Commissioning Record
Company Our reference
Client
Date
SO No.
Plant
Project/Air handling unit
Series no.:
Plant address
Type/size
Program version:
Filter calibration performed Timer, current time preset Other controls
Notes
Swegon reserves the right to alter specifications.
www.swegon.com
1
GB.GOLDSKE.150520
Function
Factory-preset value
Adjusted value
Airflow Regulation mode Supply air
X Air flow X Air flow
Extract air Operation level Flow, low speed Flow, high speed Flow, max speed Flow, min. speed Pressure, low speed Pressure, high speed Max. fan speed Pressure, max speed Demand-controlled, low speed Demand-controlled, high speed
SA EA SA EA SA
1) 1) 1) 1) 1)
EA
1)
Y2, breakpoint, sup. air Y3, breakpoint, sup. air Y4, breakpoint, sup. air Extract air, flow Y1, breakpoint, extr. air Y2, breakpoint, extr. air Y3, breakpoint, extr. air Y4, breakpoint, extr. air
Demand
Slave
Airflow
Duct press.
Demand
Slave
Duct press.
Demand
Slave
Airflow
Duct press.
Demand
Slave
m3/h
cfm
1)
1) 1) 1) 1) 1)
1)
1)
1) 1)
SA EA SA (Pa) EA (Pa)
100 100
SA (Pa)
200
EA (Pa)
200
SA (%) EA (%) SA (Pa) EA (Pa) SA (%)
100% 100% 200 200 25
EA (%) SA (%)
25 50
EA (%)
50
Optimize Optimize Set point displacement Supply air Extract air Unit Unit Outdoor air compensation Outdoor air compensation X1, breakpoint, outdoor air temp. X2, breakpoint, outdoor air temp. X3, breakpoint, outdoor air temp. X4, breakpoint, outdoor air temp. Supply air, flow Y1, breakpoint, sup. air
Duct press.
On
X Off
On
Off
On On
X Off X Off
On On
Off Off
l/s
X m3/s
l/s
m3/s
m3/h
X Disabled
°C
Low speed High Speed Low speed and high speed -20°C
°C
-10°C
°C
+10°C
°C
+20°C
cfm
Disabled Low speed High Speed Low speed and high speed
25% of max. airflow for air handling unit 25% of max. airflow for air handling unit 25% of max. airflow for air handling unit 25% of max. airflow for air handling unit 25% of max. airflow for air handling unit 25% of max. airflow for air handling unit 25% of max. airflow for air handling unit 25% of max. airflow for air handling unit
1) Low speed = 25%, high speed = 50% and max. speed = 75 % of max. flow, see Section 5.3.1.2 2
www.swegon.com
Swegon reserves the right to alter specifications.
GB.GOLDSKE.150520
Function Supply air, pressure Y1, breakpoint, supply air Y2, breakpoint, supply air Y3, breakpoint, supply air Y4, breakpoint, supply air Extract air, pressure Y1, breakpoint, extract air Y2, breakpoint, extract air Y3, breakpoint, extract air Y4, breakpoint, extract air Booster diffusers Booster diffusers
Factory-preset value Pa Pa Pa Pa
100 100 100 100
Pa Pa Pa Pa
100 100 100 100 On
Swegon reserves the right to alter specifications.
X Off
Adjusted value
On
Off
www.swegon.com
3
GB.GOLDSKE.150520
Temperature
Function
Factory-preset value
Adjusted value
Temperature Regulation mode Position Mode Xzone: Settings ERS 1 Extract related supply air-1 step Extract related supply air-1 diff Extract related supply air-1 break point Xzone Extract related supply air-1 step Xzone Extract related supply air-1 diff Xzone Extract related supply air-1 break point ERS 2 Extract air temperature Extract related supply air-2 X1 Extract related supply air-2 X2 Extract related supply air-2 X3 Extract related supply air-2 X4 Xzone Extract related supply air-2 X1 Xzone Extract related supply air-2 X2 Xzone Extract related supply air-2 X3 Xzone Extract related supply air-2 X4 Supply air temperature set point Extract related supply air-2 Y1 Extract related supply air-2 Y2 Extract related supply air-2 Y3 Extract related supply air-2 Y4 Xzone Extract related supply air-2 Y1 Xzone Extract related supply air-2 Y2 Xzone Extract related supply air-2 Y3 Xzone Extract related supply air-2 Y4 Supply air regulation Supply air (temp. set point) Xzone supply air (temp. set point) Extract air regulation Extract air (temp. set point) Supply air, min. Supply air, max. Xzone Extract air (temp. set point) Xzone Supply air min. Xzone Supply air max.
4
www.swegon.com
ERS 1
ERS 2
Extract air
ORS
ERS 1
ERS 2
Extract air
ORS
X Supply air ORE
X Supply air ORE
ERS 1
ERS 2
Supply air
Extract air
ORS
ORE
ERS 1
ERS 2
Supply air
Extract air
ORS
ORE
2 K 3 °C 22 2 K 3 °C 22
°C °C °C °C °C °C °C °C
15 20 22 22 15 20 22 22
°C °C °C °C °C °C °C °C
20 18 14 12 20 18 14 12
°C 21 °C 21 °C °C °C °C °C °C
21 16 28 21 16 28
Swegon reserves the right to alter specifications.
GB.GOLDSKE.150520
Function ORS regulation Outdoor air temperature Outdoor related supply air X1 Outdoor related supply air X2 Outdoor related supply air X3 Outdoor related supply air X4 Xzone Outdoor related supply air X1 Xzone Outdoor related supply air X2 Xzone Outdoor related supply air X3 Xzone Outdoor related supply air X4 Supply air temperature set point Outdoor related supply air Y1 Outdoor related supply air Y2 Outdoor related supply air Y3 Outdoor related supply air Y4 Xzone Outdoor related supply air Y1 Xzone Outdoor related supply air Y2 Xzone Outdoor related supply air Y3 Xzone Outdoor related supply air Y4 ORE regulation Supply air, min. Supply air, max. Outdoor air temperature Outdoor related extract air X1 Outdoor related extract air X2 Outdoor related extract air X3 Outdoor related extract air X4 Xzone Outdoor related extract air X1 Xzone Outdoor related extract air X2 Xzone Outdoor related extract air X3 Xzone Outdoor related extract air X4 Extract air temperature set point Outdoor related extract air Y1 Outdoor related extract air Y2 Outdoor related extract air Y3 Outdoor related extract air Y4 Xzone Outdoor related extract air Y1 Xzone Outdoor related extract air Y2 Xzone Outdoor related extract air Y3 Xzone Outdoor related extract air Y4 Set point displacement Set point displacement Neutral zone Supply air, temperature control Extract air, temperature control Xzone Supply air neautral zone Xzone Extract air neautral zone External temperature sensors Extract air duct, temperature sensor Room sensor 1 Room sensor 2 Room sensor 3 Room sensor 4
Swegon reserves the right to alter specifications.
Factory-preset value
°C °C °C °C °C °C °C °C
-20°C -10°C 10°C 20°C -20°C -10°C 10°C 20°C
°C °C °C °C °C °C °C °C
21.5°C 21.5°C 21.5°C 21.5°C 21.5°C 21.5°C 21.5°C 21.5°C
°C °C
16°C 28°C
°C °C °C °C °C °C °C °C
-20°C -10°C 10°C 20°C -20°C -10°C 10°C 20°C
°C °C °C °C °C °C °C °C
21.5°C 21.5°C 21.5°C 21.5°C 21.5°C 21.5°C 21.5°C 21.5°C On
K K K K
X Off
Adjusted value
On
Off
0.5 0.5 0.5 0.5 On On On On On
X X X X X
Off Off Off Off Off
On On On On On
Off Off Off Off Off
www.swegon.com
5
GB.GOLDSKE.150520
Function
Factory-preset value
External temperature sensors Room sensor mode Room temp from communication Room temp., for intermittent night heat only Outdoor air sensor 1 Outdoor air sensor 2 Outdoor air sensor 3 Outdoor air sensor 4 Outdoor air sensor mode Outdoor temp from communication Xzone room sensor 1 Xzone Room sensor 2 Xzone Room sensor 3 Xzone room sensor 4 Xzone, room sensor mode Xzone, room temp from communication Regulation sequence Heat mode
1
Cool mode
1
On On On On On On X Medium On On On On On X Medium On
X X X X X X X X X X X X
Min. Off Off Off Off Off Off Min. Off Off Off Off Off Min. Off
Max.
Max.
Max.
Medium On On On On On On Medium On On On On On Medium On
Min. Off Off Off Off Off Off Min. Off Off Off Off Off Min. Off
Min. exhaust air Min. exhaust air Min. exhaust air temperature
On 5.0
X Off
On
Off
°C
Morning Boost Morning Boost Start time
On hour:min. 00:00
X Off
On
Off
On
Off
Supply air, set point Heating boost Heating boost Start limit
Start limit (Comfort)
On K
3
Comf. Econ. Sequence Comf. and econ. Economy and sequence
K
Max.
Max.
16
Room temperature, stop
°C
18
Supply air temperature, set point
°C
28
On
Supply airflow, set point
Disabled Comf. Econ. Sequence Comf. and econ. Economy and sequence
3
°C
X On
X Off Off
On On
Off Off
On
Off
50% of max. supply air for AHU alt. 100 Pa 50% of max. supply air for AHU alt. 100 Pa
Extract airflow, set point Summer night cool Summer night cool Start time
On hour:min. 23:00
Stop time
hour:min. 06:00
Outdoor air start
°C
10
Extract air start
°C
22
Extract air stop
°C
16
Supply air, set point
°C
10
www.swegon.com
X Off
X Disabled
Intermittent night heat Intermittent night heat Air recirculation Room temperature, start
Down regulation (airflow/pressure) Down regulation
Max.
50% of max. supply air for AHU alt. 100 Pa
Cooling boost Cooling boost
6
X Medium
Adjusted value
X Off
Disabled X Supply air Supply and extract air
Disabled Supply air Supply and extract air Swegon reserves the right to alter specifications.
GB.GOLDSKE.150520
Time and schedule
Function
Factory-preset value
Adjusted value
Time and schedule Schedule settings Preselected operating mode
X Total stop Normal Stop
X On
Effective period Start date Start date
yy/mm/dd
Stop date Stop date
yy/mm/dd
Day schedule Monday Time, event 1
hour:min.
X Inactive
Enabled
Inactive
High Speed
00:00
X Disabled
Time, event 3
Low speed Normal Stop 00:00
Event 3
X Disabled
Time, event 4
Low speed Normal Stop 00:00
Event 4
X Disabled
Time, event 5
Low speed Normal Stop 00:00
Event 5
X Disabled
Time, event 6
Low speed Normal Stop 00:00
Event 6
Extended Normal Stop
Enabled
Event 2
hour:min.
Normal Stop
Off Inactive
Time, event 2
hour:min.
Off
Low speed
On Enabled
Low speed Normal Stop 00:00
hour:min.
Extended Normal Stop
Total stop
X Inactive
X Disabled
hour:min.
High Speed
Enabled
Event 1
hour:min.
Low speed
X Disabled Low speed Normal Stop
Swegon reserves the right to alter specifications.
Total stop High Speed Extended Normal Stop
Disabled Low speed Normal Stop
Total Stop High Speed Extended Normal Stop
Total stop High Speed Extended Normal Stop
Disabled Low speed Normal Stop
Total Stop High Speed Extended Normal Stop
Total stop High Speed Extended Normal Stop
Disabled Low speed Normal Stop
Total Stop High Speed Extended Normal Stop
Total stop High Speed Extended Normal Stop
Disabled Low speed Normal Stop
Total Stop High Speed Extended Normal Stop
Total stop High Speed Extended Normal Stop
Disabled Low speed Normal Stop
Total Stop High Speed Extended Normal Stop
Total stop High Speed Extended Normal Stop
Disabled Low speed Normal Stop
Total Stop High Speed Extended Normal Stop
www.swegon.com
7
GB.GOLDSKE.150520
Function Tuesday Time, event 1 Event 1
Time, event 2 Event 2
Time, event 3 Event 3
Time, event 4 Event 4
Time, event 5 Event 5
Time, event 6 Event 6
Factory-preset value hour:min.
