Transcript
New Product
Digital Temperature Controller E5@C/E5@C-T Large White PV Display That's Easier to Read. Easy to Use, from Model Selection to Setup and Operation. New Plug-in Models That Are Convenient for Maintenance and Replacement as replacing temperature controllers is possible without changing wiring. New Models That Mount to DIN Track and Are Ideal for HMI/PLC Connections. And Programmable Models to Support a Wider Range of Applications. E5GC
DIN 48 × 24 mm
E5CC E5CC-U
DIN 48 × 48 mm
page 2
page 16
Digital Temperature Controller
E5@C Series
E5EC
E5AC
E5DC
Programmable Temperature Controller (Digital Controller)
E5@C-T Series
E5CC-T
E5EC-T
E5AC-T
DIN 48 × 96 mm page 34
DIN 96 × 96 mm page 34
22.5 mm wide Mounts to DIN Track page 50
DIN 48 × 48 mm page 64
DIN 48 × 96 mm page 80
DIN 96 × 96 mm page 80
1
Digital Temperature Controller
E5GC
(48 × 24 mm)
Easy Operation and High Performance of the E5@C Series in a Compact 48 × 24mm Body • A compact body of 48 × 24 × 90 mm (W × H × D) that is ideal for small equipment, laboratory instruments, and others. • White PV display with a height of 10.5 mm for high visibility even with the compact body. • Removable terminal block to simplify maintenance. Select from screw terminals or screwless clamp terminals for the wiring method. • High-speed sampling at 50 ms. • Easy connections to a PLC with programless communications. • Set up the Controller without wiring the power supply by connecting to the computer with a Communications Conversion Cable (sold separately). Setup is easy with the CX-Thermo (sold separately).
48 × 24 mm Models with Screw Terminal Blocks E5GC-@6
48 × 24 mm Models with Screwless Clamp Terminal Blocks E5GC-@C
Refer to your OMRON website for the most recent information on applicable safety standards.
Refer to Safety Precautions on page 104.
Main I/O Functions Sensor Input Universal input • Thermocouple • Pt • Analog current/voltage
E5GC Dual displays: PV/SV
Control Output 1 • Relay output • Voltage output (for driving SSR) • Linear current output
Indication Accuracy • Thermocouple input: ±0.3% of PV • Pt input: ±0.2% of PV • Analog input: ±0.2% of FS Sampling Period • 50 ms
Event Inputs • None •1 •2 Serial Communications • None • RS-485
4-digit displays
• PF (shift) Key • Temperature status display • Simple programming • Independent heating and cooling PID control • Changed parameter display • Display brightness setting • Simple transfer output (only on models with liner current outputs) • Work Bit Message
Auxiliary Outputs • None •1 •2
This datasheet is provided as a guideline for selecting products. Be sure to refer to the following manuals for application precautions and other information required for operation before attempting to use the product. E5@C Digital Temperature Controllers User’s Manual (Cat. No. H174) E5@C Digital Temperature Controllers Communications Manual (Cat. No. H175)
2
E5GC
Model Number Legend and Standard Models Model Number Legend E5GC-@@ @ @ @ M-@@@ (Example: E5GC-RX1A6M-015) −− − − − − −−− A B C D E F
Model
A B Control No. of outputs 1 auxiliary and 2 outputs
C Power supply voltage
D
E
F
Terminal type
Input type
Options
Meaning 48 × 24 mm
E5GC Control output 1 Relay output Voltage output (for driving SSR) Linear current output
RX QX *1 CX *2 0 1 2 A D 6 C M
*3 *3, *4 *5 *1 *2 *3 *4 *5
000 015 016 023 024
Control output 2 None None
None None 1 2 100 to 240 VAC 24 VAC/DC Screw terminals (with cover) Screwless clamp terminals Universal input HB alarm and HS alarm Communications Event inputs --------RS-485 ------1 1 --------2
The control output can be used as a simple transfer output. Only option 000 can be selected if an auxiliary output is zero. Option 016 and 023 can be selected only if two auxiliary outputs are selected. Option with HB and HS alarms (023) cannot be selected if a linear current output is selected for the control output. Option 024 can be selected only if one auxiliary output is selected.
Heating and Cooling Control ●Using Heating and Cooling Control
A Control Output Assignment An auxiliary output is used as the cooling control output. B Control If PID control is used, you can set PID control separately for heating and cooling. This allows you to handle control systems with different heating and cooling response characteristics.
3
E5GC Optional Products (Order Separately) USB-Serial Conversion Cable Model E58-CIFQ2
Model Y92S-P12
Communications Conversion Cable Model E58-CIFQ2-E
Current Transformers (CTs) Model E54-CT1 E54-CT3
Mounting Adapter Model Y92F-53 (2pcs) Note: This Mounting Adapter is provided with the Digital Temperature Controller.
4
Note: This Waterproof Packing is provided with the Digital Temperature Controller.
Draw-out Jig
Note: Always use this product together with the E58-CIFQ2. This Cable is used to connect to the bottom-panel Setup Tool port.
Hole diameter 5.8 mm 12.0 mm
Waterproof Packing
Model Y92F-55
CX-Thermo Support Software Model EST2-2C-MV4 Note: CX-Thermo version 4.62 or higher is required for the E5GC. For the system requirements for the CX-Thermo, refer to information on the EST2-2C-MV4 on the OMRON website (www.ia.omron.com).
E5GC
Specifications Ratings Power supply voltage Operating voltage range Power consumption
Sensor input
Input impedance Control method Relay output Control output
Auxiliary output
Voltage output (for driving SSR) Linear current output Number of outputs Output specifications Number of inputs
Event input
External contact input specifications
Setting method Indication method Multi SP Bank switching
Other functions
Ambient operating temperature Ambient operating humidity Storage temperature Altitude Recommended fuse Installation environment
A in model number: 100 to 240 VAC, 50/60 Hz D in model number: 24 VAC, 50/60 Hz; 24 VDC 85% to 110% of rated supply voltage 5.9 VA max. at 100 to 240 VAC, and 3.2 VA max. at 24 VAC or 1.8 W max. at 24 VDC Temperature input Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II Platinum resistance thermometer: Pt100 or JPt100 Infrared temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C Analog input Current input: 4 to 20 mA or 0 to 20 mA Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V Current input: 150 Ω max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB/ THB.) ON/OFF control or 2-PID control (with auto-tuning) SPST-NO, 250 VAC, 2 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA (reference value) Output voltage 12 VDC ±20% (PNP), max. Load current: 21 mA, with short-circuit protection circuit 4 to 20 mA DC/0 to 20 mA DC, load: 500 Ω max., resolution: Approx. 10,000 1 or 2 (depends on model) SPST-NO relay outputs, 250 VAC, 2 A (resistive load), Electrical life: 100,000 operations, Minimum applicable load: 10 mA at 5 V (reference value) 1 or 2 (depends on model) Contact input ON: 1 kΩ max., OFF: 100 kΩ min. Non-contact input ON: Residual voltage 1.5 V max.; OFF: Leakage current 0.1 mA max. Current flow: approx. 7 mA per contact Digital setting using front panel keys 11-segment digital displays and individual indicators Character height: PV: 10.5 mm, SV: 5.0 mm Up to eight set points (SP0 to SP7) can be saved and selected using the event inputs, key operations, or serial communications.* None Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater burnout (HB) alarm (including SSR failure (HS) alarm), 40% AT, 100% AT, MV limiter, input digital filter, self tuning, robust tuning, PV input shift, run/stop, protection functions, extraction of square root, MV change rate limit, logic operations, temperature status display, simple programming, moving average of input value, display brightness setting, simple transfer output, and work bit message −10 to 55°C (with no condensation or icing), For 3-year warranty: −10 to 50°C with standard mounting (with no condensation or icing) 25% to 85% −25 to 65°C (with no condensation or icing) 2,000 m max. T2A, 250 VAC, time-lag, low-breaking capacity Installation Category II, Pollution Degree 2 (IEC 61010-1 compliant)
* Only four set points are selectable for event inputs.
5
E5GC Input Ranges ●Thermocouple/Platinum Resistance Thermometer (Universal inputs) Sensor type
Platinum resistance thermometer
Sensor specification
Pt100
Infrared temperature sensor
Thermocouple
JPt100
K
J
T
E
L
U
N
R
S
B
W
PLII
10 to 70°C
60 to 120°C
115 to 165°C
120
165
140 to 260°C
2300
2300
1800
1800
1700
1700
1700
Temperature range (°C)
1600 1500 1400
1300
1300
1300
1300
1200 1100 1000 900
850
850
850
800 700
600
600
500.0
500
500.0
500.0 400.0
400
400
400.0
400
400.0 260
300 200
100.0
100
Set value
90
100 0.0
-100 -200
100.0
-200 -199.9
0
1
0.0 -199.9
2
3
-20.0
-100
-20.0
6
7
8
-200
4
5
0
0
16
17
0
0
0
0
0
0
19
20
21
22
23
24
-100 -200 -199.9 -200
9
10
11
-200 -199.9 -200
12
13
14
15
18
Shaded settings are the default settings. The applicable standards for the input types are as follows: K, J, T, E, N, R, S, B: JIS C 1602-1995, IEC 60584-1 L: Fe-CuNi, DIN 43710-1985 U: Cu-CuNi, DIN 43710-1985 W: W5Re/W26Re, ASTM E988-1990
JPt100: JIS C 1604-1989, JIS C 1606-1989 Pt100: JIS C 1604-1997, IEC 60751 PL II: According to Platinel II electromotive force charts from BASF (previously Engelhard)
●Analog input Input type Input specification Setting range Set value
6
Current Voltage 4 to 20 mA 0 to 20 mA 1 to 5 V 0 to 5 V Usable in the following ranges by scaling: -1999 to 9999, -199.9 to 999.9, -19.99 to 99.99 or -1.999 to 9.999 25 26 27 28
0 to 10 V
29
E5GC Alarm Types Each alarm can be independently set to one of the following 17 alarm types. The default is 2: Upper limit. (See note.) Auxiliary outputs are allocated to alarms. ON delays and OFF delays (0 to 999 s) can also be specified. Note: In the default settings for models with HB or HS alarms, alarm 1 is set to a heater alarm (HA) and the Alarm Type 1 parameter is not displayed. To use alarm 1, set the output assignment to alarm 1. Set value
Alarm type
0
Alarm function OFF
1
Upper- and lower-limit *1
2 Upper-limit (default) 3
Lower-limit
4
Upper- and lower-limit range *1
5 6 7 8 9 10 11
Alarm output operation Description of function When alarm value X When alarm value X is positive is negative Output OFF No alarm Set the upward deviation in the set point for the alarm upper L H limit (H) and the lower deviation in the set point for the alarm ON *2 OFF PV lower limit (L). The alarm is ON when the PV is outside this SP deviation range. Set the upward deviation in the set point by setting the alarm X X ON ON value (X). The alarm is ON when the PV is higher than the OFF PV OFF PV SP SP SP by the deviation or more. Set the downward deviation in the set point by setting the X X ON ON alarm value (X). The alarm is ON when the PV is lower than OFF PV OFF PV SP SP the SP by the deviation or more. Set the upward deviation in the set point for the alarm upper L H limit (H) and the lower deviation in the set point for the alarm ON *3 OFF PV lower limit (L). The alarm is ON when the PV is inside this deSP viation range.
Upper- and lower-limit with standby sequence *1 *5 Upper-limit with standby sequence Lower-limit with standby sequence
ON OFF
Absolute-value upper-limit
ON OFF
Absolute-value lower-limit
ON OFF
Absolute-value upper-limit with standby sequence
ON OFF
Absolute-value lower-limit with standby sequence
ON OFF
LBA (alarm 1 type only) PV change rate alarm
14
SP absolute-value upper-limit alarm
ON OFF
SP absolute-value lower-limit alarm
ON OFF
X SP
PV
ON OFF
PV
ON OFF
PV
ON OFF
PV
ON OFF
PV
ON OFF
PV
ON OFF
X SP X 0 X 0 X 0 X 0
X 0
PV
A standby sequence is added to the upper-limit alarm (2). *6
PV
A standby sequence is added to the lower-limit alarm (3). *6
X SP X 0
PV
X 0
PV
X 0
PV
X 0
PV
ON OFF
SP
ON OFF
X 0
The alarm will turn ON if the process value is smaller than the alarm value (X) regardless of the set point. A standby sequence is added to the absolute-value upperlimit alarm (8). *6 A standby sequence is added to the absolute-value lowerlimit alarm (9). *6
X 0
SP
X 0
SP
This alarm type turns ON the alarm when the set point (SP) is higher than the alarm value (X). This alarm type turns ON the alarm when the set point (SP) is lower than the alarm value (X).
Standard Control
X MV
0
The alarm will turn ON if the process value is larger than the alarm value (X) regardless of the set point.
*7 *8
SP
ON OFF
X 0
MV
X MV
0
Standard Control ON OFF
17
SP
This alarm type turns ON the alarm when the manipulated Heating/Cooling Heating/Cooling variable (MV) is higher than the alarm value (X). Control (Heating MV) Control (Heating MV) ON OFF
MV absolute-value lower-limit alarm *9
X
-
ON OFF
MV absolute-value upper-limit alarm *9
*4
PV
Standard Control
16
A standby sequence is added to the upper- and lower-limit alarm (1). *6
H
SP
ON OFF
12 13
15
L
ON OFF
Standard Control
X MV
0
Always ON ON OFF
X 0
MV
This alarm type turns ON the alarm when the manipulated Heating/Cooling Heating/Cooling variable (MV) is lower than the alarm value (X). Control (Cooling MV) Control (Cooling MV) ON OFF
X 0
MV
Always ON
7
E5GC *1 With set values 1, 4, and 5, the upper- and lower-limit values can be set independently for each alarm type, and are expressed as “L” and “H.” *2 Set value: 1, Upper- and lower-limit alarm Case 3 (Always OFF)
Case 2
Case 1
H<0, L<0 L
H SP
H<0, L>0 |H| < |L|
H
SP L H H>0, L<0 |H| > |L|
H
SP
L H<0, L>0 |H| ≥ |L|
L SP SP H
L
H>0, L<0 |H| ≤ |L|
*3 Set value: 4, Upper- and lower-limit range Case 3 (Always ON)
Case 2
Case 1
H<0, L<0 L
H SP
H<0, L>0 |H| < |L|
SP L
H
H
H>0, L<0 |H| > |L|
H
SP
L
L SP SP H L
8
H<0, L>0 |H| ≥ |L| H>0, L<0 |H| ≤ |L|
*4 Set value: 5, Upper- and lower-limit with standby sequence For Upper- and Lower-Limit Alarm Described Above at *2 • In cases 1 and 2 above, the alarm is always OFF if the upperand lower-limit hysteresis overlaps. • In case 3, the alarm is always OFF. *5 Set value: 5, Upper- and lower-limit alarm with standby sequence The alarm is always OFF if upper- and lower-limit hysteresis overlaps. *6 Refer to the E5@C Digital Temperature Controllers User’s Manual (Cat. No. H174) for information on the operation of the standby sequence. *7 Refer to the E5@C Digital Temperature Controllers User’s Manual (Cat. No. H174) for information on the LBA. *8 Refer to the E5@C Digital Temperature Controllers User’s Manual (Cat. No. H174) for information on the PV change rate alarm. *9 When heating/cooling control is performed, the MV absolutevalue upper-limit alarm functions only for the heating operation and the MV absolute-value lower-limit alarm functions only for the cooling operation.
E5GC Characteristics Indication accuracy (at the temperature of 23°C) Influence of temperature *2
Influence of voltage *2
Input sampling period Hysteresis Proportional band (P) Integral time (I) Derivative time (D) Proportional band (P) for cooling Integral time (I) for cooling Derivative time (D) for cooling Control period Manual reset value Alarm setting range Influence of signal source resistance Insulation resistance
Thermocouple: (±0.3 % of indication value or ±1°C, whichever is greater) ±1 digit max.*1 Platinum resistance thermometer: (±0.2 % of indication value or ±0.8°C, whichever is greater) ±1 digit max. Analog input: ±0.2% FS ±1 digit max. CT input: ±5% FS ±1 digit max. Thermocouple input (R, S, B, W, PL II): (±1% of indication value or ±10°C, whichever is greater) ±1 digit max. Other thermocouple input: (±1% of indication value or ±4°C, whichever is greater) ±1 digit max. *3 Platinum resistance thermometer: (±1% of indication value or ±2°C, whichever is greater) ±1 digit max. Analog input: ±1% FS ±1 digit max. CT input: ±5% FS ±1 digit max. 50 ms Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F) Analog input: 0.01% to 99.99% FS (in units of 0.01% FS) Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F) Analog input: 0.1% to 999.9% FS (in units of 0.1% FS) 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4 Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F) Analog input: 0.1% to 999.9% FS (in units of 0.1% FS) 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4 0.1, 0.2, 0.5, 1 to 99 s (in units of 1 s) 0.0% to 100.0% (in units of 0.1%) −1,999 to 9,999 (decimal point position depends on input type) Thermocouple: 0.1°C/Ω max. (100 Ω max.), Platinum resistance thermometer: 0.1°C/Ω max. (10 Ω max.)
