Preview only show first 10 pages with watermark. For full document please download

Cyberpower Um Cp1000avrlcd

   EMBED


Share

Transcript

4 LCD Display Toggle/Selected Switch The switch can be used to select the LCD display contents including Input Voltage, Output Voltage, and Estimated Run Time. The toggle frequency is set to one time per second. Holding the switch for more than two seconds while running on battery will silence the buzzer. 5 Battery and Surge Protected Outlets The unit has battery powered/surge suppression outlets for connected equipment to ensure temporary uninterrupted operation of your CP850AVRLCD/CP1000AVRLCD/CP1350AVRLCD/CP1500AVRLCD equipment during a power failure. (DO NOT plug a laser printer, paper shredder, copier, space heater, vacuum, sump pump or other large electrical devices into the “Battery and Surge Protected Outlets”. The power demands of these devices may overload and User’s Manual damage the unit.) K01-0000002-02 6 Full-Time Surge Protection Outlets The unit has surge suppression outlets. PRODUCT REGISTRATION 7 Wiring Fault Indicator Thank you for purchasing a CyberPower product. Please take a few minutes to register your product at www.cpsww.com/registration. This LED indicator will illuminate to warn the user that a wiring problem exists, such as bad ground, missing ground or reversed wiring. Registration certifies your product's warranty, confirms your ownership in the event of a product loss or theft and entitles you to free technical this is illuminated, disconnect all electrical equipment from the outlet and have an electrician verify the outlet is properly wired. The unit will not provide surge protection without being plugged into a grounded and properly wired wall outlet. support. Register your product now to receive the benefits of CyberPower ownership. 8 IMPORTANT SAFETY WARNINGS 9 10 Read this manual thoroughly before attempting to unpack, install, or operate your UPS. Serial/USB Ports to PC The ports allow connection and communication between the USB/DB-9 port on the computer and the UPS unit. Note: Only one of these two CAUTION! To prevent the risk of fire or electric shock, install in a temperature and humidity controlled indoor area free of conductive (Please see specifications for acceptable temperature and humidity range). ports can be used to communicate with your computer at one time. 11 CAUTION! To reduce the risk of electric shock, do not remove the cover except to service the battery. Turn off and unplug the unit before servicing the batteries. There are no user serviceable parts inside except for the battery. 12 CAUTION! The UPS must be connected to an AC power outlet with fuse or circuit breaker protection. Coax/Cable/DSS Surge Protection The Coax/Cable/DSS protection ports will protect any cable modem, CATV converter, or DSS receiver. CAUTION! Hazardous live parts inside can be energized by the battery even when the AC input power is disconnected. Outlet Designed for AC Adapters The unit has one outlet spaced to allow AC power adapter blocks to be plugged into the UPS without blocking adjacent outlets. Do not plug into an outlet that is not 13 If you need to de-energize this equipment, turn off and unplug the unit. Input Power Cord Connect the unit into an AC outlet. CAUTION! To avoid electric shock, turn off the unit and unplug it from the AC power source before servicing the battery or installing a computer component. REPLACING THE BATTERY CAUTION! Read and follow the IMPORTANT SAFETY INSTRUCTIONS before servicing the battery. Service the battery under the supervision of CAUTION! To reduce the risk of fire, connect only to a circuit provided with 20 amperes maximum branch circuit over current protection in accordance with the National Electric Code, ANSI/NFPA 70. personnel knowledgeable of batteries and their precautions. CAUTION! Use only the specified type of battery. See your dealer for replacement batteries. DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT! CyberPower Systems does not sell products for life support or medical applications. Circuit Breaker Located on the back of the UPS, the circuit breaker serves to provide overload and fault protection. This manual contains important safety instructions. Please read and follow all instructions carefully during installation and operation of the unit. grounded. Communication Protection Ports Communication protection ports will protect any standard modem, fax, telephone line, network or Ethernet connection (RJ11/RJ45). (SAVE THESE INSTRUCTIONS) contaminants. If DO NOT use in any circumstance that would affect the operation and safety of life support equipment, medical applications, or patient care. CAUTION! The