00:00
X Disabled
hour:min.
Low speed Normal Stop 00:00
X Disabled
hour:min.
Low speed Normal Stop 00:00
X Disabled
hour:min.
Low speed Normal Stop 00:00
X Disabled
hour:min.
Low speed Normal Stop 00:00
X Disabled
hour:min.
Low speed Normal Stop 00:00
X Disabled Low speed Normal Stop
Wednesday Time, event 1 Event 1
Time, event 2 Event 2
Time, event 3 Event 3
Time, event 4 Event 4
Time, event 5 Event 5
Time, event 6 Event 6
hour:min.
Low speed Normal Stop 00:00
X Disabled
hour:min.
Low speed Normal Stop 00:00
X Disabled
hour:min.
Low speed Normal Stop 00:00
X Disabled
hour:min.
Low speed Normal Stop 00:00
X Disabled
hour:min.
Low speed Normal Stop 00:00
X Disabled Low speed Normal Stop
8
www.swegon.com
Total stop High Speed Extended Normal Stop
Disabled Low speed Normal Stop
Total Stop High Speed Extended Normal Stop
Total stop High Speed Extended Normal Stop
Disabled Low speed Normal Stop
Total Stop High Speed Extended Normal Stop
Total stop High Speed Extended Normal Stop
Disabled Low speed Normal Stop
Total Stop High Speed Extended Normal Stop
Total stop High Speed Extended Normal Stop
Disabled Low speed Normal Stop
Total Stop High Speed Extended Normal Stop
Total stop High Speed Extended Normal Stop
Disabled Low speed Normal Stop
Total Stop High Speed Extended Normal Stop
Total stop High Speed Extended Normal Stop
Disabled Low speed Normal Stop
Total Stop High Speed Extended Normal Stop
Total stop High Speed Extended Normal Stop
Disabled Low speed Normal Stop
Total Stop High Speed Extended Normal Stop
Total stop High Speed Extended Normal Stop
Disabled Low speed Normal Stop
Total Stop High Speed Extended Normal Stop
Total stop High Speed Extended Normal Stop
Disabled Low speed Normal Stop
Total Stop High Speed Extended Normal Stop
Total stop High Speed Extended Normal Stop
Disabled Low speed Normal Stop
Total Stop High Speed Extended Normal Stop
Total stop High Speed Extended Normal Stop
Disabled Low speed Normal Stop
Total Stop High Speed Extended Normal Stop
Total stop High Speed Extended Normal Stop
Disabled Low speed Normal Stop
Total Stop High Speed Extended Normal Stop
00:00
X Disabled
hour:min.
Adjusted value
Swegon reserves the right to alter specifications.
GB.GOLDSKE.150520
Function Thursday Time, event 1 Event 1
Time, event 2 Event 2
Time, event 3
Factory-preset value hour:min.
Time, event 5 Event 5
Time, event 6 Event 6
Low speed Normal Stop 00:00
X Disabled
hour:min.
Low speed Normal Stop 00:00
X Disabled
Event 3
Time, event 4 Event 4
00:00
X Disabled
hour:min.
hour:min.
Low speed Normal Stop 00:00
X Disabled
hour:min.
Low speed Normal Stop 00:00
X Disabled
hour:min.
Low speed Normal Stop 00:00
X Disabled Low speed Normal Stop
Friday Time, event 1 Event 1
Time, event 2 Event 2
Time, event 3 Event 3
Time, event 4 Event 4
Time, event 5 Event 5
Time, event 6 Event 6
hour:min.
Low speed Normal Stop 00:00
X Disabled
hour:min.
Low speed Normal Stop 00:00
X Disabled
hour:min.
Low speed Normal Stop 00:00
X Disabled
hour:min.
Low speed Normal Stop 00:00
X Disabled
hour:min.
Total stop High Speed Extended Normal Stop
Disabled Low speed Normal Stop
Total Stop High Speed Extended Normal Stop
Total stop High Speed Extended Normal Stop
Disabled Low speed Normal Stop
Total Stop High Speed Extended Normal Stop
Total stop High Speed Extended Normal Stop
Disabled Low speed Normal Stop
Total Stop High Speed Extended Normal Stop
Total stop High Speed Extended Normal Stop
Disabled Low speed Normal Stop
Total Stop High Speed Extended Normal Stop
Total stop High Speed Extended Normal Stop
Disabled Low speed Normal Stop
Total Stop High Speed Extended Normal Stop
Total stop High Speed Extended Normal Stop
Disabled Low speed Normal Stop
Total Stop High Speed Extended Normal Stop
Total stop High Speed Extended Normal Stop
Disabled Low speed Normal Stop
Total Stop High Speed Extended Normal Stop
Total stop High Speed Extended Normal Stop
Disabled Low speed Normal Stop
Total Stop High Speed Extended Normal Stop
Total stop High Speed Extended Normal Stop
Disabled Low speed Normal Stop
Total Stop High Speed Extended Normal Stop
Total stop High Speed Extended Normal Stop
Disabled Low speed Normal Stop
Total Stop High Speed Extended Normal Stop
Total stop High Speed Extended Normal Stop
Disabled Low speed Normal Stop
Total Stop High Speed Extended Normal Stop
Total stop High Speed Extended Normal Stop
Disabled Low speed Normal Stop
Total Stop High Speed Extended Normal Stop
00:00
X Disabled
hour:min.
Adjusted value
Low speed Normal Stop 00:00
X Disabled Low speed Normal Stop
Swegon reserves the right to alter specifications.
www.swegon.com
9
GB.GOLDSKE.150520
Function Saturday Time, event 1 Event 1
Time, event 2 Event 2
Time, event 3 Event 3
Time, event 4 Event 4
Time, event 5 Event 5
Time, event 6 Event 6
Factory-preset value hour:min.
00:00
X Disabled
hour:min.
Low speed Normal Stop 00:00
X Disabled
hour:min.
Low speed Normal Stop 00:00
X Disabled
hour:min.
Low speed Normal Stop 00:00
X Disabled
hour:min.
Low speed Normal Stop 00:00
X Disabled
hour:min.
Low speed Normal Stop 00:00
X Disabled Low speed Normal Stop
Sunday Time, event 1 Event 1
Time, event 2 Event 2
Time, event 3 Event 3
Time, event 4 Event 4
Time, event 5 Event 5
Time, event 6 Event 6
hour:min.
Low speed Normal Stop 00:00
X Disabled
hour:min.
Low speed Normal Stop 00:00
X Disabled
hour:min.
Low speed Normal Stop 00:00
X Disabled
hour:min.
Low speed Normal Stop 00:00
X Disabled
hour:min.
Low speed Normal Stop 00:00
X Disabled Low speed Normal Stop
10
www.swegon.com
Total stop High Speed Extended Normal Stop
Disabled Low speed Normal Stop
Total Stop High Speed Extended Normal Stop
Total stop High Speed Extended Normal Stop
Disabled Low speed Normal Stop
Total Stop High Speed Extended Normal Stop
Total stop High Speed Extended Normal Stop
Disabled Low speed Normal Stop
Total Stop High Speed Extended Normal Stop
Total stop High Speed Extended Normal Stop
Disabled Low speed Normal Stop
Total Stop High Speed Extended Normal Stop
Total stop High Speed Extended Normal Stop
Disabled Low speed Normal Stop
Total Stop High Speed Extended Normal Stop
Total stop High Speed Extended Normal Stop
Disabled Low speed Normal Stop
Total Stop High Speed Extended Normal Stop
Total stop High Speed Extended Normal Stop
Disabled Low speed Normal Stop
Total Stop High Speed Extended Normal Stop
Total stop High Speed Extended Normal Stop
Disabled Low speed Normal Stop
Total Stop High Speed Extended Normal Stop
Total stop High Speed Extended Normal Stop
Disabled Low speed Normal Stop
Total Stop High Speed Extended Normal Stop
Total stop High Speed Extended Normal Stop
Disabled Low speed Normal Stop
Total Stop High Speed Extended Normal Stop
Total stop High Speed Extended Normal Stop
Disabled Low speed Normal Stop
Total Stop High Speed Extended Normal Stop
Total stop High Speed Extended Normal Stop
Disabled Low speed Normal Stop
Total Stop High Speed Extended Normal Stop
00:00
X Disabled
hour:min.
Adjusted value
Swegon reserves the right to alter specifications.
GB.GOLDSKE.150520
Function Ex1 Time, event 1 Event 1
Time, event 2 Event 2
Time, event 3 Event 3
Time, event 4 Event 4
Time, event 5 Event 5
Time, event 6 Event 6
Factory-preset value hour:min.
00:00
X Disabled
hour:min.
Low speed Normal Stop 00:00
X Disabled
hour:min.
Low speed Normal Stop 00:00
X Disabled
hour:min.
Low speed Normal Stop 00:00
X Disabled
hour:min.
Low speed Normal Stop 00:00
X Disabled
hour:min.
Low speed Normal Stop 00:00
X Disabled Low speed Normal Stop
Ex2 Time, event 1 Event 1
Time, event 2 Event 2
Time, event 3 Event 3
Time, event 4 Event 4
Time, event 5 Event 5
Time, event 6 Event 6
hour:min.
Low speed Normal Stop 00:00
X Disabled
hour:min.
Low speed Normal Stop 00:00
X Disabled
hour:min.
Low speed Normal Stop 00:00
X Disabled
hour:min.
Low speed Normal Stop 00:00
X Disabled
hour:min.
Total stop High Speed Extended Normal Stop
Disabled Low speed Normal Stop
Total Stop High Speed Extended Normal Stop
Total stop High Speed Extended Normal Stop
Disabled Low speed Normal Stop
Total Stop High Speed Extended Normal Stop
Total stop High Speed Extended Normal Stop
Disabled Low speed Normal Stop
Total Stop High Speed Extended Normal Stop
Total stop High Speed Extended Normal Stop
Disabled Low speed Normal Stop
Total Stop High Speed Extended Normal Stop
Total stop High Speed Extended Normal Stop
Disabled Low speed Normal Stop
Total Stop High Speed Extended Normal Stop
Total stop High Speed Extended Normal Stop
Disabled Low speed Normal Stop
Total Stop High Speed Extended Normal Stop
Total stop High Speed Extended Normal Stop
Disabled Low speed Normal Stop
Total Stop High Speed Extended Normal Stop
Total stop High Speed Extended Normal Stop
Disabled Low speed Normal Stop
Total Stop High Speed Extended Normal Stop
Total stop High Speed Extended Normal Stop
Disabled Low speed Normal Stop
Total Stop High Speed Extended Normal Stop
Total stop High Speed Extended Normal Stop
Disabled Low speed Normal Stop
Total Stop High Speed Extended Normal Stop
Total stop High Speed Extended Normal Stop
Disabled Low speed Normal Stop
Total Stop High Speed Extended Normal Stop
Total stop High Speed Extended Normal Stop
Disabled Low speed Normal Stop
Total Stop High Speed Extended Normal Stop
00:00
X Disabled
hour:min.
