Corning Wic-012 12 Fiber Wall Mount Interconnect Center

   EMBED


Share

Transcript

CORNING Discovering Beyond Imagination . Corning Cable Systems Standard Recommended Procedure (SRP) 003-207 Issue 9. June 2004 Page 1 of15 Wall-mountable Interconnect Center WIC-012 WIC-024 Contents 1. 2. 3. 4. \I Related Literature ................................................................................................................... 2 Admonishments ....................................................................................................................... 2 General ............................................................................................................................................. 2 Components and Accessories ........................................................................................................... 3 2.1 Components ............................................................................................................................ 3 2.2 Accessories ............................................................................................................................... 4 2.3 Carton and IIardware Kit Contents ......................................................................................·.4 Tools and Materials .......................................................................................................................... 4 Installation ........................................................................................................................................ 5 4.1 Wall-mounting the WIC Unit ............................................................................................... 5 4.2 Installing Connector Panels .................................................................................................... 5 4.3 Installing Preconnectorized Cable ......................................................................................... 6 4.3.1 Strain-relieve Cable ...................................................................................................... 6 4.3.2 Strain-relieve Central Member, if necessary ................................................................ 6 4.3.3 Route Cable .................................................................................................................. 7 4.4 Installing Cable with Buffer Tube Fanout (BTF) Kits ........................................................... 8 4.4.1 Prepare the Cable ......................................................................................................... 8 4.4.2 Install the BTF Kits ...................................................................................................... 8 4.4.3 Strain-relieve the Cable ................................................................................................ 8 4.4.4 Route the Cable ............................................................................................................. 9 4.5 Installing Cable Using Splice Trays ..................................................................................... 10 4.5.1 Determine Orientation of Splice Tray ....................................................................... 10 4.5.2 Install Pigtails .............................................................................................................. 10 4.5.3 Prepare the Cable ....................................................................................................... 11 4.5.4 Strain-relieve the Cable ...............................................................................................11 4.5.5 Splice the Cable .......................................................................................................... 11 4.5.6 Secure Splice Tray ...................................................................................................... 12 4.6 Installing Pigtails to be Spliced in the WSC-OOI Unit........................................................ 12 4.7 Using the Optional Guards .................................................................................................. 13 4.7.1 WIC-GUARD ............................................................................................................ 13 4.7.2 WIC-I..AN-GUARD .................................................................................................. 13 4.8 Routing Patch Cords Gumpers) ..;......................................................................................... 14 Customer Service and Information ...................................................................................... 