Transcript
CLIVET TALK.COMPACT ELFO ENERGY SMALL application
WSAT EE WSAN EE WSA
Enheter utstyrt med:
WSN
1
WSH
KOMPRESSOR
WSHN
Manual kode MS04N001NO - - 02
KONTROLL SYSTEM MANUAL
Oppdatert med firmware utgivelse : tatastur
base
EJ-T 20-07-2006
EJ-b 21-07-2006
Merk: All informasjon som ansees som relevant for bruker / driftansvarlig, er oversatt til Norsk. All annen informasjon, som vedrører innstallasjon og igangkjøring er beholdt på originalspråket.
INNHOLD 1
SIKKERHET ...........................................................................................6
2
OPPDATERING AV PARAMETERVERDIER ...................................................6
3
HOVED EGENSKAPER .............................................................................7 3.1
4
VALGMULIGHETER .............................................................................................Feil! Bokmerke er ikke definert.
BLOKKSKJEMA OVER SYSTEMET MED TILLEGGSFUNKSJONER ...................8 4.1 4.2 4.3 4.4 4.5 4.6 4.7
PWM MODUL Æ FASE KUTT..................................................................................................................................8 KONVERTER MODUL RS-485 ................................................................................................................................8 BASE MODUL ..........................................................................................................................................................9 “PLUG-IN” EKSPANSJONS MODUL .....................................................................................................................11 LED TASTATUR.....................................................................................................................................................12 TASTATUR ...........................................................................................................Feil! Bokmerke er ikke definert. FJERNTABLÅ.........................................................................................................................................................17
5
TILKOBLINGER .................................................................................... 18
6
START AV ENHETEN ........................... FEIL! BOKMERKE ER IKKE DEFINERT.
7
FORANDRING AV SETTPUNKT ................................................................ 19
8
STATUSER........................................................................................... 20
9
ALARMER ............................................................................................ 21 9.1
SLETTING AV ALARM LOGG ...............................................................................................................................22
10 ALARM LOGIKK .................................................................................... 23 10.1 10.2 10.3 10.4 10.5 10.6 10.7 10.8 10.9 10.10
LAV TRYKK ALARM BEHANDLING ......................................................................................................................23 VARME LAV TRYKK FOR-ALARM ........................................................................................................................23 FROSTSIKRING GRENSEVERDI..........................................................................................................................23 FROSTSIKRING FOR-ALARM...............................................................................................................................23 FROSTSIKRING ALARM .......................................................................................................................................23 FROSTSIKRING VARMEELEMENT ......................................................................................................................23 FROSTSIKRING BEHANDLING I DE FORSKJELLIGE TYPER UTSTYR.............................................................24 STRÅLE PANEL VANN FROSTSIKRING SIKKERHET.........................................................................................24 KJØLE GRENSE ALARM.......................................................................................................................................24 SJEKK AV VANNET VED ΔT KONGRUENS.........................................................................................................24
11 STYRBARE SYSTEM ALTERNATIVER ....................................................... 26 11.1
FLEREVEIS VENTIL FOR VARMT TAPPEVANN..................................................................................................26
12 SETT-PUNKT STYRING .......................................................................... 27 12.1 KORRIGERING AV SETTPUNKT ..........................................................................................................................27 12.1.1 KORREKSJON FOR UTVENDIG TEMPERATUR ............................................................................................27 12.1.2 KORREKSJONON AV ENTALPI........................................................................................................................30 12.1.3 KORREKSJON AV VANN RESET .....................................................................................................................31 12.2 BERGENING AV TOTAL SETTPUNKT ................................................................................................................31
13 VEDLIKEHOLD SETTPUNKT ................................................................... 32 14 KOMPRESSOR TIMING .......................................................................... 32 15 KOMPENSASJONER .............................................................................. 33 15.1 15.2 15.3
KOMPENSASJON AV LASTEN ............................................................................................................................34 KOMPENSASJON AV PAUSE STYRING..............................................................................................................35 KOMPENSASJON AV VARIGHET........................................................................................................................35
16 TEMPERATUR KONTROLL ...................................................................... 36 16.1 16.2
KJØLING ................................................................................................................................................................36 VARME...................................................................................................................................................................37
17 DIGITAL SCROLL MODULERENDE KOMPRESSOR ..................................... 38 18 ELEKTRISK VARME KONTROLL .............................................................. 43 18.1
VARMEREELEMENT SOM INTEGRERT ELEMENT ............................................................................................43 4
18.2 18.3 18.4 18.5
ELEKTRISKE VARMEELEMENT SOM ERSTATTNING FOR KOMPRESSOREN ...............................................43 HOVEDREGULERENDE KOMPONENT VED VARME .........................................................................................43 EFFEKTBEGRENSNING PÅ UTVENDIG TEMPERATUR ....................................................................................44 ANALOG UTGANG BEGRENSNING.....................................................................................................................45
19 STYRBARE ENHETER TYPER ................................................................. 45 a. b. c. d. e. f. g. h.
WSHH – ENHET AV TYPE 8 .................................................................................................................................45 WBAN – ENHET AV TYPE 9 .................................................................................................................................46 WSH – ENHET AV TYPE 10..................................................................................................................................47 WSH – ENHET AV TYPE 11..................................................................................................................................47 WSHN – ENHET AV TYPE 12 ...............................................................................................................................47 WSH – ENHET AV TYPE 13..................................................................................................................................47 WSH – ENHET AV TYPE 14..................................................................................................................................47 WSHN – ENHET AV TYPE 15 ...............................................................................................................................47
20 SIRKULASJONS PUMPE......................................................................... 48 20.1 20.2 20.3 20.4 20.5
ENKEL PUMPE ......................................................................................................................................................48 ENKEL PUMPE + STAND-BY PUMPE ..................................................................................................................48 PUMPE MED VARIABEL KAPASITET...................................................................................................................49 SIRKULERING STYRT AV VARIABEL HASTIGHET............................................................................................49 TO HASTIGHETS SIRKULERING .........................................................................................................................50
21 KONDENSERING KONTROLL .................................................................. 51 21.1 21.2 21.3 21.4
LUFTKJØLTE ENHETER.......................................................................................................................................51 TRYKK TRANSDUCER AVLESNING ....................................................................................................................53 TVANGSSTYRING AV VIFTEN MED KOMPRESSOREN AV ...............................................................................54 VANNKJØLTE ENHETER......................................................................................................................................55
22 STRÅLE PANELER ................................................................................ 56 22.1 22.2 22.3 22.4
VENTIL KONTROLL TIL PANELENE ...................................................................................................................57 STRÅLING SETTPUNKT .......................................................................................................................................57 STRÅLE PANEL FORSTSIKRINGSSIKKERHET FOR VANN...............................................................................58 KJØLE BEGRENSNING VIA DIGITAL INNGANG. ................................................................................................59
23 AVRIMING ........................................................................................... 60 24 TEMPERATUR OMREGNINGSTABELL
- NTC FØLER PÅ VARMER - .............. 63
25 TILGANG TIL PARAMETERENE ............................................................... 64 26 PARAMETER LISTE ............................................................................... 65
1 SIKKERHET FORORD Arbeid, som installasjon, vedlikehold, og tilgang til elektriske komponenter, må kun utføres av kvalifisert personell, i hht. IEC 60364 - International Electrotechnical Commission -. Konfigurasjon, oppstart og vedlikehold må utføres av personell som er: • spesialiset • opplært på systemet og dets komponenter • klar over mulige farer ved systemet (spenning, beveglige deler, varmt og/eller kaldt vann, osv.) Alle spesifikasjoner i datablad, merke-etiketter, manualer og bulletiner må følges under installasjon og oppstar. TILGANG TIL SPENNINGSFØRENDE KOMPONENTER Før arbeide med spenningsførende komponenter, fjern tilførselspenningen med hovedbryteren til enheten, eller fjern spenningen ved å ta ut sikringer. Sjekk alltid at utstyret er skikkelig jordet, og kvaliteten på dette.. .
2
OPPDATERING AV PARAMETERVERDIER
Parameter verdiene i dette dokumentet er updatert til den aller siste versjon, til d.d.. Noen parameter lister som refererer til “type” enheter er vedlagt på slutten av dokumentet. Parameters kan forandres på grunnlag av erfaring ved bruk over tid. Derfor, kan du finne andre parametere, på enheten, enn de som er vist her. Ved tvil, referer til parameterlisten for gjeldende enhet, basert på serienr..
3
HOVED EGENSKAPER
Kontroll systemets hoved egenskaper: •
1-kompressor styring
•
kjøler/varme pumpe
•
avkjølt luft eller vann
•
fjern VARME - KJØLING omkobling
•
fuktighetsføler (settpunkt korreksjon, entalpi avriming)
•
vann reset (settpunkt forandring) mod. plug-in
•
2. settpunkt ( eco )
•
VEDLIKEHOLD settpunkt (systemet innenfor arbeidsgrensene)
•
variabel settpunkt styring (forandres ved: utv. temperatur, entalpi, vann reset)
•
variabel kompressor beskyttelse (kompensasjoner: last, pause styring, driftstid)
•
variabel pumpe styring (reserve pumpe, variabel kapasitet)
•
integrerte elektriske varmeelement mod. plug-in
•
stråle paneler mod. Plug-in
•
system kommunikasjon CLIVET TALK
•
grensesnitt RS 485 mod. rs 485
Noen av disse funsjoner er bare tilgjengelig ved installering av tilleggsmoduler.. 3.1
VALGMULIGHETER WSAT EE
circulator ON - OFF
YES
WSAN EE YES
WSA YES
WSN YES
WSH YES
WSHN YES
Reserve pump
OPT
OPT
OPT
OPT
OPT
OPT
Variable capacity
OPT
OPT
OPT
OPT
OPT
OPT
2 speeds
OPT
OPT
OPT
OPT
OPT
OPT
Water differential pressure switch Inlet and outlet probe Coil temperature probe
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
-
YES
-
YES
-
YES
External air temperature probe
OPT
YES
OPT
YES
OPT
YES
Pressure transducer
OPT
YES
OPT
YES
OPT
Humidity probe
OPT
Ventilation ON - OFF
YES
OPT -
OPT YES
MODULATING ventilation
OPT
Integrating electric heaters
OPT
OPT
OPT
water reset
OPT
OPT
module RS 485
OPT
OPT
Modulating external pump control
OPT
Radiating panels
OPT
YES
YES
OPT
OPT
OPT
-
-
-
-
-
OPT
OPT
OPT
OPT
OPT
OPT
OPT
OPT
OPT
OPT
OPT
OPT
OPT
OPT
OPT
OPT
OPT
OPT
OPT
OPT
OPT
OPT
YES
4
BLOKKSKJEMA OVER SYSTEMET MED TILLEGSFUNKSJONER PLUG-IN MODULE C5110767
MAIN MODULE C5110760
MODULE PWM- PHASE CUT C5111026 1
CN 2
2 3 4
2 2
5
2 3 2 4 2 5 2 6
6 7
8 9 1 0 1 1 1 2
2 7 2 8 2 9 3 0
CN 1
1
CN3
1
1
gn d
+5v
1 3
1 4
1 5
1 6
1 7
1 1 8 9
2 0
gn d
2 1
max. 100 m
CONV. MODULE RS-485 C5110761
OUT 12 VDC
AC DC
LOCAL KEYBOARD C5110766+C6541668
REMOTE KEYBOARD
PE2N0001
4.1
PWM MODUL Æ FASE KUTT
Kode C5111026 Denne modulen brukes til å styre kondenserings viften når denne trengs å styres (f.eks. varme pumpe). II II II I
AN1, AN1: PWM inn, tilført via terminal 13 og 15 på hoved modulen
AN1 AN1
I: Nettspenning inn 230 V AC Det må være samme fasen, som er tilkoblet transformatoren til hoved modulen (med 12 V ac ut på CN 1, pin 1 og 2) II, II, II: fase kutt utganger (3 i parallel) spenningstilførselen til vifta.
4.2
KONVERTER MODUL RS-485
KOD C5110761 Installert på hoved modulen for tilkobling til en ekstern seriell linje i RS485 Serial line RS-485
gnd + -
Supply module 12 Vac
4.3
HOVED MODUL
KOD C5110766 Modulen kontrollerer standard funksjonene; tilleggsfunksjonene styres av egne moduler. Figuren viser koblingen til en standard varme pumpe som, ulik kjøleren, har en trykkstyrt vifteregulator, som styrer hastigheten på kondenseringsvifta, føler for batteritemp. og utendørs temp.. 12 Vac 1 P B
6 3 2 1 T T T T B B BB
1 3 2 Q A A S S S
1 A S
C1: kompressor YV1: 4veis ventil RA: Frostsikring varmeelement M4: Kondenserings vifte FSC: Vifte kontroll modul BP1: Trykk regulator BT6: Utendørs lufttemp.føler BT3: Batteri temperatur føler BT2: Vanninntak temp.føler BT1: Vann utgangs temp.føler SP1: Høytrykk bryter SP2: Lavtrykk bryter SQ1: Strømningsbryter/Differensial trykkbryter. SA1: Fjernstyrt PÅ-AV SA2: Fjernstyrt varme/kjøling SA3: Valg 2. settpunkt.
1 2 P P S S
230 v 50 Hz
C1
1 2
1
CN2
1
CN1
3
YV1
4 5 6
RA
BASIC MODULE
7
8
FSC M4
9 1 0 1 1 1 2
+5v
gnd
gnd
13 14 15 16 17 18 19 20 21
. 116 mm 1
7
6
14 12 10 8 6 4
16 14 12
8 6 4
2
1
15 13 11 9 CN1
7 5 3
1
1
2
2 3
13 11 9 CN2
7 5 3
4 6 7
91 mm
5
8
12
9
8 +5 V Tx Rx DTR GND
9 10 11 12
11 5
13 14 15 16 17 18 19 20 21
gnd
2 3
4
8 KORT RESET STRAP Tilkobling for firmware oppdatering via en ekstern programmerer: referansen “I“ indikerer hvordan programmeringskontakten skal tilkobles. 9 RESET STRAP Må alltid være tilkoblet, både ved vanlig drift og under programmering. For å restarte modulen, ta ut strappen et kort øyeblikk. 11 SERIELL TERMINERINGS STRAP Denne må være tilkoblet hvis “CANopen” seriell skal termineres; denne seiell, hvis brukt, er tilkoblet via pin19, 20 og 21 (når en gateway brukes for å konvertere fra CANOPEN protokoll til en annen protokoll, for eksempel) 12 PIN STRIP “TTL” Ikke i bruk på nåværende tidspunkt.