Adjusted value
Low speed Normal Stop 00:00
X Disabled Low speed Normal Stop
Swegon reserves the right to alter specifications.
www.swegon.com
11
GB.GOLDSKE.150520
Function
Factory-preset value
Exceptions schedule Exceptions schedule 1(Ex1) Exceptions method
Date Start date Start weekday
Inactive Date range X Calendar 1
X Each day
Inactive Date range Calendar 1
X Each day Wednesday Saturday
Monday Thursday Sunday
Tuesday Friday
Each day Wednesday Saturday
Monday Thursday Sunday
Tuesday Friday
Monday Thursday Sunday
Tuesday Friday
Each day Wednesday Saturday
Monday Thursday Sunday
Tuesday Friday
Monday Thursday Sunday
Tuesday Friday
Each day Wednesday Saturday
Monday Thursday Sunday
Tuesday Friday
Mon 1-12 Each 15-21 Each day Wednesday Saturday
Odd Day 1-7 22-28 Monday Thursday Sunday
Even 8-14 29-31 Tuesday Friday
yy/mm/dd
X Each day Wednesday Saturday
Weekday Start date
Start weekday
X Each day Wednesday Saturday
12
www.swegon.com
Date Weekday Calendar 2
yy/mm/dd
Start weekday
Stop date Stop weekday
Date Weekday Calendar 2
yy/mm/dd Wednesday Saturday
Date range Start date
Adjusted value
Monday Thursday Sunday
Tuesday Friday
Swegon reserves the right to alter specifications.
GB.GOLDSKE.150520
Function
Factory-preset value
Exceptions schedule 2 (Ex2) Exceptions method
Date Start date Start weekday
Inactive Date range Calendar 1
X Each day
Inactive Date range Calendar 1
X Each day
Monday Thursday Sunday
Tuesday Friday
Each day Wednesday Saturday
Monday Thursday Sunday
Tuesday Friday
Monday Thursday Sunday
Tuesday Friday
Each day Wednesday Saturday
Monday Thursday Sunday
Tuesday Friday
Monday Thursday Sunday
Tuesday Friday
Each day Wednesday Saturday
Monday Thursday Sunday
Tuesday Friday
Mon 1-12 Each 15-21 Each day Wednesday Saturday
Odd Day 1-7 22-28 Monday Thursday Sunday
Even 8-14 29-31 Tuesday Friday
yy/mm/dd
X Each day Wednesday Saturday
Weekday Start date
X Each day
Start weekday
Wednesday Saturday Calendar 1 Function 1
X Inactive Date range
Date Start date
X Each day Wednesday Saturday
Stop date Weekday Start date
Start weekday
Monday Thursday Sunday
Tuesday Friday
Date Weekday
Inactive Date range
Date Weekday
yy/mm/dd
Start weekday
Date range Start date
Date Weekday Calendar 2
yy/mm/dd Wednesday Saturday
Stop date Stop weekday
Date Weekday X Calendar 2
yy/mm/dd Wednesday Saturday
Date range Start date Start weekday
Adjusted value
Monday Thursday Sunday
Tuesday Friday
Each day Wednesday Saturday
Monday Thursday Sunday
Tuesday Friday
Mon 1-12 Each 15-21 Each day Wednesday Saturday
Odd Day 1-7 22-28 Monday Thursday Sunday
Even 8-14 29-31 Tuesday Friday
yy/mm/dd yy/mm/dd
X Each day Wednesday Saturday
Swegon reserves the right to alter specifications.
Monday Thursday Sunday
Tuesday Friday
www.swegon.com
13
GB.GOLDSKE.150520
Function
Factory-preset value
X Inactive
Function 2
Date range Date Start date Start weekday
X Each day
X Each day Wednesday Saturday X Inactive Date range
Function 3
X Each day
Monday Thursday Sunday
Tuesday Friday
Each day Wednesday Saturday
Monday Thursday Sunday
Tuesday Friday
Mon 1-12 Each 15-21 Each day Wednesday Saturday Inactive Date range
Odd Day 1-7 22-28 Monday Thursday Sunday Date Weekday
Even 8-14 29-31 Tuesday Friday
Monday Thursday Sunday Date Weekday
Tuesday Friday
Monday Thursday Sunday
Tuesday Friday
Each day Wednesday Saturday
Monday Thursday Sunday
Tuesday Friday
Mon 1-12 Each 15-21 Each day Wednesday Saturday
Odd Day 1-7 22-28 Monday Thursday Sunday
Even 8-14 29-31 Tuesday Friday
Yy/mm/dd Yy/mm/dd
Start weekday
X Each day Wednesday Saturday
14
Date Weekday
Yy/mm/dd Wednesday Saturday
Date range Start date Stop date Weekday Start date
Inactive Date range
Yy/mm/dd Yy/mm/dd
Start weekday
Date Start date Start weekday
Date Weekday
Yy/mm/dd
Wednesday Saturday Date range Start date Stop date Weekday Start date
Adjusted value
www.swegon.com
Monday Thursday Sunday
Tuesday Friday
Swegon reserves the right to alter specifications.
GB.GOLDSKE.150520
Function
Factory-preset value
X Inactive
Function 4
Date range Date Start date Start weekday
X Each day
X Each day Wednesday Saturday X Inactive Date range
Function 5
Start weekday
Date Weekday
Monday Thursday Sunday
Tuesday Friday
Each day Wednesday Saturday
Monday Thursday Sunday
Tuesday Friday
Mon 1-12 Each 15-21 Each day Wednesday Saturday Inactive Date range
Odd Day 1-7 22-28 Monday Thursday Sunday Date Weekday
Even 8-14 29-31 Tuesday Friday
Monday Thursday Sunday Date Weekday
Tuesday Friday
Monday Thursday Sunday
Tuesday Friday
Each day Wednesday Saturday
Monday Thursday Sunday
Tuesday Friday
Mon 1-12 Each 15-21 Each day Wednesday Saturday
Odd Day 1-7 22-28 Monday Thursday Sunday
Even 8-14 29-31 Tuesday Friday
Yy/mm/dd
X Each day Wednesday Saturday
Date range Start date Stop date Weekday Start date
Inactive Date range
Yy/mm/dd Yy/mm/dd
Start weekday
Date Start date Start weekday
Date Weekday
Yy/mm/dd Wednesday Saturday
Date range Start date Stop date Weekday Start date
Adjusted value
Yy/mm/dd Yy/mm/dd
X Each day Wednesday Saturday
Swegon reserves the right to alter specifications.
Monday Thursday Sunday
Tuesday Friday
www.swegon.com
15
GB.GOLDSKE.150520
Function
Factory-preset value
X Inactive
Function 6
Date range Date Start date Start weekday
X Each day
X Each day Wednesday Saturday X Inactive Date range
Function 7
X Each day
Monday Thursday Sunday
Tuesday Friday
Each day Wednesday Saturday
Monday Thursday Sunday
Tuesday Friday
Mon 1-12 Each 15-21 Each day Wednesday Saturday Inactive Date range
Odd Day 1-7 22-28 Monday Thursday Sunday Date Weekday
Even 8-14 29-31 Tuesday Friday
Monday Thursday Sunday Date Weekday
Tuesday Friday
Monday Thursday Sunday
Tuesday Friday
Each day Wednesday Saturday
Monday Thursday Sunday
Tuesday Friday
Mon 1-12 Each 15-21 Each day Wednesday Saturday
Odd Day 1-7 22-28 Monday Thursday Sunday
Even 8-14 29-31 Tuesday Friday
Yy/mm/dd Yy/mm/dd
Start weekday
X Each day Wednesday Saturday
16
Date Weekday
Yy/mm/dd Wednesday Saturday
Date range Start date Stop date Weekday Start date
Inactive Date range
Yy/mm/dd Yy/mm/dd
Start weekday
Date Start date Start weekday
Date Weekday
Yy/mm/dd Wednesday Saturday
Date range Start date Stop date Weekday Start date
Adjusted value
www.swegon.com
Monday Thursday Sunday
Tuesday Friday
Swegon reserves the right to alter specifications.
GB.GOLDSKE.150520
Function
Factory-preset value
X Inactive
Function 8
Date range Date Start date Start weekday
X Each day
X Each day Wednesday Saturday X Inactive Date range
Function 9
Start weekday
Date Weekday
Monday Thursday Sunday
Tuesday Friday
Each day Wednesday Saturday
Monday Thursday Sunday
Tuesday Friday
Mon 1-12 Each 15-21 Each day Wednesday Saturday Inactive Date range
Odd Day 1-7 22-28 Monday Thursday Sunday Date Weekday
Even 8-14 29-31 Tuesday Friday
Monday Thursday Sunday Date Weekday
Tuesday Friday
Monday Thursday Sunday
Tuesday Friday
Each day Wednesday Saturday
Monday Thursday Sunday
Tuesday Friday
Mon 1-12 Each 15-21 Each day Wednesday Saturday
Odd Day 1-7 22-28 Monday Thursday Sunday
Even 8-14 29-31 Tuesday Friday
Yy/mm/dd
X Each day Wednesday Saturday
Date range Start date Stop date Weekday Start date
Inactive Date range
Yy/mm/dd Yy/mm/dd
Start weekday
Date Start date Start weekday
Date Weekday
Yy/mm/dd Wednesday Saturday
Date range Start date Stop date Weekday Start date
Adjusted value
Yy/mm/dd Yy/mm/dd
X Each day Wednesday Saturday
Swegon reserves the right to alter specifications.
Monday Thursday Sunday
Tuesday Friday
www.swegon.com
17
GB.GOLDSKE.150520
Function
Factory-preset value
X Inactive
Function 10
Date range Date Start date Start weekday
X Each day
X Each day Wednesday Saturday
Calendar 2 Function 1
X Inactive Date range
X Each day
Monday Thursday Sunday
Tuesday Friday
Each day Wednesday Saturday
Monday Thursday Sunday
Tuesday Friday
Mon 1-12 Each 15-21 Each day Wednesday Saturday
Odd Day 1-7 22-28 Monday Thursday Sunday
Even 8-14 29-31 Tuesday Friday
Monday Thursday Sunday
Tuesday Friday
Date Weekday
Inactive Date range
Date Weekday
Monday Thursday Sunday
Tuesday Friday
Each day Wednesday Saturday
Monday Thursday Sunday
Tuesday Friday
Mon 1-12 Each 15-21 Each day Wednesday Saturday
Odd Day 1-7 22-28 Monday Thursday Sunday
Even 8-14 29-31 Tuesday Friday
Yy/mm/dd Yy/mm/dd
Start weekday
X Each day Wednesday Saturday
18
Date Weekday
Yy/mm/dd Wednesday Saturday
Date range Start date Stop date Weekday Start date
Inactive Date range
Yy/mm/dd Yy/mm/dd
Start weekday
Date Start date Start weekday
Date Weekday
Yy/mm/dd Wednesday Saturday
Date range Start date Stop date Weekday Start date
Adjusted value
www.swegon.com
Monday Thursday Sunday
Tuesday Friday
Swegon reserves the right to alter specifications.
GB.GOLDSKE.150520
Function
Factory-preset value
X Inactive
Function 2
Date range Date Start date Start weekday
X Each day
X Each day Wednesday Saturday X Inactive Date range
Function 3
Start weekday
Date Weekday
Monday Thursday Sunday
Tuesday Friday
Each day Wednesday Saturday
Monday Thursday Sunday
Tuesday Friday
Mon 1-12 Each 15-21 Each day Wednesday Saturday Inactive Date range
Odd Day 1-7 22-28 Monday Thursday Sunday Date Weekday
Even 8-14 29-31 Tuesday Friday
Monday Thursday Sunday Date Weekday
Tuesday Friday
Monday Thursday Sunday
Tuesday Friday
Each day Wednesday Saturday
Monday Thursday Sunday
Tuesday Friday
Mon 1-12 Each 15-21 Each day Wednesday Saturday
Odd Day 1-7 22-28 Monday Thursday Sunday
Even 8-14 29-31 Tuesday Friday
Yy/mm/dd
X Each day Wednesday Saturday
Date range Start date Stop date Weekday Start date
Inactive Date range
Yy/mm/dd Yy/mm/dd
Start weekday
Date Start date Start weekday
Date Weekday
Yy/mm/dd Wednesday Saturday
Date range Start date Stop date Weekday Start date
Adjusted value
Yy/mm/dd Yy/mm/dd
X Each day Wednesday Saturday
Swegon reserves the right to alter specifications.