15 pin 003-207 Page 2 SRP 003-207 • Issue 9 • June 2004 Revision History Issue 9 8 7 6 5 4 3 2 1 Date Reason for Change 0612004 1012000 1111999 0111998 05/1996 0911994 06/1991 0211990 0411989 Include padlocking feature Updated corporate infonnation Removed references to total fiber count for the unit Updated corporate information Included instructions for quarter-turn latch Included instructions for fanout kits Changed length called-out in Figure 11 Combined instructions for WIC-001 and WIC-024 Initial release Related Literature SRP 003-052 SRP 001-274 EVO-108-EN Instruction, WSC-OO1 Instruction, Metal Splice Trays Specifications for Wall-mountable Interconnect Center Admonishments The precautionary terms used by Corning Cable Systems in its standard recommended procedures confonn to the guidelines expressed in the American National Standards Institute document (ANSI Z235) for hazard alert messages. Alerts are included in this instruction based on the following: DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. CAurION indicates a hazardous situation which, if not avoided, !!la.}:: result in minor or moderate injury. 1. GENERAL Two versions of the Wall-Mountable Interconnect Center (WIC) are available. The WIC-012 accepts two connector panels and the WIC-024 accepts four connector panels. The WIC unit is designed to accommodate two multiple fiber cables and multiple pigtail cables. The doors on both units are secured with a quarter-turn latch. An optional locking kit (pIn HDWR-LOCK­ KIT, purchased separately) is available when a key lock is desired. Both WIC units accept two Type 4R or four Type 2R splice trays. Wall-mountable Interconnect Center , Page 3 SRP 003-207 • Issue 9 • June 2004 2. COMPONENTS AND ACCESSORIES 2.1 Components Components of the WIC-024 are shown in Figure 1. Cable Entry Knockouts Strain-relief Bracket Connector Panels Knockout for Key Lock Identification Labels Figure 1 WIC-024 Components Wall-mountable Interconned Center Page 4 2.2 SRP 003-207 • Issue 9 • June 2004 Accessories. • A guard is available (pin WIC-GUARD or WIC-024-GUARD, purchased separately) to protect patch cord jumpers (Figure 2). • A guard with a hinged latching door is available (pin WIC-LAN-GUARD or WIC-024­ LAN-GUARD, purchased separately). The door provides easy patch cord jumper access (Figure 2). A jumper strain-relief bracket and strain-relief hardware are provided with the guard.· WIC-024-GUARD Figure 2 - Jumper Guards 2.3 Carton and Hardware Kit Contents Carton contents: • • (1) WIC unit (1) Hardware kit Hardware kit contents: • • • • • • • • • • • • • • 3. (2) #8 Flat washers .50 ft of 1/4 -inch Diameter slit grommet (.3 75ft with WIC-024) (12) Cable ties (16 with WIC-024) (2) #6 Flat washers (1)#10 Lock washer (1) .220 x .500 Washer (1) #6-32 Wing nut (6) #6-32 Nylon washers (4 with WIC-024) (2) #8-32 Hex nuts (1) #6-32 Hex nut (1) 10-32 x .375 Phillips-head screw (1) 8-32 x.5 Phillips-head screw (WIC-024 only) (2) Splice shelf clamps (for central member strain-relief) (8) #4-40 Nuts (WIC-024 only) TOOLS AND MATERIALS The normal complement of hand tools are required to install the WIC units. Wall-mountable Interconnect Center Pages SRP 003-207 • Issue 9 • June 2004 4. INSTALLATION 4.1 WaIl-mounting the WIC Unit If you are installing two WICs in a cross-connect application, install connector panels in only one WIC and fasten the units together, face-to-face, using 8-32 hardware (Figure 3). Step 1 Select a flat vertical surface to prevent warping. Determine the mounting location. Step 2 . Open the door and use a pencil to mark the location of the mounting holes on the wall. Mounting hardware is not provided. Step 3 Drive the top two screws in at these locations leaving a 1I8-inch gap between the wall and the screw head. Step 4 Hang the unit on the screws and tighten the screws. Step S . Drive the remaining two screws through the mounting holes in the bottom of the unit. Figure 3 - Cross-connect Con~guration 4.2 Installing Connector Panels Secure the connector panels to the face of the unit using the screws provided with the connector panels. If padlocking is desired, turn one of the panels 180 degrees and install it as shown in Figure 4. Orientation of Connector Panel for Padlock Installation Location for Screws to Attach 4--"";:; Two WIC Units Together for a Cross-connect Confignration Figure 4 Connector Panels Wall-mountable Interconnect Center Page 6 4.3 SRP 003-207 • Issue 9 • June 2004 Installing Preconnectorized Cable NOTE: Fiber optic cable is sensitive to excessive pulling, bending and crushingforces. Consult the cabk specification sheetfor the cable you are installing. Do not bend the cable more sharply than the minimum recommended bend radius. Do not apply more pullingforce to the cable than specified. Do not crush the cable or allow it to kink. Doing so may cause damage that can alter the transmission characteristics ofthe cable - the cable may have to be replaced. The following steps describe strain-relieving the cable and central member, if applicable. When you are instructed to strain-relieve the cable, refer to this section for instructions on doing so. 4.3.1 Strain-relieve Cable Step 1 Remove knock-out from unit. Attach the slit grommeting around the edge of the knockout and cut the grommet to fit. Step 2 Remove the strain-relief bracket from the unit. Step 3 Secure the cable sheath to the bracket using cable ties (Figure 5). 