Transcript
Installation guide
DELTA 200 Outdoor-temperature-driven controller for hot water heating
Unit compliant with the requirements of directives 2004/108/CE (Electromagnetic Compatibility) and 2006/95/CE (Low-Voltage Safety).
*2702087_Rev.1*
DELTA DORE Bonnemain - 35270 COMBOURG - France E-mail :
[email protected]
Because of changes in standards and equipment, the characteristics given in the text and the illustrations of this document are not binding unless confirmed by Delta Dore.
Contents
Installing the room unit
Installing the room unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Room unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Technical unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Installing the sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Water temperature sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Outdoor sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Determining the type of installation . . . . . . . . . . . . . . . . . . . . . . . . 6 Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Choosing a location Since the temperature measurement sensor is inside the unit, you must install the thermostat flush-mounting box: - in zone 1 (main room) only, - on an accessible wall at a height of 1.50 m, - away from heat sources (fireplaces, sunlight) and draughts (windows, doors). IMPORTANT: Do not install the thermostat on a wall in contact with the outdoors or with an unheated room (e.g. garage, etc.). The sleeve output in the flush-mounting box must be plugged (with mastic) in order to avoid unwanted air movements that would cause the sensor reading to be inaccurate.
Activation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Technical characteristics Technical unit • 230V, 50 Hz power supply, ±10% • Class I insulation • Consumption: 4 VA • 1 outdoor sensor input • 2 feed (zone 1) and return (zone 2) sensor inputs • 2 circulator control outputs (zone 1 and zone 2): 2A, 230V • 1 boiler control output, 2A dry contact (do not supply mains power) • 1 mixer valve control output: 2 2A, 24V or 230V operating contacts that open and close the valve (zone 1) • Bus connection with the room unit: insulated 1.52 electric cable, max. length 50 m • Automatic action: 1.C • Storage temperature: -10°C to +70°C • Operating temperature: 0°C to +40°C • Dimensions: 80 x 230 x 65 mm • Fire rating: 5V
• Circulator anti-seizing function: it switches the circulator on for 3 seconds if the circulator has not operated in the previous 24 hours (useful when the heating is off). Room unit • Power supply by bus, 12 to 22V voltage • Class III insulation • Clock backup during mains power failure: 2 hours (by capacitor) • Storage temperature: -10°C to +70°C • Operating temperature: 0°C to +40°C • Dimensions: LxHxD = 82 x 94 x 53 mm • Protection index: IP 30 • Fire rating: Vo
-2-
approx. 1.5 m
Min. 20 cm
-3-
Mounting
Installing the sensors
Mounting the room unit
Feed (zone 1) and return (zone 2) sensor The water temperature sensors are wall-mounted. They are used to measure the surface temperature of pipes.. They can be used in a measurement range of 30°C to +150°C, and are fitted as standard with a 10 kΩ NTC measuring element.
Switch off the mains power supply (general circuit breaker) before proceeding. To attach the unit to the wall, you must separate it from its base. To do this, unscrew the lock screw as shown opposite.
2
1
Once separated from the unit, the base can be connected to the technical unit via the bus, then attached to the flush-mounting box (distance between centres: 60 mm).
Screw the unit closed.
Mounting the technical unit The technical unit must be installed next to the boiler. Remove the cover and attach the unit using screws and plugs.
The sensors have a clamp so that they can be attached to pipes up to 1½" in diameter. The feed sensor (zone 1) must be installed after the mixer valve, between the circulator (~50 cm) and the connected equipment (underfloor heating or radiators). The return sensor (zone 2) must be installed on the return of the direct radiator network. To ensure that the temperature is measured correctly, apply the thermal paste from the syringe between the sensor and the pipe.
Outdoor sensor The outdoor sensor must be attached to a vertical wall with screws and plugs.
Connect the unit before closing the cover. The recommended position is on a wall facing north or north-west, away from unwanted heat sources (fireplace, air vents, thermal bridges, etc.).