DIGITALE UTGANGER ( 1 ) KANTKONTAKT Terminal Beskrivelse 1 Nettspenning 230V 2 Kompressor kontroll 3 4 veis ventil kontroll / defrost at hot gas 4 Integrasjon 5 2° pumpe hastighet 6 Frostsikring varmeelement kontroll 7 Ekstern vifte /vannventil /kondenserings pumpe ( 2 ) KANTKONTAKT 8 Fase inngang 9 Fordamper pumpe kontroll 1 10 Fase inngang 11 Kumulativ alarm signallering (NO) 12 Kumulativ alarm signallering (NC) ( 3 ) KANTKONTAKT DIVERSE 13 Viftekontroll (PWM) 14 Variabel pumpe kontroll (PWM) 15 Felles referanse for (13) e (14) 16 Tastatur strømforsyning (+12V - 2.5VA) 17 Net (+Clivet Bus serial positiv) 18 Gnd (-Clivet Bus serial negativ) 19 GND – CAN OPEN serial 20 L – CAN OPEN serial 21 H – CAN OPEN serial
Merknad
Relèer MAKS 5 A (AC1) - 250V AC
MAKS 5 A (AC1) – 250 VAC
DIGITALE INNGANGER ( 6 ) MULTIPOLAR PLUGG CN1 Pin 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Beskrivelse Kort strømforsyning Kort strømforsyning Kondensator strømning Lav trykk Begrensning kjøling Fase vakt Høy trykk Kompressor 1 sikkerhet + Vifte 1 sikkerhet Vann fylling system Ledig Inngang felles fra 1 til 10 Fjernkontrollert PÅ-AV Fjernkontrollert Varme – Kjøling Valg av 2. settpunkt / ”Forespørsel” om varmt tappevann Strømningsbryter Inngang felles fra 12 til 15
Merknad 12 VAC / 12 VDC
Innganger isolert med OPTO-koblere Spenning 12 VAC eller 12 V-15 VDC
ANALOGE INNGANGER UTGANGER ( 7 ) MULTIPOLAR PLUGG CN2 Pin 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Beskrivelse Veksler vannutgangs temperatur Strålingspanel vann temperatur Veksler vann inngangs temperatur Krets 1 batteri temperatur Utgangs temperatur føler for elektrisk varmeelement Ekstern luft temperatur GND (jord) (Temperatur føler felles) Krets 1 trykk Ekstern RH% +12V (Trykkføler felles) Analog utgang 0-10V (vifter / vann ventil) Analog utgang 0-10V (Pumpe inverter) Analoge utganger felles
Merknad
NTC 10 kilohm at 25 °C
4-20 mA inn
0-10 V ut
4.4
“PLUG-IN” EKSPANSJON MODUL
KOD C5110767 Er plassert over hoved modulen for å kontrollere tilleggsfunksjonene: • Integrerte varmeelement ( side 35 ) • vann reset ( side 27 ) • strålingspaneler ( side 48 )
13
14
12 10 8 22 23 24 25 26
15
6
4 2
CN3 11 9
7 5 3
1
27 28 29 30
( 13 ) ANALOGE SIGNALER UTGANGER PIN Beskrivelse 1 Ledig 2 Ledig 3 Integrasjon 4 Stålingpaneler ventil 5 Proporsjonal kompressor styring 6 Gnd (Jord)felles for utgang fra 1 til 5 og (12) INNGANGER PIN Beskrivelse 7 Vann reset 8 Ledig / WBAN trykk føler 9 +12V positiv strømforsyning(7), (8) e (11) 10 Ledig 11 Inngang 0-10V (Ikke i bruk) 12 Ikke i bruk
Merknader
0-10 V
Merknader INN 4-20 mA ikke kontrollerte innganger
DIGITALE UTGANGER ( 14 ) AVTAGBART TERMINAL KORT Terminal Beskrivelse 22 Nettspenning 230V Strålingspaneler ventil 1 23 24 Strålingspaneler pumpeventil 25 Strålingspaneler ventil 2 26 Varmt tappevann ventil kontroll ( 15 ) AVTAGBART TERMINAL KORT Terminal Beskrivelse 27 Nettspenning 28 Vanninntak solenoid ventil for varme pumpe 29 Nettspenning 30 Vannutgangs solenoid ventil for varme pumpe
Merknader 5 A 250 VAC
Merknader 5 A 250 VAC
4.5
LED TASTATUR KNAPP FUNKSJON
KOMFORT modus
VARME
1° settpunkt
ØKONOMI modus
KJØLING
2° settpunkt
1.1.1.1 PÅ / AV LANGT trykk
LED funksjons test
LED INDIKASJON ELEKTRISK krets alarm
VINTER funksj.
KULDEMEDIUM krets alarm
SOMMER funksj.
VANN krets alarm
enhet PÅ / AV / VEDLIKEHOLD (Blinker)
På tastaturet, kan du se, og forandre funksjonene til enheten. Service tastaturet trengs for å vise, og oppdatere funksjonsparameterene. PÅ - AV PÅ – AV funksjonen på tastaturet, aktiverer og deaktiverer enhetens normale funksjoner. INNSTILLING AV ARBEIDS MODUS KJØLING: for å stille inn SOMMER modus, trykk Når den er blitt aktivert, lyser tilsvarende grønne LED.
knappen, og hold den inne en liten stund.
knappen, og hold den inne en liten stund. VARME: for å aktivere VINTER modus, trykk Når den er blitt aktivert, lyser tilsvarende grønne LED. VEDLIKEHOLD: Den grønne LEDen som indikerer driftsmodus, fortsetter å lyse, selv om maskinen er i vedlikehold modus. Vedlikehold settpunktet (hvis aktivert) kontrollerer vann temperaturen når enheten er AV eller i STANDBY. For å gjøre dette, blir sirkulasjonspumpen aktivert periodisk, slik at vanntemperaturen kan sjekkes, og kompressoren starter, hvis nødvendig.. VALG AV ARBEIDS TEMPERATUR KOMFORT: for å velge KOMFORT temperatur for gjeldende arbeidsmodus, trykk KOMFORT knappen. Settpunktet vises bare på maskinen. Når denne modusen er aktivert,, vil LEDen til venstre for knappen tennes, og være tent. ECO: for å velge ØKONOMI temperatur for gjeldende arbeidsmodus, trykk ECO knappen. Settpunktet reduseres i vinterdrift, og økes i sommerdrift. Når denne modusen er aktivert, vil den grønne LEDen til venstre for knappen, blinke sakte. SIGNALLERING AV PRODUKSJON AV VARMT TAPPEVANN
VARME modus + vinter modus + Fremstilling av varmt tappevann VARME modus + sommer modus +
Blinker
på
På
blinker
fremstilling av varmt tappevann
ALARMER BLINKENDE LED: det er en uregelmessighet med AUTOMATISK reset FAST LYSENDE LED: det er en uregelmessighet med MANUAL reset ALARM RESET: TEST + ON/OFF knapper trykkes samtidig i mer enn 2 sekunder Alarm type:
ELECTRISK KRETS ALARM Inngangs føler Utgangsføler Strålingspanel vannføler Batter/strømnings føler Ekstern føler Trykk 1 føler Vann reset inngang Ekstern føler for relativ fuktighet Fase monitor Varmeelement utgangs føler Plug-in trykk føler (WBAN)
KJØLE KRETS ALARM HP LP CCMP/VENT HP1 Pre-Alarm BP1 Pre-Alarm
VANN KRETS ALARM Strømningspumpe Vannfylt system Frostsikrings alarm Frostsikring FORAlarm Pumpe alarm C1 FORAlarm PRad. Kjølebegrensning alarm PRad. Vann frost alarm Batteri frost alarm Alarm ?T° inkongruent Varmeelement frostsikring alarm
FUNKSJONS TEST “Test” bekrefter at alle 6 LEDen fungerer tilfredsstillende. Når den er trykket inn, lyser alle LEDene, helt til knappen slippes. FIRMWARE VERSJON INDIKERING Tastaturets firmware versjon står på en merkelapp på innsiden av LED tastaturet .
4.6
TASTATUR
KOD C 5110799 ( tastatur ) + C6541668 (silk-screen print ) For tastaturets bruker modus, se: set modifikasjon, side. 16, alarmer side 18. , statuser side. 17, passord side. 56 I noen serier/størrelser kan ikke tastaturet monteres. In this case, the following controls are given through external arranged by the customer: REMOTE ON- OFF , HEAT – COOL , SECONDARY Set point Det nye UNIFIED C5110799 tastaturet tilpasser seg automatisk basis firmwaren, slik at det ikke er nødvendig å programmere den for hver type enhet. Den kan også ta seg av ALARMER, alvorlige varslet med den vanlige E…. , og SIGNALLERING, mindre alvorlig med C… eller S…. Når LEDen lyser, må avlest verdi På displayet ganges 100 Indeks Dispaly
Verdi Display
Defrosting Avri di statostatus delloled 1 1
Compressor status led Led di stato 1 del compresso re 1
Pump status della led pompa Led di stato
Key ++led Tasto ledCooling Raffreddamento On-offdikey Tasto On-Off
Key + led heating Tasto + led Riscaldamento
Status per menuingresso inlet keynel menu Stati Tasto
Key forincremento value increase or decrease tasti per e decremento dei valori
Parameter inletnel keymenu parametri Tasto per menu ingresso Index scrolling key indici Tasti per scorrimento
Menuper andingresso log alarmsnel inlet key e nello sorico allarmi tasto menù
Led ON-OFF: Lyser bare hvis enheten er påslått. Led HEAT: Lyser når enheten er i VARME modus, også hvis enheten er AV Led COOL: Lyser når enheten er i KJØLE modus, også hvis enheten er AV Led SET : Lyser når PARAMETER SETTING menyen er aktiv Led STATUS : Lyser når ENHETENS STATUS meny er aktiv Led ALARM : Lyser bare i ALARM LOG menyen, blinker ved alarm. Led “Defrosting status 1”: lyser når avriming pågår, blinker for timerstyrt avriming Led “Compressor status 1”: lyser når kompressoren er PÅ, blinker for timerstyring Led “Pump status”: Lyser når pumpa går. Led “multiplier by 100”: Når den lyser, må avlest verdi i displayet ganges med 100. Led ON-OFF: Lyser bare når enheten er PÅ.
Led HEAT: Lyser når enheten er i VARME modus også når enheten er AV Led COOL: Lyser når enheten er i KJØLE modus også når enheten er AV Led SET : Lyser når PARAMETER SETTING menyen ier aktive Led STATUS : Lyser når ENHETENS STATUS meny er aktive Led ALARM : Lyser bare i ALARM LOG menyen, blinker ved alarm.. Led “Defrosting status 1”: lyser når avriming pågår, blinker for timerstyrt avriming Led “Compressor status 1”: lyser når kompressoren er PÅ, blinker for timerstyring Led “Pump status”: Lyser når pumpa går. Led “multiplier by 100”: Når den lyser, må avlest verdi i displayet ganges med 100.
4.7
REMOTE KEYBOARD
COD C5110799 (keyboard code only) The figure shows the connections of the local keyboard (if installed) and of the remote keyboard (optional). The two keyboards work in parallel and practically perform the same functions. After having supplied each keyboard, assign the relevant address within the network. keyboard on machine Keyboard address on the Clivet Bus network: Par 207 = 7 =1 remote keyboard If the unit is equipped with a led keypad rather than with a keypad with 7 segments ( C5110776 ) , the remote keypad must have address 7. Connection with the remote keyboard: • • •
shielded and twisted cable 2 x 0.35 mm2, max. 100 m installed according with the relevant norms (electric systems) laid within a dedicated raceway and far from power cables.
Terminals on the keyboard seen from the rear: 1e2 For the keyboard standard operation the two jumpers must be off to change the firmware bridge the two jumpers. 3 connector to be used to change the firmware (connection with the flash programmer… eeprom ) .
UNIT 1
3 DTG +5 V TxRxR N D
gnd +12V +12V
13 14 15 16 17 18 19 20 21
NET
MAX 100 m
gnd
2x0.35 mm twisted and shielded
2
2
1
2
3 gnd
NET
gnd +12V +12V
gnd +12V
PE2N0001 F N PE 230 VAC
5
CONNECTIONS TO THE CUSTOMER CARE
REMOTE ON-OFF : remote switching on and off of the unit compulsory connection on the units without keyboard always enabled, not linked with par 163 Remote input configuration connections on basic module, CN1 pin 12 e 16 REMOTE HEAT-COOL : switching from summer to winter mode and vice versa compulsory connection on the units without keyboard enabled only if par 163 Remote input configuration = 0 connections on basic module, CN1 pin 13 and 16 SECONDARY SET-POINT : enabling of a second set-point usually higher in summer and lower in winter than the standard set-point. enabled only if par 163 Remote input configuration = 0 connections on base module, CN1 pin 14 and 16 par 29 Summer secondary set-point 10 °C par 30 Winter secondary SetPoint 35 °C par 31 Enable second Set 0 num EXTERNAL AIR TEMPERATURE PROBE : see the paragraph on Ext. temperature correction on page Feil! Bokmerke er ikke definert.4 connections on basic module, CN2 pin 6 e 7 SONDA UMIDITÀ ARIA ESTERNA : see the paragraph on Ext. temperature correction on page 306 connections on basic module, CN 2 pin 9 and 10 WATER RESET : see the relevant paragraph page 317 connections on optional plug-in module, CN3 pin 7 and 9 REMOTE KEYBOARD : connections on base module, removable term. 16 17 18 RADIATING PANELS : See the relevant paragraph on pag 48 The following connections are required for this function: Temp. probe. (connections on basic module CN2 pin 2 and 7 ) Valve (connection on optional module on page 10) Pump (connections on optional plug-in module on page 10) Cooling limit (connections on base module, CN1 pin 5 and 11)
6
START AV ENHETEN
OF F
Enhet i AV status: • Fra tastatur • Fra FJERN PÅ/AV kontakt
OF F
PÅSLAG: FORLENGET trykk av PÅ-AV KNAPPEN
Visning av UTKOBLING TEMPERATUR
1 1. 6
7
FORANDRING AV SETTPUNKT
1 1. 6
0
2 9
0
- - - -
2 9
1 0. 0
2 9
1 0. 0
Trykk knappen SET
For å komme til ønsket verdi: trykk PIL OPP - NED
Vent 2 sekunder
PARAMETERVERDIEN vises
Justere parameterverdien: knappene
+
e
-
For å komme til andre parametere:
3 0
trykk PIL OPP - NED
1 1. 6
For å avslutte: knappen SET
Liste over parametere, som kan forandres uten passord: Par.
