DCC Commercial 15 - 25 Tons Packaged Air Conditioners 15 Tons Cooling Capacity: 180,000 BTU/h 20 Tons Cooling Capacity: 240,000 BTU/h 25 Tons Cooling Capacity: 290,000 BTU/h
■ Contents
Nomenclature................................2 Product Specifications...................3 Expanded Cooling Data..................6 Airflow Data.................................12 Heating Kit Data ..........................14 Dimensions...................................15 Roof Top Curb Installation............18 Wiring Diagrams ..........................20 Accessories...................................27
■ Standard Features
• High-efficiency scroll compressor • Copper tube / aluminum fin coils • Aluminum micro-channel indoor coil on 25-ton units • 25-ton models contain two outdoor fans • High- and low-pressure switches • High-capacity, steel-cased filter drier • Heater kits with single-point entry • Crankcase heaters • 24-volt terminal strip • Power block for field wiring • Units meet the performance outlined in Table 6.8.1-1 of ASHRAE tandard 90.1-2013 • AHRI Certified; ETL Listed
■ Cabinet Features
• Heavy-gauge, galvanized-steel cabinet with UV-resistant powder-paint finish • Built-in filter rack with standard 2” filters (convertible to 4” filters) • Full perimeter rail • Sloped drain pan
* Complete warranty details available from your local dealer or at www.daikincomfort.com.
SS-DCC15
www.daikincomfort.com
3/16 Supersedes 2/16A
Nomenclature
D 1
C 2
C 3
180 060 4,5,6 7,8,9
3 10
B 11
* 12
* 13
* 14
A * 15 16 Major & Minor
Brand D
Daikin
X A B C D E F
Configuration C Standard Efficiency T High Efficiency (3-‐5 Tons) Application C Cooling G Gas Heat H Heat Pump Nominal Cooling Capacity 036 3 Tons 102 048 4 Tons 120 060 5 Tons 150 072 6 Tons 180 090 7½ Tons 240
G
8½ Tons 10 Tons 12½ tons 15 Tons 20 Tons
300
25 Tons
H J K
Nominal Heating Capacity Gas/Electric A/C H/P Factory-‐Installed Electric Heat 045 45,000 BTU/h XXX No Heat 090 90,000 BTU/h 010 10 kW 030 30 kW 115 115,000 BTU/h 015 15 kW 031 30 kW 140 140,000 BTU/h 016 15 kW 045 45 kW 210 210,000 BTU/h 018 18 kW 046 45 kW 350 350,000 BTU/h 020 20 kW 060 60 kW 400 400,000 BTU/h 025 25 kW See product specifications for heat size(s) available for each capacity. Voltage 1 208-‐230/1/60 3 208-‐230/3/60
4 460/3/60 7 575/3/60
Supply Fan/Drive Type/Motor B Belt Drive (single speed) D Direct Drive (3-‐5 Tons)
V Two-‐Speed Belt Drive (also designates 6-‐Ton with two-‐stage compressor)
L M N O P Q R T
Factory-‐Installed Options X No Options 1 A Ultra Low-‐Leak Downflow Economizer H Disconnect Switch (non-‐fused) 1 J Ultra Low-‐Leak Downflow Economizer ; Disconnect Switch (non-‐fused) 2 V Low-‐Leak Downflow Economizer 2 W Low-‐Leak Downflow Economizer ; Disconnect Switch (non-‐fused) Note: Not all options available for all products. 1 Please contact RRS Rooftop Systems directly if Power Exhaust is required. 2 Please use part number DPE1803002 / DPE1803004 / DPE1803007 if Power Exhaust is required.
U V W Y Z
X S D K
Revision Levels
Factory-‐Installed Options No Options Non-‐powered convenience outlet Powered convenience outlet Low-‐ambient kit Return air smoke detector Supply air smoke detector Non-‐powered convenience outlet; Low-‐ambient kit Non-‐powered convenience outlet; Return air smoke detector Non-‐powered convenience outlet; Supply air smoke detector Non-‐powered convenience outlet; Return & Supply air smoke detectors Non-‐powered convenience outlet; Low-‐ambient kit; Supply air smoke detector Non-‐powered convenience outlet; Low-‐ambient kit Return & Supply air smoke detectors Powered convenience outlet; Low-‐ambient kit Powered convenience outlet; Return air smoke detector Powered convenience outlet; Return & Supply air smoke detectors Powered convenience outlet; Supply air smoke detector Powered convenience outlet; Low-‐ ambient kit; Return air smoke detector Powered convenience outlet; Low-‐ ambient kit; Supply air smoke detector Powered convenience outlet; Low-‐ambient kit; Return & Supply air smoke detectors Non-‐powered convenience outlet; Low-‐ambient kit; Return air smoke detector Low-‐ambient kit; Return air smoke detector Low-‐ambient kit; Supply air smoke detector Low-‐ambient kit; Return & Supply air smoke detectors Return & Supply air smoke detectors Factory-‐Installed Options Standard Aluminized Heat Exchanger Stainless-‐Steel Heat Exchanger Hinged Panels (3-‐12½ Tons) Stainless-‐Steel Heat Exchanger; Hinged Panels (3-‐12½ Tons)
Factory-‐Installed Options Stainless-‐Steel Heat Exchanger (DCG/DTG units only): A tubular heat exchanger made of 409-‐type stainless steel is installed in the unit. • Low-‐Ambient Kit: Allows for cooling operation at lower outdoor temperatures. On the 3-‐ to 6-‐ton units, cooling operation is extended from 60°F ambient temp-‐ •
• • • •
•
• • •
erature to 35°F outside air temperature. On 7½ -‐20 ton units, cooling operation is extended from 35°F ambient temperature to 0°F outside air temperature. For 25 ton units, cooling operation is extended from 24°F ambient temperature to 0°F outside air temperature. Economizers: Based on air conditions, can provide outside air to cool the space. Electric Heat Kits (DCC/DTC and DCH/DTH units only): Available in all voltage options. Non-‐powered Convenience Outlet: A 120V, 15A, GFCI outlet makes it easier for technicians to service the unit once an electrician runs power to the outlet. Powered Convenience Outlet: A 120V, 15A, GFCI outlet powered with a transformer built into the unit. When a factory-‐installed powered convenience outlet is installed in the equipment, the unit MCA (Min. Circuit Ampacity) will increase by 7.5A for 208/230V units, increase by 3.75A for 460V units, and by 3A for 575V units. The MOP (Max. Overcurrent Protection) device must be sized accordingly. Disconnect Switch (non-‐fused; 3-‐phase units only): A disconnect switch is installed in the unit and factory wiring will be complete from the switch to the unit. Please note that for air conditioning (DCC units) and heat pump models (DCH units), the appropriate electric heat kit must be ordered to be factory-‐installed along with the disconnect switch (non-‐fused) when it is ordered. Please note that for models with a powered convenience outlet option and a disconnect switch (non-‐fused) option, the power to the powered convenience outlet will be shut off when the disconnect switch (non-‐fused) is in the off position. Return Air and/or Supply Air Smoke Detectors: Return air and/or supply air smoke detectors are installed in the unit. Two-‐speed indoor fan blower models are available on 6, 7½, 8½, 10, 12½, 15, 20, & 25-‐ton units. Section 6.4.3.10.b of ASHRAE Standard 90.1-‐2010 and Section 6.5.3.2.1.a of ASHRAE Standard 90.1-‐2013 require a minimum of two fan speeds. Section 140.4(m)1 of California Energy Commission Title 24 2013 contains a similar requirement. Hinged Access Panels: Allows access to unit’s major components. Combined with latches for easy access to control box, compressor, filters and blower motor. Available on 3-‐12½ Tons units.
2
www.daikincomfort.com
SS-DCC15
Product Specifications — 15 Tons
DCC180*** 3B***A*
DCC180*** 3V***A*
DCC180*** 4B***A*
DCC180*** 4V***A*
DCC180*** 7B***A*
DCC180*** 7V***A*
Total, BTU/h
180,000
180,000
180,000
180,000
180,000
180,000
Sensible BTU/h
134,600
134,600
134,600
134,600
134,600
134,600
EER / IEER
11 / 11.2
11 / 12.8
11 / 11.2
11 / 12.8
11 / 11.2
11 / 12.8
88
88
88
88
88
88
6572288
6502018
6572288
6502018
6572288
6502018
Std Static
2-Speed Belt
Std Static
2-Speed Belt
Std Static
2-Speed Belt
6,000
6,000
6,000
6,000
6,000
6,000
Cooling Capacity
Decibels ARI Reference #s Evaporator Motor / Coil Motor Type (Belt Drive) Indoor Nominal CFM Indoor Motor FLA (Cooling) Horsepower - RPM (Speed: Full / Low) Metering Device
9.2
9.1
4.6
4.3
4.2
3.5
3.0 - 1,725
3.0 - 1,760/1,165
3.0 - 1,725
3.0 - 1,760/1,165
3.0 - 1,725
3.0 - 1,760/1,165
TXV
TXV
TXV
TXV
TXV
TXV
20 x 25 x 2 (6)
20 x 25 x 2 (6)
20 x 25 x 2 (6)
20 x 25 x 2 (6)
20 x 25 x 2 (6)
20 x 25 x 2 (6)
1”
1”
1”
1”
1”
1”
R-410A Refrigerant Charge Cir #1
186.2
186.2
186.2
186.2
186.2
186.2
R-410A Refrigerant Charge Cir #2
170.8
170.8
170.8
170.8
170.8
170.8
20
20
20
20
20
20
4 / 16
4 / 16
4 / 16
4 / 16
4 / 16
4 / 16
# of Wheels (D x W)
2 (15” x 12”)
2 (15” x 12”)
2 (15” x 12”)
2 (15” x 12”)
2 (15” x 12”)
2 (15” x 12”)
Motor Sheave
1VM50 x ⅞”
1VP50 x 1⅛”
1VM50 x ⅞”
1VP50 x 1⅛”
1VM50 x ⅞”
1VP50 x 1⅛”
Blower Sheave
BK100 x 1³/₁₆”
BK100 x 1³/₁₆”
BK100 x 1³/₁₆”
BK100 x 1³/₁₆”
BK100 x 1³/₁₆”
BK100 x 1³/₁₆”
BX45
BX44
BX45
BX44
BX45
BX44
3
3
3
3
3
3
Filter Size (#) Drain Size (NPT)
Evaporator Coil Face Area (ft²) Rows Deep / Fins per Inch Belt Drive Evap Fan Data
Belt Condenser Fan / Coil Quantity of Condenser Fan Motors Horsepower - RPM
⅓ - 1,075
⅓ - 1,075
⅓ - 1,075
⅓ - 1,075
⅓ - 1,075
⅓ - 1,075
Fan Diameter / # Fan Blades
22 / 3
22 / 3
22 / 3
22 / 3
22 / 3
22 / 3
Outdoor Nominal CFM
9,000
9,000
9,000
9,000
9,000
9,000
Face Area (ft²)
53.3
53.3
53.3
53.3
53.3
53.3
Rows Deep / Fins per Inch
2 / 27
2 / 27
2 / 27
2 / 27
2 / 27
2 / 27
Compressor Quantity / Type
2 / Scroll
2 / Scroll
2 / Scroll
2 / Scroll
2 / Scroll
2 / Scroll
Compressor RLA / LRA Circuit #1
25 / 164
25 / 164
12.2 / 100
12.2 / 100
9.0 / 78
9.0 / 78
Compressor RLA / LRA Circuit #2
25 / 164
25 / 164
12.2 / 100
12.2 / 100
9.0 / 78
9.0 / 78
208-230/3/60
208-230/3/60
460/3/60
460/3/60
575/3/60
575/3/60
1.2
1.2
1.2
1.2
1.2
1.2
2.0/4.4
2.0/4.4
.9/2.2
.9/2.2
0.9 / 2.2
0.9 / 2.2
Electrical Data / Static Voltage / Phase (60 Hz) Standard Max Static Outdoor Fan FLA / LRA
65.2
65.1
31.7
31.4
24.9
24.2
Min. Circuit Ampacity¹
Total Unit Amps
72
71
35
35
27
27
Max. Overcurrent Protection (amps)²
90
90
45
45
35
35
Entrance Power Supply
2⅛"
2⅛"
2⅛"
2⅛"
2⅛"
2⅛"
Entrance Control Voltage
⅞"
⅞"
⅞"
⅞"
⅞"
⅞"
Operating Weight (lbs)
1965
1965
1965
1965
1965
1965
Ship Weight (lbs)
2080
2080
2080
2080
2080
2080
¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes. ² May use fuses or HACR-type circuit breakers of the same size as noted. Note: Always check the S&R plate for electrical data on the unit being installed.
SS-DCC15
www.daikincomfort.com
3
Product Specifications — 20 Tons
DCC240 ***3B***A*
DCC240 ***3V***B*
DCC240 ***4B***A*
DCC240 ***4V***B*
DCC240 ***7B***A*
DCC240 ***7V***B* 240,000
Cooling Capacity Total, BTU/h
240,000
240,000
240,000
240,000
240,000
Sensible BTU/h
181,000
181,000
181,000
181,000
181,000
181,000
10.0 / 10.1
10.0 / 11.6
10.0 / 10.1
10.0 / 11.6
10.0 / 10.1
10.0 / 11.6
EER / IEER Decibels ARI Reference #s
88
88
88
88
88
88
6502023
8813880
6502023
8813880
6502023
8813880
Std Static
2-Speed Belt
Std Static
2-Speed Belt
Std Static
2-Speed Belt
7,000
7,000
7,000
7,000
7,000
7,000
Evaporator Motor / Coil Motor Type (Belt Drive) Indoor Nominal CFM Indoor Motor FLA (Cooling) Horsepower - RPM (Speed: Full / Low) Metering Device Filter Size (#) Drain Size (NPT)
R-410A Refrigerant Charge Cir #s 1 & 2 Face Area (ft²) Rows Deep / Fins per Inch
13.8
14
6.3
6.6
5.1
5.2
5.0 - 1,725
5.0 - 1,775/1,185
5.0 - 1,725
5.0 - 1,775/1,185
5.0 - 1,725
5.0 - 1,775/1,185
TXV
TXV
TXV
TXV
TXV
TXV
20 x 25 x 2 (6)
20 x 25 x 2 (6)
20 x 25 x 2 (6)
20 x 25 x 2 (6)
20 x 25 x 2 (6)
20 x 25 x 2 (6)
1”
1”
1”
1”
1”
1”
200 ozs.
