Transcript
Menu operation via AKA 21
ADAP-KOOL®
Controller for controlling evaporators AKC 114A, 115A and 116A
Software version 1.5x RC.1M.B2.02 → RC.1M.B3.02
11-1998
System survey
A refrigerating plant fitted with ADAP-KOOL® refrigeration controls will mostly consist of several controllers where each controller will regulate its own refrigeration appliance/cold room. The system has been designed in such a way that contact can be made to each and every controller via a data communication system. One specific controller is selected, and it will now be possible to make settings and readouts for this unit.
Operation
The individual controllers can be operated in two ways: 1. With control panel type AKA 21. Use this document when operation takes place in this way. 2. With PC and system software type AKM. Use another document with literature number RC.1M.C
Validity
This menu operation was worked out in November 1998 and applies to AKC 114A, AKC 115A and AKC 116A with the following code numbers: 084B6171 and 084B6172 (AKC 114A) 084B6173 and 084B6174 (AKC 115A) 084B6175 and 084B6176 (AKC 116A) that are fitted with software version 1.5x.
2
Menu operation
RC.1M.B3.02
©
Danfoss
11/1998
AKC 114A-116A Version 1.5x
Select a controller
All controllers that are connected to the same network can be operated with the control panel. There may be as many as 125 controllers, and they are shown in groups of 16 on the display. 1 < 1 > 16 AEAAAAAAAAEEgg A A system is shown here which consists of more than 16 controllers. The meaning of the letters is, as follows: A: AKC controller E: Controller with active ERROR (on addresses 2, 11 and 12 in this example) g: Gateway (to addresses 13 and 14 in this example) G: Gateway with connected printer : A blank field indicates that there is no unit with this address. 1 < 4 > 16 AEAAAAAAAAEEgg A Select the unit that is to be operated by using the “+/On” or “-/Off” key, and push “Enter”. In this example you select the controller with address 4. 17 < AAA
17
>
32
If the system comprises more than 16 units or units with an address code higher than 16, you may change to the next group by pushing “→”.
Settings of a controller
When a controller has been selected, you can make settings in it. This setting is performed, as follows:
-50 to +50
5 5
OFF / ON
ON ON
Shown in the upper right corner of the display is the setting with which the controller is operating. Below that value a new setting may be made. Use the three keys “+/ON”, “-/OFF” and “Digit” for setting the new value. This new value will not govern the regulation until you push the key “Enter”.
Access to a controller
The functions in the controller can be protected by means of an access code. Depending on the settings to be made, you may gain access in one of the following ways: User input: 1. Push F1 2. Push F2
3. 4.
Code 1 and then F1 Code 1 and then F3 Code 2
Gives access to: Display of alarms Reading of selected temperatures, change of temperature in the refrigeration appliance, start of defrost Acknowledgement of alarms Setting of selected parameters Operation of all settings of the entire menu system (with system software type AKM there is access to additional functions).
Pages 6 and 7 contain a description of how you gain access to the system via a code.
AKC 114A-116A Version 1.5x
Menu operation
RC.1M.B3.02
©
Danfoss
11/1998
3
Supporting text
A supporting text is attached to the individual functions. When such a function is shown in the control panel’s display, the supporting text can be obtained by pushing the key “Help”. The supporting text is intended as a help to users who no longer use these operating instructions. In the menus shown below functions with supporting texts are identified with the word “Help” next to the function.
How to localise an error
When an error appears in a system, it can be seen on the control panel’s display which will show an “E”. If the control panel shows a text from a selected controller, the LED at the word “Alarm” will furthermore flash. 1 < 2 > 16 AEAAAAAAAAAAgg A
AKC 116A Adr: 2 E Mon-11:27
Standby Mode
When an error has occurred, first select the controller on which the error is registered. When the controller has been found, push “F1”, and the error message will appear. At the end of the document there is a list of all the error messages and a description of how to acknowledge an alarm.
When one controller has been selected from the total system, the following display will appear (the display is the first one shown when you have selected an address from the total system): e.g. AKC 116A Adr: 2 E Mon-11:27
Functions of a controller
From this position you can freely choose between several forms of operating levels: 1. Display of alarms - push “F1” 2. Display and setting of a few selected functions - push “F2” 3. Display and setting of several selected functions - push “F3” The function may be protected with a code (code 1) 4. Display and setting of all allowed functions in the controller. The function may be protected with a code (code 2). Operation of the individual levels is shown below:
1. F1
When you push “F1” the alarm messages from the controller in question appear. Only active alarms are shown. With a push on “↓” you can see whether there are more alarm messages, and if so, their texts. When an alarm has been localised and corrected, the alarm is acknowledged (removed from the system, so that it no longer appears). In large systems where a gateway is also connected this acknowledgement will take place automatically. In other systems it has to be done manually, cf. end of the document. Prior to the acknowledgement of the alarm, the keying of a code is required, see page 6. Leave the F1 function by pushing “←”.
