Transcript
DHP-R&DP Installation instructions Expansion module, HPC EM Cooling module, HPC CM
VMILF102
2 – Danfoss
VMILF102
Table of contents Installation for WCS function (warm water loading) . . . 4 Installation for TWC function (tap water control) . . . . . . 6 Installation for Shunt function . . . . . . . . . . . . . . . . . . . . . . . . 8
Important information! 24 VAC 1 must not be connected together with: ⚠ ⚠ • 24 VAC 2
• 24 VDC
• Other equipment that uses 0-10V control signal
• Signal ground GND
24 VAC 2 must only be used as power supply to: ⚠ ⚠ • External equipment that requires 0-10V control signal
• Auxiliary modules
two separate 24 VAC circuits must never be connected ⚠⚠ Ttoheeach other or to protective ground. he total power load on 24 VAC 1 respectively 24 VAC 2 must ⚠⚠ Tnot exceed 50VA.
VMILF102
Danfoss – 3
Expansion module, HPC EM The operational description for the expansion module is available in the controller manual.
Installation for WCS function (warm water loading) Application The expansion module in WCS operational mode controls warm water loading of the water heaters. WCS operation is achieved by setting the switch according to the figure. Required accessories for installation Submersible sensor, Thermokon-Danelko AKF1004140, item no. 086U3364 One of the following modular cables: Modular cable 0.3 m, item no. 086U4227 Modular cable 1.1 m, item no. 086U4228 Modular cable 10.0 m, item no. 086U4229 Connection block, item no. 086U5121 Other accessories Pilot valve VVL (2-way), heat exchanger (tap water vvx), circulation pump.
System image Heat circuit
Steering valve
Heat exchanger
KV
Circulation pump
VV
Submersible sensor return VVX
VVC
Expansion module WCS operation VVB
VVB
VVB
VVB
Modular cable DHP-R Eco Hot gas circuit Cooling agent circuit
Heat exchanger A heat exchanger is connected between the heat pump and the circulation for the water heaters as depicted in the system image above. Circulation pump A circulation pump is connected near the heat exchanger. Pilot valve A pilot valve is connected between the circulation pump and the heat exchanger. Submersible sensor A submersible sensor is connected on the return line of the heat exchanger, as close to the heat exchanger as possible. 4 – Danfoss
VMILF102
Connecting
⚠⚠Note! The maximum load may not exceed 50 VA. Expansion module The expansion module is mounted in the electric cabinet on the intended rail. If there is no room, the module can be installed in an external, enclosed cabinet and connected with a longer modular cable. • Set the switches on the front of the expansion module to the WCS position
• Connect a modular cable between HP CRM Exp.out and HPC EM Exp.in Circ. pump M
24 VAC 2.1
24 VAC 2.2
DO1.2
Exp.in
DO1.1
From Exp.out
Pilot valve
G G0 Y1 GND
alt.
G G0 Y1
0-10V
AO1
Exp.out
24 VAC 2.1 24 VAC 2.2
T1 T2 AO1 GND
HPC EM WCS
24 VAC 2.1 24 VAC 2.2
Submersible sensor
Connections of expansion module for WCS operation: Temperature input, T1: Submersible sensor (heat exchanger return line) Temperature input, T2: Analogue output 0-10 V, AO1: Signal to pilot valve Relay, DO1: Signal to circulation pump (no-potential closure, maximum 6 A) Exp.in: Connection from HPC RM Exp.out: Connection to possible additional module. Submersible sensor • Connect to T1 and GND
Circulation pump • Connect to DO1.1 to 24 VAC 2.1
• Connect DO1.2 to the contactor coil (the relay coil) and further to 24 VAC 2.2
Pilot valve • Connect AO1 to the signal input of the pilot valve
• Connect GND to pilot valve GND. If GND is missing in the pilot valve, connect GND to 24 VAC 2.2 somewhere in the system. It is most appropriate to jumper terminals 144 and 146 in the controller cabinet.
• Connect the pilot valve terminal G to 24 VAC 2.1 • Connect the pilot valve terminal G0 to 24 VAC 2.2. •
VMILF102
Danfoss – 5
Installation for TWC function (tap water control) Application In the TWC mode, the expansion module ensures that outgoing hot tap waand heat water circulation have a sufficiently high temperature, to prevent the presence of Legionella bacteria.
ter
TWC operation is achieved by setting the switch according to the figure. Required accessories 2 PT1000 strap-on temperature detectors with 2 m of cable, item 086U3365 (item number corresponds to 1 transmitter)
no.
