Transcript
Digital I/O Module Engineering Information
I/O MODULES Our line of pluggable input and output modules provide a low cost, versatile method for interconnecting real world analog and digital signals to data acquisition, monitoring, or control systems. All modules provide an optically isolated barrier between sensitive microprocessor or digital logic circuits and field power devices. In the G5 and OpenLine® packages, analog and digital I/O modules are available with the same pin-out. This gives the flexibility of mixing and matching module types on the same mounting rack or base; making them perfect in applications which require interface to a variety of different sensors and loads. The case color of the single point modules identify their function. The industry standard for single point I/O module case colors is: Digital AC Output Module = Black Case Digital DC Output Module = Red Case Digital AC Input Module = Yellow Case Digital DC Input Module = White Case
DIGITAL OUTPUT MODULES Digital output modules are used to switch AC and DC loads such as solenoids, motors, or lamps from logic signal levels. Their inputs are directly compatible with TTL or CMOS interface circuitry. AC output modules have zero voltage turn-on of the load to greatly reduce generated EMI and RFI. They are highly immune to electrical
transients, and have built-in RC snubber networks for increased capability with inductive loads. DC output modules can operate DC loads over a wide voltage range and have built-in voltage spike protection.
DIGITAL INPUT MODULES Digital input modules are used to monitor the status of a load or a sensor (such as a limit switch, pressure switch, or temperature switch). The output of these modules is a logic level signal which corresponds to the status of the device being monitored. A high level output signal indicates the load is off (the switch is open). A low level output signal indicates the load is on (the switch is closed). Input modules are designed to give fast, clean switching by providing filtering and hysteresis. Input and output modules are compatible in that the output of one can drive the input of the other.
UL, CSA AND CE APPROVALS As one of the world's leading manufacturers of I/O modules, we strive to assure that our products comply with all of the applicable international standards. In doing so, we believe your products will also be readily accepted and easily certified. All modules shown in this section have been tested to UL Standard 508 and are documented in UL file number E58632. Similarly, they have been tested to CSA
Standard 22.2 No. 14-95M and are documented in CSA file LR38763. Additionally, OpenLine® modules were tested and passed CSA 22.2 No. 213-M1987 Class I, Div. 2 Groups A, B, C and D. Parts bearing the CE logo indicate conformance with EN50082-2 and EN50081-2 (89/336/EEC EMC directive) as well as EN60950 (61010-1) for the low voltage directive. Contact Grayhill for copies of our Declaration of Conformity or visit out website. Parts bearing the TÜV logo indicate that they were the agency which performed the EN60950 evaluation.
CONSTRUCTION AND LIFETIME WARRANTY All of our I/O modules are hard potted with thermally conductive epoxy to withstand harsh industrial environments. The modules provide optical isolation, immunity to mechanical shock and vibration, and operate over a wide temperature range. The module cases are a solvent resistant thermoplastic which meets UL94-V-0 rating. The terminal pins are a tinplated copper wire. Component selection and surface mount construction allow low operating junction temperatures for long life. Superior design, rigorous testing, and field data give us the confidence to back our I/O modules with the industry's first lifetime warranty.
I/O MODULE WIRING Analog and digital modules can be placed at any I/O location, however, to minimize the possibility of crosstalk and noise pickup it is a good practice to group similar module types together. 14 or 16 gauge wire is typically used to wire the field devices to the I/O rack terminal block.
PART NUMBER EXPLANATION: Digital I/O Modules
I/O Modules
Module Type 70 = Digital Module, Standard Package 70G = Digital Module, G5 Package 70L = Digital Module, OpenLine® Package 70M = Digital Module, Mini Package
70M-ODC5A
Function OAC = ODC = IAC = IDC =
Digital Output AC Digital Output DC Digital Input AC Digital Input DC
Suffix AC Inputs: DC Inputs:
AC Outputs: DC Outputs:
Blank = 120 Vac Blank = 3-32 Vdc G = 35-60 Vac/Vdc L = Inductive loads
A = 220 Vac B = Fast Switching D = 2.5–28 Vdc S = Dry Contacts
Blank = 120 Vac MA = 120 Vac, Manual Override AMA = 240 Vac, Manual Override Blank = 3-60 Vdc Fast MA = 3-60 Vdc, Manual Override
NP = 15-32 Vac/10-32 Vdc K = 2.5-16 Vdc
A = 220 Vac A-11 = Non-Zero Cross A-5 = Normally Closed A = 4-200 Vdc R = Dry Contact B = 3-60 Vdc, Low Leakage
Logic Supply Voltage or Range Digital Modules: Blank = 4.5-28 Vdc (OpenLine®) 5 Vdc, 15 Vdc, 24 Vdc = Logic Supply Voltage (Standard, Mini, G5) Analog Modules: 4.75-5.25 Vdc
H-3
Grayhill, Inc. • 561 Hillgrove Avenue • LaGrange, Illinois
60525-5997 • USA • Phone: 708-354-1040 • Fax: 708-354-2820 • www.grayhill.com
Digital I/O Modules Engineering Information
DIMENSIONS: OpenLine® Digital Modules Dimensions shown in inches (and millimeters). Tolerances are ± .010 (0,25) unless indicated otherwise.