8
Verdi
Måle enhet
Detaljer på side
29
Sommer sekundært settpunkt
10
°C
18
30
Vinter sekundært settpunkt
35
°C
18
32
Sommer Settpunkt
5.7
°C
27
33
Vinter Settpunkt
41.2
°C
27
42
Sommer vedlikehold settpunkt
20
°C
32
43
Vinter vedlikehold settpunkt
30
°C
32
44
Enable sommer vedlikehold
0
num
32
45
Enable vinter vedlikehold
0
num
32
77
Settpunkt frostsikringsvarmer
4
°C
43
80
Frostsikring alarm
4
°C
22
84
Frostsikring for-alarm
4.5
°C
22
117
Settpunkt for varmt tappevann
35
°C
163
Innstilling av fjerninnganger : 0= H/C fra fjerntablå, 1=H/C fra tastatur/ansvarlig
207
Tastatur addresse på Clivet Bus nettverket
0
num
17
STATUSER
1 1. 6
For tilgang, trykk STATUS
1
5. 5
STATUS vises For å kome til STATUS 2: PIL OPP
2
5. 0
Tilgang til de forskjellige statuser : PIL OPP – NED
1 1. 6
For å avslutte : trykk STATUS
MASKIN STATUS MENY INDEKS BESKRIVELSE Aktuelt settpunkt 1 2 3 4 5 6 7 8
VERDI °C
Temperaturfall i grader celcius, levert av kompressoren, med mulig kompensasjon inkludert °C (detaljer side 32 )
Timer for ressurs aktivering Når denne telleren har nådd verdien, satt i parameter (TimeScan), vil kontrolleren sammenligne utgangstemperaturen mot settpunktet, og hvis nødvendig, aktiverer ressursene (kompressor og/eller varmeelementer) Dynamisk TimeSkan for ressurs aktivering Verdi i grader for kompensering av utvendig temperatur Verdi i grader av kompensasjonen, pga. vann reset signal KompCar + KompOn + KompDuty summering Verdi i grader av kompensasjonen pga. duty-cycle.
Sekunder Sekunder
°C °C °C °C
MASKIN STATUS MENY INDEKS 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37
9
BESKRIVELSE Inngangs temperatur Utgangs temperatur Vanntemperatur på strålings panelene Batteri temperatur Kondenseringstrykk Prosentvis Vifte/Ventil 1 Varmeelement utgangstemperatur WBAN kondenseringstrykk Modulerende kompressor utgangsstatus Vannreset signal verdi Utvendig temperatur Utvendig fuktighet “Unit watch” ( kun enhetens driftstimer ) Driftstimer C1 Starter C1 Strålingspanel ventil status Strålingspanel ventil status Pumpe prosentandel Integration heaters status Radiating panel valve status (Out-1) Radiant set point
Tastatur programvare Validation year of keyboard SW Validation month of keyboard SW Validation day of keyboard SW Base Software Validation year of base SW Validation month of base SW Validation day of base SW
VERDI °C °C °C °C Bar 0-100% °C Bar % 4-20 mA °C 0-100% Num Num Num ON-OFF % % ON-OFF ON-OFF °C EJ – t ( ELFO 2006 07 20 EJ – b (ELFO 2006 07 21
ALARMER BLINKING alarm kode enhetens driftstimer ved hendelsen
E 1 1
2
E 1 1
2
KORT trykk på knappen ALARM Gir tilgang til ALARM LOGGEN Den ALLER SISTE alarmen vises
E 1 1
2
For å sjekke alarmer i loggen: PIL NED
E 1 7
2
KORT trykk på knappen ALARM: Går ut av alarmloggen
E 1 1
2
For å NULLSTILLE alarmene: LANGT trykk på knappen ALARM
INDEX
RESET
Defekt, eller frakoblet føler på vanninngangen
Auto.
1 2
E
Defekt, eller frakoblet føler på vannutgangen
Auto.
3
E
Defekt, eller frakoblet vannføler på strålingspanelet (strålingspanel option)
Auto.
4
E
Defekt, eller frakobler føler på batteriet
Auto.
5
E
Elektrisk varmeelement utgangsføler
Auto
6
E
Defekt, eller frakoblet ekstern føler
Auto.
7
E
Defekt, eller frakoblet trykk transducer
Auto.
8
E
WBAN plug-in trykkføler
Auto
9
S
Vannreset inngang kortsluttet, eller ute av området
Auto.
10
E
Defekt, eller frakoblet RH% føler
Auto.
11
E
Høytrykk
MANUAL
12
E
Lavtrykk
Auto.
13
E
Kondenseringsvifte og/eller kompressor termisk bryter
MANUAL
14
E
Varmeelement frostsikrings alarm
MANUAL
17
E
Strømningspumpe
Auto.
18
E
Lavtrykk på vann rørsystemet
MANUAL
19
E
Fase monitor
Auto.
20
E
Frostsikring alarm
MANUAL
21
S
Frostsikring FORAlarm
Auto.
22
S
Høytrykk ForAlarm
Auto.
24
S
Pumpe bytte (system med hoved pumpe og stand-by pumpe)
Auto.
25
E
Kondensator strømningsalarm (differensial trykkbryter, kun vannkjølte enheter) Auto.
30
E
Batteri ising alarm
MANUAL
31
E
Kjøling / Varme begrensning alarm (strålingspanel option)
Auto.
32
E
Vann frost alarm (strålingspanel option)
Auto.
E
Inkongruent deltaT alarm
MANUAL
33 34
9.1
ALARM E
S / E BP1 for-alarm
Auto.
SLETTING AV ALARMLOGG
Et passord (= 101), bekreftes ved å trykke “pil opp”, sletter alarm loggen, og nullstiller maskin klokken (detaljer side 56)
10 ALARM LOGIKK 10.1 LOW PRESSURE ALARM MANAGEMENT The low pressure alarm reset is automatic. It gets manual if the alarm occurs for the number of times set by the following parameter within one hour: par 69 hourly LP max. alarms 5 The low pressure alarm is temporarily disabled when the compressor starts in order to allow settlement of pressure. The bypass time is defined as follows: par 61 summer bypass time 12 ( 12 x 10 = 120 sec ) par 62 winter bypass time 18 ( 18 x 10 = 180 sec ) After this time every trip of the LP switch immediately stops the compressor.
10.2 HEAT LOW PRESSURE PRE-ALARM The fan, only in winter operating , can be forced at the max. speed if the evaporating pressure falls down the value defined by par 65 SetPreBP1 . The forcing stops when the evaporating pressure goes up the value of par 48 DiffBP1 . The forcing is signalled by the automatic E 34 alarm. par 47 BP1Enabled Enables the low pressure 1 pre-alarm 48 DiffBP1 Low pressure 1 pre-alarm differential 3.5 bar 65 SetPreBP1 Low pressure 1 pre-alarm set 0.5 bar
10.3 ANTIFREEZE THRESHOLDS The antifreeze prevents the outlet temperature from going below a set threshold; while it decreases, an antifreeze pre-alarm activates, followed by the electric heaters and the antifreeze alarm. Par 76 PreFreeze scan time
10
sec
active in every operating mode. The compressor is deactivated if the outlet temperature is lower than: Par 84 antifreeze prealarm 4,5 °C The compressor switched off due to an antifreeze pre-alarm can be AUTOMATICALLY restarted (if required by the controller) if the temperature rises over par 84 + the value: par 82 antifreeze pre-alarm hysteresis 1 °C
10.4 ANTIFREEZE PRE-ALARM active in every operating mode. The compressor is deactivated if the outlet temperature is lower than: Par 84 antifreeze prealarm 4,5 °C The compressor switched off due to an antifreeze pre-alarm can be AUTOMATICALLY restarted (if required by the controller) if the temperature rises over par 84 + the value: par 82 antifreeze pre-alarm hysteresis 1 °C
10.5 ANTI-FREEZE ALARM Activated when the temperature probe of the water leaving from the exchanger detects a value lower than: par 80 antifreeze alarm 4 °C The antifreeze alarm can be reset manually if the temperature rises over par 80 +: par 83 antifreeze hysteresis 2,5 °C . The antifreeze alarm can be set within the limits: par 78 Antifreeze set min. limit 4 °C par 79 Antifreeze set max. limit 15 °C
10.6 ANTIFREEZE HEATERS The antifreeze heaters are activated when the outlet temperature goes below the: par 77 antifreeze heater set point 4 °C They will be restarted when the temperature rises over par 77 +: par 81 antifreeze heater differential 2,5 °C
10.7 ANTIFREEZE MANAGEMENT IN THE DIFFERENT UNIT TYPES The safety devices are actives also with the unit in OFF
Unit type
WSAT – WSAN – WBAN
WSH - WSHN
1, 2, 3, 4, 5, 9 Water side
WSHH
6, 7, 10, 11, 12, 13
8
use
use
source
evaporator
condenser
Evaporator output
Evaporator output
Source water output
Evaporator output
Source water output
CN 2 term 1,7
CN 2 term 1,7
CN 2 term 4,7
CN 2 term 1,7
CN 2 term 4,7
E 20
E 20
E 30
E 20
E 30
Antifreeze alarm sert
par 80 AlFreeze
par 80 AlFreeze
par 208 SetFreezeExt
par 80 AlFreeze
par 208 SetFreezeExt
Differential for MANUAL reset
83 IstAlFreeze
83 IstAlFreeze
83 IstAlFreeze
83 IstAlFreeze
83 IstAlFreeze
Reference probe Connected to terminals Antifreeze alarm
UNIT IN COOL / HEAT
Pump digital outputs activated by the alarm
UNIT IN COOLING
E20 = ON
E20 = ON
E30 = ON
evaporator pump
evaporator pump
Source pump
Removable term. block 2 8,9
Removable term. block 2 8,9
Removable term. block 1 1,7
E 20 = ON
E 30 = ON
evaporator pump
Source pump
Removable term. block
Removable term. block
2 8,9
1 1,7 UNIT IN HEATING
E 20 = ON
E 30 = ON
Source pump
evaporator pump
Removable term. Block
Removable term. block
1 1,7
2 8,9
UNIT IN COOL / HEAT
Pump digital outputs activated by the alarm
UNIT IN COOLING
Use water
Use water
Source water
Activated at 100 %
Activated at 100 %
Activated at 100 %
Use water
Source water
Activated at 100 %
Activated at 100 %
UNIT IN HEATING Source water
Use water
Activated at 100 %
Activated at 100 %
Antifreeze heater ON
se t < par 77
se t < par 209
se t < par 209
se t < par 209
Attive se t < par 209
Antifreeze heater OFF
t > par 77 + par 81
t > par 209 + par 81
t > par 209 + par 81
t > par 209 + par 81
t > par 209 + par 81
10.8 RADIATING PANEL WATER ANTIFREEZE SAFETY See the relevant paragraph, page 58
10.9 COOLING LIMIT ALARM See the relevant paragraph, page Feil! Bokmerke er ikke definert.
10.10
CHECK OF THE WATER ΔT CONGRUENCE
The function is active on all the units that are reversible on gas without an enabling parameter . The Δ t is checked after 120 sec starting from the first power step activation . The alarm is determinated : • in COOLING with t.OUT > tIN • in HEATING with tOUT < tIN During the block the circulation pump is active . The alarm reset is always allowed, manually .
MAX. VENTILATION - HP1 COOL PREALARM
The fan speed control logic is explained on page45: In the units including this option, it is possible to enable a pressure threshold over which the fan is forced to the max. speed. To prevent stop due to high pressure. Par 111
Enable HP1 prealarm
0
the fan sets to the max. silenced speed, equal to 100% the max. applicable voltage if during the operation the condensing pressure rises over the value: par 112 set summer HP1 prealarm 25 bar goes back to 80% when the pressure lowers to the value par 112– par 113 delta summer HP1 prealarm 2 bar A log alarm signal is expected when condensing pressure goes over par 112 . FLOW ALARM MANAGEMENT
The management referred to a unit configured with single pump + stand-by pump is shown as example . UNIT START
COUNTING START 25 SEC (flow bypass time= par 142 )
UNIT' ON PUMP ON No
ELAPSED 25 SEC (flow bypass time = par 142 ) CLOSED FLOWSWITCH ?
No
PUMP STOP FLOW ALARM SIGNAL RESTART BY MANUAL RESET ONLY
Yes Yes
THE PUMP STILL OPERATE NORMALLY Yes
No ELAPSED 25 SEC ? (compressor start delay time= par 143 )
A TRIAL WITH THE STAND-BY PUMP HAS BEEN MADE ALREADY
Yes COMPRESSOR HAS BEEN STARTED THE PILOT PUMP STOPS AND THE STAND-BY ONE STARTS FAULT ON WATER FLOW No
THE COMPRESSOR STOPS SIGNALLING PUMP STILL OPERATING FOR 120 SEC. ( par 145 )
THE FLOW ALARM IS RECOVERED BEFORE THE TIME HAS ELAPESD 120 sec
FLOW ALARM MANAGEMENT WITH WATER CONDENSATION WINTER : the alarm is bypassed for the time par 107 TimeOffV from the condenser pump starting SUMMER : the alarm is bypassed for the time par 107 TimeOffV from the evaporator pump starting
11 MANAGEABLE SYSTEM OPTIONS The system can manage le following options (all at the same time, only one or two by choice): • heating integrative element (heaters or boiler, details on page 35) • 3-way valve for sanitary water • double temperature – radiant panels (details on page 48) Below is an indicative diagram with all options. UNIT’
RADIANTS
INSTALLATION
T Ext
On-Off / 0-10V
T. Rad
T IN YVR
FAN COIL
T OUT
BOILER
HYDRAULIC MODULE HEATING INTEGRATION
3-WAY VALVE
11.1 WAY VALVE MANAGEMENT FOR SANITARY WATER By par 50 = 1 the input of the 2° set point on the main board is configured as SANITARY WATER REQUEST. It is possible to manage a 3-way valve for the sanitary hot water production by a dedicated set point (par 117) It is necessary the expansion plug-in module that must be enabled by parameter 140 = 1 .
MODE
INPUT 2° set point on the main board
VALVE POS.
