Transcript
Q-LS 320 Output Capacity (VA) Capacity (Watts) Output Current (peak Amp) 1 phase (208/120 VAC) Output Current (peak Amp) 1 phase (415/380 VAC) Output Current (peak Amp) 1 phase (480/277 VAC) Output Current (peak Amp) 3 phase (208/120 VAC) Output Current (peak Amp) 3 phase (415/380 VAC) Output Current (peak Amp) 3 phase (480/277 VAC)
Nominal Voltage range (3 phase)* Nominal Voltage range (1 phase)* Frequency* Frequency tracking Output power factor Output Wavefrom Outlets Single phase output 3 phase output
320,000 256,000 2794 1397 1114 NA NA NA 220V / 380V / 460V 208VY / 380 VY / 400VY / 415 VY / 480VY NA 50, 60 or 400 Hz ± .1% ± 5% of the input frequency > 0.8 High resolution, pure sine wave Terminal block No Yes
Input Current (amp) (208 / 120VAC) Current (amp) (415 / 380VAC) Current (amp) (480 / 277VAC) Current (max amp) (120/130 VAC) Current (max amp) (415 / 380VAC) Current (max amp) (480 / 277VAC) Power factor (12 pulse rectifier) Power factor (18 pulse rectifier) Frequency* Input impedance of entire system
1152 576 470 1456 728 576 .75 to .90 Available 50, 60 or 400 Hz ± 5 % 750 m ohm
General Input and output impedance UPQ power conditioning topology Remote power management
5%
Five (5) Stages of Isolation and Conversion, High Frequency, True On-line digital sine wave
Yes
Voltage Regulation Input voltage range: - Full load without using battery - Half load without using battery Output voltage regulation
208 to 600 VAC ± 20% ± 25% ± 1%
Q-LS 320 Page 1
Isolation Input to output isolation Common-mode noise rejection Normal-mode noise rejection
Dielectric Strength 5 kv, 120 dB common mode attenuation Yes Yes
Suppression IEEE 587/ANSI 62.41 (North America) IEEE 587/ANSI 62.41 (International) Joules (energy absorption) TVSS MOV joule rating TVSS low pass filter Peak surge current (amp) Multi-stage protection Reverse inverter impulse protection IEC FCC EN500091-1 EN500091-2 EN 60610 (leakage current) CE approval Conditioning Output THD (linear load) Current THD (6 pulse rectifier) Current THD (12 pulse rectifier) Input frequency range
Yes Yes 2200 765 Joules per phase 750 Hz 20000 Yes 54 joules without batteries 62040-2 Class A Yes Yes < 1 mA
Yes Yes < 2% Maximum of 20% Maximum of 9% 50/60 Hz ± 7 Hz
High Frequency on-Line Inverter Inverter design Inverer driver frequency Inverter regulation Overload capacity Crest factor Transfer time Overall system efficiency Efficiency UPQ to bypass/bypass to UPQ
Full bridge 20 kHz 50/60 Hz ± 0.1 Hz >110% continuous 3:1 Zero 93% > 93% Zero cross transfer, < 4 mSec (2 mSecminimum)
Rectifier 6 pulse 12 pulse Efficiency Current limit (amp) (208 / 120VAC)
110 µs single phase triggering 6.4 kHz pulse width, 80 µs for 1.7 ms around 11 pulses 0.98 54
Q-LS 320 Page 2
Current limit (amp) (415 / 380VAC) Current limit (amp) (480 / 277VAC)
27 22
Static Switch Voltage range Frequency range Efficiency Transfer time - main to inverter Transfer time - inverter to main Transfer time - overload 100% Transfer time - overload 300%
174 VAC - 277VAC (line to neutral)
45 - 55 Hz / 55 - 65 Hz 99.5% 0 ms 0 ms 30 seconds 1 seconds
Battery (standard configurations) Full load run time 9min/ext. pack) Half load run time (min/ext. pack) DC voltage Recharge time Battery charger Maximum recharge current (amps) Boost charge Float charge Battery low voltage Battery low stop voltage Hot-swappable
18 min/(8)B 45 min/(8)B 348 VDC 5 to 8 hours Constant voltage with current limit
160 410 / 415 VDC 396 / 410 VDC 320 / 305 VDC 295 / 285 VDC Yes
Environmental Maximum heat dissipation kW Maximum heat dissipation BTU/hr Operating temperature Humidity Audible noise Altitude De-rating temperature to altitude
17.4 59,392 32° to 122° F (0° to 50° C) 0% - 90% non-condensing < 65 dBA at 1 meter Less than 6,600 ft 92,000 m) above sea level 39° F / 3,281 ft (4° C / 1,000 m)
Physical WxDxH Weight in Ibs (no battery) Weight in kg (no battery) Battery pack A/B WxDxH (26 Ah) Battery pack A/B weight (26 Ah) Battery pack C/D WxDxH (88 & 100 Ah) Battery pack C/D weight (88 & 100 Ah)
87 x 32 x 63 in (2220 x 800 x 1600 mm) 5,400 2,450 21.5 x 32 x 63 in (550 x 800 x 1600 mm) 882 Ibs (400 kg) / 1765 (800 kg) 43.5 x 32 x 63 in (1100 x 800 x 1600 mm) 2375 Ib (1077 kg) / 2500 Ibs (1134 kg)
Power Innovations Int’l, Inc. www.power-innovations.com phone: 801-785-4123 fax: 801-785-6999
Q-LS 320 Page 3