Transcript
SONNENKRAFT Solar Systems GmbH • Industriepark • 9300 St. Veit/Glan Tel.: +43 (0)4212 450 10 - 400 • Fax: +43 (0)4212 450 10-477 • E-mail:
[email protected]
SONNENKRAFT
....
. ....
m²
S4*
°C
M
S3*
°C
FWM15i/30i
S1
Control unit Solar:
SKSC2HE SKSC2+
A
B
D
S2
SM
BS
S1 > S2 = R1 S3*, S4* for heat balancing Output R2 not activated Diagram: system 1 (standard)
E
F
CW
Circ
HW
PSR .......E
F
K-RL
°C
Radiator
Heating circuit 1
M
RAS
HK-RL
°C
Diagram Manual
Q,T
PSKR18HE
R1
bar
r cto lle Co
AG...S
T
T
HW-Charging pump
Floor heating
Heating circuit 2
NOTE: ALL DIAGRAM MANUALS EARLIER THAN EDITION 140513-SM-GB BECOME VOID HEREWITH!
2
Vers.Nr. 140513-SM-GB
COMFORT E Plus 4.0 Heating-set with backup tank PSC E + PS E parallel connected; Water heating with fresh water module; Backup heating with heating circuit module; pool heating directly via solar circuit; reheating with oil-/gas-/pellets boiler Control concept: (Controller diagram: stratified buffer charging + Pool)
deactivation via temperature sensor in the circulation unit. In the circulation operation the hot return from the FWM is getting stratified via a switching valve in the middle tank area. A manually activatable disinfection mode (80 °C for max. 60 minutes) can sterilize the hot water network.
If the collector temperature (F1) is approx. 7°C higher than the backup tank temperature (F3), the solar pump (A1) is activated (Start spd.1 = 80%). If the flow temperature in the stratified charging module (F2) is approx. 5°C higher than the backup tank temperature (F3), the backup charging pump (A2) charges the backup tank to a set maximum backup tank temperature of approx. 90°C. The speed control of the pumps A1 and A2 tries to bring the temperature for backup charging to approx. 63°C and keep it there. If the secondary flow temperature in the stratified charging module (F5) is approx. 3°C higher than the upper backup tank temperature (F6), the backup tank is charged layer by layer by way of the diverter valve (A) in the upper part of the tank. The heat quantity measurement (WMZ 2/3 = YES) is automatically activated, however it only measures the solar yield in the direction of the backup tank.
The boiler pump (R5) and the switching valve DWV (R4) recharge the backup tank for the fresh water module FWM15/30i primarily via the boiler sensor (F6) of the heating circuit control unit SKSCEM1. The heating circuit is controlled by means of the flow sensor (S1 (HKM1/2)) and the exterior sensor (S2 (hKM1/2)) on the basis of weather conditions. The backup sensor (S3 (HKM1/2)) generates a requirement to the boiler via the controller output (R5 (HKM1/2)); the backup charging pump (R5 (HKM1/2)) is activated and deactivated again if the temperature falls below the set minimum.
If the maximum backup tank temperature (F3 = ΔT1_1max) has been reached and the collector temperature (F1) is approx. 7°C higher than the swimming pool temperature (F8), the swimming pool is heated by means of the pumps A3a and A3b (use relay to connect in parallel) and the plate heat exchanger until it reaches the set maximum swimming pool temperature (ΔT3max = 30°C), (SBA act. = Yes).
For details on further controller options such as minimum collector temperature, emergency collector shut-off, recooling etc., refer to controller manual SKSC3HE/ SKSCEM1 (download at http://www.sonnenkraft.com > private home). Recommendations for system hydraulics:
As is customary the backup tank is charged primarily (SLM message A3 = 1), therefore the swimming pool charging (A3) is switched off for approx. 2 min every 15 min. During this waiting time, the system checks whether the collector temperature can reach a sufficient temperature level to charge the backup tank and if necessary it is getting charged primarily again.
• Thermosiphon bends on all hot tank connections prevent excessive heat losses through “pipe-in-pipe circulation” (see commissioning and maintenance manual for design details).
The fresh water module FWM15/30i allows a hygienic hot water preparation and generates lowest RL-temperatures in the solar buffer. When hot water is dispensed a flow switch controls the variable speed controlled charging pump, which channels the hot backup water across the plate heat exchanger and heats the cold water to the set service water temperature (settings from 30°C to 65°C are available). In addition the circulation set FWM15/30i-CFK (Hmax = 0,5 bar) can be built in. Activation via automatically learning function, timer or tapping of hot water,
• As an alternative to the U-siphon bends, the connection lines between boiler, consumer net and tank can be laid near to the soil, to avoid pipe-in-pipe circulation (heat losses at standstill). • For service water circulation pipes, a flushing connection must be installed in front of the circulation set! • As is customary for hot water tanks, the cold water connection of the FWM15/30i must have a boiler safety group. A filter ensures that the module functions properly.
23
Legend of symbols used: Absperrorgan Shut-off unit Absperrorgan
Thermisches Dreiwegeventil Thermal three-way valve with mit Verteilfunktion distributive function
thermostatisches
Thermostatic thermostatisches Zirkulationsventil circulation valve
Entleerungshahn
Drain valve
Zirkulationsventil
ETI
Ausdehnungsgefäß Expansion tank mit cap Kappenventil with valve Automatic rapid deaerator
Boiler sensor for heating Boilerfühler für control
Fine filter
automatischer F1 SchnellentlüfterS1
M
Entlüftungstopf
Temperaturfühler Temperature sensor Temperature sensor Temperaturfühler Temperature sensor Temperaturfühler
F1
BF BS
Air vent
Heizungsregelung
Electromotive three-way elektromotorischer mixer Dreiwegemischer
F
PumpPumpe Boiler safety group Kesselsicherheitsgruppe
Durchflussmengenmesser
Flow volume meter
Feinfilter
Luftabscheider
Air separator
bar
stromlos
Manometer
Flushing device
Spüleinrichtung
W
Manometer
Elektromotorisches Dreiwegeventil mit Verteilfunktion und Federrückzug
Flow measuring unit Durchflussmesseinheit
Strangregulierventil
Electromotive three-way valve with distributive function and spring return
Choking valve
°C Thermometer Thermometer
Backup tank
Puffer-Verbindungsschlauch connecting hose Thermostatic TBM Thermostatischer Corrugated pipe service water mixer Wellrohr-Speicheranschluss Brauchwassermischer (For installation, see installation tank connection
instructions) (Anschluss siehe Montageanleitung)
with mit TH Thermostat Thermostat electric switching contact
elektrischem Schaltkontakt
Rückschlagventil und Schwerkraftbremse
Reflux valve and gravity brake
Safety valve with Sicherheitsventil drip funnel
mit Tropftrichter
Volume measuring instrument Volumenmessteil für
heat volume counting Wärmemengenzählung SKSRV for Plate heat exchanger Plattenwärmetauscher
Hot water-Sets Solar boiler DHW/ELB, up to 15 m2 collector area COMPACT E 1.0 – Solar hot water tank DHW
Heating-Sets: Backup tank PSR with solar pumping station PSKR18HE and fresh water module FWM15i/30i, up to 17,5 m2 collector area
COMFORT E 1.0 – Oil-/Gas-/Pellets boiler, heating integration with RAS20, 1 collector field COMFORT E 3.0 – Oil-/Gas-/Pellets boiler, heating integration with DWV25, 1 collector field
Heating-Sets: Backup tank PSC with stratified charging module SLM50HE and fresh water module FWM15i/30i, up to 55 m2 collector area COMFORT E plus 1.1 - oil-/gas-/pellets boiler, heating integration with HKM20HE, 1 collector field, PSC+PS parallel COMFORT E plus 1.3 – gas-condensing boiler (Hot water valve in RL), heating integration with RAS20, 1 collector field COMFORT E plus 1.4 – gas- condensing boiler (Hot water valve in VL), heating integration with RAS20, 1 collector field COMFORT E plus 1.5 – oil-/gas-/pellets boiler, heating integration with RAS20, 1 collector field COMFORT E plus 2.0 – oil-/gas-/pellets boiler, heating integration with HKM20HE, 2 collector fields, PSC+PS parallel COMFORT E plus 3.1 – oil-/gas-/pellets boiler, heating integration with DWV25, 1 collector field, PSC+PS parallel COMFORT E plus 4.0 – oil-/gas-/pellets boiler, heating integration with HKM20HE, 1 collector field, PSC+PS parallel, pool integration in the solar circuit 3
COMPACT E 1.0
to r ec l l Co
...
m² . . . ...