Module Type I/O Module Pin # 1 2 3 4 5 6 7 8 9
Output Function Output A+ Output AOutput B+ Output BLogic Gnd Vcc Ch. A Input Ch. B Input Module ID
Input Function Input A+ Input AInput B+ Input BLogic Gnd Vcc Ch. A Status Ch. B Status Module ID
FUSE HOLDERS (OUTPUTS ONLY)
GREEN STATUS LEDS
DATE CODE
.025 (0,635) SQ. .34 (8,64)
.51 (12,95)
2.09 (53,09) .19 (4,83)
.03 (0,76)
.10 (2,54)
.22 (5,59)
PIN 9 PIN 8 PIN 7 PIN 6 PIN 5
PIN 4
PIN 3 PIN 2 PIN 1
.14 (3,56)
2.49 (63,25) 2.23 (56,64)
.38 (9,65)
.24 (6,10) 2.70 (68,58)
Note: For PC board layout information, request Bulletin #745
DIMENSIONS: G5 Digital Modules Dimensions shown in inches (and millimeters). Tolerances are ± .010 (0,25) unless indicated otherwise. Input Modules
Ouput Modules
1.90 (48,3)
1.90 (48,3)
.46 (11,7)
.46 (11,7)
GREEN STATUS LED
I/O Modules
GREEN STATUS LED
FUSE HOLDER
4-40 X 2-1/2" PHILLIPS HOLDDOWN SCREW INCLUDED WITH EACH MODULE MAXIMUM TORQUE = 5 FT-LB 2.55 (64,8) 2.20 (55,9)
5 4 3
2
1
2.20 (55,9)
O .040/.042 (1,02/1,07)
.235 (5,97)
4 3
2
.20 (5,1)
1.15 (29,2) 1.35 (34,3)
.235 (5,97) .20 (5,1)
.40 (10,2) .90 (22,9)
1
O .040/.042 (1,02/1,07)
.40 (10,2) .20 (5,1) .15 (3,8)
.90 (22,9) 1.15 (29,2)
.20 (5,1) .15 (3,8)
1.35 (34,3)
1.55 (39,4)
Grayhill, Inc. • 561 Hillgrove Avenue • LaGrange, Illinois
60525-5997 • USA • Phone: 708-354-1040 • Fax: 708-354-2820 • www.grayhill.com
H-4
Digital I/O Modules Engineering Information
DIMENSIONS: Standard and Miniature Digital Modules Dimensions shown in inches (and millimeters). Tolerances are ± .010 (0,25) unless indicated otherwise. Standard Module
Miniature Module
1.00 (25,4)
.60 (15,2)
.40 (10,2)
4–40 X 1-1/2" PHILLIPS HOLDDOWN SCREW INCLUDED WITH EACH MODULE MAXIMUM TORQUE = 5 FT-LB 1.70 (43,2)
1.70 (43,2)
1.25 (31,8)
5 4 3
2
Ø .040/.042 (1,02/1,07)
.235 ± .02 (6,0 ± 0,52)
1
1.00 (25,4)
5 4 3
2
Ø .040/.042 (1,02/1,07)
1
.20 (5,1)
.235 ±.020 (6,0 ± 0,52)
.30 (7,6)
.30 (7,6)
.30 (7,6) .10 (2,5)
.40 (10,2) .90 (22,9) 1.10 (27,9) 1.30 (33,0)
.40 (10,2) OUTPUT MODULES HAVE ONLY TERMINALS NUMBER 1-4
.90 (22,9) 1.10 (27,9) 1.30 (33,0)
OUTPUT MODULES HAVE ONLY TERMINALS NUMBER 1-4
WIRING DIAGRAM: Digital I/O Modules DIGITAL AC OUTPUT
I/O Modules
H-5
LOAD 2
1
DIGITAL DC OUTPUT
2
1
DIGITAL AC INPUT
2
1
DIGITAL DC INPUT
2
1
DIGITAL CONTACT CLOSURE
2
LOAD
HOT AC SUPPLY NEUTRAL
+ DC SUPPLY
–
HOT AC SUPPLY NEUTRAL
+ DC SUPPLY
–
1
Grayhill, Inc. • 561 Hillgrove Avenue • LaGrange, Illinois
60525-5997 • USA • Phone: 708-354-1040 • Fax: 708-354-2820 • www.grayhill.com
AC Output Modules
FEATURES • Transient Protection: Meets the requirements of IEEE 472, “Surge Withstanding Capability Test” • SPST, Normally Open • Zero Crossing Turn-On • UL, CSA, CE, TÜV Certified • Optical Isolation • OpenLine® and G5 Modules Provide Replaceable 5x20 mm Glass Fuses • Built-in Status LED • Lifetime Warranty
••
TUV R h e i n l a n d
70L-OAC
70G-OAC
70-OAC
70M-OAC 4 LOAD CURRENT (AMPS)
Maximum Current Versus Ambient Temperature The chart indicates continuous current to limit the junction temperatures to 100°C. Information is based on steady state heat transfer in a 2 cubic foot sealed enclosure.
