Preview only show first 10 pages with watermark. For full document please download

Connect Row Expander Pdus And Set Circuit Breakers Install The

   EMBED


Share

Transcript

7 Connect Row Expander PDUs and Set Circuit Breakers 12 Connect the PowerView Display and Install the Bezels 9 Connect the Rack-Mount Power Distribution Units (PDUs) Before beginning this step, see the Row Expander PDU Installation Guide [220–240 V Countries] and the Symmetra RM [4–12 kVA N + 1 Redundant] Power Array User’s Manual for safety and hardwiring instructions. A. For each row, route the power cord for each rack-mount PDU using the holes provided on either side at the bottom of an enclosure. Push the excess cord into the channels next to the rack-mount PDUs for a neater appearance. A. In the Base Enclosure, plug each Row Expander PDU power cord into a UPS hardwiring PDU terminal block, as shown below. B. In the Base Enclosure, set the UPS input circuit breaker (on front of UPS) and all of the UPS PDU circuit breakers to the ON position. C. In each Row Expander Enclosure, set the Row Expander PDU output circuit breakers to the ON position. B. Rack-Mount PDUs L1 L2/N Cable Strain Relief Panel NetShelter VX Expansion Enclosures Rack-Mount PDUs B. Start up the UPS by turning it ON and powering up the load equipment. See the “Getting Started” procedures in the Operation section of the Symmetra RM [4–12 kVA N + 1 Redundant] Power Array User’s Manual. the “Language Setting” procedure in the Operation section of Symmetra RM [4–12 kVA N + 1 Redundant] Power Array User’s Manual. E. If necessary, configure the rack-mount PDUs alarm threshold as outlined in the Power Distribution Unit (PDU) User’s Manual. F. If your system includes Extended Run Cabinets, perform all procedures as outlined in the Symmetra Extended Run Cabinet Startup Guide. G. Configure any management accessory cards and software. Available Outlet Receptacles in the Row Expander Enclosure 14 Troubleshooting Procedures Input Circuit Breakers PDU or Output Circuit Breakers UPS Hardwiring PDU Circuit Breakers 220–240 V PDU For troubleshooting procedures, see the accompanying APC product documentation. If a system-wide problem persists, call APC technical support at 1-877-537-0607. For individual component support, visit APC’s website at www.apc.com/support. Your system is now ready for you to install optional equipment. See the documentation you received with optional equipment and accessories for their installation and setup. Base Enclosure Before beginning this step, see the Power Distribution Unit (PDU) User’s Manual for safety and installation instructions. A. Install any optional equipment and accessories before installing the Extended Run Cabinet battery modules and the UPS battery and power modules. Visit APC’s website at www.apc.com for available PowerStruXure Type A accessories. B. If you plan to manage your system using the pre-installed Web/SNMP Management Card, connect the network cable now. Problem NO power in ALL enclosures. Before beginning this step, see the “Completing the Installation” section in the Symmetra RM [4–12 kVA N + 1 Redundant] Power Array User’s Manual and the Symmetra RM Extended Run Setup Guide for safety and installation instructions. Rear Channels Caution Batteries can be permanently damaged if installed in a system that is not being used. Store battery module(s) at an ambient temperature below 25 ºC (77 ºF). Two people are required to lift, move or install a battery module. Heavy The UPS is not turned ON. Perform the “Getting Started” procedures in the Operation section of the UPS user’s manual. VAC input is not present. Ensure that Step 5 is properly completed. NO power in multiple enclosures. A UPS PDU circuit breaker is OFF. Ensure that Step 7 is properly completed. The Row Expander PDU power cord is not connected to the UPS. Ensure that Step 7 is properly completed. NO power in an individual rackmount PDU or one enclosure. The rack-mount PDU is not plugged into the outlet receptacle. Ensure that Step 9 is properly completed. A Row Expander PDU output circuit breaker or UPS PDU circuit breaker is OFF. Ensure that Step 7 is properly completed. Problem with an Extended Run Cabinet. The Extended Run Cabinet is not properly connected. See the “Troubleshooting” section in the Symmetra Extended Run Cabinet Startup Guide. A circuit breaker trips repeatedly. The circuit breaker is overloaded. Redistribute the load, then ensure that the circuit breaker is turned ON. PowerView Display not ON. The PowerView Display unit is not connected to the UPS. Ensure that Steps 12A and 12B are properly completed. Fault LEDs or error messages. There is a potential system fault or tripped alarm. See “Troubleshooting” in the Operation section of the UPS user’s manual. modues. Line ® Press to mute the alarm. Press for 10 seconds to invert the display. Metered Power Distribution Unit w w w. a p c . c o m Amps Amps Solution Ensure that the Mains circuit breaker is ON. A. Unpack and install the UPS power and battery modules. B. If your system includes Extended Run Cabinets, unpack and install the battery 16 Possible Cause 11 Install Power and Battery Modules Install the rack-mount PDU’s vertically in the left or right rear channel of each applicable enclosure. A complete daisy-chained 220–240 V circuit has a 15 A current availability. ¡ MasterSwitch VM PDUs may be substituted if remotely controllable outlets are required. Checklist” procedure in the Installation section of the Symmetra RM [4–12 kVA N + 1 Redundant] Power Array User’s Manual. Make sure that all circuit breakers on the Row Expander PDU are in the ON position. See Step 7. D. If applicable, change the PowerView Display language setting as outlined in IEC320 C19 Receptacles 10 Install Optional Equipment in the Enclosures 8 Install the Rack-Mount Power Distribution Units (PDUs) Note Base Enclosure L1 L2/N Row Expander PDU ¡ Each enclosure supports up to two rack-mount PDUs, one on each side. ¡ Each Base or Row Expander Enclosure contains receptacles to support up to four 220–240 V rackmount PDUs. They can be installed in any configuration which meets the need of your system. Install all other bezels for the UPS. C. Row Expander PDU Receptacles (4) Row Expander PDU Power Cord Output Circuit Breakers (4) C. A. Ensure that the UPS is installed correctly by performing the “Final Installation L1 L2/ N Row Expander Enclosure To connect the PowerView Display (on the door), plug its cable into the jack on the top UPS bezel as shown. Before beginning each step in this section, see the referenced documentation for detailed instructions. L1 L2/ N UPS PDUs (3) B. 13 Finish the Installation 220–240 VAC, 15 A IEC320 C19 Input Circuit Breaker UPS Top Bezel and Cable Bezel Base or Row Expander Enclosure Available Outlet Receptacles in the Base Enclosure Hardwiring PDU Circuit Breakers (2) Main Intelligence Module (MIM) into the main intelligence module (MIM) as shown, then snap the bezel into place. UPS PDU Receptacles (4) PDU Circuit Breakers (4) PowerView Display Cable A. To install the top UPS bezel, plug its cable Plug each power cord into an outlet receptacle (IEC320 C19) on the UPS or Row Expander PDU. To Row Expander Enclosure #2 Row Expander PDU Power Cords Before beginning this step, see the “Completing the Installation” section in the Symmetra RM [4–12 kVA N + 1 Redundant] Power Array User’s Manual. Routing Rack-Mount PDUs between Enclosures NetShelter VX Expansion Enclosure UPS Power Modules UPS Battery Modules Extended Run Cabinet Battery Modules 990-7204A, February 2002