Rotek® Instrument Corp., 390 Main Street, Waltham Massachusetts 02452 USA Tel. (781) 899-4611 Fax (781) 894-7273 Email: [email protected] Rotek Model 8000 User Manual Chapter 2 – Operating Instructions
Chapter 2 OPERATING INSTRUCTIONS
CONTENTS Chapter 2 Operating Instructions ....................................................................................... 2-1 Model 8000................................................................................................................... 2-3 Installation ................................................................................................................ 2-4 Front Panel Controls & Displays ................................................................................ 2-5 Rear Panel Connections ............................................................................................. 2-9 Menu System........................................................................................................... 2-11 Main Menu.............................................................................................................. 2-14 Calibrator ................................................................................................................ 2-16 User Preferences...................................................................................................... 2-19 System Settings ....................................................................................................... 2-21 Front Panel.............................................................................................................. 2-23 Calibration .............................................................................................................. 2-25 About ...................................................................................................................... 2-27 Energy..................................................................................................................... 2-28 DMM Setup ............................................................................................................ 2-31 Option 8000-3P........................................................................................................... 2-33 Installation .............................................................................................................. 2-34 Front Panel Controls & Displays .............................................................................. 2-35 Rear Panel Connections ........................................................................................... 2-37 Option 8000-200A / 8000-320A .................................................................................. 2-39 Installation .............................................................................................................. 2-40 Front Panel Controls & Displays .............................................................................. 2-41 Rear Panel Connections ........................................................................................... 2-42 Option 8000-CTR........................................................................................................ 2-44 Installation .............................................................................................................. 2-45 Connection .............................................................................................................. 2-47 Option 8000-DMM ..................................................................................................... 2-48 Installation .............................................................................................................. 2-49 Connection .............................................................................................................. 2-50 Option 8000-PRG........................................................................................................ 2-51 Hardware Installation............................................................................................... 2-52 Software Installation................................................................................................ 2-53 Hardware Operation ................................................................................................ 2-54 Software Operation.................................................................................................. 2-55 Updating The Main Program.................................................................................... 2-57 Updating The DSP Program..................................................................................... 2-58
2-1
Rotek® Instrument Corp., 390 Main Street, Waltham Massachusetts 02452 USA Tel. (781) 899-4611 Fax (781) 894-7273 Email: [email protected] Rotek Model 8000 User Manual Chapter 2 – Operating Instructions
FIGURES Figure 2-1 Front Panel Controls and Displays .................................................................... 2-5 Figure 2-2 Output Setting Display ..................................................................................... 2-5 Figure 2-3 System Settings Display ................................................................................... 2-8 Figure 2-4 Rear Panel Connections.................................................................................... 2-9 Figure 2-5 External Voltage Sense Connections............................................................... 2-17 Figure 2-6 Option 8000-3P Installation............................................................................ 2-34 Figure 2-7 Option 8000-3P Front Panel ........................................................................... 2-35 Figure 2-8 Option 8000-3P Rear Panel Connections......................................................... 2-37 Figure 2-9 Option 8000-200A Installation ....................................................................... 2-40 Figure 2-10 Option 8000-200A Front Panel ..................................................................... 2-41 Figure 2-11 Option 8000-200A Rear Panel Connections .................................................. 2-42 Figure 2-12 Option 8000-CTR Installation....................................................................... 2-45 Figure 2-13 Option 8000-CTR Counter Input................................................................... 2-47 Figure 2-14 Option 8000-DMM Connections................................................................... 2-50 Figure 2-15 Option 8000-PRG Front Panel ...................................................................... 2-51 Figure 2-16 Option 8000-PRG Rear Panel ....................................................................... 2-51 Figure 2-17 Option 8000-PRG Connections..................................................................... 2-52 Figure 2-18 Option 8000-PRG Download Program.......................................................... 2-55
TABLES Table 2-1 Menu System................................................................................................... 2-13
2-2
Rotek® Instrument Corp., 390 Main Street, Waltham Massachusetts 02452 USA Tel. (781) 899-4611 Fax (781) 894-7273 Email: [email protected] Rotek Model 8000 User Manual Chapter 2 – Operating Instructions
Model 8000 The Model 8000 Calibrator can be operated from an AC power source of 90-132 Volts or 175-264 Volts, 47-63Hz. The Power Entry Module, located on the rear panel, provides a dual voltage selector which is integrated with the fuse holder. The line fuse is rated at 10 Amps Slow Blow, set at 115; 5 Amps Slow Blow set at 230. The present line voltage configuration is displayed in the voltage window of the fuse cover located on the rear panel adjacent to the line cord connector. To change selected voltage, first disconnect the power cord to the calibrator. Open the fuse cover using a small blade screwdriver or similar tool. Pull up the red fuse holder/voltage selector module. Remove the fuse. A conversion clip is installed on the fuse holder/voltage selector module set for single fusing. Remove the clip and place it on the opposite side. Install a fuse, one of the appropriate rating, into the opposite side of the fuse holder. Replace the fuse holder so that the desired voltage is displayed through the voltage window when the fuse door is closed.