ETI Control unit Solar:
S1
SKSC2HE SKSC2
S1 > S2 = R1 S3*, S4* Heat quantity measurement (optional) Output R2 not activated Diagram: system 1 (standard) Heating circuit
bar
TBM H
R1
M
HW
C
AG...S
M
R2
BS
RLG-E S4* B*
A* S3* S2 BSG
CW
S4 Reheating
DHW....... A*: RLG-E-VAS B*: KFE-RLG (optional, especially at EWSID)
4
Scheme drawn by: Date: Basic scheme: COMPACT E 1 File name: COMPACT E 1.0.dwg
Customer: All information is not exhaustive and without warranty. Developer: Formatting and printing errors might occur. Please refer to the text description of the hydraulic schemes on the corresponding following page. Schematic diagrams including all information is not exhaustive and without warranty. assumption of liability. Project: County No specific regulations must be observed. No assumption of liability. Formatting and printing errors might occur. © SONNENKRAFT – 2014/05 www.sonnenkraft.com © 05/2012 www.sonnenkraft.com Version:
COMPACT E 1.0 Hot water set with solar hot water tank DHW; reheating with oil-/gas boiler
Control concept: (controller diagram system 1)
Recommendations for system hydraulics:
If the collector temperature (S1) is approx. 6°C higher than the tank temperature (S2), the solar pump (R1) charges the tank to a set maximum tank temperature (SMX = 60°C).
• A SONNENKRAFT service water mixer must be installed according to the hydraulics diagram and/or the installation instructions.
If you are operating the boiler manually, you can control tank recharging by means of the sensor S4 (as boiler sensor) (Controller diagram: System 8; differential control S4 > S3 with minimum temperature at S4; this variant does not allow heat quantity balancing). For boilers fired automatically, tank recharging can be controlled with the charging pump via the boiler sensor (BS) of the boiler controller (possibly time-dependent and/or with priority control). You can also control the charging pump via the sensor S3 (Controller diagram: System 3). Heat quantity balancing can be activated if the sensors S3* and S4* are built in according to the diagram. The max. volume flow can be read on the Flow meter (switch pump R1 ON manually) and entered in the controller along with the data of the heat transfer medium (type and mixture ratio). For details on further controller options such as minimum collector temperature, emergency collector shut-off, recooling etc., refer to Controller Manual SKSC2HE (download at http://www.sonnenkraft.com > partner area).
5
• Thermosiphon bends on all hot tank connections prevent excessive heat losses by “pipe-in-pipe circulation” (for design details, refer to the commissioning and maintenance manual). • As an alternative to the U-siphon bends, the connection lines between boiler, consumer net and tank can be laid near to the soil, to avoid the pipe-in-pipe circulation (causes heat losses in the tank). • For service water circulation pipes, build in a flushing connection between the pump and the reflux valves. • Systems higher than 11m require an additional gravity brake in the solar circuit return. • For systems with SKR500-collectors (up to 2 pcs.) there is required an additional flush connection (B*) at the VL-connection of the DHW-tank.
COMFORT E 1.0 Control unit Solar:
...
Radiator
SKSC2/3HE SKSC2+
S1 > S2 = R1 S3*, S4* for heat balancing Output R2 not activated Diagram: system 1 (standard)
bar S3*
°C
Floor heating
Return increase control: SKSCRAS
°C
Oil/ Gas boiler
A
AG...S
Heating circuit 2
SM..........Mid of the tank HK-RL.... Heating return K-RL....... Boiler return
HW-Charging pump
to r c e ll Co
S1
² .m . . . ..
Heating circuit 1
E
R1
BS S4*
F
PSKR18HE
FWM15i/30i
B
°C
SM
HK-RL
S2
RAS
M
°C K-RL
D
PSR .......E
M
HW Circ
T Q,T
T
6
Scheme drawn by: Date: Basic scheme: COMFORT E 1
F
CW
Customer: All information is not exhaustive and without warranty. Please refer to the text description of the hydraulic schemes on the corresponding following page. Schematic diagrams including all information is not exhaustive and without warranty. Developer: Formatting and printing errors might occur. County specific regulations must be observed. No assumption of liability. Formatting and printing errors might occur. © SONNENKRAFT – 2014/05 www.sonnenkraft.com No assumption of liability. Project:
COMFORT E 1.0 Water heating with backup tank PSR E; water heating with fresh water module; backup heating with return increase; reheating with oil-/gas-/pellets boiler
Control concept: (controller diagram system 1) If the collector temperature (S1) is approx. 6°C higher than the backup tank temperature (S2), the solar pump (R1) charges the backup tank to a set maximum backup tank temperature (change SMX up to a max. of 85°C). Heat quantity balancing can be activated if the sensors S3* and S4* are built in according to the diagram. The max. volume flow can be read on the Flow meter (switch pump R1 ON manually) and entered in the controller along with the data of the heat transfer medium (type and mixture ratio). The charging pump recharges the backup tank for the fresh water module FWM15/30i primarily via the boiler sensor (BS) of the boiler controller. The fresh water module FWM15/30i makes water heating very hygienic and it produces lowest RL-temperatures in the solar backup tank. When hot water is dispensed a flow switch sensor controls the speed controlled charging pump, which channels the hot backup water across the plate heat exchanger and heats the cold water to the set service water temperature (settings from 30°C to 65°C are available). In addition the circulation-set FWM15/30i-CFK (Hmax = 0,5 bar) can be build in. Activation via automatically learning function, timer or tapping of hot water, deactivation via temperature sensor in the circulation unit. In the circulation operation the hot return from the FWMi is getting stratified via a switching valve in the middle tank area. A manually activatable disinfection mode (80 °C for max. 60 minutes) can sterilize the hot water pipeline system. If the temperature of the backup tank (SM) is above the temperature of the heating circuit return (HK-RL), it will be lead with a variable amount over the hydraulic module RAS20 to the backup tank and thus the temperature level of the boiler return line (K-RL) is getting preheated to the corresponding nominal value. The heating circuit is controlled by the boiler control. 7
For details on further controller options such as minimum collector temperature, emergency collector shut-off, recooling etc., refer to Controller Manual SKSC2/3HE/SKSCRAS (download at http://www.sonnenkraft.com > private home). Recommendations for system hydraulics: • The hydraulic is especially suitable for condensing boilers or modulating heat pumps, because the solar pre-heating can be accordingly limited. • Thermosiphon bends on all hot tank connections prevent excessive heat losses by “pipe-in-pipe circulation” (for design details, refer to the commissioning and maintenance manual). • As an alternative to the U-siphon bends, the connection lines between boiler, consumer net and tank, can be laid near to the soil, contribute to avoid to the pipe-in-pipe circulation (causes heat losses in the tank). • For service water circulation pipes, a flushing connection must be installed in front of the circulation-set! • As customary for hot water tanks, the cold water connection of the FWM15/30i must have a boiler safety group. A filter ensures that the flow switch of the module functions properly.
COMFORT E 3.0
...