battery may present a risk of electrical shock. Do not dispose of battery in a fire as it may explode. Follow all local ordinances regarding proper disposal of batteries. Almost any retailer that sells lead-acid batteries collects used batteries for recycling, as required by most state laws. DO NOT USE WITH OR NEAR AQUARIUMS! To reduce the risk of fire or electric shock, do not use with or near an aquarium. Condensation from the aquarium can cause the unit to short out. CAUTION! Do not open or mutilate the batteries. Released electrolyte is harmful to skin and eyes and may be toxic. CAUTION! A battery can present a high risk of short circuit current and electrical shock. Take the following precautions before replacing the DO NOT USE THE UPS ON ANY TRANSPORTATION! To reduce the risk of fire or electric shock, do not use the unit on any transportation such as airplanes or ships. The effect of shock or vibration caused during transit and the damp environment can cause the unit to short out. INSTALLING YOUR UPS SYSTEM UNPACKING battery: 1. Remove all watches, rings or other metal objects. 2. Only use tools with insulated handles. 3. Do not lay tools or metal parts on top of battery or any terminals. 4. Wear rubber gloves and boots. 5. Inspect the UPS upon receipt. The box should contain the following: (a) UPS unit (b) User’s manual (c) USB A+B type cable *PowerPanel® Personal Edition software is available on our website. Please visit www.cpsww.com and go to the Software Section for free download. Determine if the battery is inadvertently grounded. If grounded, remove the source of ground. CONTACT WITH GROUNDED BATTERYCAN RESULT IN ELECTRICAL SHOCK! BATTERY REPLACEMENT PROCEDURE: 1. Turn off and unplug all connected equipment. OVERVIEW 2. Turn the UPS off and unplug it from the AC power source. The UPS provides complete power protection from utility power that is not always consistent. The 3. Turn the UPS upside down. CP850/1000/1350/1500AVRLCD features 1080/1080/1500/1500 Joules of surge protection. The units 4. Remove the retaining screw. provide long lasting battery backup during power outages with maintenance free batteries. The 5. Slide the battery compartment cover completely off of the unit. CP850/1000/1350/1500AVRLCD ensures consistent power to your computer system and includes software 6. Remove the batteries from the compartment. that will automatically save your open files and shutdown your computer system during a utility power loss. 7. Disconnect the battery wires from the batteries. 8. Install the replacement batteries by connecting the red wire (+) and black wire (-) to the same color connectors from the battery pack. AUTOMATIC VOLTAGE REGULATOR 9. Put the batteries back into the compartment. The CP850/1000/1350/1500AVRLCD stabilizes inconsistent utility power voltage to nominal levels that are safe for equipment. Inconsistent 10. Slide back the battery compartment cover and tighten the retaining screws. incoming utility power may be damaging to important data files and hardware, but with Automatic Voltage Regulation (AVR), damaging voltage 11. Recharge the UPS for 8-16 hours to fully charge the battery. levels are corrected to safe levels. AVR automatically increases low utility power or decreases high utility power to a consistent and safe 110/120 volts. HOW TO DETERMINE THE POWER REQUIREMENTS OF YOUR EQUIPMENT 1. Ensure that the equipment plugged into the outlet does not exceed the UPS unit’s rated capacity (850VA/510W for CP850AVRLCD, , 1000VA/600W for CP1000AVRLCD, 1350VA/810W for CP1350AVRLCD, 1500VA/900W for CP1500AVRLCD). If the rated capacities of the unit are exceeded, an overload condition may occur and cause the UPS unit to shut down or the CP850/1000AVRLCD circuit breaker to trip. 2. There are many factors that can affect the amount of power that your computer system will require. It is suggested that the load placed on the battery outlets not exceed 80% of the unit’s capacity. HARDWARE INSTALLATION GUIDE 1. Your new UPS may be used immediately upon receipt. However, after receiving a new UPS, to ensure the battery’s maximum charge capacity, it is recommended that you charge the battery for at least 8 hours. Your UPS is equipped with an auto-charge feature. When the UPS is plugged into an AC outlet, CP850/1000AVRLCD the battery will automatically charge whether the UPS is turned on or off. CP1350/1500AVRLCD Batteries are considered HAZARDOUS WASTE and must be disposed of properly. REMINDER: Most retailers that sell lead-acid batteries collect used batteries for recycling, as required by local regulations. 