-4-
-5-
Connection Determining the type of installation Application 1: 1 underfloor hot water zone, 1 radiator zone (with thermostatically controlled valves)
Application 3: 1 radiator zone (without thermostatically controlled valves), 1 radiator zone (with thermostatically controlled valves)
Outdoor sensor
Outdoor sensor
S
S
Boiler thermostat input control
Zone 2
Room unit in zone 1
Circulator zone 2
Boiler thermostat input control
Zone 2
Room unit in zone 1
Circulator zone 2 Mixer valve
Mixer valve
Zone 1
M
Zone 1
M
S
Feed sensor zone 1
Circulator zone 1 Return sensor zone 2
S
S
Return sensor zone 2
Application 2: 1 underfloor hot water zone
Feed sensor zone 1
Circulator zone 1 S
Application 4: 1 radiator zone (without thermostatically controlled valves)
Outdoor sensor
Outdoor sensor
S
S
Boiler thermostat input control
Boiler thermostat input control Mixer valve
Mixer valve
M
M S
Circulator zone 1
S
Feed sensor zone 1
IMPORTANT: If zone 2 is not used, switch it to Economy mode (with a setting of 10°C). -6-
Circulator zone 1
Feed sensor zone 1
Zone 1 can be fitted with radiators that have thermostatically controlled valves operating as limiters. -7-
Connection The wiring for the boiler thermostat input control is optional. It must be connected if you wish to authorise reductions when the DELTA 200 is not being used for heating.
The diagrams provided are simplified for greater clarity. Protections and other accessories required by standards are not illustrated. - The connection must comply with UTE standard NF C15-100 and good practice. - Nearby units or those that are connected must not generate excessive interference (directive 2004/108/EEC).
• The contact sensor cable is 2.5 m long. • The outdoor sensor can be connected using Ro2V cable (1.5 mm2). • Sensor cables must never be longer than 50 m. • Use an optional rate 3-way mixer valve, equipped with a 24 V or 230 V servomotor. Duration of travel: 60 sec. to 240 sec.
Room unit
To connect it, remove the shunt (electric wires to be wire) connecting the two thermostat input connected to the thermostat terminals. If the boiler has a clock input, do not mistake it for the thermostat input.
Testing the installation
Boiler thermostat input Zone 2 circulator
Zone 1 circulator Mixer valve
M
Before closing the cover of the technical unit: - Switch the installation on, - Check that the green LED comes on (dialogue between the technical unit and the room unit), - Use a temperature setting that is high enough to activate the heating, - The red LEDs indicate the status of the relay outputs: Dialogue
Valve opening
Valve closing
Green LED Zone 1 Valve Network Feed Sensor
Zone 2 Outdoor Direct sensor Network Return Sensor
NTC sensors 10,000 Ohms at 25°C
To room unit
Pwr sup. Op. Cls. 24 V or 230 V valve (2A) Zone 1
Boiler Zone 1 Zone 2 230 V-50 Hz thermostat 230 V (2A) 230 V (2A) Cons. 4 VA input circulator power supply radiator network circulator control 2A
Boiler control
Red LEDs
- Restore the settings required for normal use, - Close the cover of the technical unit.
IMPORTANT : - Before connecting the return sensor for network 2, remove the resistor wired to terminals 3 and 4. - To prevent any confusion when connecting the bus, it is advisable to use a cable of a completely different colour from that used for the unit’s power supply (take care to align the poles properly). - Any junctions or terminal block connections must be made outside the unit. - The underfloor heating system must have a safety device that automatically cuts off the supply of heat to the underfloor heating system when it reaches the limits set by DTU standard 65.8. This underfloor heating security thermostat must be connected in series to the zone 1 circulator. - In this wiring example, the mixer valve is supplied with 230 V power. Some valves may be supplied with 24 V power. If this is the case, you must modify the wiring.
-8-
remove the shunt do not mistake for the clock input (on some boiler models)
-9-
Circulator 2
Circulator 1
Activation Turn the knob to
Menu C03: Setting the minimum water temperature for network 1
.
General principle: In each menu, press the and press to go to the next menu.
or
button to modify,
This is the minimum temperature provided for a heating request from the network. Changes not allowed
Menu C01: Access to program and setting changes To modify settings, press the buttons in the following sequence: times, 3 times, 5 times.
5
Modification of installer settings
Programming limitation
Allowed
No
Access to the installer and programming limitation settings
Not allowed
No
Not allowed
• Programs cannot be modified • The frost protection setting cannot be changed • For each zone, the temperature settings are from 5°C to the Comfort setting
Authorisation to modify the minimum temperature for network 1
Default setting: C03=0 and the temperature set to 20°C. OK
Menu C04 : Réglage de la température d’eau maximum du réseau 1 Changes not allowed Authorisation to modify the maximum temperature of network 1
Default setting: C01=0
Menu C02: Outdoor temperature for no heating Above this temperature, the circulators are off. The boiler thermostat input control is off and the valve is forced to close.
Changes not allowed Authorisation to modify the outdoor temperature for no heating
Changes allowed (from 15°C to 25°C) Upon activation, the temperature is set to 20°C
Default setting: C02=0 and the temperature set to 20°C.
Changes allowed (from 20°C to 60°C) Upon activation, the temperature is set to 20°C
Changes allowed (from network 1 minimum T° + 1°C to 90°C) Upon activation, the temperature is set to 50°C (to match underfloor heating requirements).