!
WARNING !
Replace fuse only with a 250V fuse of noted rating. Always use fuses of type T (SB). Use of incorrect fuses could result in damage to the calibrator and injury to personnel!
A three-conductor power cable is provided and when this cable is connected to a standard three-wire outlet the instrument chassis is connected to earth ground. This feature prevents the instrument case from assuming voltages that are potentially hazardous to personnel. In the event that an adapter is used to connect the three-wire cable to a two-wire outlet the green (ground) adapter terminal should be connected to the earth ground.
2-3
Rotek® Instrument Corp., 390 Main Street, Waltham Massachusetts 02452 USA Tel. (781) 899-4611 Fax (781) 894-7273 Email: [email protected] Rotek Model 8000 User Manual Chapter 2 – Operating Instructions
Installation The Model 8000 Calibrator's standard configuration is bench mounted. Combination handles and rackmounting ears are available on special order and are interchangeable with the bench mounting handles. Suitable support must be provided for rack mounts.
2-4
Rotek® Instrument Corp., 390 Main Street, Waltham Massachusetts 02452 USA Tel. (781) 899-4611 Fax (781) 894-7273 Email: [email protected] Rotek Model 8000 User Manual Chapter 2 – Operating Instructions
Front Panel Controls & Displays Figure 2-1 illustrates the location of the front panel controls, connections and indicators. Each element of control, display or connection is numbered and a description of the function of each appears below. 3
5
4
1
6
2
7
14
8
13
9
12 11
10
Figure 2-1 Front Panel Controls and Displays
1. Output Settings Display. The Output Settings Display is an LCD graphic display which provides information about the present setting of each of the output parameters, Voltage, Current, VA, Phase Angle, and Frequency. The present state of the output, either OPERATE or STANDBY, is also displayed. If the 3 phase option 8000-3P has been installed, the phase being edited will be indicated, either phase A, B or C. In addition, the angular relationship between each phase is also indicated. The standard output setting display is shown below.
Voltage Current Power
0.00000 0.00000V A 0.00000VA
60.00 Hz 0.000 ° Phase A 0.000° Standby
Frequency Phase Angle
Phase Indicator Output State
Figure 2-2 Output Setting Display
2-5
Rotek® Instrument Corp., 390 Main Street, Waltham Massachusetts 02452 USA Tel. (781) 899-4611 Fax (781) 894-7273 Email: [email protected] Rotek Model 8000 User Manual Chapter 2 – Operating Instructions
2. Output Setting Edit Keys. The Output Setting Edit Keys are used to select which output parameter is to be modified. The keys labeled V, A, VA, φ, and Hz are used to modify Voltage, Current, Volt-Amperes, Phase Angle, and Frequency. Pressing one of these keys will cause the selected field in the Output Settings Display to be highlighted, indicating that it is ready to be edited. 3. Numeric Keypad. The Numeric Keypad is the means by which all numeric entries are made. Once a certain output parameter has been selected for modification, a new value may be keyed in using the keypad. The Keypad provides the digits 0 to 9 and also includes a decimal point and ± symbol. The ± key is used to change the polarity of an entry, if the output parameter being edited supports negative values. Valid entries for each of the output parameters are described below. Voltage: Values from between 9V and 700V may be entered. Current: Values from between 900µA and 10A may be entered. Always enter the desired value in the units indicated in the output setting display. If the indicated units are A then 100mA would be entered as 0.1A. Whenever an entry is made which is less than 1A the display will automatically change the units to mA to maintain resolution. Thus, when 0.1A is entered, the display will change to 100.000mA. To enter a setting of 5A, the value 5000mA would be entered and the display will change to 5.00000A. Volt-Amperes: The maximum and minimum values for this field depend on the present settings for both voltage and current. This field is automatically updated when either the voltage or current settings are changed. When this setting is changed the value of the current setting is updated to maintain the appropriate Voltage × Current relationship. The units of this field may be expressed as either VA, Watts or VARs. Frequency: Values from between 25 and 1000Hz may be entered. Phase Angle: Values from between +180.0 and -180.0° may be entered. The units of this field may be changed from Degrees to Radians or Power Factor. 4. Enter Key. The ENTER key is used to complete any numeric entry such as changing the setting of one of the output parameters. Pressing the ENTER key causes the new setting to take effect and exits the setting edit mode. 5. Cancel Entry Key. The Cancel Entry Key causes the removal of the editing highlight from the currently selected output parameter. The display will revert to the setting that was active when the editing process was begun. 6. Setting Control Knob. The Setting Control Knob may be used to change any specific digit of one of the output setting parameters. Rotating the knob clockwise will cause the selected digit to increment and rotating the knob counterclockwise will cause that digit to decrement, providing that the setting is valid. Changes to the output setting which are made with the setting control knob take effect at the output terminals
2-6
Rotek® Instrument Corp., 390 Main Street, Waltham Massachusetts 02452 USA Tel. (781) 899-4611 Fax (781) 894-7273 Email: [email protected] Rotek Model 8000 User Manual Chapter 2 – Operating Instructions
immediately and there is no need to press the enter key except to indicate the conclusion of the setting edit function. 7. Digit Selection Keys. The Digit Selection Keys are used to select which digit is to be modified as the setting control knob is adjusted. 8. Voltage Output Terminal Array. The Voltage Output Terminal Array consists of 4 voltage terminals, 2 output and 2 Sense. The right two terminals are the voltage high and voltage low output terminals. All voltage outputs are derived from these terminals. The left 2 terminals are the Sense High and Sense Low terminals. These terminals are used to make the sense connections in a four-wire voltage connection. The current and voltage outputs are completely isolated.