SET POINT
2° SET POINT
HEATING
ON
to the installation
set HEAT
2° setpoint heat *
SANITARY WATER
OFF
to the boiler
SetH2OSanitaria
not manageable
ON
to the installation
set cool
2° setpoint cool *
OFF
to the installation
set cool
2° setpoint cool *
COOLING
* enable : from led keypad or setting the par 49 =1 Par
Description
Meaning
value
49
Comando2°Set Mode control 2° set point by parameter
0
50
EnH2OSanitaria Enabling sanitary water valve management
0
117 SetH2OSanitaria Set Point sanitary water 140
PlugInEn
35
Enables the PLUG-IN presence. 1=YES / 0=NO
The setH2Osanitaria is not loaded of the different compensations and corrections ; only the relative compensation is in case active at the external temperature limit ( par 73 , see page 30 )
12 SET-POINT MANAGEMENT The controller uses two set-points, one for summer and for winter Par Par
32 33
Summer Set Point Winter Set Point
def = 5.7 def = 41.2
°C °C
In both cases the set-point is automatically limited within the max. and min. limits defined by Par Par Par Par
25 26 27 28
MAX Set Heat Min Set Heat Max Set Cool Min Set Cool
def = 51 def =22 def = 21 def = 5
°C °C °C °C
12.1 CORRECTIONS ON SET-POINT The corrections are aimed at optimising the unit energy efficiency.
To achieve this, the corrections modify the set-point dynamically according to certain variables. For example, in the summer operation with low external temperatures, thus with reduced load, it is possible to obtain an indoor comfort with set-points even higher than the standard, thus with a higher energy efficiency
Correct Set Point (es 6.7 °C)
Slettet: Summer/Winter Slettet:
correction Set Point (es 5.7 °C)
The static set-point can be modified dynamically with two CORRECTIONS based on as many factors external to the unit: •
correction based on the external temperature/enthalpy
•
correction based on the Water reset (signal 4-20 mA supplied by the customer)
The correct set-point, to which all corrections have been added or subtracted, is identified as ACTUAL set-point and is displayed by the status n°1 ( see page 20 )
ACTUAL Set point or right ( state n° 1 ) CORRECTIO N Summer/Winter Set Point 12.1.1
CORRECTION ON THE EXTERNAL TEMPERATURE
This function can be activated on the chillers only if the external air probe BT6 is installed (basic module, CN2 pin 6 and 7) Par 152 EXT. air probe presence 1 num Par 9 Comp. enabling for external temperature = 0 no compensation 1 compensates in summer mode only 2 compensates in winter mode only
Slettet: Summer/Winter
3 modes
compensates in both
SUMMER In the summer operation with low external temperatures a reduced cooling demand is supposed. Thus, the indoor confort can be obtained even with set-points higher than the standard. In the summer operation, the correction is added to the set-point (thus it is increased while external temperature decreases. )
Max correction = par 14
ACTUAL set-point correction Par 10
External Temp.
par 11
The max. value of the correction that can be applied is set by: Par 14 Max. value of summer correction The correction is active in the temperature range defined by: Par 10 External temperature for max. summer correction Par 11 External temperature for min. summer correction
6
°C
15 30
°C °C
This function can be used also with a different logic: increase the set-point while the external temperature increases. In this case, the required operation is opposite the previous one; the set values are thus reversed: Par 10 External temperature for max. summer correction 30 °C Par 11 External temperature for min. summer correction 15 °C WINTER
In the winter mode with mild external temperatures (e.g. 15°C) the thermal requirement is supposed low and thus the room comfort can be reached with a lower set-point, too. The correction is thus subtracted from the set-point (thus it is decreased while the external temperature increases )
ACTUAL set-point correction
Correction Max. Value = par 15
External Temp. Par 13
par 12
The max. value of the correction that can be applied is set by: Par 15 Max. value of winter correction The correction is active in the temperature range defined by: Par 12 External temperature for max. winter correction Par 13 External temperature for min. winter correction
10
°C
15 -5
°C °C
The above remarks apply here, too: the function can be used with a different logic: decrease the set-point while the external temperature decreases. The required operation is opposite the previous one; the set values are thus reversed. Par 12 External temperature for max. winter correction -5 Par 13 External temperature for min. winter correction 15
°C °C
CORRECTION ON THE EXTERNAL TEMPERATURE FOR COMPRESSOR OPERATING LIMIT This function allows to extend the operating limit lowering the setpoint when the external temperature decreases SET POINT COMP. =0
COMP. MAX P175
P 74
P 160
par
73
par par par
Text °c
enables correction for the ext temp limit
1=YES
74
external temperature for max heat setpoint
- 2 °C
160
external temperature for min heat setpoint
-15 °C
175
min value settable of the heat setpoint
35 °C
Enabling both the correction for the external temperature ( curve A ) and the correction for limit ( curve B ) , the correct setpoint has this performance : SET POINT
40 °C
A B
37 °C 35 °C -15 °C
-2 °C
15°C
7 °C
T EXT
12.1.2 CORRECTION ON ENTHALPY
The function can be activated only if the expansion PLUG-IN module and the humidity probe are installed. The enthalpy correction is active in the summer operation; in the winter operation the correction is applied only on the external air dry bulb temperature (enthalpy value is not active). The logic is the previously described one: the lower the humidity content in the air, the lower the cooling demand thus the set-point can be increased (compensated)
set point
MAX correction Par 14 = 6 °C
Slettet: Correzione MASSIMA
correzione par 16 = 10.5
Par Par Par Par
14 16 17 156
par 17 = 13.5
Max. value of summer correction External enthalpy min. correction External enthalpy max. correction Enable external RH% probe
temp b.u. °C
6 10.5 13.5 0
°C °C °C num
12.1.3 CORRECTION ON WATER RESET The WATER RESET is a 4-20 mA signal supplied by an external device of the customer. The function can be activated only if the expansion PLUG-IN module is installed. Par 18 Water Reset enabling: 0 not enabled 1 only summer only winter 2 3 summer and winter In SUMMER the correction increases the set-point: with signal at 20 mA = max correction , 4 mA = min. correction °C set point ATTUALE
Max summer correction = Par 22
Slettet: correzione Slettet: estate
par 24 4 mA
22 23 24 140 151
par 23 20 mA
Max. value of summer correction Signal corresponding MAX summer correction Signal corresponding MIN summer correction Plug_in presence Offset Water Reset
8 20 4 1 0
°C mA mA num mA
in WINTER the correction decreases the set-point with signal at 20 mA = max correction , 4 mA = min. correction °C
Max winter correction = par 19
set point ATTUALE
par 21 20 mA
par 20 4 mA
19 Max. value of winter correction 10 °C 20 Signal corresponding to Max. winter correction 4 mA 21 Signal corresponding to Min. winter correction 20 mA As in the external temperature correction, it is possible to use the function with reverse logic: simply reversing the values on the parameters 23 and 24 (for the summer) and 20 and 21 (for the winter).
12.2
TOTAL SET-POINT CALCULATION
In the end, considering both the previous factors, the set-point will be re-calculated as follows: SUMMER Actual Setpoint = setpoint of default + external temp./enthalpy correction + Water reset correction WINTER Actual Setpoint = setpoint of default - external temp./enthalpy correction - Water reset correction
13 MAINTENANCE SET-POINT It can be used to maintain the system within the operating limits during unit OFF period. The MAINTENANCE set-point thus controls the temperature of the treated water when the unit is OFF or in Stand-by. To achieve this, it activates periodically the circulation pump, it tests the water temperature and possibly activates the compressor. Par 42 Summer maintenance Set Point 20 °C Par 43 Winter maintenance Set point 30 °C It is enabled with the parameters: Par 44 Summer maintenance enabling Par 45 Winter maintenance enabling
1 1
num num
With unit and pump OFF it starts counting the time: par 41 Maintenance scan time
1800
sec
at the end of the time the pump is activated par 144 Pumps in maintenance starting time
120
Sec
at the end of the time, if the set is not met it remains active with the compressor as long as the set is reached.
14 COMPRESSOR TIMING The number of starts and thus the wear of the compressor are reduced as much as possible by the control system with 2 parameters. The max. number of starts/hour of the compressor is limited by setting the delay between a start and the following restart of the same compressor: par 63 start time/ compr. start 360 sec The pressure equolization before the compressor restart is aided by setting the delay between a stop and a start of the same compressor: par 64 stop / start time 30 sec
15
COMPENSATIONS
The compensations are aimed at safeguarding the compressor; thus they prolong compressor’s operating time and limit the number of hourly start pulse s To achieve this, the compensations add an OFFSET to the activation point of the compressor
activation Level with OMPENSATION
offset by COMPENSATION
Activation level without COMPENSATION
ACTUAL set point
By means of compensation, the compressor working point is taken away from the set, avoiding too short working periods. The possible compensations are 3:
Compensation on the LOAD = based on the inlet-outlet water temperature difference Compensation on the DUTY-CYCLE = base on the frequency and duration of the compressor ONOFF cycles Compensation on the DURATION = based on the compressor ON time The compensation off-set is dynamically calculated and is the sum of the instantaneous values of the active compensations. It cannot exceed the highest value among the maximum limits of the compensations; it can reach max. 3°C with the default parameters.
compensations Total max value always Equal or minor than The higher singol max. values
Max value Max value
temp. °C Compressor start
°C
+
+
=
On duration
°C
Singol value sum Compensation offset
Max value
°C on duty-
On water inlet temperature
Histeresys ON Compensation Offest
Capacity step
Actual setpoint Histeresys OFF Compressor stop
15.1
COMPENSATION ON THE LOAD
The compensation is based on the average temperature difference between water inlet and outlet.
LOW load
HIGH load
delta T °C
Medium average
5 °C
Medium average
par 4 = 300 sec
par 4 = 300 sec
If the average temperature drop is 5°C, that is the compressor has always been active, the thermal load is high.
If the average temperature drop is low, this means that the compressor has stopped several times, thus the thermal load is low. In this case it is possible to compensate (namely to delay the compressor start).
low average temperature drop = low load = frequent compressor start pulse s + short operating periods The highest compensation corresponds to the minimum average temperature drop, namely with inlet temperature close to the set-point.
Compensation val.
Compensation val.
SUMMER
par 2 = 1 °C
par 3 = 1 °C
7,5
10,5
Inlet temp..
set+par 5
set+par 6
Par 1
enables the compensations
par par par par par par par
Max. Summer load compensation Max.Winter load compensation Time for average on (Ting. – Tout) Summer temperature min. delta* Summer temperature max. delta* Winter temperature min. delta Winter temperature max. delta
2 3 4 5 6 7 8
0 1 2 3 1 1 300 1 4 1 4
WINTER
40.5
37.5
set - par 7
set - par 8
not enabling only summer only winter summer and winter °C °C sec °C °C °C °C
The compensation of the load has a “mild” effect: it compensates max. 1°C. It is especially useful if the load is variable.
Inlet temp..
15.2
COMPENSATION ON DUTY-CYCLE
The compensation on DUTY-CYCLE is based on the ratio : operating time Oper. time + stop time
This function is based on elaborate mathematical calculations and test checks. The resulting values are thus to be meant as standard and cannot be modified. Please note that the worst conditions occur for duty-cycle values included in the range between 20% and 50% (ON time = 50 % OFF time) . 53 54 55 56
Enables compensation on duty Value of critic duty Max. value compensation on duty Time of medium duty calculation
1 20 1,5 1800
num % °C sec
The compensation on the duty operates a standard optimisation of the ON-OFF cycles; thus, it is of general use and must be enabled always.
15.3
COMPENSATION ON THE DURATION
The compensation on the DURATION is based on the compressor ON time. Short ON times, even if followed by long OFF periods, are critical for the compressor (lubrication problems).
ON compr. with active compensation ON Average temp. drop That's why at the end of each operating cycle of the compressor the controller checks the duration (compressor ON). If the ON time is lower than 200 sec the controller increases the compensation, then it checks if ON reaches 200 sec; otherwise, it increases the compensation again. The compensation is increased max. three times the max. value. If the ON time is longer than 300 sec, the compensation is decreased with the same logic. Par Par Par Par
57 58 59 60
It enables the duration of compensation Min. operating time Max. operating time Max. duration comp. value
1 200 300 1
num sec sec °C
The duration compensation has an “incisive” effect: it compensates up to 3°C. It is useful when the water content is limited. The incisiveness is detrimental to the low temperature control accuracy: in industrial applications, where a fine temperature control is required, this compensation can be disabled but a fair water quantity in the system is necessary. PLEASE NOTE THAT WITH SHORT COMPRESSOR ON PERIODS IT IS POSSIBLE TO HAVE A LOW AVERAGE TEMPERATURE DROP; IN THIS CASE, THE LOAD COMPENSATION WOULD HAVE A LIMITED EFFECT.
16
TEMPERATURE CONTROL
The temperature control is based on the outlet temperature and is based on temperature drop between water inlet and outlet defined while designing the system Par 37 Summer temperature average 5 °C If the temperature drop on the system is not 5°C, it is basic to update the parameter value to the current temperature drop on the system; otherwise, the adjustment logic is distorted. The cooling/heating capacity supplied by the individual resources is defined (capacity step): single capacity step the compressor alone supplies 100% of the required power (SUMMER) double capacity step the compressor alone supplies only a part of the required power (WINTER with electric heaters) Par 72 Compressor output capacity 70 % Par 177 Output by the integration heaters 30 % The controller can activate one and only one step at a time, and only after the activation scanning time (status 4, page 20) . The activation scan time is not fixed, rather it changes according to the difference between water outlet temperature and current set-point value. The higher the difference value (both positive and negative) the shorter the interval between scanning points. Par 34 Max. activation scanning time 1200 sec Par 35 Min. activation scanning time 120 sec The release of active power steps can take place one step at a time, except the safety devices, when the release scanning time has elapsed. Par 36 Release scan time 10 sec
16.1 COOLING compressor ON if : at the end of the scanning time the outlet water temperature is over the current set-point (which considers the possible corrections) plus the capacity step that the compressor can supply KEY
temp. °C START ZONE COMPRESSOR
Compressor on
SENSING
ON Hysteresis Offest compensations
SENSING SENSING
ON hysteresis par 40 First step activation hysteresis OFF hysteresis par 39 Last step release hysteresis
SENSING
Drop supplied by the compressor
Compensation offset see pag 339
Actual setpoint OFF Hysteresis
Capacity step supplied by the compressor par 37 summer temperature delta ( 5 °C ).
Compressor off
Scan time
compressor OFF when the temperature goes below the set-point minus hysteresis last step Par par par par
37 39 40 72
Summer temperature delta Last step release hysteresis First step activation hysteresis Compressor 1 capacity
5 -0.3 -0.3 100
°C °C °C %
Output capacity c1 always expressed as percentage of deltatc and in this case equal to 100% (single-compressor unit in cooling), namely the design 5°c
16.2 HEATING In this mode also the heaters can be installed and managed, that is a second capacity step integrating the first one. Thus, the total capacity is distributed between compressor and electric heaters. Compressor ON if : at the end of the scanning time the outlet water temperature is below the current set-point (which considers the possible corrections) plus the capacity supplied by the single capacity step of the compressor. Heaters ON if : the scan time has started and ended, if the outlet temperature is over the heater capacity step. If the heaters are not installed, the capacity step supplied by the compressor is equal to the total capacity step as in the cooling mode. Par par par par par par par
37 38 39 40 72 161 177
Summer temperature delta Winter temperature delta Last step release hysteresis First step activation hysteresis Compressor output power Cycle reversing valve polarity Output by the integration heaters
5 5 0.3 0.3 70 * 0 30 *
°C °C °C °C % num %
* the value is indicative: it depends on how the power is distributed between heaters and compressor. temp. °C Scan time + Time Compressor switching-OFF OFF Hysteresis
Heater switching-off
Actual setpoint OFF Heater capcity step
drop
Compressor capcity step ON OFF
Compensation offset
OFF OFF
Integration heater Start are (after compressor Start,only)
ON
ON Hysteresis Compressor switching on
START COMP
COMPRESSOR E.g. 70% di DeltaTH
HEATERS E.g.. 30% di DeltaTH 100% of capcity step
DeltaTH
KEY • • • •
ON Hysteresis : par 40 First step activation hysteresis OFF Hysteresis : par 39 Last step release hysteresis, heater switching-off area, too Compensation offset : see page 33 Compressor capacity step: calculated as percentage of par 38 (Winter temperature delta, the total capacity step the machine can supply in heating). Heater drop: calculated as percentage of par 38 (Winter temperature delta)
17
DIGITAL SCROLL MODULATING COMPRESSOR
The function , if enabled with par 51 = 1, allows to control a modulating compressor . Characteristics of the pilot signal : • is a function of the INLET water temperature • is a 0-10Vcc • the min. value can be limited with the par 52
NG COMPRESSOR The function , if enabled with par 51 = 1, allows to control a modulating compressor . Characteristics of the pilot signal : • is a function of the INLET water temperature • •
N G C O M P R E S S O R The funct ion , if enabl ed with par 51 = 1, allow s to contr ol a modu lating comp resso r. Char acteri stics of the pilot signa l: •
is a 0-10Vcc the min. value can be limited with the par 52
• •
•
•
unction of the INLET water temperature is a 0-10Vcc the min. value can be limited with the par 52
min. value can be limited with the par 52
Keypad index
51
StepLessEn
52
MinVcc
“Modulating compressor” enabling 0= NO 1= YES Min. voltage on the analogic outlet of the modulating compressor if the compressor is active
0
0
1
0
2
flag
2,0
0
100
1
2
Volt
37
DeltaTC
Summer Temperature Delta
5
2
0
20
1
°C
38
DeltaTH
Winter Temperature Delta
5
2
0
20
1
°C
39
IsLastStep
Hysteresis of Last step release
0,3
2
0
5
1
°C
40
IsFirstStep
Hysteresis of First step insertion
0,3
2
0
5
1
°C
In the WSHH type 8 units ( details at page 45 ) the functionality can not be activated
COOLING
HEATING
100% Vcc
ANALOGIC INLET temp.