3 2
STANDARD, G5 PACKAGES MINIATURE PACKAGE
DIMENSIONS For complete dimensional drawings, see pages H-4 or H-5.
OPENLINE PACKAGE/CH
1
FUSES
-40˚
G5 Fuses are 5 Amp Littelfuse part number 217005 or equivalent. OpenLine® fuses are 3.15 Amp Littelfuse part number 217315.
-20˚
0 20˚ 40˚ 60˚ 80˚ AMBIENT TEMPERATURE (˚C)
100˚
Fuse kits available, see page H-106.
Figure 1
CIRCUITRY Standard, Mini, G5 LOAD
OpenLine
TYPICAL WIRING FOR MODULE 0 SNUBBER 2
GND
5
Vcc
6
CHANNEL A
A TRIGGER CIRCUIT
CH. A CONTROL
Rx
OPTICAL ISOLATION
CH. B CONTROL
3
1
1
2
2
3
3
4
4
LOAD
SNUBBER
SNUBBER
LOAD
CHANNEL B
DC CONTROL
–
OPTICAL ISOLATION
7
B
+
I/O MODULE PIN #
1
VAC LOAD
®
2.15K
4
MODULE ID
RACK OR BASE
MODULE
Fuse and status LED in G5 and OpenLine modules only.
TERMINAL BLOCK #
I/O Modules
SPECIFICATIONS: By Package Style Package Style Specifications Load Current Range Maximum 1 Cycle Surge2 Maximum Turn-On-Time (60 Hz)3 Maximum Turn-Off Time (60 Hz) Static dv/dt7 Typ. Power Dissipation Isolation Voltage4 Vibration5 Mechanical Shock6 Storage Temp. Range Operating Temp. Range Warranty 2
3 4 5 6 7
Mini (70M-)
G5 (70G-)
OL (70L-)
0.03 to 3.5 80 8.33 8.33 3000 1.0 4000 MIL-STD-202 MIL-STD-202 -40 to 125 -40 to 100 Lifetime
0.03 to 3.0 80 8.33 8.33 3000 1.0 4000 MIL-STD-202 MIL-STD-202 -40 to 125 -40 to 100 Lifetime
0.03 to 3.5 80 8.33 8.33 3000 1.0 4000 MIL-STD-202 MIL-STD-202 -40 to 125 -40 to 100 Lifetime
0.03 to 2.0/CH 30 8.33 8.33 3000 1.0 2500 IEC68-2-6 IEC68-2-27 -40 to 100 -40 to 85 Lifetime
Units 1
1
Std (70-)
A rms A rms mSec mSec V/µsec W/A V rms °C °C
See Figure 1 for derating. Maximum 10 cycle surge is 50% of 1 cycle surge. Application of maximum surge may not be repeated until module temperature has returned to its steady state value. Except 70-OAC5A5 which is 200 µSec and 70-OAC5A-11, 70M-OAC5A-11, and 70G-OAC5A-11 which are 100 µSec. Field to logic and channel-to-channel if Grayhill racks are used. MIL-STD-202, Method 204, 20 , 10-2000 Hz or IEC68-2-6, 0.15 mm/sec2, 10-150 Hz. MIL-STD-202, Method 213, Condition F, 1500G or IEC68-2-27, 11 mS, 15g. Except part numbers with -L suffix which have a dv/dt rating of 200 V/µSec.
