Transcript
INSTALLATION AND COMMISSIONING INSTRUCTION Control-Module CM Control-Module CM Part.-No.: 680120 Application: Module for the self installation on customer side into an EMB 8000 control unit, for the connecting of automatic smoke detectors and breakglass units. Operating voltage: Detector line voltage: Internal consumption:
24 V DC 24 V DC 20,6 mA
Housing (WxHxD): Module units: Inputs:
100 x 120 x 22,5 mm, ABS, black 1 ME 3 detector lines (max. 10 detectors / line) Vent. push button line (max. 10 pcs.) 1 feedback contact (change-over switch, 42 V / 0,5 A) Power, fault, alarm Front push button: Reset Plug-in terminals 1 mm² (rigid wire), socket and plug with cable for internal BUS
Outputs: Display: Control elements: Connections: Feature / Equipment:
Control-Module CM Setting of functions requires the software of the control unit‘s manufacturer. Functions: • Monitors three fire signalling lines for triggering and faults. • Processes signals from ventilation buttons. • Has connections for relaying of external signals for operation, fault and alarm. • Belongs to the basic equipment of a control unit and must be connected directly with the power module PM via BUS cable.
!
Warranty claims require proper and professional assembly, installation and maintenance in accordance with national regulations and manufacturer‘s instructions as to SHEV Control Unit. Always disconnect the system from power supply and back-up battery voltage prior to any installation or modification work on the control unit.
Detector line monitoring, fixing on 35-mm mounting rail, configuration of the functional and performance features which deviates from the standard systems via configuration software EMB 8000. Take the module into operation: • Integrated module into the internal BUS. • Position behind Power-Module PM / Power-Modul-Extension PME. • Fixing on 35-mm mounting rail.
!
Strictly observe the information given in the SHEV Control Unit EMB 8000 description when mounting the Control-Module CM. Setting of functions requires the software of the control unit‘s manufacturer. Keep this instruction over the lifetime of the control unit.
CONNECTION: CONTROL-MODULE CM
CONNECTION: CONTROL-MODULE CM Connection: Control-Module CM (VdS-tested) Signalling line 1
Signalling line 2
Signalling line 3 Automatic smoke detector or triggering of external fire alarm unit
Breakglass units (manual fire alarm) Resistance RE must remain in the last or only detector. Remove RE in last breakglass unit switched before it!
Cable length: max. 400 m 0,5 mm2 Connect a max. of 10 smoke detectors to CM
Displays of breakglass unit button: RD = red (Alarm) GN = green (Operation / OK) YE = yellow (Fault)
Manual fire alarm x Displays EmergencyOPEN
max. 10 piece 400 m
RD
Buttons EmergencyCLOSE
EmergencyOPEN
GN YE
Insert resistance RE in last detector of line! Cable length: max. 400 m 0,5 mm2
Manual fire alarm 1 Displays EmergencyOPEN
RD
Buttons EmergencyCLOSE
Connection module
EmergencyOPEN
GN YE
Insert resistance RE in unused signalling line!
or
or
Terminals module: = not for secondary control device
OPEN CLOSE
Ventilation control
Signalling max. 0,1 A, 24 V DC max. 400 m
Cable length: max. 400 m 0,5 mm2
Superordinated opening and closing for all Drive-Module DM (Standard)
Alarm / EMERGENCY-OPEN Operation Fault
Via USB for • Configuration • Update • Maintenance • Protocol
Signalling contact collective fault (standard) Volt free max. 42 V, 0,5 A
Operation display (green) Fault display (yellow) Alarm (EMERGENCY-OPEN) display (red) Printer
USB connection
BUS
Reset button BUS
Installation instruction Control-Module CM
BK = BN = BU = OG = RD =
black brown blue orange red
INDICATOR AND CONTROL ELEMENTS TROUBLSHOOTING AND REPAIR
INDICATOR AND CONTROL ELEMENTS Display the operating state Icon
Importance Display green: ermanently lit: Correct conditions Blinks: Back-up battery operation (power failure) No signal: Back-up battery operation (power failure)
TROUBLSHOOTING AND REPAIR All functions and system components that are important for the SHEVS operation are constantly monitored for faults. A fault indication signals the type of fault and, respectively, possible errors when connecting system components during commissioning of the Control Unit.
Control module CM Triggering of alarm (EMERGENCY-OPEN) red
Cause / possible solution triggered EMERGENCY-OPEN
Displays of status: Fault Icon
Importance
Displays also valid for external LEDs (breakglass unit)
Smoke detector still active after EMERGENCY-CLOSE
red Display yellow: Fault
Displays also valid for external LEDs (breakglass unit)
Manual alarm still on after EMERGENCY-CLOSE
red
Displays also valid for external LEDs (breakglass unit)
Displays: Triggering of Alarm / EMERGENCY-OPEN Icon
Importance Display red: Automatic or manual triggering of EMERGENCY-OPEN
Display: Control-Module CM
Display:
Fault
Cause / possible solution green
no signal
yellow
Fault signalling line 1 (automatic detector or ext. fire alarm)
yellow
Fault signalling line 2 (automatic detector or ext. fire alarm)
yellow
Fault signalling line 3 (automatic detector or ext. fire alarm)
yellow
Back-up battery fault
yellow
System in back-up battery operation
Operation (green) Fault (yellow) Alarm (red) Maintenance information yellow Connection USB
Maintenance of system required
Displays also valid for all connected breakglass units of control module CM
Fault CAN-BUS green
Button: Resetting des of module
Cause / possible solution
Cause / possible solution and
yellow
Number of modules in system doesn‘t coincide with system configuration (display also signalizes change of original system configuration)
yellow
CAN participant is (still) missing or system with CAN BUS is being parameterised just now
Displays also valid for external LEDs (breakglass unit)
Installation instruction Control-Module CM