100% Vcc
SetCool
SetHeat
Min Vcc
T ing
0 Vcc
T ing
0 Vcc
P 37
P 39
P 40
P 40
P 38 P 39
ON
ON
DIGITAL
Min Vcc
SetCool
SetHeat OFF
OFF
OUTLET temp.
T out
T out
P 39
P 37 P 40
P 40
P 38
P 39
18
ELECTRIC HEATER CONTROL
While heating, besides the compressor, optionally, it is possible to use the electric heaters. The operating modes and thus the adjustment logics can be different, as indicated here below. If present, is possible to perform the temperature control in heat with the Tout1 probe , installed on the electric heater output . The temperature control in cool will be performed always by the Tout probe installed downstream from the exchanger. 70 150
it enables the heater output probe offset temp. uscita riscaldatore elettrico
T Ext
1 YES , 0 NO °C
T IN
If the Tout1 is present, the antifreeze alarm is monitored from both the probes : • the Tout activates the antifreeze heaters on the exchanger • the Tout1 activates the integration heaters
T OUT1 T OUT
UNIT WITHOUT HEATERS The unit can heat only by means of the compressor Par 178 Compressor oper. enabling in heating Par 179 Power limit enabling for ext. temperature
0 0
num num
18.1 HEATERS AS INTEGRATION ELEMENT The heaters integrate the compressor work. If it is defrosting or is stopped due to alarms, it becomes the main heating component. Starting from the machine ON, the heaters before operating wait for a delay time controlled by parameters; the same occurs also during the maintenance step (see page 32) at each pump restart. 72 177 178 179 182
Compressor capacity Capacity by the integration heaters Compressor operation enabling in heating Power limit enabling for ext. temperature Heater timeout
70 * 30 * 1 0 1200
% % num num sec
* the value is indicative: it depends on how the power is distributed between heaters and compressor
18.2 ELECTRIC HEATERS REPLACING THE COMPRESSOR In this mode the electric heaters operate only as an alternative to the compressor: • when this is excluded due to the external temperature limit • when this is excluded due to an alarm. With external temperatures lower than parameter 180 the only available step is represented by the heaters. The compressor is enabled again when the heat pump operates for external temperatures over par 180 + 2°C. 177 178 179 180
Capacity by the integration heaters Compressor oper. enabling in heating Power limit enabling for ext. temperature Ext. temp. limit at the compressor oper.
100 1 1 0
% num num °C
18.3 MAIN ADJUSTMENT COMPONENT IN HEATING In this case heaters are the only heating element of the unit The compressor does not operate in heating mode ( par 178 = 2 ) . 178 179
Compressor oper. enabling in heating Power limit enabling for ext. temperature
2 1
num num
18.4 POWER LIMITING ON EXTERNAL TEMPERATURE In this case the operation of compressor and heaters in heating mode is subject to the external temperature conditions as shown in the diagram.
1° zone compressor ENABLED, heaters DISABLED
3° zone compressor DISABLED, heaters ENABLED
178 179 181
External temperature
2° zone compressor ENABLED, heaters ENABLED
1a zone COMPRESSOR enabled
Compressor oper. enabling in heating Power limit enabling for ext. temperature Differential on ext. temp. limit for heater act
Dead zone = 2 °C par 180 = 0 °C
0 °C 2a zone COMPRESSOR + HEATERS
par 181 = 5 °C
Dead zone = 2 °C - 5 °C
3a zona HEATERS ENABLED
2 2 5
num num °C
HEATERS CONTROL OUTPUTS
The heaters control mode described above is ON – OFF. Anyway, it is possible to control the heaters proportionally, using the plug-in module and a diving signal (option still to be implemented, not available at the present). apacity 100 %
ON
230 V 50 Hz N
0%
Digital
GND
0-10 VDC
F
1
OFF 4
6
10 Vdc
CN3 3
0 Vdc
Analogue BASIC MODULE
°C Heater temperature drop Set Point
PLUG-IN MODULE
18.5 ANALOGICAL OUTPUT LIMITATION With the par 207 is possible to define the max. value of the integration heaters pilotage when they are used together with the compressor . Keypad par
207
Mnemonic MaxInteg
Description
Default Min Max Tenths
Max. value of the CN3_3/6 analogical output when the heaters are actives together with the compressor
100
0
100
pwd level
U.M.
1
%
0
The CN3 analogical output limitation on the PLUG-IN module, pin 3/6 , is active when the heaters are managed :
Electric elements only as integration element
Par 178 ModeHeater
Par 179 LimPotTextEn
1
0
Electric elements in the place of the compressor
1
1
Power limitation on the external temperature
2
2
19
MANAGEABLE UNIT TYPES
type
example
159
106
162
WSA
0
0
0
0
pressurised ventilation
WSAT
2
0
0
0
5
pressurised ventilation, defrosting in temperature
WSAN
2
0
1
0
6
condensation in water , pressurised modulating valve
WSH
2
1
0
0
7
condensation in water, pressurised modulating valve, reversing cycle on gas, management of pump to condenser
WSHN
2
1
1
0
8
condensation in water, reversing cycle on water, management of pump to condenser
WSHH
1
2
1
0
9
Only heat pump with defrosting at hot gas , without reversing cycle valve
WBAN
2
0
1
2
10
Water condensing, valve On for compressor On, antifreeze probe Not active
WSH
0
1
0
0
11
Water condensing, valve On for compressor On, antifreeze probe active
WSH
1
1
0
0
12
Inversing cycle on gas, water condensing, valve On for compressor On, antifreeze probe Not active
WSHN
0
1
1
0
13
Inversing cycle on gas, water condensing, valve On for compressor On, antifreeze probe active
WSHN
1
1
1
0
14
WSH (water condensing, pressurised modulating valve, antifreeze probe Not active)
WSH
3
1
0
0
15
WSHN (Inversing cycle on gas, water condensing, pressurised modulating valve, antifreeze probe Not active)
WSHN
3
1
1
0
1
ventilation ON for compressor ON
4
A. WSHH – UNIT OF TYPE 8 The unit is reversible on the water circuit so are present the following variations : EVAPORATOR output probe CONDENSER output probe Fan digital output
control in cooling and antifreeze control in heating and antifreeze pump control output to condenser
The pump to condenser : It is activated in advance respect the compressor ( par 100 Tstartup ) • It stops in late respect the compressor ( par 107 TimeOffV ) •
119
B. WBAN – UNIT OF TYPE 9 The unit can operate exclusively for hot water production . The reversing cycle valve does not exist ; the defrosting is performed with a defrosting valve with hot gas . The expansion plug-in module is necessary . External exchanger
a c tia ts o m re T
Compressor
Gas defrosting valve
YVR Internal exchanger
Water valve
Electric heater BOILER
It is possible to manage a 3-way valve for the production of sanitary hot water with a dedicated set point ( par 117 ) With the par 50 = 1 the 2° set point input on the main board is set as SANITARY WATER REQUEST. HEAT/COOL input
MODE
2° setpoint input
VALVE
SET POINT
2° SET POINT
ON
to the installation
set HEAT
2° setpoint HEAT * not manageable
OFF
HEATING HEATING + H2O SANITARIA
OFF
OFF
to the boiler
SetH2OSanitaria
COOLING
ON
ON
to the boiler
Temperature control NOT ALLOWED
COOLING + H2O SANITARIA
ON
OFF
to the boiler
SetH2OSanitaria
not manageable
* enable : • from led keypad • setting par 49 =1 par
Description Meaning
49 Comando2°Set EnH2OSanitari 50 Enabling of the sanitary water valve management a SetH2OSanitar 117 Sanitary water Set Point ia 140 PlugInEn It enables the PLUG-IN presence. 1=YES / 0=NO 2° set point mode control from parameter
value 0 0 35
PRESSURE TRANSDUCER Only with WBAN type 9 units is possible to use a pressure transducer to prevent peaks in the high pressure . At the compressor starting , or if the set is over ( par 210 ) , the gas is bypassed on the coil thought the defrosting valve at hot gas . After the TimerPcondON the valve is managed again exclusively in function of the defrosting request . If the transducer is present , par 203 > 1 : •
the compressor start is delayed of 1 sec respect the activation moment
•
at the same time the defrosting valve at hot gas is activated and is deactivated 1 second after the compressor start
•
at the compressor start, on the basis of parameters 210 and 211, starts the timer that enables the valve management. If Pcond>SetValvolaON then Valve=ON if Pcond< SetValvolaON- DiffValvolaON then Valve=OFF
•
when the timer ends ( it arrives to 0 ) the defrosting valve at hot gas management is again in the defrosting function .
Index
203
210 211
212
Mnemonic
Description
Set value that allows to enable the transducer, and at the same time the bottom scale is linear EnPCondPlugIN 0= Transducer disabled (alarm not managed) 30= Transducer from 4mA-0Bar / 20mA-30bar 50= Transducer from 4mA-0Bar / 20mA-50bar Plug In condensing pressure value (CN3_8/9) over which SetValvolaON the defrosting valve at Hot Gas is activated Differential for the reset in OFF of the defrosting valve at DiffValvolaON Hot Gas Timer that is activated on the instant of the compressor start during which it is allowed the management of the Hot TimerPcondON Gas valve activation in function of the set and band set to the added parameters to manage the condensing pressure
C.
Pwd level
U. M
0
1
Bar
50
1
1
Bar
0
50
1
1
Bar
0
999
0
1
Sec
Default
Min
Max Tenths
0
0
50
28.5
0
1.5
300
WSH – UNIT OF TYPE 10
Only cool unit with water condensing, valve On for Compressor On, antifreeze probe not active The ON/OFF and modulating valves are activated TstartUp seconds before the compressor start and they are off TimeOffV seconds after the compressor stop. In this configuration the source water antifreeze sensor is not managed.
D.
WSH – UNIT OF TYPE 11
Only cool unit with water condensing, valve On for Compressor On, antifreeze probe active The ON/OFF and modulating valves are activated TstartUp seconds before the compressor start and they are off TimeOffV seconds after the compressor stop. In this configuration the source water antifreeze sensor is not managed.
E.
WSHN – UNIT OF TYPE 12
Unit reversible on Gas, water condensing, valve On for Compressor On, antifreeze probe not active The ON/OFF and modulating valves are activated TstartUp seconds before the compressor start and they are off TimeOffV seconds after the compressor stop. In this configuration the source water antifreeze sensor is not managed.
F.
WSH – UNIT OF TYPE 13
Unit reversible on Gas, water condensing, valve On for Compressor On, antifreeze probe active The ON/OFF and modulating valves are activated TstartUp seconds before the compressor start and they are off TimeOffV seconds after the compressor stop. In this configuration the source water antifreeze sensor is not managed.
G. WSH – UNIT OF TYPE 14 Only cool unit with water condensing, pressurised modulating valve, antifreeze probe not active In this configuration the management of the source water valve/pump control outputs is under the the pressure control. The antifreeze probe is not managed (No probe alarm and no antifreeze alarm)
H. WSHN – UNIT OF TYPE 15 Unit reversible on Gas, water condensing, pressurised modulating valve, antifreeze probe not active In this configuration the management of the source water valve/pump control outputs is under the the pressure control. The antifreeze probe is not managed (No probe alarm and no antifreeze alarm)
20
CIRCULATION PUMP
It is possible to control: • single pump on the unit • single pump + stand-by pump • modulating pump controlling the assisted starts of the compressor (changing the number of pump revolutions the water flow rate is modulated in order to, keep the water temperature within the working limits at the start) Par 141 =
0 1 2
single pump on the unit single pump + stand-by pump one pump with variable flow
The different outputs to control the pumps are all on the main control module. COMMON
1 2 3
FIRST SPEED PUMP
COMMON FIRST PUMP OR SINGLE PUMP SPEED
4 5 6 7
8 +5 DTG V TxRxR N D
9 1 0 1 1 1 2
13 14 15 16 17 18 19 20 21
REFERENCE
PWM
0-10 V
By precise choice control is carried out on the system water pressure: the relevant input on the card is bridged ( CN1 pin 9 e 11 ) Par Par Par Par
142 143 144 145
Flow by-pass from pump start Delay at Comp. start from pump activation Maintenance pump start time Delay at pump switch-off from comp. OFF
25 25 120 120
sec sec Sec Sec
20.1 SINGLE PUMP The circulation pump sets ON every time the unit is switched on. (actually, first a check on the system charged with water through the input 9 of CN1 is made; being this bridged, it is always positive). On page 22 the flow alarm management is described.
20.2 SINGLE PUMP + STAND-BY PUMP There are 2 pumps: • one operating • one in stand-by ready to start if the first one does not work roperly The stand-by pump is always the one having less running hours. THE ONLY DIFFERENCE WITH RESPECT TO THE PREVIOUS CYCLE IS A TRIAL IS MADE WITH THE STAND-BY PUMP BEFORE STOPPING THE UNIT BY FLOW ALARM ( SEE PAGE 25 ) .
20.3 VARIABLE DELIVERY PUMP The variable flow is mainly intended to assist the compressor at start, reducing the possible thermal shock caused by water temperature outside the operating limits. The speed control depends on water inlet and outlet temperature. The circulator can be: two speeds proportional depending on a diving signal • 0-10 Vdc (pump inverter) • PWM On units configured with variable flow pump (par 141 = 2) parameter 189 activates the two speeds output alternatively (e.g. 1st step with smaller pump and 2nd with bigger one), or together (e.g. 1st step one pump, 2nd step two pumps together). Par 189
Step activation mode = 0 steps in alternative with 100 ms between de-activation of one and activation of the other. =1 steps operating together, in this mode it is not necessary to manage any safety time during speed change.