20 MΩ min. (at 500 VDC) 100 to 240 VAC: 3,000 VAC, 50/60 Hz for 1 min between terminals of different charge Dielectric strength 24 VAC/DC: 2,300 VAC, 50/60 Hz for 1 min between terminals of different charge Malfunction 10 to 55 Hz, 20 m/s2 for 10 min each in X, Y and Z directions Vibration Resistance 10 to 55 Hz, 20 m/s2 for 2 hr each in X, Y, and Z directions Malfunction 100 m/s2, 3 times each in X, Y, and Z directions Shock Resistance 300 m/s2, 3 times each in X, Y, and Z directions Weight Controller: Approx. 80 g, Adapter: Approx. 4 g × 2 Degree of protection Front panel: IP66, Rear case: IP20, Terminals: IP00 Memory protection Non-volatile memory (number of writes: 1,000,000 times) Setup Tool CX-Thermo version 4.62 or higher E5GC side panel: An E58-CIFQ2 USB-Serial Conversion Cable is used to connect a USB port on the computer. *5 Setup Tool port E5GC bottom panel: An E58-CIFQ2 USB-Serial Conversion Cable and E58-CIFQ2-E Conversion Cable are used together to connect a USB port on the computer.*5 Approved standards UL 61010-1, Korean Radio Waves Act (Act 10564) Standards Conformed standards EN 61010-1 (IEC 61010-1): Pollution Degree 2 , overvoltage category II EMI: EN61326 Radiated Interference Electromagnetic Field Strength: EN55011 Group 1, class A Noise Terminal Voltage: EN55011 Group 1, class A EMS: EN61326 ESD Immunity: EN61000-4-2 EMC Electromagnetic Field Immunity: EN61000-4-3 Burst Noise Immunity: EN61000-4-4 Conducted Disturbance Immunity: EN61000-4-6 Surge Immunity: EN61000-4-5 Voltage Dip/Interrupting Immunity: EN61000-4-11 *1 The indication accuracy of K thermocouples in the −200 to 1,300°C range, T and N thermocouples at a temperature of −100°C max., and U and L thermocouples at any temperature is ±2°C ±1 digit max. The indication accuracy of B thermocouples at a temperature of 400°C max. is not specified. The indication accuracy of B thermocouples at a temperature of 400 to 800°C is ±3°C max. The indication accuracy of R and S thermocouples at a temperature of 200°C max. is ±3°C ±1 digit max. The indication accuracy of W thermocouples is (±0.3% of PV or ±3°C, whichever is greater) ±1 digit max. The indication accuracy of PLII thermocouples is (±0.3% of PV or ±2°C, whichever is greater) ±1 digit max. *2 Ambient temperature: −10°C to 23°C to 55°C, Voltage range: −15% to 10% of rated voltage *3 K thermocouple at −100°C max.: ±10°C max. *4 The unit is determined by the setting of the Integral/Derivative Time Unit parameter. *5 External serial communications (RS-485) and USB-Serial Conversion Cable communications can be used at the same time.
9
E5GC USB-Serial Conversion Cable Applicable OS
Windows XP, Vista, or 7
Applicable software
CX-Thermo version 4.62 or higher
Applicable models
E5@C-T Series, E5@C Series, and E5CB Series
Component Communications
When Digital Temperature Controllers are connected, set points and RUN/STOP commands can be sent from the Digital Temperature Controller that is set as the master to the Digital Temperature Controllers that are set as slaves. Slope and offsets can be set for the set point. Number of connected Digital Temperature Controllers: 32 max. (including master)
Copying*
When Digital Temperature Controllers are connected, the parameters can be copied from the Digital Temperature Controller that is set as the master to the Digital Temperature Controllers that are set as slaves.
USB interface standard Conforms to USB Specification 2.0 DTE speed
38,400 bps
Connector specifications
Computer: USB (Type A plug) Digital Temperature Controller: Special serial connector
Power supply
Bus power (Supplied from the USB host controller) *
MELSEC is a registered trademark of Mitsubishi Electric Corporation. KEYENCE is a registered trademark of Keyence Corporation.
Power supply voltage
5 VDC
*
Current consumption
450 mA max.
Output voltage
4.7±0.2 VDC (Supplied from USB-Serial Conversion Cable to the Digital Temperature Controller.)
Output current
250 mA max. (Supplied from USB-Serial Conversion Cable to the Digital Temperature Controller.)
Ambient operating temperature
0 to 55°C (with no condensation or icing)
Ambient operating humidity
10% to 80%
Storage temperature
−20 to 60°C (with no condensation or icing)
Storage humidity
10% to 80%
Altitude
2,000 m max.
Weight
Approx. 120 g
*
Use a high-power port for the USB port.
Note: A driver must be installed on the computer. Refer to the Instruction Manual included with the Cable for the installation procedure.
Communications Specifications Transmission line connection method
RS-485: Multidrop
Communications
RS-485 (two-wire, half duplex)
Synchronization method
Start-stop synchronization
Protocol
CompoWay/F, or Modbus
Baud rate*
9,600, 19,200, 38,400, or 57,600 bps
Transmission code
ASCII
Data bit length *
7 or 8 bits
Stop bit length *
1 or 2 bits
Error detection
Vertical parity (none, even, odd) Block check character (BCC) with CompoWay/F or CRC-16 with Modbus
Flow control
None
Interface
RS-485
Retry function
None
Communications buffer
217 bytes
Communications response wait time
0 to 99 ms Default: 20 ms
* The baud rate, data bit length, stop bit length, and vertical parity can be individually set using the Communications Setting Level.
Communications Functions
Programless communications
10
You can use the memory in the PLC to read and write E5@C parameters, start and stop operation, etc. The E5@C automatically performs communications with PLCs. No communications programming is required. Number of connected Digital Temperature Controllers: 32 max. (Up to 16 for the FX Series) Applicable PLCs: OMRON PLCs CS Series, CJ Series, or CP Series Mitsubishi Electric PLCs MELSEC Q Series, L Series, or FX Series (compatible with the FX2 or FX3 (excluding the FX1S)) KEYENCE PLCs KEYENCE KV Series
Current Transformer (Order Separately) Ratings Dielectric strength
1,000 VAC for 1 min
Vibration resistance
50 Hz, 98 m/s2
Weight
E54-CT1: Approx. 11.5 g, E54-CT3: Approx. 50 g
Accessories (E54-CT3 only)
Armatures (2) Plugs (2)
Heater Burnout Alarms and SSR Failure Alarms CT input (for heater current detection)
Models with detection for single-phase heaters: One input
Maximum heater current
50 A AC
Input current indication accuracy
±5% FS ±1 digit max.
Heater burnout alarm setting range *1
0.1 to 49.9 A (in units of 0.1 A) Minimum detection ON time: 100 ms *3
SSR failure alarm setting range *2
0.1 to 49.9 A (in units of 0.1 A) Minimum detection OFF time: 100 ms *4
*1 *2 *3 *4
For heater burnout alarms, the heater current will be measured when the control output is ON, and the output will turn ON if the heater current is lower than the set value (i.e., heater burnout detection current value). For SSR failure alarms, the heater current will be measured when the control output is OFF, and the output will turn ON if the heater current is higher than the set value (i.e., SSR failure detection current value). The value is 30 ms for a control period of 0.1 s or 0.2 s. The value is 35 ms for a control period of 0.1 s or 0.2 s.
Electrical Life Expectancy Curve for Control Output Relay (Reference Values) Life (× 104 operations)
Windows is a registered trademark of Microsoft Corporation in the United States and or other countries.
Both the programless communications and the component communications support the copying.
500 300 200 100
E5GC 250 VAC, 30 VDC (resistive load) cosφ = 1
50 30 20 10 5 3 2 1 0.1
0.2 0.3 0.5
1
2
3
5
10
Switching current (A)
E5GC
External Connections E5GC Control Outputs
E5GC-@ @ @ @ @ M - @ @ @
Relay output 250 VAC, 2 A (resistive load) Voltage output (for driving SSR) 12 VDC, 21 mA Linear current output 0 to 20 mA DC 4 to 20 mA DC Load: 500 Ω max.
(1) (2)(3)(4)(5)
(6)
↑ Terminal type Auxiliary outputs 1, 2 The E5GC is set for a K-type thermocouple (input type = 5) by default. An input error (s.err) wil occur if the input type setting does not agree with the temperature sensor. Check the input type.
Relay outputs 250 VAC, 2 A (resistive load)
(6) Options 015 Communications (RS-485) RS-485 B(+)
016
023
Event input 1
CT input
EV1
A(−)
−
+
7
8
(5) Sensor (Temperature/ Analog) Input
024 Event inputs 1 and 2 EV2 CT
−
+
−
+
EV1
+
TC 10 11 12 7
8
9
9
7
8
7
9
8
9 B
A
Pt
(3) Input Power Supply 100 to 240 VAC
1
B
10 11 12 + mA
−
24 VAC/DC
2
1
2
7
8
9 10 11 12
1
2
3
I
10 11 12 −
(no polarity)
4
5
6
V
V
+
10 11 12
(2) Auxiliary Outputs Auxiliary output 1
(1) Control Outputs RX
QX
Relay output R
Voltage output (for driving SSR) Linear current output Q C
CX
+
−
+
9
−
5 3
4
3
4
3
Auxiliary outputs 1, 2 Auxiliary output 2
4
5
6
Auxiliary output 1
6
Auxiliary output 1
Note: 1. The application of the terminals depends on the model. 2. Do not wire the terminals that are shown with a gray background. 3. When complying with EMC standards, the cable that connects the sensor must be 30 m or less. If the cable length exceeds 30 m, compliance with EMC standards will not be possible. 4. Connect M3 crimped terminals.
Isolation/Insulation Block Diagrams Sensor input and CT input Communications and event inputs Power supply
Voltage output (for driving SSR) and linear current output Relay output Auxiliary outputs 1 and 2
: Reinforced insulation : Functional isolation
Note: Auxiliary outputs 1 to 2 are not insulated.
11
E5GC
Wiring Methods E5GC-@C Controllers with Screwless Clamp Terminal Blocks
E5GC-@6 Controllers with Screw Terminal Blocks (M3 Screws)
Controllers with Screw Terminal Blocks
Controllers with Screwless Clamp Terminals Blocks
• Terminal type: Forked or round crimped terminals • Tightening torque for all terminals: 0.43 to 0.58 N·m
• Wire stripping length: 8 to 12 mm • Ferrules: 8 to 12 mm 0.8 to 1.4 mm
5.8 mm max. 8 to 12 mm
8 to 12 mm
5.8 mm max.
Wires: AWG24 to AWG18 (equal to a cross-sectional area of 0.205 to 0.823 mm2) braided or solid wires
Nomenclature E5GC
Front panel
Left Side View of the E5GC Left-panel Setup Tool port
No. 1 display Temperature unit
PV or specified parameter No.2 display SP or specified parameter value
Bottom View of E5GC
Operation indicators
Press O Key once to go to Adjustment Level.
Use the U D Keys to set the parameter.
Press O Key for at least 3 seconds to go to the Initial Setting Level.
Bottom-panel Setup Tool port
Use the M Key to change to another parameter.
12
Use S Key to change the digit (default setting).
E5GC
Dimensions
(Unit: mm)
Controllers E5GC-@6 Controllers with Screw Terminal Blocks
Waterproof Packing (Accessory) 63.6 48
Mounting Adapter (Accessory) Terminal Cover (Accessory)
4
90
44.8 1 22
40.8
24
22
• Use two Mounting Adapters, either on the top and bottom or on the right and left. • Setup Tool ports are provided as standard feature. Use these ports to connect a computer to the Digital Temperature Controller. The E58CIFQ2 USB-Serial Conversion Cable is required to connect to the port on the side panel. The E58-CIFQ2 USB-Serial Conversion Cable and E58-CIFQ2-E Communications Conversion Cable are required to connect to the port on the bottom panel. (You cannot leave either port connected constantly during operation.)
Mounted Separately
Horizontally Group Mounted L1
To mount the Temperature Controller so that it is waterproof, insert the Waterproof Packing onto the Temperature Controller. Group mounting does not allow waterproofing.
22.2+0.3 0 40 min
45+0.60
L1=(48×n-2.5) 22.2+0.3 0
+1.0 +0
n: Number of mounted Controllers (2 ≤ n ≤ 6)
• To install the Temperature Controller, insert it into a square hole in a panel with a thickness of 1 to 8 mm, and then insert the enclosed adapter so that it locks into the grooves on the top and bottom or on the left and right of the rear case. • Tighten the two mounting screws on the top and bottom or on the right and left of the Mounting Adapters alternately little by little to maintain a balance, and tighten them to a torque of between 0.29 and 0.39 N·m. • When two or more Temperature Controllers are mounted, make sure that the surrounding temperature does not exceed the allowable operating temperature range given below. Horizontal group mounting: −10 to 55°C • Use Temperature Controllers with Screwless Clamp Terminal Blocks for vertical group mounting.
E5GC-@C Controllers with Screwless Clamp Terminal Blocks
Waterproof Packing (Accessory) Mounting Adapter (Accessory) 63.6 48
4
93 44.8 1 22
40.8
24
22
• Use two Mounting Adapters, either on the top and bottom or on the right and left. • Setup Tool ports are provided as standard feature. Use these ports to connect a computer to the Digital Temperature Controller. The E58CIFQ2 USB-Serial Conversion Cable is required to connect to the port on the side panel. The E58-CIFQ2 USB-Serial Conversion Cable and E58-CIFQ2-E Communications Conversion Cable are required to connect to the port on the bottom panel. (You cannot leave either port connected constantly during operation.)
Mounted Separately
Horizontally Group Mounted
Vertically Group Mounted 45
L1
+0.6 +0
22.2+0.3 0 40 min
45+0.60
L1=(48×n-2.5)
+1.0 +0
n: Number of mounted Controllers (2 ≤ n ≤ 6)
22.2+0.3 0
L2
To mount the Temperature Controller so that it is waterproof, insert the Waterproof Packing onto the Temperature Controller. Group mounting does not allow waterproofing.
L2=(24×n-1.5) +1.0 +0
• To install the Temperature Controller, insert it into a square hole in a panel with a thickness of 1 to 8 mm, and then insert the enclosed adapter so that it locks into the grooves on the top and bottom or on the left and right of the rear case. • Tighten the two mounting screws on the top and bottom or on the right and left of the Mounting Adapters alternately little by little to maintain a balance, and tighten them to a torque of between 0.29 and 0.39 N·m. • When two or more Temperature Controllers are mounted, make sure that the surrounding temperature does not exceed the allowable operating temperature range given below. Horizontal group mounting: −10 to 55°C Vertical group mounting of two Controllers: −10 to 45°C Vertical group mounting of three or more Controllers: −10 to 40°C • If you use vertical group mounting, you cannot draw out the interior body of the Controller.
13
E5GC Accessories (Order Separately) ● USB-Serial Conversion Cable E58-CIFQ2
(2110) 250
263
1510
LED (RD)
USB connector (type A plug)
Serial connector
LED (PWR) LED (SD)
● Conversion Cable E58-CIFQ2-E Conversion Cable
Connecting to the E58-CIFQ2 USB-Serial Conversion Cable (2110)
(1510)
250
263
1510
E58-CIFQ2 (Order separately)
Note: Always use this product together with the E58-CIFQ2.
Conversion Cable
● Current Transformers E54-CT1 21 15
Thru-current (Io) vs. Output Voltage (Eo) (Reference Values) E54-CT1
2.8 5.8 dia. 7.5
3
Output voltage (Eo) V (r.m.s.)
25
Maximum continuous heater current: 50 A (50/60 Hz) Number of windings: 400±2 Winding resistance: 18±2 Ω
10.5 40 Two, 3.5 dia. 10 30
100V
Frequency: 50 Hz ∞ 1kΩ
10
Distortion factor 10%
1
3% 1% 100mV 100Ω
10
E54-CT3
2.36 dia. 30
RL=10Ω
1
12 dia. 9
100μV 10 1
40 × 40
10
100mA
1
10
100 1,000A
Thru-current (Io) A (r.m.s.)
Two , M3 holes (depth: 4)
30
Connection Example Armature Plug
Approx. 3 dia.
Lead
18
Output voltage (Eo) V (r.m.s.)
