 6.8 6.8 6.8 6.8 6.8
113
Indoor units
071
TC : Total Capacity(kW), SHC : Sensible Heat Capacity(kW) Indoor temperature (ºC, WB) 27 (ºC, DB) 19 (ºC, WB) TC SHC
9
Ceiling 9-3. Dimensional drawing
Unit:mm
6
5 3
4
2
No.
Name
Description 5.6kW 7.1kW
1
Liquid pipe connection
Ø6.35 Flare
2
Gas pipe connection Drain pipe connection Conduit for power supply & communication wiring Air inlet grille Air outlet louver
Ø12.70 Flare Ø15.88 Flare ID18 Hose
3 4 5 6
114
1
Ø9.52 Flare
-
9
Ceiling 9-5. Sound pressure level 1) Operation sound level
Unit : dB(A)
1m 1m
Model
High
Low
AM056FNCDEH✴✴✴
40 1m 44
34
AM071FNCDEH✴✴✴
40
1m
Microphone
Microphone
Note These operation values were obtained in an anechoic room. Sound pressure level will vary depending on a range Microphone of factors such as the construction of the particular room where the equipment is installed. Operation sound level may differ depending on operation and ambient conditions. 1m
1m
2) NC curves (2) AM071FNCDEH✴✴✴
60
60
50
50
NC 45
40
NC 40
30
NC 35
HIGH
NC 30
20
NC 25
LOW
NC 20 NC 15
10
0
63
125
250
500
1000
2000
4000
Octave band center frequency(Hz)
116
8000
Sound pressure level (dB)
Sound pressure level (dB)
(1) AM056FNCDEH✴✴✴
NC 45
40
NC 40
30
NC 35
HIGH
NC 30
20
NC 25
LOW
NC 20 NC 15
10
0
63
125
250
500
1000
2000
4000
Octave band center frequency(Hz)
8000
9-6. Temperature and air flow distribution 1) AM071FNCDEH✴✴✴ (Floor installation) (1) Cooling air velocity distribution
Discharge angle : 36°
Ceiling height
3m
0.2m/s
2m
Indoor units
0.4m/s
1m 0.6m/s
0m
2m
1m
3m
5m 4m Floor distance
6m
7m
(2) Cooling temperature distribution
8m
Discharge angle : 36°
Ceiling height
3m
2m 25 24 22
23
21
1m
24 25
0m
2m
1m
3m
5m 4m Floor distance
6m
(3) Heating air velocity distribution
7m
8m
Discharge angle : 54° 3m
0.6m/s 0.8m/s
0.6m/s
0.4m/s 1.0m/s
Ceiling height
0.2m/s
0.4m/s
2m
0.2m/s 1.2m/s
1m
0m
2m
1m
3m
5m 4m Floor distance
6m
(4) Heating temperature distribution
7m
8m
Discharge angle : 54° 3m
27
Ceiling height
29
2m
27 29 31 25
1m
23 21
0m
1m
2m
3m
5m 4m Floor distance
6m
7m
8m
117
9
Ceiling 9-6. Temperature and air flow distribution 2) AM071FNCDEH✴✴✴ (Ceiling installation) (1) Cooling air velocity distribution
Discharge angle : 36° 3m
Ceiling height
1.0m/s
2m
0.2m/s
1m
0.4m/s 0.2m/s 0.6m/s
0m
2m
1m
5m 4m Floor distance
3m
6m
(2) Cooling temperature distribution
7m
8m
Discharge angle : 36° 3m
Ceiling height
25
2m
21
24 24
1m 23 23
0m
2m
1m
5m 4m Floor distance
3m
6m
(3) Heating air velocity distribution
7m
8m
Discharge angle : 54° 3m
Ceiling height
0.2m/s
2m
0.4m/s 1.0m/s 0.8m/s
1m
0.6m/s 0.4m/s
0.2m/s
0m
2m
1m
3m
5m 4m Floor distance
6m
(4) Heating temperature distribution
7m
8m
Discharge angle : 54° 3m
Ceiling height
25
2m
33 31 25 27
1m
23 21 21
0m
118
1m
2m
3m
5m 4m Floor distance
6m
7m
8m