2. With the UPS unit turned off and unplugged, connect your computer, monitor, and any other peripherals requiring battery backup into the DEFINITIONS FOR ILLUMINATED LED INDICATORS battery power supplied outlets. DO NOT plug a laser printer, paper shredder, copier, space heater, vacuum, sump pump or other large electrical devices into the “Battery and Surge Protected Outlets”. The power demands of these devices may overload and damage the unit. 3. To protect a fax, phone or modem, connect a telephone cable or network cable from the wall jack outlet to the IN CONDITION jack of the UPS. Connect a telephone cable or network cable from the OUT jack of the UPS to a fax machine, Power ON Wiring Fault Alarm On Off Off On Off telephone, modem, or network devices. 4. Plug the UPS into a 2 pole, 3 wire grounded receptacle (wall outlet). Make sure the wall branch outlet is Normal protected by a fuse or circuit breaker and does not service equipment with large electrical demands (e.g. air conditioner, copier, etc…). The warranty prohibits the use of extension cords, outlet strips, and surge strips. 5. Press the power switch to turn the unit on. The Power On indicator light will illuminate and the unit will “beep”. Beep twice every 30 seconds Utility Failure- The UPS is providing power to battery power-supplied outlets from its battery. If an overload is detected, an audible alarm will sound and the unit will emit one long beep. To correct this, turn the UPS off and unplug at least one piece of equipment from the battery power supplied outlets. Make sure the circuit breaker is depressed and then turn the UPS on. On Off 6. To maintain optimal battery charge, leave the UPS plugged into an AC outlet at all times. Rapid Beeping every 1/2 second 7. To store the UPS for an extended period, cover it and store with the battery fully charged. While in storage, recharge the battery every three Utility Failure- The UPS is providing battery power. Rapid beeping indicates the unit will run out of power shortly. Battery Overload - Occurs when connected equipment exceeds the months to ensure battery life. Off 8. Ensure the wall outlet and UPS are located near the equipment being attached for proper accessibility. Off Constant tone BASIC OPERATION listed capacity of the UPS. Turn the UPS off, unplug at least one piece of equipment from battery outlets, wait 10 seconds, reset the circuit breaker and turn the unit on. Electrical Wiring Fault - This indicates a wiring problem with the DESCRIPTION On/Off On None AC outlet such as bad ground, missing ground, or reversed wiring. Disconnect all electrical equipment from the outlet and have an electrician check the outlet to insure proper wiring. DEFINITIONS FOR ILLUMINATED LCD INDICATORS 1. INPUT voltage meter: This meter measures the AC voltage that the UPS system is receiving from the utility wall outlet. The UPS is designed, through the use of automatic voltage regulation, to continuously correct output voltage to connected equipment to a safe 110/120 1 Power Switch CP850/1000AVRLCD voltage output range. In the event of a complete CP1350/1500AVRLCD power loss, severe brownout, or over-voltage, the Used as the master on/off switch for equipment connected to the battery power supplied outlets. 2 UPS relies on its internal battery to supply Power On Indicator consistent 110/120 output voltage. The INPUT This LED is illuminated when the utility power is normal and the UPS outlets are providing power, free of surges and spikes. 3 voltage meter can be used as a diagnostic tool to LCD module display High resolution and intelligent LCD display shows all the UPS information using icons and messages. the “Definitions for Illuminated LCD Indicators” section below. For more information please review identify poor-quality input power. 2. OUTPUT voltage meter: This meter measures, in real time, the AC voltage that the UPS system is providing to the computer, such as normal line mode, AVR mode, transformer to regulate voltage and provide “safe” power. Since utility power is normal over 88% of the time, the GreenPower UPS™ and battery backup mode. (Note: The OUTPUT voltage meter shows the status of the battery backup outlets.) operates primarily in its efficient bypass mode. 3. 4. ESTIMATED RUN TIME: The GreenPower UPS™ is also manufactured in accordance with the Restriction on Hazardous Substances (RoHS) directive making This displays the run time estimate of the UPS with current battery capacity and load. it one of the most environmentally-friendly on the market today. NORMAL icon: Limited Warranty and Connected Equipment Guarantee This icon appears when the UPS is working under normal conditions. 