FLAME DETECTION SYSTEM
IRIS P520 AMPLIFIER
IRIS P520 AMPLIFIER COMBUSTION AND ENERGY - [email protected] - www.ce2k.com - tel. +39.0341.260926
FLAME DETECTION SYSTEM
IRIS P520 AMPLIFIER SERIAL COMMUNICATION
• • • • •
• • •
• • •
• •
Flame signal amplifier Input signal: from viewing head Flame relay 2 from C contacts Self-checking relay 1 from C contact Relay contact ratings: ▪ max switching power 60W/125VA ▪ max switching voltage 220VDC, 250VAC ▪ max switching current 2A Ambient Temperature: 0°C to + 50°C Flame strength signal: bar graph-four digit readout Analog Flame Signal: 0 to 20 mA or 4 to 20 mA output for remote meters 360 ohm maximum resistance Power to Viewing Head: +26 VDC, fused 25A, +14.3 VDC Pulsing 2Sec ON / 8 Sec OFF Mounting type: 19” RACK DIN 41494 Power supply: 26Vdc + 5% - 20%, 300mA with one Viewing Head (24VDC when not using battery backup) (100mA for each additional Viewing Head) Electrical connection: screw terminals Weight: 1.0Kg
• RS - 422 (Differential) 4800 or 9600 baud • Input / Output circuits photocoupler isolated from P520 power supplies and ground • Baud rate selectable from front panel of P520
APPLY TO • Flares • Boilers • Burners
MANUFACTURER Combustion and Energy Srl Part number: IRIS P520 AMPLIFIER.
COMBUSTION AND ENERGY - [email protected] - www.ce2k.com - Tel. +39.0341.260926 Document is subject to change without any notice
IRIS P520 AMPLIFIER
KEY FEATURES