!
WARNING !
Caution should be used when making and removing connections to the voltage output terminal array. Always ensure that the calibrator is in the STANDBY state before changing connections. Failure to use appropriate care could result in dangerous electric shock!
9. Current Output Terminals The Current Output Terminals consist of Current Output High and Current Output Low terminals. The Current Output Terminals allow for both binding post and banana type connections. The current and voltage outputs are completely isolated. 10. Output Control Keys There are two Output Control Keys, STANDBY and OPERATE. When in the standby state, the green LED located above the STANDBY key is illuminated. The Voltage terminals are configured as an open circuit and the current terminals are shorted and the output amplifiers are removed from each. Once the desired settings have been established, pressing the OPERATE key will cause these settings to be present at the output terminals. At voltage settings of greater than 30V an audible warning can be sounded for one second before the output is actually activated. Whenever the calibrator is in the OPERATE state the red LED located over the OPERATE key is illuminated. To remove the output and restore the output terminals to a safe condition, simply press the STANDBY key. The STANDBY key is the only key that functions when the calibrator is in the remote state. Pressing the STANDBY key when in REMOTE and OPERATE will cause the calibrator to revert to the standby state and local control. Pressing this key when in REMOTE and STANDBY will cause the calibrator to simply revert to local control. 11. DMM Input Terminals (Optional). The DMM Input Terminals consist of 3 terminals labeled V, COM, and I. The terminal labeled V is used for AC and DC voltage or frequency inputs. Maximum voltage input is 1000V. Then terminal labeled I is for AC or DC current inputs. Maximum current input is 25mA. The terminal labeled COM is the common for both the voltage and current input terminals. Located to the left of the current input terminal is a protection fuse for the current input.
2-7
Rotek® Instrument Corp., 390 Main Street, Waltham Massachusetts 02452 USA Tel. (781) 899-4611 Fax (781) 894-7273 Email: [email protected] Rotek Model 8000 User Manual Chapter 2 – Operating Instructions
12. Menu Selection Keys. The Menu Selection Keys consist of 5 keys used to maneuver through the various configuration menus of the Model 8000. The MENU key must be pressed to activate the menu system. Pressing the MENU key when already in the menu system will exit the menu system. Once the menus have been activated, the t or s keys are used move the cursor either up or down through the menu choices. Once the desired choice is highlighted, pressing the SELECT key activates the selection. The CANCEL key closes the current menu and moves back one layer in the menu system. 13. Line Power Indicator. The Line Power Indicator is a green led indicating that power has been applied to the calibrator. The power switch itself is located on the rear panel beside the line cord receptacle. 14. System Setting Display. The System Setting Display is an LCD Graphic display which provides all information relative to the present status or configuration of the calibrator. In its normal state this display indicates the status of the calibrator. Items displayed are Status, Sense, Control and Date and Time. Status will indicate ‘OK’ in normal operation. Whenever either frequency or phase angle output settings are changed Status will indicate ‘Updating’ as the output waveform is computed and verified. In the event of either a voltage or current overload the Status will indicate either ‘V Overload’ or ‘I Overload’ respectively. The Sense item will indicate the voltage sense as either ‘Internal’ or ‘External’. The Control item will indicate the control state as either ‘Local’ or ‘Remote’. The setting of the internal real time clock is displayed in the bottom of this display. The clock settings are maintained regardless of whether the calibrator connected to line power or not. Once the MENU key is pressed the System Setting Display changes to display the main menu. The menu keys may be used at this point to navigate through the menu system. The standard System Setting screen is shown in Figure 2-3. Voltage Sense Mode Status Message Error Message
Deviation Display Energy Mode Display
OK
Control Mode
Local Date & Time
Internal
DMM Display
4 Jan 96 10:17am Figure 2-3 System Settings Display
2-8