One of the following modular cables: Modular cable 0.3 m, item no. 086U4227 Modular cable 1.1 m, item no. 086U4228 Modular cable 10.0 m, item no. 086U4229 Connection block, item no. 086U5121
System image Heat circuit
KV VV
Sensor, water heater
VVC
Sensor, hot water return
Expansion module TWC function
VVB
VVB
Modular cable
VVB
VVB
Electric cartridge DHP-R Eco Hot gas circuit
Cooling agent circuit
Sensor, water heater A strap-on temperature detector is connected on the supply line lead of the end heater, before the mixing valve. Sensor, hot water return A strap-on temperature detector is connected on the return lead of the warm water circulation, before the circulation pump.
6 – Danfoss
VMILF102
Connecting
⚠⚠Note! The maximum load may not exceed 50 VA. Expansion module The expansion module is mounted in the electric cabinet on the intended rail. If there is no room, the module can be installed in an external, enclosed cabinet and connected with a longer modular cable. • Set the switches on the front of the expansion module to the TWC position
• Connect a modular cable between HP CRM Exp.out and HPC EM Exp.in Start signal for electric cartridge
24 VAC 2.1
24 VAC 2.2
DO1.2
Exp.in
DO1.1
From Exp.out
water heater
HPC EM TWC
T1 T2 AO1 GND
Hot water return
Exp.out
Connections of expansion module for TWC operation: Temperature input, T1: Sensor, water heater Temperature input, T2: Transmitter, hot water return Analogue output 0-10 V, AO1: Relay, DO1: Signal to electric cartridge, hot water (no-potential closure, maximum 6A) Exp.in: Connection from HPC RM Exp.out: Connection to possible additional module. Electric cartridge • Connect to DO1.1 to 24 VAC 2.1.
• Connect DO1.2 to the contactor coil (the relay coil) and further to 24 VAC 2.2.
Sensor, water heater • Connect the sensor cable to T1 and GND.
Sensor, hot water return • Connect the sensor cable to T2 and GND.
VMILF102
Danfoss – 7
Installation for Shunt operation Application In the shunt mode, the expansion module maintains the required temperature for a second heat circuit. The shunt function is achieved by setting the switch according to the figure. Required accessories 1 PT1000 strap-on temperature detector, item no. 086U3365 One of the following modular cables: Modular cable 0.3 m, item no. 086U4227 Modular cable 1.1 m, item no. 086U4228 Modular cable 10.0 m, item no. 086U4229 Connection block, item no. 086U5121 Other accessories Shunt valve, circulation pump.
System image Shunt valve Heat circuit 2
Sensor, shunt temperature Heat circuit 1
Circulation pump KV VV
VVC
Expansion module Shunt function VVB
VVB
VVB
VVB
Cooling agent circuit
Modular cable DHP-R Eco Hot gas circuit
Sensor, shunt temperature A strap-on temperature detector is connected on the supply line of the heat circuit, after the circulation pump.
8 – Danfoss
VMILF102
Connecting
⚠⚠Note! The maximum load may not exceed 50 VA. Expansion module The expansion module is mounted in the electric cabinet on the intended rail. If there is no room, the module can be installed in an external, enclosed cabinet and connected with a longer modular cable. • Set the switches on the front of the expansion module to the Shunt position.
• Connect a modular cable between HP CRM Exp.out and HPC EM Exp.in Circ. pump M
24 VAC 2.1
24 VAC 2.2
DO1.2
Exp.in
DO1.1
From Exp.out
Shunt valve
G G0 Y1 GND
alt.
G G0 Y1
0-10V
AO1
Exp.out
24 VAC 2.1 24 VAC 2.2
T1 T2 AO1 GND
HPC EM Shunt
24 VAC 2.1 24 VAC 2.2
Shunt temperature
Connections of expansion module for shunt operation: Temperature input, T1: Sensor, shunt temperature. Temperature input, T2: Analogue output 0-10 V, AO1: Signal to shunt valve. Relay, DO1: Signal to circulation pump (no-potential closure, maximum 6A). Exp.in: Connection from HPC RM. Exp.out: Connection to possible additional module. Sensor, shunt temperature • Connect to T1 and GND
Circulation pump • Connect to DO1.1 to 24 VAC 2.1.