4
Menu operation
RC.1M.B3.02
©
Danfoss
11/1998
AKC 114A-116A Version 1.5x
2. F2
When you push “F2” a number of functions will appear where it is possible to read or set values. You can move to and from the individual functions by pushing “↑” or “↓”. On page 3 you can see how a setting is changed. Man.Def. OFF/ON 7:03:02 | CutOut A °C -50 - 50 3:05:02 | CutOut B °C -50 - 50 4:05:02 | CutOut C °C -50 - 50 5:05:02 | Ther.Air A 3:04:01 | Ther.Air B 4:04:01 | Ther.Air C 5:04:01 | RunTime A 3:04:08 | RunTime B 4:04:08 | RunTime C 5:04:08 | Reg Cond. A 3:02:01 | Reg Cond. B 4:02:01 | Reg Cond. C 5:02:01
Manual defrost is activated when ON (Changes automatically to OFF)
Setting of thermostat cut-out value MUST BE SET. Even if the thermostat function has not been selected. (The value is used by the injection function). Only AKC 115A/ AKC 116A
Setting of thermostat cut-out value MUST BE SET. Even if the thermostat function has not been selected. (The value is used by the injection function)
Only AKC 116A
Setting of thermostat cut-out value MUST BE SET. Even if the thermostat function has not been selected. (The value is used by the injection function) Actual air temperature (section A)
Only AKC 115A/ AKC 116A
Actual air temperature (section B)
Only AKC 116A
Actual air temperature (section C)
Actual thermostat cut-in time of section A or duration of the latest finished cut-in Only AKC 115A/ AKC 116A
Actual thermostat cut-in time of section B or duration of the latest finished cut-in
Only AKC 116A
Actual thermostat cut-in time of section C or duration of the latest finished cut-in
Help
Help Only AKC 115A/ AKC 116A
Regulating condition 0: No cooling 1: Start up 2: Adaptive control
5: Start after defrost 6: Forced closing
4: Defrosting
8: Sensor errror 9: Modulating temperature control 10: Forced cutout (Melt function)
Help Only AKC 116A
Leave the F2 function by pushing “←”.
AKC 114A-116A Version 1.5x
Menu operation
RC.1M.B3.02
©
Danfoss
11/1998
5
3. F3
When you push “F3”, a number of functions will appear which are used when the system is serviced. • If access code is used (code 1), key it as follows: - Push the “key” - Enter the code by using the three keys “+”, “-” and “Digit” (the code is mentioned later as code 1, and the factory setting is 40. If code 2 has been set at 0, access code 1 cannot be used). - Push “Enter” - Push “F3” Move to and from the individual functions by pushing “↑” or “↓”. On page 3 you can see how a setting is changed. Main Switch -1 / 0 / 1 2:02:01 | Def.Stop °C 0 - 60 7:04:03 | MaxDefTime 5 - 180 7:04:02 | T0 °C 3:02:05 | Superheat A 3:02:02 | Superheat B 4:02:02 | Superheat C 5:02:02 | AKV OD % A 3:02:04 | AKV OD % B 4:02:04 | AKV OD % C 5:02:04
Main switch: 1: Regulation 0: Controller stop -1: Service Temperature value of defrost stop
Max. permissible defrost time in minutes (Security time on Temperature stop)
Evaporating temperature
Superheat section A
Superheat section B
Superheat section C
Actual valve opening degree
Actual valve opening degree
Actual valve opening degree
Leave the function by pushing “←”.