Heating circuit 1
Control unit Solar:
Radiator / Floor heating
SKSC2/C2+ SKSC2/3HE S1 > S2 = R1 S3 > S4 = R2 Diagram: system 9
HW-Charging pump
to r c e ll Co
S1
² .m . . . ..
bar
°C
E
R1
A B
HKMHE
Oil-/Gasboiler
*
AG...S
°C
BS
F
S4
S3
PSKR18HE
S2 D
FWM15i/30i
PSR .......E
M
T
HW
T
8
A
*
AB
B no current TH
*
> 50°C
Circ
Q,T
Scheme drawn by: Date: Basic scheme: COMFORT E 3 File name: COMFORT 3.0.dwg
DWV R2
F
CW
Wood fired boiler
* KP
Customer: All information is not exhaustive and without warranty. Developer: Formatting and printing errors might occur. Please refer to the text description of the hydraulic schemes on the corresponding following page. Schematic diagrams including all information is not exhaustive and without warranty. assumption of liability. Project: County No specific regulations must be observed. No assumption of liability. Formatting and printing errors might occur. © SONNENKRAFT – 2014/05 www.sonnenkraft.com © 05/2012 www.sonnenkraft.com Version:
COMFORT E 3.0 Heating-set with backup tank PSR E; water heating with fresh water module; backup heating with return increase; reheating with oil-/gas-/pellets-/wood fired boiler
Control concept: (controller diagram system 9)
The heating circuit is controlled by the boiler control.
If the collector temperature (S1) is approx. 6°C higher than the backup tank temperature (S2), the solar pump (R1) charges the backup tank to a set maximum backup tank temperature (SMX = 85°C).
For details on further controller options such as minimum collector temperature, emergency collector shut-off, recooling etc., refer to Controller Manual SKSC2/3HE (download at http://www.sonnenkraft.com > private home).
The heat quantity balancing cannot be activated here. A heat volume meter can just be integrated in the solar-RL/-VL. The charging pump recharges the backup tank for the fresh water module FWM15/30i primarily via the boiler sensor (BS) of the boiler controller.
Recommendations for system hydraulics:
The fresh water module FWM15/30i provides a hygienic hot water preparation and generates lowest RL-temperatures in the solar buffer. When hot water is dispensed a flow switch activates the variable speed charging pump, which channels the hot backup water across the plate heat exchanger and heats the cold water to the set service water temperature (settings from 30°C to 65°C are available). In addition the circulation set FWM15/30i-CFK (Hmax = 0,5 bar) can be built in. Activation via automatically learning function, timer or tapping of hot water, deactivation via temperature sensor in the circulation unit. In the circulation operation the hot return from the FWM is getting stratified via a switching valve in the middle tank area. A manually activatable disinfection mode (80 °C for max. 60 minutes) can sterilize the hot water pipeline system. If the temperature of the backup tank (S3) is approx. 5°C higher than the temperature of the heating circuit return (S4), the latter is channeled via the switching valve DWV (R2) to the backup tank and thus the temperature level of the boiler return is accordingly preheated. If the backup tank is only approx. 3°C warmer than the temperature of the heating return, the switching valve is getting deactivated again (“no-current method”) and the heating circuit is heated by the boiler only.
9
• Thermosiphon bends on all hot tank connections prevent excessive heat losses by “pipe-in-pipe circulation” (for design details, refer to the commissioning and maintenance manual). • As an alternative to the U-siphon bends, the connection lines between boiler, consumer net and tank, can be laid near to the soil, contribute to avoid to the pipe-in-pipe circulation (causes heat losses in the tank). • The constant use of the solid fuel boiler can strongly reduce the solar yield. • For service water circulation pipes, a flushing connection must be installed in front of the circulation set! • As customary for hot water tanks, the cold water connection of the FWM15/30i must have a boiler safety group. A filter ensures that the flow switch of the module functions properly.
COMFORT E Plus 1.1 Heating circuit 2 Heating circuit 2 (Floor ( Floorheating) heating )
°C
S2 Exterior sensor
HKMHE
S1+S5 R1+R2+R3+R4 S5 Remote control unit
R4(HKM1)
F2 SLM50HE
bar T
Q,T
Oil-/Gasboiler
A R5(HKM1)
F6
A2
A1
no current
*
F5
AG
M
B
S5 Remote control unit
SKSCEM1
R2/R3 (HKM2)
°C
S1+S2+S3+S5+S6( = F6 ) R1+R2+R3+R4+R5
Heating circuit module control( HKM2 )
A
T
HKMHE
SKSCEM1
R1 (HKM2)
F1 > F3 = A1 F2 > F3 = A2 F5 > F6 = A VFS1, F2 for heat balancing Diagram: Stratified buffer charging
VL
°C
°C
SKSC3HE SKSC3+
S1 (HKM2)
Heating circuit module control( HKM1 )
DWV
Q,T
S1 (HKM1)
Control unit Solar:
R2/R3 (HKM1)
RL
VFS1
F1
m² . . . .... r ..
R1 (HKM1)
cto lle o C
( (Radiator) Radiator)
AB
Heating circuit Heating circuit1 1
A
VFS2
B
S3 DN40
C
FWM15i/30i
*
*
Wood fired boiler
*
D M
HW T
Circ
Q,T
T
10
Scheme drawn by: Date: Basic scheme: COMFORT E plus 1
F
PSC...........E
F3
PS...........E
CW
Customer: All information is not exhaustive and without warranty. PleaseFormatting refer to theand textprinting description of the hydraulic all information is not exhaustive and without warranty. Developer: errors might occur. schemes on the corresponding following page. Schematic diagrams including County specific regulations must be observed. No assumption of liability. Formatting and printing errors might occur. © SONNENKRAFT – 2014/05 www.sonnenkraft.com No assumption of liability. Project:
COMFORT E Plus 1.1 Heating-set with backup tank PSC E; water heating with fresh water module; backup heating with heating circuit module; reheating with oil-/gas-/pellets-/wood fired boiler
Control concept: (Controller diagram: stratified buffer charging) If the collector temperature (F1) is approx. 7°C higher than the backup tank temperature (F3), the solar pump (A1) is activated (Start spd.1 = 80%). If the flow temperature in the stratified charging module (F2) is approx. 5°C higher than the backup tank temperature (F3), the backup charging pump (A2) charges the backup tank to a set maximum backup tank temperature of approx. 90°C. The speed control of the pumps A1 and A2 tries to bring the temperature for backup charging to approx. 63°C and keep it there. If the secondary flow temperature in the stratified charging module (F5) is approx. 3°C higher than the upper backup tank temperature (F6), the backup tank is charged layer by layer by way of the diverter valve (A) in the upper part of the tank. The heat quantity measurement (WMZ 2/3 = YES) is automatically activated. The boiler pump (R5) and the diverter valve DWV (R4) recharges the backup tank for the fresh water module FWM15/30i primarily via the boiler sensor (F6) of the heating circuit control unit SKSCEM1. The fresh water module FWM15/30i allows a hygienic hot water preparation and generates lowest RL-temperatures in the solar buffer. When hot water is dispensed a flow switch controls the variable speed controlled charging pump, which channels the hot backup water across the plate heat exchanger and heats the cold water to the set service water temperature (settings from 30°C to 65°C are available). In addition the circulation set FWM15/30i-CFK (Hmax = 0,5 bar) can be built in. Activation via automatically learning function, timer or tapping of hot water, deactivation via temperature sensor in the circulation unit. In the circulation operation the hot return from the FWM is getting stratified via a switching valve in the middle tank area. A manually activatable disinfection mode (80 °C for max. 60 minutes) can sterilize the hot water network.