IMPORTANT: If you are using underfloor heating, the temperature must not exceed 50°C. When you increase the maximum temperature of network 1 from 50 to 51°C, network 1 acquires the status of a radiator network: - zone 1 automatically goes into Comfort mode from 6am to 11pm for each day of the week, - the slope of zone 1 is initialised at 2. When you decrease the maximum temperature of network 1 from 51 to 50°C, network 1 acquires the status of an underfloor heating network: - zone 1 automatically goes into continuous Comfort mode for each day of the week, - the slope of zone 1 is initialised at 0.8. Default setting: C04=0 and the temperature set to 50°C.
OK
OK
- 10 -
- 11 -
Activation Menu C05: Setting the minimum water temperature for network 2 Zone 2 does not have a room sensor. Adjustments are made using the thermostatically controlled valves. The setting displayed on DELTA 200 is merely theoretical.
Menu C07: Setting the slope of zone 1 (see pg. 14) Changes not allowed Authorisation to change the slope of network 1 (zone 1)
Changes allowed (from 0 to 4 in increments of 0.1) Upon activation, the slope is set to 0.8.
Default setting: C07=0 and the slope is set to 0.8. Changes not allowed Authorisation to modify the minimum temperature for network 2
Changes allowed (from 20°C to 60°C) Upon activation, the temperature is set to 20°C
Changes not allowed Authorisation to change the slope of network 1 (zone 1)
Changes allowed (from 0 to 4 in increments of 0.1) Upon activation, the slope is set to 0.8.
Default setting: C05=0 and the temperature set to 20°C.
Example 1: Setting network 1 for underfloor heating OK
Menu C06: Setting the maximum water temperature for network 2
To determine the correct slope for your installation, on the corresponding axes, note down the maximum feed temperature for network 1 (set in menu C04, e.g. 45°C) and the minimum outdoor base temperature (e.g. -6°C). In this example, the correct slope is 0.9. IMPORTANT: In a few days (if the programming authorises enough comfort periods), DELTA 200 will automatically adapt the slope to the installation settings: this is self-adaptation.
Changes not allowed Authorisation to modify the maximum temperature of network 2
Changes allowed (from network 2 minimum T° + 1°C to 90°C) Upon activation, the temperature is set to 80°C.
Default setting: C06=0 and the temperature set to 80°C.
Example 2: Setting network 1 for radiators
On the corresponding axes, note down the maximum feed temperature for network 1 (set in menu C04, e.g. 75°C) and the minimum outdoor base temperature (e.g. -6°C). In this example, the correct slope is 2.
OK
- 12 -
- 13 -
Activation Example 1: Setting network 1 for underfloor heating Slope 3
Slope 4
Slope 3,5
90
Slope 2
Slope 2,5
Menu C08: Setting the slope of zone 2 Changes not allowed
Slope 1,8
Authorisation to change the slope of network 2 (zone 2)
Slope 1,6 80
Slope 1,4
70
Slope 1,2
Changes allowed (from 0 to 4 in increments of 0.1) Upon activation, the slope is set to 1.
Default setting: C08=0 and the slope set is 1.0. OK
Feed T
Slope 1 60 Slope 0,8 50 Slope 0,6 40
Slope 0,4 Slope 0,2
30
20
20
18
16
14
12
10
8
6
4
2
0
-2
-4
Text
-6
-8
-10
-12
-14
-16
-18
-20
Example 2: Setting network 1 for radiators Slope 3
Slope 4
Slope 3,5
90
Slope 2
Slope 2,5
Slope 1,8 Slope 1,6
Example:
Minimum outdoor base temperature: -6°C Direct radiator network feed temperature: 70°C Determine the temperature drop (Δt) between the network feed and return in accordance with the installation characteristics: e.g. 20°C In this example, the return temperature is estimated to be 50°C. On the corresponding axes, note down the maximum return temperature for network 2 and the minimum outdoor base temperature (e.g. -6°C). In this example, the correct slope is 1. Manual setting: Set the temperature to 20°C on the DELTA 200 and set the thermostatically controlled valves to maximum. For outdoor temperatures of around 10°C, you must obtain 20°C in the room measured. Use a higher slope if the temperature is lower. Use a lower slope if the temperature is higher. Return the thermostatically controlled valves to the desired setting. Slope 3
Slope 4 Slope 1,4
80
Slope 3,5
90
Slope 2
Slope 2,5
Slope 1,8 Slope 1,6
Slope 1,2 70
80
Slope 1,4
70
Slope 1,2
Slope 0,8 Slope 1 50
60
Slope 0,6
40
Slope 0,8
Slope 0,4
50
Slope 0,6
40
Slope 0,4
Slope 0,2 30
20
20
18
16
14
12
10
8
6
4
2
0
Text
-2
-4
-6
-8
-10
-12
-14
-16
-18
-20
Network T
Feed T
Slope 1 60
Slope 0,2 30
20
- 14 -
20
18
16
14
12
10
8
6
4
2
0
-2
- 15 -
-4
-6
-8
-10
-12
-14
-16
-18
-20
Activation Menu C9: Valve operating time Corresponds to the maximum time for the valve to open or close. Changes not allowed Setting the valve operating time (zone 1)
Changes allowed (from 1 to 240 seconds) Upon activation, the time is set to 120 seconds.