177 & 195 ozs.
200 ozs.
177 & 195 ozs.
200 ozs.
177 & 195 ozs.
20
20
20
20
20
20
4 / 16
4 / 16
4 / 16
4 / 16
4 / 16
4 / 16
Belt Drive Evap Fan Data # of Wheels (D x W)
2 (15” x 15”)
2 (15” x 15”)
2 (15” x 15”)
2 (15” x 15”)
2 (15” x 15”)
2 (15” x 15”)
Motor Sheave Blower Sheave Belt
1VP60 x 1⅛”
1VP60 x 1⅜”
1VP60 x 1⅛”
1VP60 x 1⅜”
1VP60 x 1⅛”
1VP60 x 1⅜”
BK100 x 1⁷/₁₆”
BK100 x 1⁷/₁₆”
BK100 x 1⁷/₁₆”
BK100 x 1⁷/₁₆”
BK100 x 1⁷/₁₆”
BK100 x 1⁷/₁₆”
BX46
BX45
BX46
BX45
BX46
BX45
Condenser Fan / Coil Quantity of Condenser Fan Motors Horsepower - RPM Fan Diameter / # Fan Blades Outdoor Nominal CFM Face Area (ft²) Rows Deep / Fins per Inch Compressor Quantity / Type
3
3
3
3
3
3
⅓ - 1,075
⅓ - 1,075
⅓ - 1,075
⅓ - 1,075
⅓ - 1,075
⅓ - 1,075
22 / 3
22 / 3
22 / 3
22 / 3
22 / 3
22 / 3
9,000
9,000
9,000
9,000
9,000
9,000
53.3
53.3
53.3
53.3
53.3
53.3
2 / 27
2 / 27
2 / 27
2 / 27
2 / 27
2 / 27
2 / Scroll
2 / Scroll
2 / Scroll
2 / Scroll
2 / Scroll
2 / Scroll
34.0 / 240.0
34.0 / 240.0
16.0 / 140.0
16.0 / 140.0
12.9 / 107.6
12.9 / 107.6
34.0 / 240.0
34.0 / 240.0
16.0 / 140.0
16.0 / 140.0
12.9 / 107.6
12.9 / 107.6
Voltage / Phase (60 Hz)
208-230/ 3
208-230/ 3
460/ 3
460/ 3
575/ 3
575/ 3
Outdoor Fan FLA / LRA
2.4 / 5.2
2.4 / 5.2
1.2 / 2.6
1.2 / 2.6
0.9 / 2.2
0.9 / 2.2
89
89.2
41.9
42.2
33.6
33.7
97.5
97.7
46
46.2
36.8
36.9
Compressor RLA / LRA CIR. #1 Compressor RLA / LRA CIR. #2 Electrical Data / Static
Total Unit Amps Min. Circuit Ampacity¹ Max. Overcurrent Protection (amps)²
125
125
60
60
45
45
Entrance Power Supply
2⅛"
2⅛"
2⅛"
2⅛"
2⅛"
2⅛"
Entrance Control Voltage
⅞"
⅞"
⅞"
⅞"
⅞"
⅞"
Operating Weight (lbs)
2085
2085
2085
2085
2085
2085
Ship Weight (lbs)
2202
2202
2202
2202
2202
2202
¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes. ² May use fuses or HACR-type circuit breakers of the same size as noted. Note: Always check the S&R plate for electrical data on the unit being installed.
4
www.daikincomfort.com
SS-DCC15
Product Specifications — 25 Tons
DCC300 ***3B***A*
DCC300 ***3V***A*
DCC300 ***4B***A*
DCC300 ***4V***A*
DCC300 ***7B***A*
DCC300 ***7V***A*
Cooling Capacity Total, BTU/h
290,000
290,000
290,000
290,000
290,000
290,000
Sensible BTU/h
196,000
196,000
196,000
196,000
196,000
196,000
10.2 / 11.2
10.2 / 11.8
10.2 / 11.2
10.2 / 11.8
10.2 / 11.2
10.2 / 11.8
92
92
92
92
92
92
8199469
8582013
8199469
8582013
8199469
8582013
Std Static
2-speed Belt Drive
Std Static
2-speed Belt Drive
Std Static
2-speed Belt Drive
8,200
8,200
8,200
8,200
8,200
8,200
EER / IEER Decibels AHRI Reference #s Evaporator Motor / Coil Motor Type (Belt Drive) Indoor Nominal CFM Indoor Motor FLA (Cooling) Horsepower - RPM (Speed: Full / Low) Metering Device Filter Size (#) Drain Size (NPT) R-410A Refrigerant Charge Cir #s 1 & 2
20.4
21.0
9.41
10.1
7.5
8.2
7.5 - 1745
7.5 - 1770/1175
7.5 - 1745
7.5 - 1770/1175
7.5 - 1745
7.5 - 1770/1175
TXV
TXV
TXV
TXV
TXV
TXV
20 x 20 x 2 (8)
20 x 20 x 2 (8)
20 x 20 x 2 (8)
20 x 20 x 2 (8)
20 x 20 x 2 (8)
20 x 20 x 2 (8)
1"
1"
1"
1"
1"
1" 215 & 198 ozs.
215 & 198 ozs.
215 & 198 ozs.
215 & 198 ozs.
215 & 198 ozs.
215 & 198 ozs.
Face Area (ft²)
17.2
17.2
17.2
17.2
17.2
17.2
Rows Deep / Fins per Inch
2 / 15
2 / 15
2 / 15
2 / 15
2 / 15
2 / 15
2 (15" x 15")
2 (15" x 15")
2 (15" x 15")
2 (15" x 15")
2 (15" x 15")
2 (15" x 15")
Belt Drive Evap Fan Data # of Wheels (D x W) Motor Sheave
1VP60 x 1⅜"
1VP60 x 1⅜"
1VP60 x 1⅜"
1VP60 x 1⅜"
1VP60 x 1⅜"
1VP60 x 1⅜"
Blower Sheave
BK110 x 1⁷/₁₆"
BK110 x 1⁷/₁₆"
BK110 x 1⁷/₁₆"
BK110 x 1⁷/₁₆"
BK110 x 1⁷/₁₆"
BK110 x 1⁷/₁₆"
BX46
BX46
BX46
BX46
BX46
BX46
Belt Condenser Fan / Coil Quantity of Condenser Fan Motors Horsepower - RPM
2
2
2
2
2
2
1 - 1145
1 - 1145
1 - 1145
1 - 1145
1 - 1145
1 - 1145
Fan Diameter / # Fan Blades
30 / 2
30 / 2
30 / 2
30 / 2
30 / 2
30 / 2
Outdoor Nominal CFM
15,000
15,000
15,000
15,000
15,000
15,000
Face Area (ft²)
53.3
53.3
53.3
53.3
53.3
53.3
Rows Deep / Fins per Inch
2 / 27
2 / 27
2 / 27
2 / 27
2 / 27
2 / 27
Compressor 2 / Scroll
2 / Scroll
2 / Scroll
2 / Scroll
2 / Scroll
2 / Scroll
Compressor RLA / LRA CIR. #1
Quantity / Type
48.1 / 245
48.1 / 245
18.6 / 125
18.6 / 125
14.7 / 100
14.7 / 100
Compressor RLA / LRA CIR. #2
48.1 / 245
48.1 / 245
18.6 / 125
18.6 / 125
14.7 / 100
14.7 / 100
Voltage / Phase (60 Hz)
208-230/ 3
208-230/ 3
460/ 3
460/ 3
575/ 3
575/ 3
Outdoor Fan FLA / LRA
1.6/6.5
Electrical Data 4.5/ 24.1
4.5/24.1
2.1/ 12.2
2.1/12.2
1.6/ 6.5
Total Unit Amps
125.6
126.2
50.8
51.5
40.1
40.8
Min. Circuit Ampacity¹
137.6
138.2
55.4
56.1
43.9
44.6
Max. Overcurrent Protection (amps)²
175
175
70
70
50
50
Entrance Power Supply
2⅛"
2⅛"
2⅛"
2⅛"
2⅛"
2⅛"
Entrance Control Voltage
⅞"
⅞"
⅞"
⅞"
⅞"
⅞"
Operating Weight (lbs)
2109
2119
2109
2119
2109
2119
Ship Weight (lbs)
2377
2387
2377
2387
2377
2387
¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes. ² May use fuses or HACR-type circuit breakers of the same size as noted. Note: Always check the S&R plate for electrical data on the unit being installed.
SS-DCC15
www.daikincomfort.com
5
6
www.daikincomfort.com
4800
6000
6750
4800
6000
6750
71
-
116
284
16
0.65
127
300
12
0.45
115
282
16
0.62
126
297
13
0.43
105
254
21
0.72
112
273
18
0.60
122
288
14
0.41
154.4 160.0 175.3
108
262
19
0.74
167.3 173.4 189.9
109
264
18
0.78
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
71
59
63
67
121
323
16
0.67
132
342
12
0.46
120
320
16
0.64
131
338
13
0.44
109
289
21
0.73
116
311
18
0.61
127
328
14
0.42
150.7 156.2 171.1
112
298
19
0.76
163.3 169.2 185.4
114
301
18
0.80
168.2 174.3 191.0
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
71
59
63
67
127
368
16
0.69
139
389
12
0.48
126
365
17
0.66
137
385
13
0.45
115
329
21
0.76
122
354
18
0.63
133
374
14
0.44
147.0 152.4 167.0
118
339
19
0.79
159.3 165.1 180.9
119
342
18
0.82
164.1 170.1 186.3
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
71
59
63
67
133
414
16
0.71
145
438
12
0.49
132
410
16
0.68
144
433
12
0.47
120
370
21
0.79
128
398
18
0.66
139
420
14
0.46
139.7 144.8 158.6
124
381
19
0.82
151.3 156.9 171.9
125
385
18
0.86
155.9 161.6 177.0
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
71
59
63
67
138
458
15
0.72
150
484
11
0.50
136
453
15
0.69
149
479
12
0.48
124
409
20
0.79
132
440
17
0.66
144
464
13
0.46
129.4 134.1 146.9
128
421
18
0.82
140.2 145.3 159.2
129
425
17
0.86
144.4 149.7 164.0
115
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
71
19
0.81 16
0.61 11
0.40 21
0.94
20
0.84
16
0.63
11
0.41
21
0.97
19
0.87
16
0.66
11
0.42
20
0.98
18
0.88
15
0.66
10
0.43
20
0.77
17
0.59
11
0.38
142
360
22
0.89
121
346
17 389 139
20 368 127
0.60
140
393
0.80
128
372
12
0.39
149
410
22
0.93
126
389
20
0.83
134
419
16
0.63
147
442
11
0.40
156
461
20
0.94
131
430
19
0.84
139
463
15
0.63
152
488
11
0.41
162
509
24
228
100
∆T
HI PR
LO PR
107
246
22
0.70
110
253
117
260
18
0.53
120
268
124
271
13
0.34
128
279
106
256
24
0.81
109
264
113
276
23
0.73
116
284
123
291
18
0.55
127
300
131
304
13
0.35
135
313
117
314
23
0.75
121
323
128
331
18
0.56
132
342
136
346
13
0.36
141
356
116
332
25
0.86
119
342
Shaded area reflects ACCA (TVA) conditions
110
292
25
0.83
114
301
123
357
23
0.77
134
377
19
0.58
121
374
24
0.89
125
385
129
402
22
0.80
133
415
141
425
18
0.61
145
438
150
443
13
0.39
155
457
125
413
23
0.90
129
426
133
444
21
0.81
138
458
146
469
17
0.61
150
484
155
489
12
0.39
160
504
High and low pressures are measured at the liquid and suction access fittings.
