Transcript
D-Series Operator Interface
Quick Start Programming Guide Version 1.0 © 2011
Acrolon Technologies, Inc. Sonoma, California 707-938-1300
D-Series Operator Interface
Acrolon Technologies, Inc.
Overview The D-Series operator interface (sold separately) provides users with the ability to locally monitor and modify operating parameters of the D-Series controller to which it is attached. This is accomplished through the 4 x 20 character back-lit LCD and the four membrane front panel push buttons provided.
Monitor Mode At power up, the D-Series controller flashes its firmware version momentarily and then enters monitor mode. In monitor mode, the controller sequentially cycles through its eight control loops (channels), displaying key parameters of each. Figure 1.0 below illustrates the channel parameters displayed in monitor mode, as well as definitions of the four front panel push buttons. Channel Indicator
Probe Temperature
Temperature Units
Relay Status
CH 1 SP:21.0 C
Setpoint
22.5 C COOL*
Mode
Enter Button
Advance Buton
Down Button
Up Button
Figure 1.0 Item Descriptions: Channel Indicator: Probe Temperature: Temperature Units: Setpoint: Mode: Relay Status:
Displays the currently selected control loop channel (CH1 - CH8) Indicates the temperature of the probe attached to the currently selected channel Indicates the temperature unit of measure (configurable as either Celsius or Fahrenheit) Indicates the Setpoint of the currently selected channel Indicates the mode of the currently selected channel (configurable as either OFF, COOL, HEAT or AUTO, depending on model and options) Indicates the status of the relay output(s) associated with the currently selected channel; COOL* indicates the cooling relay is engaged HEAT* indicates that the heating relay is engaged AUTO* indicates that the cooling relay is engaged (note no space in front of *) AUTO * indicates that the heating relay is engaged (note space in front of *)
1
D-Series Operator Interface
Acrolon Technologies, Inc.
General Programming Procedure The flow chart below details the general procedure for programming the D-Series controller via the local operator interface. This process of involves the following steps: 1. Enter program mode 2. Select the desired control loop channel 3. Selected the desired process loop parameter 4. Adjust the selected parameter to the desired value 5. Exit program mode (return to monitor mode)
Programming Flow Chart
1. Press and hold for 2 seconds to enter program mode
CH 1 SP:21.0 °C
Programming Cursor
22.5 °C COOL
2. Press as needed to select desired channel
3. Press to advance to desired parameter
4. Press to adjust selected programming parameter Next parameter
5. Press and hold for 2 seconds to end program mode and return to monitor mode
2
D-Series Operator Interface
Acrolon Technologies, Inc.
SETPOINT Programming The Setpoint control parameter determines the temperature above or below which a channels cooling and heating relays are engaged. In COOL mode setpoint determines the temperature above which cooling is engaged. In HEAT mode, setpoint determines the temperature below which heating is engaged. In AUTO mode, setpoint determines the temperature around which both cooling and heating is engaged.
Programming Cursor
CH 1 SP:21.0 °C
22.5 °C COOL
1. Press and hold for 2 seconds to enter program mode
2. Press as needed to select desired channel
3. Press as needed to advance to the SP parameter
4. Press or hold to adjust setpoint to the desired value.
5. Press and hold for 2 seconds to end program mode and return to monitor mode or press the advance button again as needed to select another parameter
3
D-Series Operator Interface
Acrolon Technologies, Inc.
MODE Programming Each D-Series channel supports the following thermostatic modes: § § § §
COOL Mode: In this mode the channel will engage its cooling relay whenever its probe temperature rises above its setpoint value. HEAT Mode: In this mode the channel will engage its heating relay whenever its probe temperature falls below its setpoint. AUTO Mode: In this mode the channel will automatically switch between HEAT mode and COOL mode as needed to maintain temperature around its setpoint. OFF: In this mode all thermostatic operation and alarm processing is disabled for the selected channel. Additionally, when networked to TankNET® control software, data logging and alarm notifications for the channel are also disabled.
