Central ventilation with heat recovery unit KWLC 1800 SEH OPERATION AND INSTALLATION INSTRUCTIONS NO. 94225 It is important for safety reasons, that you read and observe this instruction fully before proceeding. RECEIPT The consignment contains: KWLC 1800 SEH vertical installation with electric after heating including a controller with 12 m connecting cable Please check delivery immediately on receipt for accuracy and damage, please notifiy carrier immediately. In case of delayed notification, any possible claim may be void. STORAGE When storing for a prolonged period the following steps should be taken to avoid damage to the unit: Protection of motor by dry, air- and dust-proof packing (e.g. plastic bags with drying agent and moisture indicators). Store in a place that is water proof, vibrationfree and free of temperature variations. When storing for several years or at motor standstill an inspection of the bearings with possible re-lubrication and an insulation inspection are essential before starting operation. With the SEH-type the heater is to be checked. Damages due to improper - transportation, storage or putting into operation are detectable and cannot be claimed as warranty – Condensation run-off The condensation pipe is to be connected to the water run off by means of a flexible pipe of 32 mm diameter. If it is not in a room, which is heated, it must be insulated. The frost protection control via self-regulating heating cable is recommended. Attention: When connecting the condensation pipe by (cold) pressing avoid any axial or radial forces on the unit drainpipe. The use of a flexible pipe is recommended. Fill the drain trap with water before putting into operation to avoid smells from the drain system. The regulations of the water board and other legislations must be observed.
OPERATION – USE Compact unit KWLC 1800 SEH to use in dry indoor areas for ventilation with heat recovery. Suitable as central or decentral solution for commercial or industrial applications. The standard equipment permits the installation and use in frost-protected rooms up to +5 °C. . For operation under difficult conditions, e.g. high humidity, long periods of standstill, high air pollution or through climatic, technical or electronic influences other than standard operations may not be suitable. For this reason please enquire and obtain operation release. A release by a third party is not valid. UNIT OPERATION In the heat exchanger the cold outside air and the warm extracted air "crosses over " without touching. Through this method approx. 80% of the energy of the warm air is transferred to the incoming air. Additionally a thermostat controlled electric heating element (after heating) warms up the inlet air (in extreme cold weather conditions) to the required temperature. It is controlled by a temperature sensor at the terminal box and an inlet air sensor. Frost conditions are detected by a Thermo-Humidity sensor, which is positioned in the heat exchanger and the bypass flap. In addition an electric heater battery can warm up the inlet air (No heater for buildings). The inlet air is directed to the living rooms and bedrooms through ducts and dampers. The stale air is extracted from the bathrooms, toilets and kitchens and flows back to the heat exchanger via the ducting system and fan, transferring heat before being discharge into the open air.
– Technical room requirements Minimum space for service in front of unit 1000 mm. Minimum space for service above the unit 500 mm. The unit must be placed in a separate technical room with a gully. Ceiling/floor/walls/doors must be in the necessary fire class. – Fireplaces Fire and building regulations must be observed – Air Ducting, Ventialtion circuit When designing the ductwork, try to achieve the shortest possible runs. Use smooth pipes (rigid plastic or steel ducting), to avoid high-pressure loss, noise etc. For the main ducting (outside air, extract air, inlet air, discharge collection) a diameter 400 mm is recommended. To reduce condensation in the extract pipes, the ducting has to be insulated where appropriate. Also if inlet and extract ductwork cross unheated rooms insulation must be provided to reduce heat loss. Fresh air should be taken into living- and bedrooms, extraction from bathrooms, toilets and kitchens. To regulate the whole system use adjustable Helios valves. The extract from the kitchen needs to be filtered. A kitchen hood must not be connected up to the unit (danger of grease carried into the heat exchanger). There must be a good air flow (e.g. using door grilles) within the building between intake rooms and extract rooms. Important: all fire protection regulations - where applicable- must be followed.
