Transcript
https://www.phoenixcontact.com/us/produkte/2986562
Coupling relay - PSR-SPP- 24DC/ETP/1X1 - 2986562 Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's documentation. Our General Terms of Use for Downloads are valid (http://download.phoenixcontact.com)
Coupling relay for SIL 3 low demand applications, couples digital output signals to the periphery, 1 enabling current path, module for F&G applications, test pulse filter, plug-in spring-cage connection, 17.5 mm width
Product Features Narrow 17.5 mm housing Up to SIL 3 according to IEC 61508 Long service life thanks to filtering of controller test pulses One enabling current path Couples digital output signals from failsafe controllers to I/O devices (valves, etc.) for electrical isolation and power adaptation
Key commercial data package_quantity
1
GTIN
4046356540780
Technical data Note: Utilization restriction
EMC: class A product, see manufacturer's declaration in the download area
Dimensions Width
17.5 mm
Height
112 mm
Depth
114.5 mm
Ambient conditions Ambient temperature (operation)
-20 °C ... 55 °C
Ambient temperature (storage/transport)
-40 °C ... 65 °C
Max. permissible humidity (storage/transport)
≤ 85 % (Condensation and icing are not permitted based on the average annual temperature)
Max. permissible humidity (storage/transport)
≤ 85 % (On an individual basis, condensation and icing are not permitted)
Shock
15 g
Vibration (operation)
2g
Input data Nov 10, 2013 1 / 5
https://www.phoenixcontact.com/us/produkte/2986562
Coupling relay - PSR-SPP- 24DC/ETP/1X1 - 2986562 Technical data Input data Nominal input voltage UN
24 V DC
Input voltage range
20.4 V DC ... 26.4 V DC
Input voltage range in reference to UN
0.85 ... 1.1
Typical input current at UN
75 mA
Typical inrush current
200 mA
Typical response time
30 ms
Recovery time
1s
Output data Contact type
1 enabling current path
Contact material
AgCuNi, + 0.2 µm Au
Maximum switching voltage
250 V AC (125 V DC)
Minimum switching voltage
15 V AC/DC
Limiting continuous current
5 A (N/O contact, pay attention to the derating)
Maximum inrush current
5A
Inrush current, minimum
100 mA
Sq. Total current
25 A (ITH = I1 + I2 + ... + IN )
Switching capacity min.
1.5 W
2
2
2
2
2
General Relay type
Electromagnetic dust-proof relay
Mechanical service life
Approx. 10 cycles
Mounting position
Any
Assembly instructions
In rows with zero spacing
Name
Air and creepage distances between the power circuits
Standards/regulations
DIN EN 50178
Rated surge voltage / insulation
6 kV/safe isolation
Rated insulation voltage
250 V AC
Pollution degree
2
Surge voltage category
III
7
Connection data Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
1.5 mm²
Conductor cross section stranded min.
0.2 mm²
Conductor cross section stranded max.
1.5 mm²
Conductor cross section AWG/kcmil min.
24
Conductor cross section AWG/kcmil max
16
Stripping length
8 mm
Connection method
Spring-cage conn.
Nov 10, 2013 2 / 5
https://www.phoenixcontact.com/us/produkte/2986562
Coupling relay - PSR-SPP- 24DC/ETP/1X1 - 2986562 classifications eCl@ss eCl@ss 4.0
27371102
eCl@ss 4.1
27371102
eCl@ss 5.0
27371901
eCl@ss 5.1
27371901
eCl@ss 6.0
27371819
eCl@ss 7.0
27371819
eCl@ss 8.0
27371819
ETIM ETIM 2.0
EC001449
ETIM 3.0
EC001449
ETIM 4.0
EC001449
ETIM 5.0
EC001449
UNSPSC UNSPSC 6.01
30211901
UNSPSC 7.0901
39121501
UNSPSC 11
39121501
UNSPSC 12.01
39121501
UNSPSC 13.2
39121501
approvals Functional Safety /
Approval details Functional Safety
Drawings
Nov 10, 2013 3 / 5
https://www.phoenixcontact.com/us/produkte/2986562
Coupling relay - PSR-SPP- 24DC/ETP/1X1 - 2986562 Diagram
Circuit diagram
Nov 10, 2013 4 / 5
https://www.phoenixcontact.com/us/produkte/2986562
Coupling relay - PSR-SPP- 24DC/ETP/1X1 - 2986562 Circuit diagram
© Phoenix Contact 2013 - all rights reserved http://www.phoenixcontact.com
Nov 10, 2013 5 / 5