6
Menu operation
RC.1M.B3.02
©
Danfoss
11/1998
AKC 114A-116A Version 1.5x
4. Access to all functions
The access to the functions may be protected with a code (code 2). • If access code is used, key it as follows: - Push the “key” - Enter the code by using the three keys “+”, “-” and “Digit” - Push “Enter” - Push “←” Move to and from the individual functions by pushing the four arrow keys. On page 3 you can see how a setting is changed. When you wish to leave the “Access to all functions” function, push “Clear” and then “←”. List of functions on level 1: 1. Controller’s access display and access to system information 2. Interruption of regulation and selection of language 3. Controller A 4. Controller B (AKC 115A/116A only) 5. Controller C (AKC 116A only) 6. Common functions; Thermostat function, day/night Ctrl. settings, fan control, rail heat control, display control, DI Alarm, Output control at forced closing, safety function, Ext. injection, Ext. Temp. reference 7. Defrost control 8. Forced control functions for service and initial setting Below and on the following pages the individual functions are shown together with a brief description:
Level 1
Level 2
Level 3
Level 4
Description
AKC 11xA Adr: xxx Mon hh:mm
Controller access display If the code function is used, continue by pushing the "key" key.
Enter Code 0 - 255 0 1:01 AKC 11xA Adr: xxx Mon hh:mm 1 Code No. Prog. Ver. 1:02 | Clock: Mon hh:mm 1:03
Entry of access code 1 or access code 2 (cf. also 1:07 and 1:08). Continue by pushing "arrow left" Access to system information If an E appears in the display, an error has been registered. Reading of the controller’s code no. and programme version.
Setting of controller clock (AKC clock)
Setting of day (1 = Monday, 7 = Sunday)
Clock: Day. Mon(1) Sun(7) 1:03:01 | Clock: Hour 0 - 23 1:03:02 | Clock: Min. 0 - 59 1:03:03
Setting of hours
Setting of minutes
| System Address Addr. yyy xxx 1:04 | Alarm report to Addr. yyy xxx 1:05
AKC 114A-116A Version 1.5x
Reading of the controller’s system address yyy=network no. and xxx=address. The system address can only be set via PC Reading of the alarm address (end receiver) the alarms are to be sent to. The alarm address can only be set via PC.
Menu operation
RC.1M.B3.02
©
Danfoss
11/1998
7
| Gateway Address xxx 1:06 | Chg. Code1 0 - 255 1:07 | Chg. Code2 0 - 255 1:08
Reading of the address on the nearst gateway which has to effect alarms (see 1:05) The address can only be set via PC Change of code 1. The code gives access to acknowledgement of active alarm by means of the F1 key. Also access to the selected settings/readouts via the F3 key. (Factory setting = 40) (See also code 2) Change of code 2. The code gives access to the whole menu system. (Factory setting = 0. Setting = 0 offers free access where neither code 1 not code 2 is required)
| Main Function
Main function
2 In case of alarm, an E is shown on the display (Error log becomes visible)
Alarm Message(s) 2:01
See page 19, check of error log 2:01:01 | Main Function Settings 2:02
Access to the main switch
Main Switch -1 / 0 / 1 2:02:01 | Language 0-4 2:02:02
Main switch: 1: Regulation 0: Controller stop -1: Service
Help
Selection of language. Three languages have been entered in the controller Either: Or: 0: English 0: English 1: German 3: Danish 2: French 4: Spanish NB! This function must be set prior to any uploading to system software type AKM. When the language code has been changed, push "ENTER" and then "Clear".
Help
| Rfg. Type R
Reading of set refrigerant type
2:02:03 | Rfg. Type 0 - 23 2:02:04
Refrigerant selection: 0: No refrigerant selection. 1: R12 2: R22 3: R134a 4: R502 5: R717 (ammonia) 6: R13 7: R13b1 8: R23 9: R500 10: R503 11: R114
Help
| Controller A
12: R142b 13: User define 14: R32 15: R227 16: R401A 17: R507 18: R402A 19: R404A 20: R407C 21: R407A 22: R407B 23: R410A
Section A
3
In case of alarm, an E is shown on the display (Error log becomes visible)
Alarm message(s) 3:01
See page 19, check of error log 3:01:01
8
Menu operation
RC.1M.B3.02
©
Danfoss
11/1998
AKC 114A-116A Version 1.5x
| Injection A Measurements 3:02
Read-out of measuring values related to section A
Reg Cond. A 3:02:01
Help
| Superheat A 3:02:02 | SH Ref K A 3:02:03 | AKV OD % A 3:02:04 | T0 °C 3:02:05 | S2 A °C 3:02:06
5: Start after defrost 6: Forced closing
4: Defrosting
8: Sensor errror 9: Modulating temperature control 10: Forced cutout (Melt function)
Superheat section A
Actual superheat reference of the regulation
Actual valve opening degree
Evaporating temperature
Gas temperature at evaporator outlet.
| Injection A Settings 3:03
Setting of expansion valve function section A
Inj. Ctrl. A OFF / ON 3:03:01
Choose expansion valve function ON/OFF
| Thermostat Measurements 3:04
Read.out of measuring values related to thermostat function.