143
394
13
0.38
148
406
0.79
22
0.87
133
345
160.7 165.5 179.1 192.3 157.0 161.6 175.0 187.8 153.3 157.8 170.8 183.3 149.5 154.0 166.6 178.8 142.0 146.3 158.3 169.9 131.6 135.5 146.6 157.4
11
0.37
122
327
S/T
17
0.57
115
304
MBh
20
0.76
137
316
103
22
0.84
128
303
LO PR
11
0.35
117
287
22
16
0.55
110
267
236
20
0.73
129
282
∆T
0.81
121
270
HI PR
S/T
111
256
174.2 179.3 194.1 208.3 170.1 175.1 189.6 203.5 166.1 171.0 185.1 198.6 162.0 166.8 180.5 193.8 153.9 158.5 171.5 184.1 142.6 146.8 158.9 170.5
21
0.91
MBh
11
0.39
104
16
0.60
LO PR
19
0.79
21
21
0.89
238
11
0.37
∆T
16
0.58
HI PR
19
0.76
0.85
115
-
-
67
105
179.4 184.7 199.9 214.5 175.2 180.4 195.3 209.6 171.0 176.1 190.6 204.6 166.9 171.8 186.0 199.6 158.5 163.2 176.7 189.6 146.8 151.2 163.6 175.6
106
14 257
63
95
Entering Indoor Wet Bulb Temperature
85
Outdoor Ambient Temperature
S/T
99
LO PR
18
243
59 172.3 178.6 195.6
75
MBh
21
226
∆T
HI PR
0.40
-
0.58
-
0.69
S/T
-
-
-
-
-
MBh 158.1 163.8 179.5
109
265
12
0.41
120
-
102
LO PR
251
16
0.60
110
-
-
119
19
233
0.72
S/T
∆T
171.2 177.5 194.5
MBh
HI PR
103
268
LO PR
253
18
236
12
0.43
∆T
16
0.63
HI PR
0.75
-
67
S/T
63 -
59
MBh 176.4 182.8 200.3
Airflow
IDB: Entering Indoor Dry Bulb Temperature
75
70
IDB
65
Expanded Cooling Data — 15 Tons (Standard motor and two-speed motor at high speed)
SS-DCC15
SS-DCC15
www.daikincomfort.com
4800
6000
6750
4800
6000
6750
59
63
67
71
59
63
75 67
71
59
95
63
67
71
59
63
67
Entering Indoor Wet Bulb Temperature
85
Outdoor Ambient Temperature
71
59
63
105 67
71
59
63
115 67
71
16
0.55 24
1.00 23
0.93 20
0.76 16
0.57 23
1.00 23
0.96 20
0.78 16
0.59 22
1.00 22
1.00 20
0.81 16
0.61 20
1.00
21
1.00
18
0.82
15
0.61
24
0.89 20
0.72 16
0.54
143
363
25
0.98
122
349
24
0.92
130
376
16 410 149
21 393 140
0.56
151
414
0.75
141
397
24
1.00
128
393
23
0.95
136
423
20
0.78
148
447
16
0.58
158
466
22
1.00
132
434
22
0.96
140
467
19
0.78
153
493
15
0.59
163
515
18
0.52
142
360
28
0.94
121
346
26
0.89
128
372
23
0.72 18
0.54
27
0.98
126
389
26
0.92
134
419
23
0.75
147
442
18
0.56
156
461
25
0.99
131
430
24
0.93
139
463
21
0.75
152
488
17
0.56
162
510
107
LO PR
24
113
261 124
276
23
0.86
118
262
132
288
20
0.69
125
274
113
272
25
1.00
107
259
120
293
25
0.98
114
279
131
309
23
0.89
124
294
139
323
20
0.72
132
307
117
310
24
1.00
111
295
125
333
25
1.00
118
317
136
352
23
0.91
129
335
145
367
20
0.74
138
349
123
353
24
1.00
117
335
131
380
24
1.00
124
361
143
401
24
0.94
136
381
152
418
20
0.76
145
398
129
397
22
1.00
123
377
137
427
23
1.00
130
406
150
451
23
0.97
142
429
159
470
20
0.79
152
447
133
439
21
1.00
127
417
142
472
21
1.00
135
449
155
498
22
0.98
147
474
165
520
19
0.80
157
494
106
LO PR
112
259
25
0.90
123
273
24
0.82
131
285
21
0.66
112
270
26
0.97
119
290
26
0.94
130
306
24
0.85
138
320
21
0.69
116
307
26
1.00
123
330
26
0.96
135
349
24
0.87
143
363
21
0.70
122
349
26
1.00
130
376
26
0.99
141
397
25
0.89
151
414
21
0.73
128
393
24
1.00
136
423
25
1.00
148
447
24
0.93
158
466
21
0.75
132
434
23
1.00
140
467
23
1.00
153
493
23
0.94
163
515
20
0.76
29
233
102
∆T
LO PR
0.90
HI PR
S/T
109
251
28
0.87
119
265
27
0.79
127
276
23
0.64
108
262
29
0.94
115
281
29
0.90
126
297
27
0.81
112
297
29
0.96
120
320
29
0.93
131
338
27
0.84
139
353
23
0.68
Shaded area reflects AHRI (TVA) conditions
134
310
23
0.66
118
339
29
0.99
126
365
29
0.96
137
385
27
0.86
124
381
28
1.00
132
410
28
0.99
144
433
27
0.90
153
452
23
0.73
128
421
26
1.00
136
453
27
1.00
149
479
25
0.90
158
499
22
0.73
High and low pressures are measured at the liquid and suction access fittings.
146
402
24
0.70
MBh 166.5 169.7 177.7 189.6 162.6 165.7 173.6 185.2 158.7 161.8 169.4 180.8 154.8 157.8 165.3 176.4 147.1 149.9 157.0 167.5 136.3 138.9 145.5 155.2
26
240
∆T
0.94
HI PR
S/T
MBh 180.3 183.8 192.5 205.4 176.1 179.6 188.1 200.6 172.0 175.3 183.6 195.8 167.8 171.0 179.1 191.1 159.4 162.5 170.1 180.5 147.6 150.5 157.6 168.1
25
243
∆T
HI PR
0.95
108
248
0.98
23
0.70
133
345
185.8 189.3 198.3 211.6 180.4 184.9 193.7 206.6 177.1 180.5 189.1 201.7 172.8 176.1 184.5 196.8 164.2 167.3 175.2 187.0 152.1 155.0 162.3 173.2
26
0.86
122
327
S/T
27
0.92
115
304
MBh
18
0.51
137
316
101
23
0.68
128
303
LO PR
26
0.84
117
287
27
27
0.89
110
267
231
18
0.49
129
282
∆T
22
0.66
121
270
HI PR
26
0.81
111
256
0.86
25
0.95
135
349
163.6 167.2 178.6 190.9 159.8 163.3 174.4 186.5 156.0 159.4 170.3 182.0 152.2 155.5 166.1 177.6 144.6 147.7 157.8 168.7 133.9 136.8 146.2 156.3
16
0.53
123
330
S/T
20
0.71
116
307
MBh
24
0.87
138
320
105
25
0.93
130
306
LO PR
16
0.51
119
290
24
20
0.68
112
270
238
23
0.84
131
285
∆T
0.89
123
273
HI PR
S/T
112
259
177.2 180.1 193.5 206.9 173.1 176.9 189.0 202.0 169.0 172.7 184.5 197.2 164.9 168.5 180.0 192.4 156.6 160.1 171.0 182.8 145.1 148.3 158.4 169.3
20
0.74
MBh
23
0.91
106
24
0.97
LO PR
16
0.53
23
19
0.71
240
22
0.88
∆T
0.94
HI PR
S/T
MBh 182.6 186.5 199.3 213.1 178.3 182.2 194.7 208.1 174.1 177.9 190.0 203.1 169.8 173.5 185.4 198.2 161.3 164.9 176.1 188.3 149.4 152.7 163.2 174.4
Airflow
IDB: Entering Indoor Dry Bulb Temperature
85
80
IDB
65
Expanded Cooling Data — 15 Tons (Standard motor and two-speed motor at high speed)
7
8
www.daikincomfort.com
5600
7000
7875
5600
7000
7875
71
-
112
313
18
0.66
122
330
14
0.45
111
310
19
0.63
121
327
14
0.43
101
279
24
0.72
108
300
21
0.60
118
317
16
0.42
205.8 213.4 233.8
104
288
22
0.75
223.0 231.2 253.3
105
290
21
0.78
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
71
59
63
67
117
356
18
0.67
127
375
14
0.47
115
352
19
0.64
126
372
14
0.44
105
317
24
0.74
112
341
21
0.62
122
361
16
0.43
200.9 208.3 228.2
108
327
22
0.77
217.7 225.7 247.2
110
330
21
0.80
224.2 232.4 254.6
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
71
59
63
67
122
405
18
0.69
134
428
14
0.48
121
401
19
0.66
132
423
15
0.46
110
361
25
0.76
118
389
21
0.64
128
411
16
0.44
196.0 203.2 222.6
114
373
22
0.79
212.4 220.1 241.2
115
376
21
0.83
218.8 226.8 248.4
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
71
59
63
67
128
456
18
0.72
140
481
14
0.50
127
451
19
0.69
139
476
14
0.48
116
407
24
0.79
123
438
21
0.66
134
462
16
0.46
186.2 193.0 211.5
119
419
22
0.82
201.8 209.1 229.1
121
423
21
0.86
207.8 215.4 236.0
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
71
59
63
67
133
503
17
0.73
145
531
13
0.50
131
498
18
0.69
143
526
13
0.48
120
449
23
0.80
127
483
20
0.67
139
510
15
0.46
172.5 178.8 195.9
123
463
20
0.83
186.9 193.7 212.3
125
468
20
0.87
192.5 199.5 218.6
115
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
71
22
0.82 18
0.62 13
0.40 25
0.94
23
0.84
19
0.64
13
0.41
24
0.98
22
0.88
18
0.66
13
0.43
23
0.99
21
0.88
17
0.67
12
0.43
23
0.78
19
0.59
13
0.38
137
396
26
0.90
116
380
19 428 134
24 405 122
0.61
135
432
0.81
124
409
13
0.39
144
451
25
0.93
122
428
23
0.84
130
460
19
0.63
141
486
13
0.41
151
507
24
0.94
126
472
22
0.84
134
508
18
0.64
146
537
12
0.41
156
560
28
251
97
∆T
HI PR
LO PR
103
270
26
0.71
106
279
112
285
21
0.54
116
294
120
298
15
0.34
123
307
102
282
28
0.82
105
291
109
303
26
0.73
112
313
119
320
21
0.56
122
330
126
334
15
0.36
130
344
113
345
26
0.75
117
356
123
364
21
0.57
127
376
131
380
15
0.37
136
392
112
365
28
0.87
115
376
Shaded area reflects ACCA (TVA) conditions
106
321
28
0.84
110
330
119
393
26
0.78
130
415
21
0.59
117
411
28
0.90
121
423
124
442
26
0.81
128
456
136
467
21
0.61
140
481
145
487
15
0.39
149
502
121
454
26
0.91
125
468
129
488
24
0.81
133
503
141
516
20
0.62
145
532
150
538
14
0.40
154
554
High and low pressures are measured at the liquid and suction access fittings.
138
433
15
0.38
142
446
0.79
25
0.87
129
379
214.3 220.7 238.8 256.3 209.3 215.5 233.3 250.4 204.4 210.4 227.7 244.4 199.4 205.3 222.2 238.5 189.4 195.0 211.1 226.5 175.4 180.6 195.5 209.8
13
0.37
118
359
S/T
19
0.58
111
334
MBh
23
0.76
132
348
100
25
0.85
124
333
LO PR
13
0.36
113
316
25
19
0.56
106
293
259
23
0.73
125
310
∆T
0.82
117
297
HI PR
S/T
107
281
232.2 239.1 258.8 277.7 226.8 233.5 252.8 271.3 221.4 228.0 246.7 264.8 216.0 222.4 240.7 258.4 205.2 211.3 228.7 245.4 190.1 195.7 211.8 227.4
24
0.91
MBh
13
0.39
101
18
0.60
LO PR
22
0.80
24
24
0.89
262
13
0.37
∆T
18
0.58
HI PR
22
0.77
0.86
111
-
-
67
105
239.2 246.2 266.5 286.1 233.6 240.5 260.3 279.4 228.0 234.8 254.1 272.8 222.5 229.1 247.9 266.1 211.4 217.6 235.5 252.8 195.8 201.6 218.2 234.2
102
16 283
63
95
Entering Indoor Wet Bulb Temperature
85
Outdoor Ambient Temperature
S/T
96
LO PR
21
268
59 229.7 238.1 260.9
75
MBh
24
249
∆T
HI PR
0.40
-
0.58
-
0.70
S/T
-
-
-
-
-
MBh 210.7 218.4 239.3
105
291
14
0.42
116
-
99
LO PR
276
19
0.60
106
-
-
115
22
256
0.72
S/T
∆T
228.3 236.7 259.3
MBh
HI PR
100
294
LO PR
279
21
259
14
0.44
∆T
18
0.63
HI PR
0.76
-
67
S/T
63 -
59
MBh 235.2 243.8 267.1
Airflow
IDB: Entering Indoor Dry Bulb Temperature
75
70
IDB
65
Expanded Cooling Data — 20 Tons (Standard motor and two-speed motor at high speed)
SS-DCC15
SS-DCC15
www.daikincomfort.com
5600
7000
7875
5600
7000
7875
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
115 67
71
26
0.94 23
0.77 18
0.57 26
1.00 27
1.00 23
0.79 18
0.59 25
1.00 26
1.00 22
0.82 18
0.61 23
1.00
24
1.00
21
0.83
17
0.62
27
0.90 24
0.73 19
0.55
138
400
29
0.99
117
384
27
0.93
125
413
19 451 144
24 432 135
0.56
145
455
0.75
136
436
27
1.00
123
432
27
0.96
131
465
23
0.78
143
491
19
0.58
152
512
25
1.00
127
477
25
0.97
135
514
22
0.79
148
542
17
0.59
157
566
121
31 103
285 110
306
30
0.84
113
316
120
323
26
0.69
124
334
128
337
21
0.51
132
348
107
324
32
0.92
111
334
114
348
30
0.87
118
359
125
368
26
0.70
129
379
133
384
21
0.53
137
396
113
369
32
0.95
116
380
120
397
30
0.89
124
409
131
419
26
0.73
139
437
21
0.54
118
415
31
0.99
122
428
126
446
30
0.93
130
460
137
471
26
0.75
141
486
146
492
21
0.56
151
507
122
458
29
1.00
126
473
130
493
28
0.93
134
509
142
521
24
0.76
146
537
151
543
19
0.57
156
560
23
0.74 27
1.00
27
1.00
27
0.95
24
0.77
26
1.00
26
1.00
27
0.98
23
0.80
24
1.00
24
1.00
25
0.99
22
0.80
102
LO PR
29
108
284 118
300
28
0.82
119
303
126
313
24
0.67
127
316
108
296
30
0.98
109
299
114
319
30
0.94
116
322
125
337
28
0.85
126
340
133
351
24
0.69
134
355
112
337
30
1.00
113
340
119
363
30
0.97
120
366
130
383
28
0.87
131
387
138
400
24
0.71
140
404
117
384
29
1.00
119
388
125
413
30
1.00
126
417
136
436
28
0.90
138
441
145
455
24
0.73
147
460
123
432
28
1.00
124
436
131
465
28
1.00
132
469
143
491
28
0.94
144
496
152
512
24
0.76
154
517
127
477
26
1.00
129
482
135
514
26
1.00
137
519
148
542
26
0.94
149
548
157
566
23
0.77
159
571
33
256
99
∆T
LO PR
0.91
HI PR
S/T
105
276
33
0.88
115
291
31
0.79
122
304
27
0.64
104
288
34
0.94
111
309
33
0.91
121
327
31
0.82
108
327
34
0.97
115
352
33
0.93
126
372
31
0.84
134
388
27
0.68
Shaded area reflects AHRI (TVA) conditions
129
341
27
0.67
114
372
34
1.00
121
401
33
0.96
132
423
31
0.87
119
419
32
1.00
127
451
33
1.00
139
476
31
0.90
148
497
27
0.73
123
463
30
1.00
131
498
30
1.00
143
526
29
0.91
153
549
25
0.74
High and low pressures are measured at the liquid and suction access fittings.