Maximum continuous heater current: 120 A (50/60 Hz) (Maximum continuous heater current for an OMRON Digital Temperature Controller is 50 A.) Number of windings: 400±2 Winding resistance: 8±0.8 Ω
15
E54-CT3 Accessories • Armature
Thru-current (Io) vs. Output Voltage (Eo) (Reference Values) E54-CT3
100V
Frequency: 50 Hz Distortion factor 10% 3% 1%
∞ 1kΩ 500Ω
10
1
100mV 100Ω 50Ω
10
RL=10Ω
• Plug
1
Approx. 6 dia.
100μV
(22)
10 1
10
100mA
1
10
100 1,000A
Thru-current (Io) A (r.m.s.)
14
E5GC ● Mounting Adapter Y92F-53 (Two provided.) One pair is provided with the Termperature Controller. Order this Adapter separately if it becomes lost or damaged.
34.7
12
11.8 9.4
● Waterproof Packing Y92S-P12 The Waterproof Packing is provided with the Temperature Controller. Order the Waterproof Packing separately if it becomes lost or damaged. The Waterproof Packing can be used to achieve an IP66 degree of protection. (Deterioration, shrinking, or hardening of the waterproof packing may occur depending on the operating environment. Therefore, periodic replacement is recommended to ensure the level of waterproofing specified in IP66. The time for periodic replacement depends on the operating environment. Be sure to confirm this point at your site. Consider three years a rough standard.) The Waterproof Packing does not need to be attached if a waterproof structure is not required.
● Draw-out Jig Y92F-55 Use this Draw-out Jig to remove the interior body of the Digital Temperature Controller from the case to perform maintenance without removing the terminal wiring. 32.9 15
30.5
1.4
27.4 28.7
22 20
23
15
Digital Temperature Controller
E5CC/E5CC-U
(48 × 48 mm)
Large White PV Display That’s Easier to Read. Easy to Use, from Model Selection to Setup and Operation. A Complete Range of I/O Capacities, Functions, and Performance. Handles More Applications. • The white PV display with a height of 15.2 mm improves visibility. 48 × 48 mm 48 × 48 mm • High-speed sampling at 50 ms. E5CC-U E5CC • Models are available with up to 3 auxiliary outputs, up to 4 event inputs, a transfer output, and a remote SP input to cover a wide Refer to your OMRON website for the most recent information on applicable safety standards. range of applications. • E5CC: Short body with depth of only 60 mm. • Set up the Controller without wiring the power supply by Refer to Safety Precautions on page 104. connecting to the computer with a Communications Conversion Cable (sold separately). Setup is easy with the CX-Thermo (sold separately). • Easy connections to a PLC with programless communications. Use component communications to link Temperature Controllers to each other.
Main I/O Functions Sensor Input Universal input • Thermocouple • Pt • Analog current/voltage
E5CC/E5CC-U Dual displays: PV/SV
Control Output 1 • Relay output • Voltage output (for driving SSR) • Linear current output
Indication Accuracy • Thermocouple input: ±0.3% of PV • Pt input: ±0.2% of PV • Analog input: ±0.2% of FS
Control Output 2 • None • None • Voltage output (for driving SSR)
Sampling Period • 50 ms Event Inputs • None • None •2 •4 Remote SP Input • None • None •1
4-digit displays
• PF (shift) Key • Temperature status display • Simple programming • Independent heating and cooling PID control • Changed parameter display • Display brightness setting
Auxiliary Outputs •3 • None •1 •2 Transfer Output • None • None •1
Serial Communications • None • None • RS-485
This datasheet is provided as a guideline for selecting products. Be sure to refer to the following manuals for application precautions and other information required for operation before attempting to use the product. E5@C Digital Temperature Controllers User’s Manual (Cat. No. H174) E5@C Digital Temperature Controllers Communications Manual (Cat. No. H175)
16
E5CC/E5CC-U
Model Number Legend and Standard Models Model Number Legend ●Models with Screw Terminals E5CC-@@ 3 @ 5 M -@@@ (Example: E5CC-RX3A5M-000) −− − − − − −−− A B C D E F A Model
Control outputs 1 and 2
B
C
D
No. of Power Terminal auxiliary supply type outputs voltage
E
F
Input type
Options
Meaning 48 × 48 mm Control output 1 Relay output Voltage output (for driving SSR) Linear current output *2 Voltage output (for driving SSR)
E5CC RX QX *1 *3 CX QQ CQ
Linear current output *2 3 A D 5 M
*1
000 001
*1
003
*3
004 005 006 007
Control output 2 None None None Voltage output (for driving SSR) Voltage output (for driving SSR)
3 (one common) 100 to 240 VAC 24 VAC/DC Screw terminals (with cover) Universal input Event Remote Transfer HB alarm and Communications HS alarm inputs SP Input output ----------1 --2 ----2 (for 3-phase RS-485 ------heaters) --RS-485 2 --------4 --------2 Provided. ----2 Provided. ---
*1. Options with HB and HS alarms (001 and 003) cannot be selected if a linear current output is selected for the control output. *2. The control output cannot be used as a transfer output. *3. Option 004 can be selected only when "CX" is selected for the control outputs.
Heating and Cooling Control ● Using Heating and Cooling Control A Control Output Assignment If there is no control output 2, an auxiliary output is used as the cooling control output. If there is a control output 2, the two control outputs are used for heating and cooling. (It does not matter which output is used for heating and which output is used for cooling.) B Control If PID control is used, you can set PID control separately for heating and cooling. This allows you to handle control systems with different heating and cooling response characteristics.
17
E5CC/E5CC-U Model Number Legend ●Plug-in Models E5CC-@@ @ @ U M -000 (Example: E5CC-RW0AUM-000) A
B C D E A
Model
B
F C
D
Control No. of Power Terminal outputs auxiliary supply type 1 and 2 outputs voltage
E
F
Input type
Options
Meaning 48 × 48 mm
E5CC RW
Control output 1 Relay output (SPDT)
Control output 2 None
QX
Voltage output (for driving SSR)
None
CX
Linear current output*
None
0
None
1
1
2
2 (one common) A
100 to 240 VAC
D
24 VAC/DC U
Plug-in model M HB alarm and HS alarm ---
000
Universal input CommuniRemote SP Transfer outEvent inputs cations Input put ---------
* The control output can be used as a simple transfer output for the Digital Temperature Controllers manufactured in May 2014 or later.
List of Models Options Control output
No. of auxiliary outputs
HB alarm and HS alarm
No. of event inputs
Voltage output (for driving SSR)
1
---
---
---
100 to 240 VAC
24 VAC/DC
E5CC-RW0AUM-000
E5CC-RW0DUM-000
E5CC-RW1AUM-000
E5CC-RW1DUM-000
2
E5CC-RW2AUM-000
E5CC-RW2DUM-000
---
E5CC-QX0AUM-000
E5CC-QX0DUM-000
E5CC-QX1AUM-000
E5CC-QX1DUM-000
E5CC-QX2AUM-000
E5CC-QX2DUM-000
E5CC-CX0AUM-000
E5CC-CX0DUM-000
E5CC-CX1AUM-000
E5CC-CX1DUM-000
E5CC-CX2AUM-000
E5CC-CX2DUM-000
1
---
---
---
2 --Linear current output
Model Power supply voltage
Communications
--Relay output
Model Power supply voltage
1
---
---
2
---
Heating and Cooling Control ●Using Heating and Cooling Control A Control Output Assignment An auxiliary output is used as the cooling control output. B Control If PID control is used, you can set PID control separately for heating and cooling. This allows you to handle control systems with different heating and cooling response characteristics.
18
E5CC/E5CC-U Optional Products (Order Separately) USB-Serial Conversion Cable
Front Covers
Model E58-CIFQ2
Type Hard Front Cover Soft Front Cover
Model Y92A-48H Y92A-48D
Terminal Covers (for E5CC) CX-Thermo Support Software
Model E53-COV17 E53-COV23 (3pcs)
Model EST2-2C-MV4
Note: The Terminal Covers E53-COV23 are provided only with E5CC Controllers. The E53-COV10 cannot be used. Refer to page 28 for the mounted dimensions.
Waterproof Packing
Note: CX-Thermo version 4.5 or higher is required for the E5CC. CX-Thermo version 4.61 or higher is required for the E5CC-U. For the system requirements for the CX-Thermo, refer to information on the EST2-2C-MV4 on the OMRON website (www.ia.omron.com).
Model Y92S-P8 Note: The Waterproof Packing is provided only with E5CC Controllers. The E5CC-U cannot be waterproofed even if the Waterproof Packing is attached.
Current Transformers (CTs) Hole diameter 5.8 mm 12.0 mm
Model E54-CT1 E54-CT3
Adapter Model Y92F-45 Note: Use this Adapter when the panel has already been prepared for an E5B@ Controller.
Waterproof Cover Model Y92A-48N
Mounting Adapter Model Y92F-49 Note: This Mounting Adapter is provided with the Digital Temperature Controller.
DIN Track Mounting Adapter Model Y92F-52
Sockets (for E5CC-U) Type Front-connecting Socket Front-connecting Socket with Finger Protection Back-connecting Socket Terminal Cover for Back-connecting socket with Finger Protection
Model P2CF-11 P2CF-11-E P3GA-11 Y92A-48G
19
E5CC/E5CC-U Specifications Ratings Power supply voltage Operating voltage range Power consumption
Sensor input
Input impedance Control method Relay output Control output
Voltage output (for driving SSR) Linear current output Number of outputs
Auxiliary output
Output specifications Number of inputs
Event input*
Transfer output*
External contact input specifications Number of outputs Output specifications
Setting method Remote SP input* Indication method Multi SP* Bank switching
Other functions
Ambient operating temperature Ambient operating humidity Storage temperature Altitude Recommended fuse Installation environment
A in model number: 100 to 240 VAC, 50/60 Hz D in model number: 24 VAC, 50/60 Hz; 24 VDC 85% to 110% of rated supply voltage Models with option selection of 000: 5.2 VA max. at 100 to 240 VAC, and 3.1 VA max. at 24 VAC or 1.6 W max. at 24 VDC All other models: 6.5 VA max. at 100 to 240 VAC, and 4.1 VA max. at 24 VAC or 2.3 W max. at 24 VDC Temperature input Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II Platinum resistance thermometer: Pt100 or JPt100 Infrared temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C Analog input Current input: 4 to 20 mA or 0 to 20 mA Voltage input: 1 to 5 V, 0 to 5 V, 0 to 10 V,or 0 to 50 mV (The 0 to 50 mV range applies to the E5CC-U only for those manufactured in May 2014 or later.) Current input: 150 Ω max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB/THB.) ON/OFF control or 2-PID control (with auto-tuning) E5CC: SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA (reference value) E5CC-U: SPDT, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA (reference value) Output voltage: 12 VDC ±20% (PNP), max. load current: 21 mA, with short-circuit protection circuit 4 to 20 mA DC/0 to 20 mA DC, load: 500 Ω max., resolution: approx. 10,000 E5CC: 3 E5CC-U: 1 or 2 (depends on model) SPST-NO relay outputs, 250 VAC, Models with 1 or 2 outputs: 3 A (resistive load), or Models with 3 outputs: 2 A (resistive load), Electrical life: 100,000 operations, Minimum applicable load: 10 mA at 5 V (reference value) 2 or 4 (depends on model) Contact input: ON: 1 kΩ max., OFF: 100 kΩ min. Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max. Current flow: Approx. 7 mA per contact 1 (only on models with a transfer output) Current output: 4 to 20 mA DC, load: 500 Ω max., resolution: approx. 10,000 Linear voltage output: 1 to 5 VDC, load: 1 kΩ min., resolution: Approx. 10,000 Digital setting using front panel keys Current input: 4 to 20 mA DC or 0 to 20 mA DC (input impedance: 150 Ω max.) Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V (input impedance: 1 MΩ min.) 11-segment digital display and individual indicators Character height: PV: 15.2 mm, SV: 7.1 mm Up to eight set points (SP0 to SP7) can be saved and selected using the event inputs, key operations, or serial communications. None Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater burnout (HB) alarm (including SSR failure (HS) alarm), 40% AT, 100% AT, MV limiter, input digital filter, self tuning, robust tuning, PV input shift, run/stop, protection functions, extraction of square root, MV change rate limit, logic operations, temperature status display, simple programming, moving average of input value, and display brightness setting −10 to 55°C (with no condensation or icing), For 3-year warranty: −10 to 50°C with standard mounting (with no condensation or icing) 25% to 85% -25 to 65°C (with no condensation or icing) 2,000 m max. T2A, 250 VAC, time-lag, low-breaking capacity Installation Category II, Pollution Degree 2 (IEC 61010-1 compliant)
* There are no optional functions for the E5CC-U. Refer to Model Number Legend and List of Models on page 18.
20
E5CC/E5CC-U Input Ranges ●Thermocouple/Platinum Resistance Thermometer (Universal inputs) Sensor type
Platinum resistance thermometer
Sensor specification
Pt100
Infrared temperature sensor
Thermocouple
JPt100
K
J
T
E
L
U
N
R
S
B
W
PLII
10 to 70°C
60 to 120°C
115 to 165°C
120
165
140 to 260°C
2300
2300
1800
1800
1700
1700
1700
Temperature range (°C)
1600 1500 1400
1300
1300
1300
1300
1200 1100 1000 900
850
850
850
800 700
600
600
500.0
500
500.0
500.0 400.0
400
400
400.0
400
400.0 260
300 200
100.0
100
90 100
0
0.0
-100 -200
100.0
-200
-199.9
0
1
Set value
0.0 199.9
2
3
-20.0
-100
-20.0
6
7
8
-200
4
5
0
0
16
17
0
0
0
0
0
0
19
20
21
22
23
24
-100 -200
-199.9
-200
9
10
11
12
-200
-199.9
-200
13
14
15
18
Shaded settings are the default settings. The applicable standards for the input types are as follows: K, J, T, E, N, R, S, B: JIS C 1602-1995, IEC 60584-1 L: Fe-CuNi, DIN 43710-1985 U: Cu-CuNi, DIN 43710-1985 W: W5Re/W26Re, ASTM E988-1990
JPt100: JIS C 1604-1989, JIS C 1606-1989 Pt100: JIS C 1604-1997, IEC 60751 PL II: According to Platinel II electromotive force charts from BASF (previously Engelhard)
●Analog input Input type Input specification Setting range Set value
Current 4 to 20 mA
0 to 20 mA
Voltage 1 to 5 V
Usable in the following ranges by scaling: -1999 to 9999, -199.9 to 999.9, -19.99 to 99.99 or -1.999 to 9.999 25 26 27
0 to 5 V
0 to 10 V
0 to 50 mV*
28
29
30
* The range applies to the E5CC-U only for those manufactured in May 2014 or later.
21
E5CC/E5CC-U Alarm Types Each alarm can be independently set to one of the following 19 alarm types. The default is 2: Upper limit. (see note.) Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified. Note: In the default settings for models with HB or HS alarms, alarm 1 is set to a heater alarm (HA) and the Alarm Type 1 parameter is not displayed. To use alarm 1, set the output assignment to alarm 1. Set value
Alarm type
0
Alarm function OFF
1
Upper- and lower-limit *1
2 Upper-limit (default) 3
Lower-limit
4
Upper- and lower-limit range *1
5 6 7 8 9 10 11
Alarm output operation Description of function When alarm value X When alarm value X is positive is negative Output OFF No alarm Set the upward deviation in the set point for the alarm upper L H limit (H) and the lower deviation in the set point for the alarm ON *2 OFF PV lower limit (L). The alarm is ON when the PV is outside this SP deviation range. Set the upward deviation in the set point by setting the alarm X X ON ON value (X). The alarm is ON when the PV is higher than the OFF PV OFF PV SP SP SP by the deviation or more. Set the downward deviation in the set point by setting the X X ON ON alarm value (X). The alarm is ON when the PV is lower than OFF PV OFF PV SP SP the SP by the deviation or more. Set the upward deviation in the set point for the alarm upper L H limit (H) and the lower deviation in the set point for the alarm ON *3 OFF PV lower limit (L). The alarm is ON when the PV is inside this deSP viation range.