5. Read the following terms and conditions carefully before using the CyberPower CP850/900/1000/1100/1350/1500AVRLCD (the BATTERY icon: During a severe brownout or blackout, this icon appears and an alarm sounds (two short beeps followed by a pause) to indicate the UPS is “Product”). By using the Product you consent to be bound by and become a party to the terms and conditions of this Limited Warranty operating from its internal batteries. During a prolonged brownout or blackout, the alarm will sound continuously (and the and Connected Equipment Guarantee (together referred to as this “Warranty”). If you do not agree to the terms and conditions of this BATT.CAPACITY meter shows one 20% capacity segment shaded) to indicate the UPS’s batteries are nearly out of power. You should Warranty, you should return the Product for a full refund prior to using it. save files and turn off your equipment immediately or allow the software to shut the system down. 6. Who is Providing this Warranty? AVR (Automatic Voltage Regulation) icon: This icon appears whenever your UPS is automatically correcting low AC line voltage without using battery power. This is a normal, automatic operation of your UPS, and no action is required on your part. 7. What Does This Warranty Cover? SILENT MODE icon: This icon appears whenever the UPS is in silent mode. The buzzer does not beep during silent mode until the battery reaches low capacity. 8. CyberPower Systems (USA), Inc. (“CyberPower”) provides this Limited Warranty. This warranty covers defects in materials and workmanship in the Product under normal use and conditions. It also covers equipment that was connected to the Product and damaged because of the failure of the Product. OVER LOAD icon: What is the Period of Coverage? This icon appears and an alarm sounds to indicate the battery-supplied outlets are overloaded. To clear the overload, unplug some of your This warranty covers the Product for three years and connected equipment for as long as you own the Product. equipment from the battery-supplied outlets until the icon turns off and the alarm stops. 9. 10. FAULT icon: Who Is Covered? This icon appears if there is a problem with the UPS, Contact CyberPower Systems at [email protected] for further help and support. This warranty only covers the original purchaser. Coverage ends if you sell or otherwise transfer the Product. BATT. CAPACITY meter: This meter displays the approximate charge level (in 20% increments) of the UPS’s internal battery. During a blackout or severe brownout, the UPS switches to battery power, the BATTERY icon appears, and the charge level decreases. 11. How Do You Get Warranty Service? 1. LOAD CAPACITY meter: This meter displays the approximate output load level (in 20% increments) of the UPS battery outlets. TROUBLESHOOTING 2. Visit our web site at http://www.cpsww.com/support or Call us at (877) 297-6937. 3. If your product requires warranty service you must provide a copy of your dated purchase receipt or invoice. How Do You Open A Connected Equipment Claim? 1. Problem Possible Cause Solution Turn the UPS off and unplug at least one piece of equipment. Wait 10 seconds, reset the circuit breaker by depressing the button, and then turn the UPS on. Circuit breaker has tripped due to an overload. The UPS does not perform expected runtime. The UPS will not turn on. Call us at (877) 297-6937 or write to us at Cyber Power Systems (USA), Inc., 4241 12th Ave. E., STE 400, Shakopee, MN 55379, or send us an e-mail message at [email protected] for instructions, within 10 days of the occurrence. 2. Circuit breaker button is projecting from the back of the unit. Before contacting CyberPower, identify Your Product model number, the Purchase Date, and each item of Connected Equipment (E.G. Computer tower, Computer Monitor, Ink Jet Printer, Cable Modem, etc). When you contact CyberPower, identify the Product, the Purchase Date, and the item(s) of Connected Equipment. Have information on all applicable insurance or other resources of recovery/payment that are available to the Initial Customer and Request a Claim Number. 3. You must provide a dated purchase receipt (or other proof of the original purchase) and provide a description of the damage to your connected equipment. Battery not fully charged. Recharge the battery by leaving the UPS plugged in. Battery is worn out. Contact CyberPower Systems about replacement batteries at [email protected] The on/off switch is designed to prevent damage from rapidly turning it off and on. Turn the UPS off. Wait 10 seconds and then turn the UPS on. The unit is not connected to an AC outlet. The unit must be connected to a 110/120V 60Hz outlet. The battery is worn out. Contact CyberPower Systems about replacement batteries at [email protected] Mechanical problem. Contact CyberPower Systems at [email