H-7
Grayhill, Inc. • 561 Hillgrove Avenue • LaGrange, Illinois 60525-5997 • USA • Phone: 708-354-1040 • Fax: 708-354-2820 • www.grayhill.com
AC Output Modules
SPECIFICATIONS: By Part Number Standard and Miniature Modules Type/Function
Grayhill Part Number
Miniature, Normally Open, Random Turn-on
70M-OAC5A-11
Miniature, Normally Open, Zero Voltage Turn-on (ZVT)
70M-OAC5
70M-OAC5A
Miniature, Normally Open, ZVT, Inductive Load
70M-OAC5-L
70M-OAC5A-L
Standard, Normally Closed, Random Turn-on
70M-OAC15A
70M-OAC24
70M-OAC24A
70-OAC15
70-OAC15A
70-OAC24
70-OAC24A
120 24-140 400 2 24 15-30 9 2700 1 -5
240 24-280 600 4 24 15-30 9 2700 1 -5
70G-OAC24
70G-OAC24A
70-OAC5A5
Standard, Normally Open, Random Turn-on
70-OAC5A-11
Standard, Normally Open, ZVT Standard, Normally Open, ZVT, Inductive Load Specifications Nominal Line Voltage Load Voltage Range Minimum Peak Blocking Voltage Maximum Off-state Leakage @ 60Hz Nominal Logic Voltage (Vcc) Logic Voltage Range Max. Logic Supply Current @ Nominal Vcc Nominal Input Resistance (Rx) Minimum Drop Out Voltage Maximum Reverse Logic Voltage
70M-OAC15
Units Vac Vac Volts mA, rms Vdc Vdc mA Ω Vdc Vdc
70-OAC5
70-OAC5A
70-OAC5-L
70-OAC5A-L
120 24-140 400 2 5 2.5-10 16 240 1 -5
70-OAC24A-11
240 24-280 600 4 5 2.5-10 16 240 1 -5
120 24-140 400 2 15 10-18 9 1800 1 -5
240 24-280 600 4 15 10-18 9 1800 1 -5
G5 Modules Grayhill Part Number
Type/Function G5 Fusible, Normally Open, ZVT
70G-OAC5
G5 Fusible, Normally Open, ZVT, Inductive Load
70G-OAC5-L 70G-OAC5A-L
G5 Fusible, Normally Open, Random Turn-on Specifications
70G-OAC5A
70G-OAC15
70G-OAC15A
70G-OAC15-L 70G-OAC15A-L 70G-OAC24-L
70G-OAC24A-L
70G-OAC5A-11 Units
Nominal Line Voltage Load Voltage Range Minimum Peak Blocking Voltage Maximum Off-state Leakage @ 60Hz Nominal Logic Voltage (Vcc) Logic Voltage Range Max. Logic Supply Current @ Nominal Vcc Nominal Input Resistance (Rx) Minimum Drop Out Voltage Maximum Reverse Logic Voltage
Vac Vac Volts mA, rms Vdc Vdc mA W Vdc Vdc
120 24-140 400 2 5 4-6 20 100 1 -5
240 24-280 600 4 5 4-6 20 100 1 -5
120 24-140 400 2 15 8-20 12 1000 1 -5
240 24-280 600 4 15 8-20 12 1000 1 -5
120 24-140 400 2 24 18-32 8 2700 1 -5
240 24-280 600 4 24 18-32 8 2700 1 -5
Type/Function
Grayhill Part Number
Dual, Fusible, Normally Open, ZVT Dual, Fusible, Normally Open, ZVT, Inductive Load Specifications
Units
Nominal Line Voltage Load Voltage Range Minimum Peak Blocking Voltage Maximum Off-State Leakage @ 60 Hz Nominal Logic Voltage Logic Voltage Range Max. Logic Supply Current @ Nominal Vcc Module ID Resistance to Logic Ground Minimum Drop Out Voltage
Vac Vac Volts mA, rms Vdc Vdc mA Ω Vdc
70L-OAC
70L-OACA
70L-OAC-L
70L-OACA-L
120 24-140 600 2 5 4.5-28 7/CH 2.15K 1
240 24-280 600 4 5 4.5-28 7/CH 2.15K 1
Available from your local Grayhill Distributor. For prices and discounts, contact a local Sales Office, an authorized local Distributor or Grayhill.
Grayhill, Inc. • 561 Hillgrove Avenue • LaGrange, Illinois 60525-5997 • USA • Phone: 708-354-1040 • Fax: 708-354-2820 • www.grayhill.com
H-8
I/O Modules
OpenLine® Modules
DC Output Modules
FEATURES • Transient Protection: Meets the requirements of IEEE 472, "Surge Withstanding Capability Test" • SPST, Normally Open • UL Recognized, CSA Certified, CE Mark, TÜV (see Engineering Information) • Optical Isolation • OpenLine® and G5 Modules Provide Replaceable 5 x 20 mm Glass Fuse • Built-in Status LED • Lifetime Warranty
••
TUV R h e i n l a n d
70L-ODC
70G-ODC
70-ODC
70M-ODC
4 LOAD CURRENT (AMPS)
Maximum Current Versus Ambient Temperature The chart indicates continuous current to limit the junction temperatures to 115°C. Information is based on steady state heat transfer in a 2 cubic foot sealed enclosure.
3 2 1
DIMENSIONS
STANDARD, G5 PACKAGES
For complete dimensional drawings, see pages H-4 or H-5.
MINIATURE PACKAGE
OPENLINE PACKAGE/CH
FUSES G5 Fuses are 5 Amp Littelfuse part number 217005 or equivalent. OpenLine® fuses are 3.15 Amp Littelfuse part number 217315.