PERFORMANCE DATA To achieve the given performance, the unit must be correctly installed. The duct system must be designed to be within the units pressure capabilities and have good flow into and out of the unit otherwise there will be a reduction in the units performance. Noise figures are stated as sound power levels LWA in dB (A) (conforming to DIN 45635 Pt.1). Sound pressure levels LPA depend on room specific conditions. INSTALLATION-ASSEMBLY The KWLC 1800 SEH is suitable for "vertical" installation. When installed in areas with low ambient temperature (e.g. roof space) the unit may require additional insulation. Otherwise condensate could occur at the casing side walls. For maintenance work the unit has an access door on both sides. For the installation the unit can be turned by 180°, so that the outside- and extract- as well as the extractand inlet air connections can be on the left like on the right. Bends and long ducting are deleted by these alternatives. They reduce pressure loss and increase the system effectiveness. The ducting should be as short as possible and tight bends should be avoided as they can lead to a high-pressure loss and airflow noise. The ductwork joints should be fully sealed to prevent air loss. An easy connection of the condensation drainage with the drain system of the house has to be guaranteed. Note: The operating switch is supplied inside the unit and must be removed before installation. It is essential that the installed unit tray has a drop in the direction of the condensate water flow.
– Recommended sound insulation - To avoid vibrations a vibration damper or a damping mat should be installed under the unit. - After installation of the unit a flexible connector must be mounted between unit and duct. - Allow cable a sufficient length for "oscillation". - The main silencer must be placed near the unit, preferably in the technical room. – Supply air/Exhaust air - The openings for supply air and exhaust air must lie in a sufficient distance to each other to prevent a shortcut. - The fresh air intake must be placed away from smoke, dust and walls exposed to the sun. - The supply air intake should be placed min. 1 m above ground level to reduce the risk of clogging with snow and leaves. - Follow the supplier's recommendations for max. /min. air flow rates through the intake/ exhaust gratings/covers.
1
Central ventilation with heat recovery unit KWLC 1800 SEH – Backdraught shutter in supply/exhaust air connection (accessory). Must be used as protection of cold air and draft.
SPEEDS AND SETTINGS Note: if the power supply of the unit is cut it will restart afterwards in NORMAL speed (speed 2) and the electric after heater is activated. Attention: For good room conditions and to avoid condensation water damage, the unit should not be completely switched off, except in case of servicing / maintenance or in case of breakdown.
– Electrical connection Important: Electrical connection may only be carried out by a qualified person. All electrical work must only be carried out with the power supply off. A lockable isolator is required to isolate from the mains with a minimum of 3 mm contact opening of each pole. All relevant safety and installation regulations (for example DIN VDE 0100 and IEE regulations) are to be adhered to. Electrical connections are to be made according to wiring diagrams provided in these instructions. The connection takes place in the terminal box on the top side of the casing according to the wiring diagram. The installation of the intake air temperature sensor should be fitted inside the intake air duct (approx. 1-1,5 meters from the unit). The sensor is pre-wired as standard.
– DIP-Switch setting Important: When putting the unit into operation the dip-switch settings and the temperature settings must be checked. It is recommended to carry out customer specific setting on site.
OPERATION - ADJUSTMENT The KWLC 1800 SEH is speed controlled by a switch with 12 m (max. length 50 m) flying cable (included in delivery), mountable in any distance from the KWLC. The unit supports two operation steps: " Normal " and " Lowered " (A display indicates the operation mode). These functions are set-up during the installation. The built-in clock timer automatically controls the weekly timing of the fans (from "Normal" to "Lowered" or "Off"). The lowered mode can be switched to normal for a given time of 60, 120 or 180 minutes. Afterwards the mode automatically returns to "Lowered". Differential pressure switch to supervise the filters is included as standard. – Regulating the additional heating for units with electric heater battery The thermostat for the additional heating (15) is at the terminal box on the top of the unit sensing the extract air after the heat exchanger. The thermostat is factory set at 5 °C. The heater is protected against overheating by a thermal overload thermostat (22) that switches off automatically when a temperature of 50 °C has been reached. When the temperature is lower again, the thermostat switches on automatically. In case of repeated switching off the overload thermostat the reasons have to be investigated and problems to be solved. As an additional safety control, a second thermostat (21) switches off the whole unit if a temperature of 80 °C is exceeded. The thermostat can be manually reset by pressing the red push button, which is accessible in the inside of the unit by opening the doors.