Monday Thursday Sunday
Tuesday Friday
www.swegon.com
19
GB.GOLDSKE.150520
Function
Factory-preset value
X Inactive
Function 4
Date range Date Start date Start weekday
X Each day
X Each day Wednesday Saturday X Inactive Date range
Function 5
X Each day
Monday Thursday Sunday
Tuesday Friday
Each day Wednesday Saturday
Monday Thursday Sunday
Tuesday Friday
Mon 1-12 Each 15-21 Each day Wednesday Saturday Inactive Date range
Odd Day 1-7 22-28 Monday Thursday Sunday Date Weekday
Even 8-14 29-31 Tuesday Friday
Monday Thursday Sunday Date Weekday
Tuesday Friday
Monday Thursday Sunday
Tuesday Friday
Each day Wednesday Saturday
Monday Thursday Sunday
Tuesday Friday
Mon 1-12 Each 15-21 Each day Wednesday Saturday
Odd Day 1-7 22-28 Monday Thursday Sunday
Even 8-14 29-31 Tuesday Friday
Yy/mm/dd Yy/mm/dd
Start weekday
X Each day Wednesday Saturday
20
Date Weekday
Yy/mm/dd Wednesday Saturday
Date range Start date Stop date Weekday Start date
Inactive Date range
Yy/mm/dd Yy/mm/dd
Start weekday
Date Start date Start weekday
Date Weekday
Yy/mm/dd Wednesday Saturday
Date range Start date Stop date Weekday Start date
Adjusted value
www.swegon.com
Monday Thursday Sunday
Tuesday Friday
Swegon reserves the right to alter specifications.
GB.GOLDSKE.150520
Function
Factory-preset value
X Inactive
Function 6
Date range Date Start date Start weekday
X Each day
X Each day Wednesday Saturday X Inactive Date range
Function 7
Start weekday
Date Weekday
Monday Thursday Sunday
Tuesday Friday
Each day Wednesday Saturday
Monday Thursday Sunday
Tuesday Friday
Mon 1-12 Each 15-21 Each day Wednesday Saturday Inactive Date range
Odd Day 1-7 22-28 Monday Thursday Sunday Date Weekday
Even 8-14 29-31 Tuesday Friday
Monday Thursday Sunday Date Weekday
Tuesday Friday
Monday Thursday Sunday
Tuesday Friday
Each day Wednesday Saturday
Monday Thursday Sunday
Tuesday Friday
Mon 1-12 Each 15-21 Each day Wednesday Saturday
Odd Day 1-7 22-28 Monday Thursday Sunday
Even 8-14 29-31 Tuesday Friday
Yy/mm/dd
X Each day Wednesday Saturday
Date range Start date Stop date Weekday Start date
Inactive Date range
Yy/mm/dd Yy/mm/dd
Start weekday
Date Start date Start weekday
Date Weekday
Yy/mm/dd Wednesday Saturday
Date range Start date Stop date Weekday Start date
Adjusted value
Yy/mm/dd Yy/mm/dd
X Each day Wednesday Saturday
Swegon reserves the right to alter specifications.
Monday Thursday Sunday
Tuesday Friday
www.swegon.com
21
GB.GOLDSKE.150520
Function
Factory-preset value
X Inactive
Function 8
Date range Date Start date Start weekday
X Each day
X Each day Wednesday Saturday X Inactive Date range
Function 9
X Each day
Monday Thursday Sunday
Tuesday Friday
Each day Wednesday Saturday
Monday Thursday Sunday
Tuesday Friday
Mon 1-12 Each 15-21 Each day Wednesday Saturday Inactive Date range
Odd Day 1-7 22-28 Monday Thursday Sunday Date Weekday
Even 8-14 29-31 Tuesday Friday
Monday Thursday Sunday Date Weekday
Tuesday Friday
Monday Thursday Sunday
Tuesday Friday
Each day Wednesday Saturday
Monday Thursday Sunday
Tuesday Friday
Mon 1-12 Each 15-21 Each day Wednesday Saturday
Odd Day 1-7 22-28 Monday Thursday Sunday
Even 8-14 29-31 Tuesday Friday
Yy/mm/dd Yy/mm/dd
Start weekday
X Each day Wednesday Saturday
22
Date Weekday
Yy/mm/dd Wednesday Saturday
Date range Start date Stop date Weekday Start date
Inactive Date range
Yy/mm/dd Yy/mm/dd
Start weekday
Date Start date Start weekday
Date Weekday
Yy/mm/dd Wednesday Saturday
Date range Start date Stop date Weekday Start date
Adjusted value
www.swegon.com
Monday Thursday Sunday
Tuesday Friday
Swegon reserves the right to alter specifications.
GB.GOLDSKE.150520
Function
Factory-preset value
X Inactive
Function 10
Date range Date Start date Start weekday
X Each day
Inactive Date range
Date Weekday
Monday Thursday Sunday
Tuesday Friday
Each day Wednesday Saturday
Monday Thursday Sunday
Tuesday Friday
Mon 1-12 Each 15-21 Each day Wednesday Saturday
Odd Day 1-7 22-28 Monday Thursday Sunday
Even 8-14 29-31 Tuesday Friday
Yy/mm/dd Yy/mm/dd
X Each day
Start weekday
Wednesday Saturday Prolonged operation Ext. low speedt Ext. high speed
Date Weekday
Yy/mm/dd Wednesday Saturday
Date range Start date Stop date Weekday Start date
Adjusted value
hour:min. hour:min.
Monday Thursday Sunday
Tuesday Friday
00:00 00:00
Filters
Function
Factory-preset value
Adjusted value
Filters X Inactive
Pre-filters
Supply air Supply and extract air X Disabled Supply air Supply and extract air X Off On
Internal filter (GOLD SD) End filter Alarm limits Supply air pre-filter Extract air pre-filter Supply air internal filter Extract air internal filter Supply air end filter
Pa Pa Pa Pa Pa
Extract air Extract air
Disabled Supply air Supply and extract air Disabled Supply air Supply and extract air On Off
Extract air Extract air
100 100 100 100 100
Language
Function
Factory-preset value
Adjusted value
Language Language
English
Swegon reserves the right to alter specifications.
www.swegon.com
23
GB.GOLDSKE.150520
Alarm settings
Function
Factory-preset value
Adjusted value
Alarm priorities Fire alarms Internal fire alarm Inernal fire alarm reset Internal fire alarm after cool External fire alarm 1 reset External fire alarm 1 after cool External fire alarm 2 reset External fire alarm 2 after cool Fan operation at internal fire alarm
On
X Manual Enabled
X Manual Enabled
X Manual Enabled
X Disabled Extract air
Supply air fan at internal fire alarm Extract air fan at internal fire alarm Fan operation at external fire alarm 1
% %
100 100
X Disabled Extract air
Supply air fan at external fire alarm 1 Extract air fan at external fire alarm 1 Fan operation at external fire alarm 2
% %
100 100
X Disabled Extract air
Supply air fan at external fire alarm 2 Extract air fan at external fire alarm 2 Order of priority:
% %
100 100
X Ext. fire alarm 1 Int. fire alarm
External alarms External alarm 1 reset External alarm 1 after cool External alarm 1 input External alarm 1 delay time External alarm 2 reset External alarm 2 after cool External alarm 2 input External alarm 2 delay time Temperature protection Temperature protection Alarm delay Alarm limit Temperature alarm limits Pre-heat below set point Supply air below set point Supply air above set point Extract air below alarm limit Outdoor temperature limit stop Service period Service period Alarm priority See alarm list
24
www.swegon.com
Manual Enabled
X Closed circuit s
10
s
Manual Enabled X Closed circuit 10
s °C
30 7
K K K °C °C
5.0 5.0 7.0 12.0 5.0
mon
12
On
X Off
On Manual Enabled Manual Enabled Manual Enabled Disabled Extract air
Off Auto Disabled Auto Disabled Auto Disabled Supply air Supply and extract air
Supply air Supply and extract air
Disabled Extract air
Supply air Supply and extract air
Supply air Supply and extract air
Disabled Extract air
Supply air Supply and extract air
Ext. fire alarm 2 Automatic
Ext. fire alarm 1 Int. fire alarm
Ext. fire alarm 2 Automatic
Manual
Auto
Enabled Closed circuit
Disabled Open circuit
Manual Enabled Closed circuit
Auto Disabled Open circuit
On
Off
Auto X Inactive Auto X Inactive Auto X Inactive Supply air Supply and extract air
X Auto X Inactive Open circuit
X Auto X Inactive Open circuit
X Off
Swegon reserves the right to alter specifications.
GB.GOLDSKE.150520
Log
Function
Factory-preset value
Adjusted value
Log X On
Log file period Log sender active Live mode
Off X Off FTP
On
X E-mail
On On E-mail E-mail and FTP
E-mail and FTP
Off Off FTP
Air handling unit
Function
Factory-preset value
Adjusted value
Air handling unit Type of air handling unit
GOLD RX/PX/CX Name Fan position 1 Flowchart, fan position supply air GOLD SD Name Flowchart, fan position VOC/CO2 sensor VOC sensor, operating mode CO2 unit
Type of air handling unit supplied, except the GOLD SD extract air handling unit
X Extract air
GOLD PX GOLD SD Supply air GOLD SD Supply air+CX GOLD SD Supply air+Extract air+CX
Upper level
X Bottom
Extract air Upper level
Supply air Bottom
Upper level
X Bottom
Upper level
Bottom
X Inactive
Supply air
GOLD RX GOLD CX GOLD SD Extract air GOLD SD Supply air+Extract air
Monitoring only Monitoring and regulation X% ppm
Swegon reserves the right to alter specifications.
Inactive Monitoring only Monitoring and regulation % ppm
www.swegon.com
25
GB.GOLDSKE.150520
Heat
Function
Factory-preset value
Adjusted value
Heat Pre-heat Pre-heat Pre-heat set point Periodic operation of pump Periodic operation of valve Periodic operation interval Periodic operation time Alarm input
°C
h min
%
h min
Re-heat Air heater for hot water Periodic operation of pump Periodic operation of valve Periodic operation interval Periodic operation time Xzone Xzone Air heater for hot water Periodic operation of pump Periodic operation of valve Periodic operation interval Periodic operation time Alarm input Electrical heaters After cool Season Heat Season Heat
Extra regulation sequence 26
www.swegon.com
On
Off
X On X On
Off Off
On On
Off Off
24 3
X Inactive
Al. on open cont. Contactor function
X Inactive
Heat Heat and cool X Off X Off
Cool On On 100
X On X On
%
h min
Al.on closed cont. X Inactive Cool On On 100
X On X On
Al. on closed cont.
h min
Disabled Cool On On
Heat Heat and cool Off Off
On On
Off Off
Al. on open cont. Contactor function Heat Heat and cool X Off X Off Off Off
Inactive Al. on closed cont. Disabled Cool On On On On
Al. on open cont. Contactor function Heat Heat and cool Off Off Off Off
Al. on open cont. Contactor function
Inactive Al. on closed cont.
Al. on open cont. Contactor function
X On X On
Off Off
On On
Off Off
On
X Off
On
Off
X On X On
Off Off
On On
Off Off
24 3
24 3
X Inactive
Al. on closed cont.
min
Al. on open cont. Contactor function
24 3
X Inactive
h min
Off Off
Inactive Al.on closed cont.
