12 Fiber MPO MultiMode Trunk Cables
The 12 fiber MPO trunk cables are designed for data center solutions supporting the topologies as specified in the data center standards EN50173-5, ISO/IEC 24764 and TIA-942. The MPO system supports data center applications such as 10-40-100 Gigabit Ethernet, 4-8-16G Fibre Channel or InfiniBand. 12 fiber MPO female/female trunk cables are used to connect 12 fiber (10G) MPO/LC-SC cassettes. MPO trunk cables allow for either crossconnections or inter-connections to the equipment. When the MPO cable is connected with MPO couplers, one of the MPO connectors must have pins. The MPO trunk cables are constructed from loose tube, gel-filled indoor/outdoor rated cable. The transition at each end to 3.2mm round MPO tails is protected with an over-molded fan-out with free floating fiber technology. On both sides of the MPO connector, the tails are protected with a clear plastic protection sleeve. The sleeve is closed with a re-usable tie-wrap which later can be used as a strain relief for the MPO trunk to the panel or cabinet at the over-molded fan-out. For placing/pulling the trunks over longer lengths, a re-usable IP67 protection/pulling kit can be ordered separately. MPO trunk cables are available with a 12, 24 and 48 fibers.
Features • Pre-terminated low loss MPO LSZH trunk cable • Overmolded midi fan-out offers additional strain relief when trunks are terminated within enclosures/panels. • Overmolded midi fan-out offers free floating fiber technology
• MPO performance for OM3: Attenuation ≤0.5 dB(max.) RL ≥25 dB(min) • MPO tail length 60 cm (12 and 24 fiber) and 60/70cm (48 fiber) • Protection / pulling kit can be ordered separately.
• OM3 OPTOBEND bend insensitive fiber glass loose tube gel filled cable jacket
1
For more information, visit commscope.com
12 Fiber MPO MultiMode Trunk Cables
Specification (The following content can be copied and pasted directly into tender response documents. Choose your preferred option from content inside [x,y,z].) The MPO trunk will be [1x12 – 2x12(24) – 4x12(48)] fiber. The optical cable used is an OM3 LSZH, indoor/outdoor, loose tube, [12 – 24 - 48] fiber, bend insensitive fiber with a diameter of [6.4 +/- 0.4mm (for 12 fiber), 7.5 +/- 0.4mm (for 24fiber), 11.5 +/- 0.4mm (for 48fiber]. The outer jacket color is aqua with the standard AMP NETCONNECT printing. At both ends of the MPO trunk, the transition from the round cable to the [1, 2 or 4] round MPO tails [60cm for the 12 and 24 fiber trunks and 2x60 +2x 70cm for the 48 fiber trunks] is achieved via an over-molded Midi Fan-out that includes the option for strain relief of the trunk using a tie-wrap. If the cable length “L” is ≤50m, the MPO-trunk will be bundled with hook & eye style cable ties and packed in a box. For length “L” >50m, the trunk will be delivered on a reel to facilitate the installation of these trunks. The MPO tails are protected on both sides with a clear plastic protection sleeve which can be closed with a re-usable tie wrap. The re-usable tie-wrap can be used as strain relief on the MPO trunk to the panel or cabinet. For placing/pulling the trunks over longer lengths, a re-usable IP67 protection/ pulling kit can be ordered separately.
Cable drawing and wire map Note: MPO trunk cable lengths are measured between the fan-outs.
2
For more information, visit commscope.com
12 Fiber MPO MultiMode Trunk Cables
Technical Details Connector type MPO/MTP
12 fiber (1 row) low loss MPO connector
† The MTP multi-fiber connector is US Conec’s trademarked name for an improved MPO connector. The CommScope MPO connectors meet and exceed the MTP performance.
Optical Characteristics MPO Attenuation
OM3 ≤0.5dB
MPO Return Loss
OM3 ≥25dB
OM3 fiber
OPTOBEND bend insensitive fiber , IEC 60793-2-10 type A1a.2 / A1a.3, ISO/IEC 11801 OM3 / OM4, TIA/EIA-492AAAC / 492AAAD
OM3 bandwidth
OFL bandwidth ≥ 1500 MHz.km @ 850nm /EMB ≥2000MHz.km @ 850nm
Mechanical Characteristics Operating Temperature
-10 to +60°C
Flammability
IEC 60332 Parts 1 and 3
Approvals/Compliant Structured cabling
ISO/IEC 11801 / Cenelec EN 50173-1 / TIA-568 C.0
Data Center
Cenelec EN 50173-5 / ISO/IEC 24764/ TIA-942
Application
Ethernet IEEE 802.3; 10/40/100GbE / Fiber Channel PI5; 4-8-16G / InfiniBand Architecture spec Volume 2
Connectors
IEC61754-4.20; IEC61754-7; IEC 61300-3-30; TIA 604-5-D (FOCIS 5); EN50377-15-1 RoHS Compliant
† Specifications subject to change without notice.
Ordering Information Tail Length**
Part Number 2-99 meter*
1x12 fiber MPO female-female, OM3
1x60 cm
y-2055707-x
y-2055708-x
2x12 fiber MPO female-female, OM3
2x60 cm
y-2055709-x
y-2055710-x
4x12 fiber MPO female-female, OM3
2x60 + 2x70cm
y-2160071-x
y-2160072-x
Description *
Part Number 100-500 meter*
* For OM4 MPO patch cables see the CommScope MPOptimate MPO trunk cable spec sheet ** X and Y indicate the length of the patch cable. Cable lengths (“L”) from 2-99 meter are defined in length table with part number 2055705. Cable lengths (“L”) from 100-500 meter are defined in length table with part number 2055706
3
For more information, visit commscope.com
www.commscope.com Visit our website or contact your local CommScope representative for more information. © 2015 CommScope, Inc. All rights reserved. AMP NETCONNECT, MPOptimate and all trademarks identified by ® or ™ are registered trademarks or trademarks, respectively, of CommScope, Inc. This document is for planning purposes only and is not intended to modify or supplement any specifications or warranties relating to CommScope products or services. PS-321221.1-EU (12/15)