20.4 CIRCULATOR PILOTED AT VARIABLE SPEED The pump speed changes according to the inlet temperature on the exchanger: COOLING for high inlet temperatures the flow is progressively reduced to get a higher water temperature drop % driving signal
par 188 = 80
par 187 = 50 par 185 17
25 par 183
exchanger Inlet water temp.
HEATING for low inlet temperatures, the flow is progressively reduced to get an higher water temperature drop and to maintain the condensing sufficiently high.
par 188 = 80
par 187 = 50 par 186 30 par 184
183 184 185 186 187 188
COOLING flow decrease threshold HEATING flow decrease threshold Cooling flow decrease hysteresis Heating flow decrease hysteresis Pump signal corresponding to max. flow decrease Pump signal corresponding to rated flow
35
exchanger
Inlet water temp. 25 30 8 5 50 80
°C °C °C °C % %
20.5 TWO SPEED CIRCULATOR The pump can operate only at a reduced speed or at its nominal speed according to the inlet water temperature. COOLING
The concept is similar to the previously described one : for high inlet temperature the speed is reduced to get a higher water heat drop
nd
2 speed
st
1 speed par 185 = 8 °C 17
par 183 = 25
water IN
HEATING
For high inlet temperatures the speed is increased to get a lower water heat drop
nd
2 speed
1st speed par 186 = 5 °C par 184 = 30
35
water IN
FORCINGS • MAX. SPEED: in case of anti-frost pre-alarm • MIN. speed: in case of high pressure pre-alarm • MAX. SPEED: in cooling if the inlet temperature is over 25°C (par 183 COOLING delivery decrease threshold) and the outlet temperature is within the off hysteresis (par 39 = 1°C, see diagram on page 32 ) •
MAX. SPEED: in heating if the inlet temperature is below 30°C (par 184 HEATING delivery decrease threshold) and the outlet temperature is within the off hysteresis (par 39 = 1°C, see diagram on page 37 )
21 CONDENSING CONTROL the controller can manage units: • Air cooled, using fans • Water cooled, using valves in both cases the regulation can be • On-Off type • Proportional according to condensing pressure • proportional according to condensing temperature The configuration is carried out by the parameters below: 106 Condensation type 159 Selection of the type of condensation probe 162 Configuration of the unit as CHILLER or HEAT PUMP PARAMETERS
159
162
106
WSAT (Ventilation On for Compressor On)
0
0
0
WSAN (Ventilation On for Compressor On)
0
1
0
WSAT (Ventilation temperature controlled)
1
0
0
WSAT (Ventilation pressure controlled)
2
0
0
WSAN (Ventilation pressure controlled, defrosting temperature controlled)
2
1
0
WSH (Water cooled, valve modulating according to pressure)
2
0
1
WSHN (Cycle reversal on refrigerant side, valve modulating according to pressure)
2
1
1
WSHH (Cycle reversal, pump management at the condenser)
1
1
2
Unit type
21.1 AIR COOLED UNITS The condensation/evaporation fans are active only when the compressor is active. Their type can be: • ON-OFF • variable speed • with control according to condensing temperature • with control according to condensing/evaporating pressure The parameters determining fan operating mode are: 92 93 94 95 96 97 98 99 100 101 102 103 104 112
Summer FAN start pressure with comp. off Winter FAN start pressure with comp. off Max. Fan speed pressure Min. Fan speed pressure Max. Fan cool pressure Min. Fan cool pressure Fan Cut-OFF Heat Fan Cut-OFF Cool Fan start pulse duration Bypass cut-off duration Max % Fan % Fan Fan % at start Summer HP pre-alarm set ( see page 25 )
23 0 3.7 4.2 17 13,5 4.8 12 5 25 100 40 70 25
Bar/°C Bar/°C bar/°C bar/°C bar/°C bar/°C bar/°C bar/°C sec sec % % % bar
ON-OFF TYPE REGULATION COOLING At the compressor start: regardless of the pressure value the fan activates for: par 100 fan start pulse duration 5 sec. After the counting, the fan is kept in On if the pressure is higher than Par 99 cool fan cut off 12 bar/°C otherwise it remains active until: par 101 cut-off bypass duration 25 sec has elapsed During the compressor operation: the fan, when stopped, starts again when Par 97 min fan speed pressure cool 13,5 bar/°C is exceeded and stops when the pressure drops below par 99 cool fan cut-off 12 bar / °C HEATING At the compressor start: regardless of the pressure value the fan activates for: par 100 fan start pulse duration 5 sec. After that fan is kept ON if the pressure is lower than Par 98 heat fan cut off 4,8 bar / °C otherwise it remains active until par 101 cut-off bypass duration 25 sec has elapsed During the compressor operation: the fan, when stopped, starts if pressure drops below par 95 Min fan speed pressure heat 4,2 bar/°C and stops when the pressure goes over par 98 cut-off heat fan 4,8 bar / °C REGULATION ACCORDING TO CONDENSING TEMPERATURE WITH PROPORTIONAL PHASE CUT OR INVERTER OUTPUT (COOLING ONLY) COOLING MODE it is possible to control the fan speed according to condensing temperature. fan speed
100 % = par 102 = MAX speed
5 sec = duration Start pulse = par 100
70 % = par 104 = % AT PICK-UP
40 % = par 103 = MIN SPPED
25 sec = par 101
CONDENSING 26 °C = par 99 = CUTOFF COOL
30 °C = par 97 = MIN temp. COOL SPEED
42 °C = par 96 = . MAX temp. COOL SPPED
TEMPERATURE
REGULATION ACCORDING TO CONDENSING PRESSURE WITH PROPORTIONAL PHASE CUT OR INVERTER OUTPUT COOLING Fan Speed 100 % = Max Fan Silent 80 % = par 102 =MAX SPEED
5 sec = duration Start pulse = par 100
70 % = par 104 = % AT START PULSE
2 bar = par 113 = delta preal. HP
40 % = par 103 = MIN SPEED
25 sec = par 101 CONDENSIN 12 bar = par 99 = CUTOFF COOL
13.5 bar = par 97 = Min.press COOL speed
17 bar = par 96 = Max. press. COOL speed
25 bar = par 112 = preALHP
PRESSURE .
MaxFanSilent is not defined by a parameter: it is always 100% of the speed. If par 102 = MaxFan = 100% that is Max. SPEED = MaxFanSilent, the “superventilation” does not take place. HEATING Fan Speed
100 % = par 102 = MAX speed
5 sec = par 100 = Start pulse duration
70 % = par 104 = Start pulse fan
40 % = par 103 = MIN speed
25 sec = par 101
3.7 bar = par 94 = pres MAX HEAT
4.2 bar = par 95 = pres MIN HEAT
4.8 bar = par 98 = CUT OFF HEAT
Evaporating pressure
21.2 PRESSURE TRANSDUCER READING It is possible to use a transducer with 0-30 bar or 0-50 bar field ( both correspond to the 4-20 ma output signal ) par 67 bottom scale of the 4-20Ma pressure probe 30 = 30 bar , 50 = 50 bar
21.3 FAN FORCING WITH COMPRESSOR OFF
The function activates the condensing fans when , with compressors in off , the pressure/temperature on the condensong coil reaches high values . The function is active only with unit in cooling . ventilation
Fan start
Fan stop
par 158
-2°C
ON –OFF
External temp. Probe in contact with the coil to enable with par 152
Modulation in temperature
Probe on the coil
par 92
-2°C
Modulation in pressure
transducer
par 92
- 2 bar
21.4 WATER COOLED UNITS
The differences with respect to air cooled units are the following: • no defrost cycles. • The coil temperature probe becomes external exchanger inlet probe, necessary on heat pumps to check the min. water temperature at the inlet (antifreeze). • •
Input 3 of the CN1 connector is used for differential pressure switch of external exchanger. Condensation is kept under control sensing only the relevant pressure (no temperature control)
WATER VALVE MODULATION The valve is closed with steady compressor. When the controller requires capacity the water valve opens by the extent set by the parameter: par 104 % Fan at start 70 % This step has a duration, in seconds, equal to: par 100 Fan start pulse duration 5 sec after this time the system checks the condition of the water differential pressure switch.
If it is closed, the compressor can start and the water valve starts modulating according to the condensing/evaporating pressure and takes at least the min. opening percentage set by the parameters: par 94 Pressure for max fan speed heat 3.7 bar par 95 Pressure for min fan speed heat 4.2 bar par 96 Pressure for max fan speed cool 17 bar par 97 Pressure for min fan speed cool 13,5 bar if the pressure switch is open the compressor cannot start and an alarm is signalled. A valve closing delay vs. the compressor stop, set by the parameter: par 107 water flow bypass time 0 sec FLOW ALARM MANAGEMENT The water flow alarm is not detected: • with compressor steady • at during valve modulation start-up ( par 100 ) • while modulating ( SUMMER : par 96 / 97 ; WINTER par 94 / 95 ) • in this situation the differential pressure switch could have problems in detecting the flow presence. Therefore the alarm is thus active only if the start-up time has elapsed and if the valve is completely open. The alarm resets automatically, a delay of 30 seconds starts together with the alarm signalling (compressor stop / start time = par 64 , see page 28), after which the alarm is reset and the delay of the flow bypass time (TstartUp) starts again; now the cycle is repeated, as long as the flow check is positive.
OPERATION OF THE ON-OFF TYPE WATER VALVES
The valve is closed with steady compressor and the flow alarm detection is inhibited. With active compressor, the valve opens immediately and the delay of the water flow alarm bypass time in the exchanger starts. While operating, the alarm detection is always active, as there is no valve modulation. As for the rest, the alarm detection and reset logic is the same as described in the previous paragraph. Also in this case, too, there is a valve closing delay vs. the compressor stop: par 107 Water flow bypass time 0 sec
22 RADIATING PANELS The following is necessary for the management: • expansion PLUG-IN module • radiating panel water temperature probe • external air temperature probe • external temperature radiating compensation enabling The system return water for uses such as FanCoil is used to supply a floor system with radiating panels. A set-point is fixed for the outlet water to the radiating panels. If the water temperature is lower than set point, the valve deviates the water flow returning from the fan coil to the radiating panels. If the water temperature is higher or equal than set point, the valve will close and the panels will work only with their own recirculation water. The water outlet pump to the radiating panels is controlled in parallel with the pump to the exchanger installed on the machine. Thus, it is always active when the chiller is set ON and switches off with a delay that can be set from the machine setting OFF.
DISACTIVE RADIATING (panels in recirculation)
ACTIVE RADIATING
UNIT
OUT
UNIT
OUT
IN
IN
CIRCULATING PUMP (ON-OFF, 0-10 V, PWM)
CIRCULATING PUMP (ON-OFF, 0-10 V, PWM)
WATER VALVE 3 POINTS O 0-10 V
WATER VALVE 3 POINTS O 0-10 V
WATER PUMP RADIATING PANELS
WATER PUMP RADIATING PANELS OUTLET PROBE RADIATING PANELS
OUTLET PROBE RADIATING PANELS
TO FAN-COIL
190 192 202
TO RADIATINGI PANELS
TO FAN-COIL
External temperature radiating compensation enabling. 1 Radiating set-point. 25 Radiating panel water temperature probe enabling 1
TO RADIATING PANELS
num °C num
22.1
VALVE CONTROL TO THE PANELS
As alternative, it is possible to control 3-point or proportional valves. There are 3 outputs for radiating panels: • analogue 0-10 V • •
valve opening digital valve closing digital
CALCULATION OF THE START THRESHOLD OF THE RADIANT VALVE CONTROL The outlet temperature threshold for the control start is calculated with the parameter 169 TdeltaChiller :
22.2
Active control
Inhibited control
COOL
t mandata < SetPointRAD – 2 °C
t mandata > SetPointRAD + 2 °C
HEAT
t mandata > SetPointRAD + 2 °C
t mandata < SetPointRAD – 2 °C
RADIANT SET-POINT
There are 3 modalities to set the radiant . 1. Value setting by parameter or by ModBus variable. The valve is managed to obtain water on the panels at the parameter value “192 SetPointTR” independently from the operating mode selected on the chiller. 2. Set point calculated in function of the external air temperature. The electronics determinates two reference set point ( summer / winter ) that are set automatially in base of the operating mode selected on the unit. This configuration is obtained setting “190 EnCompExttR = 1” 3. Summer set point correction in function of the dew temperature value. The system must be interfaced with a ModBus (Ex ElfoControl) net Master, able to communicate the ambient UR and the ambient temperature values thorough the serial. In function of these information, an algorithm inside the board allows to correct the min. summer set point if the dew temperature value calculated is critical. This configuration is obtained setting “191 EnCompRugiada = 1”
setpoint
2 - HEATING While the external temperature increases, the heating demand decreases, and thus can be complied even with a lower set-point (increasing the power efficiency). 36,0 35,0 34,0 33,0 32,0 31,0 30,0 29,0 28,0 27,0 4
5
6
7
8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 external temp.
The set is automatically limited within the limits : par 198 Min heating set point par 199 Max heating set point the actual value is function of the external temperature: par 200 Min external temperature heating par 201 Max external temperature heating
30 35
°C °C
5 20
°C °C
2 - COOLING
When external temperature decreases, the cooling demand decreases accordingly, and can be complied with a higher set-point (increasing the power efficiency). 24,0 23,0
setpoint
22,0 21,0 20,0 19,0 18,0 17,0 16,0 15,0 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 temp. esterna External temp.
The set is automatically limited within the limits: 194 Min. cooling set point 195 Max. cooling set point
18 23
°C °C
the actual value is function of the external temperature: 196 Min. external temperature cooling 197 Max. external temperature cooling
20 35
°C °C
3 - INTERFACING WITH ELFO CONTROL
It is possible to calculate the set to activate the radiating panel valve preventing from condensing water rising. This operation must be enabled by the parameter: 191 Enables the compensation for condensing in cooling mode.
1
num
The controller processes the information coming through serial part from Elfo Control (Zone Master): • Ambient temperature • Ambient relative humidity • Ambient Set-point The controller calculates the so-called dew point, according to these values, re-defining the values of • Min. set point in cooling • Max. set point in cooling The dew compensation is automatically deactivated if a communication problem does not allow the values to be transmitted by the Elfo Control to the unit; only the compensation for external temperature remains active in this case.
22.3
RADIATING PANEL WATER ANTIFREEZE SAFETY
With unit steady possible freezing in the radiating panels must be prevented. Thus, a radiating water ANTI-FREEZE alarm function is active based on the temperature of the water outlet to the panels, with the same parameters seen for the anti-freeze alarm for the evaporator water described on page 23
When the alarm is activated : • the radiating water pump outputs are automatically activated • the radiating valve sets in opening towards the floor panels (recirculation on panels). When the probe detects a value over the differential for the recovery, • the alarm is AUTOMATICALLY reset • the pump and the valve are piloted again with the standard logic based on the radiating set-point and on the outlet temperature.