Upper- and lower-limit with standby sequence *1 *5 Upper-limit with standby sequence Lower-limit with standby sequence
ON OFF
Absolute-value upper-limit
ON OFF
Absolute-value lower-limit
ON OFF
Absolute-value upper-limit with standby sequence
ON OFF
Absolute-value lower-limit with standby sequence
ON OFF
LBA (alarm 1 type only) PV change rate alarm
14
SP absolute-value upper-limit alarm
ON OFF
SP absolute-value lower-limit alarm
ON OFF
X SP
PV
ON OFF
PV
ON OFF
PV
ON OFF
PV
ON OFF
PV
ON OFF
PV
ON OFF
X SP X 0 X 0 X 0 X 0
X
ON OFF
19
22
A standby sequence is added to the upper-limit alarm (2). *6
PV
A standby sequence is added to the lower-limit alarm (3). *6
X SP X 0
PV
X 0
PV
X 0
PV
X 0
PV
0
ON OFF
SP
ON OFF
X 0
The alarm will turn ON if the process value is smaller than the alarm value (X) regardless of the set point. A standby sequence is added to the absolute-value upperlimit alarm (8). *6 A standby sequence is added to the absolute-value lowerlimit alarm (9). *6
X 0
SP
X 0
SP
This alarm type turns ON the alarm when the set point (SP) is higher than the alarm value (X). This alarm type turns ON the alarm when the set point (SP) is lower than the alarm value (X).
Standard Control
X MV
0
The alarm will turn ON if the process value is larger than the alarm value (X) regardless of the set point.
ON OFF
X 0
MV
X MV
0
X MV
0
Always ON Standard Control ON OFF
X 0
MV
This alarm type turns ON the alarm when the manipulated Heating/Cooling Heating/Cooling variable (MV) is lower than the alarm value (X). Control (Cooling MV) Control (Cooling MV) ON OFF
18
PV
*7 *8
SP
Standard Control
17
SP
This alarm type turns ON the alarm when the manipulated Heating/Cooling Heating/Cooling variable (MV) is higher than the alarm value (X). Control (Heating MV) Control (Heating MV) ON OFF
MV absolute-value lower-limit alarm *9
X
-
ON OFF
MV absolute-value upper-limit alarm *9
*4
PV
Standard Control
16
A standby sequence is added to the upper- and lower-limit alarm (1). *6
H
SP
ON OFF
12 13
15
L
ON OFF
RSP absolute-value upper-limit alarm *10
ON OFF
RSP absolute-value lower-limit alarm *10
ON OFF
X MV
0 X 0
RSP
ON OFF
RSP
ON OFF
X 0
Always ON X 0
RSP
X 0
RSP
This alarm type turns ON the alarm when the remote SP (RSP) is higher than the alarm value (X). This alarm type turns ON the alarm when the remote SP (RSP) is lower than the alarm value (X).
E5CC/E5CC-U *1 *2
With set values 1, 4 and 5, the upper and lower limit values can be set independently for each alarm type, and are expressed as “L” and “H.” Set value: 1, Upper- and lower-limit alarm Case 2
Case 1
Case 3 (Always ON)
H<0, L<0 L
H SP
H<0, L>0 |H| < |L|
H
SP L H H>0, L<0 |H| > |L|
SP
L H<0, L>0 |H| ≥ |L|
L SP
H
SP H
*3
L
H>0, L<0 |H| ≤ |L|
Set value: 4, Upper- and lower-limit range Case 1
Case 3 (Always OFF)
Case 2
H<0, L<0 L
H SP
H<0, L>0 |H| < |L|
SP L
H
H
H>0, L<0 |H| > |L|
H
SP
L
L SP SP H L
H<0, L>0 |H| ≥ |L| H>0, L<0 |H| ≤ |L|
*4
Set value: 5, Upper- and lower-limit with standby sequence For Upper- and Lower-Limit Alarm Described Above *2 • Case 1 and 2 Always OFF when the upper-limit and lower-limit hysteresis overlaps. • Case 3: Always OFF *5. Set value: 5, Upper- and lower-limit with standby sequence Always OFF when the upper-limit and lower-limit hysteresis overlaps. *6 Refer to the E5@C Digital Temperature Controllers User's Manual (Cat. No. H174) for information on the operation of the standby sequence. *7 Refer to the E5@C Digital Temperature Controllers User's Manual (Cat. No.H174) for information on the loop burnout alarm (LBA). *8 Refer to the E5@C Digital Temperature Controllers User's Manual (Cat. No. H174) for information on the PV change rate alarm. *9 When heating/cooling control is performed, the MV absolute upper limit alarm functions only for the heating operation and the MV absolute lower limit alarm functions only for the cooling operation. *10 This value is displayed only when a remote SP input is used. It functions in both Local SP Mode and Remote SP Mode. Remote SP input is supported only for the E5CC.
23
E5CC/E5CC-U Characteristics E5CC Thermocouple: (±0.3% of indication value or ±1°C, whichever is greater) ±1 digit max. *1 Platinum resistance thermometer: (±0.2% of indication value or ±0.8°C, whichever is greater) ±1 digit max. Analog input: ±0.2% FS ±1 digit max. Indication accuracy CT input: ±5% FS ±1 digit max. (at the ambient temperature of 23°C) E5CC-U Thermocouple: (±1% of indication value or ±2°C, whichever is greater) ±1 digit max. *1 Platinum resistance thermometer: (±0.2% of indication value or ±0.8°C, whichever is greater) ±1 digit max. Analog input: ±0.2% FS ±1 digit max. Transfer output accuracy ±0.3% FS max. Remote SP Input Type ±0.2% FS ±1 digit max. Influence of temperature *2 Thermocouple input (R, S, B, W, PL II): (±1% of indication value or ±10°C, whichever is greater) ±1 digit max. Other thermocouple input: (±1% of indication value or ±4°C, whichever is greater) ±1 digit max. *3 Platinum resistance thermometer: (±1% of indication value or ±2°C, whichever is greater) ±1 digit max. Influence of voltage *2 Analog input: ±1%FS ±1 digit max. CT input: ±5% FS ±1 digit max. Remote SP input: ±1% FS ±1 digit max. Input sampling period 50 ms Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F) Hysteresis Analog input: 0.01% to 99.99% FS (in units of 0.01% FS) Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F) Proportional band (P) Analog input: 0.1% to 999.9% FS (in units of 0.1% FS) Integral time (I) 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4 Derivative time (D) 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4 Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F) Proportional band (P) for cooling Analog input: 0.1% to 999.9% FS (in units of 0.1% FS) Integral time (I) for cooling 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4 Derivative time (D) for cooling 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4 Control period 0.1, 0.2, 0.5, 1 to 99 s (in units of 1 s) Manual reset value 0.0 to 100.0% (in units of 0.1%) Alarm setting range -1999 to 9999 (decimal point position depends on input type) Influence of signal source resistance Thermocouple: 0.1°C/Ω max. (100 Ωmax.) Platinum resistance thermometer: 0.1°C/Ω max. (10 Ω max.) Insulation resistance 20 MΩ min. (at 500 VDC) Dielectric strength 3,000 VAC, 50/60 Hz for 1 min between terminals of different charge Malfunction 10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions Vibration Resistance 10 to 55 Hz, 20 m/s2 for 2 hrs each in X, Y, and Z directions Malfunction 100 m/s2, 3 times each in X, Y, and Z directions Shock Resistance 300 m/s2, 3 times each in X, Y, and Z directions E5CC: Controller: Approx. 120 g, Adapter: Approx. 10 g Weight E5CC-U: Controller: Approx. 100 g, Adapter: Approx. 10 g E5CC: Front panel: IP66, Rear case: IP20, Terminals: IP00 Degree of protection E5CC-U: Front panel: IP50, Rear case: IP20, Terminals: IP00 Memory protection Non-volatile memory (number of writes: 1,000,000 times) E5CC: CX-Thermo version 4.5 or higher Setup Tool E5CC-U: CX-Thermo version 4.61 or higher E5CC/E5CC-U top panel: An E58-CIFQ2 USB-Serial Conversion Cable is used to connect to a USB Setup Tool port port on the computer. *5 Approved standards UL 61010-1*6, KOSHA certified (some models) *7, Korean Radio Waves Act (Act 10564) Standards Conformed standards EN 61010-1 (IEC 61010-1): Pollution Degree 2, overvoltage category II, Lloyd's standards *8 EMI: EN61326 Radiated Interference Electromagnetic Field Strength: EN 55011 Group 1, class A Noise Terminal Voltage: EN 55011 Group 1, class A EMS: EN 61326 ESD Immunity: EN 61000-4-2 EMC Electromagnetic Field Immunity: EN 61000-4-3 Burst Noise Immunity: EN 61000-4-4 Conducted Disturbance Immunity: EN 61000-4-6 Surge Immunity: EN 61000-4-5 Voltage Dip/Interrupting Immunity: EN 61000-4-11
*1 The indication accuracy of K thermocouples in the -200 to 1,300°C range, T and N thermocouples at a temperature of -100°C max., and U and L thermocouples at any temperatures is ±2°C ±1 digit max. The indication accuracy of the B thermocouple at a temperature of 400°C max. is not specified. The indication accuracy of B thermocouples at a temperature of 400 to 800°C is ±3°C max. The indication accuracy of the R and S thermocouples at a temperature of 200°C max. is ±3°C ±1 digit max. The indication accuracy of W thermocouples is (±0.3% of PV or ±3°C, whichever is greater) ±1 digit max. The indication accuracy of PL II thermocouples is (±0.3% of PV or ±2°C, whichever is greater) ±1 digit max. *2 Ambient temperature: -10°C to 23°C to 55°C, Voltage range: -15% to 10% of rated voltage *3 K thermocouple at -100°C max.: ±10°C max. *4 The unit is determined by the setting of the Integral/Derivative Time Unit parameter. *5 External communications (RS-485) and USB-serial conversion cable communications can be used at the same time. *6 The E5CC-U plug-in model is certified for UL listing only when used together with the OMRON P2CF-11 or P2CF-11-E Socket. The P3GA-11 is not certified for UL listing. *7 Access the following website for information on certified models. http://www.ia.omron.com/support/models/index.html *8 Refer to information on maritime standards in Shipping Standards on page 106 for compliance with Lloyd's Standards.
24
E5CC/E5CC-U USB-Serial Conversion Cable Windows XP, Vista, or 7
Applicable software
CX-Thermo version 4.5 or higher (Version 4.61 or higher is required for the E5CC-U.)
Applicable models
E5@C-T Series, E5@C Series, and E5CB Series
USB interface standard
Conforms to USB Specification 2.0.
DTE speed
38400 bps
Connector specifications
Computer: USB (type A plug) Digital Temperature Controller: Special serial connector
Power supply
Bus power (Supplied from USB host controller.)*
Power supply voltage
5 VDC
Current consumption
450 mA max.
Output voltage
4.7±0.2 VDC (Supplied from USB-Serial Conversion Cable to the Digital Temperature Controller.)
Output current
250 mA max. (Supplied from USB-Serial Conversion Cable to the Digital Temperature Controller.)
Ambient operating temperature
0 to 55°C (with no condensation or icing)
Ambient operating humidity
10% to 80%
Storage temperature
-20 to 60°C (with no condensation or icing)
Storage humidity
10% to 80%
Altitude
2,000 m max.
Weight
Approx. 120 g
Windows is a registered trademark of Microsoft Corporation in the United States and or other countries. * Use a high-power port for the USB port. Note: A driver must be installed on the computer. Refer to the Instruction Manual included with the Cable for the installation procedure.
Communications Specifications Transmission line connection method
RS-485: Multidrop
Communications
RS-485 (two-wire, half duplex)
Synchronization method
Start-stop synchronization
Protocol
CompoWay/F, or Modbus
Baud rate*
9600, 19200, 38400, or 57600 bps
Transmission code
ASCII
Data bit length*
7 or 8 bits
Stop bit length*
1 or 2 bits
Error detection
Vertical parity (none, even, odd) Block check character (BCC) with CompoWay/F or CRC-16 Modbus
Flow control
None
Interface
RS-485
Retry function
None
Communications buffer 217 bytes Communications response wait time
0 to 99 ms Default: 20 ms
* The baud rate, data bit length, stop bit length, and vertical parity can be individually set using the Communications Setting Level.
Communications Functions
Programless communications*1
You can use the memory in the PLC to read and write E5@C parameters, start and stop operation, etc. The E5@C automatically performs communications with PLCs. No communications programming is required. Number of connected Digital Temperature Controllers: 32 max. (Up to 16 for the FX Series) Applicable PLCs OMRON PLCs CS Series, CJ Series, or CP Series Mitsubishi Electric PLCs MELSEC Q Series, L Series, or FX Series (compatible with the FX2 or FX3 (excluding the FX1S)) KEYENCE PLCs KEYENCE KV Series
Component Communications*1
When Digital Temperature Controllers are connected, set points and RUN/STOP commands can be sent from the Digital Temperature Controller that is set as the master to the Digital Temperature Controllers that are set as slaves. Slope and offsets can be set for the set point. Number of connected Digital Temperature Controllers: 32 max. (including master)
Copying*2
When Digital Temperature Controllers are connected, the parameters can be copied from the Digital Temperature Controller that is set as the master to the Digital Temperature Controllers that are set as slaves.
MELSEC is a registered trademark of Mitsubishi Electric Corporation. KEYENCE is a registered trademark of Keyence Corporation. *1 A Temperature Controller with version 1.1 or higher is required. A Temperature Controller with version 2.1 or higher is required for the FX Series or the KV Series. *2 Both the programless communications and the component communications support the copying.
Current Transformer (Order Separately) Ratings Dielectric strength Vibration resistance Weight Accessories (E54-CT3 only)
1,000 VAC for 1 min 50 Hz, 98 m/s2 E54-CT1: Approx. 11.5 g, E54-CT3: Approx. 50 g Armatures (2) Plugs (2)
Heater Burnout Alarms and SSR Failure Alarms CT input (for heater current detection) Maximum heater current Input current indication accuracy Heater burnout alarm setting range *1 SSR failure alarm setting range *2
Models with detection for single-phase heaters: One input Models with detection for singlephase or three-phase heaters: Two inputs 50 A AC ±5% FS ±1 digit max. 0.1 to 49.9 A (in units of 0.1 A) Minimum detection ON time: 100 ms *3 0.1 to 49.9 A (in units of 0.1 A) Minimum detection OFF time: 100 ms *4
*1 For heater burnout alarms, the heater current will be measured when the control output is ON, and the output will turn ON if the heater current is lower than the set value (i.e., heater burnout detection current value). *2 For SSR failure alarms, the heater current will be measured when the control output is OFF, and the output will turn ON if the heater current is higher than the set value (i.e., SSR failure detection current value). *3 The value is 30 ms for a control period of 0.1 s or 0.2 s. *4 The value is 35 ms for a control period of 0.1 s or 0.2 s.
Electrical Life Expectancy Curve for Relays (Reference Values) Life (× 104 operations)
Applicable OS
500 300
100 50 30
10 5
E5CC 250 VAC, 30 VDC (resistive load) cosφ = 1
3
1
0
1
2
3
4
5
6
Switching current (A)
25
E5CC/E5CC-U External Connections E5CC Control output 1
E5CC-@@ 3 @ 5 M - @ @ @
Relay output 250 VAC, 3A (resistive load) Voltage output (for driving SSR) 12 VDC, 21 mA Linear current output 0 to 20 mA DC 4 to 20 mA DC Load: 500 Ω max.
(1) Auxiliary outputs 1, 2, 3
(1) Control outputs 1, 2 RX QX Models with 1 Relay Output
1 2 3
QQ
CX
OUT1 + - Q
(5) Sensor (Temperature/Analog) Input Pt TC V I A + 4 4 4 4 B mA - 5 - 5 5 5 B V 6 6 6 + 6 + (6) Options 001 Event Inputs 1 and 2, and CT1 -
B(+) RS-485
+
14 + EV1 15 EV2 CT1
A(-)
17
COM
CT2
18
13 14
3 4 5
15 16
004 Communications (RS-485), and Event Inputs 3 and 4 B(+)
13
RS-485
14
A(-)
8 9 10 11
17 18
12
-
13
+
14
+
Auxiliary output 1 ●
●
11
11
12
12
-
16 +
17
+
18
EV3
EV1
+
17
+
18
EV4
006 Event Inputs 1 and 2, and Transfer Output
13 14
EV2
EV3
EV4
15
13 14 + EV1 15 EV2
16
16
-
+
17
17
18
18
+ +V I
E5CC-UM-000
The E5CC-U is set for a K-type thermocouple (input type = 5) by default. An input error (s.err) will occur if the input type setting does not agree with the temperature sensor. Check the input type.
Control output 1 Auxiliary outputs 1, 2 Relay output 250 VAC, 3 A (resistive load)
Control output 1
Auxiliary output 1 Auxiliary output 2: Control output (cooling side)
I Pt
+ V
mA
−
A
TC
−
−
B
+
+
B
V
Input power supply
Sensor (temperature/analog) input Control output 1
• 100 to 240 VAC • 24 VAC/DC (no polarity)
Control output 1:
−
Output 1 Q
+
RW
CX
QX Models with 1 Voltage Output (for Driving SSR)
Models with 1 Relay Output
Models with 1 Linear Current Output
− Output 1 C
Output 1 R
+
Note: 1. The application of the terminals depends on the model. 2. Do not wire the terminals that are shown with a gray background. 3. When complying with EMC standards, the cable that connects the sensor must be 30 m or less. If the cable length exceeds 30 m, compliance with EMC standards will not be possible. 4. Connect M3 crimped terminals. Connect M3.5 crimped terminals for the E5CC-U.