11
The heating circuit is controlled by means of the flow sensor (S1 (HKM1/2)) and exterior sensor (S2 (hKM1/2)) on the basis of weather conditions. By the backup sensor (S3 (HKM1)) the boiler requirement and the buffer charging pump (R5 (hKM1/2)) is activated or rather deactivated again if the temperature falls below the set minimum. For details on further controller options such as minimum collector temperature, emergency collector shut-off, recooling etc., refer to Controller Manual SKSC3HE and/or SKSCEM1 (download at http://www.sonnenkraft.com > private home). Recommendations for system hydraulics: • Thermosiphon bends on all hot tank connections prevent excessive heat losses through “pipe-in-pipe circulation” (see commissioning and maintenance manual for design details). • As an alternative to the U-siphon bends, the connection lines between boiler, consumer net and tank can be laid near to the soil, to avoid pipe-in-pipe circulation (heat losses at standstill). • The constant use of the solid fuel boiler can strongly reduce the solar yield. • For service water circulation pipes, a flushing connection must be installed in front of the circulation set! • As is customary for hot water tanks, the cold water connection of the FWM15/30i must have a boiler safety group. A filter ensures that the module functions properly.
COMFORT E Plus 1.3 Heating circuit 1
m² . . . ...
RL
VFS1
Q,T
Return increase control:
SKSC3+ SKSC3HE F1 > F3 = A1 F2 > F3 = A2 F5 > F6 = A VFS1, F2 for heat balancing Diagram: Stratified buffer charging
VL
T
SKSCRAS SM..........Mid of the tank HK-RL.... Heating return K-RL....... Boiler return
bar T
F5
M
F6 BS
A
A
A2
A1
SM Q,T
Note: Consult the manufacturer about installing and controlling of the heat source!
Header sensor
F2 SLM50HE
AG
Gasboiler
HW-Charging pump
cto lle o C
. r ..
Control unit Solar:
S1
Radiator / Floor heating
B
°C HK-RL
VFS2
M
°C
Hydraulic gate
K-RL
C
RAS D
FWM15i/30i
F3
PSC...........E
M
T
HW Circ
Q,T
T
12
Scheme drawn by: Date: Basic scheme: COMFORT E plus 1
F
CW
Customer: All information is not exhaustive and without warranty. Please refer to the text description of the hydraulic schemes on the corresponding following page. Schematic diagrams including all information is not exhaustive and without warranty. Developer: Formatting and printing errors might occur. County specific regulations must be observed. No assumption of liability. Formatting and printing errors might occur. © SONNENKRAFT – 2014/05 www.sonnenkraft.com No assumption of liability. Project:
COMFORT E Plus 1.3 Heating-set with backup tank PSC E; Water heating with fresh water module; Backup heating with controlled return increase; reheating with gas condensing boiler (Hot water-switching in RL)
Control concept: (Controller diagram: stratified buffer charging) If the collector temperature (F1) is approx. 7°C higher than the backup tank temperature (F3), the solar pump (A1) is activated (Start spd.1 = 80%). If the flow temperature in the stratified charging module (F2) is approx. 5°C higher than the backup tank temperature (F3), the backup charging pump (A2) charges the backup tank to a set maximum backup tank temperature of approx. 90°C. The speed control of the pumps A1 and A2 tries to bring the temperature for backup charging to approx. 63°C and keep it there. If the secondary flow temperature in the stratified charging module (F5) is approx. 3°C higher than the upper backup tank temperature (F6), the backup tank is charged layer by layer by way of the diverter valve (A) in the upper part of the tank. The heat quantity measurement (WMZ 2/3 = YES) is automatically activated.
If the temperature of the backup tank (SM) is above the temperature of the heating circuit return (HK-RL), it will be lead with a variable amount over the hydraulic module RAS20 to the backup tank and thus the temperature level of the boiler return line (K-RL) is getting preheated to the corresponding nominal value.
The charging pump recharges the backup tank for the fresh water module FWM15/30i primarily via the boiler sensor (BS) of the gas boiler control.
Recommendations for system hydraulics:
The fresh water module FWM15/30i allows a hygienic hot water preparation and generates lowest RL-temperatures in the solar buffer. When hot water is dispensed a flow switch controls the variable speed controlled charging pump, which channels the hot backup water across the plate heat exchanger and heats the cold water to the set service water temperature (settings from 30°C to 65°C are available). In addition the circulation set FWM15/30i-CFK (Hmax = 0,5 bar) can be built in. Activation via automatically learning function, timer or tapping of hot water, deactivation via temperature sensor in the circulation unit. In the circulation operation the hot return from the FWM is getting stratified via a switching valve in the middle tank area. A manually activatable disinfection mode (80 °C for max. 60 minutes) can sterilize the hot water network.
13
The heating circuit is controlled by the boiler control. For details on further controller options such as minimum collector temperature, emergency collector shut-off, recooling etc., refer to Controller Manual SKSC3HE and/or SKSCRAS (download at http://www.sonnenkraft.com > private home).
• The hydraulic is particularly suited for condensing boilers, because the solar pre-heating can be limited accordingly. • Thermosiphon bends on all hot tank connections prevent excessive heat losses through “pipe-in-pipe circulation” (see commissioning and maintenance manual for design details). • As an alternative to the U-siphon bends, the connection lines between boiler, consumer net and tank can be laid near to the soil, to avoid pipe-in-pipe circulation (heat losses at standstill). • For service water circulation pipes, a flushing connection must be installed in front of the circulation set! • As is customary for hot water tanks, the cold water connection of the FWM15/30i must have a boiler safety group. A filter ensures that the module functions properly.
COMFORT E Plus 1.4
to r c e ll Co
...
² .m . . . ..
RL
VFS1
Q,T
Return increase control:
Control unit Solar:
F1
T
Heating circuit 1 Radiator / Floor heating
SKSCRAS
SKSC3HE SKSC3+
F1 > F3 = A1 F2 > F3 = A2 F5 > F6 = A VFS1, F2 for heat balancing Diagram: Stratified buffer charging
VL
Gasboiler
Note: Consult the manufacturer about installing and controlling of the heat source!
SM..........Mid of the tank HK-RL.... Heating return K-RL....... Boiler return
F2 SLM50HE
bar T
F5
AG
M
F6 BS
A
A
A2
A1
°C SM
Q,T
VFS2
°C
B HK-RL
C
M
K-RL
RAS
D
FWM15i/30i
F3
PSC...........E
M
T
HW Circ
Q,T
T
14
Scheme drawn by: Date: Basic scheme: COMFORT E plus 1
F
CW
Customer: All information is not exhaustive and without warranty. Please refer to the text description of the hydraulic schemes on the corresponding following page. Schematic diagrams including all information is not exhaustive and without warranty. Developer: Formatting and printing errors might occur. County specific regulations must be observed. No assumption of liability. Formatting and printing errors might occur. © SONNENKRAFT – 2014/05 www.sonnenkraft.com No assumption of liability. Project:
COMFORT E Plus 1.4 Heating-set with backup tank PSC E; Water heating with fresh water module; Backup heating with controlled return increase; reheating with gas condensing boiler (Hot water-switching in VL)
Control concept: (Controller diagram: stratified buffer charging) If the collector temperature (F1) is approx. 7°C higher than the backup tank temperature (F3), the solar pump (A1) is activated (Start spd.1 = 80%). If the flow temperature in the stratified charging module (F2) is approx. 5°C higher than the backup tank temperature (F3), the backup charging pump (A2) charges the backup tank to a set maximum backup tank temperature of approx. 90°C. The speed control of the pumps A1 and A2 tries to bring the temperature for backup charging to approx. 63°C and keep it there. If the secondary flow temperature in the stratified charging module (F5) is approx. 3°C higher than the upper backup tank temperature (F6), the backup tank is charged layer by layer by way of the diverter valve (A) in the upper part of the tank. The heat quantity measurement (WMZ 2/3 = YES) is automatically activated. The charging pump recharges the backup tank for the fresh water module FWM15/30i primarily via the boiler sensor (BS) of the gas boiler control. The fresh water module FWM15/30i allows a hygienic hot water preparation and generates lowest RL-temperatures in the solar buffer. When hot water is dispensed a flow switch controls the variable speed controlled charging pump, which channels the hot backup water across the plate heat exchanger and heats the cold water to the set service water temperature (settings from 30°C to 65°C are available). In addition the circulation set FWM15/30i-CFK (Hmax = 0,5 bar) can be built in. Activation via automatically learning function, timer or tapping of hot water, deactivation via temperature sensor in the circulation unit. In the circulation operation the hot return from the FWM is getting stratified via a switching valve in the middle tank area. A manually activatable disinfection mode (80 °C for max. 60 minutes) can sterilize the hot water network.