22.4
COOLING LIMITING BY DIGITAL INPUT.
To prevent from condensing it is possible to control a signal from external digital contact to be connected with the base module, CN1 pins 5 and 11 The regulation logic is the following: Input Closed = Standard operation Input Opened = Valve in full recirculation position on the radiating panel side The logic is active if: • the unit is in cooling mode • par 203 = 1 Enables Cooling Limit With active logic, a signal for “Cooling limit” alarm is enabled with AUTOMATIC reset. par
Mnemonic
46
MinStatoValvola
71
MaxRateoRad
118
TempoCorrezione
120
TmaxRicircolo
169
TDeltaChiller
192
SetPointR
205
TempAperturaValv
206
BandaApertura
Description
Default
Min. opening of the radiant modulating valve (0-10V)
20
Variation rateo value of the radiant outlet temp. that impose in closing the on/off valve
2
Radiant Correction time
20
Radiant valve max. time in recirculation position, for the periodical activation on the pump
800
Delta for the control start threshold calculation of the radiant water valve
2
Radiant Set Point (if compensations are disabled)
25
Necessary time to position the VRad from closet to opened
90
It allows to weigh the valve opening time
200
23 DEFROSTING Defrost can occur when: • the unit is working as heat pump • the compressor is active. The cycle starts with: • a pressure test a defined threshold is exceeded • a counting is started o at the counting end the temperature is checked If it is lower than a defined value • defrosting starts.
COUNTING CALCULATION The counting, or basic delay time for defrost, is dynamic and is calculated in two ways: according to external temperature or to the enthalpy. EXTERNAL TEMPERATURE ONLY The basic delay time for defrost increases while the external temperature decreases. Indeed, it is supposed that when the external temperature decreases the humidity rate in air decreases, and therefore the need for defrost is lower. BASIC TIME
2700 SEC par 132
1800 SEC par 131
- 10 °C par 134
5 °C par 133
EXTERNAL TEMP.
EXTERNAL TEMPERATURE + HUMIDITY or enthalpy defrost The basic delay time is determined according to the air specific humidity calculated through the humidity probe (optional, to be declared present with par 156). The BASIC DELAY TIME for defrost changes depending on the variation of evaporating pressure (ratio). Practically, if the pressure: • decreases quickly the coil is icing and thus the counting must speed up • decreases slowly the counting can slow down • is stable (with low values, too) the counting keeps the values according to the graph above. For example if the pressure in 1 minute falls down of 1 bar ( par130=1) , at every second the time is decreased of 4 seconds ( par 129 ) .
Switch to defrost: • keeps the compressor active • the refrigerating circuit direction is reversed through the 4-way valve • The fans are stopped and the low pressure by-pass is active at reversal. • The safety devices remain active • Defrost is performed even if the controller does not require the step anymore. Defrost end: • by temperature or max. time • the compressor is stopped • the compressor can restart in heating after having counted the dropping time or the compressor safety times • the fans are activated at max. speed for 15 sec (par 136) if the external temperature is over 3°C (par 137)
Setting the par 135 dropping time at 0, the compressor is not stopped at the of the defrosting but it remains active. FORCING DEFROST FOR LOW PRESSURE
In special situations sudden drops in the evaporation pressure can occur (typically while counting the delay time for defrosting, that is with low pressure/external temperature and with high humidity). The defrost forcing prevents such situations. It is active only if the counting of the delay time for defrost has been active for at least 10 minutes. Defrost starts immediately if the pressure drops below 1.4 bar (par 138 defrost forcing pressure), regardless of the temperature value at the coil. If this function is activated for more than 3 times, in the same circuit during one hour of machine operation, this is signalled in the alarm log. DEFROSTING CONTROL PARAMETERS 121 122 123 124 125 126 128 129 130 131 132 133 134 135 136 137 138 156
Defrost Start Press. Defrosting start temperature Defrosting stop temperature Max. defrost time Max. defrost delay time Defrost transient duration Defrost delta pressure Max. counting IN defrost Max. pressure ratio Min defrosting counting delay Max defrosting count. delay Ext. temperature min delay Ext. temperature max delay Drip time Fan running time after defrost Min external temperature fan activation after defrost Defrost forcing pressure External RH % probe enable
3.4 1 15 480 2700 90 1,5 4 1 1800 2700 5 -10 60 15 3 1.4 0
bar °C °C sec sec sec bar num bar/min sec sec °C °C sec sec °C bar num
Analogue inputs External temperature probe
External temperature probe + External relative Humidity probe
Evporating pressure < 3,4 bar ( par 121 )
Calculation of the BASE TIME FOR DEFROST delay: up 1800 to 2700 sec up parameters 131 to 132
COUNTING STOPPED WAITING FOR THE CONDITIONS TO RESTART
Yes
COUNTING RESET
COUNTING START
enthalpy calculation
No
comparison
Pressure transducer
Pressure > 3,4 bar ( par 121 )
Yes
Pressure > 4, 9 bar ( par 121 + par 128 )
Yes
NO The system evaluates The pressure change speed In time ( RATIO ) And then increases or Decreases the DELAY BASIC TIME
The compressor is activated
NO
Yes
Yes
DELAY TIME reaches 0
NO Evaporating time< 1 °C par 122 defrosting start treshold
No
Yes DEFROSTING START
reached15 °C DEFROSTING END par 123 defrosting end Temp.
after 480 sec DEFROSTING END par 124 max. time
Evaporating temp.> 15 °C par 123 defrosting end treshold
24 TEMPERATURE CONVERSION TABLE - NTC PROBE HEATER Temperature
Heater
Temperature
Heater
Temperature
-10,0°C
43547Ω
16,0°C
14324Ω
42,0°C
Heater 5559Ω
-9,5°C
42543Ω
16,5°C
14046Ω
42,5°C
5466Ω
-9,0°C
41566Ω
17,0°C
13774Ω
43,0°C
5374Ω
-8,5°C
40615Ω
17,5°C
13508Ω
43,5°C
5285Ω
-8,0°C
39689Ω
18,0°C
13249Ω
44,0°C
5197Ω
-7,5°C
38787Ω
18,5°C
12995Ω
44,5°C
5111Ω
-7,0°C
37909Ω
19,0°C
12746Ω
45,0°C
5026Ω
-6,5°C
37054Ω
19,5°C
12503Ω
45,5°C
4943Ω
-6,0°C
36221Ω
20,0°C
12266Ω
46,0°C
4862Ω
-5,5°C
35410Ω
20,5°C
12034Ω
46,5°C
4782Ω
-5,0°C
34619Ω
21,0°C
11806Ω
47,0°C
4704Ω
-4,5°C
33849Ω
21,5°C
11584Ω
47,5°C
4627Ω
-4,0°C
33099Ω
22,0°C
11367Ω
48,0°C
4552Ω
-3,5°C
32368Ω
22,5°C
11154Ω
48,5°C
4478Ω
-3,0°C
31655Ω
23,0°C
10946Ω
49,0°C
4405Ω
-2,5°C
30961Ω
23,5°C
10742Ω
49,5°C
4334Ω
-2,0°C
30284Ω
24,0°C
10543Ω
50,0°C
4264Ω
-1,5°C
29624Ω
24,5°C
10348Ω
50,5°C
4196Ω
-1,0°C
28981Ω
25,0°C
10157Ω
51,0°C
4129Ω
-0,5°C
28353Ω
25,5°C
9970Ω
51,5°C
4063Ω
0,0°C
27742Ω
26,0°C
9787Ω
52,0°C
3998Ω
0,5°C
27146Ω
26,5°C
9608Ω
52,5°C
3934Ω
1,0°C
26564Ω
27,0°C
9433Ω
53,0°C
3872Ω
1,5°C
25997Ω
27,5°C
9261Ω
53,5°C
3810Ω
2,0°C
25444Ω
28,0°C
9093Ω
54,0°C
3750Ω
2,5°C
24904Ω
28,5°C
8929Ω
54,5°C
3691Ω
3,0°C
24378Ω
29,0°C
8768Ω
55,0°C
3633Ω
3,5°C
23864Ω
29,5°C
8610Ω
55,5°C
3576Ω
4,0°C
23363Ω
30,0°C
8456Ω
56,0°C
3520Ω
4,5°C
22874Ω
30,5°C
8305Ω
56,5°C
3465Ω
5,0°C
22397Ω
31,0°C
8157Ω
57,0°C
3411Ω
5,5°C
21931Ω
31,5°C
8012Ω
57,5°C
3358Ω
6,0°C
21477Ω
32,0°C
7870Ω
58,0°C
3306Ω
6,5°C
21033Ω
32,5°C
7730Ω
58,5°C
3255Ω
7,0°C
20600Ω
33,0°C
7594Ω
59,0°C
3205Ω
7,5°C
20177Ω
33,5°C
7461Ω
59,5°C
3156Ω
8,0°C
19764Ω
34,0°C
7330Ω
60,0°C
3107Ω
8,5°C
19361Ω
34,5°C
7202Ω
60,5°C
3060Ω
9,0°C
18967Ω
35,0°C
7076Ω
61,0°C
3013Ω
9,5°C
18583Ω
35,5°C
6953Ω
61,5°C
2967Ω
10,0°C
18208Ω
36,0°C
6832Ω
62,0°C
2922Ω
10,5°C
17841Ω
36,5°C
6714Ω
62,5°C
2878Ω
11,0°C
17483Ω
37,0°C
6598Ω
11,5°C
17133Ω
37,5°C
6485Ω
12,0°C
16791Ω
38,0°C
6374Ω
12,5°C
16457Ω
38,5°C
6264Ω
13,0°C
16131Ω
39,0°C
6158Ω
13,5°C 14,0°C 14,5°C 15,0°C 15,5°C
15812Ω 15501Ω 15196Ω 14899Ω 14608Ω
39,5°C 40,0°C 40,5°C 41,0°C 41,5°C
6053Ω 5950Ω 5849Ω 5751Ω 5654Ω
25 TILGANG TIL PARAMETERENE Parameterene kan ha behov for oppdateringer, og finjusteringer fra tid til annen. Det kan skje at verdiene på en aktuell enhet, er forskjellige fra de som er vist på flg. sider. Ved tvil, vennligst se parameterliste tilhørende den aktuelle enhet, basert på serienr.. Det er tre nivåer av parametere: • Nivå 0 : Passord ikke nødvendig • Nivå 1 : passord VEDLIKEHOLD = 115 • Nivå 2 : passord FABRIKANT = 321 En vil bli kastet ut av passordbeskyttede parametere, hvis ingen knapp betjenes i løpet av 2 minutter. Et passord (= 101), bekreftet ved å trykke knappen “PIL OPP ”, sletter alarmloggen, og nullstiller maskinklokken. Merk: noen få parametere er ikke brukt, de blir derfor ikke vist.
1 1. 6
0
0
Parameter PASSORD
0
3 2 1
Sett PASSORD verdi
1
0
1
1
1 1. 6
Parameter tilgang
Verdi modifisering
Utgang og lagring
26 PARAMETER LISTE PARAMETER MENY Tastat ur Index
Mnemonic Name ENCCar
1
Beskrivelse
Default
Psw level
Min
maks
Tenths
UM
It enables charged comp. 0=No 1=Cool 2=Heat 3=Always
0
1
0
3
0
0=None 1=cooling only 2= heating only 3=Always °C
2
CompCarC
Max. Summer load compensation
1
2
0
10
1
3
CompCarH
Max. Winter load compensation
1
2
0
10
1
°C
4
MediaDelta
Time for average on (Ting. – Tout)
300
2
0
999
0
sec
5
MinDeltaC
Min. Summer delta temperature
1
2
0
10
1
°C
6
MaxDeltaC
Max. Summer delta temperature
4
2
0
10
1
°C
7
MinDeltaH
Min. Winter delta temperature
1
2
0
10
1
°C
8
MaxDeltaH
Max. Winter delta temperature
4
2
0
10
1
°C
0
0=None 1=cooling only 2= heating only 3=Always
CompExt 9
Ext.temp. comp. enabling 0=No 1=Cool 2=Heat 3=Always
0
1
0
3
10
CextMaxC
Ext. temp. for max. summer correction
15
2
-60
90
0
°C
11
CextMinC
Ext. temp. for min. summer correction
30
2
-60
90
0
°C
12
CextMaxH
Ext. temp. for max. winter correction
15
2
-60
90
0
°C
13
CextMinH
Ext. temp. for min winter correction
0
2
-60
90
0
°C
14
MaxCExtC
Max. value of summer correction
8
2
0
25
1
°C
15
MaxCExtH
Max. value of winter correction
10
2
0
25
1
°C
16
HExtMinC
Ext. enthalpy for min. correction
10,5
2
0
50
0
g/Kg
17
HExtMaxC
Ext. enthalpy for max. correction
13,5
2
0
50
0
g/Kg
WaterReset
Water Reset enabling 0=No 1=Cool 2=Heat 3=Always
0
1
0
3
0
0=None 1=cooling only 2= heating only 3=Always
MaxCWRH
Max. value of WR winter correction
10
2
0
15
1
°C
4
2
4
20
0
mA
20
2
4
20
0
mA
8
2
0
15
1
°C
20
2
4
20
0
mA
18 19 20 21 22 23
SWRMAXH SWRMinH MaxCWRC SWRMaxC
Signal corresponding to Max. winter correction Signal corresponding to Min. winter correction Max. value of WR correction in summer operation Signal corresponding to Max. WR in summer operation Signal corresponding to Min. WR in summer operation
4
2
4
20
0
mA
25
MaxSetHeat
MAX Set Heat
51
2
-60
90
1
°C
26
MinSetHeat
Min Set Heat
22
2
-60
90
1
°C
27
MaxSetCool
Max Set Cool
21
2
-60
90
1
°C
28
MinSetCool
Min Set Cool
5
2
-60
90
1
°C
29
SecondSetC
Secondary summer SetPoint
10
0
-60
90
1
°C
30
SecondSetH
Secondary winter SetPoint
35
0
-60
90
1
°C
31
Set2EN
Enables second Set Point
0
1
0
1
0
1=YES / 0=NO
32
SetCool
Summer Set Point
5,7
0
-30
60
1
°C
33
SetHeat
Winter Set Point
41,2
0
-30
60
1
°C
34
TScanMax
Max. activation scann time
600
2
0
9999
0
sec
24
SWRMinC
PARAMETER MENU Keybo ard Index
Mnemonic Name
Description
Default
Psw level
Min
Max
Tenths
UMa
35
TScanMin
Min. activation scann time
60
2
0
9999
0
sec
36
TSRelease
Release scann time
10
2
0
9999
0
sec
37
DeltaTC
Summer Delta Temperature
5
2
0
20
1
°C
38
DeltaTH
Winter Delta Temperature
5
2
0
20
1
°C °C
39
IsLastStep
Last step release hysteresis
0,3
2
0
5
1
40
IsFirstStep
First step activation hysteresis
0,3
2
0
5
1
°C
41
TScanMant
Maintenance scann time
1800
2
0
9999
0
sec
42
SetMantCool
Summer maintenance Set Point
20
0
-30
60
1
°C
43
SetMantHeat
Winter maintenance Set Point
30
0
-30
60
1
°C
44
MantCoolEn
Enables Summer maintenance
0
0
0
1
0
1=YES / 0=NO
MantHeatEn
Enables winter maintenance
1= YES / 0=NO
45 46 47
MinStatoValvola Radiant modulating valve min. opening BP1Enabled
Low pressure 1 pre-alarm enabling
48
DiffBP1
49
Comando2°Set
50
EnH2OSanitaria Sanitary water valve control enabling
51
StepLessEn
52
MinVcc
53
CompDutyEn
54
DutyVar
55
MaxCompDuty
56
TimeCycle
57
CompONEN
Low pressure 1 pre-alarm differential 2° set point mode control by parameter
0
0
0
1
0
20
2
0
100
0
%
0
1
0
1
0
1= YES / 0=NO
0,3
1
0
15
1
bar
0
1
0
1
0
1= YES / 0=NO
0
1
0
1
0
1= YES / 0=NO 1= YES / 0=NO
Modulatine compressor enabling
0
2
0
1
0
Min. analogic output voltage of the modulating compressor with active compr.