• Connect DO1.2 to the contactor coil (the relay coil) and further to 24 VAC 2.2.
Shunt valve • Connect AO1 to the signal input of the pilot valve.
• Connect GND to pilot valve GND. If GND is missing in the pilot valve, connect GND to 24 VAC 2.2 somewhere in the system. It is most appropriate to jumper terminals 144 and 146 in the controller cabinet.
• Connect the pilot valve terminal G to 24 VAC 2.1. • Connect the pilot valve terminal G0 to 24 VAC 2.2.
VMILF102
Danfoss – 9
Inputs and outputs, HPC EM Temperature inputs
Input
Shunt
TWC
WCS
T1
Shunt temperature
HW heater temp
WCS temperature
T2
–
HW return temp
–
Outputs
Shunt
TWC
WCS
AO1
Control signal
–
Control signal
Outputs
Shunt
TWC
WCS
DO1
Circulation pump
Heater HW
Circulation pump
Analogue outputs
Relay outputs
10 – Danfoss
VMILF102
Cooling module, HPC CM The operational description for the cooling module is available in the controller manual.
Installation Application The cooling module controls the temperature of a cooling using a pilot valve. The cold is collected from a cooling tank, which is cooled with active or passive cold. Passive cold means that cooling agent fluid is circulated through the drill hole and the cooling tank, without activation of any heating pump. Only circulation pumps for cooling agents are used. The heat from the cooling tank is transported down into the mountain. An assumption for passive cooling to work is that the cooling agent fluid is colder than the cooling tank. Active cooling means that a heat pump is activated to lower the temperature of the cooling agent, before it is transferred into the cooling tank. If the cooling integral continues to rise, more heat pumps are started. The valve for active cooling changes its mode and disconnects the drill hole. Therefore, the cooling agent only circulates through the cooling tank and heat pump, so that all the produced cold can be collected. Additionally, a dew point control function can be activated in the cooling module. This function is not necessary, but if it is used a dew point sensor must be connected. Surplus heat produced during active cooling can either be returned to the drill hole or cooled in a coolant cooler. If a coolant cooler is used, a temperature sensor is connected for the cooler and the coolant module then controls the cooling fans.
Required accessories 4 PT1000 contact strap-on temperature detector with 2 m of cable, item no. 086U3365 (item number corresponds to 1 detector) One of the following modular cables: Modular cable 0.3 m, item no. 086U4227 Modular cable 1.1 m, item no. 086U4228 Modular cable 10.0 m, item no. 086U4229 Connection block, item no. 086U5121 Dew point sensor for wall mounting, item no. 086U3396 (if the dew point function is used)
VMILF102
Danfoss – 11
System image Heat circuit
Circulation pump Coolant cooler Dew point sensor
Reversing valve surplus heat
Cooling fan
Sensor, cooling tank outlet Sensor, coolant cooler Pilot valve cooling circuit Cooling circuit
Cooling tank
Sensor, cooling tank Sensor, cooling circuit
Cooling module DHP-R Eco
Circulation pump cooling circuit
Modular cable
Reversing valve, cooling tank Cooling agent circuit
Reversing valve cooling agent return
Transmitter, cooling tank A strap-on temperature detector is connected on the cooling tank at about a third of the tank’s height. Transmitter, cooling circuit A strap-on temperature detector is connected on the supply line of the cooling circuit, after the circulation pump. Transmitter, cooling tank outlet A strap-on temperature detector is connected on the return line of the cooling tank. Transmitter, coolant cooler A strap-on temperature detector is connected on the return line from the coolant cooler, as close to the cooler as possible.
12 – Danfoss
VMILF102
Connecting
⚠⚠Note! The maximum load may not exceed 50 VA. Cooling module The cooling module is mounted in the electric cabinet on the intended rail. If there is no room, the module can be installed in an external, enclosed cabinet and connected with a longer modular cable.