200 VDC STYLE
-40˚
-20˚
0 20˚ 40˚ 60˚ 80˚ AMBIENT TEMPERATURE (˚C)
OpenLine ®
Standard, Mini, G5 LOAD
VOLTAGE SPIKE PROTECTION LOAD
GND 5 Vcc 6
CHANNEL A
A
2
CH. A CONTROL 7
OPTICAL ISOLATION
DRIVER CIRCUIT
DRIVER CIRCUIT OPTICAL ISOLATION
–
1
1
LOAD
2
2
DC SUPPLY
3
3
DC SUPPLY
4
4
LOAD
DRIVER CIRCUIT
CHANNEL B
CH. B 8 CONTROL
Rx 3
–
I/O Modules
2.15K
DC CONTROL
–
+
+ B
+
I/O MODULE PIN #
TYPICAL WIRING FOR MODULE 0
1
VDC
–
Fuse kits available, see page H-106.
Figure 1
CIRCUITRY +
100˚
MODULE ID 9
4
BASE OR RACK
Fuse and status LED in G5 and OpenLine modules only.
TERMINAL BLOCK #
SPECIFICATIONS: By Package Style Package Style Specifications Load Current Range Surge Current for 1 Sec. Maximum Reverse Logic Voltage Isolation Voltage2 Vibration3 Mechanical Shock4 Storage Temp. Range Operating Temp. Range Warranty 2 3 4
Mini (70M-)
G5 (70G-)
OL (70L-)
0.02-3.5 5 -5 4000 MIL-STD-202 MIL-STD-202 -40 to 125 -40 to 100 Lifetime
0.02-3.0 5 -5 4000 MIL-STD-202 MIL-STD-202 -40 to 125 -40 to 100 Lifetime
0.02-3.5 5 -5 4000 MIL-STD-202 MIL-STD-202 -40 to 125 -40 to 100 Lifetime
0.02-2.0/CH 5 -5 2500 IEC68-2-6 IEC68-2-27 -40 to 100 -40 to 85 Lifetime
Units 1
1
Std (70-)
A A Vdc Vrms
°C °C
See Figure 1 for derating. Field to logic and channel-to-channel if Grayhill racks are used. MIL-STD-202, Method 204, 20 G, 10-2000 Hz or IEC68-2-6, 0.15 mm/sec2, 10-150 Hz. MIL-STD-202, Method 213, Condition F, 1500 G or IEC68-2-27, 11 mS, 15g.
H-9
Grayhill, Inc. • 561 Hillgrove Avenue • LaGrange, Illinois
60525-5997 • USA • Phone: 708-354-1040 • Fax: 708-354-2820 • www.grayhill.com
DC Output Modules
SPECIFICATIONS: By Part Number Standard and Miniature Modules Type/Function
Grayhill Part Number
Miniature, Normally Open Standard, Normally Open
70M-ODC5 70M-ODC5A 70M-ODC5B 70M-ODC15 70-ODC5 70-ODC5A 70-ODC5B 70-ODC15
70M-ODC15B 70-ODC15B
70M-ODC24 70M-ODC24B 70-ODC24 70-ODC24B
Specifications
Units
Maximum Line Voltage Load Voltage Range Max. Off-State Leakage @ Max. Line Maximum Turn-On Time Maximum Turn-Off Time Typ. Power Dissipation Clamping Voltage Nominal Logic Voltage (Vcc) Logic Voltage Range Maximum Logic Supply Current @ Nominal Vcc Nominal Input Resistance (Rx) Minimum Drop Out Voltage
Vdc Vdc mA µSec µSec W/A Vdc Vdc Vdc
60 3-60 1.5 20 50 1 80 5 2.5-10
200 4-200 0.01 75 750 1.5 360 5 2.5-9
60 3-60 0.01 75 500 1 80 5 2.5-10
60 3-60 1.5 20 50 1 80 15 10-18
60 3-60 0.01 75 500 1 80 15 10-18
60 3-60 1.5 20 50 1 80 24 15-30
60 3-60 0.01 75 500 1 80 24 15-30
mA Ω Vdc
14 300 1
18 220 1
14 300 1
9 1800 1
9 1800 1
9 2700 1
9 2700 1
G5 and OpenLine® Modules Grayhill Part Number
Type/Function Fusible, Normally Open Specifications
70G-ODC5
70G-ODC5A
70G-ODC5B
70G-ODC15
70G-ODC15B
70G-ODC24
70G-ODC24B
Units
Maximum Line Voltage Load Voltage Range Max. Off-State Leakage @ Max. Line Maximum Turn-On Time Maximum Turn-Off Time Typ. Power Dissipation Clamping Voltage Nominal Logic Voltage (Vcc) Logic Voltage Range Maximum Logic Supply Current @ Nominal Vcc Nominal Input Resistance (Rx) Minimum Drop Out Voltage