protected] The USB / serial cable is not connected. Connect the USB / serial cable to the UPS unit and an open USB / serial port on the back of the computer. You must use the cable that came with the unit. If it appears that our Product failed to protect any equipment plugged into it, we will also send you forms for making your claim for the The USB / serial cable is connected to the wrong port. Check the back of the computer for an additional USB / serial port. Move the cable to this port. another a third-party valuation guide, or eBay, craigslist, or other source to establish that amount. Our maximum liability is limited to The unit is not providing battery power. Shutdown your computer and turn the UPS off. Wait 10 seconds and turn the UPS back on. This should reset the unit. 4. Pack and ship the product to CyberPower and, if requested, the item(s) of Connected Equipment, a repair cost estimate for the damage to the Connected Equipment, and all claim forms that CyberPower provides to you. Show the Claim Number on the shipping label or include it with the product. You must prepay all shipping costs, you are responsible for packaging and shipment, and you must pay the cost of the repair estimate. How Long Do I Have To Make A Claim? All claims must be made within ten days of the occurrence. What Will We Do To Correct Problems? CyberPower will inspect and examine the Product. If the Product is defective in material or workmanship, CyberPower will repair or replace it at CyberPower's expense, or, if CyberPower is unable to or decides not to repair or replace the Product (if defective) within a reasonable time, CyberPower will refund to you the full purchase price you paid for the Product (purchase receipt showing price paid is required). ® PowerPanel Personal Edition is inactive (all icons are gray). connected equipment. We will repair or replace the equipment that was damaged because of the failure of our Product or pay you the fair market value (NOT REPLACEMENT COST) of the equipment at of the time of the damage. We will use Orion Blue Book, or $250,000 for the CP850AVRLCD, $350,000 for the CP1000AVRLCD, and $500,000 for the CP1350AVRLCD and the CP1500AVRLCD. Who Pays For Shipping? We pay when we send items to you; you pay when you send items to us. Additional troubleshooting information can be found under “Support” at www.CPSww.com What isn’t covered by the warranty? TECHNICAL SPECIFICATIONS 1. Model CP850AVRLCD CP1000AVRLCD CP1350AVRLCD CP1500AVRLCD Capacity 850VA / 510W 1000VA / 600W 1350VA / 810W 1500VA / 900W This Warranty does not cover any software that was damaged or needs to be replaced due to the failure of the Product or any data that is lost as a result of the failure or the restoration of data or records, or the reinstallation of software. 2. This Warranty does not cover or apply to: misuse, modification, operation or storage outside environmental limits of the Product or the equipment connected to it, nor for damage while in transit or in storage, nor if there has been improper operation or maintenance, or use with items not designed or intended for use with the Product, such as laser printers, appliances, aquariums, Nominal Input Voltage 120V Input Frequency 60 Hz +/- 3 Hz(Auto-sensing) On-Battery Output Voltage 120Vac ± 5% medical or life support devices, etc. What are the Limitations? The sole and exclusive remedies of the Initial Customer are those provided by this Warranty. 1. This Warranty does not apply unless the Product and the equipment that was connected to it were connected to properly wired and grounded outlets (including compliance with electrical and safety codes of the most current electrical code), without the use Transfer Time 4ms Typical Max. Load for UPS Outlets (4 / 5 Outlets) 850VA / 510W 1000VA / 600W of any adapters or other connectors. 1350VA / 810W 1500VA / 900W 2. The Product must have been plugged directly into the power source and the equipment connected to the Product must be directly connected to the Product and not “daisy-chained” together in serial fashion with any extension cords, another Product or device similar to the Product, surge suppressor, or power tap. Any such installation voids the Limited Warranty. Max. Load for Full-Time Surge Protection outlets 3. 