15
If the temperature of the backup tank (SM) is above the temperature of the heating circuit return (HK-RL), it will be lead with a variable amount over the hydraulic module RAS20 to the backup tank and thus und the temperature level of the boiler return line (K-RL) is getting preheated to the corresponding nominal value. The heating circuit is controlled by the boiler control. For details on further controller options such as minimum collector temperature, emergency collector shut-off, recooling etc., refer to Controller Manual SKSC3HE and/or SKSCRAS (download at http://www.sonnenkraft.com > private home). Recommendations for system hydraulics: • The hydraulic is particularly suited for condensing boilers, because the solar pre-heating can be limited accordingly. • Thermosiphon bends on all hot tank connections prevent excessive heat losses through “pipe-in-pipe circulation” (see commissioning and maintenance manual for design details). • As an alternative to the U-siphon bends, the connection lines between boiler, consumer net and tank can be laid near to the soil, to avoid pipe-in-pipe circulation (heat losses at standstill). • For service water circulation pipes, a flushing connection must be installed in front of the circulation set! • As is customary for hot water tanks, the cold water connection of the FWM15/30i must have a boiler safety group. A filter ensures that the module functions properly.
COMFORT E Plus 1.5
...
RL
VFS1
Q,T
Radiator / Floor heating
SKSCRAS
SKSC3HE SKSC3+
SM..........Mid of the tank HK-RL.... Heating return K-RL....... Boiler return
F1 > F3 = A1 F2 > F3 = A2 F5 > F6 = A VFS1, F2 for heat balancing Diagram: Stratified buffer charging
VL
T
F2 SLM50HE
bar T
F5
AG
M
F6 BS
A
A
Oil-/Gasboiler
A2
A1
SM Q,T
Heating circuit 1
HW-Charging pump
to r ec l l Co
Return increase control:
Control unit Solar:
F1
m² . . . ...
VFS2
B
°C HK-RL
C
M
RAS D
FWM15i/30i
F3
PSC...........E
M
T
*
Wood fired boiler
*
HW
Q,T
Scheme drawn by: Date: Basic scheme: COMFORT E plus 1
K-RL
Circ
T
16
°C
F
CW
Customer: All information is not exhaustive and without warranty. Please refer to the text description of the hydraulic schemes on the corresponding following page. Schematic diagrams including all information is not exhaustive and without warranty. Developer: Formatting and printing errors might occur. County specific regulations must be observed. No assumption of liability. Formatting and printing errors might occur. © SONNENKRAFT – 2014/05 www.sonnenkraft.com No assumption of liability. Project:
COMFORT E Plus 1.5 Heating-set with backup tank PSC E; Water heating with fresh water module; Backup heating with controlled return increase; reheating with oil-/gas-/pellets-/ wood fired boiler
Control concept: (Controller diagram: stratified buffer charging) If the collector temperature (F1) is approx. 7°C higher than the backup tank temperature (F3), the solar pump (A1) is activated (Start spd.1 = 80%). If the flow temperature in the stratified charging module (F2) is approx. 5°C higher than the backup tank temperature (F3), the backup charging pump (A2) charges the backup tank to a set maximum backup tank temperature of approx. 90°C. The speed control of the pumps A1 and A2 tries to bring the temperature for backup charging to approx. 63°C and keep it there. If the secondary flow temperature in the stratified charging module (F5) is approx. 3°C higher than the upper backup tank temperature (F6), the backup tank is charged layer by layer by way of the diverter valve (A) in the upper part of the tank. The heat quantity measurement (WMZ 2/3 = YES) is automatically activated.
If the temperature of the backup tank (SM) is above the temperature of the heating circuit return (HK-RL), it will be lead with a variable amount over the hydraulic module RAS20 to the backup tank and thus und the temperature level of the boiler return line (K-RL) is getting preheated to the corresponding nominal value.
The charging pump recharges the backup tank for the fresh water module FWM15/30i primarily via the boiler sensor (BS) of the gas boiler control.
Recommendations for system hydraulics:
The fresh water module FWM15/30i allows a hygienic hot water preparation and generates lowest RL-temperatures in the solar buffer. When hot water is dispensed a flow switch controls the variable speed controlled charging pump, which channels the hot backup water across the plate heat exchanger and heats the cold water to the set service water temperature (settings from 30°C to 65°C are available). In addition the circulation set FWM15/30i-CFK (Hmax = 0,5 bar) can be built in. Activation via automatically learning function, timer or tapping of hot water, deactivation via temperature sensor in the circulation unit. In the circulation operation the hot return from the FWM is getting stratified via a switching valve in the middle tank area. A manually activatable disinfection mode (80 °C for max. 60 minutes) can sterilize the hot water network.
17
The heating circuit is controlled by the boiler control. For details on further controller options such as minimum collector temperature, emergency collector shut-off, recooling etc., refer to Controller Manual SKSC3HE/ SKSCRAS (download at http://www.sonnenkraft.com > private home).
• The hydraulic is particularly suited for condensing boilers, because the solar pre-heating can be limited accordingly. • Thermosiphon bends on all hot tank connections prevent excessive heat losses through “pipe-in-pipe circulation” (see commissioning and maintenance manual for design details). • As an alternative to the U-siphon bends, the connection lines between boiler, consumer net and tank can be laid near to the soil, to avoid pipe-in-pipe circulation (heat losses at standstill). • The constant use of the solid fuel boiler can strongly reduce the solar yield. • For service water circulation pipes, a flushing connection must be installed in front of the circulation set! • As is customary for hot water tanks, the cold water connection of the FWM15/30i must have a boiler safety group. A filter ensures that the module functions properly.
COMFORT E Plus 2.0
HKMHE VFS1
Q,T
T
HKMHE
R4(HKM1)
F2 SLM50HE
B
bar
A
m²
°C
°C
F1 > F3 = A1 F2 > F3 = A2 F5 > F6 = A F7 > F3 = A3 VFS2, F5 for heat balancing Diagram: Comfort 2
no current
Oil-/Gasboiler
AB
°C
°C
S1 (HKM2)
SKSC3HE SKSC3+
DWV
....
( (Floor Floor heating) heating )
R2/R3 (HKM2)
.... .
S1 (HKM1)
Heating circuit Heating circuit2 2
Control unit Solar:
R1 (HKM2)
Co lle cto r
( (Radiator) Radiator )
R2/R3 (HKM1)
...
m² . . . ...