Switch No. Recommendation 1 ON
Function ON = Electrical heater
2
OFF
3
OFF
4
ON
OFF= No change of the fan speed ON = Fan is turned off during night mode OFF = No temperature drop ON = 3 °C supply air temperature drop during night mode OFF = No change of the fan speed ON = Lowered speed during night mode
5
OFF
6
ON
7
OFF
8
OFF
OFF = No change of the fan speed ON = Speed reduction due to low temperature. Starting the heating OFF = Bypass off ON = Must be switched on. Bypass is affected by after-heating. OFF = Requisite for 1800-Type ON = Other Types OFF = Must be in OFF-position (Thermal sensor ISDN) ON = -----
– Start-up of the unit - Make sure that the fuses F1 (servo motor, fan) are activated. - Make sure that the fuses F2 (electric heater element group 1) are activated. - Make sure that the external isolator switch exists.
– Frost Protection of the Heat Exchanger Unit A thermal humidistat (14) avoids ice build up on the heat exchanger unit of the KWLC. This sensor controls the intake air fan to avoid ice build up and is mounted where the extract air leaves the heat exchanger. Warm air e.g. from the bathroom contains high humidity and therefore it is very likely that condensation occurs. Therefore the temperature in the heat exchanger must not drop as low that water in it freezes. The thermal humidistat measures the humidity of the air. In addition it measures the temperature of the heat exchanger unit. In case of frost danger and high humidity in the heat exchanger the bypass flap opens simultaneously to protect the heat exchanger unit. The open bypass flap remains unchanged until the heat exchanger has warmed itself sufficiently. In case of frost danger und dry air in the heat exchanger the KWLC keeps its adjusted operating state (no reduced output).
CONNECTION OF EXTERNAL COMPONENTS SEH Pic. 4
clock
(page 8, pic.8)
1 Switch Switch for KWLC 1800 SEH with 12 m (max .length 50 m) connecting cable. The switch should be preferably installed in a central place so that the settings can be chosen simply and monitored. The device consists of a clock timer and a control mode. The fans run in normal operation on maximum speed. A speed reduction is achieved via clock timer or external components via point 5.
Remote display – Clock timer Can be programmed with day and night functions. The day mode regulates the high fan speed whose speed steps can be preset manually with the transformer. The night mode regulates the low fan speeds or switches off the fan.(Set DIPswitch no.4 on circuit board to ON). With lowered fan speed during the night, the same inlet air temperatures can be achieved with the day mode.
2
Central ventilation with heat recovery unit KWLC 1800 SEH –
No reactivation necessary, after malfunction the unit goes over to normal operation again. 5 Alternatively external lowering of fan speed / Potential free contact For example "Lowering" as master control 6 Unit Off / Potential free contact Potential free gate input which turns off unit when contact is connected. Comfort control of different conditions of operation. 7 Optional room air temperature sensor (NTC) For the time being not available. 8 Master alarm / Potential free exit if thermal cutout trips then, - terminal 7/8 is closed - heating is switched off - bypass flaps open up (outside air inlet) - fans are switched off Reset button on the circuit board must not be pressed for deleting the interference. If thermal cutout opens the lower reset button must be reset manually (see point 21). 9 Outside air back draught shutter 230 V~ Shutter outlet for connection of motor driven back draught shutter type RVM 400 (wiring diagram SS-380.1) 10 Extract air back draught shutter 230 V~ Shutter outlet for connection of motor driven back draught shutter type RVM 400 (wiring diagram SS-380.1)
Control mode/Display - Fast blinking: serious errors - Slow blinking: normal errors - Symbol for high fan speed. - Symbol for low fan speed or Stop (switch on DIP-switch)
TEST
- switch for light test
60 MIN
- LED for speed step 60
120 MIN
- LED for speed step 120
180 MIN
- LED for speed step 180 - Symbol: Switch for fan speed setting 60, 120, 180 min.
Clock - Manual operation/hand control Normally the fans run on full speed during the day, on lowered fan speed at night or are turned off. - A "C" on the display directly on the left of ON/OFF button shows up during the day. - A "C-" shows up in the same place at night. If you wish a different operational mode, proceed as follows: Reduced fan speed during the day: Press ON/OFF button once, so that "C-" appears in the display. Then the fan speed is lowered to" fan speed at night". Increased fan speed during the day: Press ON/OFF button once, so that "C" appears in the display. The fan speed increases to" fan speed by day". If the temperature night setback is programmed the temperature set point changes itself accordingly. Note: At the next cyclical impulse of the clock timer the unit returns to the automatic mode again.