Vdc Vdc mA µSec µSec W/A Vdc Vdc Vdc
60 3-60 1.5 20 50 1 80 5 4-6
200 4-200 0.01 75 750 1.5 360 5 4-6
60 3-60 0.01 75 500 1 80 5 4-6
60 3-60 1.5 20 50 1 80 15 10-20
60 3-60 0.01 75 500 1 80 15 10-20
60 3-60 1.5 20 50 1 80 24 18-32
60 3-60 0.01 75 500 1 80 24 18-32
mA Ω Vdc
13 150 1
13 150 1
13 150 1
9 1500 1
9 1500 1
9 2700 1
9 2700 1
OpenLine® Modules Type/Function
Grayhill Part Number 70L-ODC
70L-ODCA
70L-ODCB
Specifications
Units
Maximum Line Voltage Load Voltage Range Max. Off-State Leakage @ Max. Line Maximum Turn-On Time Maximum Turn-Off Time Typ. Power Dissipation Clamping Voltage Nominal Logic Voltage (Vcc) Logic Voltage Range Maximum Logic Supply Current @ Nominal Vcc Module ID Resistance to Logic Ground Minimum Drop Out Voltage
Vdc Vdc mA µSec µSec WA Vdc Vdc Vdc
60 3-60 1.5 20 50 1 80 5 4.5-28
200 4-200 .01 75 750 1.5 360 5 4.5-28
60 3-60 .01 75 500 1 80 5 4.5-28
mA
7/CH
7/CH
7/CH
Ω Vdc
2.15K 1
2.15K 1
2.15K 1
Grayhill, Inc. • 561 Hillgrove Avenue • LaGrange, Illinois
60525-5997 • USA • Phone: 708-354-1040 • Fax: 708-354-2820 • www.grayhill.com
H-10
I/O Modules
Dual, Fusible, Normally Open
Available from your local Grayhill Distributor. For prices and discounts, contact a local Sales Office, an authorized local Distributor or Grayhill.
AC Input Modules
FEATURES • Transient Protection: Meets the requirements of IEEE 472, “Surge Withstanding Capability Test” • UL, CSA, CE, TÜV Certified (TÜV not available on OpenLine) • Optical Isolation • OpenLine ® and G5 Modules have Built-in Status LED • Lifetime Warranty
••
TUV R h e i n l a n d
70L-IAC
70G-IAC
70-IAC
70M-IAC
DIMENSIONS For complete dimensional drawings, see pages H-4 or H-5.
CIRCUITRY OpenLine®
Standard, Mini, G5 I/O MODULE PIN #
Rx 1
TYPICAL WIRING FOR MODULE 70
VDC
6
Vcc
7
CH. A STATUS
5
GND
8
CH. B STATUS
9
MODULE ID
A 2
INPUT DEVICE
1
1
FILTER OPTICAL ISOLATION
+VCC 3
INPUT VOLTAGE HYST. CIRC.
INPUT DEVICE
CURRENT REGULATING
OUTPUT
2
2
3
3
OPTICAL ISOLATION
4
4
GROUND
TERMINAL BLOCK #
5
B
FILTER
*
HYSTERESIS
HYSTERESIS
4 BASE OR RACK
Status LED in G5 modules only.
0Ω
MODULE
* Separate supplies may also be used.
SPECIFICATIONS: By Package Style I/O Modules
Package Style
1 2 3
Specifications
Units
Output Current Range Minimum Output Breakdown Voltage Maximum Turn-On Time Maximum Turn-Off Time Isolation Voltage 1 Vibration2 Mechanical Shock3 Storage Temp. Range Operating Temp. Range Warranty
mA Vdc mS mS Vrms
°C °C
Std (70-)
Mini (70M-)
G5 (70G-)
OL (70L-)
1-50 50 20 20 4000 MIL-STD-202 MIL-STD-202 -40 to +125 -40 to +100 Lifetime
1-50 50 20 20 4000 MIL-STD-202 MIL-STD-202 -40 to +125 -40 to +100 Lifetime
1-50 50 20 20 4000 MIL-STD-202 MIL-STD-202 -40 to +125 -40 to +100 Lifetime
1-50 50 20 20 2500 IEC68-2-6 IEC68-2-27 -40 to +100 -40 to +85 Lifetime
Field to logic and channel-to-channel if Grayhill racks are used. MIL-STD-202, Method 204, 20 G, 10-2000 Hz or IEC68-2-6, 0.15 mm/sec2, 10-150 Hz. MIL-STD-202, Method 213, Condition F, 1500 G or IEC68-2-27, 11 mS, 15g.