Heating circuit Heating circuit1 1
F1
R1 (HKM1)
to r ec l l Co
F7
bar
*
AG...S
T
A3
F5
AG
A
R5(HKM1) A
F6
A2
A1
RLG
M
B Q,T
VFS2
DN40 C
FWM15/30
Wood fired boiler
*
*
D
F3 M
HW T
*
S3
Circ
Q,T
T
F
CW
PSC...........E
PS...........E
Heating circuit module control( HKM1 ) SKSCEM1 S1+S2+S3+S5+S6( = F6 ) R1+R2+R3+R4+R5 S5 Remote control unit
Heating circuit module( HKM2 ) SKSCEM1 S1+S5 R1+R2+R3+R4 S5 Remote control unit
S2 Exterior sensor
18
Scheme drawn by: Date: Basic scheme: COMFORT E plus 2
Customer: All information is not exhaustive and without warranty. Please refer to the text description of the hydraulic schemes on the corresponding following page. Schematic diagrams including all information is not exhaustive and without warranty. Developer: Formatting and printing errors might occur. County specific regulations must be observed. No assumption of liability. Formatting and printing errors might occur. © SONNENKRAFT – 2014/05 www.sonnenkraft.com No assumption of liability. Project:
COMFORT E Plus 2.0 Heating-set with backup tank PSC E + PS E parallel connected (2 separate collector fields); Water heating with fresh water module; Backup heating with heating circuit module; reheating with oil-/gas-/pellets-/ wood fired boiler Control concept: (Controller diagram: Comfort 2) If the collector temperatures (F1 and/or F7) is approx. 10°C higher than the backup tank temperature (F3), the solar pump (A1 and/or A3) is activated (Start spd.1/3 = 80%). If the flow temperature in the stratified charging module (F2) is approx. 5°C higher than the backup tank temperature (F3), the backup charging pump (A2) charges the backup tank to a set maximum backup tank temperature (F3 = 85°C or F6 = 90°C). The speed control of the pumps A1, A2 and A3 tries to bring the temperature for backup charging to approx. 63°C and keep it there. If the secondary flow temperature in the stratified charging module (F5) is approx. 3°C higher than the upper backup tank temperature (F6), the backup tank is charged layer by layer by way of the diverter valve (A) in the upper part of the tank. The heat quantity measurement (WMZ 2/3 = YES) is automatically activated. The boiler pump (R5) and the switching valve DWV (R4) recharge the backup tank for the fresh water module FWM15/30i primarily via the boiler sensor (F6) of the heating circuit control unit SKSCEM1. The fresh water module FWM15/30i allows a hygienic hot water preparation and generates lowest RL-temperatures in the solar buffer. When hot water is dispensed a flow switch controls the variable speed controlled charging pump, which channels the hot backup water across the plate heat exchanger and heats the cold water to the set service water temperature (settings from 30°C to 65°C are available). In addition the circulation set FWM15/30i-CFK (Hmax = 0,5 bar) can be built in. Activation via automatically learning function, timer or tapping of hot water, deactivation via temperature sensor in the circulation unit. In the circulation operation the hot return from the FWM is getting stratified via a switching valve in the middle tank area. A manually activatable disinfection mode (80 °C for max. 60 minutes) can sterilize the hot water network.
19
The heating circuit is controlled on the basis of weather conditions by the flow sensor (S1 (HKM1/2)) and the exterior sensor (S2 (HKM1/2)). The backup sensor (S3 (HKM1/2)) submits a requirement to the boiler via the controller output (R5 (HKM1/2)) and the backup charging pump (R5 (HKM1/2)) is activated or respectively deactivated after falling below the set minimum temperature. For details on further controller options such as minimum collector temperature, emergency collector shut-off, recooling etc., refer to Controller Manual SKSC3HE/ SKSCEM1 (download at http://www.sonnenkraft.com > private home). Recommendations for system hydraulics: • Thermosiphon bends on all hot tank connections prevent excessive heat losses through “pipe-in-pipe circulation” (see commissioning and maintenance manual for design details). • As an alternative to the U-siphon bends, the connection lines between boiler, consumer net and tank can be laid near to the soil, to avoid pipe-in-pipe circulation (heat losses at standstill). • The constant use of the solid fuel boiler can strongly reduce the solar yield. • For service water circulation pipes, a flushing connection must be installed in front of the circulation set! • As is customary for hot water tanks, the cold water connection of the FWM15/30i must have a boiler safety group. A filter ensures that the module functions properly. • The common solar flow and the Y-connection piece should be executed one pipe dimension larger than the solar return. Otherwise there may be unwanted hydraulic operating conditions at simultaneous operation of the two solar pumps. • For optimal commissioning (flushing, vent) both collector fields need their own air vents.
COMFORT E Plus 3.1 Control unit Solar:
VFS1
...
Q,T
T
Heating circuit 1
SKSC3HE SKSC3+
Radiator / Floor heating
F1 > F3 = A1 F2 > F3 = A2 F5 > F6 = A F7 > F8 = A3 VFS1, F2 for heat balancing Diagram: Comfort 3
HW-Charging pump
to r c e ll Co
F1
² .m . . . ..
F2 SLM50HE
bar T
F5
AG
A1
M
F6 BS
A
A
Oil-/Gasboiler
A2
Q,T
B
F7
VFS2
FWM15i/30i
F3
PSC...........E
M
PS...........E
C
F8
D
DWV A3 A AB
B no current
*
HW T
Circ
Q,T
T
20
Scheme drawn by: Date: Basic scheme: COMFORT E plus 3
F
CW
Wood fired boiler
*
Customer: All information is not exhaustive and without warranty. Please refer to the text description of the hydraulic schemes on the corresponding following page. Schematic diagrams including all information is not exhaustive and without warranty. Formatting and printing errors might occur. Developer: County specific regulations must be observed. No assumption of liability. Formatting and printing errors might occur. © SONNENKRAFT – 2014/05 www.sonnenkraft.com No assumption of liability. Project:
COMFORT E Plus 3.1 Heating-set with backup tank PSC E + PS E parallel connected; Water heating with fresh water module; Backup heating with return increase; reheating with oil-/gas-/pellets-/wood fired boiler
Control concept: (Controller diagram: Comfort 3) If the collector temperature (F1) is approx. 7°C higher than the backup tank temperature (F3), the solar pump (A1) is activated (Start spd.1 = 80%). If the flow temperature in the stratified charging module (F2) is approx. 5°C higher than the backup tank temperature (F3), the backup charging pump (A2) charges the backup tank to a set maximum backup tank temperature of approx. 90°C. The speed control of the pumps A1 and A2 tries to bring the temperature for backup charging to approx. 63°C and keep it there. If the secondary flow temperature in the stratified charging module (F5) is approx. 3°C higher than the upper backup tank temperature (F6), the backup tank is charged layer by layer by way of the diverter valve (A) in the upper part of the tank. The heat quantity measurement (WMZ 2/3 = YES) is automatically activated. The charging pump recharges the backup tank for the fresh water module FWM15/30i primarily via the boiler sensor (BS) of the gas boiler control. The fresh water module FWM15/30i allows a hygienic hot water preparation and generates lowest RL-temperatures in the solar buffer. When hot water is dispensed a flow switch controls the variable speed controlled charging pump, which channels the hot backup water across the plate heat exchanger and heats the cold water to the set service water temperature (settings from 30°C to 65°C are available). In addition the circulation set FWM15/30i-CFK (Hmax = 0,5 bar) can be built in. Activation via automatically learning function, timer or tapping of hot water, deactivation via temperature sensor in the circulation unit. In the circulation operation the hot return from the FWM is getting stratified via a switching valve in the middle tank area. A manually activatable disinfection mode (80 °C for max. 60 minutes) can sterilize the hot water network.
21
If the temperature of the backup tank (F7) is approx. 5°C higher than the temperature of the heating return (F8), the latter is channeled to the backup tank by means of the switching valve DWV (A3) and thus the temperature level of the boiler return preheated accordingly. If the backup tank is only approx. 3°C warmer than the heating return, the switching valve is deactivated again (“no-current”) and the heating circuit heated by the boiler only. The heating circuit is controlled by the boiler control. For details on further controller options such as minimum collector temperature, emergency collector shut-off, recooling etc., refer to controller manual SKSC3HE (download at http://www.sonnenkraft.com > private home). Recommendations for system hydraulics: • Thermosiphon bends on all hot tank connections prevent excessive heat losses through “pipe-in-pipe circulation” (see commissioning and maintenance manual for design details). • As an alternative to the U-siphon bends, the connection lines between boiler, consumer net and tank can be laid near to the soil, to avoid pipe-in-pipe circulation (heat losses at standstill). • The constant use of the solid fuel boiler can strongly reduce the solar yield. • For service water circulation pipes, a flushing connection must be installed in front of the circulation set! • As is customary for hot water tanks, the cold water connection of the FWM15/30i must have a boiler safety group. A filter ensures that the module functions properly.