CONNECTION OF INTERNAL COMPONENTS SEH (page 8, pic. 8) Frost protection sensor in the heat exchanger / extract air The electronic frost protection sensor is in the heat exchanger in order to detect the humidity level and temperature of the extract air. This allows a more precise detection of the risk of frost in the heat exchanger. 15 Potentiometer for temperature set point Standard value for the internal electric heater control 17 Supply air motor 18 Extract air motor 19 Bypass flap in front of heat exchanger The bypass flap is operated dependent on the supply air temperature and the heating need. 20 Supply air duct temperature sensor (NTC) Supply air duct sensor (NTC) must be installed in the air duct. Installed terminal-sided. 21 Thermal cutout with manual reset 22 Thermal cutout with automatic reset 23 Filter control outside air If the sensors indicate an obstruction of the filter, clean the filter or change the filter if necessary. To monitor the filter, a differential pressure switch is integrated to the KWLC 1800 SEH. If the filter is dirty a red LED is blinking. 24 Filter control extract air If the sensors indicate an obstruction of the filter, clean the filter or change the filter if necessary. To monitor the filter, a differential pressure switch is integrated to the KWLC 1800 SEH. If the filter is dirty a warning lamp lights up. 25 Pressure control outside air / supply air fan Only for SEH-unit. Heater can be only switched on, if the fan runs. 26 Fan Cooling Control box 27 Heating rods 14
– Permanent manual operation Same result as manual operation , however ,it is not reset automatically. - For "fan speed by day" press the button "m" and ON/OFF at the same time so that a "C" appears in the display. - For "fan speed at night" press the button "m" and ON/OFF at the same time so that a "C-" appears in the display. If the permanent mode is activated, a dot appears in the display. The manual operation is deactivated by pressing the same buttons again, until the dot disappears. Set-up options With the night setback the fans can be reduced in speed or be switched off completely. The set temperature can be lowered up to 3 °C. The programming must be carried out by qualified personnel on delivery of the unit. 2
KWL FD- Remote display - Not in operation ! - Attention: Danger of icing ! - Attention: Thermal cutout has tripped ! - Reduced air flow volume due to low inlet air temperature - Heavily soiled extract air filter (must be replaced) - Heavily soiled supply air filter (must be replaced) - Electric after-heating in operation.
A motor disturbance is not signalised at the KWL FD, although LED is present. The motor is monitored through in series connected thermal contacts. 3 Supply line EH = 400V 3N~ 5 x 2,5 mm2* (*minimum, depending on the kind of permanent installation. Depending on ambient conditions) 4 Input for smoke/fire sensor / potential free contact Linked by default, generates an alarm (fast blinking of red LED) and a cutoff of unit - terminal 7/8 is closed - heating is switched off - bypass flaps open (outside air inlet) - fans are switched off
3
Central ventilation with heat recovery unit KWLC 1800 SEH CLEANING – MAINTENANCE Attention: The unit should be isolated from the mains before any servicing starts. Danger by movable parts (fan) and hot surfaces.
TECHNICAL DATA KWLC 1800 SEH Voltage / Frequency Nominal power max. Amps -fans Electric supply Condensation run-off Duct connection Heat power / Heater battery Weight Nominal power max. Amps -heater Nominal power max. Amps -total
– Opening of access doors Open the clamps. The unit has a door on each side. Thus the accessible side can be opened respectively – Filter The zones for supply and extract airof the device are supplied with class F7 pollen filters as standard. • Supply air/Extract air 2 x Spare filter set F7
ELF-KWL 7/1800
400V 3N~ 50Hz 5,8 A NYM-J 5 x 2,5 mm2 spigot outer 0 - 32 mm, Ø DN 400 mm 10kW (electric) 325 kg 14,4 A / 14,4 A / 14,4 A 20,2 A / 14,4 A / 14,4 A
Accessories Remote display with the following display: - danger of icing - volume reduction of supply air because of icing-alarm - filter change for supply air and extract air heater battery in operation
Ref.no. 0734
The outside and extract air filters are to be maintained or cleaned at least every three months or be replaced at least once a year of use for hygienic reasons. When replacing the filter the correct air flow direction through the filter has to be observed.
Type KWL-FD – Fan The fans are to be maintained and cleaned at least once a year. If heavily soiled the fans are to be dismantled (electrically firmly connected) by specialised personnel and to be cleaned professionally (vacuum cleaner, compressed air).