H-15
Grayhill, Inc. • 561 Hillgrove Avenue • LaGrange, Illinois 60525-5997 • USA • Phone: 708-354-1040 • Fax: 708-354-2820 • www.grayhill.com
AC Input Modules
SPECIFICATIONS: By Part Number Standard and Miniature Modules Type/Function
Grayhill Part Number
Miniature Standard
70M-IAC5 70-IAC5
Specifications
70M-IAC5A 70-IAC5A
70M-IAC15 70M-IAC15A 70M-IAC24 70-IAC15 70-IAC15A 70-IAC24
70M-IAC24A 70-IAC24A
Units
Nominal Input Voltage Vac Vac/Vdc Input Voltage Range1 Input Current @ Maximum Input Voltage mA, rms Nominal Input Resistance (Rx) Ω Maximum Pick-Up Voltage (Output Low) Vac Minimum Drop-Out Voltage (Output High) Vac Nominal Logic Voltage (Vcc) Vdc Logic Voltage Range Vdc Max. Logic Supply Current @ Nominal Vcc mA
120 90-140 8 22K 90 25 5 3-6 10
240 180-280 6 60K 180 50 5 3-6 10
120 90-140 8 22K 90 25 15 8-18 10
240 180-280 6 60K 180 50 15 8-18 10
120 90-140 8 22K 90 25 24 15-30 10
240 180-280 6 60K 180 50 24 15-30 10
G5 Modules Type/Function
Grayhill Part Number
G5, Status LED
70G-IAC5
Specifications
70G-IAC5A
70G-IAC15 70G-IAC15A 70G-IAC24 70G-IAC24A
Units
Nominal Input Voltage Vac Input Voltage Range1 Vac/Vdc Input Current @ Maximum Input Voltage mA, rms Nominal Input Resistance (Rx) Ω Maximum Pick-Up Voltage (Output Low) Vac Minimum Drop-Out Voltage (Output High) Vac Nominal Logic Voltage (Vcc) Vdc Logic Voltage Range Vdc Max. Logic Supply Current @ Nominal Vcc mA
120 0-140 8 22K 90 25 5 4.5-6 10
240 0-280 6 60K 180 50 5 4.5-6 10
120 0-140 8 22K 90 25 15 10-18 10
240 0-280 6 60K 180 50 15 10-18 10
120 0-140 8 22K 90 25 24 17-30 10
240 0-280 6 60K 180 50 24 17-30 10
OpenLine® Modules Grayhill Part Number
Type/Function Dual, Status LED Specifications
1
70L-IACA
120 0-140 8 22K 90 25 5 4.5-28 6/CH 0
240 0-280 6 64K 180 50 5 4.5-28 6/CH 0
Units Vac Vac/Vdc mA, rms " Vac Vac Vdc Vdc mA "
I/O Modules
Nominal Input Voltage Input Voltage Range1 Input Current @ Max. Input Voltage Nominal Input Resistance (Rx) Max. Pick-Up Voltage (Output Low) Min. Drop-Out Voltage (Output High) Nominal Logic Voltage (Vcc) Logic Voltage Range Max. Logic Supply Current @ Nominal Vcc Module ID Resistance to Logic Ground
70L-IAC
Available from your local Grayhill Distributor. For prices and discounts, contact a local Sales Office, an authorized local Distributor or Grayhill.
For input voltages in the range of 15-32 Vac, or 35-60 Vac, see DC input Modules with the NP or G suffix.
Grayhill, Inc. • 561 Hillgrove Avenue • LaGrange, Illinois 60525-5997 • USA • Phone: 708-354-1040 • Fax: 708-354-2820 • www.grayhill.com
H-16
DC Input Modules
FEATURES • Fast Switching Polarized Input Types • UL, CSA, CE, TÜV Certified (TÜV not available on OpenLine®) • Optical Isolation • OpenLine® and G5 Modules have Built-in Status LED
••
TUV R h e i n l a n d
70L-IDC
70G-IDC
70-IDC
DIMENSIONS
70M-IDC
For complete dimensional drawings, see pages H-4 or H-5.
CIRCUITRY OpenLine®
Standard, Mini, G5 +
I/O MODULE PIN #
Rx 1
TYPICAL WIRING FOR MODULE 0
VDC 2
INPUT DEVICE
1
1
FILTER
OPTICAL ISOLATION
FILTER
OPTICAL ISOLATION
– +VCC 3
INPUT VOLTAGE HYST. CIRC. CURRENT REGULATING
OUTPUT
INPUT DEVICE
+
2
2
3
3
+
DC SUPPLY
4
–
GROUND 5
TERMINAL BLOCK #
Status LED in G5 modules only.
4
4
6
Vcc
A
+
HYSTERESIS
B
7
CH. A STATUS
5
GND
8
CH. B STATUS
9
MODULE ID
HYSTERESIS
–
BASE OR RACK
0Ω
MODULE
SPECIFICATIONS: By Package Style Package Style I/O Modules 1 2 3
Specifications
Units
Output Current Range Minimum Output Breakdown Voltage Isolation Voltage1 Vibration2 Mechanical Shock3 Storage Temp. Range Operating Temp. Range Warranty
mA Vdc Vrms
°C °C
Std (70-)
Mini (70M-)
G5 (70G-)
OL (70L-)
1-50 50 4000 MIL-STD-202 MIL-STD-202 -40 to 125 -40 to 100 Lifetime
1-50 50 4000 MIL-STD-202 MIL-STD-202 -40 to 125 -40 to 100 Lifetime
1-50 50 4000 MIL-STD-202 MIL-STD-202 -40 to 125 -40 to 100 Lifetime
1-50 50 2500 IEC68-2-6 IEC68-2-27 -40 to 100 -40 to 85 Lifetime
Field to logic and channel-to-channel if Grayhill racks are used. MIL-STD-202, Method 204, 20G, 10-2000 Hz or IEC68-2-6, 0.15 mm/sec2, 10-150 Hz. MIL-STD-202, Method 213, Condition F, 1500G or IEC68-2-27, 11 mS, 15g.