24 3
X Inactive
Extra regulation sequence 2 Inverted output 10 - 0 V Recirculation control Max. output signal Periodic operation of pump Periodic operation of valve Periodic operation interval Periodic operation time Pump alarm
X Off
Al. on closed cont.
Extra regulation sequence Extra regulation sequence 1 Inverted output 10 - 0 V Recirculation control Max. output signal Periodic operation of pump Periodic operation of valve Periodic operation interval Periodic operation time Pump alarm
On 5
Al. on open cont. Contactor function
Inactive Al. on closed cont.
Al. on open cont. Contactor function
3
X Disabled Extra regul. 1 seq. closed cont. On
Extra regul.1 seq.closed cont. Extra regul.sequence 1 manual X Off
Disabled Extra regul.1 seq.closed cont. On
Extra regul. 1 seq. closed cont. Extra regul. 1 sequence manual Off
Swegon reserves the right to alter specifications.
GB.GOLDSKE.150520
Cool
Function
Factory-preset value
Adjusted value
Cool Extra regulation sequence Extra regulation sequence 1 Inverted output signal Recirculation control Max output signal Periodic operation of pump Periodic operation of valve Periodic operation interval Periodic operation time Pump alarm
X Inactive
%
h min
X On X On
Cool
Off Off
%
h min
Ala. on open cont. Al. on closed cont. Contactor function X Inactive Heat Cool Heat and cool X Off On X Off On 100
X On X On
Off Off
Al. on open cont. Contactor function
X Disabled
1-step
2-step
X On X On X On
Off Off Off
1-step
2-step
Off Off Off
X Disabled COOL DX Top min
Heat
Cool
Off Off Off Off
Inactive Al. on closed cont.
Disabled 3-step, binary
Al. on open cont. Contactor function
1-step
2-step
Off Off Off
Disabled 3-step, binary On On On
1-step
2-step
Off Off Off
24 3
Al. on closed cont. X Inactive Al. on closed cont.
COOL DX COOL DX Delay time Restart time
X On X On X On
X Inactive
Alarm input 2
Disabled Heat and cool On On
Al. on open cont. Contactor function
24 3
X Disabled
h min
Inactive Alarm on closed cont.
On On On
3-step, binary Air cooler for water Periodic operation pump 1 Periodic operation pump 2 Periodic operation of valve Periodic operation interval Periodic operation time Alarm input 1
Off Off
24 3
Al. on closed cont.
h min
Cool
Off Off
On On
3-step, binary Air cooler for water Periodic operation pump 1 Periodic operation pump 2 Periodic operation of valve Periodic operation interval Periodic operation time Xzone DX air cooler Cool
Heat
24 3
X Inactive
Cool DX air cooler Cool
Disabled Heat and cool On On On On
X Inactive
Extra regulation sequence 2 Inverted output signal Recirculation control Max output signal Periodic operation of pump Periodic operation of valve Periodic operation interval Periodic operation time Pump alarm
Heat Heat and cool X Off On X Off On 100
Al. on open cont. Contactor function Al. on open cont. Contactor function
Economy
Comfort
Inactive Al. on open cont. Alarm on closed cont. Contactor function Inactive Al. on open cont. Ala. on closed cont. Contactor function Disabled
Economy
Comfort
COOL DX Top
5
Swegon reserves the right to alter specifications.
www.swegon.com
27
GB.GOLDSKE.150520
Step switch time Stop/start time Outdoor air limits Step 1 Step 2 Step 3 Air flow limits Cooling, 0-10 V Supply air 0-10 V Extract air 0-10 V Cooling, On/Off Supply air, On/Off, step 1 Extract air, On/Off, step 1 Supply air, On/Off, step 2 Extract air, On/Off, step 2 Supply air, On/Off, step 3 Extract air, On/Off, step 3
min min
5 5
°C °C °C
15 18 20
25% of max. airflow for air handling unit 25% of max. airflow for air handling unit 25% of max. airflow for air handling unit 25% of max. airflow for air handling unit 25% of max. airflow for air handling unit 25% of max. airflow for air handling unit 25% of max. airflow for air handling unit 25% of max. airflow for air handling unit
Heat exchange
Function
Factory-preset value
Adjusted value
Heat/Cooling energy recovery Carry over control Carry over control Defrost Defrost Defrost, limit value Pa Calibration Calibration/Optimization (PX) Calibration Bypass optimization
28
www.swegon.com
On
X Off
On
Off
On
X Off
On
Off
On
X Off
On
Off
On On
X Off X Off
On On
Off Off
50
Swegon reserves the right to alter specifications.
GB.GOLDSKE.150520
SMART Link
Function
Factory-preset value
Adjusted value
SMART Link X Disabled
Type of unit
Water, chiller DX, heat pump DX, reversible Water Heated water (set point) Heated water diff Chilled water (set point) Chilled water diff Outdoor air limit (not applicable to the chiller) Optimize Cooling optim, regulation speed Heating optim. regulation speed Valve limit, lower Valve limit, upper Delay AQUA Link Pump alarm
°C K °C K °C
40 3 12 2 -30
K/min
On 0.3
K/min
0.3
% % s
75 95 60 On
X Disabled Al. on open cont.
DX (Celest+) Amount of units Comfort mode, duration Outdoor air limit (not applicable to the chiller) Defrost delay Dead band, supply air temp. Stabilization time
min °C
1 30 -30
s K
180 1,0
s
240
Swegon reserves the right to alter specifications.
Water, heat pump Water, reversible DX, chiller
Disabled Water, chiller DX, heat pump DX, reversible
Water, heat pump Water, reversible DX, chiller
X Off
On
Off
X Off
On Disabled Al. on open cont.
Off Al. on closed cont. Contactor function
Al. on closed cont. Contactor function
www.swegon.com
29
GB.GOLDSKE.150520
Humidity
Function
Factory-preset value
Adjusted value
Air humidity Humidifying Humidifying
X Disabled
On/Off
0 - 10 V
X Supply air
Location, regulating humidity sensor Evaporative Start limit Stop limit Steam Set point Max. supply air Dehumidification Dehumidification Supply air, relative humidity Extract air, relative humidity Humidifyer alarm Alarm input
%RH %RH
40 45
%RH %RH
30 80
Extract air
X Inactive %RH
Extract air 50
%RH
50
X Disabled Open circuit
Disabled 0 - 10 V Supply air
Supply air
Inactive Extract air
Closed circuit Contactor function
Disabled Open circuit
On/Off Extract air
Supply air
Closed circuit Contactor function
ReCO2
Function
Factory-preset value
Adjusted value
ReCO2 CO2/VOC, operating mode Temperature mode
X Inactive
CO2/VOC CO2/VOC and air flow boost X Inactive Heat sequence Cool sequence
CO2/VOC Set point CO2, set point VOC, set point Min. outdoor air Min. exhaust air Calibration Temperature Min. outdoor air Min. exhaust air Calibration
30
www.swegon.com
% ppm ppm
Heat and cool sequence
Inactive CO2/VOC CO2/VOC and air flow boost Disabled Heat sequence Cool sequence
Heat and cool sequence
On
Off
On
Off
50 1000 1500 25% of max. airflow for air handling unit 25% of max. airflow for air handling unit On
X Off
25% of max. airflow for air handling unit 25% of max. airflow for air handling unit On
X Off
Swegon reserves the right to alter specifications.
GB.GOLDSKE.150520
All Year Comfort
Function
Factory-preset value
Adjusted value
All Year Comfort X Disabled
Function
Heated water Chilled water Chilled water °C Outdoor temp. compensation Outdoor temp X1 °C Outdoor temp X2 °C Outdoor temp X3 °C Outdoor temp X4 °C Chilled water temp Y1 °C Chilled water temp Y2 °C Chilled water temp Y3 °C Chilled water temp Y4 °C Outdoor temp. for pump start °C Outdoor temp. for pump stop °C Room temp. compensation Room temp. set point °C Room temp. P-band K Room comp. night block Night compensation Reduction, night K Time channel 1 start of night hour:min. Time channel 1 end of night hour:min. Time channel 1 period
Dew point compensation Air flow compensation Periodic operation of pump Periodic operation of valve Periodic operation interval Periodic operation time Pump alarm
Valve alarm
Swegon reserves the right to alter specifications.
Disabled Heated water
Chilled water Chilled and heated water
14 On
X Off
On
Off
On
X Off
On
Off
On On
X Off X Off
On On
Off Off
Disabled Tuesday Thursday Saturday Mon.-Fri. Sat.-Sun. On On On On
Monday Wednesday Friday Sunday Mon.-Sun.
10 20 25 30 22 18 14 12 10 7 21 5
2 00:00 00:00
X Inactive Tuesday Thursday Saturday Mon.-Fri. Sat.-Sun. On On
h min
Chilled water Chilled and heated water
Monday Wednesday Friday Sunday Mon.-Sun.
X Off X Off
X On
Off
On
X Off
Off Off Off Off
24 3
X Inactive
Al. on closed cont. Alarm on open contact Contactor function X Off On
Inactive Al. on closed cont. Alarm on open contact Contactor function On Off
www.swegon.com
31
GB.GOLDSKE.150520
Function Heated water Heated water Outdoor temp. compensation Outdoor temp X1 Outdoor temp X2 Outdoor temp X3 Outdoor temp X4 Heated water temp Y1 Heated water temp Y2 Heated water temp Y3 Heated water temp Y4 Outdoor temp. for pump start Outdoor temp. for pump stop Room temp. compensation Room temp. set point Room temp. P-band Room comp. night block Night compensation Reduction, night Time channel 2 start of night Time channel 2 end of night Time channel 2 period
Factory-preset value °C
30 On -20 0 5 15 40 30 20 15 15 18
X Off
On
Off
°C °C °C °C °C °C °C °C °C °C
On
X Off
On
Off
°C K
21 5 On On
X Off X Off
On On
Off Off
Monday Wednesday Friday
Disabled Tuesday Thursday
Monday Wednesday Friday
Sunday Mon.-Sun.
Saturday Mon.-Fri. Sat.-Sun. On On On
Sunday Mon.-Sun.
Inactive
Al. on closed cont.
K hour:min. hour:min.
-2 00:00 00:00
X Inactive Tuesday Thursday
Air flow compensation Periodic operation of pump Periodic operation of valve Periodic operation interval Periodic operation time Pump alarm
Valve alarm
Adjusted value
Saturday Mon.-Fri. Sat.-Sun. On
h min
X Off
X On
Off
On
X Off
Off Off Off
24 3
X Inactive
Al. on closed cont.
Alarm on open contact Contactor function X Off On
Alarm on open contact Contactor function On Off
MIRU Control
Function
Factory-preset value
MIRU Control
See the commissioning report for MIRU Control
32
www.swegon.com
Adjusted value
Swegon reserves the right to alter specifications.
GB.GOLDSKE.150520
Inputs / Outputs
Function
Factory-preset value
Adjusted value
Inputs / Outputs External operation, module 3 Digital output 1, operating mode
Inactive
Digital output 2, operating mode
Inactive
Digital Input 1 Digital Input 2 Analogue Input 1
X Disabled
Analogue Input 2
Stop AYC heating water
X Disabled Stop AYC heating water See Section 6.4.19
See Section 6.4.19
Swegon reserves the right to alter specifications.