• Connect a modular cable between HP CRM Exp.out and HPC CM Exp.in
Pilot valve, alternative connection of cooling circuit
Pilot valve, cooling circuit
Dew point sensor
24 VAC 2.1 24 VAC 2.2
G G0 Y1 GND
G G0 Y1
24 VAC 2.1 24 VAC 2.2
Room temperature
Sensor, cooling circuit Sensor, cooling tank outlet Sensor, surplus cooler
24 VAC 2.1 24 VAC 2.2 AO1
Relative air humidity
Cooling fans Y1 GND
0-10V
Sensor, cooling tank 0-10V
AO2
GND
AO1
GND
AI2
GND
GND
AI1
GND
T4
GND
T3
GND
T2
Exp.out
T1
Exp.in
GND
From Exp.out
G0
DO5
G0
DO4
G0
DO3
G0
DO2
G0
DO1
G0
24VAC
HPC CM
24 VAC 2.1 24 VAC 2.2 DO1,2,4 24 VAC
24 VAC
24 VAC
24 VAC
24 VAC
24 VAC 2.1 24 VAC 2.2
Alternative connection with constant voltage feed for 2-point 24 VAC reversing valve.
M
cooling tank
Cooling module connections: Temperature input, T1: Sensor, cooling tank
Reversing valve, cooling agent return
Circ. pump, coolant cooler
M
Reversing valve, surplus heat
Circ. pump, coolant circuit
Temperature input, T2: Sensor, coolant cooler Temperature input, T3: Sensor, cooling tank outlet Temperature input, T4: Sensor, cooling circuit Analogue input 0-10 V, AI1: Signal from dew point sensor, room temperature 0 - 50°C Analogue input 0-10 V, AI2: Signal from dew point sensor, relative humidity 0-100% Analogue output 0-10 V, AO1: Signal to cooling circuit pilot valve Analogue output 0-10 V, AO2: Signal to cooling fans Relay 24 VAC, DO1: Signal to reversing valve against cooling tank (passive cold) VMILF102
Danfoss – 13
Relay 24 VAC, DO2: Signal to reversing valve against cooling agent return (active cold) Relay 24 VAC, DO3: Signal to coolant cooler circulation pump Relay 24 VAC, DO4: Signal to reversing valve, surplus heat Relay 24 VAC, DO5: Signal to cooling circuit circulation pump
Transmitter, cooling tank • Connect to T1 and GND
Transmitter, coolant cooler • Connect to T2 and GND
Transmitter, cooling tank outlet • Connect to T3 and GND
Transmitter, cooling circuit • Connect to T4 and GND
Dew point sensor • Connect to 24 VAC 2.1 and 24 VAC 2.2
• Connect room temperature sensor to AI1 and GND • Connect relative air humidity sensor to AI2 and GND
Pilot valve, cooling circuit • Connect AO1 to the signal input of the pilot valve
• Connect GND to pilot valve GND • Connect the pilot valve terminal G to 24 VAC 2.1 • Connect the pilot valve terminal G0 to 24 VAC 2.2
Cooling fans • Connect AO2 to the signal input of the cooling fan
• Connect GND to the cooling fan GND
Voltage feed to DO output terminals • Connect 24 VAC to 24 VAC 2.1
• Connect G0 to 24 VAC 2.2
Reversing valve, cooling tank • Connect start relay to DO1 and G0
Reversing valve, cooling agent return • Connect start relay to DO2 and G0
Circulation pump, coolant cooler • Connect start relay to DO3 and G0
Reversing valve, surplus heat • Connect start relay to DO4 and G0
Circulation pump, cooling circuit • Connect start relay to DO5 and G0
Alternative connection of reversing valves: When constant voltage feed to a reversal valve’s 2-point 24 VAC adjuster is required, establish direct connection to 24 VAC 2.1 and 24 VAC 2.2. A start relay is not necessary when using a 2-point 24 VAC actuator. Connect the control signal to the corresponding digital output terminal, DO1, DO2 or DO4.
14 – Danfoss
VMILF102
Inputs and outputs, HPC CM Temperature inputs
Input
Use
Measurement range
T1
Temperature cooling tank
-30 to 70 °C
T2
Temp coolant cooler
-30 to 70 °C
T3
Temp outlet cooling tank
-30 to 70 °C
T4
Temp cooling circuit
0 to 100 °C
Analogue inputs
Input
Use
AI1
Room temperature 0 to 50 °C
AI2
Relative humidity 0 to 100 %
Analogue outputs
Outputs
Use
AO1
Control valve cooling circuit
AO2
Cooling fans
Relay outputs
Outputs
Use
DO1
Valve passive cooling (Exchange valve brine to tank) 24 VAC
DO2
Valve active cooling 24 VAC
DO3
Circulation pump surplus cooler 24 VAC
DO4
Valve surplus heat 24 VAC
DO5
Circulation pump cooling circuit 24 VAC
VMILF102
Danfoss – 15
VMILF102