Transcript
053-023 Issue 2 Config’ Section Analogue senders
Parameter
Type
Low Pressure
Trip
Low Pressure
Pre Alarm
High Temperature
Pre Alarm
DEEP SEA ELECTRONICS
Icons displayed
Model 5210 Installation and Configuration Instructions
High Temperature
Trip
Low Fuel Level %
Pre Alarm
Calendar
Date/time
Date/time
Timers
Start delay
Timer (secs)
2
Preheat
Timer (secs)
3
Crank attempt
Timer (secs)
4
Crank rest
Timer (secs)
5
Safety delay
Timer (secs)
6
Overspeed overshoot
Timer (secs)
7
Warming up
Timer (secs)
8
Return delay
Timer (secs)
10
NOTE:- To exit the front panel configuration editor at any time, press the Stop/Reset button. Ensure you have saved any changes you have made by pressing the 9 button first.
Generator output
Engine speed
DC Voltages
Accessing the front panel config’ editor
Cooling run
Timer (secs)
11
E.T.S.(Energise to stop) solenoid hold
Timer (secs)
12
Generator Under Voltage L1-N
Trip
Generator Under Voltage L1-N
Pre Alarm
Generator Over Voltage
Pre Alarm
Generator Over Voltage
Trip
Generator Under Frequency
Trip
Generator Under Frequency
Pre Alarm
Generator Over Frequency
Pre Alarm
Generator Over Frequency
Trip
Delayed Overcurrent %
Trip
Under Speed (RPM)
Trip
Under Speed (RPM)
Pre Alarm
Over Speed (RPM)
Pre Alarm
Over Speed (RPM)
Trip
Low DC Voltage
Warning
High DC Voltage
Warning
Charge Alternator Failure
Warning
Deep Sea Electronics Plc. Highfield House, Hunmanby Industrial Estate, North Yorkshire. YO14 0PH. ENGLAND. Tel:+44 (0)1723 890099 Fax: +44 (0)1723 893303. Email:
[email protected] Web: www.deepseaplc.com LO CALL (from UK BT landlines) : Telephone 0845 260 8900.
V V V V
Press the configure/log and Stop/Reset buttons simultaneously. The LCD configure indicator# will flash to indicate that the module is in ‘configuration button and the configure/log button. mode’. Release the Stop/Reset If a PIN number has been set, press + / - to set the first digit, then press 9 to adjust the next digit. Repeat this until all four digits have been entered. The first configurable parameter is now displayed. Pressing the + or - buttons will cycle through the parameters.
Editing an analogue value Access the front panel config editor as detailed above. Press the +/- buttons to view the parameter you wish to change (see parameter table overleaf). Press the 9 button to enter adjust mode. The value to be adjusted will flash. Press the +/- buttons to adjust the parameter to the desired value. Press the 9 button to ‘save’ the value. The value will stop flashing to confirm that it has been saved. To select another value to edit, press the + button. Continuing to press the +/- buttons will cycle through the available parameters.
Editing the time
A
V V
Deep Sea Electronics Inc. 3230 Williams Avenue, Rockford, IL 61101-2668, USA Phone: +1 (815) 316-8706 Fax: +1 (815) 316-8708 Email:
[email protected] Web: www.deepseausa.com TOLL FREE (USA only) Tel: 1 866 636 9703
The date/time should initially be set using the 5200 series configuration software. However there may be certain circumstances where a minor change to the module’s time is required. One such instance is correction for daylight saving. Access the front panel config editor as detailed above. Press the + button until the calendar is shown : To edit the time, press the 9 button. The time, 4.30 in this example, will begin flashing. Press the + or - buttons to adjust the time in one minute steps until the desired time is shown. Press the 9 button to save the change. The time stops flashing to confirm that it has been successfully stored. Example : This display is showing a time of st 4:30 on 21 October 2002.
NOTE: Full configuration of the 5210 module is possible using the 5200 series configuration software for PC in conjunction with the P810 interface.
43
CT Earth
F2A
35
F2A
36
F2A
37
46
L1
38
47
N
L
LOAD L2 L3
H
22
Optional CanBus COM
21
11
20
10
Optional RS232
13
9 way D
12
SCR
23
A
25
B
15
26
6
5200 series configuration software
24
Optional RS485
810 interface To plant supply +ve
14
Not connected
Output expansion 157 relay board or 548 annunciator
16
17 18
157/548
8
19 810
7
Configurable auxiliary output 3
5210 controller 45
Not connected
CT common 42
44
Configurable auxiliary output 2
41
9
Configurable auxiliary output 1
40
4
Configurable auxiliary input 6
internal emergency stop
5
Configurable auxiliary input 5
L1
39
3
Configurable auxiliary input 4
L2
2
Fuel
Configurable auxiliary input 1
L3 N
1
F
+
Configurable auxiliary input 2
Configurable auxiliary input 3
3 phase, 3 wire These ground connections must be on the engine block and must be a sound electrical connection to the sender bodies. The ground connection to terminal 47 must not be used to provide a ground connection to any other device.
Fuel level sender
Module Dimensions - 240mm x 172mm x 57mm (9½” x 6¾” x 2¼”) Panel cutout - 220mm x 160mm ( 8.7” x 6.3”) Supply for controller
F
Crank
Oil pressure sender Charge WL alt.
Coolant temp. sender
Alternative AC wiring Starter motor Battery
Not connected
2 phase, 3 wire ( 2 phase centre tap neutral) Emergency stop
Dimensions Typical wiring diagram
MPU
Ground screen at one end only
Functional Earth