2–35 Installation , Wiring, and Specifications
D4–32ND3–1, 24VDC Input
D4–32ND3–2 5–12VDC Input
32 (sink/source)
Inputs per module
32 (sink/source)
Commons per module
4 (isolated)
Commons per module
4 (isolated)
Input voltage range
20–28VDC
Input voltage range
4.75–13.2VDC (TTL, CMOS)
Peak voltage
30VDC
Peak voltage
15VDC
ON voltage level
> 19V
ON voltage level
> 4 V (use pullup R for TTL in)
OFF voltage level
< 10 V
OFF voltage level
<2V
Input impedance
4.8 K W
Input impedance
2 KW @ 5V,1.6 KW @ 12V
Input current
5 mA
Input current
3.1 mA @ 5V, 7.5 mA @ 12V
Minimum ON current
3.5 mA
Minimum ON current
1.8 mA
Maximum OFF current
1.6 mA
Maximum OFF current
0.8 mA
Base power required 5V
150 mA max
Base power required 5V
150 mA max
OFF to ON response
2–10 ms
OFF to ON response
1–4 ms
ON to OFF response
2–10 ms
ON to OFF response
1–4 ms
Terminal type
Removable, 40 pin conn.
Terminal type
Removable, 40 pin conn.
Status indicators
Logic Side
Status indicators
Logic Side
Weight
6.6 oz. (190 g)
Weight
6.6 oz. (190 g)
Derating Chart
Points 32 28 24 20 16 12 8 4 0
24VDC
INPUT A-B C-D B/D
A/C 0 1 2 3
4 5 6 7
0 1 2 3
4 5 6 7
D4–32ND3–1
0 10 20 30 40 50 60° C 32 50 68 86 104 122 140° F Ambient Temperature (°C/°F) Current Flow User Supply –
Current Flow –
User Supply +
Current Flow
+ User Supply – Current Flow
B0 B4 B1 B5 B2 B6 B3 B7 COM II C0 C4 C1 C5 C2 C6 C3 C7 COM III D0 D4 D1 D5 D2 D6 D3 D7 COM IV
24 VDC Common + –
A-B
0 10 20 30 40 50 60° C 32 50 68 86 104 122 140° F Ambient Temperature (°C/°F)
20–28VDC, CLASS2 4.2–5.8mA
Current Flow +
User Supply –
Current Flow – User Supply +
Current Flow
+ User Supply – Current Flow
5–12 VDC + –
0 1 2 3
4 5 6 7
A0 A4 A1 A5 A2 A6 A3 A7 COM I
DISPLAY SELECT
A-B C-D
4.75–13.2VDC, CLASS2 3.1–8.2mA A0 A4 A1 A5 A2 A6 A3 A7 CI CI B0 B4 B1 B5 B2 B6 B3 B7 CII CII C0 C4 C1 C5 C2 C6 C3 C7 CIII CIII D0 D4 D1 D5 D2 D6 D3 D7 CIV CIV
B0 B4 B1 B5 B2 B6 B3 B7 COM II C0 C4 C1 C5 C2 C6 C3 C7 COM III D0 D4 D1 D5 D2 D6 D3 D7 COM IV
Common To LED
Use Display Select switch to view Optical(A0–A7, B0–B7) or (C0–C7, D0–D7) Isolator
4 5 6 7
D4–32ND3–2
To LED
Input
INPUT A-B C-D B/D
A/C 0 1 2 3
C-D
A0 A4 A1 A5 A2 A6 A3 A7 CI CI B0 B4 B1 B5 B2 B6 B3 B7 CII CII C0 C4 C1 C5 C2 C6 C3 C7 CIII CIII D0 D4 D1 D5 D2 D6 D3 D7 CIV CIV
5–12VDC
Current sinking config. shown
Input
Use Display Select switch to view B0–B7) or (C0–C7, D0–D7) Current sinking config. shown
Optical (A0–A7, Isolator
DL405 User Manual, 3rd Edition, Rev. E
Installation and Safety Guidelines
+
A0 A4 A1 A5 A2 A6 A3 A7 COM I
DISPLAY SELECT
Derating Chart
Points 32 28 24 20 16 12 8 4 0
Installation, Wiring, and Specifications
Inputs per module