Ther.Air A 3:04:01 | AlarmAir A 3:04:02 | S3 A °C 3:04:03 | S4 A °C 3:04:04 | CutOut A °C 3:04:05 | CutIn A °C 3:04:06 | Night Cond 3:04:07 | RunTime A 3:04:08
Actual air temperature (section A)
Actual air temperature for the alarm function in section A
Air temperature at evaporator inlet (section A) (air on)
Air temperature at evaporator outlet (section A) (air off)
Actual thermostat(s) cut-out value
Actual thermostat(s) cut-in value
Status of day-/night operation (ON/OFF)
Actual thermostat cut-in time of section A or duration of the latest finished cut-in
| Thermostat Settings 3:05
Settings for thermostat function
Ther. Sx A 1 - 3 3:05:01
Definition of thermostat sensor(s) 1: S3 in use 2: S4 in use 3: S3, S4 in use. CPT(calculated product temperature)
Help
| CutOut A °C -50 - 50 3:05:02 | Diff. A K 0.5 - 10 3:05:03
AKC 114A-116A Version 1.5x
Regulating condition 0: No cooling 1: Start up 2: Adaptive control
Menu operation
Setting of thermostat cut-out value MUST BE SET. Even if the thermostat function has not been selected. (The value is used by the injection function). Setting of thermostat differential
RC.1M.B3.02
©
Danfoss
11/1998
9
| S4A Day % 0 - 100 3:05:04 | S4A Night % 0 - 100 3:05:05 | S4MinLim A -50 - 50 3:05:06
S4 weighting by day S3 is automatically weighted. Must only be set if "Ther.Sx" = 3
S4 is weighting at night S3 is automatically weighted
Setting of low S4 temperature alarm limit The function is only active, if weighting between S3 and S4 is used for the thermostat function
Help
| Air Temp. Alarm Settings 3:06
Settings for alarm function
Alarm ModeA 0 - 3 3:06:01
| High LimA °C -50 - 50 3:06:02 | High1Del A 0 - 240 3:06:03 | High2Del A 0 - 60 3:06:04 | Low LimA °C -50 - 50 3:06:05 | Low Del A 0 - 60 3:06:06 | Controller B
Definition of alarm thermostat 0: No alarm thermostat 1: S3 used as alarm sensor 2: S4 used as alarm sensor 3: TherAir used as alarm sensor
Help
High air temperature alarm limit (absolute value). When there is night setback operation, the alarm limit is raised by the night setback value. Time delay of high air temperature alarm during pull-down. This value will apply until the actual air temperature has dropped below the "upper alarm limit". Thereafter shift to the time delay "High2Del m".
Help
Time delay of high air temperature alarm during normal regulation. Help
Low air temperature alarm limit (absolute value)
Time delay for low air temperature alarm
Only AKC 115A/116A
Section B (only AKC 115A and AKC 116A) Description for "Controller B" is the same as for "Controller A" (3)
Only AKC 116A
Section C (only AKC 116A) Description for "Controller C" is the same as for "Controller A" (3)
4 | Controller C 5 | Common Controller 6
Functions common to sections A, B and C
In case of alarm, an E is shown on the display (Error log becomes visible)
Alarm message(s) 6:01
See page 19, check of error log 6:01:01 | Thermostat Mode 6:02 Ther. Mode 0-3 6:02:01
10
Menu operation
Definition of thermostat function 0: No thermostat function 1: The thermostat function is atached to section A (cutout and cutin of sections B and C will come after section A) 2: There is one thermostat function in each function 3: Modulating temperature regulation (there is one thermostat in each section.)