141
441
27
0.71
MBh 221.9 226.2 236.9 252.8 216.8 221.0 231.4 246.9 211.6 215.7 225.9 241.0 206.5 210.5 220.4 235.1 196.1 199.9 209.4 223.4 180.7 185.2 194.0 206.9
30
264
∆T
HI PR
0.91
109
287
0.94
27
0.92
240.5 245.1 256.7 273.9 234.9 239.4 250.7 267.5 229.3 233.7 244.8 261.1 223.7 228.0 238.8 254.8 212.5 216.6 226.9 242.0 196.8 200.6 210.1 224.2
28
1.00
S/T
28
1.00
MBh
23
0.72
103
27
0.89
LO PR
28
0.99
29
28
1.00
267
23
0.70
∆T
27
0.86
HI PR
28
0.96
0.99
114
21 301
0.90
106
293
247.7 252.5 264.4 282.1 241.9 246.6 258.3 275.5 236.2 240.7 252.1 269.0 230.4 234.8 246.0 262.4 218.9 223.1 233.7 249.3 202.7 206.7 216.4 230.9
104
26 288
0.50
125
310
S/T
98
LO PR
30
273
0.66
117
297
MBh
31
254
∆T
HI PR
0.81
107
281
0.87
28
0.96
130
383
218.1 222.9 238.1 254.6 213.1 217.7 232.6 248.6 208.0 212.5 227.1 242.7 202.9 207.3 221.5 236.8 192.8 197.0 210.4 225.0 178.6 182.5 194.9 208.4
19
0.53
119
363
S/T
24
0.71
112
337
MBh
27
0.88
133
351
101
28
0.93
125
337
LO PR
19
0.51
114
319
28
23
0.69
108
296
262
27
0.84
126
313
∆T
0.90
118
300
HI PR
S/T
108
284
236.3 241.5 258.0 275.8 230.8 235.9 252.0 269.4 225.3 230.3 246.0 263.0 219.8 224.6 240.0 256.6 208.8 213.4 228.0 243.7 193.5 197.7 211.2 225.8
27
1.00
MBh
18
0.56
102
23
0.75
LO PR
26
0.92
27
28
1.00
264
18
0.54
∆T
22
0.72
HI PR
26
0.89
0.94
63
105
S/T
59
95
Entering Indoor Wet Bulb Temperature
85
Outdoor Ambient Temperature
243.4 248.7 265.7 284.1 237.8 242.9 259.6 277.5 232.1 237.2 253.4 270.9 226.4 231.4 247.2 264.3 215.1 219.8 234.8 251.0 199.3 203.6 217.5 232.5
75
MBh
Airflow
IDB: Entering Indoor Dry Bulb Temperature
85
80
IDB
65
Expanded Cooling Data — 20 Tons (Standard motor and two-speed motor at high speed)
9
10
www.daikincomfort.com
59 284.2 0.67 19 22.18 270 102 275.9 0.64 20 22.00 267 101 262.1 0.61 20 21.66 262 99
289.0 0.76 22 22.36 272 103 280.6 0.73 23 22.18 270 102 266.5 0.70 24 21.83 264 100
Airflow MBh S/T ∆T 9202 kW HI PR LO PR MBh S/T ∆T 8200 kW HI PR LO PR MBh S/T ∆T 7257 kW HI PR LO PR
MBh S/T ∆T 9202 kW HI PR LO PR MBh S/T ∆T 8200 kW HI PR LO PR MBh S/T ∆T 7257 kW HI PR LO PR
297.5 0.68 20 22.83 293 110 288.9 0.65 21 22.65 290 108 274.4 0.63 22 22.29 284 106
63 294.5 0.56 17 22.65 290 108 286.0 0.54 17 22.47 287 107 271.7 0.51 18 22.11 282 105 322.1 0.52 17 23.55 310 120 312.7 0.49 17 23.36 307 118 297.1 0.47 18 22.99 300 116
67 322.7 0.39 13 23.36 306 118 313.3 0.37 13 23.17 303 117 297.6 0.36 13 22.80 297 115 345.7 0.3 12 24.3 322.9 127.4 335.6 0.3 12 24.1 319.7 126.1 318.8 0.3 12 23.7 313.3 123.6
71 282.3 0.79 22 24.07 306 109 274.1 0.76 23 23.88 303 108 260.3 0.72 24 23.50 297 106
59 277.6 0.70 19 23.88 303 108 269.5 0.67 20 23.69 300 107 256.0 0.64 21 23.31 294 105 290.6 0.71 21 24.59 329 116 282.2 0.68 21 24.40 326 115 268.1 0.65 22 24.00 319 112
337.6 0.3 12 26.2 362.3 134.6 327.8 0.3 12 26.0 358.7 133.3 311.4 0.3 12 25.6 351.5 130.6
71 283.7 0.73 21 26.15 374 120 275.4 0.69 21 25.94 370 119 261.7 0.66 22 25.51 363 117
307.1 0.55 17 27.00 395 131 298.1 0.52 18 26.78 391 130 283.2 0.50 18 26.34 383 127
329.6 0.4 12 27.9 412.0 139.9 320.0 0.3 12 27.7 408.0 138.5 304.0 0.3 12 27.2 399.8 135.7
268.8 0.84 23 26.93 396 119 261.0 0.80 23 26.71 392 118 248.0 0.77 24 26.27 384 115
276.8 0.75 21 27.52 426 126 268.7 0.72 22 27.30 422 125 255.3 0.69 22 26.84 413 123 Shaded area reflects ACCA (TVA) Rating Conditions.
275.6 0.81 22 25.59 348 113 267.5 0.78 23 25.38 344 112 254.1 0.74 24 24.97 337 110
59 271.0 0.72 19 25.38 344 112 263.1 0.68 20 25.17 341 111 249.9 0.65 21 24.76 334 109 299.6 0.57 17 28.43 450 138 290.9 0.54 18 28.19 446 137 276.3 0.52 18 27.72 437 134
Outdoor Ambient Temperature 85 95 Entering Indoor Wet Bulb Temperature 63 67 71 59 63 67 280.8 307.7 264.3 274.0 300.2 0.60 0.41 0.74 0.62 0.43 17 13 19 17 13 25.93 26.77 26.70 27.29 28.19 370 391 392 422 445 119 130 118 125 137 272.7 298.7 256.7 266.0 291.5 0.57 0.39 0.70 0.59 0.41 17 13 20 18 13 25.72 26.55 26.48 27.07 27.95 367 387 388 418 441 118 129 116 124 135 259.0 283.8 243.8 252.7 276.9 0.55 0.38 0.67 0.56 0.39 18 14 21 18 14 25.30 26.12 26.05 26.62 27.49 359 379 380 409 432 116 126 114 121 133 321.5 0.4 12 29.4 469.3 147.0 312.2 0.3 12 29.1 464.7 145.5 296.6 0.3 13 28.6 455.4 142.6
71 262.9 0.78 20 28.69 479 132 255.3 0.74 21 28.45 475 131 242.5 0.71 22 27.98 465 129
63 260.3 0.64 17 28.45 475 131 252.7 0.61 17 28.21 470 130 240.1 0.58 18 27.74 460 127 284.6 0.59 17 29.64 506 145 276.3 0.56 17 29.39 501 143 262.5 0.54 18 28.90 491 140
67 285.2 0.44 13 29.39 501 143 276.9 0.42 13 29.14 496 142 263.0 0.40 13 28.65 486 139 305.5 0.4 12 30.6 528.0 154.0 296.6 0.4 12 30.4 522.7 152.5 281.7 0.3 12 29.9 512.3 149.4
71 236.6 0.88 21 29.05 492 129 229.7 0.84 22 28.80 487 128 218.2 0.80 22 28.32 478 125
59 232.6 0.77 18 28.80 487 127 225.9 0.74 19 28.56 482 126 214.6 0.71 19 28.08 473 124 263.6 0.59 16 30.69 559 150 256.0 0.57 16 30.43 554 148 243.2 0.54 17 29.91 543 145
67 264.2 0.45 12 30.43 554 148 256.5 0.43 12 30.17 548 147 243.7 0.41 13 29.66 537 144
283.0 0.4 10.8 31.7 583.3 159.3 274.7 0.4 11.2 31.5 577.6 157.7 261.0 0.3 11.6 30.9 566.0 154.6
71 -
kW = Total system power
243.6 0.79 19 29.70 530 137 236.5 0.75 20 29.45 524 136 224.7 0.72 20 28.95 514 133
63 241.1 0.65 16 29.44 524 136 234.1 0.62 16 29.20 519 134 222.4 0.59 17 28.71 509 132
115
Amps: Unit amps (comp.+ evaporator + condenser fan motors)
255.4 0.87 22 28.07 445 125 248.0 0.83 23 27.83 441 123 235.6 0.80 24 27.37 432 121
59 251.1 0.77 19 27.83 441 123 243.8 0.73 20 27.60 437 122 231.6 0.70 21 27.14 428 120
105
Design Subcooling, 16 - 19 °F @ the liquid access fitting connection ARI 95 test conditions. Design Superheat 8 - 12°F @ the compressor suction access fitting connection.
314.6 0.54 17 25.38 347 126 305.4 0.51 18 25.18 344 125 290.1 0.49 18 24.77 337 123
67 315.2 0.40 13 25.17 344 125 306.0 0.38 13 24.97 340 124 290.7 0.37 14 24.56 334 121
75 63 287.7 0.58 17 24.39 326 115 279.3 0.56 17 24.20 322 113 265.3 0.53 18 23.80 316 111
High and low pressures are measured at the liquid and suction access fittings.
IDB: Entering Indoor Dry Bulb Temperature
75
70
IDB
65
Expanded Cooling Data — 25 Tons (Standard motor and 2 speed motor on high speed)
SS-DCC15
SS-DCC15
www.daikincomfort.com
59 294.1 0.84 25 22.54 275 104 285.6 0.80 26 22.36 272 103 271.3 0.77 26 22.00 267 101
299.3 0.88 26 22.72 278 105 290.6 0.84 27 22.54 275 104 276.0 0.80 28 22.18 270 102
Airflow MBh S/T ∆T 9202 kW HI PR LO PR MBh S/T ∆T 8200 kW HI PR LO PR MBh S/T ∆T 7257 kW HI PR LO PR
MBh S/T ∆T 9202 kW HI PR LO PR MBh S/T ∆T 8200 kW HI PR LO PR MBh S/T ∆T 7257 kW HI PR LO PR
305.1 0.85 26 23.20 299 112 296.2 0.81 27 23.01 296 111 281.4 0.78 28 22.65 290 108
63 300.6 0.79 24 23.01 296 111 291.8 0.75 25 22.83 293 110 277.2 0.72 25 22.47 287 107 319.5 0.77 24 23.93 316 122 310.2 0.73 25 23.74 313 121 294.7 0.70 26 23.36 306 118
67 321.1 0.64 21 23.74 313 121 311.8 0.61 21 23.55 310 120 296.2 0.59 22 23.17 303 117 340.9 0.6 21 24.7 329.4 130.0 330.9 0.6 22 24.5 326.1 128.7 314.4 0.6 23 24.1 319.6 126.1
71 343.3 0.5 16 24.5 326.1 128.7 333.3 0.5 17 24.3 322.9 127.4 316.6 0.4 18 23.9 316.5 124.9 292.3 0.91 27 24.47 312 111 283.8 0.87 28 24.27 309 110 269.6 0.83 28 23.88 303 108
59 287.3 0.87 25 24.27 309 110 278.9 0.83 26 24.08 306 109 265.0 0.79 27 23.69 300 107 298.0 0.88 26 25.00 336 118 289.3 0.84 27 24.79 332 117 274.8 0.80 28 24.39 326 115
332.9 0.6 21 26.6 369.6 137.3 323.2 0.6 22 26.4 366.0 136.0 307.1 0.6 23 26.0 358.6 133.3
71 335.3 0.5 17 26.4 366.0 136.0 325.5 0.5 17 26.2 362.3 134.6 309.2 0.5 18 25.8 355.1 131.9 290.9 0.90 26 26.58 382 123 282.4 0.86 27 26.37 378 122 268.3 0.82 28 25.93 370 119
304.6 0.81 25 27.45 403 134 295.8 0.78 26 27.23 399 133 281.0 0.74 26 26.77 391 130
325.0 0.7 21 28.4 420.4 142.7 315.5 0.6 22 28.1 416.2 141.3 299.8 0.6 23 27.7 407.9 138.5
278.4 0.96 27 27.38 404 121 270.3 0.92 28 27.15 400 120 256.8 0.88 29 26.70 392 118
283.8 0.93 26 27.99 435 129 275.5 0.89 27 27.75 430 128 261.7 0.85 28 27.29 422 125 Shaded area reflects AHRI) Rating Conditions.