COMFORT E Plus 4.0 Heating Heating circuit circuit 1 1
Heating circuit Heating circuit2 2
( (Radiator) Radiator)
HKMHE
SKSCEM1
S1+S2+S3+S5+S6( = F6 ) R1+R2+R3+R4+R5
M
F5
AG
no current
Oil-/Gasboiler
A B
S3 R5(HKM1)
A2
A1
AB
A
A
R4(HKM1)
bar T
S5 Remote control unit
S2 Exterior sensor
F6
F2 SLM50HE
S1+S5 R1+R2+R3+R4
S5 Remote control unit
VL
T
Heating circuit module control( HKM2 )
SKSCEM1
°C
DWV
VFS1
Q,T
HKMHE
°C
Heating circuit module control( HKM1 )
B
F1 > F3 = A1 F2 > F3 = A2 F5 > F6 = A F1 > F8 = A3a+A3b Diagram: Stratif. buffer charg. + Pool
°C
R2/R3 ( HKM2)
°C
S1 ( HKM2) R1 ( HKM2)
S1 ( HKM1)
SKSC3HE SKSC3+
RL
( (Floor Floor heating) heating )
R2/R3 ( HKM1)
m² . . . .... r ..
R1 ( HKM1)
cto lle o C
F1 Control unit Solar:
DN40 C
DWF
A3a
RLG
Q,T
max. 50 °C
VFS2
Bypass for flow regulation RAT
max.45 °C
22
Scheme drawn by: Date: Basic scheme: COMFORT E plus 4
F3
PS...........E
PSC...........E
M
T
°C
HW Circ
Q,T
T
°C
SBPWT
FWM 15i/30i
D
F8
F
CW
Pool
A3b F
Customer: All information is not exhaustive and without warranty. Please refer to the text description of the hydraulic schemes on the corresponding following page. Schematic diagrams including all information is not exhaustive and without warranty. Developer: Formatting and printing errors might occur. County specific regulations must be observed. No assumption of liability. Formatting and printing errors might occur. © SONNENKRAFT – 2014/05 www.sonnenkraft.com No assumption of liability. Project:
NOTE: ALL DIAGRAM MANUALS EARLIER THAN EDITION 140513-SM-GB BECOME VOID HEREWITH!
2
Vers.Nr. 140513-SM-GB
COMFORT E Plus 4.0 Heating-set with backup tank PSC E + PS E parallel connected; Water heating with fresh water module; Backup heating with heating circuit module; pool heating directly via solar circuit; reheating with oil-/gas-/pellets boiler Control concept: (Controller diagram: stratified buffer charging + Pool)
deactivation via temperature sensor in the circulation unit. In the circulation operation the hot return from the FWM is getting stratified via a switching valve in the middle tank area. A manually activatable disinfection mode (80 °C for max. 60 minutes) can sterilize the hot water network.
If the collector temperature (F1) is approx. 7°C higher than the backup tank temperature (F3), the solar pump (A1) is activated (Start spd.1 = 80%). If the flow temperature in the stratified charging module (F2) is approx. 5°C higher than the backup tank temperature (F3), the backup charging pump (A2) charges the backup tank to a set maximum backup tank temperature of approx. 90°C. The speed control of the pumps A1 and A2 tries to bring the temperature for backup charging to approx. 63°C and keep it there. If the secondary flow temperature in the stratified charging module (F5) is approx. 3°C higher than the upper backup tank temperature (F6), the backup tank is charged layer by layer by way of the diverter valve (A) in the upper part of the tank. The heat quantity measurement (WMZ 2/3 = YES) is automatically activated, however it only measures the solar yield in the direction of the backup tank.
The boiler pump (R5) and the switching valve DWV (R4) recharge the backup tank for the fresh water module FWM15/30i primarily via the boiler sensor (F6) of the heating circuit control unit SKSCEM1. The heating circuit is controlled by means of the flow sensor (S1 (HKM1/2)) and the exterior sensor (S2 (hKM1/2)) on the basis of weather conditions. The backup sensor (S3 (HKM1/2)) generates a requirement to the boiler via the controller output (R5 (HKM1/2)); the backup charging pump (R5 (HKM1/2)) is activated and deactivated again if the temperature falls below the set minimum.
If the maximum backup tank temperature (F3 = ΔT1_1max) has been reached and the collector temperature (F1) is approx. 7°C higher than the swimming pool temperature (F8), the swimming pool is heated by means of the pumps A3a and A3b (use relay to connect in parallel) and the plate heat exchanger until it reaches the set maximum swimming pool temperature (ΔT3max = 30°C), (SBA act. = Yes).
For details on further controller options such as minimum collector temperature, emergency collector shut-off, recooling etc., refer to controller manual SKSC3HE/ SKSCEM1 (download at http://www.sonnenkraft.com > private home). Recommendations for system hydraulics:
As is customary the backup tank is charged primarily (SLM message A3 = 1), therefore the swimming pool charging (A3) is switched off for approx. 2 min every 15 min. During this waiting time, the system checks whether the collector temperature can reach a sufficient temperature level to charge the backup tank and if necessary it is getting charged primarily again.
• Thermosiphon bends on all hot tank connections prevent excessive heat losses through “pipe-in-pipe circulation” (see commissioning and maintenance manual for design details).
The fresh water module FWM15/30i allows a hygienic hot water preparation and generates lowest RL-temperatures in the solar buffer. When hot water is dispensed a flow switch controls the variable speed controlled charging pump, which channels the hot backup water across the plate heat exchanger and heats the cold water to the set service water temperature (settings from 30°C to 65°C are available). In addition the circulation set FWM15/30i-CFK (Hmax = 0,5 bar) can be built in. Activation via automatically learning function, timer or tapping of hot water,
• As an alternative to the U-siphon bends, the connection lines between boiler, consumer net and tank can be laid near to the soil, to avoid pipe-in-pipe circulation (heat losses at standstill). • For service water circulation pipes, a flushing connection must be installed in front of the circulation set! • As is customary for hot water tanks, the cold water connection of the FWM15/30i must have a boiler safety group. A filter ensures that the module functions properly.