Help
RC.1M.B3.02
©
Danfoss
11/1998
AKC 114A-116A Version 1.5x
| Day/Night Ctrl. Settings 6:03
Settings of day/night function
Day/Night 0 3 6:03:01
Choose day-/night operation function 0: No night setback 1: Change between day and night operation according to signal on S6 input 2: Change between day and night operation according to internal time clock 3: Change between day and night operation according to the signal from the master controller (Signal via DANBUSS)
Help
| Dt Night K -25 - 25 6:03:02
Night set back value
Time table for day and night operation on Mondays End of night setback At setting = 0 there is no night setback this day
Mo Day h 0 24 6:03:03 | Mo Night h 0 24 6:03:04
Time table continued: Start (of night setback) At setting = 0 there is no displacement this day If day and night settings are identical, or if night is set before the function will be changed. See functional description
| Tu day h 0 24 6:03:05 | Tu night h 0 24 6:03:06 | We day h 0 24 6:03:07 | We night h 0 24 6:03:08 | Th day h 0 24 6:03:09 | Th night h 0 24 6:03:10 | Fr day h 0 24 6:03:11 | Fr night h 0 24 6:03:12 | Sa day h 0 24 6:03:13 | Sa night h 0 24 6:03:14 | Su day h 0 24 6:03:15 | Su night h 0 24 6:03:16
AKC 114A-116A Version 1.5x
Menu operation
As above, Tuesdays
As above, Tuesdays
As above, Wednesdays
As above, Wednesdays
As above, Thursdays
As above, Thursdays
As above, Fridays
As above, Fridays
As above, Saturdays
As above, Saturdays
As above, Sundays
As above, Sundays
RC.1M.B3.02
©
Danfoss
11/1998
11
| Fan Pulsing (CutOut Night) 6:04
Setting of fan pulsing during night operation
Setting of the fans’ ON period in percent of the "FanCycl m" time (the function is only active in the cutout period during night operation).
Fan On % 0 - 100 6:04:01 | FanCycl m 0.0 - 60.0 6:04:02
Period time for total ON / OFF time
| Railheat Pulsing (Day/Night) 6.05
Settings for railheat function
During day operation: Setting of rail heat ON period in percent of the "RailCycl m" time.
RailOnDay % 0 - 100 6:05:01 | RailOnNgt % 0 - 100 6:05:02 | RailCycl m 6 - 60 6:05:03
During night operation: Setting of rail heat ON period in percent of the "RailCycl m" time
Period time for total ON / OFF time
| Display Ctrl. Settings 6:06
Settings for external temperature display type AKA 14
Disp. Ctrl. 0 - 3 6:06:01
Choose read-out for display 0: No display function 1: S3 read out 2: S4 read out 3: Ther.Air read out
Help
| Offset K A -10.0 10.0 6:06:02 | Offset K B -10.0 10.0 6:06:03 | Offset K C -10.0 10.0 6:06:04
Offset adjustment of display signal, display A
Offset adjustment of display signal, display B
Offset adjustment of display signal, display C
| DI Alarm
Settings for DI alarm function
6:07 DI Alarm OFF / ON 6:07:01 | DI Text 0 - 4 6:07:02
Choose alarm function ON / OFF
Select the alarm text 0: DI alarm 1: Door alarm 2: Safety cutout 3: Fan failure 4: Leak alarm
Help
| DI Delay m 0 - 180 6:07:03
12
Menu operation
Time delay from the alarm is registered until executed
RC.1M.B3.02
©
Danfoss
11/1998
AKC 114A-116A Version 1.5x
| Output Ctrl. at Forced Closing 6:08
Definition of controller outputs at forced control signal (when the "ON" inlet is cut-out (terminal 32 - 33)) Output Ctrl. 1 - 3 6:08:01
Output functions when there is forced control 1: Fan outlet is ON 2: Fan outlet is OFF 3: All outlets are OFF and alarm thermostat function is stopped.
Help
| ON-InpMode 0 - 1 6:08:02
Definition of AKC-ON input (terminals 32-33) 0: Connection not used, as the regulation is controlled by the gateway’s override function 1: Connection must be made (when the voltage is interrupted, the valve closes)
| Safety Function Fan Stop by S5 6:09
Settings for fan stop function
FanStopS5 OFF/ON 6:09:01 | FanStop °C -50 - 50 6:09:02
Choose Fan stop function ON / OFF Help
Temperature limit for fan stop (the fans are stopped when the S5A temperature is higher than this value. The fans will start again when S5A is lower than "FanStop °C" - 2K)
| Extended Inject. Ctrl. Settings 6:10
Extended settings for injection function
SH Max K 3.0 - 15.0 6:10:01 | SH Min K 3.0 - 10.0 6:10:02 | MOP Ctrl. OFF/ON 6:10:03 | MOP °C -50 - 15 6:10:04
Max. superheat reference value
Min. superheat reference value
Choose MOP function ON/OFF
MOP point value
| Ext. Temperature Reference 6:11
Settings for Extern AL temperature reference
Definition for extern AL reference signal 1: 0 - 10 V signal 2: 2 - 10 V signal
ExtRef Sig 1 - 2 6:11:01 | ExtRefTemp -50 - 50 6:11:02 | ExtRef K 6:11:03 | Al MaxLim % 0 - 100 6:11:04 | Al MinLim % 0 - 100 6:11:05 | AI Delay m 0 - 180 6:11:06 | Al Input % 6:11:07
AKC 114A-116A Version 1.5x
Menu operation
Displacement to be produced by max. reference signal (10 V) (With setting = 0 the function is OFF)
Display of reference (input signal + displacement)
Upper alarm limit. Set in percentage of input signal
Lower alarm limit. Set in percentage of input signal
Time delay for alarm
Input signal value in per cent.