285.3 0.93 27 26.01 355 115 277.0 0.89 28 25.80 351 114 263.2 0.85 28 25.38 344 112
59 280.4 0.89 25 25.80 351 114 272.3 0.85 26 25.59 348 113 258.7 0.81 27 25.17 341 111 297.2 0.84 25 28.91 459 141 288.6 0.80 26 28.67 455 139 274.1 0.77 27 28.19 445 137
Outdoor Ambient Temperature 85 95 Entering Indoor Wet Bulb Temperature 63 67 71 59 63 67 286.6 306.2 327.3 273.6 279.6 298.7 0.84 0.68 0.5 0.92 0.86 0.70 24 21 17 25 24 21 26.37 27.23 28.1 27.15 27.75 28.67 378 399 416.2 400 430 455 122 133 141.3 120 128 139 278.2 297.3 317.8 265.6 271.4 290.0 0.80 0.65 0.5 0.88 0.82 0.67 25 22 17 26 25 22 26.15 27.00 27.9 26.93 27.53 28.43 374 395 412.1 396 426 450 120 131 139.9 119 126 138 264.3 282.4 301.9 252.4 257.9 275.5 0.76 0.62 0.5 0.84 0.79 0.64 18 27 26 22 26 22 25.72 26.55 27.4 26.48 27.07 27.95 367 387 403.8 388 418 441 118 129 137.1 116 124 135 317.1 0.7 22 29.9 478.8 149.9 307.8 0.7 22 29.6 474.0 148.4 292.4 0.6 23 29.1 464.6 145.5
71 319.3 0.5 17 29.6 474.0 148.4 310.0 0.5 17 29.4 469.4 147.0 294.5 0.5 18 28.9 460.0 144.0 269.6 0.97 26 29.18 489 135 261.7 0.92 27 28.93 484 134 248.6 0.88 28 28.45 475 131
63 265.6 0.90 24 28.93 484 134 257.9 0.85 25 28.69 479 132 245.0 0.82 25 28.21 470 130 282.3 0.87 25 30.15 516 148 274.1 0.83 26 29.89 511 146 260.4 0.80 26 29.39 501 143
67 283.8 0.73 21 29.89 511 146 275.5 0.70 21 29.64 506 145 261.7 0.67 22 29.14 496 142 301.2 0.7 21 31.2 538.6 157.1 292.4 0.7 22 30.9 533.3 155.6 277.8 0.6 23 30.4 522.6 152.5
71 303.3 0.5 17 30.9 533.3 155.6 294.5 0.5 17 30.6 528.0 154.0 279.8 0.5 18 30.1 517.5 150.9 245.0 1.00 24 29.54 502 131 237.8 0.96 26 29.29 497 130 226.0 0.92 26 28.80 487 127
59 240.8 0.96 23 29.29 497 130 233.8 0.92 24 29.05 492 129 222.1 0.88 25 28.56 482 126 261.5 0.88 23 31.21 571 153 253.9 0.84 24 30.95 565 151 241.2 0.80 25 30.43 554 148
67 262.9 0.74 19 30.95 565 151 255.2 0.70 20 30.69 559 150 242.4 0.67 21 30.17 548 147
279.0 0.7 19.9 32.3 595.1 162.5 270.9 0.7 20.7 32.0 589.2 160.9 257.4 0.7 21.3 31.5 577.5 157.7
71 281.0 0.5 15.4 32.0 589.2 160.9 272.8 0.5 16.0 31.7 583.4 159.3 259.2 0.5 16.5 31.2 571.7 156.1
kW = Total system power
249.7 0.97 24 30.20 540 140 242.5 0.93 25 29.95 535 138 230.3 0.89 26 29.44 524 136
63 246.0 0.90 22 29.95 535 138 238.9 0.86 23 29.70 530 137 226.9 0.83 24 29.20 519 134
115
Amps: Unit amps (comp.+ evaporator + condenser fan motors)
264.5 1.00 26 28.54 454 127 256.8 0.96 27 28.30 450 126 243.9 0.91 28 27.83 441 123
59 259.9 0.96 25 28.30 450 126 252.4 0.91 26 28.07 446 125 239.7 0.87 27 27.60 437 122
105
Design Subcooling, 16 - 19 °F @ the liquid access fitting connection ARI 95 test conditions. Design Superheat 8 - 12°F @ the compressor suction access fitting connection.
312.1 0.79 25 25.80 354 129 303.0 0.76 26 25.59 351 128 287.8 0.73 26 25.17 344 125
67 313.6 0.66 21 25.59 351 128 304.5 0.63 22 25.38 347 126 289.3 0.61 22 24.97 340 124
75 63 293.6 0.82 24 24.79 332 117 285.0 0.78 25 24.59 329 116 270.8 0.74 26 24.20 322 113
High and low pressures are measured at the liquid and suction access fittings.
IDB: Entering Indoor Dry Bulb Temperature
85
80
IDB
65
Expanded Cooling Data — 25 Tons (Standard motor and 2 speed motor on high speed)
11
Airflow Data — 15 Tons Standard & Two-Speed Belt Drive at High Speed — Down Shot ESP (" H₂O)
0.2 0.4 0.6 0.8 1.0 1.2
Turns Open 0
1
2
3
4
5
6
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
------7112 5983 4426
------2.96 2.38 1.71
----7477 6467 5190 ---
----2.97 2.46 1.89 ---
----6899 5795 -----
----2.51 2.01 -----
--7306 6323 5101 -----
--2.54 2.10 1.61 -----
--6777 5716 -------
--2.14 1.72 -------
7203 6257 5103 -------
2.18 1.80 1.39 -------
6718 5711 ---------
1.84 1.48 ---------
High-Static Belt Drive — Down Shot ESP (" H₂O)
1.0 1.2 1.4 1.6 1.8 2.0
Turns Open 0
1
2
3
4
5
6
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
----------6261
----------4.01
--------6419 ---
--------3.84 ---
------6587 4877 ---
------3.69 2.70 ---
----6739 5245 -----
----3.52 2.67 -----
--6927 5602 -------
--3.39 2.65 -------
7120 5924 ---------
3.26 2.61 ---------
6223 -----------
2.55 -----------
Airflow Data — 20 Tons Standard & Two-Speed Belt Drive at High Speed — Down Shot ESP (" H₂O)
0.2 0.4 0.6 0.8 1.0 1.2
Turns Open 0
1
2
3
4
5
6
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
----------7344
----------4.35
------8171 7901 ---
------2.93 2.85 ---
------7630 7203 ---
------3.70 3.42 ---
----9038 7068 -----
----3.82 2.79 -----
--9570 8460 -------
--4.08 3.46 -------
--9197 7949 -------
--3.82 3.14 -------
9664 8702 ---------
4.05 3.51 ---------
High-Static Belt Drive — Down Shot ESP (" H₂O)
1.0 1.2 1.4 1.6 1.8 2.0
Turns Open 0
1
2
3
4
5
6
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
--------7967 6594
--------6.02 4.87
------8209 6883 ---
------6.14 5.01 ---
----8471 7194 -----
----5.43 4.45 -----
--8774 7549 -------
--5.60 4.63 -------
9090 7914 ---------
5.79 4.83 ---------
8297 6989 ---------
5.06 4.07 ---------
7479 -----------
3.62 -----------
Notes • Airflow table represent dry coil with filters installed; SCFM correction factor for wet coil is 4%. • Any adjustment made to the blower should not cause the motor to draw more than the motor rated RLA. Minimum rated SCFM is 350 per ton. • Unit factory shipped with the sheave set at 2.5 turns open.
12
www.daikincomfort.com
SS-DCC15
Airflow Data — 25 Tons Standard & Two-Speed Belt Drive at High Speed - Down Shot Turns Open
0
1
2
3
4
5
6
RPM
972
941
910
877
845
813
781
ESP
SCFM
BHP
SCFM
BHP
SCFM
BHP
SCFM
BHP
SCFM
BHP
SCFM
BHP
SCFM
BHP
0.2
---
---
---
---
---
---
10,369
5.07
9,748
4.41
9,191
3.82
8,683
3.28
0.4
---
---
10,802
6.00
10,125
5.30
9,484
4.62
8,905
4.01
8,386
3.46
7,913
2.95
0.6
10,519
6.20
9,821
5.47
9,193
4.81
8,599
4.18
8,062
3.61
7,582
3.10
7,143
2.63
0.8
9,482
5.60
8,839
4.93
8,261
4.32
7,714
3.74
7,220
3.21
6,777
2.74
---
---
1
8,446
5.01
7,857
4.39
7,329
3.83
6,829
3.30
---
---
---
---
---
---
1.2
7,409
4.41
6,876
3.85
---
---
---
---
---
---
---
---
---
---
High Static Belt Drive Turns Open
0
RPM
1
1254
2
1208
3
1163
4
1124
5
1085
6
1046
1007
ESP
SCFM
BHP
SCFM
BHP
SCFM
BHP
SCFM
BHP
SCFM
BHP
SCFM
BHP
SCFM
BHP
0.6
---
---
---
---
---
---
---
---
---
---
---
---
11,409
7.12
0.8
---
---
---
---
---
---
---
---
---
---
---
---
10,302
6.46
1
---
---
---
---
---
---
---
---
---
---
10,159
6.79
9,195
5.79
1.2
---
---
---
---
---
---
---
---
9,990
7.11
8,961
6.04
8,087
5.13
1.4
---
---
---
---
---
---
9,789
7.39
8,686
6.25
7,763
5.29
6,980
4.46
1.6
---
---
---
---
9,543
7.63
8,357
6.40
7,382
5.39
6,566
4.53
---
---
1.8
---
---
---
---
7,957
6.48
6,925
5.41
6,077
4.53
---
---
---
---
2
---
---
7,667
6.68
6,370
5.34
---
---
---
---
---
---
---
---
2.2
7,280
6.78
---
---
---
---
---
---
---
---
---
---
---
---
Notes • Airflow table represent dry coil with filters installed; SCFM correction factor for wet coil is 4%. • Any adjustment made to the blower should not cause the motor to draw more than the motor rated RLA. Minimum rated SCFM is 350 per ton. • Unit factory shipped with the sheave set at 2.5 turns open.
Airflow Pressure Drop of Downflow Economizer for 15- to 25-Ton Rooftop Units (100% Return Air)
CFM
4,500
5,000
5,500
6,000
6,500
7,000
7,500
8,000
8,500
9,000
9,500
10,000
(In. WG)
0.15
0.18
0.22
0.27
0.32
0.37
0.42
0.48
0.55
0.61
0.69
0.76
SS-DCC15
www.daikincomfort.com
13
Heat Kit Electrical Data (Blower Only, Heat Mode) DCC180***(3B/3V) @ 208 / 240V – 15 Tons Model
MCA1,3 (3B/3V)
DCC240***(3B/3V) @ 208 / 240V – 20 Tons
MOP2,3 Actual kW Recommended (3B / 3V) @ 240V Airflow Range
Model
MCA1,3 (3B/3V)
MOP2,3 (3B/3V)
Actual kW @240V
Recommended Airflow Range
EHK3-31
98.0/98.0
100/100
28.8
5250 - 6750 CFM
EHK3-31
103.9/104.1
125/125
28.8
7200 - 8500 CFM
EHK3-46
141.0/141.3
150/150
43.2
5250 - 6750 CFM
EHK3-46
147.1/147.4
150/150
43.2
7200 - 8500 CFM
EHK3-60
185.0 /184.6
200/200
57.6
5250 - 6750 CFM
EHK3-60
155.9/156.1
175/175
57.6
7200 - 8500 CFM
EHK3-75
190.0/190.7
225/225
72
7200 - 8500 CFM
DCC180***(4B/4V) @ 480V – 15 Tons Model
MCA1,3 (4B/4V)
MOP2,3 Actual kW Recommended (4B/4V) @ 480V Airflow Range
EHK4-31
49.0/48.7
50/50
28.8
5250 - 6750 CFM
EHK4-46
71.0/70.3
80/80
43.2
5250 - 6750 CFM
EHK4-60
92.0/92.0
100/100
57.6
5250 - 6750 CFM
DCC180***(7B/7V) @575V – 15 Tons Model
MCA1,3 (7B/7V)
MOP2,3 Actual kW Recommended (7B/7V) @ 575V Airflow Range
EHK7-31
41.0/40.5
45/45
28.8
5250 - 6750 CFM
EHK7-46
59.0/58.6
60/60
43.2
5250 - 6750 CFM
EHK7-60
78.0/76.7
80/80
57.6
5250 - 6750 CFM
MCA1,3 (3B/3V)
MOP2,3 Actual kW (4B /4V) @ 240V
MCA1,3 (4B/4V)
MOP2,3 Actual kW (4B /4V) @ 480V
Recommended Airflow Range
EHK4-31
51.3/51.5
60/60
28.8
7200 - 8500 CFM
EHK4-46
73.0/73.3
80/80
43.2
7200 - 8500 CFM
EHK4-60
77.3/77.6
90/90
57.6
7200 - 8500 CFM
EHK4-75
94.6/ 94.9
110/110
72
7200 - 8500 CFM
DCC240***(7B/7V) @575V – 20 Tons MOP2,3 (7B/7V)
Actual kW @ 575V
Recommended Airflow Range
EHK7-31
42.5/42.6
45/45
28.8
7200 - 8500 CFM
EHK7-46
60.6/60.7
70/70
43.2
7200 - 8500 CFM
EHK7-60
64.2/64.3
70/70
57.6
7200 - 8500 CFM
Airflow Range
EHK7-75
78.7/78.8
90/90
72
7200 - 8500 CFM
¹ Minimum Circuit Ampacity ² Maximum Overcurrent Protection (amps) 3 If Powered Convenience Outlet option is installed, see unit Serial Plate for correct MCA and MOP values. Note: When using electric heat kit, the single-point kit installed in the unit is needed to meet UL requirements.
EHK3-31
137.8/138.4 175/175
28.8
7200 - 8500 CFM
EHK3-46
155.4/156.1 175/175
43.2
7200 - 8500 CFM
EHK3-60
164.1/164.9 175/175
57.6
7200 - 8500 CFM
EHK3-75
198.7/199.5 225/225
72
7200 - 8500 CFM
DCC300***(4B/4V) @ 480V – 25 Tons MCA1,3 (4B/4V)
MOP2,3 (4B/4V)
Actual kW @ 480V
airflow range
EHK4-31
55.8/56.5
70/70
28.8
7200 - 8500 CFM
EHK4-46
76.8/77.6
80/80
43.2
7200 - 8500 CFM
EHK4-60
81.1/81.9
90/90
57.6
7200 - 8500 CFM
EHK4-75
98.4/99.2
110/110
72
7200 - 8500 CFM
Model
Model
MCA1,3 (7B/7V)
DCC300***(3B/3V) @ 240 / 240V – 25 Tons Model
DCC240***(4B/4V) @ 480V – 20 Tons
Model
Heater Kit Power Correction Formulas • Due to voltage variation, the following formulas and tables are provided to assist the customer with determining the precise electric heat power rating based on voltage supplied to the unit. • Power Rating (kW) = Rated Power (kW) x Correction Factor • Correction Factor = (Supply Voltage)2 / (Rated Voltage)2 • Heater kits are grouped in three separate families of voltages; 240, 480, and 575.The rated power and voltage may be obtained from tables on this page. Check heater kit, and unit serial plate for size of heater kit installed in unit.