20
2
0
100
1
volt
0
0=None 1=cooling only 2= only heating 3=Always
It enables comp. Duty 0=No 1=Cool 2=Heat 3=Always
3
1
Critical duty value
20
Max. duty compensation value
1,5 1800
Duty compensation calculation time frame It enables comp. Duration 0=No 1=Cool 2=Heat 3=Always
3
0
3
2
0
100
0
%
2
0
10
1
°C
2
0
32000
0
sec
0
0=None 1=cooling only 2= only heating 3=Always
2
0
3
58
TimeOnMin
Min. operating time
200
1
0
32000
0
sec
59
TimeOnMAX
Max. operating time
300
2
0
32000
0
sec
Max. comp. Value on duration
1
2
0
10
1
°C
Summer LP bypass time Sec*10
12
2
0
120
0
sec*10 sec*10
60
MaxCON
61
BypMinCool
62
BypMinHeat
Winter LP bypass time Sec10*
18
2
0
120
0
63
TimeONON
Min. start/start compr.delay
360
2
0
32000
0
sec
64
TimeOFFON
Min. stop/start compr. delay
30
2
0
32000
0
sec
65
SetPreBP1
Low pressure 1 pre-alarm set
3,5
1
0
50
1
bar
66
ByPassFanHeat
Cond. fan OFF time from ON comp.in Heat
60
2
0
999
0
sec
67
PCond20mA
Scale bottom of the 4-20mA pressure probe
30
2
0
50
0
bar
68
MaxHPHour
HP hour max. alarms
2
2
0
20
0
none
69
MaxLPHour
max LP alarms/hour
3
2
0
20
0
none
70
TOut1En
It enables the heater output probe
0
2
0
1
0
1=YES / 0=NO
71
MaxRateoRad
Variation rateo value of the radiant outlet temp. that put the onoff valve in closing
2
1
0
10
1
°C
PARAMETER MENU Keybo ard Index
Mnemonic Name
72
PotC1
73
EnLimiteTExtH
74
TlimiteMaxH
76
ScanPreAF
Description
Default
Psw level
Min
Max
Tenths
100
2
0
100
0
%
0
2
0
1
0
1=YES / 0=NO
External temperature for max SP Heat
-5
2
-60
90
0
°C
PreFreeze scann time
10
2
0
9999
0
sec
Compressor1 capacity percentage 1 SP Heat corr. Enabling for external air limit
UMa
77
SetHeater
Antifreeze heater set point
4
0
-60
90
1
°C
78
MinFreeze
Min. level antifreeze alarm
4
2
-60
90
1
°C
79
MaxFreeze
Max. level antifreeze alarm
15
2
-60
90
1
°C
80
AlFreeze
Antifreeze alarm set
4
0
-60
90
1
°C
81
DiffHeater
2,5
1
0
15
1
°C
82
IsPreAF
83
IstAlFreeze
Antifreeze heater differential Antifreeze Pre-alarm hysteresis Antifreeze Alarm hysteresis Antifreeze pre-alarm set
1
2
0
15
1
°C
2,5
2
0
15
1
°C
4,5
0
0
15
1
°C
3800
1
0
32000
0
1=500ns
84
PreAF
91
FanPFCorr
92
ONFanCool
FAN start pressure with comp. Off summer
17
1
-60
90
1
bar
93
ONFanHeat
FAN start pressure with comp. Off winter
0
1
-60
90
1
bar
94
MaxFanHeat
Pressure for max fan speed heat.
3,7
1
-60
90
1
bar
95
MinFanHeat
Pressure for min fan speed heat
4,2
1
-60
50
1
bar
96
MaxFanCool
Pressure for max fan speed cool
17
1
-60
50
1
bar
97
MinFanCool
Pressure for min fan speed cool
13,5
1
-60
50
1
bar
98
CutOffHeat
Fan Cut-OFF heat
4,8
1
-60
50
1
bar
99
CutOffCool
Fan Cut-OFF cool
12
1
-60
50
1
bar
Fan phase factor correction
100
TstartUp
Pulse duration at fan start
5
1
0
120
0
sec
101
TbypCutOf
Cut-off by-pass duration
25
1
0
120
0
sec
102
MaxFan
Max % Fan
70
1
0
100
0
%
103
MinFan
Min % Fan
40
1
0
100
0
%
104
MaxStartUp
% Fan at start pulse
70
1
0
100
0
%
105
ToutEn
It enables the evaporator outlet temp. probe
1
2
0
1
0
1=YES / 0=NO
106
TypeCE
Condensing time 0=In Air 1=In Water 2=Temp. Control in heat for unit reversible on water
0
2
0
2
0
none
107
TimeOffV
111
HP1Enabled
Water flow by-pass time
0
1
0
120
0
sec
Enables HP1 Prealarm
0
1
0
1
0
1=YES / 0=NO
24,5
1
0
50
1
bar
2
1
0
15
1
bar sec
112
SMaxPreC
113
DiffMaxPreC
Summer HP1 Prealarm Set Summer HP1 Prealarm Hysteresis
114
ByPassFreeze
ByPassAntifreeze alarm
120
1
0
32000
0
117
SetH2OSanitaria
Sanitary water set point
35
0
-60
90
1
°C
118
TempoCorrezione
Radiant correction time
20
1
0
999
0
sec
119
ModeEnable
It sets the operating modes
0
2
0
4
0
none
Radiant valve max. time in recirculation position
120
TmaxRicircolo
800
2
10
990
0
min
121
PstartDfr
Defrost start press.
3,4
1
0
50
1
bar
122
TstartDfr
Defrost start temp.
1
1
-10
30
1
°C
PARAMETER MENU Keybo ard Index
Mnemonic Name
Description
Default
Psw level
Min
Max
Tenths
UMa
123
TstopDfr
Defrost stop. Temp.
15
2
-10
30
1
°C
124
TmaxDfr
Defrost max. time
480
2
0
32000
0
sec
125
TimeInDfr
Defrost start max. time
2700
2
0
32000
0
sec
126
Ttransient
Defrost transient time
90
2
0
32000
0
sec
128
DeltaPDfr
Defrost delta press.
1,5
1
0
30
1
bar
129
MaxCnt
4
2
0
10
0
none bar/min
Max. counting IN defrost
130
RateoMaxP
Max. pressure ratio
1
2
0
30
1
131
TminCntDfr
Min. defrost. counting time
1800
2
0
32000
0
sec
132
TmaxCntDfr
Max. defrost. counting time
2700
2
0
32000
0
sec
133
TextMinDly
External temperature for minimum delay
5
2
-10
30
1
°C
134
TextMaxDly
External temperature for maximum delay
-10
2
-10
30
1
°C
135
TimeDrain
136
TimeFanDfr
137
TExtDfr
138
PFDfr
140
PlugInEN
Drop time
60
1
0
900
0
sec
Fan time after defrost
15
1
0
900
0
sec
Extern. temperature for fan start after defrost
3
1
-10
30
1
°C
1,4
1
0
50
1
bar
Defrost forcing pressure Plug-in presence
1
2
0
1
0
1=YES / 0=NO
0
2
0
2
0
none
141
SecondPump
Second pump presence 0=Single pump on board 1=Single pump+reserve 2=Variable pump
142
ByPassFlusso
Flow by-pass from pump start
25
1
0
32000
0
sec
143
RitComp
Comp. start delay from pump On
25
1
0
32000
0
sec
144
TStartPump
Maintenance pump start time
120
1
0
32000
0
sec
145
DlyPumpC
Pump switch-off delay from comp. OFF
120
2
0
32000
0
sec
146
OffsetBTIn
Inlet temp.Offset
0
1
-10
10
1
°C
147
OffsetBT1
Outlet 1 temp.Offset
0
1
-10
10
1
°C
148
OffsetPR
Radiating panel water temperature Offset
0
1
-10
10
1
°C
149
OffsetBT3
Coil 1 temp.Offset
0
1
-10
10
1
°C
150
OffsetBTRe
Electric heater output temp. offset
0
2
-10
10
1
°C
151
OffsetWR
Offset Water Reset
0
1
-100
100
0
mA 1=YES / 0=NO
152
TextEn
EXT air probe presence
1
1
0
1
0
153
OffsetBTE
Offset external temperature
0
1
-10
10
1
°C
154
OffsetBP1
Offset pressure 1
0
1
-10
10
1
bar
155
OffsetURExt
Offset Ext RH
0
1
-10
10
1
%
156
URProbeExt
Enables external RH% probe
0
1
0
1
0
1=YES / 0=NO bar
157
OffsetPCWBAN WBAN condensing pressure offset
0
1
-10
10
1
158
Threshold of fan Start ext. temperature at TextOnFanCool stopped compressor
43
1
-30
90
0
°C
2
2
0
3
0
none
-15
2
-60
90
0
°C
0
2
0
1
0
flag
1
2
0
1
0
flag
0
0
0
1
0
flag
159
ProbeCondEn
Selection of the type of condensation probe
160
TlimiteMinH
Ext. Temperature for min SP Heat
161
ValveMode
Cycle reversing valve polarity
162
HeatPump
163
RemMode
Configurate unit as CHILLER (0)HEAT PUMP (1) Remote input setting 0=H/C from ID 1=H/C from keypad or supervisor
PARAMETER MENU Keybo ard Index
Mnemonic Name
164
Address
165
Baud Rate
166
Parity
Description
Default
Psw level
Min
Max
Tenths
UMa
ModBus serial address
55
2
0
127
0
none
Baud Rate (0=4800 / 1=9600)
0
2
0
1
0
flag
Parity 0=NO / 1=YES
0
2
0
1
0
flag
169
TDeltaChiller
Water delta for the calculation of the water outlet control threshold
2
1
-20
20
0
°C
173
TPompaMax
Max. flow-rate activation timer
20
2
0
999
0
sec
Min. settable value for the SP Heat
35
2
-30
90
1
°C
CANOPEN board address
1
1
0
127
0
none
175
MinSetLimiteH
176
CANAddressNode
177
PotRes
178
ModeHeater
179
LimPotTextEn
180
LimText
181
IstRes
Output by the integration heaters Compressor oper. enabling in heating Power limit enabling for ext. temperature. Ext. temperature limit for compressor operation Differential on the LimText value for activating the heaters
2
0
100
0
%
0
2
0
2
0
none
0
2
0
2
0
none
0
2
-30
30
0
°C
5
2
2
20
0
°C
182
Tregime
1200
1
0
10000
0
sec
183
MaxTempC
COOLING delivery decrease threshold
15
2
0
90
1
°C
184
MinTempH
HEATING delivery decrease threshold
15
2
0
90
1
°C
185
IstTempC
Cooling delivery decrease hysteresis
8
2
0
15
1
°C
186
IstTempH
Heating delivery decrease hysteresis
5
2
0
15
1
°C
187
MinSignal
Pump signal corresponding to max. delivery decrease
60
2
0
100
0
%
188
MaxSignal
Pump signal corresponding to rated delivery
100
2
0
100
0
%
189
StepType
Modality of variable pump step insertion
1
2
0
1
0
flag
190
EnCompExtR
External temperature radiating compensation enabling
0
1
0
1
0
1= YES / 0=NO
191
EnCompRugiada
Enables the compensation for dew in cooling
0
1
0
1
0
1=YES / 0=NO
192
SetPointR
Radiating set-point
25
2
-60
90
1
°C
194
SetMinC
Differential for radiating set-point
18
2
-60
90
0
°C
195
SetMaxC
Min. set-point in cooling
23
2
-60
90
0
°C
196
TMinExtC
Max. set-point in cooling
20
2
-60
90
0
°C
197
TmaxExtC
Min. summer temperature in cooling
35
2
-60
90
0
°C
198
SetMinH
Max. summer temperature in cooling
30
2
-60
90
0
°C
199
SetMaxH
Min. set-point in heating
35
2
-60
90
0
°C
200
TMinExtH
Max. set-point in heating
5
2
-60
90
0
°C
201
TMaxExtH
Min. external temperature heating
20
2
-60
90
0
°C
202
TPannRadEn
Max. external temperature heating
0
2
0
1
0
1=YES / 0=NO
203
EnPCondPlugIn
204
PumpPFCorr
205
TempAperturaValv
206
BandaApertura
207
MaxInteg
208
SetfreezeExt
209
SetHeaterExt
210
SetValvolaOn
Heaters Timeout
100
It enables and sets F.S. WBAN condensing press. probe Evaporator pump power factor correction
0
1
0
50
0
bar
3800
1
0
32000
0
1=500ns
Necessary time to position the VRad from closed to completely opened
90
1
0
999
0
sec
It allows to weigh the valve opening time
200
1
100
1000
0
none
100
1
0
100
1
%
4
1
-30
90
1
°C
4
1
-30
90
1
°C
28,5
1
0
50
10
bar
Max. value of the integration heater outputs when activated at the same time of the compressor Source water temp. threshold for the Coil freeze alarm activation Source water temp. Threshold for the antifreeze heater activation Activation threshold of the defrosting valve at hot gas
PARAMETER MENU Keybo ard Index
Mnemonic Name
211
DiffValvolaOn
212
TimerPCondOn
213
AddTast
Description Differential for the reset in OFF of the defrosting valve at hot gas Active timer from ON compressor that manages the DFR valve at hot gas in base of the critical pressure thresholds Keypad address 7=Local 1=Remote
Default
Psw level
Min
Max
Tenths
UMa
1,5
1
0
50
10
bar
300
1
0
900
1
sec
7
0
0
127
0
none
70
www.clivet.com The information contained in this manual is not binding and may be changed by the manufacturer without prior notice. All copying, even partial, is prohibited.