Alarm reset Stop AYC chilled water Alarm reset Stop AYC chilled water
Inactive AHU in auto op. mode AHU in low speed op. mode
Air handling unit in op. AHU in man. op. mode AHU in high speed op. mode
A alarm Damper relay Heat exchanger, defrost. Reheat, cap. red. Morning Boost Air flow down regulation Extra reg. sequ. 2, heating Extra reg. sequ. 2, cooling Cooling Boost Supply air fan in operation Internal fire alarm tripped External fire alarm 2 Any fire alarm Inactive AHU in auto op. mode AHU in low speed op. mode
B-alarm Heat exchange Re-heat Heating boost Intermittent night op. Extra reg. sequ.1 , heating Extra reg. sequ. 1, cooling Cool Summer night cool Extract air fan in operation External fire alarm 1 External fire alarms 1 and 2
A alarm Damper relay Heat exchanger, defrost. Reheat, cap. red. Morning Boost Air flow down regulation Extra reg. sequ. 2, heating Extra reg. sequ. 2, cooling Cooling Boost Supply air fan in operation Internal fire alarm tripped External fire alarm 2 Any fire alarm Disabled Stop AYC heating water Disabled Stop AYC heating water Disabled Set point displacement, supply air
B-alarm Heat exchange Re-heat Heating boost Intermittent night op. Extra reg. sequ.1 , heating Extra reg. sequ. 1, cooling Cool Summer night cool Extract air fan in operation External fire alarm 1 External fire alarms 1 and 2
Disabled Set point displacement, supply air
Set point displacement Set point displacement, extract air
Air handling unit in op. AHU in man. op. mode AHU in high speed op. mode
Alarm reset Stop AYC cooling water Alarm reset Stop AYC chilled water Set point displacement Set point displacement, extract air
www.swegon.com
33
GB.GOLDSKE.150520
Function
Factory-preset value
Adjusted value
Inputs / Outputs External operation, module 6 Digital output 1, operating mode
Inactive
Digital output 2, operating mode
Inactive
Digital Input 1 Digital Input 2 Analogue Input 1
X Disabled
Analogue Input 2
34
Stop AYC heating water
X Disabled Stop AYC heating water See Section 6.4.19
See Section 6.4.19
www.swegon.com
Alarm reset Stop AYC chilled water Alarm reset Stop AYC chilled water
Inactive AHU in auto op. mode AHU in low speed op. mode
Air handling unit in op. AHU in man. op. mode AHU in high speed op. mode
A alarm Damper relay Heat exchanger, defrost. Reheat, cap. red. Morning Boost Air flow down regulation Extra reg. sequ. 2, heating Extra reg. sequ. 2, cooling Cooling Boost Supply air fan in operation Internal fire alarm tripped External fire alarm 2 Any fire alarm Inactive AHU in auto op. mode AHU in low speed op. mode
B-alarm Heat exchange Re-heat Heating boost Intermittent night op. Extra reg. sequ.1 , heating Extra reg. sequ. 1, cooling Cool Summer night cool Extract air fan in operation External fire alarm 1 External fire alarms 1 and 2 Air handling unit in op. AHU in man. op. mode AHU in high speed op. mode
A alarm Damper relay Heat exchanger, defrost. Reheat, cap. red. Morning Boost Air flow down regulation Extra reg. sequ. 2, heating Extra reg. sequ. 2, cooling Cooling Boost Supply air fan in operation Internal fire alarm tripped External fire alarm 2 Any fire alarm Disabled Stop AYC heating water Disabled Stop AYC heating water Disabled Set point displacement, supply air
B-alarm Heat exchange Re-heat Heating boost Intermittent night op. Extra reg. sequ.1 , heating Extra reg. sequ. 1, cooling Cool Summer night cool Extract air fan in operation External fire alarm 1 External fire alarms 1 and 2
Disabled Set point displacement, supply air
Set point displacement Set point displacement, extract air
Alarm reset Stop AYC cooling water Alarm reset Stop AYC chilled water Set point displacement Set point displacement, extract air
Swegon reserves the right to alter specifications.
GB.GOLDSKE.150520
Communication
Function
Factory-preset value
Adjusted value
Communication External Port B DHCP IP address Net mask Standard value GATEWAY Primary DNS Secondary DNS Wireless LAN Wireless LAN SSID Password IP address Net mask Channel, frequency band E-mail SMTP-server SMTP server address SMTP port number SMTP username SMTP password Encryption E-mail user E-mail reply path EIA-485 Protocol
On 10.200.1.1 255.255.255.0 0.0.0.0 0.0.0.0 0.0.0.0
X Off
On
Off
On GOLD 123456789 192.168.234.1 255.255.255.0 5
X Off
On
Off
External
Internal
X External 25
Baudrate Parity Stopbits Modbus ID/Metasys ID/PLA ELA Shortest feedback delay ms Modbus TCP Port number Approved client IP address Approved client netmask BACnet IP Network number Ext. B Network number Int. A. Device ID Port number EXOline TCP Port number PLA ELA Operation level communication Operation level
Port number
Internal
On
X Off
On
Off
Inactive EXOline LON 4800 19200
X Modbus
Disabled EXOline LON 4800 19200 None
Modbus Metasys N2 Open
Disabled Low speed Normal Stop
Total Stop High Speed Extended Normal Stop
X None
Metasys N2 Open
X 9600 38400 Even
odd
9600 38400 Even
odd
2 1 1 0 502 0.0.0.0 0.0.0.0 0 0 0 47808 26486 1 1
X Disabled Low speed Normal Stop 26486
Swegon reserves the right to alter specifications.
Total stop High Speed Extended Normal Stop
www.swegon.com
35
GB.GOLDSKE.150520
Users
Function
Factory-preset value
Adjusted value
Users Demand password user
On
X Off
On
Off
IQnavigator
Function
Factory-preset value
Adjusted value
IQnavigator Connect to IQlogic
X Direct Static IP
IQnavigator IP address IQnavigator Netmask Pre-selected IQnavigator gateway IQlogic IP address Brightness mode Button sound effects Volume
36
www.swegon.com
X Auto adjust Medium On
DHCP Wireless
Low High
X Off
Direct
DHCP
Static IP
Wireless
Auto adjust Medium On
Low High Off
3
Swegon reserves the right to alter specifications.
GB.GOLDSKE.150520
Alarm No.
Factory-preset value Priority Function
0 = Blocked A = Type A alarm B = Type B alarm A1) A1) A1) A B A A1)
Effect 1 = Stop
3:3 3:4 3:5 3:6 3:7 3:8 4:1
Preheat, frost guard tripped Preheat, frost guard temperature sensor defective Preheat, temperature sensor defective Pre-heat, valve monitoring tripped Pre-heat, temperature below set point alarm limit Pre-heat, alarm input tripped Extra regulation sequence 1, I/O module no. E communication error
A1) A1) A B A A A
1 1 03) 03) 03) 0 03)
4:2
Extra regulation sequence 1, overheating protection for electric air heater tripped Extra regulation sequence 1, frost guard tripped Extra regulation sequence 1, fost guard temperature sensor defective
A1)
03)
A1) A1)
1 1
Extra regulation sequence 1, valve monitoring tripped Extra regulation sequence 1, alarm input tripped Extra regulation sequence 1, temperature protection via communication, communication error 4:9 Extra regulation sequence 2, I/O module no. F communication error 4:10 Extra regulation sequence 2, overheating protection for electric air heater tripped
B A B
03) 0 0
A
03)
A1)
03)
4:11 Extra regulation sequence 2, frost guard tripped 4:12 Extra regulation sequence 2, fost guard temperature sensor defective
A1) A1)
1 1
4:13 4:14 5:1 5:2 5:3 5:4 6:1 6:2 6:3 6:4 6:5 6:6 6:7 6:8 6:9 7:1
B A A1) A1) A1) B A A1) A1) A1) A B A B A A
03) 0 03) 1 1 03) 03) 03) 1 1 13) 03) 03) 03) 0 03)
Extra regulation sequence 2, valve monitoring tripped Extra regulation sequence 2, alarm input tripped Reheat, overheating protection for electric air heater tripped Reheat, frost guard tripped Reheat, frost guard temperature sensor defective Reheat, heat valve monitoring tripped Xzone, I/O-module no. A communication error Xzone, overheating protection for electric air heater tripped Xzone, frost guard tripped Xzone, frost guard temperature sensor defective Xzone, supply air temperature sensor defective Xzone, heating valve monitoring tripped Xzone, supply air temperature below set point alarm limit Xzone, supply air temperature above set point alarm limit Xzone, heat, alarm input tripped Xzone, I/O-module no. B communication error
Swegon reserves the right to alter specifications.
A = Type A alarm B=Type B alarm
1 = Stop
1 1 1 13) 03) 03) 03)
External fire alarm no. 1 tripped External fire alarm no. 2 tripped Internal fire alarm tripped External alarm no. 1 tripped 2) External alarm no. 2 tripped 2) Preheating, I/O module no. 9 communication error Preheating, overheating protection for electric air heater tripped
4:5 4:6 4:7
Effect
0 = In operation 0 = Blocked 0 = In operation
1:1 1:2 1:3 2:1 2:2 3:1 3:2
4:3 4:4
Adjusted value Priority
www.swegon.com
37
GB.GOLDSKE.150520
Factory-preset value Alarm No.
Priority Function
7:2 7:3 7:4 7:5 7:6 8:5 10:1 10:2
Xzone, extract air temperature sensor defective Xzone, cooling valve monitoring tripped Xzone, extract air temperature below set point alarm limit Xzone, cool, alarm input 1 tripped Xzone, cool, alarm input 2 tripped Cooling, valve monitoring tripped Supply air temperature sensor defective Supply air temperature sensor for density compensation defective
0 = Blocked A = Type A alarm B = Type B alarm A B A A A B A B
Effect 1 = Stop
13) 03)
10:5 Extract air temperature sensor for heat exchanger defrosting defective
A
13)
10:6 Extract air temperature sensor for density compensation in SD air handling unit defective
A
13)
10:10 11:1 11:2 11:3 11:4 11:5 11:6 11:7 11:8 11:9 11:10 11:11 11:12 11:13 11:14 11:15 12:1 12:2 12:6 12:11 13:1 13:2 13:3 13:9 13:11 13:12 13:13 13:14 15:1 15:2 15:3 15:4 15:7
B B B B B B B B B B B B B B B B A B A A B A A A B B B B A A A A A
03) 03) 03) 03) 03) 03) 03) 03) 03) 03) 03) 03) 03) 03) 03) 03) 13) 03) 13) 13) 03) 03) 03) 03) 03) 03) 03) 03) 13)4) 13)4) 13)4) 03)4) 1
www.swegon.com
A = Type A alarm B=Type B alarm
1 = Stop
13) 03) 03) 0 0 03) 13) 03)
A B
38
Effect
0 = In operation 0 = Blocked 0 = In operation
10:3 Extract air temperature sensor defective 10:4 Extract air temperature sensor for density compensation defective (RX/PX/CX)
Outdoor air temperature sensor defective (GOLD SD) Room temperature sensor no. 1 defective Room temperature sensor no. 2 defective Room temperature sensor no. 3 defective Room temperature sensor no. 4 defective Xzone, room temperature sensor no. 5 defective Xzone, room temperature sensor no. 6 defective Xzone, room temperature sensor no. 7 defective Xzone, room temperature sensor no. 8 defective Outdoor temperature sensor no. A defective Outdoor temperature sensor no. B defective Outdoor temperature sensor no. C defective Outdoor temperature sensor no. D defective Room temperature from communication error 2) Xzone, room temperature from communication error 2) Outdoor temperature from communication error 2) Supply air temperature below set point alarm limit Supply air temperature above set point alarm limit Extract air temperature below alarm limit Temperature protection below alarm limit 2) Humidifying, I/O module no. 4 communication error Supply air humidity sensor defective Extract air humidity sensor defective Humidifier, alarm output tripped VOC sensor communication errod VOC sensor, internal communication error VOC sensor, internal error VOC sensor, level below/above set point alarm limit Plate heat exchanger, I/O module no. 2 communication error Plate heat exchanger, temperature sensor no. 1 defective Plate heat exchanger, temperature sensor no. 2 defective Plate heat exchanger, damper monitor tripped Plate heat exchanger, I/O module no. 3 communication error
Adjusted value Priority
Swegon reserves the right to alter specifications.
