CWS Series
INSTALLATION GUIDE
CWS Series
CO2-Based Occupancy Sensing Switch Installer's Specifications Power Supply 3-wire (terminal blocks) 24VAC or 12-30VDC Response Time 2 min to 90% of saturated level; 4 min to 90% of base level Lifespan 5 years at room temperature Detection Range 400-3000 ppm CO2 Operating Temperature Range 10°C to 35°C (50°F to 95°F) Accuracy ±150 ppm@25°C (77°F) (±4.5 ppm/°C/F) Relay Setpoint Jumper selectable: 800 ppm, 1000 ppm, 1500 ppm, or 2000 ppm Relay Hysteresis 10% of setpoint Output Relay contact, normally open (Form A), 1A@30VDC, 0-3V (used for testing verification) Status Indicators Solid Green = Below threshold; Red = Above threshold; Flashing Green = Warming up; Flashing Red = Sensor failure
/05*$& t t t t t
5IJTQSPEVDUJTOPUJOUFOEFEGPSMJGFPSTBGFUZBQQMJDBUJPOT %POPUJOTUBMMUIJTQSPEVDUJOIB[BSEPVTPSDMBTTJmFEMPDBUJPOT 3FBEBOEVOEFSTUBOEUIFJOTUSVDUJPOTCFGPSFJOTUBMMJOH UIJTQSPEVDU 5VSOPõBMMQPXFSTVQQMZJOHFRVJQNFOUCFGPSFXPSLJOHPOJU 5IFJOTUBMMFSJTSFTQPOTJCMFGPSDPOGPSNBODFUPBMMBQQMJDBCMFDPEFT
Product Identification
Warm-up time is approximately 2 hrs (typical readings are 400-425 ppm). For optimal performance, allow 5 days to establish background calibration. Any test gas must be air balanced. DO NOT use nitrogen balanced gas.
quick install 1. Choose an indoor location to mount the CWS. 2. Wire the device to the power source and the control system.
CWS
3. Set the relay jumper to the desired setpoint. 4. Install the cover in the wall using the screws provided.
Dimensions
board diagram 0.3" (6 mm)
1.4" (35 mm)
1.9" (49 mm)
GND
OUTPUT
V+
4.5" (114 mm)
Relay Output
OUT
3.3" (83 mm)
RESET
2000 1500 1000 800
Relay Jumpers
Board (wall-facing)
2.8" (70 mm)
Z204113-0C
PAGE 1
0.5" (13 mm)
©2008 Veris Industries USA 800.354.8556 or 503.598.4564 /
[email protected]
Reset Button
07082
6%2)3 ).$5342)%3
INSTALLATION GUIDE
CWS Series
installation
operation
1. Choose an indoor location to mount the sensor, away from ventilation sources, radiant heat, vibration, or direct sunlight. Position the sensor vertically on the wall, 4 1/2 feet above the floor.
The wall mount CWS Series CO2-based occupancy sensor utilizes solid electrolyte CO2 sensing technology that provides a low cost solution for improving air quality. The self-calibrating sensor allows for easy installation and setup. The CWS is equipped with an adjustable setpoint relay for direct control and alarm applications. There are four jumper settings to program the setpoint alarm relay and an LED for local status indication.
2. Wire the device to the power source and the control system. The relay output leads are not polarity sensitive.
+
POWER SOURCE 12-30VDC/24VAC
-
V+ GND OUT
CONTROL SYSTEM
RELAY OUTPUT
1. If necessary, the baseline can be manually reset. Allow the CWS to warm up for 2 hours. Then push the Reset button when the ambient CO2 level is near 400 ppm. This is not required at setup.
(0-3VDC Output)
OUTPUT
RESET
CO2 Contact Closure
2. To field test the CWS sensor, measure the voltage between the indicated terminals. 3. Set the relay setpoint to the desired CO2 concentration.
RESET
V+ GND OUT
2000 1500 1000 800
(0-3VDC Output) 3000 ppm
4. Install the cover on a single gang electrical box using the screws provided. 0.3" 1.4" (35 mm)
(6 mm)
1.9" (49 mm)
4.5" (114 mm)
3.3" (83 mm)
2.8" (70 mm)
0.5" (13 mm)
CO2 concentration
0 ppm 0
1
2
3
Volts DC Note:
Z204113-0C
PAGE 2
0 Volts represents 0 ppm CO2. 3 Volts represents 3000 ppm CO2. This product cannot be field calibrated.