Ref.no. 3320
Back draught shutter, motor driven. Prevents inflow of cold air when unit stopped. Automatic operation when fan is in use. Comes with built-on spring release motor (installed outside the air flow). To be installed in any position. Closing pressure adjustable according to fan power and mounting position.
– Cross flow heat exchanger Must be cleaned at least twice a year. Remove frost protection sensor and pull out the heat exchanger unit carefully. For cleaning put in warm soapy water (do not use cleaning fluid containing sodium carbonate) and finally clean with warm water. When re-assembling ensure correct installation and take care not to damage the seals.
Type RVM 400
Ref.no. 2580
ACCESSORIES The use of accessories not offered or recommended by HELIOS will make the guarantee invalid. The use of an electronic speed or transformer speed controller is not permitted.
– Valves for intake and extract To be cleaned at least once a year
WARRANTY If the preceding instructions are not observed all warranty claims and accommodation treatment are excluded. The Helios warranty is limited to the material and workmanship of the product.
– Outer grilles Check yearly that grilles are free from leaves etc.
CERTIFICATES When installed correctly and used for its intended purpose, the product complies with applicable European standards and regulations at date of manufacture.
4
Central ventilation with heat recovery unit KWLC 1800 SEH SCHEMATIC DIAGRAM KWLC 1800 SEH with electric heater batter fig. 5
DDS2
DDS1 BK1
Extract air
Abluft
Outside air Außenluft
WT
F1
3
F2 VK2
BT OT T1
Zuluft T2 2
Exhaust air
Fortluft 4
M2
M1
Supply air
1 2 3 4 M1 M2 F1 F2 WT EH-R
1
EH-R
VK1
BK1
Outside air Supply air Extract air Exhaust air Supply air fan Extract air fan Extract air filter Outside air filter Heat exchanger Electric heater battery
DDS1 DDS2 BT OT T1 T2 VK1 VK2 BK1
Differential pressure switch for filter monitoring, extract air Differential pressure switch for filter monitoring, supply air Thermal cutout, manually resetable Thermal cutout, automatically resetable Frost protection sensor in the heat exchanger Supply air duct temperature sensor Backdraught shutter extract air Backdraught shutter outside air Bypass flap
Dimensions KWLC 1800 SEH
Supply Exhaust
Exhaust Outside air
fig. 6
condensation drainage Dimmensions / mm
5
6
2937 001 20.09.07
10. LED, heater active
9. Reset button for frost protection malfunction (WW)
8. Temperatur - Humidity sensor in the heat exchanger
7. LED, frostprotection alarm (heat exchanger)
5. Min °C: Limitation of minimum supply air temperature 6. DPB: Heater fine adjustment, standard setting! Do not adjust!
1+2. Standard=Switch off, green LED off, supply air sensor active (wiring diagram pos.20) Switch on, green LED on, room sensor (wiring diagram pos.7) All the moment not available 3. Cal.T2: Supply air temperatur sensor. Standard setting! Do not adjust! 4. Max °C: Limitation of maximum supply air temperature