Default setting: C09=0 and the time set is 120 seconds. OK
IMPORTANT: To determine the valve operating time, refer to the valve documentation.
Menu C10: Anticipation value of zone 1 Anticipation is the time it takes to reach the desired temperature at the time specified in the program, namely: Tanticipation = (Zone 1 setting - Zone 1 T° as measured) x Setting C10. It keeps the temperature from rising too quickly, which would consume too much energy. Example: You are in economy mode and the room temperature is 17°C. The Comfort temperature setting is 20°C. C10 is set to 30 min/°C. For room temperature to have reached 20°C by the time Comfort mode is programmed to come on, heating will need to begin 1.5 hours in advance: Ta = (20°C - 17°C) x 30 min./°C = 1:30.
Tip: Initially, use the default setting (30 min/°C). - If the desired temperature is reached too quickly, set a higher value (e.g. 45 min./°C). - If the desired temperature is not reached quickly enough, set a lower value (e.g. 20 min./°C). IMPORTANT : If you do not require anticipation, set C10 to 0.
Menu C11: Setting the temperature increase time for zone 2 This is the period during which overpower is used in zone 2 to increase the temperature. The following formula is used when switching from Economy to Comfort mode: Toverpower = setting C11 x (zone 2 setting - outdoor T°) The following formula is used when switching from Shutdown or Frost Protection to Economy or Comfort mode: Tsoverpower = 2 x setting C11 x (zone 2 setting - outdoor T°) Changes not allowed Setting the overpower time for zone 2
Upon activation, the time is set to 5 min./°C.
OK
Menu C12: Control differential for zone 2
Changes not allowed Setting the anticipation time for zone 1
Changes allowed (from 0 to 120 minutes/°C in increments of 5) Upon activation, the time is set to 30 min./°C.
Default setting: C10=0 and anticipation time is set to 30 minutes/°C.
Changes allowed (from 0 to 20 minutes/°C) Upon activation, the time is set to 5 min./°C.
Changes not allowed Setting the control differential for zone 2
Changes allowed (from 0.5°C to 10°C) Upon activation, the temperature is set to 3°C.
Default setting: C12=0 and the differential is set to 3°C. OK
OK
- 16 -
- 17 -
Default setting: C15=0.
Activation Menu C13: Authorising and modifying the access code
OK
Only if DELTA 200 is associated with a TYPHONE 500. No access code (upon activation) Access code authorisation
Code authorised (the code can be modified)
Menu C16: Combining heating with the alarm This menu is displayed if a TYXAL alarm control unit is used with the DELTA 200. Not allowed
Default setting: C13=0. Combining heating with alarm operation
Default setting: C16=1.
OK
For each access code digit, press the press to go to the next digit.
or
Allowed
buttons to modify it and
Menu C14: Language selection Only if DELTA 200 is associated with a TYPHONE 500.
Fully activating the control unit switches the installation into Economy override mode in both zones. Shutting the control unit down switches the installation into Comfort override in both zones (up to the next change of program).
French Language selection
English
Maintenance
Default setting: C14=0.
Diagnosis/Solutions
Menu C15: Correcting the room temperature measurement (zone 1) If there is a difference between the actual temperature (taken with a thermometer) and the temperature measured and displayed by the unit, menu C15 can be used to compensate for the difference (from -4°C to +3.9°C in increments of 0.1°C) by changing the way the sensor measures. No access to correction Correction of the temperature measured in zone 1
Nothing is displayed on the room unit screen.
There is no power supply: Check your circuit breaker or the link with the technical unit
The screen flashes
There has been a lengthy mains power failure. Reset the unit's clock.
The unit displays:
• Communication fault between the room unit and the technical unit • Zone 1 feed sensor fault • Zone 2 return sensor fault
Correction possible
• Outdoor sensor fault Contact your installer.
- 18 -
- 19 -