GB.GOLDSKE.150520
Alarm No.
Factory-preset value
15:8 15:9 15:10 15:11 15:12 15:14 15:15 16:1 16:2 16:3 16:4 17:1 17:2 17:3 17:4 17:5 17:6 17:7 17:8 17:9 18:1 18:2 18:3 18:4 18:5 18:6 18:9 18:10 18:11 18:12 18:13 21:1 21:2 21:3 21:4 21:5 21:6 21:7 21:8 21:9 21:10 21:11 21:12 21:13 21:14 21:15 23:1
Priority Function
0 = Blocked
A = Type A alarm B = Type B alarm Plate heat exchanger, bypass damper monitoring tripped A Plate heat exchanger, damper no. 1 monitoring tripped A Plate heat exchanger, damper no. 2 monitoring tripped A Plate heat exchanger, I/O module no. 3 communication error A Plate heat exchanger, bypass damper monitoring tripped A Plate heat exchanger, defrosting sensor no. C communication B error Plate heat exchanger, defrosting pressure over alarm limit B Coil heat exchanger, I/O module no. 1 communication error A Coil heat exchanger, temperature sensor defective A Coil heat exchanger, valve monitor tripped A Coil heat exchanger, pump monitor tripped A Rotary heat exchanger, motor controller communication error A Rotary heat exchanger, defrosting pressure sensor no. 7 comB munication error Rotary heat exchanger, defrosting pressure above alarm limit Rotary heat exchanger, rotation detector tripped Rotary heat exchanger, motor controller overcurrent Rotary heat exchanger, motor controller undervoltage Rotary heat exchanger, motor controller overvoltage Rotary heat exchanger, motor controller excess temperature Rotary heat exchanger, motor controller start up error AYC I/O module no. 7 communication error AYC heating, temperature sensor defective AYC heat, valve monitor tripped AYC heat, pump monitor tripped AYC heat, temperature below set point alarm limit AYC heating, temperature above set point alarm limit 5) AYC cooling, temperature sensor defective AYC cool, valve monitor tripped AYC cool, pump monitor tripped AYC cool, temperature below set point alarm limit AYC cooling, temperature above set point alarm limit 5) COOL DX, I/O module no. 2 communication error COOL DX, compressor no. 1 low pressure sensor defective COOL DX, compressor no. 1 low pressure below alarm limit COOL DX, compressor no. 1 high pressure sensor defective COOL DX, compressor no. 1 high pressure above alarm limit COOL DX, compressor no. 1 monitoring tripped COOL DX, compressor no. 1 restart error COOL DX, compressor no. 2 low pressure sensor defective COOL DX, compressor no. 2 low pressure below alarm limit COOL DX, compressor no. 2 high pressure sensor defective COOL DX, compressor no. 2 high pressure above alarm limit COOL DX, compressor no. 2 monitoring tripped COOL DX, compressor no. 2 restart error COOL DX, outdoor air temperature sensor defective COOL DX, phase monitoring error SMART Link, communication error
Swegon reserves the right to alter specifications.
B A1) A1) A1) A1) A1) A1) A A B A A B A B A A B B A1) A1) A1) A1) A A A1) A1) A1) A1) A A B A A
Effect
Adjusted value Priority
Effect
0 = In operation 0 = Blocked 0 = In operation 1 = Stop
A = Type A alarm B=Type B alarm
1 = Stop
0 0 0 1 0 0 1 13)4) 13)4) 03)4) 13)4) 13) 03) 13)4) 13)4) 13)4) 13)4) 13)4) 13)4) 13)4) 03) 03) 03) 03) 03) 03) 03) 03) 03) 03) 03) 03) 03) 03) 03) 03) 03) 03) 03) 03) 03) 03) 03) 03) 03) 03) 03) www.swegon.com
39
GB.GOLDSKE.150520
Factory-preset value Alarm No.
Priority Function
23:2 23:3 23:4 23:10 23:11 24:1 24:2 24:4 24:5 24:7 24:8 24:10 24:11 26:1
0 = Blocked
A = Type A alarm B = Type B alarm SMART Link, alarm level 1 tripped B SMART Link, alarm level 2 tripped B SMART Link, alarm level 3 tripped B AQUA Link, I/O-module no. 5 communication error 5 tripped B SMART Link, no. 1 communication error B SMART Link, no. 1 communication error A SMART Link, no. 1 alarm tripped A SMART Link, no. 2 communication error A SMART Link, no. 2 alarm tripped A SMART Link, no. 3 communication error A SMART Link, no. 3 alarm tripped A SMART Link, no. 4 communication error A SMART Link, no. 4 alarm tripped A Pre-filter, supply air pressure sensor no. 8 communication B error
Effect 1 = Stop
A = Type A alarm B=Type B alarm
1 = Stop
03) 03) 03) 03) 03) 03) 03) 03) 03) 03) 03) 03) 03) 03)
B B
03) 03)
26:8 Pre-filter, extract air fouled 27:1 AHU filter, supply air pressure sensor no. 3/4 communication error
B B
03) 03)
27:2 AHU filter, supply air fouled 27:7 AHU filter, extract air pressure sensor no. 3/4 communication error
B B
03) 03)
27:8 AHU filter, extract air fouled 28:1 End filter, supply air pressure sensor no. A communication error 28:2 End filter, supply air fouled 30:1 Flow measurement, supply air pressure sensor no. 1/2 communication error 30:2 Flow measurement, supply airflow below set point alarm limit 30:3 Flow measurement, supply air flow above set point alarm limit 30:6 Flow measurement, extract air pressure sensor no. 1/2 communication error 30:7 Flow measurement, extract airflow below set point alarm limit 30:8 Flow measurement, extract airflow below set point alarm limit 30:11 Flow measurement, purging pressure sensor no. B communication error 31:1 Pressure regulation, supply air pressure sensor no. AQUA Link, pump monitor tripped 31:2 Pressure regulation, supply air pressure below set point alarm limit 31:3 Pressure regulation, supply air pressure above set point alarm limit 31:6 Pressure regulation, extract air pressure sensor no. 6 communication error 31:7 Pressure regulation, extract air pressure below set point alarm limit
B B
03) 03)
B A
03) 13)
B B
03) 03)
A
13)
B
03)
B
03)
B
03)
A
13)
B
03)
B
03)
A
13)
B
03)
www.swegon.com
Effect
0 = In operation 0 = Blocked 0 = In operation
26:2 Pre-filter, supply air dirty 26:7 Pre-filter, extract air pressure sensor no. 9 communication error
40
Adjusted value Priority
Swegon reserves the right to alter specifications.
GB.GOLDSKE.150520
Alarm No.
Factory-preset value
31:8 32:1 32:2 32:3 32:4 33:1 33:15 34:1 34:2 35:1 38:1 38:2 38:3 38:4 38:5
Priority Function
0 = Blocked
A = Type A alarm B = Type B alarm Pressure regulation, extract air pressure above set point alarm B limit RECO2, I/O module no. 0 communication error A RECO2, pressure sensor no. 0 communication error A RECO2,/Intermittent night heating, recirculated air damper B monitoring tripped RECO2, outdoor air damper monitoring tripped B Service period above alarm limit 2) B Lock function tripped A External control, I/O module no. 3 communication error B External control, I/O module no. 6 communication error B Booster diffusers, I/O module no. 8 communication error B MIRU Control no. 1 communication error A MIRU Control no. 1 motor controller alarm tripped A MIRU Control no. 1 motor controller communication error A MIRU Control no. 1 flow measurement pressure sensor no. 0 A communication error MIRU Control no. 1 pressure regulation sensor no. 1 commuA nication error
Effect 1 = Stop
A = Type A alarm B=Type B alarm
1 = Stop
03) 03) 03) 03) 03) 03) 1 03) 03) 0 03) 03) 03) 03) 03)
B B
03) 03)
A A A A
03) 03) 03) 03)
A
03)
B B
03) 03)
A A A A
03) 03) 03) 03)
A
03)
B B
03) 03)
41:1 41:2 41:3 41:4
A A A A
03) 03) 03) 03)
A
03)
B
03)
Swegon reserves the right to alter specifications.
Effect
0 = In operation 0 = Blocked 0 = In operation
38:6 MIRU Control no. 1 temperature sensor defective 38:7 MIRU Control no. 1 flow/pressure deviation from set point alarm limit 39:1 MIRU Control no. 2 communication error 39:2 MIRU Control no. 2 motor controller alarm tripped 39:3 MIRU Control no. 2 motor controller communication error 39:4 MIRU Control no. 2 flow measurement pressure sensor no. 0 communication error 39:5 MIRU Control no. 2 pressure regulation sensor no. 1 communication error 39:6 MIRU Control no. 2 temperature sensor defective 39:7 MIRU Control no. 2 flow/pressure deviation from set point alarm limit 40:1 MIRU Control no. 3 communication error 40:2 MIRU Control no. 3 motor controller alarm tripped 40:3 MIRU Control no. 3 motor controller communication error 40:4 MIRU Control no. 3 flow measurement pressure sensor no. 0 communication error 40:5 MIRU Control no. 3 pressure regulation sensor no. 1 communication error 40:6 MIRU Control no. 3 temperature sensor defective 40:7 MIRU Control no. 3 flow/pressure deviation from set point alarm limit MIRU Control no. 4 communication error MIRU Control no. 4 motor controller alarm tripped MIRU Control no. 4 motor controller communication error MIRU Control no. 4 flow measurement pressure sensor no. 0 communication error 41:5 MIRU Control no. 4 pressure regulation sensor no. 1 communication error 41:6 MIRU Control no. 4 temperature sensor defective
Adjusted value Priority
www.swegon.com
41
GB.GOLDSKE.150520
Factory-preset value Alarm No.
Priority Function
41:7 MIRU Control no. 4 flow/pressure deviation from set point alarm limit 42:1 MIRU Control no. AQUA Link, pump monitor tripped 42:2 MIRU Control no. 5 motor controller alarm tripped 42:3 MIRU Control no. 5 motor controller communication error 42:4 MIRU Control no. 5 flow measurement pressure sensor no. 0 communication error 42:5 MIRU Control no. 5 pressure regulation sensor no. 1 communication error 42:6 MIRU Control no. 5 temperature sensor defective 42:7 MIRU Control no. 5 flow/pressure deviation from set point alarm limit 43:1 MIRU Control no. 6 communication error 43:2 MIRU Control no. 6 motor controller alarm tripped 43:3 MIRU Control no. 6 motor controller communication error 43:4 MIRU Control no. 6 flow measurement pressure sensor no. 0 communication error 43:5 MIRU Control no. 6 pressure regulation sensor no. 1 communication error 43:6 MIRU Control no. 6 temperature sensor defective 43:7 MIRU Control no. 6 flow/pressure deviation from set point alarm limit 44:1 MIRU Control no. 7 communication error 44:2 MIRU Control no. 7 motor controller alarm tripped 44:3 MIRU Control no. 7 motor controller communication error 44:4 MIRU Control no. 7 flow measurement pressure sensor no. 0 communication error 44:5 MIRU Control no. 7 pressure regulation sensor no. 1 communication error 44:6 MIRU Control no. 7 temperature sensor defective 44:7 MIRU Control no. 7 flow/pressure deviation from set point alarm limit 45:1 MIRU Control no. 8 communication error 45:2 MIRU Control no. 8 motor controller alarm tripped 45:3 MIRU Control no. 8 motor controller communication error 45:4 MIRU Control no. 8 flow measurement pressure sensor no. 0 communication error 45:5 MIRU Control no. 8 pressure regulation sensor no. 1 communication error 45:6 MIRU Control no. 8 temperature sensor defective 45:7 MIRU Control no. 8 flow/pressure deviation from set point alarm limit 46:1 MIRU Control no. 9 communication error 46:2 MIRU Control no. 9 motor controller alarm tripped 46:3 MIRU Control no. 9 motor controller communication error 46:4 MIRU Control no. 9 flow measurement pressure sensor no. 0 communication error 46:5 MIRU Control no. 9 pressure regulation sensor no. 1 communication error 46:6 MIRU Control no. 9 temperature sensor defective 46:7 MIRU Control no. 9 flow/pressure deviation from set point alarm limit 47:1 MIRU Control no. 10 communication error 42
www.swegon.com
0 = Blocked A = Type A alarm B = Type B alarm B
Effect
Adjusted value Priority
Effect
0 = In operation 0 = Blocked 0 = In operation 1 = Stop
A = Type A alarm B=Type B alarm
1 = Stop
03)
A A A A
03) 03) 03) 03)
A
03)
B B
03) 03)
A A A A
03) 03) 03) 03)
A
03)
B B
03) 03)
A A A A
03) 03) 03) 03)
A
03)
B B
03) 03)
A A A A
03) 03) 03) 03)
A
03)
B B
03) 03)
A A A A
03) 03) 03) 03)
A
03)
B B
03) 03)
A
03) Swegon reserves the right to alter specifications.