26
Auxiliary output 2
(3) Input Power Supply 100 to 240 VAC 24 VAC/DC
E5CC-U
Voltage output (for driving SSR) 12 VDC, 21 mA Linear current output 4 to 20 mA DC 0 to 20 mA DC Load: 500 Ω max. Relay output (three terminals used) SPDT, 250 VAC, 3 A (resistive load)
Auxiliary output 3
7
005 Event Inputs 1 to 4
15
16
CT1
1 2
7 8 9 10
(no polarity)
15
16
(2) Auxiliary Outputs Auxiliary outputs 1, 2, 3
OUT1 +C - Q + OUT2
1 2 3
6
003 Communications (RS-485), CT1, and CT2
13
The E5CC is set for a K-type thermocouple (input type = 5) by default. An input error (s.err) will occur if the input type setting does not agree with the temperature sensor. Check the input type.
Models with 2 Outputs: Linear Current Output and Voltage (for Driving SSR)
OUT1 +Q - Q + OUT2
OUT1 1 + - C 2 3
1 2 3
(6)
CQ
Models with 2 Models with Voltage Outputs 1 Linear Current Output (for Driving SSR)
Models with 1 Voltage Output (for Driving SSR)
OUT1 1 R 2 3
Relay outputs Models with 3 auxiliary outputs: 250 VAC, 2 A (resistive load)
Control output 2 Voltage output (for driving SSR) 12 VDC, 21 mA
(2) (3) (4) (5) ↑ Terminal type
-
007 Event Inputs 1 and 2, and Remote SP Input 13 + 14 + EV1 15 EV2 + 16 V + 17 mA 18
E5CC/E5CC-U
Isolation/Insulation Block Diagrams • E5CC
Models with 3 Auxiliary Outputs Sensor input, CT inputs, and remote SP input Communications and event inputs Voltage output (for driving SSR), linear current output, and transfer output
Power supply
Relay output Auxiliary outputs 1, 2, 3
: Reinforced insulation : Functional isolation
Note: Auxiliary outputs 1 to 3 are not insulated. • E5CC-U
Models with 2 Auxiliary Outputs Sensor input Power supply
Voltage output (for driving SSR) and linear current output Relay output Auxiliary outputs 1 and 2
: Reinforced insulation : Functional isolation
Nomenclature E5CC E5CC-U
Front panel Temperature unit Operation indicators
Top View of E5CC
Top View of E5CC-U
No. 1 display
PV or specified parameter No. 2 display
SP or specified parameter value
Use the U D Keys to set the parameter.
Top-panel Setup Tool port
Press O Key once to go to Adjustment Level.
Use S Key to change the digit (default setting).
Press O Key for at least 3 seconds to go to Initial Setting Level. Use the M Key to change to another parameter.
27
E5CC/E5CC-U
Dimensions
(Unit: mm)
Controllers E5CC 73.1 60
4 48 × 48
1
48 × 48
44.8 × 44.8 48.8 58
Waterproof Packing (Accessory)
Mounting Adapter (Accessory)
Terminal Cover (E53-COV17) (Sold separately)
The Setup Tool port is on the top of the Temperature Controller. It is used to connect the Temperature Controller to the computer to use the Setup Tool. The E58-CIFQ2 USB-Serial Conversion Cable is required to make the connection. Refer to the instructions that are provided with the USB-Serial Conversion Cable for the connection procedure.
Note: Do not leave the USB-Serial Conversion Cable connected when you use the Temperature Controller. Panel Cutout Mounted Separately Group Mounted (48 × number of units - 2.5)+1.0 0
• Recommended panel thickness is 1 to 5 mm. • Group mounting is not possible in the vertical direction. (Maintain the specified mounting space between Controllers.) • To mount the Controller so that it is waterproof, insert the waterproof packing onto the Controller. • When two or more Controllers are mounted, make sure that the surrounding temperature does not exceed the allowable operating temperature specified in the specifications. • Use a control panel thickness of 1 to 3 mm if the Y92A-48N and a USB-Serial Conversion Cable are used together.
45+0.6 0
60 min.
45+0.6 0
45+0.6 0
E5CC-U 48 × 48
4
76.8 58.6
14.2 48 × 48
58
Mounting Adapter (Accessory)
The Setup Tool port is on the top of the Temperature Controller. It is used to connect the Temperature Controller to the computer to use the Setup Tool. The E58-CIFQ2 USB-Serial Conversion Cable is required to make the connection. Refer to the instructions that are provided with the USB-Serial Conversion Cable for the connection procedure.
Note: Do not leave the USB-Serial Conversion Cable connected when you use the Temperature Controller. Panel Cutout Mounted Separately Group Mounted (48 × number of units - 2.5)+1.0 0
45+0.6 0
60 min.
45+0.6 0
45+0.6 0
28
• Recommended panel thickness is 1 to 5 mm. • Group mounting is not possible in the vertical direction. (Maintain the specified mounting space between Controllers.) • When two or more Controllers are mounted, make sure that the surrounding temperature does not exceed the allowable operating temperature specified in the specifications. • Use a control panel thickness of 1 to 3 mm if the Y92A-48N and a USB-Serial Conversion Cable are used together.
E5CC/E5CC-U Accessories (Order Separately) ● USB-Serial Conversion Cable E58-CIFQ2
(2110)
250
263
1510
LED (RD)
USB connector (type A plug)
Serial connector
LED (PWR) LED (SD)
● Terminal Covers E53-COV17
● Terminal Covers E53-COV23 (Three Covers provided.)
48
2
3.8
48.8
10 Terminal Cover (E53-COV23) 22
44.8
9.1
● Terminal Cover (for the P3GA-11 Back-connecting Socket) Y92A-48G Twelve, 6.4-dia.
34
Y92A-48G
UP
47.7×47.7
48×48
P C
16.5
24.6 27.6
47.4
Note: You can attach the P3GA-11 Back-connecting Socket for finger protection.
● Waterproof Packing Y92S-P8 (for DIN 48 × 48)
The Waterproof Packing is provided only with the E5CC. Order the Waterproof Packing separately if it becomes lost or damaged. The Waterproof Packing can be used to achieve an IP66 degree of protection. (Deterioration, shrinking, or hardening of the waterproof packing may occur depending on the operating environment. Therefore, periodic replacement is recommended to ensure the level of waterproofing specified in IP66. The time for periodic replacement depends on the operating environment. Be sure to confirm this point at your site. Consider three years as a rough standard.) The Waterproof Packing does not need to be attached if a waterproof structure is not required. The E5CC-U cannot be waterproofed even if the Waterproof Packing is attached.
29
E5CC/E5CC-U ● Current Transformers E54-CT1
21 15
Thru-current (Io) vs. Output Voltage (Eo) (Reference Values) E54-CT1
2.8 5.8 dia. 7.5
25
Maximum continuous heater current: 50 A (50/60 Hz) Number of windings: 400±2 Winding resistance: 18±2 Ω
3
Output voltage (Eo) V (r.m.s.)
10.5 40 Two, 3.5 dia. 10 30
100V
Frequency: 50 Hz ∞ 1kΩ
10
Distortion factor 10%
1
3% 1%
100mV 100Ω
10
E54-CT3 2.36 dia. 30
RL=10Ω
1 12 dia. 9
100μV 10 1
40 × 40
10
100mA
1
10
100 1,000A
Thru-current (Io) A (r.m.s.)
Thru-current (Io) vs. Output Voltage (Eo) (Reference Values) E54-CT3
Two, M3 (depth: 4) 15
E54-CT3 Accessories • Armature Approx. 3 dia.
Connection Example Plug
Armature
Lead
18
• Plug
Output voltage (Eo) V (r.m.s.)
Maximum continuous heater current: 120 A (50/60 Hz) (Maximum continuous heater current for an OMRON Digital Temperature Controller is 50 A.) Number of windings: 400±2 Winding resistance: 8±0.8 Ω
30
100V
Frequency: 50 Hz Distortion factor 10% 3% 1%
∞ 1kΩ 500Ω
10 1 100mV
100Ω 50Ω
10
RL=10Ω 1
Approx. 6 dia.
100μV (22) 10 1
10
100mA
1
10
100 1,000A
Thru-current (Io) A (r.m.s.)
30
E5CC/E5CC-U ● Adapter Y92F-45
Note: 1. Use this Adapter when the Front Panel has already been prepared for the E5B@. 2. Only black is available. 3. You cannot use the E58-CIFQ2 USB-Serial Conversion Cable if you use the Y92F-45 Adapter. To use the USB-Serial Conversion Cable to make the settings, do so before you mount the Temperature Controller in the panel. Fixture (Accessory) 76
4.7
69.6 to 77.6 72 × 72
67 × 67 87
Mounted to E5CC
Panel (1 to 8 mm)
Mounting Adapter Y92F-30 (Accessory)
72 × 72
48 × 48
2.2
4.7 62.8 To back of the E5CC
● DIN Track Mounting Adapter Y92F-52
Note: This Adapter cannot be used together with the Terminal Cover. Remove the Terminal Cover to use the Adapter.
61
3.5
This Adapter is used to mount the E5CC to a DIN Track. If you use the Adapter, there is no need for a plate to mount in the panel or to drill mounting holes in the panel.
38
50
Mounted to E5CC
48
80.5
31
E5CC/E5CC-U
● Watertight Cover
● Mounting Adapter
Y92A-48N
Y92F-49 21.9
14
The Mounting Adapter is provided with the Temperature Controller. Order this Adapter separately if it becomes lost or damaged.
(2)
87.7
69
79.2
12 67.6
● Protective Cover
● Protective Cover
Y92A-48D
Y92A-48H
Note: This Protective Cover cannot be used if the Waterproof Packing is installed.
This Protective Cover is hard type. Please use it for the mis-operation prevention etc.
This Protective Cover is soft type. It is able to operate the controller with using this cover.
● E5CC-U Wiring Socket Front-connecting Socket P2CF-11 Eleven, M3.5 × 7.5 sems screws
3
Terminal Layout/Internal Connections (Top View)
4.5
7.8
8 7 6 5
Mounting Holes
4
Two, 4.5 dia. mounting holes 35.4
70 max. Two, 4.5-dia. holes
4
50 max.
40±0.2
9 3 10 11 1 2
Note: Can also be mounted to a DIN track
31.2 max.
Note: 1. A model with finger protection (P2CF-11-E) is also available. 2. You cannot use the P2CF-11 or P2CF-11-E together with the Y92F-45.
Back-connecting Socket P3GA-11 27dia.
4
7
3
Eleven, M3.5 sems screws
Terminal Layout/Internal Connections (Bottom View) 5 6 7 8 4
45
25.6
3 9 2 1 11 10 45
4.5 16.3 6.2
6 8.7
Note: 1. Using any other sockets will adversely affect accuracy. Use only the specified sockets. 2. A Protective Cover for finger protection (Y92A-48G) is also available. 3. You cannot use the P3GA-11 together with the Y92F-45.
32
MEMO
33
Digital Temperature Controller
E5EC/E5AC
(48 × 96 mm/96 × 96 mm)
Large White PV Display That’s Easier to Read. Easy to Use, from Model Selection to Setup and Operation. A Complete Range of I/O Capacities, Functions, and Performance. Handles More Applications. • A white LCD PV display with a height of approx. 18 mm for the E5EC and 25 mm for the E5AC improves visibility. • Tool ports are provided both on the top panel and the front panel. Set up the Controller without wiring the power supply by 96 × 96 mm 48 × 96 mm connecting to the computer with a Communications Conversion E5AC E5EC Cable (sold separately). Setup is easy with the CX-Thermo (sold Refer to your OMRON website for the most recent separately). information on applicable safety standards. • High-speed sampling at 50 ms. • Models are available with up to 4 auxiliary outputs, up to 6 event Refer to Safety Precautions on page 104. inputs, a transfer output, and a remote SP input to cover a wide range of applications. • Short body with depth of only 60 mm. • Easy connections to a PLC with programless communications. Use component communications to link Temperature Controllers to each other. • The new position-proportional control models allow you to control valves as well.
Main I/O Functions Sensor Input Universal input • Thermocouple • Pt • Analog current/voltage
E5EC
E5AC
Three-level Display PV, SV, and MV displayed at the same time.
4-digit displays
Indication Accuracy • Thermocouple input: ±0.3% of PV • Pt input: ±0.2% of PV • Analog input: ±0.2% of FS
Control Output 1 • Relay output • Voltage output (for driving SSR) • Linear current output
Sampling Period
Control Output 2 • Voltage output (for driving SSR) • Relay output • Linear current output
• 50 ms Event Inputs • None •2 •4 •6 Remote SP Input • None •1
• PF (shift) Key • Setup Tool port on front panel • Temperature status display • Simple programming • Independent heating and cooling PID control • Changed parameter display • Display brightness setting
Auxiliary Outputs •4 Transfer Output • None •1
Serial Communications • None • RS-485
This datasheet is provided as a guideline for selecting products. Be sure to refer to the following manuals for application precautions and other information required for operation before attempting to use the product. E5@C Digital Temperature Controllers User’s Manual (Cat. No. H174) E5@C Digital Temperature Controllers Communications Manual (Cat. No. H175)
34
E5EC/E5AC
Model Number Legend and Standard Models Model Number Legend ●Models with Screw Terminals E5EC-@@ 4 @ 5 M -@@@ (Example: E5EC-RX4A5M-000) −− − − − − −−− A B C D E F
E5AC-@@ 4 @ 5 M -@@@ (Example: E5AC-RX4A5M-000) −− − − − − −−− A B C D E F A Model
B
C
D
E
F
No. of auxil- Power Terminal Input Options iary out- supply type type puts voltage
Control outputs 1 and 2
Meaning 48 × 96 mm 96 × 96 mm Control output 1 Relay output Voltage output (for driving SSR) Linear current output Voltage output (for driving SSR) Voltage output (for driving SSR) Relay output
E5EC E5AC RX QX *2 CX QQ QR RR
*2 CQ PR *3 4 A D 5 For RX, For CX or QX, QQ, QR, RR, or CC CQ
M
For PR
Selectable Selectable Selectable Selectable Selectable Option Selectable selection conditions *1 Selectable Selectable Selectable Selectable Selectable Selectable
None None Voltage output (for driving SSR) Relay output
Relay output Linear current outLinear current output put Voltage output Linear current output (for driving SSR) Position-proportionPosition-proportional relay output al relay output 4 (auxiliary outputs 1 and 2 with same common and auxiliary outputs 3 and 4 with same common) 100 to 240 VAC 24 VAC/DC Screw terminals (with cover) Universal input
*2 CC
Control outputs 1 and 2
Control output 2 None
000 004 005 009 010 011 013 014
HB alarm Event Remote Transfer and Communications inputs SP Input output HS alarm ------------RS-485 2 --------4 ----2 (for 3-phase RS-485 2 ----heaters) 1 --4 ----1 --6 Provided. Provided. ----6 Provided. Provided. --RS-485 4 Provided. Provided.
*1. The options that can be selected depend on the type of control output. *2. The control output cannot be used as a transfer output. *3. A model with four auxiliary outputs must be selected.
Heating and Cooling Control l Using Heating and Cooling Control A Control Output Assignment If there is no control output 2, an auxiliary output is used as the cooling control output. If there is a control output 2, the two control outputs are used for heating and cooling. (It does not matter which output is used for heating and which output is used for cooling.) B Control If PID control is used, you can set PID control separately for heating and cooling. This allows you to handle control systems with different heating and cooling response characteristics.
35
E5EC/E5AC Optional Products (Order Separately) USB-Serial Conversion Cable Model E58-CIFQ2
Communications Conversion Cable
Note: Always use this product together with the E58-CIFQ2. This Cable is used to connect to the front-panel Setup Tool port.
Terminal Covers Model E53-COV24 (3pcs) Note: The Terminal Covers E53-COV24 are provided with the Digital Temperature Controller.
Waterproof Packing Model Y92S-P9 Y92S-P10
Note: This Waterproof Packing is provided with the Digital Temperature Controller.
Waterproof Cover Applicable Controller E5EC E5AC
Model Y92A-49N Y92A-96N
Front Port Cover Model Y92S-P7 Note: This Front Port Cover is provided with the Digital Temperature Controller.
Mounting Adapter Model Y92F-51 (2pcs) Note: This Mounting Adapter is provided with the Digital Temperature Controller.