DCC300***(7B/7V) @ 575V – 25 Tons
kW Correction Factors
MCA1,3 (7B/7V)
MOP2,3 (7B/7V)
Actual kW @ 575V
airflow range
EHK7-31
45.5/46.4
50/50
28.8
7200 - 8500 CFM
Supply Voltage
EHK7-46
63.6/64.5
70/70
43.2
7200 - 8500 CFM
Correction Factor
EHK7-60
67.2/68.1
80/80
57.6
7200 - 8500 CFM
EHK7-75
81.7/82.6
90/100
72
7200 - 8500 CFM
Model
kW Correction Factor (for 208/230V Units) 240
230
220
210
208
1
0.93
0.82
0.78
0.76
kW Correction Factor (for 460V Units) Supply Voltage
460
440
430
Correction Factor
0.92
0.84
0.8
kW Correction Factor (for 575V Units)
14
Supply Voltage
560
550
540
Correction Factor
0.95
0.91
0.88
www.daikincomfort.com
SS-DCC15
SS-DCC15
www.daikincomfort.com BACK VIEW
133.354
CONDENSATE DRAIN OUTLET THIS SIDE ONLY
35.551
50.750
7.017
ALL DIMENSIONS ARE GIVEN IN INCHES ALL DIMENSIONS AND SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTIFICATION
LIFT SHACKLE HOLES BOTH SIDES AND ENDS
FORK HOLES BOTH SIDES AND CONDENSER END
TOP VIEW
15 AND 20 TON COMERCIAL
DC*180/240***
LEFT END VIEW
88.116
LINE WIRE ENTRANCE
18.579
12.137
8.949
3.058
8.204
TSTAT WIRE ENTRANCE
(if applicable)
DISCONNECT SWITCH LOCATION
Dimensions — 15 & 20 Tons
15
16
www.daikincomfort.com BACK VIEW
LEFT SHACKLE HOLES BOTH SIDES AND ENDS
FORK HOLES BOTH SIDES AND CONDENSER END
133.354
CONDENSATE DRAN OUTLET THIS SIDE ONLY
ALL DIMENSION GIVEN ARE IN INCHES ALL DIMENSIONS AND SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
53.212
TOP VIEW
35.551
7.017
50.750
88.116 LEFT END VIEW
3.058
8.204
DC*300*** 25-TON COMMERCIAL
12.125
LINE WIRE ENTRANCE TSTAT WIRE ENTRANCE
Dimensions — 25 Tons
SS-DCC15
Unit Clearances Maintain an adequate clearance around the unit for safety, service, maintenance, and proper unit operation. Leave a total clearance of 75” on the main control panel side of the unit for possible removal of fan shaft, coil, electric heat, and gas furnace. Leave a clearance of 48” on all other sides of the unit for possible compressor removal or service access, and to ensure proper ventilation and condenser airflow. Do not install the unit beneath any obstruction. Install the unit away from all building exhausts to inhibit Ingestion of exhaust air into the unit’s fresh-air intake.
36” minimum roof overhang
Electrical Entrance Locations 12¹/₈”
3³/₅” High-Voltage Entrance 3⁴/₅”
LowVoltage Entrance
Gas Inlet Location (¾” NPT)
2 x 21”
2 x 60”
7”
48”
9⅔”
22” 46¹⁄₁₀”
22”
Return
Supply
Flue Vent
Vertical Discharge (Top of Unit)
SS-DCC15
www.daikincomfort.com
17
Roof Curb Installation — Rigging
15-Ton Units
Weights (bls.)
20-Ton Units
Weights (lbs.)
25-Ton Units
C
Return
Supply
EVAPORATOR Evaporator CCOILS oil
Provisions for forks have been included in the unit base frame. No other fork locations are approved. • Unit must be lifted by the four lifting holes located at the base frame corners. • Lifting cables should be attached to the unit with shackles. • The distance between the crane hook and the top of the unit must not be less than 60”. • Two spreader bars must span over the unit to prevent damage to the cabinet by the lift cables. Spreader bars must be of sufficient length so that cables do not come in contact with the unit during transport. Remove wood struts mounted beneath unit base frame before setting unit on roof curb. These struts are intended to protect unit base frame from fork lift damage. To remove the struts, extract the sheet metal retainers and pull the struts through the base of the unit. Refer to rigging label on the unit. Important: If using bottom discharge with roof curb, duct-work should be attached to the curb prior to installing the unit. Ductwork dimensions are shown in Roof Curb Installation Instructions Manual. Refer to the Roof Curb Installation Instructions A for proper curb installation. Curbing must be installed in compliance with the National COMPRESSOR Roofing Contractors Association Manual. Compressor 11 Y 40” Lower unit carefully onto roof mounting curb. While rigging the unit, the center of gravity will cause the condenser end to be lower than the CG supply air end. Bring condenser end of unit into alignment with the curb. With condenser end of the unit resting on curb member and using curb as a fulcrum, lower opposite end of the unit until entire unit is seated on the curb. When a COMPRESSOR Compressor 22 rectangular cantilever curb is used, take care to center the unit. Check for proper alignment B and orientation of supply and return openings X 60" with duct. Corner & Center-of-Gravity Locations To assist in determining rigging requirements, unit weights are shown below.
D
Weights (lbs.)
Weight A Weight B Weight C Weight D
590 482 492 401
Weight A Weight B Weight C Weight D
644 525 504 412
Weight A Weight B Weight C Weight D
626 464 501 518
Shipping Weight Operating Weight
2080 1965
Shipping Weight Operating Weight
2202 2085
Shipping Weight Operating Weight
2377 2109
Note: These weights are calculated without installed accessories.
18
www.daikincomfort.com
SS-DCC15
Roof Curb Installation Curb installations must comply with local codes and should follow the established guidelines of the National Roofing Contractors Association. Proper unit installation requires that the roof curb be firmly and permanently attached to the roof structure. Check for adequate fastening method prior to setting the unit on the curb. Full perimeter roof curbs are available from the factory and are shipped unassembled. The installing contractor is responsible for field assembly, squaring, leveling, and mounting on the roof structure. All required hardware necessary for the assembly of the sheet metal curb is included in the curb accessory package. • Determine sufficient structural support before locating and mounting the curb and package unit. • Duct-work must be constructed using industry guidelines. The duct-work must be placed into the roof curb before mounting the package unit. Our full perimeter curbs include duct connection frames to be assembled with the curb. Cantilevered-type curbs are not available from the factory. • Contractor furnishes curb insulation, cant strips, flashing, and general roofing material. • Support curbs on parallel sides with roof members. To prevent damage to the unit, the roof members cannot penetrate supply and return duct openings. Note: The unit and curb accessories are designed to allow vertical duct installation before unit placement. Duct installation after unit placement is not recommended. See the manual shipped with the roof curb for assembly and installation instructions.
123 Curb Top O.D. 119¾ Curb Top O.D.
17²/₂₅
17²/₂₅
17²/₂₅ 74¾ Curb O.D. 61⅞
61⅞
78 Curb Top O.D.
23⅞
1⅝ Typ.
Insulated Panels
11¼
1¾
1¾ 123 Curb Bottom O.D.
SS-DCC15
1⅜ Typ.
www.daikincomfort.com
77½ Curb Bottom O.D.
19
Wiring Diagram — DCC 15 & 20 Tons (230V/460V/575V, Three-Phase Belt Drive)
BK BK
PB
RD
POWER SUPPLY
208V-240V-460V-575V 3 ph / 60hZ
RD OR OR OR
RD
BK
BL
OR
BL
OR
OR RD
OR
RD
BK
RD BK
L3
L1
L2
L3
L1
CC2
L2
L3
T2
T3
⚡
L2
BK
GND
BL CC1
BL
BC T1
T2
T1
T3
T2
T3
T1
BL GR
BK
RD
BK
BL
OR
RD
RD
PU
BL
C FC1
RD
BK
RD
YL
BK
YL
YL
RD
RD
F
BR
YL EM BK
BK
C
PU OR
FC2
CCH2 BL OR
COMP 2
T1
BK
T2
RD
T3
YL
F
BR
RD
PU YL
CCH1
BK
COMP 1
T1
BK
T2
RD
T3
C BK
FC3 BR
F
YL BK OR BK
BL
3 4
2
4
240v
BL
OR 6
1
CCHR2
2
YL
LPS2
HPS2
24V
3
8
5
2
BL
WH
4
BL PK
CM3
BK
LPS1
HPS1
BR
3
PU
BK
CCR1
RD BR PU 2
1
PK
RD
GR
6
5 8
7
PU
9
RD
RD
RD
RD G
GR BL
BR
WH
R
PU BR RD
RD GR
RD
GR
BL
BR R
RD
BL
S2
R
C
NO
BL
GR
K1
XFMR-R COM K1 PU NC
C
BL
YL
GR
#2
XFMR-C
BL BL
EBTDR NOTE
RD
YL YL
CM1
3
PLF 1 4
PK
CM2
1
4 BL
YL
PU
WH
BR
YL
PU
W1
W2
Y1
Y2
SPEED UP
PU
M1
M2
BR S1
G
O
PU
WH
TO THERMOSTAT
SEE NOTE 4
REPLACE JUMPER WITH SMOKE/FIRE DETECTOR
RD
BR
20
BK
BL
YL
TB1
BK
BR
YL
BL
2
1
WH
PU
BL
PU 7
BK
BL
YL
YL 6
BK
PK
GR
9
TB2
575v
BL
1 YL
YL
PU
1 C
YL
3
4 BL
2 208v
GR
PU
R
BL
CCHR1
SEE NOTE 3 PLF 2
BR
460v
CCR2
6
1
PU
⚠
2
BR
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
BK
RD
PU NOTE 5
GR
High Voltage: Disconnect all power before servicing or installing this unit. Multiple power sourcesmaybepresent.Failuretodosomaycausepropertydamage, personal injury, or death.
L1
BK BL
Warning
BK
0140L02581-A
www.daikincomfort.com
SS-DCC15
Wiring Diagram — DCC 15 & 20 Tons (230V/460V/575V, Three-Phase Belt Drive)
COMPONENT LEGEND L3
BC
SUPPLY VOLTAGE
T2 CC1
CC1
T1
COMP1
CC1
T3 T3
COMPRESSOR CONTACTOR
CCH
CRANK CASE HEATER
CCHR
CRANK CASE HEATER RELAY
CCR
COMPRESSOR CONTACTOR RELAY
CM
CONDENSER MOTOR
T2
T1
BLOWER CONTACTOR
CC
208-240/460/575/3/60
CMR
CONDENSER MOTOR RELAY
COMP
COMPRESSOR
ECON C CF1 F
ELECTRONIC BLOWER TIME DELAY
EMR
EVAPORATOR MOTOR RELAY
C
CM1
ECONOMIZER
EBTD
RELAY
R EM
EVAPORATOR MOTOR
FC
CM2
F
CF2
FAN CAPACITOR
GND
EQUPIMENT GROUND
HPS
HIGH PRESSURE SWITCH
LPS C
LOW PRESSURE SWITCH
PB
CF3
POWER DISTRUBTION BLOCK FEMALE PLUG / CONNECTOR
PLF
F
CM3
TB1
TERMINAL BLOCK (24V SIGNAL)
TB2
TERMINAL BLOCK (L1) TRANSFORMER
TR T2
CC2
⚡
L2
High Voltage: Disconnect all power before servicing or installing this unit. Multiple power sourcesmaybepresent.Failuretodosomaycausepropertydamage, personal injury, or death.
L1
CC2
T2
T1 T1
COMP2
CC2
T3 T3
T1
BC
T2
BC
T3
BC
NOTES:
EM
1
2
CCH1
2
CCH2
1. REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE INSULATION AS ORIGINAL (AT LEAST 105°C) USE COPPER CONDUCTOR ONLY. 2. USE COPPER CONDUCTORS ONLY ++ USE N.E.C. CLASS 2 WIRE 3. ECONOMIZER PLUG LOCATED IN THE RETURN AIR COMPARTMENT, REMOVE MALE PLUG, ATTACH FEMALE PLUG TO THE ECONOMIZER ACCESSORY. 4. FOR TWO STAGE OPERATION REMOVE W1 TO W2 WIRE JUMPER. 5. FOR 208V OPERATION MOVE BLACK WIRE FROM TERMINAL 3 TO TERMINAL 2 ON 240V TRANSFORMER
1
208-240V NOTE 5 2 3
1
TR 24V
EBTDR
R
C
G
Warning
BC EBTDR FACTORY WIRING EBTDR
LINE VOLTAGE LOW VOLTAGE
CC1 LPS2
OPTIONAL HIGH VOLTAGE
CC2 4
LPS1
PLF1
7
4
8
5
9
6
3
4
2
FACTORY WIRING
3 CCR2
HPS2
1
2 STAGE COOLING
2
1
9
6
3
8
5
2
7
4
1
6
CCR1
HIGH VOLATGE
PLF2
4
LOW VOLATGE
WIRE CODE
CCHR2 6
4 CCHR1
SEE NOTE 3
BK
BLACK
BL
BLUE
BR
BROWN
GR
GREEN
OR
ORANGE
PK
PINK
PU
PURPLE
RD
RED
WH TB1
S1
S2
C
G
W2
W1
Y1
Y2
YL
O
THERMOSTAT ++
WHITE
W1
WH
G
GR
R
RD
Y1
YL
Y2
PK
C
BL
O
OR
W2
BR
TB1
W1 G R Y1 Y2 C O W2 STAT
YELLOW
YL/PK
YELLOW WITH PINK STRIP
BL/PK
BLUE WITH PINK STRIP
WH
SEE NOTE 4
REPLACE JUMPER WITH SMOKE/FIRE DETECTOR
RD
R
++
FIELD WIRING
⚠
HPS1
THERMOSTAT
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
R
SEE UNIT RATING PLATE FOR TYPE AND SIZE OF OVER CURRENT PROTECTION
0140L02582-A
SS-DCC15
www.daikincomfort.com
21
Wiring Diagram — DCC 15 & 20 Tons (230V/460V/575V, Two-Speed Belt Drive)
CCH1
BK
CCHR1 YL
T3
RD
T2
BK
L3 L2
CC1 T1
L1
OR
BL BK
RD
RD
OR
CCHR2 YL
T3
L3
RD
T2
L2
T1
BK
POWER SUPPLY SEE NOTE 4 208V-240V-460V-575V 3 ph - 60Hz
CC2 L1
OR
1
6 4
2
PU
BK
BK
RD
BL
PU
BK
GRND
RD
CB1 HIGH SPEED L3
RD
T2
L2
BK
T1
BC1
C FC2
L1
T1
PU
OR
L2
RD
T1
YL
GR
L3
BK
T3 T2
BK
RD
GY BL
BC2
L1
YL
1
BK
BL
L3 L2
GY
3
T3 T2
2
RD
F
BR
L1
BL
CB2 LOW SPEED
BK BK BK
C FC1
OR
BL
HIGH EM LOW
OR
T3
OR
YL
L1
RD BK
T1
OR
13 11
T3 T2
YL
12
PU
L3 L2
RD
OR
YL
⚡
T1
BR
F
GR
BK
RD
BK RD OR
PU
C
OR
BK
BL
BK
FC3 F
BR
OR
BL
TR 1 C
2
3 208 460 240 575
GR
BR
PK
SEE NOTE 5
24V
PU
BR
PU
TB2
BK
GR
BK BK
PK
BK
BR
BL
SEE NOTE 3
PU
BL
PU 3
3
3
2
5
2
5
BR1
4 NC
NO
BR2
NO 4 NC
BL
BR
GR
YL
BL
YL
1
2
1
1
4
BL
8
HPS2
6
7
HPS1
5
PK
3
4
9
2
PLF 2
1
WH
BL
BL
GR
YL
WH
YL
RD
PU
BL
CCR1
CM3
GR
YL
YL
YL
PU
GR
BL
CM2
PU
CCR2
2
1
3
PU
4
LPS2
LPS1
RD
RD WH
YL
YL
YL
BR
CM1
PU
WH
1
2
3
4
5
6
7
8
9
⚠
PLF 1
RD
PU
BR
RD
RD RD G
GR BL
EBTDR NOTE
WH
#2
NO
PU
R
GR
K1
PU XFMR-R
RD
RD
PK
GR
PU
BL
RD RD
GR
RD BL
BR
BL
BL
YL WH
GR
PU
BR
W1
W2
YL
PU
Y1
Y2
K1
PU NC
C
BL
YL
WH
COM
XFMR-C
BR
RD
SPEED UP
PU
M1
BR TB1
S1
S2
C
G
O
M2
PU
WH
TO THERMOSTAT
SEE NOTE 4
REPLACE JUMPER WITH SMOKE/FIRE DETECTOR
RD
R
High Voltage: Disconnect all power before servicing or installing this unit. Multiple power sourcesmaybepresent.Failuretodosomaycausepropertydamage, personal injury, or death.