GB.GOLDSKE.150520
Alarm No.
Factory-preset value Priority Function
47:2 MIRU Control no. 10 motor controller alarm tripped 47:3 MIRU Control no. 10 motor controller communication error 47:4 MIRU Control no. 10 flow measurement pressure sensor no. 0 communication error 47:5 MIRU Control no. 10 pressure regulation sensor no. 1 communication error 47:6 MIRU Control no. 10 temperature sensor defective 47:7 MIRU Control no. 10 flow/pressure deviation from set point alarm limit 49:1 Supply air fan no. 1A communication error 49:2 Supply air fan no. 1A motor controller overcurrent 49:3 Supply air fan no. 1A motor controller undervoltage 49:4 Supply air fan no. 1A motor controller overvoltage 49:5 Supply air fan no. 1A motor controller excess temperature 49:6 Supply air fan no. 1A motor controller start up error 49:7 Supply air fan no. 1A motor controller uneven phase voltage 49:8 Supply air fan no. 1A motor controller phase error 49:9 Supply air fan no. 1A motor controller internal memory error 49:10 Supply air fan no. 1A motor controller current limitation 50:1 Supply air fan no. 2A communication error 50:2 Supply air fan no. 2A motor controller overcurrent 50:3 Supply air fan no. 2A motor controller undervoltage 50:4 Supply air fan no. 2A motor controller overvoltage 50:5 Supply air fan no. 2A motor controller excess temperature 50:6 Supply air fan no. 2A motor controller start up error 50:7 Supply air fan no. 2A motor controller uneven phase voltage 50:8 Supply air fan no. 2A motor controller phase error 50:9 Supply air fan no. 2A motor controller internal memory error 50:10 Supply air fan no. 2A motor controller current limitation 51:1 Supply air fan no. 3A communication error 51:2 Supply air fan no. 3A motor controller overcurrent 51:3 Supply air fan no. 3A motor controller undervoltage 51:4 Supply air fan no. 3A motor controller overvoltage 51:5 Supply air fan no. 3A motor controller excess temperature 51:6 Supply air fan no. 3A motor controller start up error 51:7 Supply air fan no. 3A motor controller uneven phase voltage 51:8 Supply air fan no. 3A motor controller phase error 51:9 Supply air fan no. 3A motor controller internal memory error 51:10 Supply air fan no. 3A motor controller current limitation 52:1 Supply air fan no. 1B communication error 52:2 Supply air fan no. 1B motor controller overcurrent 52:3 Supply air fan no. 1B motor controller undervoltage 52:4 Supply air fan no. 1B motor controller overvoltage 52:5 Supply air fan no. 1B motor controller excess temperature 52:6 Supply air fan no. 1B motor controller start up error 52:7 Supply air fan no. 1B motor controller uneven phase voltage 52:8 Supply air fan no. 1B motor controller phase error 52:9 Supply air fan no. 1B motor controller internal memory error 52:10 Supply air fan no. 1B motor controller current limitation 53:1 Supply air fan no. 2B communication error Swegon reserves the right to alter specifications.
0 = Blocked A = Type A alarm B = Type B alarm A A A
Effect
Adjusted value Priority
Effect
0 = In operation 0 = Blocked 0 = In operation 1 = Stop
A = Type A alarm B=Type B alarm
1 = Stop
03) 03) 03)
A
03)
B B
03) 03)
A A1) A1) A1) A1) A1) A1) A1) A1) B A A1) A1) A1) A1) A1) A1) A1) A1) B A A1) A1) A1) A1) A1) A1) A1) A1) B A A1) A1) A1) A1) A1) A1) A1) A1) B A
13) 13) 13) 13) 13) 13) 13) 13) 13) 03) 13) 13) 13) 13) 13) 13) 13) 13) 13) 03) 13) 13) 13) 13) 13) 13) 13) 13) 13) 03) 13) 13) 13) 13) 13) 13) 13) 13) 13) 03) 13) www.swegon.com
43
GB.GOLDSKE.150520 Factory-preset value Alarm No.
Priority
53:2 53:3 53:4 53:5 53:6 53:7 53:8 53:9 53:10 54:1 54:2 54:3 54:4 54:5 54:6 54:7 54:8 54:9 54:10 55:1 55:2 55:3 55:4 55:5 55:6 55:7 55:8 55:9 55:10 56:1 56:2 56:3 56:4 56:5 56:6 56:7 56:8 56:9 56:10 57:1 57:2 57:3 57:4 57:5 57:6 57:7 57:8 57:9 57:10 58:1 44
Function
0 = Blocked
Supply air fan no. 2B motor controller overcurrent Supply air fan no. 2B motor controller undervoltage Supply air fan no. 2B motor controller overvoltage Supply air fan no. 2B motor controller excess temperature Supply air fan no. 2B motor controller start up error Supply air fan no. 2B motor controller uneven phase voltage Supply air fan no. 2B motor controller phase error Supply air fan no. 2B motor controller internal memory error Supply air fan no. 2B motor controller current limitation Supply air fan no. 3B communication error Supply air fan no. 3B motor controller overcurrent Supply air fan no. 3B motor controller undervoltage Supply air fan no. 3B motor controller overvoltage Supply air fan no. 3B motor controller excess temperature Supply air fan no. 3B motor controller start up error Supply air fan no. 3B motor controller uneven phase voltage Supply air fan no. 3B motor controller phase error Supply air fan no. 3B motor controller internal memory error Supply air fan no. 3B motor controller current limitation Extract air fan no. 1A communication error Extract air fan no. 1A motor controller overcurrent Extract air fan no. 1A motor controller undervoltage Extract air fan no. 1A motor controller overvoltage Extract air fan no. 1A motor controller excess temperature Extract air fan no. 1A motor controller start up error Extract air fan no. 1A motor controller uneven phase voltage Extract air fan no. 1A motor controller phase error Extract air fan no. 1A motor controller internal memory error Extract air fan no. 1A motor controller current limitation Extract air fan no. 2A communication error Extract air fan no. 2A motor controller overcurrent Extract air fan no. 2A motor controller undervoltage Extract air fan no. 2A motor controller overvoltage Extract air fan no. 2A motor controller excess temperature Extract air fan no. 2A motor controller start up error Extract air fan no. 2A motor controller uneven phase voltage Extract air fan no. 2A motor controller phase error Extract air fan no. 2A motor controller internal memory error Extract air fan no. 2A motor controller current limitation Extract air fan no. 3A communication error Extract air fan no. 3A motor controller overcurrent Extract air fan no. 3A motor controller undervoltage Extract air fan no. 3A motor controller overvoltage Extract air fan no. 3A motor controller excess temperature Extract air fan no. 3A motor controller start up error Extract air fan no. 3A motor controller uneven phase voltage Extract air fan no. 3A motor controller phase error Extract air fan no. 3A motor controller internal memory error Extract air fan no. 3A motor controller current limitation Extract air fan no. 1B communication error
A = Type A alarm B = Type B alarm A1) A1) A1) A1) A1) A1) A1) A1) B A A1) A1) A1) A1) A1) A1) A1) A1) B A A1) A1) A1) A1) A1) A1) A1) A1) B A A1) A1) A1) A1) A1) A1) A1) A1) B A A1) A1) A1) A1) A1) A1) A1) A1) B A
www.swegon.com
Effect
Adjusted value Priority
Effect
0 = In operation 0 = Blocked 0 = In operation 1 = Stop
A = Type A alarm B=Type B alarm
1 = Stop
13) 13) 13) 13) 13) 13) 13) 13) 03) 13) 13) 13) 13) 13) 13) 13) 13) 13) 03) 13) 13) 13) 13) 13) 13) 13) 13) 13) 03) 13) 13) 13) 13) 13) 13) 13) 13) 13) 03) 13) 13) 13) 13) 13) 13) 13) 13) 13) 03) 13) Swegon reserves the right to alter specifications.
GB.GOLDSKE.150520
Alarm No.
Factory-preset value Priority Function
0 = Blocked
A = Type A alarm B = Type B alarm 58:2 Extract air fan no. 1B motor controller overcurrent A1) 58:3 Extract air fan no. 1B motor controller undervoltage A1) 58:4 Extract air fan no. 1B motor controller overvoltage A1) 58:5 Extract air fan no. 1B motor controller excess temperature A1) 58:6 Extract air fan no. 1B motor controller start up error A1) 58:7 Extract air fan no. 1B motor controller uneven phase voltage A1) 58:8 Extract air fan no. 1B motor controller phase error A1) 58:9 Extract air fan no. 1B motor controller internal memory error A1) 58:10 Extract air fan no. 1B motor controller current limitation B 59:1 Extract air fan no. 2B communication error A 59:2 Extract air fan no. 2B motor controller overcurrent A1) 59:3 Extract air fan no. 2B motor controller undervoltage A1) 59:4 Extract air fan no. 2B motor controller overvoltage A1) 59:5 Extract air fan no. 2B motor controller excess temperature A1) 59:6 Extract air fan no. 2B motor controller start up error A1) 59:7 Extract air fan no. 2B motor controller uneven phase voltage A1) 59:8 Extract air fan no. 2B motor controller phase error A1) 59:9 Extract air fan no. 2B motor controller internal memory error A1) 59:10 Extract air fan no. 2B motor controller current limitation B 60:1 Extract air fan no. 3B communication error A 60:2 Extract air fan no. 3B motor controller overcurrent A1) 60:3 Extract air fan no. 3B motor controller undervoltage A1) 60:4 Extract air fan no. 3B motor controller overvoltage A1) 60:5 Extract air fan no. 3B motor controller excess temperature A1) 60:6 Extract air fan no. 3B motor controller start up error A1) 60:7 Extract air fan no. 3B motor controller uneven phase voltage A1) 60:8 Extract air fan no. 3B motor controller phase error A1) 60:9 Extract air fan no. 3B motor controller internal memory error A1) 60:10 Extract air fan no. 3B motor controller current limitation B
Effect
Adjusted value Priority
Effect
0 = In operation 0 = Blocked 0 = In operation 1 = Stop
A = Type A alarm B=Type B alarm
1 = Stop
13) 13) 13) 13) 13) 13) 13) 13) 03) 13) 13) 13) 13) 13) 13) 13) 13) 13) 03) 13) 13) 13) 13) 13) 13) 13) 13) 13) 03)
Cannot be blocked. The delay is adjustable. 3) Adjustable. 4) Stops the AHU if the temperature is below the adjustable limit. 5) Inactive as factory setting. 1)
2)
Commissioning performed by: Date Company Name
Swegon reserves the right to alter specifications.
www.swegon.com
45