4.3.2 Strain-relieve Central Member, if necessary Step 1 Insert the provided screw through the flat M6 washer and the u-shaped washer, then through a hole in the strain-relief bracket. Step 2 Start the 8-32 hex nut onto the screw and tighten a couple of turns. Step 3 IT aramid yarn is present, wrap the in a clockwise direction around the screw and beneath the u-shaped washer. Step 4 Insert the central member between the flat washer and the u-shaped washer and . tighten the 8-32 screwlhex nut assembly. . Step S Trim excess central member and yarn as needed . Buffer Tubes Central Member Figure 5 Wall-mountable Interconned Center Strain-relieve Cable Page 7 SRP 003-207 • Issue 9 • June 2004 4.3.3 Route Cable Step 1 Reinstall the strain-relief bracket in the WIC unit. Step 2 Route the cable around the radius guides (Figure 6). Step 3 Clean connectors and install into connector panels. !t\ CAUTION: Isopropyl alcohol is flammable with a flashpoint at 50 R It can cause ill 0 irritation to eyes on contact. In case ofeye contact, flush eyes with water for at least 15 minutes. Inhalingfomes may induce mild dizziness. In case ofingestion, consult a physician. NOTE: Obey the following precautions in order not to damage the suiface ofthe connector and make it unusable: • Use a clean tissue soaked in alcohol to gently clean the connector. Do not press heavily on it as you clean. • Dry the connector prior to installation by using a dry tissue or blowing it dry with compressed air. • Clean all areas that will contact the connector adapter. • Do not force the connector into the receptacle. If the connector does not fit easily into the receptacle, back it out and reinstalL Top Cable Entry Bottom Cable Entry Figure 6 - Cable Routing Wall-mountable Interconnect Center Page 8 4.4 SRP 003-207 • Issue 9 • June 2004 Installing Cable with Buffer Tube Fanout (BTF) Kits 4.4.1 Prepare the Cable CAUTION: The wearing ofsafety glasses to protect the eyes from accidental injury is strongly recommended when handling chemicals and cuttingfiber. Pieces ofglass fiber are very sharp and can damage the cornea easily. CAUTION: The wearing ofsafety gloves to protect handsfrom accidental injury is strongly recommended when using sharp instruments. Remove cable sheath as shown in Figure 7. Do not expose the bare fiber until you are ready to terminate it. IMPORTANT: 7ypicallengths are illustrated. Since the actual application may vary, it is recommended to route the buffer tubes as they will lie in the unit to detennine actual strip lengths before cutting fibers. Central Member _ _ 10 em (4 in.) 1-+----BufferTubes - - ­ 137 em (54 in.) .... -I Bare Fibers 89 em (35 in.) Figure 7 - Sheath Removal for Fanout Application 4.4.2 Install the BTF Kits &• WARNING: Cleaved glass fibers are very sharp and can pierce the skin easily. Do not let cut pieces offiber stick to your clothing or drop in the work area where they can cause injury later. Use tweezers to pick up cut or broken pieces ofthe glassfibers and place them on a loop oftape kept for that purpose alone. Good housekeeping is very important. Install buffer tube fanouts (purchased separately) onto the buffer tubes as described in instructions supplied with the BTF kits. Install the connectors per the manufacturer's instructions. 4.4.3 Strain-relieve the Cable Strain-relieve the cable and central member, if applicable, as described in Sections 4.3.1 and 4.3.2. Wall-mountable Interconnect Center Pageg SRP 003-207 • Issue 9 • June 2004 4.4.4 Route the Cable Step 1 Route the buffer tubes three times around the radius guides. Step 2 Secure the BTF assemblies in the strain-relief bracket as shown in Figure 8 by sliding the BTF assembly mounting extensions into the slot in the bracket. Step 3 Install a cable tie to keep the BTF assemblies from sliding out. Step 4 Route the connectorized fibers around the routing guides (Figure 9). Step 5 Clean connectors as described in Section 4.3.3 and install into the connector panels. Fanout Body Figure 8 Secure Fanout Bodies to Bracket Fanout Body Fanout Body Figure 9 - Route Cable Wall-mountable Interconnect Center Page 10 4.5 SRP 003-207 • Issue 9 • June' 2004 Installing Cable Using Splice Trays 4.5.1 Determine Orientation of Splice Tray Place the splice tray on the stud in the unit and route cable to the tray to determine the length required for routing. The orientation of the splice tray is dependent upon the direction of cable entry into the WIC (Figure 10). Splice Tray Orientation for Bottom Entry of Cable into WIC Splice Tray Orientation for Top Entry of Cable into WIC 4.5.2 Figure 10 Splice Tray Orientation Install Pigtails Step 1 Clean connectors as described in Section 4.3.3 and install pigtails into the connector panels. Step 2 Route the pigtails twice around the radius guides and to the splice tray (Figure 11). Step 3 Mark the pigtails where they enter the tray. Strip pigtails at this location. Pigtail Routing for Bottom Entry of Cable into WIC Pigtail Routing for Bottom Entry of Cable into WIC Figure 11 - Route Pigtails Around Guides Wall-mountable Interconnect Center Page 11 SRP 003-207 • Issue 9 • June 2004 4.5.3 Prepare the Cable Remove cable sheath as shown in Figure 12. Do not expose the bare fiber until you are ready to terminate it. IMPORTANT: Typical lengths are illustrated. Since the actual application may vary, it is recommended to route the buffir tubes as they will lie in the unit to determine actual strip lengths before cuttingfibers. 