RC.1M.B3.02
©
Danfoss
11/1998
13
| Defrost Control
Defrost function
7:00 In case of alarm, an E is shown on the display (Error log becomes visible)
Alarm message(s) 7:01
See page 19, check of error log 7:01:01 | Defrost Measurements 7:02
Read-out of measuring values related to defrost function
Def. Cond. 7:02:01
Defrost condition 0: No defrost 1: Pump down 2: Not used 3: Defrosting
Help
4: Not used 5: Draining 6: Injection delay 7: Fan delay
| S5 A °C 7:02:02
Defrost sensor temperature in section A |
S5 B °C 7:02:03
Only AKC 115A/ AKC 116A
Defrost sensor temperature in section B
Only AKC 116A
Defrost sensor temperature in section C
| S5 C °C 7:02:04 | DefTime m 7:02:05 | MDefTime m 7:02:06 | AccDefSkip 7:02:07 | AccNo.Def 7:02:08
Actual defrost cut-in time or duration of the latest finished defrosting period. Average value of the latest 4 defrosting periods.
Total number of skipped defrosts since start
Total number of sustained defrosts since start
| Defrost Ctrl. Settings 7:03
Definition of defrosting method
Def. Ctrl. OFF/ON 7:03:01 | Man.Def. OFF/ON 7:03:02 | DOD Ctrl. OFF/ON 7:03:03 | Fan run OFF/ON 7:03:04
Choose defrost function ON/OFF
Manual defrost is activated when ON (Changes automatically to OFF)
Choose defrost on demand ON/OFF
Choose fan operation during defrost ON/OFF
| Defrost Stop. Temp(1)/Time(2) 7:04
Definitions of defrost stop
Temp/Time 1 - 2 7:04:01 | MaxDefTime 5 - 180 7:04:02 | Def.Stop °C 0 - 60 7:04:03 | DefStop Sx 2 - 5 7:04:04
14
Menu operation
1: Temperature stop (time as security) 2: Stop on time
Max. permissible defrost time in minutes (Security time on Temperature stop)
Temperature value of defrost stop
Definition of sensor for defrost 2: S2 3:S3 4: S4 5: S5 (default setting)
Help
RC.1M.B3.02
©
Danfoss
11/1998
AKC 114A-116A Version 1.5x
| Defrost Sequence Settings 7:05
Defrost sequence
Inj.Del m 0 - 60 7:05:01 | FanOnDel m 0 - 60 7:05:02 | Fan On °C -15 - 0 7:05:03
Liquid injection delay time
Max. permissible fan start delay after defrosting. The delay time runs from the expiry of the delay time, if applicable, for the liquid injection. Temperature at which the fan starts after defrost. Fans starts when all S5 temperatures are below the value.
| Def.Programme schedules Select 7:06 | Mon Sched. 1 - 3 7:06:01 | Tue Sched. 1 - 3 7:06:02 | Wed Sched. 1 - 3 7:06:03 | Thu Sched. 1 - 3 7:06:04 | Fri Sched. 1 - 3 7:06:05 | Sat Sched. 1 - 3 7:06:06 | Sun Sched. 1 - 3 7:06:07
Choose defrost programme for Mondays See also 7:08. 7:09 and 7:10
Choose defrost programme for Tuesdays See also 7:08. 7:09 and 7:10
Choose defrost programme for Wednesdays See also 7:08. 7:09 and 7:10
Choose defrost programme for Thursdays See also 7:08. 7:09 and 7:10
Choose defrost programme for Fridays See also 7:08. 7:09 and 7:10
Choose defrost programme for Saturdays See also 7:08. 7:09 and 7:10
Choose defrost programme for Sundays See also 7:08. 7:09 and 7:10
| Def. Schedules Auto programming 7:07
Help function for setting of defrost times The defrost periods are distributed evenly during a defined period of time within a 24-hour period. Number of defrosts/24 hours
No. Per Day 2 - 8 7:07:01 | FirstDef 00:00 7:07:02
Setting of time the 1st defrost begins
FirstDef Hour 0 - 23 07.07.02.01 | FirstDef Min. 0 - 59 07.07.02.02
AKC 114A-116A Version 1.5x
Menu operation
RC.1M.B3.02
Setting of hours
Setting of minutes
©
Danfoss
11/1998
15
| Setting of time the last defrost begins
LastDef 00:00 7:07:03
Setting of hours
LastDef Hour 0 - 23 07.07.03.01 | LastDef Min. 0 - 59 07.07.03.02 | Auto Set OFF/ON 7:07:04
Setting of minutes
Transfer the values to the three subsequent defrost programmes. In pos. ON they are entered in "7:08", "7:09" and "7:10". If the three defrost programmes are not to be identical, corrections subsequent must be made in the individual programmes.