Rotek® Instrument Corp., 390 Main Street, Waltham Massachusetts 02452 USA Tel. (781) 899-4611 Fax (781) 894-7273 Email: [email protected] Rotek Model 8000 User Manual Chapter 2 – Operating Instructions
Rear Panel Connections Figure 2-4 illustrates the location of all rear panel connections. Each item is numbered and a description of the function of each appears below. 1. Power Amplifier Cooling Fan. Provides cooling air for the power amplifier heat sinks. 14
13
1
12
2
3
4
5
6
7
8
9
10
11
Figure 2-4 Rear Panel Connections
2. Ground Stud. Provides chassis grounding point for the calibrator. It is connected via the third wire of the power cable to the line power protective conductor. 3. External Amplifier Connector. External amplifiers such as the Option 8000-200A are connected using this 9 pin D-SUB type connector. Always use the interconnect cable supplied by Rotek. 4. Multi-Phase Connector The Option 8000-3P, 3 phase extender, is attached using this 15 pin D-SUB type connector. Be certain to always use the interconnect cable supplied by Rotek. 5. Rear Panel Voltage Output Terminals The rear panel voltage output terminal array is a duplicate of the front panel voltage output terminals. Output is switched from front to rear terminals using ‘Terminals menu choice.
2-9
Rotek® Instrument Corp., 390 Main Street, Waltham Massachusetts 02452 USA Tel. (781) 899-4611 Fax (781) 894-7273 Email: [email protected] Rotek Model 8000 User Manual Chapter 2 – Operating Instructions
!
WARNING
!
Caution should be used when making and removing connections to the voltage output terminal array. Always ensure that the calibrator is in the STANDBY state before changing connections. Failure to use appropriate care could result in dangerous electric shock!
6. Rear Panel Current Output Terminals. The rear panel current output terminal array is a duplicate of the front panel current output terminals. 7. Line Cord Receptacle. 8. Power Switch. 9. Line Fuse Holder. 10. Cooling Exhaust Fan. Always ensure that when power is applied the exhaust fan is not obstructed. 11. IEEE-488 Interface Connector. 12. Option Expansion Panel. Space reserved for future option connections. 13. Pulse Counter Input Connectors. Standard BNC type connectors are used to attached pulse inputs from energy meters. Refer to options 8000-CTR and 8000-CTR6. 14. 50A Current Output Terminals. High current output terminals used with option 8000-50A, 50A current option.
2-10
Rotek® Instrument Corp., 390 Main Street, Waltham Massachusetts 02452 USA Tel. (781) 899-4611 Fax (781) 894-7273 Email: [email protected] Rotek Model 8000 User Manual Chapter 2 – Operating Instructions
Menu System The Model 8000 provides an extensive menu system that provides the user with the ability to configure all aspects of the calibrator. To activate the menu system press the MENU key and the main menu will be displayed on the System Settings Display. To exit the menu system, press the MENU key again and the System Settings Display will revert to the normal state. Certain menu choices open ‘Selection Boxes’ which can offer a list of choices. Only four choices are ever displayed in the box even if more choice are available. A small arrow appears in the lower right corner of the selection box to indicate that there are more choices below the visible choices. Likewise, a small arrow appears in the upper right corner of the selection box to indicate that there are more choices above the visible choices. If the visible choices are in the middle of the list an both arrows will be displayed to indicate that there are choices both above and below the visible choices. The t and s keys are used to scroll through the list of choices. Table 2-1 illustrates the Menu System.
2-11
Rotek® Instrument Corp., 390 Main Street, Waltham Massachusetts 02452 USA Tel. (781) 899-4611 Fax (781) 894-7273 Email: [email protected] Rotek Model 8000 User Manual Chapter 2 – Operating Instructions
Main
Calibrator
Menu Item Output Terminals Voltage Sense Line-Line Phase Harmonics Inductive Mode Deviation On/Zero
User Preferences
Overload Delay Power Units
Phase Units
Deviation Units
Temperature Units Language Time Format Date Format System Settings
Front Panel
Front Rear Internal External TBD OFF On Off Voltage Current Power Phase Frequency Watt VA VAR Degree Radian Power Factor Percent PPM Difference Ratio C F TBD 12 Hour 24 Hour D/M/Y M/D/Y Keyboard Sound Operate Warning Menu Timeout Backlight Timeout Video Mode
Set Time Set Date Change Password GPIB Address Calibration
Top Contrast Bottom Contrast