36
Hole diameter 5.8 mm 12.0 mm
Model E54-CT1 E54-CT3
CX-Thermo Support Software
Model E58-CIFQ2-E
Applicable Controller E5EC E5AC
Current Transformers (CTs)
Model EST2-2C-MV4 Note: CX-Thermo version 4.5 or higher is required for the E5EC/ E5AC. For the system requirements for the CX-Thermo, refer to information on the EST2-2C-MV4 on the OMRON website (www.ia.omron.com).
E5EC/E5AC Specifications Ratings Power supply voltage Operating voltage range E5EC Power consumption E5AC
Sensor input
Input impedance Control method Relay output Control output
Auxiliary output
Voltage output (for driving SSR) Linear current output Number of outputs Output specifications Number of inputs
Event input External contact input specifications Transfer output
Number of outputs Output specifications
Remote SP input Potentiometer input Setting method
Indication method
Multi SP Bank switching
Other functions
Ambient operating temperature Ambient operating humidity Storage temperature Altitude Recommended fuse Installation environment
A in model number: 100 to 240 VAC, 50/60 Hz D in model number: 24 VAC, 50/60 Hz; 24 VDC 85% to 110% of rated supply voltage Models with option selection of 000:6.6 VA max. at 100 to 240 VAC, and 4.1 VA max. at 24 VAC or 2.3 W max. at 24 VDC All other models: 8.3 VA max. at 100 to 240 VAC, and 5.5 VA max. at 24 VAC or 3.2 W max. at 24 VDC Models with option selection of 000:7.0 VA max. at 100 to 240 VAC, and 4.2 VA max. at 24 VAC or 2.4 W max. at 24 VDC All other models: 9.0 VA max. at 100 to 240 VAC, and 5.6 VA max. at 24 VAC or 3.4 W max. at 24 VDC Temperature input Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II Platinum resistance thermometer: Pt100 or JPt100 Infrared temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C Analog input Current input: 4 to 20 mA or 0 to 20 mA Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V Current input: 150 Ω max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB/THB.) ON/OFF or 2-PID control (with auto-tuning) SPST-NO, 250 VAC, 5 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA (reference value) Output voltage: 12 VDC ±20% (PNP), max. load current: 40 mA, with short-circuit protection circuit (The maximum load current is 21 mA for models with two control outputs.) 4 to 20 mA DC/0 to 20 mA DC, load: 500 Ω max., resolution: approx. 10,000 4 SPST-NO. relay outputs, 250 VAC, Models with 4 outputs: 2 A (resistive load), Electrical life: 100,000 operations, Minimum applicable load: 10 mA at 5 V (reference value) 2, 4 or 6 (depends on model) Contact input: ON: 1 kΩ max., OFF: 100 kΩ min. Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max. Current flow: Approx. 7 mA per contact 1 (only on models with a transfer output) Current output: 4 to 20 mA DC, Load: 500 Ω max., Resolution: Approx. 10,000 Linear voltage output: 1 to 5 VDC, load: 1 kΩ min., Resolution: Approx. 10,000 Current input: 4 to 20 mA DC or 0 to 20 mA DC (input impedance: 150 Ω max.) Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V (input impedance: 1 MΩ min.) 100 Ω to 10 kΩ Digital setting using front panel keys 11-segment digital display and individual indicators Character height: E5EC: PV: 18.0 mm, SV: 11.0 mm, MV: 7.8 mm E5AC: PV: 25.0 mm, SV: 15.0 mm, MV: 9.5 mm Three displays Contents: PV/SV/MV, PV/SV/Multi-SP, or PV/SV/Remaining soak time Numbers of digits: 4 digits each for PM, SV, and MV displays Up to eight set points (SP0 to SP7) can be saved and selected using the event inputs, key operations, or serial communications. None Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater burnout (HB) alarm (including SSR failure (HS) alarm), 40% AT, 100% AT, MV limiter, input digital filter, self tuning, robust tuning, PV input shift, run/stop, protection functions, extraction of square root, MV change rate limit, logic operations, temperature status display, simple programming, moving average of input value, and display brightness setting −10 to 55°C (with no condensation or icing), For 3-year warranty: −10 to 50°C with standard mounting (with no condensation or icing) 25% to 85% -25 to 65°C (with no condensation or icing) 2,000 m max. T2A, 250 VAC, time-lag, low-breaking capacity Installation Category II, Pollution Degree 2 (IEC 61010-1 compliant)
37
E5EC/E5AC Input Ranges ●Thermocouple/Platinum Resistance Thermometer (Universal inputs) Sensor type
Platinum resistance thermometer
Sensor specification
Pt100
Infrared temperature sensor
Thermocouple
JPt100
K
J
T
E
L
U
N
R
S
B
W
PLII
10 to 70°C
60 to 120°C
115 to 165°C
120
165
140 to 260°C
2300
2300
1800
1800
1700
1700
1700
Temperature range (°C)
1600 1500 1400
1300
1300
1300
1300
1200 1100 1000 900
850
850
850
800 700
600
600
500.0
500
500.0
500.0 400.0
400
400
400.0
400
400.0 260
300 200
100.0
100
90
100 0.0
-100 -200
100.0
-200
-199.9
0
1
Set value
0.0 -199.9
2
3
-20.0
-100
-20.0
6
7
8
-200
4
5
0
0
16
17
0
0
0
0
0
0
19
20
21
22
23
24
-100 -200
-199.9
-200
9
10
11
12
-200
-199.9
-200
13
14
15
18
Shaded settings are the default settings. The applicable standards for the input types are as follows: K, J, T, E, N, R, S, B: JIS C 1602-1995, IEC 60584-1 L: Fe-CuNi, DIN 43710-1985 U: Cu-CuNi, DIN 43710-1985 W: W5Re/W26Re, ASTM E988-1990
JPt100: JIS C 1604-1989, JIS C 1606-1989 Pt100: JIS C 1604-1997, IEC 60751 PL II: According to Platinel II electromotive force charts from BASF (previously Engelhard)
●Analog input Input type Input specification Setting range Set value
38
Current 4 to 20 mA 0 to 20 mA
Voltage 1 to 5 V
0 to 5 V
Usable in the following ranges by scaling: -1999 to 9999, -199.9 to 999.9, -19.99 to 99.99 or -1.999 to 9.999 25 26 27 28
0 to 10 V
29
E5EC/E5AC Alarm Types Each alarm can be independently set to one of the following 19 alarm types. The default is 2: Upper limit. (see note.) Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified. Note: In the default settings for models with HB or HS alarms, alarm 1 is set to a heater alarm (HA) and the Alarm Type 1 parameter is not displayed. To use alarm 1, set the output assignment to alarm 1. Set value
Alarm type
0
Alarm function OFF
1
Upper- and lower-limit *1
2 Upper-limit (default) 3
Lower-limit
4
Upper- and lower-limit range *1
Alarm output operation Description of function When alarm value X When alarm value X is positive is negative Output OFF No alarm Set the upward deviation in the set point for the alarm upper L H limit (H) and the lower deviation in the set point for the alarm ON *2 OFF PV lower limit (L). The alarm is ON when the PV is outside this SP deviation range. Set the upward deviation in the set point by setting the alarm X X ON ON value (X). The alarm is ON when the PV is higher than the OFF PV OFF PV SP SP SP by the deviation or more. Set the downward deviation in the set point by setting the X X ON ON alarm value (X). The alarm is ON when the PV is lower than OFF PV OFF PV SP SP the SP by the deviation or more. Set the upward deviation in the set point for the alarm upper L H limit (H) and the lower deviation in the set point for the alarm ON *3 OFF PV lower limit (L). The alarm is ON when the PV is inside this deSP viation range.
Upper- and lower-limit with standby sequence *1 *5 Upper-limit with standby sequence
ON OFF
7
Lower-limit with standby sequence
ON OFF
8
Absolute-value upper-limit
ON OFF
9
Absolute-value lower-limit
ON OFF
10
Absolute-value upper-limit with standby sequence
ON OFF
11
Absolute-value lower-limit with standby sequence
ON OFF
12 13
LBA (alarm 1 type only) PV change rate alarm
14
SP absolute-value upper-limit alarm
ON OFF
15
SP absolute-value lower-limit alarm
ON OFF
5 6
L
H
X
ON OFF
SP
PV
ON OFF
PV
ON OFF
PV
ON OFF
PV
ON OFF
PV
ON OFF
PV
ON OFF
X SP X 0 X 0 X 0 X 0
ON OFF
MV absolute-value upper-limit alarm *9
X 0
PV
A standby sequence is added to the upper-limit alarm (2). *6
PV
A standby sequence is added to the lower-limit alarm (3). *6
X SP X 0
PV
X 0
PV
The alarm will turn ON if the process value is smaller than the alarm value (X) regardless of the set point.
PV
A standby sequence is added to the absolute-value upperlimit alarm (8). *6
PV
A standby sequence is added to the absolute-value lowerlimit alarm (9). *6
X 0 X 0
ON OFF
SP
ON OFF
X 0
X 0
SP
This alarm type turns ON the alarm when the set point (SP) is higher than the alarm value (X).
SP
This alarm type turns ON the alarm when the set point (SP) is lower than the alarm value (X).
X 0
Standard Control
X MV
0
The alarm will turn ON if the process value is larger than the alarm value (X) regardless of the set point.
*7 *8
SP
ON OFF
X 0
MV
X MV
0
Standard Control ON OFF
17
SP
This alarm type turns ON the alarm when the manipulated Heating/Cooling Heating/Cooling variable (MV) is higher than the alarm value (X). Control (Heating MV) Control (Heating MV) ON OFF
MV absolute-value lower-limit alarm *9
X
-
Standard Control
16
A standby sequence is added to the upper- and lower-limit alarm (1). *6
*4
PV
SP
X MV
0
Always ON Standard Control ON OFF
X 0
MV
This alarm type turns ON the alarm when the manipulated Heating/Cooling Heating/Cooling variable (MV) is lower than the alarm value (X). Control (Cooling MV) Control (Cooling MV) ON OFF
18
RSP absolute-value upper-limit alarm *10
ON OFF
19
RSP absolute-value lower-limit alarm *10
ON OFF
X MV
0 X 0
RSP
ON OFF
RSP
ON OFF
X 0
Always ON X 0
RSP
This alarm type turns ON the alarm when the remote SP (RSP) is higher than the alarm value (X).
RSP
This alarm type turns ON the alarm when the remote SP (RSP) is lower than the alarm value (X).
X 0
39
E5EC/E5AC *1
With set values 1, 4 and 5, the upper and lower limit values can be set independently for each alarm type, and are expressed as “L” and “H.” *2. Set value: 1, Upper- and lower-limit alarm Case 2
Case 1
Case 3 (Always ON)
H<0, L<0 L
H SP
H<0, L>0 |H| < |L|
H
SP L H H>0, L<0 |H| > |L|
H
SP
L H<0, L>0 |H| ≥ |L|
L SP SP H
L
H>0, L<0 |H| ≤ |L|
*3. Set value: 4, Upper- and lower-limit range Case 1
L
Case 3 (Always OFF)
Case 2
H SP
H<0, L>0 |H| < |L|
SP L
H
H
H>0, L<0 |H| > |L|
H
SP
L
L SP SP H L
40
H<0, L<0 H<0, L>0 |H| ≥ |L| H>0, L<0 |H| ≤ |L|
*4. Set value: 5, Upper- and lower-limit with standby sequence For Upper- and Lower-Limit Alarm Described Above *2 • Case 1 and 2 Always OFF when the upper-limit and lower-limit hysteresis overlaps. • Case 3: Always OFF *5. Set value: 5, Upper- and lower-limit with standby sequence Always OFF when the upper-limit and lower-limit hysteresis overlaps. *6. Refer to the E5@C Digital Temperature Controllers User's Manual (Cat. No. H174) for information on the operation of the standby sequence. *7. Refer to the E5@C Digital Temperature Controllers User's Manual (Cat. No. H174) for information on the loop burnout alarm (LBA). This setting cannot be used with a position-proportional model. *8. Refer to the E5@C Digital Temperature Controllers User's Manual (Cat. No. H174) for information on the PV change rate alarm. *9. When heating/cooling control is performed, the MV absolute upper limit alarm functions only for the heating operation and the MV absolute lower limit alarm functions only for the cooling operation. *10. This value is displayed only when a remote SP input is used. It functions in both Local SP Mode and Remote SP Mode.
E5EC/E5AC Characteristics Thermocouple: (±0.3% of indication value or ±1°C, whichever is greater) ±1 digit max. *1 Platinum resistance thermometer: (±0.2% of indication value or ±0.8°C, whichever is greater) ±1 digit max. Analog input: ±0.2% FS ±1 digit max. CT input: ±5% FS ±1 digit max. Potentiometer input: ±5% FS ±1 digit max. Transfer output accuracy ±0.3% FS max. Remote SP Input Type ±0.2% FS ±1 digit max. Thermocouple input (R, S, B, W, PL II): (±1% of indication value or ±10°C, whichever is greater) ±1 digit Influence of temperature *2 max. Other thermocouple input: (±1% of indication value or ±4°C, whichever is greater) ±1 digit max. *3 Platinum resistance thermometer: (±1% of indication value or ±2°C, whichever is greater) ±1 digit max. Analog input: ±1%FS ±1 digit max. Influence of voltage *2 CT input: ±5% FS ±1 digit max. Remote SP input: ±1% FS ±1 digit max. Input sampling period 50ms Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or°F) Hysteresis Analog input: 0.01% to 99.99% FS (in units of 0.01% FS) Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F) Proportional band (P) Analog input: 0.1 to 999.9% FS (in units of 0.1% FS) Standard, heating/cooling, or Position-proportional (Close): 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in Integral time (I) units of 0.1 s) Position-proportional (Floating): 1 to 9999 s (in units of 1 s), 0.1 to 999.9 s (in units of 0.1 s)*4 Derivative time (D) 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4 Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F) Proportional band (P) for cooling Analog input: 0.1 to 999.9% FS (in units of 0.1% FS) Integral time (I) for cooling 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4 Derivative time (D) for cooling 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4 Control period 0.1, 0.2, 0.5, 1 to 99 s (in units of 1 s) Manual reset value 0.0 to 100.0% (in units of 0.1%) Alarm setting range -1999 to 9999 (decimal point position depends on input type) Influence of signal source resisThermocouple: 0.1°C/Ω max. (100 Ω max.) tance Platinum resistance thermometer: 0.1°C/Ω max. (10 Ω max.) Insulation resistance 20 MΩ min. (at 500 VDC) Dielectric strength 3,000 VAC, 50/60 Hz for 1 min between terminals of different charge Malfunction 10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions Vibration Resistance 10 to 55 Hz, 20 m/s2 for 2 hrs each in X, Y, and Z directions Malfunction 100 m/s2, 3 times each in X, Y, and Z directions Shock Resistance 300 m/s2, 3 times each in X, Y, and Z directions E5EC Controller: Approx. 210 g, Adapter: Approx. 4 g × 2 Weight E5AC Controller: Approx. 250 g, Adapter: Approx. 4 g × 2 Degree of protection Front panel: IP66, Rear case: IP20, Terminals: IP00 Memory protection Non-volatile memory (number of writes: 1,000,000 times) Setup Tool CX-Thermo version 4.5 or higher E5EC/E5AC top panel: An E58-CIFQ2 USB-Serial Conversion Cable is used to connect to a USB port on the computer.*5 Setup Tool port E5EC/E5AC front panel: An E58-CIFQ2 USB-Serial Conversion Cable and E58-CIFQ2-E Conversion Cable are used together to connect to a USB port on the computer.*5 Approved standards UL 61010-1, Korean Radio Waves Act (Act 10564) Standards Conformed standards EN 61010-1 (IEC 61010-1): Pollution Degree 2, overvoltage category II, Lloyd's standards *6 EMI EN61326 Radiated Interference Electromagnetic Field Strength: EN 55011 Group 1, class A Noise Terminal Voltage: EN 55011 Group 1, class A EMS: EN 61326 ESD Immunity: EN 61000-4-2 EMC Electromagnetic Field Immunity: EN 61000-4-3 Burst Noise Immunity: EN 61000-4-4 Conducted Disturbance Immunity: EN 61000-4-6 Surge Immunity: EN 61000-4-5 Voltage Dip/Interrupting Immunity: EN 61000-4-11 Indication accuracy (at the ambient temperature of 23°C)
*1
*2 *3 *4 *5 *6
The indication accuracy of K thermocouples in the -200 to 1,300°C range, T and N thermocouples at a temperature of -100°C max., and U and L thermocouples at any temperatures is ±2°C ±1 digit max. The indication accuracy of the B thermocouple at a temperature of 400°C max. is not specified. The indication accuracy of B thermocouples at a temperature of 400 to 800°C is ±3°C max. The indication accuracy of the R and S thermocouples at a temperature of 200°C max. is ±3°C ±1 digit max. The indication accuracy of W thermocouples is (±0.3% of PV or ±3°C, whichever is greater) ±1 digit max. The indication accuracy of PL II thermocouples is (±0.3% of PV or ±2°C, whichever is greater) ±1 digit max. Ambient temperature: -10°C to 23°C to 55°C, Voltage range: -15% to 10% of rated voltage K thermocouple at -100°C max.: ±10°C max. The unit is determined by the setting of the Integral/Derivative Time Unit parameter. External communications (RS-485) and USB-serial conversion cable communications can be used at the same time. Refer to information on maritime standards in Shipping Standards on page 106 for compliance with Lloyd's Standards.