CH 1 SP:21.0 °C
22.5 °C COOL
1. Press and hold for 2 seconds to enter program mode
2. Press as needed to select desired channel
3. Press as needed to advance to the MODE parameter
4. Press as needed to select the desired MODE
5. Press and hold for 2 seconds to end program mode and return to monitor mode or press the advance button again as needed to select another parameter
4
Programming Cursor
D-Series Operator Interface
Acrolon Technologies, Inc.
DEVIATION ALARM Programming The deviation alarm parameter (SPDEV ALRM) specifies the maximum desired temperature deviation from setpoint for alarming purpose. Should the channel’s probe temperature exceed these thresholds, an alarm condition is raised and indicated by the front panel ALARM LED. Additionally, when networked to TankNET control software, D-Series channel alarms may also trigger e-mail alarm notifications. Note: To disable alarm processing, set ALDEV ALRM equal to 0.0° Example: For: SP = 20.0°C, SPDEV ALRM = 2.0°C; A channel alarm state will exist per the following: 18.0°C > Probe_Temp > 22.0°C
CH 1 SPDEV ALRM:
22.5 °C 2.0 °C
1. Press and hold for 2 seconds to enter program mode
2. Press as needed to select desired channel
3. Press as needed to advance to the SPDEV ALRM parameter
4. Press as needed to adjust SPDEV ALRM to the desired value (0.0 for OFF)
5. Press and hold for 2 seconds to end program mode and return to monitor mode or press the advance button again as needed to select another parameter
5
Programming Cursor
D-Series Operator Interface
Acrolon Technologies, Inc.
DIFFERENTIAL Programming Channel differential determines the amount of hysteresis applied to thermostat switching near setpoint. Access to this parameter requires an extra programming step. Differential is applied per the following: §
§
§
COOL Mode: COOLING ON: Probe_Temp >= SP + Differential COOLING OFF: Probe_Temp <= SP HEAT Mode: HEATING ON: Probe_Temp <= SP - Differential HEATING OFF: Probe_Temp >= SP AUTO Mode: see COOL and HEAT modes above
Programming Cursor
CH 1 Dif: 0.5 °C
22.5 °C
1. Press and hold for 2 seconds to enter program mode
2. Press as needed to select desired channel
3. Press as needed to advance to the SPDEV ALRM parameter
4. Press and hold to advance to SP DIFF
5. Press as needed to adjust SP DIFF to the desired value.
6. Press and hold for 2 seconds to end program mode and return to monitor mode or press the advance button again as needed to select another parameter
6
D-Series Operator Interface
Acrolon Technologies, Inc.
OFFSET Programming The offset parameter provides a means of calibrating a channel’s probe temperature to a known reference temperature. This single-point calibration procedure can be performed at any reference temperature between 0°C and 50°C with equal accuracy across the probe’s full temperature range of -25°C to +105°C. Offset is algebraically added to its probe temperature to produce a calibrated temperature reading, which is then used for all thermostat logic and alarm processing. Access to this parameter requires an extra programming step.
Programming Cursor
CH 1 22.5 °C OFFSET: 1.0 °C
1. Press and hold for 2 seconds to enter program mode
2. Press as needed to select desired channel
3. Press as needed to advance to the SPDEV ALRM parameter
4. Press and hold to advance to SP DIFF
5. Press to advance to OFFSET
6. Press as needed to adjust OFFSET so that probe temperature equals that of the reference temperature.
7. Press and hold for 2 seconds to end program mode and return to monitor mode or press the advance button again as needed to select another parameter
7
D-Series Operator Interface
Acrolon Technologies, Inc.
TEMPERATURE UNITS Programming The units parameter determines units of measure (°C or °F) for all temperature type process parameters. This setting applies to all channels.
Programming Cursor
SYS CONFIG: Units: °C
1. Press and hold for 2 seconds to enter program mode
3. With programming cursor pointing to CH selection, press and hold the advance button until the UNITS parameter is displayed
4. Press as needed to select the desired temperature unit of measure (°C or °F).
5. Press and hold for 2 seconds to end program mode and return to monitor mode or press the advance button again as needed to select another parameter
8