23
Legend of symbols used: Absperrorgan Shut-off unit Absperrorgan
Thermisches Dreiwegeventil Thermal three-way valve with mit Verteilfunktion distributive function
thermostatisches
Thermostatic thermostatisches Zirkulationsventil circulation valve
Entleerungshahn
Drain valve
Zirkulationsventil
ETI
Ausdehnungsgefäß Expansion tank mit cap Kappenventil with valve Automatic rapid deaerator
Boiler sensor for heating Boilerfühler für control
Fine filter
automatischer F1 SchnellentlüfterS1
M
Entlüftungstopf
Temperaturfühler Temperature sensor Temperature sensor Temperaturfühler Temperature sensor Temperaturfühler
F1
BF BS
Air vent
Heizungsregelung
Electromotive three-way elektromotorischer mixer Dreiwegemischer
F
PumpPumpe Boiler safety group Kesselsicherheitsgruppe
Durchflussmengenmesser
Flow volume meter
Feinfilter
Luftabscheider
Air separator
bar
stromlos
Manometer
Flushing device
Spüleinrichtung
W
Manometer
Elektromotorisches Dreiwegeventil mit Verteilfunktion und Federrückzug
Flow measuring unit Durchflussmesseinheit
Strangregulierventil
Electromotive three-way valve with distributive function and spring return
Choking valve
°C Thermometer Thermometer
Backup tank
Puffer-Verbindungsschlauch connecting hose Thermostatic TBM Thermostatischer Corrugated pipe service water mixer Wellrohr-Speicheranschluss Brauchwassermischer (For installation, see installation tank connection
instructions) (Anschluss siehe Montageanleitung)
with mit TH Thermostat Thermostat electric switching contact
elektrischem Schaltkontakt
Rückschlagventil und Schwerkraftbremse
Reflux valve and gravity brake
Safety valve with Sicherheitsventil drip funnel
mit Tropftrichter
Volume measuring instrument Volumenmessteil für
heat volume counting Wärmemengenzählung SKSRV for Plate heat exchanger Plattenwärmetauscher
SONNENKRAFT Solar Systems GmbH • Industriepark • 9300 St. Veit/Glan Tel.: +43 (0)4212 450 10 - 400 • Fax: +43 (0)4212 450 10-477 • E-mail:
[email protected]
SONNENKRAFT
....
. ....
m²
S4*
°C
M
S3*
°C
FWM15i/30i
S1
Control unit Solar:
SKSC2HE SKSC2+
A
B
D
S2
SM
BS
S1 > S2 = R1 S3*, S4* for heat balancing Output R2 not activated Diagram: system 1 (standard)
E
F
CW
Circ
HW
PSR .......E
F
K-RL
°C
Radiator
Heating circuit 1
M
RAS
HK-RL
°C
Diagram Manual
Q,T
PSKR18HE
R1
bar
r cto lle Co
AG...S
T
T
HW-Charging pump
Floor heating
Heating circuit 2
NOTE: ALL DIAGRAM MANUALS EARLIER THAN EDITION 140513-SM-GB BECOME VOID HEREWITH!
2
Vers.Nr. 140513-SM-GB
COMFORT E Plus 4.0 Heating-set with backup tank PSC E + PS E parallel connected; Water heating with fresh water module; Backup heating with heating circuit module; pool heating directly via solar circuit; reheating with oil-/gas-/pellets boiler Control concept: (Controller diagram: stratified buffer charging + Pool)
deactivation via temperature sensor in the circulation unit. In the circulation operation the hot return from the FWM is getting stratified via a switching valve in the middle tank area. A manually activatable disinfection mode (80 °C for max. 60 minutes) can sterilize the hot water network.
If the collector temperature (F1) is approx. 7°C higher than the backup tank temperature (F3), the solar pump (A1) is activated (Start spd.1 = 80%). If the flow temperature in the stratified charging module (F2) is approx. 5°C higher than the backup tank temperature (F3), the backup charging pump (A2) charges the backup tank to a set maximum backup tank temperature of approx. 90°C. The speed control of the pumps A1 and A2 tries to bring the temperature for backup charging to approx. 63°C and keep it there. If the secondary flow temperature in the stratified charging module (F5) is approx. 3°C higher than the upper backup tank temperature (F6), the backup tank is charged layer by layer by way of the diverter valve (A) in the upper part of the tank. The heat quantity measurement (WMZ 2/3 = YES) is automatically activated, however it only measures the solar yield in the direction of the backup tank.
The boiler pump (R5) and the switching valve DWV (R4) recharge the backup tank for the fresh water module FWM15/30i primarily via the boiler sensor (F6) of the heating circuit control unit SKSCEM1. The heating circuit is controlled by means of the flow sensor (S1 (HKM1/2)) and the exterior sensor (S2 (hKM1/2)) on the basis of weather conditions. The backup sensor (S3 (HKM1/2)) generates a requirement to the boiler via the controller output (R5 (HKM1/2)); the backup charging pump (R5 (HKM1/2)) is activated and deactivated again if the temperature falls below the set minimum.
If the maximum backup tank temperature (F3 = ΔT1_1max) has been reached and the collector temperature (F1) is approx. 7°C higher than the swimming pool temperature (F8), the swimming pool is heated by means of the pumps A3a and A3b (use relay to connect in parallel) and the plate heat exchanger until it reaches the set maximum swimming pool temperature (ΔT3max = 30°C), (SBA act. = Yes).
For details on further controller options such as minimum collector temperature, emergency collector shut-off, recooling etc., refer to controller manual SKSC3HE/ SKSCEM1 (download at http://www.sonnenkraft.com > private home). Recommendations for system hydraulics:
As is customary the backup tank is charged primarily (SLM message A3 = 1), therefore the swimming pool charging (A3) is switched off for approx. 2 min every 15 min. During this waiting time, the system checks whether the collector temperature can reach a sufficient temperature level to charge the backup tank and if necessary it is getting charged primarily again.
• Thermosiphon bends on all hot tank connections prevent excessive heat losses through “pipe-in-pipe circulation” (see commissioning and maintenance manual for design details).
The fresh water module FWM15/30i allows a hygienic hot water preparation and generates lowest RL-temperatures in the solar buffer. When hot water is dispensed a flow switch controls the variable speed controlled charging pump, which channels the hot backup water across the plate heat exchanger and heats the cold water to the set service water temperature (settings from 30°C to 65°C are available). In addition the circulation set FWM15/30i-CFK (Hmax = 0,5 bar) can be built in. Activation via automatically learning function, timer or tapping of hot water,
• As an alternative to the U-siphon bends, the connection lines between boiler, consumer net and tank can be laid near to the soil, to avoid pipe-in-pipe circulation (heat losses at standstill). • For service water circulation pipes, a flushing connection must be installed in front of the circulation set! • As is customary for hot water tanks, the cold water connection of the FWM15/30i must have a boiler safety group. A filter ensures that the module functions properly.
23
Legend of symbols used: Absperrorgan Shut-off unit Absperrorgan
Thermisches Dreiwegeventil Thermal three-way valve with mit Verteilfunktion distributive function
thermostatisches
Thermostatic thermostatisches Zirkulationsventil circulation valve
Entleerungshahn
Drain valve
Zirkulationsventil
ETI
Ausdehnungsgefäß Expansion tank mit cap Kappenventil with valve Automatic rapid deaerator
Boiler sensor for heating Boilerfühler für control
Fine filter
automatischer F1 SchnellentlüfterS1
M
Entlüftungstopf
Temperaturfühler Temperature sensor Temperature sensor Temperaturfühler Temperature sensor Temperaturfühler
F1
BF BS
Air vent
Heizungsregelung
Electromotive three-way elektromotorischer mixer Dreiwegemischer
F
PumpPumpe Boiler safety group Kesselsicherheitsgruppe
Durchflussmengenmesser
Flow volume meter
Feinfilter
Luftabscheider
Air separator
bar
no current stromlos
Manometer
Flushing device
Spüleinrichtung
W
Manometer
Elektromotorisches Dreiwegeventil mit Verteilfunktion und Federrückzug
Flow measuring unit Durchflussmesseinheit
Strangregulierventil
Electromotive three-way valve with distributive function and spring return
Choking valve
°C Thermometer Thermometer
Backup tank
Puffer-Verbindungsschlauch connecting hose Thermostatic TBM Thermostatischer Corrugated pipe service water mixer Wellrohr-Speicheranschluss Brauchwassermischer (For installation, see installation tank connection
instructions) (Anschluss siehe Montageanleitung)
with mit TH Thermostat Thermostat electric switching contact
elektrischem Schaltkontakt
Rückschlagventil und Schwerkraftbremse
Reflux valve and gravity brake
Safety valve with Sicherheitsventil drip funnel
mit Tropftrichter
Volume measuring instrument Volumenmessteil für
heat volume counting Wärmemengenzählung SKSRV for Plate heat exchanger Plattenwärmetauscher