41
E5EC/E5AC USB-Serial Conversion Cable Windows XP, Vista, or 7
Applicable software
CX-Thermo version 4.5 or higher
Applicable models
E5@C-T Series, E5@C Series, and E5CB Series
USB interface standard
Conforms to USB Specification 2.0.
DTE speed
38,400 bps
Connector specifications
Computer: USB (type A plug) Digital Temperature Controller: Special serial connector
Power supply
Bus power (Supplied from USB host controller.)*
Power supply voltage
5 VDC
Current consumption
450 mA max.
Output voltage
4.7±0.2 VDC (Supplied from USB-Serial Conversion Cable to the Digital Temperature Controller.)
Output current
250 mA max. (Supplied from USB-Serial Conversion Cable to the Digital Temperature Controller.)
Ambient operating temperature
0 to 55°C (with no condensation or icing)
Ambient operating humidity
10% to 80%
Storage temperature
-20 to 60°C (with no condensation or icing)
Storage humidity
10% to 80%
Altitude
2,000 m max.
Weight
Approx. 120 g
Windows is a registered trademark of Microsoft Corporation in the United States and or other countries. *
Use a high-power port for the USB port.
Note: A driver must be installed on the computer. Refer to the Instruction Manual included with the Cable for the installation procedure.
Communications Specifications Transmission line connection method
RS-485: Multidrop
Communications
RS-485 (two-wire, half duplex)
Synchronization method
Start-stop synchronization
Protocol
CompoWay/F, or Modbus
Baud rate*
9600, 19200, 38400, or 57600 bps
Transmission code
ASCII
Data bit length*
7 or 8 bits
Stop bit length*
1 or 2 bits
Error detection
Vertical parity (none, even, odd) Block check character (BCC) with CompoWay/F or CRC-16 Modbus
Flow control
None
Interface
RS-485
Retry function
None
Communications buffer 217 bytes Communications response wait time *
0 to 99 ms Default: 20 ms
The baud rate, data bit length, stop bit length, and vertical parity can be individually set using the Communications Setting Level.
Communications Functions
Programless communications*1
You can use the memory in the PLC to read and write E5@C parameters, start and stop operation, etc. The E5@C automatically performs communications with PLCs. No communications programming is required. Number of connected Digital Temperature Controllers: 32 max. (Up to 16 for the FX Series) Applicable PLCs OMRON PLCs CS Series, CJ Series, or CP Series Mitsubishi Electric PLCs MELSEC Q Series, L Series, or FX Series (compatible with the FX2 or FX3 (excluding the FX1S)) KEYENCE PLCs KEYENCE KV Series
Component Communications*1
When Digital Temperature Controllers are connected, set points and RUN/STOP commands can be sent from the Digital Temperature Controller that is set as the master to the Digital Temperature Controllers that are set as slaves. Slope and offsets can be set for the set point. Number of connected Digital Temperature Controllers: 32 max. (including master)
Copying*2
When Digital Temperature Controllers are connected, the parameters can be copied from the Digital Temperature Controller that is set as the master to the Digital Temperature Controllers that are set as slaves.
MELSEC is a registered trademark of Mitsubishi Electric Corporation. KEYENCE is a registered trademark of Keyence Corporation. *1 A Temperature Controller with version 1.1 or higher is required. A Temperature Controller with version 2.1 or higher is required for the FX Series or the KV Series. *2 Both the programless communications and the component communications support the copying.
Current Transformer (Order Separately) Ratings Dielectric strength Vibration resistance Weight Accessories (E54-CT3 only)
1,000 VAC for 1 min 50 Hz, 98 m/s2 E54-CT1: Approx. 11.5 g, E54-CT3: Approx. 50 g Armatures (2) Plugs (2)
Heater Burnout Alarms and SSR Failure Alarms CT input (for heater current detection) Maximum heater current Input current indication accuracy Heater burnout alarm setting range *1 SSR failure alarm setting range *2
Models with detection for singlephase heaters: One input Models with detection for singlephase or three-phase heaters: Two inputs 50 A AC ±5% FS ±1 digit max. 0.1 to 49.9 A (in units of 0.1 A) Minimum detection ON time: 100 ms *3 0.1 to 49.9 A (in units of 0.1 A) Minimum detection OFF time: 100 ms *4
*1. For heater burnout alarms, the heater current will be measured when the control output is ON, and the output will turn ON if the heater current is lower than the set value (i.e., heater burnout detection current value). *2. For SSR failure alarms, the heater current will be measured when the control output is OFF, and the output will turn ON if the heater current is higher than the set value (i.e., SSR failure detection current value). *3. The value is 30 ms for a control period of 0.1 s or 0.2 s. *4. The value is 35 ms for a control period of 0.1 s or 0.2 s.
Electrical Life Expectancy Curve for Relays (Reference Values) Life (× 104 operations)
Applicable OS
500 300 E5EC/E5AC 250 VAC, 30 VDC (resistive load) cosφ = 1
100 50 30
10 5 3
1 0
1
2
3
4
5
6
Switching current (A)
42
E5EC/E5AC External Connections E5EC/E5AC
E5EC-@@ 4 @ 5 M - @ @ @ (1)
(2) (3) (4) (5) ↑ Terminal type
Control output 1
Control output 2
Relay output 250 VAC, 5 A (resistive load) Voltage output (for driving SSR) 12 VDC, 40 mA When There Is a Control Output 2: 21 mA Linear current output 0 to 20 mA DC 4 to 20 mA DC Load: 500 Ω max.
Relay output 250 VAC, 5 A (resistive load) Voltage output (for driving SSR) 12 VDC, 21 mA Linear current output 0 to 20 mA DC 4 to 20 mA DC Load: 500 Ω max.
(1) Control output RX
Auxiliary outputs 1, 2, 3, 4
(2) (3) (4) (5) ↑ Terminal type
OUT1 + C -
3 4 5 6
17 EV1 18 EV2 19
RR
+Q OUT2 PR
Models with 2 Relay Outputs OUT1
3 4 5 6
R R OUT2
100 to 240 VAC
R OUT2
CC
R Close
OUT1
3 4 5 6
+ C + C -
OUT2
1 2 3 4 5 6 7 8 9 10 11 12
1
2
2
28 + 29 + EV5 30 EV6 31 32 33 34 + Remote V + 35 mA SP input 36 -
13 14 15 16 17 18 19 20 21 22 23 24
25 26 27 28 29 30 31 32 33 34 35 36
+ Q OUT2
Auxiliary outputs 1, 2, 3, 4
O W C
Auxiliary output 4 Auxiliary output 3 Auxiliary output 2
TC 22 - 23 + 24
19 20 21
CT1
013 6 event Inputs, transfer output, and remote SP input
-
13
+
28
-
+
29
+ EV5 30 EV6
19 20 21
+ Transfer V + output I -
Pt
A 22 B 23 B 24
I + 22 mA 23 24
31
32 33 34 + + V Remote 35 mA SP input 36
(5) Sensor (Temperature/Analog) Input
Auxiliary output 1
13
+ 17 + EV1 18 EV2
+ Transfer V + I output -
Potentiometer Input
(2) Auxiliary Outputs 7 8 9 10 11 12
21
14 + EV3 15 EV4 16 -
24 VAC/DC
1
CQ
OUT1 + C -
21
+
(no polarity)
OUT1 +Q -
R
CT2
-
Models with 2 Outputs: Linear Current Output and Voltage (for Driving SSR)
3 4 5 6
19 20 21
(3) Input Power Supply
Models with 2 Models with 2 Position-proportional Linear Current Relay Output Outputs Open
3 4 5 6
EV2
011 6 event Inputs, 1 CT input, transfer output, and remote SP input
Models with Voltage Output (for Models with 2 Voltage Outputs (for Driving SSR) Driving SSR) and Relay Output
3 4 5 6
009 010 Communications, 2 event 4 event inputs and 1 CT input inputs, and 2 CT inputs B(+) 13 13 RS-485 + 14 14 EV3 A(-) + 15 15 EV4 16 16 + + 17 17 + EV1 18 + EV1 18 EV2 EV2 19 19 CT1 CT1 20 COM 20
+ 17 + EV1 18
+
+
QR
OUT1 +Q -
The E5EC is set for a K-type thermocouple (input type = 5) by default. An input error (s.err) will occur if the input type setting does not agree with the temperature sensor. Check the input type.
005 004 4 event inputs Communications and 2 event inputs B(+) 13 13 RS-485 + 14 14 A(-) + EV3 15 15 EV4 16 16 -
Models with 1 Linear Current Output
OUT1 +Q -
3 4 5 6
QQ
3 4 5 6
(6)
(6) Options
Relay output Models with 4 auxiliary outputs: 250 VAC, 2 A (resistive load)
CX
Models with 1 Voltage Output (for Driving SSR)
OUT1 R
3 4 5 6
(1)
20 21
QX
Models with 1 Relay Output
E5AC-@@ 4 @ 5 M - @ @ @
(6)
V V +
22 23 24
14
+ EV3 15 EV4 16 + 17 + EV1 18 EV2
19 20 21
014 Communications, 4 event Inputs, transfer output, and remote SP input B(+) 13 RS-485 14 A(-) 15
-
+
+ EV5 EV6 + Transfer V + I output -
28 29 30 31
32 33 + 34 + V Remote mA 35 SP input 36
16
-
+
17 + EV1 18 EV2 19 20 21
Note: 1. The application of the terminals depends on the model. 2. Do not wire the terminals that are shown with a gray background. 3. When complying with EMC standards, the cable that connects the sensor must be 30 m or less. If the cable length exceeds 30 m, compliance with EMC standards will not be possible. 4. Connect M3 crimped terminals.
Isolation/Insulation Block Diagrams Models with 4 Auxiliary Outputs Sensor input, CT inputs, potentiometer input, and remote SP input Communications and event inputs Power Supply
Voltage output (for driving SSR), linear current output, and transfer output Relay output Auxiliary outputs 1, 2 Auxiliary outputs 3, 4 : Reinforced insulation : Functional isolation
Note: Auxiliary outputs 1 to 2 and 3 to 4 are not insulated.
43
E5EC/E5AC Nomenclature E5EC Front panel
No. 1 display PV or specified parameter
Temperature unit
Top View of E5EC
No. 2 display
Operation indicators
SP or specified parameter value No. 3 display Front-panel Setup Tool port
Manipulated value or other value Manipulated or other value Use the Uvalue D Keys to set
Top-panel Setup Tool port
the parameter. Use S Key to change the digit (default setting).
Use the M Key to change to another parameter. Press O Key once to go to Adjustment Level. Press O Key for at least 3 seconds to go to Initial Setting Level.
E5AC Front Panel
Temperature unit Operation indicators
Top View of E5AC
No. 1 display PV or specified parameter No. 2 display SP or specified parameter value
Front-panel Setup Tool port
No. 3 display Manipulated value or other value
Press the U or D Key to set the parameter.
Press the S Key to change the digit (default setting). Press the O Key once to go to the Adjustment Level. Press the O Key for at least 3 seconds to go to the Initial Setting Level.
44
Press the M Key to change to another parameter.
Top-panel Setup Tool port
E5EC/E5AC
Dimensions
(Unit: mm)
Controllers E5EC 48
(64) 60
4 1
96
44
The Setup Tool ports are on the front and top of the Digital Temperature Controller. It is used to connect the Temperature Controller to the computer to use the Setup Tool. The E58-CIFQ2 USB-Serial Conversion Cable is required to make the connection. 91 Refer to the instructions that are provided with the USB-Serial Conversion Cable for the connection procedure.
110
Note: Do not leave the USB-Serial Conversion Cable connected when you use the Temperature Controller. Waterproof Packing (Accessory)
Mounted Separately
Mounting Adapter (Accessory)
Group Mounted *
(48 × number of units − 2.5)+1.0 0 45+0.6 0
*
Selections for Control Outputs 1 and 2: QQ, QR, RR, CC, PR, or CQ If you also specify 011, 013, or 014 for the option selection and use group mounting, the ambient temperature must be 45°C or less. If the ambient temperature is 55°C, maintain the following mounting spaces between Controllers.
92+0.8 0
60 min. 45-0.6 0 Group mounting does not allow waterproofing.
120 min.
92+0.8 0 92-0.8 0
120 min.
• Recommended panel thickness is 1 to 8 mm. • Group mounting is not possible in the vertical direction. (Maintain the specified mounting space between Controllers.) • To mount the Controller so that it is waterproof, insert the waterproof packing onto the Controller. • When two or more Controllers are mounted, make sure that the surrounding temperature does not exceed the allowable operating temperature specified in the specifications.
45
E5EC/E5AC
E5AC
(64) 60
4 1
96 x 96
91 x 91
110
Waterproof Packing (Accessory)
91
Mounting Adapter (Accessory)
The Setup Tool ports are on the front and top of the Digital Temperature Controller. It is used to connect the Temperature Controller to the computer to use the Setup Tool. The E58-CIFQ2 USB-Serial Conversion Cable is required to make the connection. Refer to the instructions that are provided with the USB-Serial Conversion Cable for the connection procedure.
Note: Do not leave the USB-Serial Conversion Cable connected when you use the Temperature Controller. Group Mounted *
Mounted Separately
(96 × number of units − 3.5)+1.0 0 92+0.8 0
92+0.8 0
Group mounting does not allow waterproofing.
120 min.
92+0.8 0
46
• Recommended panel thickness is 1 to 8 mm. • Group mounting is not possible in the vertical direction. (Maintain the specified mounting space between Controllers.) • To mount the Controller so that it is waterproof, insert the waterproof packing onto the Controller. • When two or more Controllers are mounted, make sure that the surrounding temperature does not exceed the allowable operating temperature specified in the specifications.
E5EC/E5AC Accessories (Order Separately) ● USB-Serial Conversion Cable E58-CIFQ2
(2110) 250
263
1510
LED (RD)
USB connector (type A plug)
Serial connector
LED (PWR) LED (SD)
● Conversion Cable E58-CIFQ2-E Conversion Cable
Connecting to the E58-CIFQ2 USB-Serial Conversion Cable (2110)
(1510)
250
263
E58-CIFQ2 (Order Separately)
1510
Conversion Cable
Note: Always use this product together with the E58-CIFQ2.
● Terminal Covers E53-COV24 (Three Covers provided.) 2
3.8
● Waterproof Packing Y92S-P9 (for DIN 48 × 96) The Waterproof Packing is provided with the Temperature Controller. Order the Waterproof Packing separately if it becomes lost or damaged. The degree of protection when the Waterproof Packing is used is IP66. Also, keep the Port Cover on the front-panel Setup Tool port of the E5EC/E5AC securely closed. To maintain an IP66 degree of protection, the Waterproof Packing and the Port Cover for the front-panel Setup Tool port must be periodically replaced because they may deteriorate, shrink, or harden depending on the operating environment. Y92S-P10 (for DIN 96 × 96) The replacement period will vary with the operating environment. Check the required period in the actual application. Use 3 years or sooner as a guideline. If a waterproof structure is not required, then the Waterproof Packing does not need to be installed.
10
91
● Setup Tool Port Cover for top panel Y92S-P7
Order this Port Cover separately if the Port Cover on the front-panel Setup Tool port is lost or damaged. The Waterproof Packing must be periodically replaced because it may deteriorate, shrink, or harden depending on the operating environment.
● Mounting Adapter Y92F-51 (Two Adapters provided.) One pair is provided with the Controller. Order this Adapter separately if it becomes lost or damaged.
47
E5EC/E5AC ● Watertight Cover Y92A-96N (96 × 96)
● Watertight Cover Y92A-49N (48 × 96) 21.9
21.9
(2)
(2)
131.7
131.7
67.6
115.6
29.4
29.4
● Current Transformers E54-CT1 21 15
Thru-current (Io) vs. Output Voltage (Eo) (Reference Values) E54-CT1
2.8 5.8 dia. 7.5
25
Maximum continuous heater current: 50 A (50/60 Hz) Number of windings: 400±2 Winding resistance: 18±2 Ω
3
Output voltage (Eo) V (r.m.s.)