Help
| Schedule 1 Def. Start Times 7:08
Settings for defrost programme 1 See 07:06 No. Per Day 0 - 8 7:08:01 | Def1 Sc1 00:00 7:08:02
Number of defrosts/24 hours
Setting of time the 1st defrost begins
Setting of hours
Def1 Sc1 Hour 0 - 23 07:08:02:01 | Def1 Sc1 Min. 0 - 59 07:08:02:02
Setting of minutes
| Def2 Sc1 00:00 7:08:03 | Def3 Sc1 00:00 7:08:04 | Def4 Sc1 00:00 7:08:05 | Def5 Sc1 00:00 7:08:06 | Def6 Sc1 00:00 7:08:07 | Def7 Sc1 00:00 7:08:08 | Def8 Sc1 00:00 7:08:09
Setting of time the 2nd defrost begins See 7:08:02
Setting of time the 3rd defrost begins
Setting of time the 4th defrost begins
Setting of time the 5th defrost begins
Setting of time the 6th defrost begins
Setting of time the 7th defrost begins
Setting of time the 8th defrost begins
| Schedule 2 Def. Start Times 7:09 | Schedule 3 Def. Start Times 7:10
16
Settings for defrost programme 2 See 7:06 / 7:08
Settings for defrost programme 3 See 7:06 / 7:08
Menu operation
RC.1M.B3.02
©
Danfoss
11/1998
AKC 114A-116A Version 1.5x
| Service mode
Service function
8 Measurements of input terminals 8:01
Measurements on inlets
P0 Bar 8:01:01
Suction pressure (measured with P0 pressure transmitter) | Evaporating temperature
To °C 8:01:02 | S2 A °C 8:01:03 | S3 A °C 8:01:04 | S4 A °C 8:01:05 | S5 A °C 8:01:06 | S2 B °C 8:01:07 | S3 B °C 8:01:08 | S4 B °C 8:01:09 | S5 B °C 8:01:10 | S2 C °C 8:01:11 | S3 C °C 8:01:12 | S4 C °C 8:01:13 | S5 C °C 8:01:14 | Def. Start 8:01:15 | ON input 8:01:16 | DI input 8:01:17 | S6 Input 8:01:18 | Ext.Ref. V 8:01:19
Gas temperature at evaporator outlet
Air temperature at evaporator inlet (air on)
Air temperature at evaporator outlet (air off)
Temperature at defrost sensor
Only AKC 115A/ AKC 116A
Gas temperature at evaporator outlet
Only AKC 115A/ AKC 116A
Air temperature at S3 sensor (air on)
Only AKC 115A/ AKC 116A
Air temperature at evaporator outlet (air off)
Only AKC 115A/ AKC 116A
Temperature at defrost sensor
Only AKC 116A
Gas temperature at evaporator outlet
Only AKC 116A
Air temperature at S3 sensor (air on)
Only AKC 116A
Air temperature at evaporator outlet (air off)
Only AKC 116A
Temperature at defrost sensor
Statement of defrost start signal (terminal 30 - 31) Statement of forced closing input (terminal 32 - 33) Statement of DI input
Statement of S6 inlet (terminal 60 - 61) Voltage signal on "Ext.Ref." input
| Manual Control of Outputs 8:02
Forced operation of outlets during service "Main switch" must be set to be "-1" (see 2:02:01) Man Ctrl. OFF / ON 8:02:01 | Fan OFF / ON 8:02:02
AKC 114A-116A Version 1.5x
Menu operation
ON: Manual control is permitted when "Main Switch"= -1. NOTE: No monitoring When manual setting is finished, setting must be changed to OFF. Forced operation of fan outlet (terminal 10-11)
RC.1M.B3.02
©
Danfoss
11/1998
17
| Railheat OFF / ON 8:02:03 | AKV OD % A 0 - 100 8:02:04 | DO Output OFF / ON 8:02:05 | Compressor OFF / ON 8:02:06 | Alarm OFF / ON 8:02:07 | Defrost A OFF / ON 8:02:08 | AKV OD % B 0 - 100 8:02:09 | Defrost B OFF / ON 8:02:10 | AKV OD % C 0 - 100 8:02:11 | Defrost C OFF / ON 8:02:12
18
Menu operation
Forced operation of railheat outlet (terminal 12-13)
Forced operation of expansion valve opening degree (terminal 14-15) (Fans must be operating during forced control operation) Forced operation of DO Output (terminal 16-17)
Forced operation of compressor outlet (terminal 18-19)
Forced opertion of alarm outlet (terminal 20 - 21) ON: Relay switch closed (no alarm) OFF: Relay switch interrupted (alarm) Forced operation of defrost outlet (terminal 22-23)
Only AKC 115A/ AKC 116A