140 cm (55 in.) Top Entry into Tray 114 em (45 in.) Bottom Entry into Tray Refer to Instruction Provided w:ith Splice Tray for Length Required Inside Splice Tray Figure 12 - Sheath Removal for Splice Tray Application 4.5.4 Strain-relieve the Cable Strain-relieve the cable and central member, if applicable, as described in Sections 4.3.1 and 4.3.2. 4.5.5 Splice the Cable Step 1 Step 2 Route at least one full loop of buffer tubes around the radius guides and into the splice tray. Do not bend cable too sharply. Mark the cable where it enters the splice tray. Step 3 Bring splice tray (pin M67 -110 shown) and fibers to splicer. Step 4 Strip buffer tubes at the mark made in Step 2. Step 5 Secure buffer tubes and pigtails to splice trays as described in the procedure provided with the splice tray. Step 6 Splice buffer tube fibers to pigtail fibers as described for the splicing method you are using (Figure 13 ­ slack loops not shown for clarity). ,, ,, i I I ; ti:====="--..tr",/ " Figure 13 Splice Pigtails to Buffer Tube Wall-mountable Interconnect Center Page 12 SRP 003-207 • Issue 9 • June 2004 4.5.6 Secure Splice Tray Install the splice tray in the \VIC unit and secure the tray onto the stud with the nylon wing nut. Figure 14 - Secure Splice Tray 4.6 Installing Pigtails to be Spliced in the WSC-OOI Unit Figure 15 illustrates common WSC-\VIC cross-connect configurations. Refer to the procedure provided with the WSC-OO 1 for detailed instructions. Step 1 Clean connectors as described in Section 4.3.3 and install pigtails into the connector panel. Step 2 Route the pigtails around the radius guides in the \VIC and then route on to the WSCunit. Step 3 Secure the pigtails to the strain-relief bracket use a loosely installed cable tie. Patch Cords Incoming Cable t t Patch Cords Incoming Cable Figure 15 - WSCfWIC Mounting Configuration Wall-mountable Interconned Center Page 13 SRP 003-207 • Issue 9 • June 2004 4.7 Using the Optional Guards 4.7.1 WIC-GUARD Step 1 Loosen the two wall-mount screws on the face of the 'WIC unit and slide the guard under the two screws. Step 2 Retighten the screws to attach the guard to the unit. 4.7.2 WIC-LAN-GUARD Hardware required to mount the guard to the wall is not provided. Step 1 Attach the 'WIC-LAN-GUARD to the face of the 'WIC unit using the mating holes between both units (using hardware provided). Step 2 Select a flat vertical surface to prevent warping. Determine the mounting location. Step 3 Open the door and use a pencil to mark the location of the mounting holes on the walL Mounting hardware is not provided. Step 4 Drive the top two screws in at these locations leaving a liS-inch gap between the wall and the screw head. Step 5 Hang the unit on the screws and tighten the screws. Step 6 Drive the remaining two screws through the mounting holes in the bottom of the unit. Figure 16 illustrates configurations using the optional guards. Incoming Cable t Patch Cords t Patch Cords - - \((1 - .... ~ ~ ~I ~ WSC-OOI LJ t Incoming Cable t Patch Cords Incoming Cable Figure 16 - Patch Cord Routing Wall-mountable Interconnect Center Page 14 4.8 SRP 003-207 • Issue 9 • June 2004 Routing Patch Cords (Jumpers) Step 1 Clean connectors as described in Section 4.3.3 and install patch cords into the connector paneL Step 2 Route patch cords appropriately. Maintain cable bend radius when routing to adjacent hardware (Figure 17). Step 3 Record fiber identification information on the labels attached to the inside of the door. WIC WI / Storage Center Figure 17 Wall-mountable Interconned Center Patch Cord Bend radius SRP 003-207 • issue 9 • May 2004 PagelS Customer Service and Information Telephone:----------------------------------------------------------­ Customer Service-US or Canada: 1-800-743-2671 International: +1-828-901-5000 Fax: +1-828-325-5060 Correspondence:------------------------------------------------------------­ I~orning ~~Box489 . Hickory, Cable Systems LLC NC 28603-0489 USA ProductInformation:--------------------------------------------------------­ http://www.coming.comlcablesystems CORNING Olsawerlng Beyond Imagination Corning Cable Systems reserves the right to improve, enhance and modify the features and specifications of Corning Cable Systems' products without prior notification. Discovering Beyond Imagination is a trademark of Corning Incorporated. All other trademarks are the properties of their respective owners. Corning Cable Systems is ISO 9001 certified. © 1989-91, 1994,1996,1998,1999,2004 Corning Cable Systems. All rights reserved. Published in the USA. pin 003-207 I June 2004