4
2
2
T3 T2
Warning
6
YL
BK
COMP
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
1
BK
BL
CCH2
PB
RD
T3 T2 T1
RD
BK
YL
1
BK
OR COMP
BR 0140L03208-A
22
www.daikincomfort.com
SS-DCC15
Wiring Diagram — DCC 15 & 20 Tons (230V/460V/575V, Two-Speed Belt Drive cont.)
L1
L2
L3 COMPONENT LEGEND
SUPPLY VOLTAGE 208-240/460/575/3/60
BLOWER CONTACTOR
BR
BLOWER RELAY
CC
COMPRESSOR CONTACTOR
T2
T1 T1
COMP1
CC1
T3 T3
C CF1 F
C
CM1
CCH
CRANK CASE HEATER
CCHR
CRANK CASE HEATER RELAY
CCR
COMPRESSOR CONTACTOR RELAY
CM
CONDENSER MOTOR
CMR
CONDENSER MOTOR RELAY
COMP
COMPRESSOR
ECON
CM2
F
CF2
ECONOMIZER
EBTD
ELECTRONIC BLOWER TIME DELAY
EMR
EVAPORATOR MOTOR RELAY RELAY
R EM
EVAPORATOR MOTOR
FC
C CF3 F
FAN CAPACITOR
GND
EQUPIMENT GROUND
HPS
HIGH PRESSURE SWITCH
CM3
LPS
LOW PRESSURE SWITCH
PB
T2
CC2
T2
T1 T1
CC2
COMP2
POWER DISTRUBTION BLOCK
PLF
FEMALE PLUG / CONNECTOR
TB1
TERMINAL BLOCK (24V SIGNAL)
TB2
TERMINAL BLOCK (L1) TRANSFORMER
TR
CC2
T3
⚡
CC1
CC1
High Voltage: Disconnect all power before servicing or installing this unit. Multiple power sourcesmaybepresent.Failuretodosomaycausepropertydamage, personal injury, or death.
T2
BC
T3
BC2
CB2
BC1
CB1
LOW SPEED
BC2
CB2
BC2
CB2
NOTES:
EM CB1
BC1
CB1
BC1
HIGH SPEED
1. REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE INSULATION AS ORIGINAL (AT LEAST 105°C) USE COPPER CONDUCTOR ONLY. 2. USE COPPER CONDUCTORS ONLY ++ USE N.E.C. CLASS 2 WIRE 3. ECONOMIZER PLUG LOCATED IN THE RETURN AIR COMPARTMENT, REMOVE MALE PLUG, ATTACH FEMALE PLUG TO THE ECONOMIZER ACCESSORY. 4. FOR TWO STAGE OPERATION REMOVE W1 TO W2 WIRE JUMPER. 5. FOR 208V OPERATION MOVE BLACK WIRE FROM TERMINAL 3 TO TERMINAL 2 ON 240V TRANSFORMER
CCHR1 1
2
CCH1
2
CCH2
1
208-240V
CCHR2
NOTE 5 2 3
1
TR 24V
C
G
BR1
R
4
EBTDR
EBTDR
1
BR1
2
BC1
5
BC2
3
FACTORY WIRING
BR2
2
4
LINE VOLTAGE LOW VOLTAGE
5 1
BR2
2 STAGE COOLING
LPS2
HPS1
++
FIELD WIRING
OPTIONAL HIGH VOLTAGE
FIELD WIRING CC2
PLF1
THERMOSTAT
3
CC1 LPS1
Warning
R
HPS2
4
2
1
3
⚠
EBTDR
HIGH VOLATGE LOW VOLATGE
4
8
5
9
6
1
3
4
2
CCR1
9
6
3
8
5
2
7
4
1
6
PLF2
WIRE CODE
4 CCHR2
6
4 CCHR1
SEE NOTE 3
BK
BLACK
BL
BLUE
BR
BROWN
GR
GREEN
OR
ORANGE
PK
PINK
PU
PURPLE
RD
RED
WH YL
TB1
S1
S2
C
G
W2
W1
Y1
Y2
O
GR
R
RD
Y1
YL
Y2
PK
C
BL
O
OR
W2
BR
TB1
W1 G R Y1 Y2 C O W2 STAT
YELLOW
YL/PK
YELLOW WITH PINK STRIP
BL/PK
BLUE WITH PINK STRIP
WH
THERMOSTAT ++
SEE UNIT RATING PLATE FOR TYPE AND SIZE OF OVER CURRENT PROTECTION
SS-DCC15
WH
G
SEE NOTE 4
REPLACE JUMPER WITH SMOKE/FIRE DETECTOR
RD
R
WHITE
W1
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
CCR2 7
0140L02915-A
www.daikincomfort.com
23
Wiring Diagram — DCC 25 Tons (230V/460V/575V)
POWER DIAGRAM DCC300 ***(3,4,7) LINE VOLTAGE
L2
L3
YL PU OR
RD BR
⚡
BK
GND
PB
CCAS1 BK BK
CC1 BK RD YL
BK
L1
T1
BK
RD
L2
T2
RD
YL
L3
T3
YL
L2
GY
BK
GY
BK
CCH1
L1
COMP 1
GR
GY
L3
CCAS2 CC2 BK RD PU
BK
L1
T1
BK
RD
L2
T2
RD
PU
L3
T3
PU
BK
L1 L2
BK
BR
BK
PU
BK
F1
BR
BR
F2
PU
BR
PU
F3
BK
PU
BK
GR
L3
FB 1 BK
BK
BR
CCH2
COMP 2
PU
BR
PU
CMC 1
PLF PLM
L1
T1
BK
BK
L2
T2
BR
BR
L3
T3
YL
YL
1
1
2
2
3
3
BK BR PU
L1
CM1
L2
T3 T2 T1
BK
GR
L3
8
LAC MC
BK
4
BR PU
PU
RD
L1
T1
L2
T2
BR
YL
L3
T3
YL
BK
CMC 2
BK
24V CNTL VOLTAGE
BK BR
PU
L1
T1
BK
BK
L2
T2
BR
BR
L3
T3
PU
PU
PLF PLM
TR1
2,3
RD LINE VOLTAGE
BK
FB 2 RD
F4
RD
F5
OR
F6
CB1 HIGH SPEED
BC1
3
BK
BR PU
L1 L2
CM2
GR
L3
BLOWER CONTACTOR BLOWER RELAY CIRCUIT BREAKER COMPRESSOR CONTACTOR CC AUX SWITCH CRANK CASE HEATER COMPRESSOR CONTACTOR RELAY COMPRESSOR CONDENSER MOTOR CONDENSER MOTOR CONTACTOR CONDENSER MOTOR RELAY ELECTRONIC BLOWER TIME DELAY RELAY ECONOMIZER ECON EVAPORATOR MOTOR EM CM/CCH/TR1 FUSE BLOCK FB1 EM FUSE BLOCK FB2 EVAPORATOR FREEZE STAT FM MODULE F1, F2, F3 CM/CCH/TR1 FUSES F4, F5, F6 EM FUSES HIGH PRESSURE SWITCH HPS LOW AMBIENT CONDENSER MOTOR LACMC CONTACTOR LOW AMBIENT MODULE LAM LOW AMBIENT RELAY LAR LOW AMBIENT TIMER LAT LOW PRESSURE SWITCH LPS POWER DISTRIBUTION BLOCK PB FEMALE PLUG / CONNECTOR PLF MALE PLUG / CONNECTOR PLM LOW VOLTAGE TERMINAL BLOCK 1 TB1 LOW VOLTAGE TERMINAL BLOCK 3 TB3 CONTROL TRANSFORMER TR1 (LINE VOLTAGE/24VAC)
5
BK
L1
T1
BK
YL (11)
T2
RD
L2
T2
RD
YL (13)
T3
OR
L3
T3
OR
YL (12)
YL
L1
T1
YL
BK (1)
BK
L1
T1
RD
RD
L2
OR
OR
L3
BK
2
3
COMPONENT LEGEND
BK
BK
1
2
BC BR CB CC CCAS CCH CCR COMP CM CMC CMR EBTDR
RD
BK
1
CB2 LOW SPEED
BC 2
FACTORY WIRING
LINE VOLTAGE LOW VOLTAGE OPTIONAL HIGH VOLTAGE
EM
BK
L1
T1
RD
L2
T2
BL
L2
T2
BL
BK (3)
OR
L3
T3
GY
L3
T3
GY
BK (2)
FIELD WIRING
GR
HIGH VOLTAGE LOW VOLTAGE
WIRE CODE
BK BL BR GR GY OR PK PU RD WH YL
BLACK BLUE BROWN GREEN GRAY ORANGE PINK PURPLE RED WHITE YELLOW
High Voltage: Disconnect all power before servicing or installing this unit. Multiple power sourcesmaybepresent.Failuretodosomaycausepropertydamage, personal injury, or death.
L1
Warning
L3
⚠
L2
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
7
L1
NOTES: 1. REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL (USE COPPER CONDUCTORS ONLY). 2. THE CONTROL TRANSFORMER HAS MULTIPLE HIGH VOLTAGE TAPS. ENSURE WIRE CONNECTIONS ARE CORRECT FOR UNIT SUPPLY VOLTAGE RATING 3. 208/230V SUPPLY POWER UNITS ARE FACTORY CONNECTED TO THE CONTROL TRANSFORMER 240V TAP. MOVE WIRE CONNECTION FROM 240V TAP TO 208V TAP WHEN 208V POWER SUPPLY IS USED. 4. SEE CONTROL DIAGRAM FOR CONTROL TRANSFORMER LOW VOLTAGE CONNECTIONS 5. OPTIONAL; CB1,CB2,BC2 AND ASSOCIATED WIRING IS PRESENT ONLY WITH 2-SPEED EVAPORATOR MOTOR. 6. USE COPPER CONDUCTORS ONLY. UNIT TERMINALS ARE NOT DESIGNED FOR OTHER CONDUCTORS. THE USE OF OTHER TYPE CONDUCTORS MAY CAUSE DAMAGE TO THE UNIT. 7. SEE ACCESSORY KIT LITERATURE FOR OPTIONAL ELEC HEAT AND CONVENIENCE OUTLET WIRING DIAGRAMS. 8. IF LOW AMBIENT KIT INSTALLED, DISCONNECT CONDENSER MOTOR WIRES (BK,BR,YL) FROM CMC1 (T1,T2,T3) AND CONNECT TO CORRESPONDING BK,BR,YL WIRES ON LOW AMBIENT HARNESS (INSULATED MALE QUICK CONNECT). ALSO CONNECT LOW AMBIENT HARNESS WIRES (BK,BR,YL) (INSULATED FEMALE QUICK CONNECT) TO T1,T2,T3 ON CMC1.
24
www.daikincomfort.com
0140L04899-A
SS-DCC15
Wiring Diagram — DCC 25 Tons (230V/460V/575V - Controls Diagram)
THERMOSTAT WIRING 2 STAGE COOLING
S2
R
4
C
S1
5
WH
GR
BR
RD
PU
BK
YL
RD
RD
BL
9
RD
R
YL
Y1
Y2
PK
Y2
C
BL
C
O
OR
Y1
RD
WH
G
16 AUX A
BR
B
Y
Y
Y
Y
R
R
B
B
AUX B
18
O
STAT
TB1
R
B
SENSOR 2
17
5
Y
Y R
6
8
Y
Y
SENSOR 1
SEN1 TB3 TR1
SEN2
SUPPLY (LINE) VOLTAGE
RD
BL
BL
24 VAC
SMK DET OPTION
7
3 GR
BL
BL
RD
RD
⚡
BK
3 TB3 RD
CCR1
RD
RD
2
4
5
6
LPS1
HPS1
YL OR YL
YL
YL
YL
CC1
YL
YL
BL
YL
BL
YL
High Voltage: Disconnect all power before servicing or installing this unit. Multiple power sourcesmaybepresent.Failuretodosomaycausepropertydamage, personal injury, or death.