Forced operation of expansion valve opening degree (terminal 110-111) (Fans must be operating during forced control operation)
Only AKC 115A/ AKC 116A
Forced operation of defrost outlet (terminal 112-113)
Only AKC 116A
Forced operation of expansion valve opening degree (terminal 120-121) (Fans must be operating during forced control operation)
Only AKC 116A
Forced operation of defrost outlet (terminal 122-123)
RC.1M.B3.02
©
Danfoss
11/1998
AKC 114A-116A Version 1.5x
Error Log: The following display read-outs are only visible if there is an active error. A, B or C in brackets show in which regulation an active error i recorded. When the error is corrected, the error message can be removed by pressing ENTER. (If the code function has been selected, a code must also be entered). S2 ( ) Error
S2 sensor error
Check sensor connection / sensor resistance
S3 ( ) Error
S3 sensor error
Check sensor connection / sensor resistance
S4 ( ) Error
S4 sensor error
Check sensor connection / sensor resistance
S5 ( ) Error
S5 sensor error
Check sensor connection / sensor resistance
AKS 32 Error
AKS 32 sensor error
Check sensor connection
High Air Temp ( )
Too high air temperature
Low Air Temp ( )
Too low air temperature
Low S4 Temp. ( )
Too low S4 temperature
Overfloated evaporator ( )
Overfilled evaporator
Max. Def. period exceeded ( )
Max. defrosting period exceeded
Defrosting finished according to time not as selected according to temperature
Max. fan del time exceeded ( )
Max. fan delay exceeded
When defrost has been completed, the fan start will be based on time, and not on temperature (6:04:01)
230 Volt on Def. start input
Wrong defrost demand
Active defrost signal on terminal 30 - 31 contrary to just finished defrosting.
See "3:05:06"
Check clock settings
After power failure, timer must be set
Standby mode
The Main switch is either set in the position "Controller stop" or "Service" (see 2:02:01).
Refrigerant not selected
No selection of refrigerant
Select refrigerant
Rfg. Changed
Changed refrigerant
Check chosen refrigerant. Regulation with changed refrigerant has come into force.
DI Alarm / Door Alarm / Safety cutout / Fan failure / Leak alarm
Alarm on digital input
Check the function
AI Max Alarm limit exceeded
Too high level on analog input
AI Min Alarm limit exceeded
Too low level on analog input
Liquid supply fault alarm ( )
Flashgas or missing liquid
AKC 114A-116A Version 1.5x
Menu operation
Check for flashgas / liquid
RC.1M.B3.02
©
Danfoss
11/1998
19
Communications/messages from AKA 21
Message not sent
There is no contact between control panel and a controller
Check the data communication system
Regulator message not received
- ll -
Check the data communication system
No node
- ll -
Check the data communication system (There is no gateway on the data communication system)
Initialisation error
- ll -
Check the data communication system (There is a gateway on the data communication system) The message may be removed, if you disconnect AKA 21 briefly
Message not understood
Temporary communication problem or wrong setup
Wait, or if it is a newly started system, check the setup of the data communication system
Dansett supervising
Pause function
When you push a key, the display disappears.
Supervising no answer
Lack of contact to a controller
Check the data communication system
AKC Occupied
AKA 21 had been disconnected for a brief period
Wait. The message disappears on its own after three minutes.
AC-RDT
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respecitve companies. Danfoss and Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
20
Menu operation
RC.1M.B3.02
©
Danfoss
11/1998
AKC 114A-116A Version 1.5x