H-19
Grayhill, Inc. • 561 Hillgrove Avenue • LaGrange, Illinois 60525-5997 • USA • Phone: 708-354-1040 • Fax: 708-354-2820 • www.grayhill.com
DC Input Modules
SPECIFICATIONS: By Part Number Standard and Miniature Modules Type/Function
Grayhill Part Number
Miniature, Polarized Standard, Non-Polarized Specifications
Units
Maximum Input Voltage Input Voltage Range1 Input Current @ Maximum Input Voltage Maximum Turn-On Time Maximum Turn-Off Time Nominal Input Resistance (Rx) Maximum Pick-Up Voltage (Output Low) Minimum Drop-Out Voltage (Output High) Nominal Logic Voltage (Vcc) Logic Voltage Range Max. Logic Supply Current @ Nominal Vcc
Vdc Vdc mA mSec mSec Ω Vdc Vdc Vdc Vdc mA
70M-IDC5 70-IDC5
70-IDC5B
32 3-32 18 0.20 0.40 1.8K 3 1 5 3-6 10
32 3-32 18 0.050 0.075 1.8K 3 1 5 3-6 18
70-IDC5K
16 2.5-16 30 0.025 0.030 500 2.5 1 5 3.5-6 18
70M-IDC15 70-IDC15
32 3-32 18 0.20 0.40 1.8K 3 1 15 8-18 10
70M-IDC24 70-IDC24
32 3-32 18 0.20 0.40 1.8K 3 1 24 15-30 10
G5 Modules Type/Function
Grayhill Part Number
G5, Polarized, Status LED
70G-IDC5
Specifications
Units
Maximum Input Voltage Input Voltage Range1 Input Current @ Maximum Input Voltage Maximum Turn-On Time Maximum Turn-Off Time Nominal Input Resistance (Rx) Maximum Pick-Up Voltage (Output Low) Minimum Drop-Out Voltage (Output High) Nominal Logic Voltage (Vcc) Logic Voltage Range Max. Logic Supply Current @ Nominal Vcc
Vdc Vdc mA mSec mSec Ω Vdc Vdc Vdc Vdc mA
32 3-32 18 0.20 0.40 1.8K 3 1 5 4.5-6 10
70G-IDC5B
70G-IDC5D 70G-IDC5K
32 3-32 18 0.050 0.075 1.8K 3 1 5 4.5-6 18
28 2.5-28 23 0.050 0.075 1.2K 2.5 1 5 4.5-6 10
16 2.5-16 30 0.025 0.030 500 2.5 1 5 4.5-6 18
70G-IDC15 70G-IDC24
32 3-32 18 0.20 0.40 1.8K 3 1 15 10-18 10
32 3-32 18 0.20 0.40 1.8K 3 1 24 17-30 10
OpenLine® Modules Type/Function
Grayhill Part Number
Dual, Polarized
70L-IDCB
Specifications
Units
Maximum Input Voltage Input Voltage Range1 Input Current @ Max. Input Voltage Maximum Turn-on Time Maximum Turn-off Time Nominal Input Resistance (Rx) Maximum Pick-Up Voltage (Output Low) Minimum Drop-Out Voltage (Output High) Nominal Logic Voltage (Vcc) Logic Voltage Range Max. Logic Supply Current @ Nominal Vcc Module ID Resistance to Logic Ground
Vdc Vdc mA mSec mSec Ω Vdc Vdc Vdc Vdc
32 0-32 18 0.20 0.40 1800 3 0.9 5 4.5-28
32 0-32 18 0.05 0.075 900 3 0.9 5 4.5-28
mA Ω
6/CH 0
6/CH 0
I/O Modules
1
70L-IDC
Available from your local Grayhill Distributor. For prices and discounts, contact a local Sales Office, an authorized local Distributor or Grayhill.
For input voltages in the range of 90 to 140 Vdc, use AC input modules 70-IAC5, 70M-IAC5, 70G-IAC5 or 70L-IAC. For input voltages in the range of 180 to 280 Vdc, use AC input modules 70-IAC5A, 70M-IAC5A, 70G-IAC5A or 70L-IACA.
Grayhill, Inc. • 561 Hillgrove Avenue • LaGrange, Illinois 60525-5997 • USA • Phone: 708-354-1040 • Fax: 708-354-2820 • www.grayhill.com
H-20