GB
10. LED, Heizung aktiv
9. Reset - Taste für Frostschutz Störung (WW)
7. LED, Frostschutz Alarm Wärmetauscher 8. Temperatur - Feuchtefühler im Wärmetauscher!
6. DPB: Heizungs-Feineinstellung, Werkseinstellung ! Nicht verstellen !
5. MIN °C: Begrenzung der minimalen Zulufttemperatur
1. Standard = Schalter Aus , grüne LED Aus, Zuluft Sensor aktiv (Schaltplan Pos.20) 2. Schalter Ein, grüne LED Ein, Raum Sensor (Schaltplan Pos.7) z.Zt nicht verfügbar ! 3. Cal. T2: Zuluft Temperatursensor. Werkseinstellung ! Nicht verstellen ! 4. MAX °C: Begrenzung der maximalen Zulufttemperatur
D
max. 50m
Switch with built in clock timer
Betriebsschalter mit Uhr
10
09
08
07
06
05
04
03
02
01
Steuerplatine Control board
20
LED-info
InfoEinheit
max. 50m
21
19
18
17
16
15
14
13
12
11
1 2 3 4 5 6 7 8
Typenauswahl Selection types 1800 (must!) 1800er (muss !) Muss OFF sein. Thermosensor ISDN Must be OFF ISDN) (Thermowächter
Bypass BypassOFF Aus
Keine Ventilator no fan changing Veränderung Keine Temperaturno temperature reduction reduzierung Keine Drehzahlno speed reduction reduzierung Keine Drehzahlno speed reduction reduzierung
heater water WW Heizung Wasser
off
Ventilator im Nachtfan off in night modus betrieb AUS Zulufttemperatur um 3°C supply air temperature reduced 3 °C reduziertabout im Nachtbetrieb Kleine Drehzahl low fan speed inimnight modus Nachtbetrieb Drezahlreduzierung reduction of fan speed atbei lowkleiner temperature Temperatur Bypass Ein, Bypass ON Temperaturabhängig
heater electric EH Heizung Elektrisch
on
18. Alarm (water) frost protection 19. Alarm, general
11. Supply air, high speed 12. Supply air, low speed 13. Extractair, high speed 14. Extractair, low speed 15. Water pump 16. Supply air / extract air back draught shutter 17. (Bypass)
GB
11. Zuluft, große Drehzahl 12. Zuluft, kleine Drehzahl 13. Fortluft, große Drehzahl 14. Fortluft, kleine Drehzahl 15. Wasserpumpe 16. Zuluft/Fortluft, Klappe 17. (Bypass) 18. Alarm (Wasser), Frostschutz 19. Alarm, allgemein 20. LED, kleine Drehzahl aktiv 21. LED, große Drehzahl aktiv
D
Central ventilation with heat recovery unit KWLC 1800 SEH
KWLC 1800 SEH - Control circuit board fig. 7
N
K1
29
PDrucküberwachung ressure control OAußen utside/ Zuluft air / sVentilator upply air fan
HeHeizstäbe ating rods
32 33 34
92957 001 16.07.04
SSR2
SSR1
P
28
L2
F2
L
M 230V~
N
30 31
N
L1
L1 L2
Ventilator Fan Kühlung Cooling Steuerkasten Control box
F1
25
PE
(GND)
N
23
24
3
GND
Kl. 27 Kl. 4
Kl. 26
Kl. 22
Kl.1 Kl.2
PE
SSR-
Kl.6
10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30
KWLC 1800 EH control circuit board Steuerplatine
E xternal clUhr ock Externe
FFilterüberwachung ilter control exhaust aAbluft ir
GND
FFilterüberwachung ilter control outside aiAußenluft r
GND
TÜberhitzungstherm. hermal cutout automatauto ic reset
TÜberhitzungstherm. hermal cutout with mamanuell nual reseund t S moke a/nFeuer d fire seSensor nsor Rauch
GND
Wasser Pumpe
Water pump
EFortluft xhaust aiMotor r motor
SZuluft upply aMotor ir motor
46 45 44 43 Alarm
48 47
50 49
34 35 36 37 38 39 40 41 42
A2Platine Kl.12
SSR1
SSR2 A2-
A1+
A1+
PE
L1
M 230V~
L
N
L2
N
L1
N
M 230V~
L
12 13 14
L1
230V 190V 170V 150V 120V 105V 85V 60V 0V
230V 190V 170V 150V 120V 105V 85V 60V 0V
PE bBypassack draught sklappe hutter
ExhaustKlappe air flap S upply Klappe air flap Fortluft Zuluft
N
9 10 11
+ 0-10V
Kl. 7 Kl. 8
L1
Kl. 11, 14
Trafo 170V Kl. 18 Trafo 85V
55 54 53 52 51
Trafo 170V Kl. 16 Trafo 85V
58 57 56
FrFrostschutz ost protection Ala(Wasser) rm (water) Alarm
Bypass
SuppZuluft ly air/ E/xFortluft tract air flap Klappe