12 Amp The Product and equipment connected to it must have been used properly in a suitable and proper environment and in conformance with any license, instruction manual, or warnings provided with the Product and the equipment connected to it. (8 / 9 Outlets) 4. On-Battery Output Wave The Product must have been used at all times within the limitations on the Product’s VA capacity. Simulated Sine Wave Form The Product was designed to eliminate disrupting and damaging effects of momentary (less than 1ms) voltage spikes or impulses Operating Temperature from lightning or other power transients. If it can be shown that a voltage spike lasting longer than 1ms has occurred, the occurrence + 32°F to 100.4° F / 0° C to 38° C will be deemed outside the rated capabilities of the Product and the Limited Warranty is void. CyberPower Does Not Cover or Operating Relative 0 to 90% non-condensing Humidity Undertake Any Liability in Any Event for Any of the Following: 1. Size (H x W x D) 8.7" x 4.3" x 10.2" 8.7" x 4.3" x 10.2" 9.8" x 3.9" x 13.4" 9.8" x 3.9" x 13.4" Net Weight 16.2 lbs 16.9 lbs 25 lbs 25.2 lbs Typical Battery Recharge 2. Typical Battery Life lines, PBX telephone equipment lines or Base 10T Ethernet lines, when properly installed and connected. (This exclusion applies, for example, to fluctuations in data transmission or reception, by CATV or RF transmission or fluctuations, or by transients in such transmission.) 3 to 6 years, depending on number of discharge/recharge cycles 3. 4. Recommended Battery Sealed Maintenance Free Lead Acid Battery Safety Approvals UL1778, cUL107, FCC/DoC Class B Damage from causes other than AC Power Line Transients, spikes, or surges on properly installed, grounded and code-compliant 120 volt power lines in the United States and Canada; transients, surges or spikes on standard telephone land 8 hours from total discharge Time Loss of or damage to data, records, or software or the restoration of data or records, or the reinstallation of software. Damage from any circumstance described as excluded above with respect to the Product. Damages from fire, flood, wind, rain, rising water, leakage or breakage of plumbing, abuse, misuse or alteration of either the product or the Connected Equipment. 5. CyberPower excludes any liability for personal injury under the Limited Warranty and Connected Equipment Guarantee. CyberPower excludes any liability for direct, indirect, special, incidental or consequential damages, whether for damage to or loss of property [EXCEPT FOR (AND ONLY FOR) the specific limited agreement of CyberPower to provide certain warranty SYSTEM FUNCTIONAL BLOCK DIAGRAM Input EMI Filter benefits regarding "Connected Equipment" under this Warranty], loss of profits, business interruption, or loss of information or Surge Suppressor AVR data. NOTE: Some States or Provinces do not allow the exclusion or limitation of incidental or consequential damages, so the Output above limitation may not apply to you. 6. Charger AC/DC Inverter The Product is not for use in high-risk activities or with aquariums. The Product is not designed or intended for use in hazardous environments requiring fail-safe performance, or for use in any circumstance in which the failure of the Product could lead directly to death, personal injury, or severe physical or property damage, or that would affect operation or safety of any medical Normal Mode or life support device (collectively, "High Risk Activities"). CyberPower expressly disclaims any express or implied warranty of Battery Mode fitness for High Risk Activities or with aquariums. CyberPower does not authorize use of any Product in any High Risk Activities Battery CYBERPOWER GREENPOWER UPS™ TECHNOLOGY or with Aquariums. ANY SUCH USE IS IMPROPER AND IS A MISUSE OF THE PRODUCT. Where Can I Get More Information? The application of the United Nations Convention of Contracts for the International Sale of Goods is expressly excluded. Advanced Energy-Saving Patented Bypass Technology CyberPower is the warrantor under this Limited Warranty. CyberPower’s patented GreenPower UPS™ with Bypass Technology reduces UPS energy costs by up to For further information please feel free to contact CyberPower at CyberPower Systems (USA), Inc. 4241 12th Ave E., STE 400, 75% compared to conventional UPS models. Even when utility power is normal, conventional UPS models Shakopee, MN 55379; call us at (877) 297-6937; or send us an e-mail message at [email protected]. constantly pass power through a transformer. By contrast, under normal conditions the advanced circuitry of a GreenPower UPS™ bypasses the transformer. As a result, the power efficiency is significantly increased while decreasing waste heat, using less energy, and reducing energy costs. When an abnormal power condition occurs, the GreenPower UPS™ automatically runs power through its CyberPower Systems encourages environmentally sound methods for disposal and recycling of its UPS products. Please dispose and/or recycle your UPS and batteries in accordance to the local regulations of your state. All rights reserved. Reproduction without permission is prohibited.