Transcript
Three Phase Solid State Relays Series: 12 SJ/K
HIGHLIGHTS !" !" !" !" !" !" !" !"
INPUT: DC CONTROL HIGH DV/DT OUTPUT: DIRECT COPPER BONDED BACK-TO-BACK SCR OPTO ISOLATION 2500 VAC (4000 V optional) VOLTAGE RANGE 100 TO 660 VAC LOAD CURRENT 3x25A / 50A / 75A / 90A REVERSE POLARITY PROTECTION FOR DC INPUT CONTROL Weight = 344 g
(J: Zero voltage turn-on; K: Random turn-on)
ELECTRICAL SPECIFICATIONS Parameter
DC CONTROL Control voltage range Control current range Pick-up voltage Drop-out voltage Input resistance OUTPUT Mains control voltage Repetitive peak off state voltage RMS on-state current (per phase) Zero turn-on voltage On-state voltage drop Off-state leakage current @ rated voltage Peak one cycle surge current (non-rep) Holding current Critical rate of rise of off-state voltage Thermal resistance (junction to case) Frequency range Operating temperature Turn-on time Turn-off time Fusing current
Type
Symbol
Unit
PSD 12 D 122500
PSD 12 D 125000
PSD 12 D 127500
PSD 12 D 129000
4-32 8-80 4-0 1-0
4-32 8-80 4-0 1-0
4-32 8-80 4-0 1-0
4-32 8-80 4-0 1-0
Vdc mA Vdc Vdc
100-660 800-1600 90 35 2.0 1 1150 250 1000 0.56 47-63 -30 to +80 10 10 5000
Vac Vpk A Vac Vac mA A mA V/µs K/W Hz °C ms ms A2s
Current regulator
VRMS VDRM IT VTM IDRM ITSM IH dv/dt Rthjc f TO T-on T-off I2t
100-660 800-1600 25 35 1.8 1 400 250 1000 1.38 47-63 -30 to +80 10 10 600
100-660 800-1600 50 35 2.0 1 500 250 1000 0.7 47-63 -30 to +80 10 10 1250
100-660 800-1600 75 35 2.0 1 1150 250 1000 0.6 47-63 -30 to +80 10 10 5000
released, E 197669
POWERSEM reserves the right to change limits, test conditions and dimensions -
[email protected] - www.POWERSEM.net POWERSEM 2007 All rights reserved
Three Phase Solid State Relays MECHANICAL SPECIFICATIONS Dimensions in mm
+0,4
+0,1
20
73,0
57,0 47,6
+1,0
Three Phase Solid State Relay
22
20
20 92 +0,1
34,5
23 +0,3 24 +0,4
104
30 (MAX)
90
75
F
CURRENT (A)
60 50 45
30 25
F
F
15
10
20
30
40
50
60
70
80
90
AMBIENT TEMPERATURE ( C )
HEAT SINK USED:
0,14 K/W
FAN USED:
70 CFM
VALIED FOR SERIES: PSD 12 SJK
POWERSEM reserves the right to change limits, test conditions and dimensions -