S upply aKanal ir, ductTemperatursensor temperature sensor (N TC) Zuluft, (NTC)
+10V
TTemp. emperaSollwert ture set p0-10V oint 0-10 V
GND
Optionaler O ptional exteexterner rnal exhauFortluft st air – Fr-oFrostschutz st protection TTemperatursensor emperature sensor (N(NTC) TC)
+10V
GND
GND
nput 24V~ iEingang
24V
Kl.19 Kl.20
nput 24V~ iEingang
GND Unit offAus Gerät
Kl. 5
1 2 3 4 5 6 7 8 9
24V Heizungsrelais 24 V für for h eater relay
230 / 24V~
24V~
0-10V= 0-10V= baBypassklappe ck draught shutter
Kl. 21
PE
L1
M 24V~
L1 L2 L3 N N PE PE
-
24V~
L- Signal auf
N
7
19 20 21
L- Signal auf
N
L1 L2 L3 N PE
Central ventilation with heat recovery unit KWLC 1800 SEH
KWLC 1800 SEH - Wiring, control circuit board fig. 8
Central ventilation with heat recovery unit KWLC 1800 SEH
fig. 9
SS-836
KWLC 1800 EH Anschluss externe Komponenten / Connection of external components 5
6
7
8
9
4
5
6
PE
3
PE
L1 L2 L3 N PE
LED.Panel
PE
Cont.Panel
PE
Platine
7 8
9 10 11
max. 50m
max. 50m
10
230V~ Ausgang
Fühler Eingang
L
N
230V~ Ausgang
12 13 14
N
Fortluft Verschlussklappe 230V~
M 230V~
Zuluft Verschlussklappe 230V~
Alarm Potentialfreier Ausgang
Optionaler Raumluft Temperatursensor (NTC)
Alternativ externes Drehzahl absenken. Potentialfreier Kontakt
Rauch / Feuer Sensor Potentialfreier Kontakt
400V~ 5 x 2,5*mm²
*mindestens, je nach Verlegeart
Zuleitung
Ferndisplay
Bedienelement mit WochenSchaltuhr
8888
Gerät Aus Potentialfreier Kontakt
M 230V~
L
PE
4
L- Signal auf
3
PE
2
L- Signal auf
1
Geräte interne Komponenten / Inside components 14
15
17
18
19
20
21
22
23
24
25
26
27
24V~/0-10V=
P
32 33 34
L
P
M 230V~
Filterüberwachung Außenluft
Überhitzungsthermostat mit automatischem Reset
Bypass-Klappe vor Wärmetauscher
Service und Information D HELIOS Ventilatoren GmbH & Co · Lupfenstraße 8 · 78056 VS-Schwenningen CH HELIOS Ventilatoren AG · Steinackerstraße 36 · 8902 Urdorf / Zürich A HELIOS Ventilatoren · Postfach 854 · Siemensstraße 15 · 6023 Innsbruck
Überhitzungsthermostat mit manuellem Reset
Fortluft Motor
1. Switch with clock timer 2. Remote display 3. Supply line - minimum, dependig on the kind of permanent 4. Smoke / Fire sensor - potential free contact 5. Alternatively external - lowering of fan speed - potential free contact 6. Unit off - potential free contact 7. Optional room air temperature sensor 8. Alarm, potential free contact 9. Supply air, back draught shutter 10. Extract air, back draught shutter
Zuluft KanalTemperatursensor (NTC)
M 24V~
Zuluft Motor
Poti für Temperatur - Sollwert
Frostschutzfühler im Wärmetauscher / Abluft
GB
M 230V~
PE
PE
PE
PE
PE
N P
M 230V~
30 31
14. Frost protection sensor in heat exchanger / extract air 15. Poti for temperatur set point 17. Supply air motor 18. Extract air motor 19. Bypass flap in front of heat exchanger 20. Supply air duct temperature sensor 21. Thermal cutout with manual reset 22. Thermal cutout with automatic reset 23. Filter control outside air 24. Filter control extract air 25. Pressure control for outside / supply air fan 26. Fan cooling control box 27. Heating rods 92945 001 SS-836 17.09.07
F HELIOS Ventilateurs · Z.I. La Fosse à la Barbière · 2, rue Louis Saillant · 93605 Aulnay sous Bois Cedex GB HELIOS Ventilation Systems Ltd. · 5 Crown Gate · Wyncolls Road · Severalls Industrial Park · Colchester · Essex · CO4 9HZ
Druckschrift-Nr. 94225/ 10.07
24V~
28 29
Heizstäbe
L
27
Ventilator Kühlung Steuerkasten
N
26
Drucküberwachung Außen / Zuluft-Ventilator
L
23 24 25
Filterüberwachung Abluft
N
22
-
19 20 21 + 0-10V
17 18
PE
PE
15 16
blau
rot
weiß
1 2
PE
Ausgang Cont.Panel