RD
3
1
CCR2 OR
2
4
5
6
PU
HPS2
WH
BR
GR
RD
PU
YL
RD
RD
PU YL
3
1
LPS2
PU
PU
PU
CC2 BL
PU
PU
PU
BL
BL PU
BL
BL
YL PU GY
GY
PU
PU
CMC1 BL
PU
CMR 4
2
RD
5
BL 3
BL
BL PU
GY
6
1
BL
GY
YL
RD
CMC2
LAM1
BL GY
BL
1
BK
2
BK
3
PLF
PLM
1
1
2
2
BK
WH
BK
WH -t°
BL
BK
BK
BC1
BR
GR
RD
PU
YL
RD
RD PU
2
3
2
YL
1
PLM 3
1
PLF 3
ECON ECON SHRT PLF PLM 2
GR YL PU PU YL BL GR
WH WH WH
RD
1
1
2
2
3
3
4
4
5
5
1
PU
3
YL
1 Y2-I 2 Y2-O 3 Y1-I 4 Y1-O
5 6
6
7
7
7
8
8
9
9
MAT 1 MAT 2
MAS
OAT 1 OAT 2
1 EXH1 2 AUX1-O
4
6
ECON MODULE 1 2 AUX2-I 3 OCC 4 E-GND
2
8 9
GRD LUG
ECON PLM
2
YL PU
BL
S-BUS 1 S-BUS 2
OD ENTH
IAQ 2-10 1 IAQ COM 2 IAQ 24V 3
1 C 2 R
ECON ACT
ACT COM 1 ACT 24V 2 3 4
ECON OPTION BL
OR
LAR
RD YL
2
4
5
6
BL
GY
LAM2
PLF WH
1 2
1
WH
2
3
BK
GY
BL
OR 3
1
8
LOW AMB OPTION
PLM 1 2
WH
WH
WH
WH -t°
LAT BK
BL
BL
YL
T1 T6
BL
8
T2
LA CMC
BL
OR BK YL RD
⚠
WH
3
BL BL
PU YL BK
RD
BL
9 RD BL
WH WH
GR
BR
RD
RD
GR
GR
RD
EBTDR XFMR-R
RD
R GR GR PU RD WH BL BR WH 1
2
3
4
5
6
PU RD 7
8
9
C SPEEDUP
G (NC)
BL
XFMR-C
3A
RD
7
BL
M1 M2 COM
6
(NO)
GR BL
BL
HEAT PLF
NOTES: 1.
REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL (USE COPPER CONDUCTORS ONLY).
6.
EBTDR RELAY ENERGIZES 7 SEC AFTER 24VAC IS APPLIED TO "G". THE RELAY DE-ENERGIZES 65 SEC AFTER 24VAC IS REMOVED FROM "G".
2.
IF OPTIONAL ECONOMIZER IS INSTALLED, REMOVE ECON SHRT PLM AND CONNECT ECON PLM TO ECON PLF.
7.
EBDTR RELAY DELAYS WILL DECREASE TO APPROX 3-5 SEC WHEN "SPEEDUP" IS SHORTED TO "C".
3.
TB3 LOW VOLTAGE TERMINAL BLOCK.4 TERMINALS FOR 24VAC PWR (RD,BK,BR WIRE) AND 6 TERMINALS FOR 24VAC COM (BL WIRE).
8.
IF LOW AMBIENT KIT IS INSTALLED, CONNECT GY WIRE FROM LAM2-3 TO CMR-4. ALSO CONNECT BL COM WIRES FROM LAT-T6 AND LAM2 -2 TO TB3 (24V COM).
4.
CONNECTIONS SHOWN ARE FOR 1-STAGE HEAT OPERATION. WHEN 2-STAGE OPERATION IS REQUIRED REMOVE WH JUMPER WIRE CONNECTING W2 TO W1 ON TB1.
5.
IF OPTIONAL SMOKE DETECTOR IS INSTALLED, REMOVE RD JUMPER WIRE CONNECTING S1 TO S2 ON TB1 AND MAKE THE FOLLOWING WIRE CONNECTIONS: RD WIRE TO S1,BR WIRE TO TB3 (24V/PWR),BL WIRE TO TB3 (24V/COM).
SS-DCC15
Warning
YI
Y2
R
10 PK
9.
LAT ON/OFF TIME SETTINGS : ON -TIME (LEFT COLUMN): 2,8 = ON OFF -TIME ( RIGHT COLUMN): 8 = ON ALL OTHER DIP SWITCHES = OFF
www.daikincomfort.com
CONTROLS DIAGRAM DCC300***(3,4,7) B 1 SPD EM
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
G
W2
SMOKE DETECTOR BL
W
GR
G
TB1 W1
WH
W
24V AC/DC
FIELD CONTROL WIRING
CLASS 2
0140L04763-A
25
Wiring Diagram — DCC 25 Tons (230V/460V/575V, Two-Speed Belt Drive - Controls Diagram)
THERMOSTAT WIRING 2 STAGE COOLING WH
W
GR
G
TB1
4
R
5
Y1
RD
BR
GR
RD
YL YL
PU
BK
RD
RD
RD
Y1
Y2
PK
Y2
C
BL
C
OR
O
BL
R
YL
16 AUX A
BR
6
8
AUX B
R
B
B
Y
Y
Y
Y
R
R
B
B
18
O
TB3 SUPPLY (LINE) VOLTAGE
TR1
SEN2
3 GR
RD
BL
BL
24 VAC
BL
BL
CCR1
RD
2
4
5
6
OR
YL
YL
YL
BK
YL
BL
YL BL
3
3 TB3
OR
BK
PLF
YL
FM1
BL
1
RD
BL
2
RD
3
BK
PLM
1
1
2
2
RD
WH
RD
WH -t°
RD
HPS2 CCR2
YL
YL
CC1
BL 1
RD
LPS1
HPS1
BK
YL
RD
SEN1
SMK DET OPTION
7
STAT
TB1
SENSOR 2
17
5
Y
Y R
2
OR
4
5
BL
BR
⚡
WH
WH WH
C
S1
RD
Y
Y
SENSOR 1
BL
LPS2
PU
CC2
PU
PU
PU
BL PU
BL
6
PU
BL
PU
3
1
BL
FM2
PU BL BR
PLF
1
OR
2
OR
3
PLM
1
1
2
2
OR
WH
OR
WH -t°
BL
BL
BL YL
YL
PU GY
CMC1
GY
PU
2
4
5
6
PU
GY
RD GY
BL GY
3
1
1
BK
2
BK
3
CMC2
PU
PLF
LAM1
PU
BL
RD
1
1
BL
2
2
BK
WH
BK
WH
BL -t° BL
GR
BR2 BR
GR
RD
PU
PU
YL YL
RD
RD
PU YL
2
BR1
4
YL
2
4
5
6
BK
WH 5
6
BL 3
1
BL
BL
RD
GR
PU
YL
RD
RD PU
3
2
YL
BL
BK BR BK
BK BL
PU YL GR
BR
BC1 HIGH SPEED
BL
BR
GR
WH
BL
BR
BL
YL
BL 3
1
2
BC2 LOW SPEED
GR
BR
YL
3
BL
PLM
BL
WH WH
BL BL
CMR
YL
1
PLM 3
1
PLF 3
High Voltage: Disconnect all power before servicing or installing this unit. Multiple power sourcesmaybepresent.Failuretodosomaycausepropertydamage, personal injury, or death.
S2
9
ECON ECON SHRT PLF PLM
GR YL
1
PU PU YL BL GR
WH
WH WH
RD
YL
1
2
2
3
3
BL
2
2
ECON PLM
GRD LUG
1
PU
ECON MODULE 1 2 AUX2-I 3 OCC 4 E-GND
2
PU
3
YL
4
5
5
5
6
6
6
7
7
7
8
8
8
9
9
9
1 Y2-I 2 Y2-O 3 Y1-I 4 Y1-O 1 C 2 R
MAS
OAT 1 OAT 2
1 EXH1 2 AUX1-O
4
4
MAT 1 MAT 2
S-BUS 1 S-BUS 2
OD ENTH
IAQ 2-10 1 IAQ COM 2 IAQ 24V 3
ECON ACT
ACT COM 1 ACT 24V 2 3 4
ECON OPTION
BL
BL
OR
LAR RD YL
2
4
5
6
BL
GY
BL
LAM2 1
WH
2
WH
3
BK
BL
OR
GY BK
BL 3
1
8
BL
OR BK YL RD
YL
Warning
YI
Y2
R
G
PLF
PLM
1
1
2
2
WH
WH
WH
WH
LOW AMB OPTION -t°
LAT T1 T6
BL
⚠
G
W2
10 PK
8
T2 RD
LA CMC
BL
9 RD BL
WH WH
BR
GR
RD
RD
GR
GR
RD
EBTDR
RD
XFMR-R
RD R GR GR PU RD WH BL BR WH 1
2
3
4
5
6
RD
PU 7
8
9
C SPEEDUP
G (NC)
BL
XFMR-C
3A
7
BL
BL
M1 M2 COM
6
(NO)
GR BL
BL
HEAT PLF
NOTES: 1. REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL (USE COPPER CONDUCTORS ONLY).
6.
EBTDR RELAY ENERGIZES 7 SEC AFTER 24VAC IS APPLIED TO "G". THE RELAY DE-ENERGIZES 65 SEC AFTER 24VAC IS REMOVED FROM "G".
2. IF OPTIONAL ECONOMIZER IS INSTALLED, REMOVE ECON SHRT PLM AND CONNECT ECON PLM TO ECON PLF.
7.
EBDTR RELAY DELAYS WILL DECREASE TO APPROX 3-5 SEC WHEN "SPEEDUP" IS SHORTED TO "C".
3. TB3 LOW VOLTAGE TERMINAL BLOCK.4 TERMINALS FOR 24VAC PWR (RD,BK,BR WIRE) AND 6 TERMINALS FOR 24VAC COM (BL WIRE).
8.
IF LOW AMBIENT KIT IS INSTALLED, CONNECT GY WIRE FROM LAM2-3 TO CMR-4. ALSO CONNECT BL COM WIRES FROM LAT-T6 AND LAM2 -2 TO TB3 (24V COM).
4. CONNECTIONS SHOWN ARE FOR 1-STAGE HEAT OPERATION. WHEN 2-STAGE OPERATION IS REQUIRED REMOVE WH JUMPER WIRE CONNECTING W2 TO W1 ON TB1.
9.
5. IF OPTIONAL SMOKE DETECTOR IS INSTALLED, REMOVE RD JUMPER WIRE CONNECTING S1 TO S2 ON TB1 AND MAKE THE FOLLOWING WIRE CONNECTIONS: RD WIRE TO S1,BR WIRE TO TB3 (24V/PWR),BL WIRE TO TB3 (24V/COM).
26
LAT ON/OFF TIME SETTINGS : ON -TIME (LEFT COLUMN) : 2,8 = ON OFF -TIME (RIGHT COLUMN) : 8 = ON ALL OTHER DIP SWITCHES = OFF
www.daikincomfort.com
CONTROLS DIAGRAM DCC300***(3,4,7) V 2SPD EM
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
W1
SMOKE DETECTOR BL
W
24V AC/DC
FIELD CONTROL WIRING
CLASS 2
0140L04764-A
SS-DCC15
Accessories
Filed-Installed Item #
Description
Fits Model Sizes
FieldInstalled
14" Roof Curb 25% Manual Fresh Air Damper 25% Motorized Fresh Air Damper Burglar Bar Sleeves with Supply and Return Concentric Duct Kit Concentric Duct Kit Concentric Duct Kit Convenience Outlet: Powered Convenience Outlet: Non Powered Disconnect Switch (non-fused) Ultra Low-Leak Downflow Economizer3 Low-Leak Downflow Economizer4 Electric Heat Kits (75kW not available as factory-installed kit) High-Static Kit (230/460v) High-Static Kit (575v) High-Static Kit (230/460v) High-Static Kit (575v) High-Static Kit (all voltages) Horizontal Discharge Curb — End Discharge
15-25 tons 15-25 tons 15-25 tons 15-25 tons 15 tons 20 tons 25 tons All Models All Models All Models 15-25 tons 15-25 tons All Models 15 tons 15 tons 20 tons 20 tons 25 tons 15-25 tons
√ √ √ √ √ √ √
√ √ √ √ √ √ √ √
HZCURB180240SDN
Horizontal Discharge Curb — Side Discharge; duct openings on non-service side
15-25 tons
√
1100
HZCURB180240SDS
Horizontal Discharge Curb — Side Discharge; duct openings on service side
15-25 tons
√
1100
Hurricane Restraint Clips Low-Ambient Kit Low-Ambient Kit (208/230V & 460V) Downflow Power Exhaust (208/230v) Downflow Power Exhaust (460v) Downflow Power Exhaust (575v) Smoke Detector Freeze Stat Kit
All Models 15-20 tons 25 tons 15-25 tons 15-25 tons 15-25 tons All Models 25 tons
√ √ √ √ √ √
2 2 2 200 200 200 11 1
14CURB180300 D25FD180300 D25MFD180300 DDNBB180240 CDK180 CDK240 CDK300
DDNECNJ180300B HSKT180 ¹ HSKT180-7 ¹ HSKT240 ¹ HSKT240-7 ¹ HSKT300C HZCURB180240ED
GHRC-1 LAKT03 LAKT05 DPE1803002 DPE1803004 DPE1803007 FSKT02A
FactoryInstalled
√ √ √ √ √ √
√ √
√ √2
Operating Weight (lbs)
285 34 42 60 158 197 244 42 2 5 281 416 21 4 4 126 126 8 800
1 HSKT High-static kits are for use with standard single-speed belt-drive units only. 2 FSK02A is standard on 2 speed, V, models, and field installed for single speed, B, models. 3 Please contact RRS Rooftop Systems directly if Power Exhaust is required. 4 Please use part number DPE1803002 / DPE1803004 / DPE1803007 if Power Exhaust is required. Note: Where multiple variations are available, the heaviest combination is listed.
SS-DCC15
www.daikincomfort.com
27
Notes
Our continuing commitment to quality products may mean a change in specifications without notice. © 2016 • Houston, Texas • Printed in the USA.
28
www.daikincomfort.com
SS-DCC15