10.5 40 Two, 3.5 dia. 10 30
100V
Frequency: 50 Hz ∞ 1kΩ
10
Distortion factor 10%
1
3% 1%
100mV 10
100Ω
1
RL=10Ω
E54-CT3 2.36 dia. 30 12 dia. 9
100μV 10 1
10
100mA
1
40 × 40
30
Connection Example Plug
Armature
Lead
18
Output voltage (Eo) V (r.m.s.)
Maximum continuous heater current: 120 A (50/60 Hz) (Maximum continuous heater current for an OMRON Digital Temperature Controller is 50 A.) Number of windings: 400±2 Winding resistance: 8±0.8 Ω
15
Approx. 3 dia.
100 1,000A
Thru-current (Io) vs. Output Voltage (Eo) (Reference Values) E54-CT3
Two, M3 (depth: 4)
E54-CT3 Accessories • Armature
10
Thru-current (Io) A (r.m.s.)
100V
Frequency: 50 Hz Distortion factor 10% 3% 1%
∞ 1kΩ 500Ω
10 1 100mV
100Ω 50Ω
10
RL=10Ω
• Plug
1
Approx. 6 dia.
100μV (22)
10 1
10
100mA
1
10
100 1,000A
Thru-current (Io) A (r.m.s.)
48
MEMO
49
Digital Temperature Controller
E5DC
(22.5 mm Wide, and DIN Track-mounting Type)
The E5DC Mounts to DIN Track and Is Ideal for Connections to HMIs and PLCs. It provides the Same Easy Operation and Advanced Performance as the Rest of the E5@C Series. • A slim body at 85 × 22.5 mm (D × W) that fits into narrow control panels and mounts to DIN Track. • Removable terminal block for easy replacement to simplify maintenance. • High-speed sampling at 50 ms for applications with high-speed temperature increases. • Easy connections to a PLC with programless communications. • Set up the Controller without wiring the power supply by connecting to the computer with a Communications Conversion Cable (sold separately). Setup is easy with the CX-Thermo (sold separately). • Models are available with up to 2 auxiliary outputs and 1 event input to complete basic functions. • A white PV display (height: 8.5 mm) is easy to read when setting up, checking alarms, and making settings in a control panel.
22.5 mm Wide, and DIN Track-mounting Type E5DC Refer to your OMRON website for the most recent information on applicable safety standards. Refer to Safety Precautions on page 104.
Main I/O Functions Sensor Input Universal input • Thermocouple • Pt • Analog current/voltage
E5DC Dual displays: PV/SV
Control Output 1 • Relay output • Voltage output (for driving SSR) • Linear current output
Indication Accuracy • Thermocouple input: ±0.3% of PV • Pt input: ±0.2% of PV • Analog input: ±0.2% of FS
Auxiliary Outputs • None •2
Sampling Period • 50 ms Event Inputs • None •1 Serial Communications • None • RS-485
4-digit displays
• PF (shift) Key • Temperature status display • Simple programming • Independent heating and cooling PID control • Changed parameter display • Display brightness setting
This datasheet is provided as a guideline for selecting products. Be sure to refer to the following manuals for application precautions and other information required for operation before attempting to use the product. E5@C Digital Temperature Controllers User’s Manual (Cat. No. H174) E5@C Digital Temperature Controllers Communications Manual (Cat. No. H175)
50
E5DC
Model Number Legend and Standard Models Model Number Legend ●Models with Screw Terminals E5DC-@@ @ @ S M-@@@ (Example: E5DC-RX0ASM-015) −− − − − − −−− A B C D E F A
Model
B No. of Control auxiliary output 1 outputs
C Power supply voltage
D
E
F
Terminal type
Input type
Options
Meaning
E5DC
22.5 mm wide and mounts to DIN Track Control output 1 Control output 2 Relay output None Voltage output None (for driving SSR) Linear current output *5 None None 2 (one common) 100 to 240 VAC 24 VAC/DC Screw terminals Universal input HB alarm and HS alarm Communications Event input ------1 RS-485 ----RS-485 ------1 1 --1
RX QX CX 0 2 A D S M *1 *2 *3 *4 *2 *1 *2 *3 *4 *5
000 002 015 016 017
Option 000 can be selected only if two auxiliary outputs are selected. Options 002 and 017 can be selected only if the control output is a relay output or voltage output and two auxiliary outputs are selected. Option 015 cannot be selected if the control output is a relay output or voltage output and two auxiliary outputs are selected. Options 016 can be selected only if the control output is a linear current output and two auxiliary outputs are selected. The control output cannot be used as a transfer output.
List of Models Options Control output
No. of auxiliary outputs ---
Relay output
2 ---
Voltage output (for driving SSR)
2
HB alarm and HS alarm --Detection for singlephase heater --Detection for singlephase heater
No. of event inputs
2
---
Model Power supply voltage
Communications
--1 --1
--Linear current output
Model Power supply voltage
--1
100 to 240 VAC
24 VAC/DC
RS-485
E5DC-RX0ASM-015
E5DC-RX0DSM-015
---
E5DC-RX2ASM-000
E5DC-RX2DSM-000
RS-485
E5DC-RX2ASM-002
E5DC-RX2DSM-002
---
E5DC-RX2ASM-017
E5DC-RX2DSM-017
RS-485
E5DC-QX0ASM-015
E5DC-QX0DSM-015
---
E5DC-QX2ASM-000
E5DC-QX2DSM-000
RS-485
E5DC-QX2ASM-002
E5DC-QX2DSM-002
---
E5DC-QX2ASM-017
E5DC-QX2DSM-017
RS-485
E5DC-CX0ASM-015
E5DC-CX0DSM-015
---
E5DC-CX2ASM-000
E5DC-CX2DSM-000
RS-485
E5DC-CX2ASM-015
E5DC-CX2DSM-015
---
E5DC-CX2ASM-016
E5DC-CX2DSM-016
Note: These products are sold as a set with a terminal block (i.e., Terminal Unit).
Heating and Cooling Control ●Using Heating and Cooling Control
A Control Output Assignment An auxiliary output is used as the cooling control output. B Control If PID control is used, you can set PID control separately for heating and cooling. This allows you to handle control systems with different heating and cooling response characteristics.
51
E5DC Optional Products (Order Separately) USB-Serial Conversion Cable
End Plate
Model E58-CIFQ2
Model PFP-M
Communications Conversion Cable
Spacer
Model E58-CIFQ2-E
Model PFP-S
Note: Always use this product together with the E58-CIFQ2. This Cable is used to connect to the front-panel Setup Tool port.
DIN Tracks Model PFP-100N PFP-50N
Current Transformers (CTs) Hole diameter 5.8 mm 12.0 mm
Model E54-CT1 E54-CT3
Unit Labels Model Y92S-L2
Mounting Adapter Model Y92F-53 (2pcs)
Short Bars Model Y92S-P11 (4 pcs)
CX-Thermo Support Software Model EST2-2C-MV4 Note: CX-Thermo version 4.6 or higher is required for the E5DC. For the system requirements for the CX-Thermo, refer to information on the EST2-2C-MV4 on the OMRON website (www.ia.omron.com).
52
End Cover Model Y92F-54
E5DC
Specifications Ratings Power supply voltage Operating voltage range Power consumption
Sensor input
Input impedance Control method Relay output Control output
Auxiliary output
Voltage output (for driving SSR) Linear current output Number of outputs Output specifications Number of inputs
Event input
External contact input specifications
Setting method Indication method Multi SP Bank switching
Other functions
Ambient operating temperature Ambient operating humidity Storage temperature Altitude Recommended fuse Installation environment
A in model number: 100 to 240 VAC, 50/60 Hz D in model number: 24 VAC, 50/60 Hz; 24 VDC 85% to 110% of rated supply voltage 4.9 VA max. at 100 to 240 VAC, and 2.8 VA max. at 24 VDC or 1.5 W max. at 24 VDC Temperature input Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II Platinum resistance thermometer: Pt100 or JPt100 Infrared temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C Analog input Current input: 4 to 20 mA or 0 to 20 mA Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V Current input: 150 Ω max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB/ THB.) ON/OFF control or 2-PID control (with auto-tuning) SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA (reference value) Output voltage 12 VDC ±20% (PNP), max. Load current: 21 mA, with short-circuit protection circuit 4 to 20 mA DC/0 to 20 mA DC, load: 500 Ω max., resolution: Approx. 10,000 2 (depends on model) SPST-NO relay outputs: 250 VAC, 2 A (resistive load), Electrical life: 100,000 operations, Minimum applicable load: 10 mA at 5 V (reference value) 1 (depends on model) Contact input ON: 1 kΩ max., OFF: 100 kΩ min. Non-contact input ON: Residual voltage 1.5 V max.; OFF: Leakage current 0.1 mA max. Current flow: approx. 7 mA per contact Digital setting using front panel keys 11-segment digital displays and individual indicators Character height: PV: 8.5 mm, SV: 8.0 mm Up to eight set points (SP0 to SP7) can be saved and selected using the event inputs, key operations, or serial communications.* None Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater burnout (HB) alarm (including SSR failure (HS) alarm), 40% AT, 100% AT, MV limiter, input digital filter, self tuning, robust tuning, PV input shift, run/stop, protection functions, extraction of square root, MV change rate limit, logic operations, temperature status display, simple programming, moving average of input value, and display brightness setting −10 to 55°C (with no condensation or icing), For 3-year warranty: −10 to 50°C with standard mounting (with no condensation or icing) 25% to 85% −25 to 65°C (with no condensation or icing) 2,000 m max. T2A, 250 VAC, time-lag, low-breaking capacity Installation Category II, Pollution Degree 2 (IEC 61010-1 compliant)
* Only two set points are selectable for event inputs.
53
E5DC Input Ranges ●Thermocouple/Platinum Resistance Thermometer (Universal inputs) Sensor type
Platinum resistance thermometer
Sensor specification
Pt100
Infrared temperature sensor
Thermocouple
JPt100
K
J
T
E
L
U
N
R
S
B
W
PLII
10 to 70°C
60 to 120°C
115 to 165°C
120
165
140 to 260°C
2300
2300
1800
1800
1700
1700
1700
Temperature range (°C)
1600 1500 1400
1300
1300
1300
1300
1200 1100 1000 900
850
850
850
800 700
600
600
500.0
500
500.0
500.0 400.0
400
400
400.0
400
400.0 260
300 200
100.0
100
Set value
90
100 0.0
-100 -200
100.0
-200 -199.9
0
1
0.0 -199.9
2
3
-20.0
-100
-20.0
6
7
8
-200
4
5
0
0
16
17
0
0
0
0
0
0
19
20
21
22
23
24
-100 -200 -199.9 -200
9
10
11
-200 -199.9 -200
12
13
14
15
18
Shaded settings are the default settings. The applicable standards for the input types are as follows: K, J, T, E, N, R, S, B: JIS C 1602-1995, IEC 60584-1 L: Fe-CuNi, DIN 43710-1985 U: Cu-CuNi, DIN 43710-1985 W: W5Re/W26Re, ASTM E988-1990
JPt100: JIS C 1604-1989, JIS C 1606-1989 Pt100: JIS C 1604-1997, IEC 60751 PL II: According to Platinel II electromotive force charts from BASF (previously Engelhard)
●Analog input Input type Input specification Setting range Set value
54
Current Voltage 4 to 20 mA 0 to 20 mA 1 to 5 V 0 to 5 V Usable in the following ranges by scaling: -1999 to 9999, -199.9 to 999.9, -19.99 to 99.99 or -1.999 to 9.999 25 26 27 28
0 to 10 V
29
E5DC Alarm Types Each alarm can be independently set to one of the following 17 alarm types. The default is 2: Upper limit. (See note.) Auxiliary outputs are allocated to alarms. ON delays and OFF delays (0 to 999 s) can also be specified. Note: In the default settings for models with HB or HS alarms, alarm 1 is set to a heater alarm (HA) and the Alarm Type 1 parameter is not displayed. To use alarm 1, set the output assignment to alarm 1. Set value
Alarm type
0
Alarm function OFF
1
Upper- and lower-limit *1
2 Upper-limit (default) 3
Lower-limit
4
Upper- and lower-limit range *1
Alarm output operation Description of function When alarm value X When alarm value X is positive is negative Output OFF No alarm Set the upward deviation in the set point for the alarm upper L H limit (H) and the lower deviation in the set point for the alarm ON *2 OFF PV lower limit (L). The alarm is ON when the PV is outside this SP deviation range. Set the upward deviation in the set point by setting the alarm X X ON ON value (X). The alarm is ON when the PV is higher than the OFF PV OFF PV SP SP SP by the deviation or more. Set the downward deviation in the set point by setting the X X ON ON alarm value (X). The alarm is ON when the PV is lower than OFF PV OFF PV SP SP the SP by the deviation or more. Set the upward deviation in the set point for the alarm upper L H limit (H) and the lower deviation in the set point for the alarm ON *3 OFF PV lower limit (L). The alarm is ON when the PV is inside this deSP viation range.
Upper- and lower-limit with standby sequence *1 *5 Upper-limit with standby sequence
ON OFF
7
Lower-limit with standby sequence
ON OFF
8
Absolute-value upper-limit
ON OFF
9
Absolute-value lower-limit
ON OFF
10
Absolute-value upper-limit with standby sequence
ON OFF
11
Absolute-value lower-limit with standby sequence
ON OFF
12 13
LBA (alarm 1 type only) PV change rate alarm
14
SP absolute-value upper-limit alarm
ON OFF
15
SP absolute-value lower-limit alarm
ON OFF
5 6
L
H
X
ON OFF
SP
PV
ON OFF
PV
ON OFF
PV
ON OFF
PV
ON OFF
PV
ON OFF
PV
ON OFF
X SP X 0 X 0 X 0 X 0
ON OFF
MV absolute-value upper-limit alarm *9
X
PV
A standby sequence is added to the upper-limit alarm (2). *6
PV
A standby sequence is added to the lower-limit alarm (3). *6
X SP X 0
PV
X 0
PV
The alarm will turn ON if the process value is smaller than the alarm value (X) regardless of the set point.
PV
A standby sequence is added to the absolute-value upperlimit alarm (8). *6
PV
A standby sequence is added to the absolute-value lowerlimit alarm (9). *6
X 0 X 0
0
ON OFF
SP
ON OFF
X 0
X 0
SP
This alarm type turns ON the alarm when the set point (SP) is higher than the alarm value (X).
SP
This alarm type turns ON the alarm when the set point (SP) is lower than the alarm value (X).
X 0
Standard Control
X MV
0
The alarm will turn ON if the process value is larger than the alarm value (X) regardless of the set point.
*7 *8
SP
ON OFF
X 0
MV
X MV
0
Standard Control ON OFF
17
SP
This alarm type turns ON the alarm when the manipulated Heating/Cooling Heating/Cooling variable (MV) is higher than the alarm value (X). Control (Heating MV) Control (Heating MV) ON OFF
MV absolute-value lower-limit alarm *9
X
-
Standard Control
16
A standby sequence is added to the upper- and lower-limit alarm (1). *6
*4
PV
SP
Standard Control
X MV
0
Always ON ON OFF
X 0
MV
This alarm type turns ON the alarm when the manipulated Heating/Cooling Heating/Cooling variable (MV) is lower than the alarm value (X). Control (Cooling MV) Control (Cooling MV) ON OFF
X 0
MV
Always ON
55
E5DC *1 With set values 1, 4, and 5, the upper- and lower-limit values can be set independently for each alarm type, and are expressed as “L” and “H.” *2 Set value: 1, Upper- and lower-limit alarm Case 3 (Always OFF)
Case 2
Case 1
H<0, L<0 L
H SP
H<0, L>0 |H| < |L|
H
SP L H H>0, L<0 |H| > |L|
H
SP
L H<0, L>0 |H| ≥ |L|
L SP SP H
L
H>0, L<0 |H| ≤ |L|
*3 Set value: 4, Upper- and lower-limit range Case 3 (Always ON)
Case 2
Case 1
H<0, L<0 L
H SP
H<0, L>0 |H| < |L|
SP L
H
H
H>0, L<0 |H| > |L|
H
SP
L
L SP SP H L
56
H<0, L>0 |H| ≥ |L| H>0, L<0 |H| ≤ |L|
*4 Set value: 5, Upper- and lower-limit with standby sequence For Upper- and Lower-Limit Alarm Described Above at *2 • In cases 1 and 2 above, the alarm is always OFF if the upperand lower-limit hysteresis overlaps. • In case 3, the alarm is always OFF. *5 Set value: 5, Upper- and lower-limit alarm with standby sequence The alarm is always OFF if upper- and lower-limit hysteresis overlaps. *6 Refer to the E5@C Digital Temperature Controllers User’s Manual (Cat. No. H174) for information on the operation of the standby sequence. *7 Refer to the E5@C Digital Temperature Controllers User’s Manual (Cat. No. H174) for information on the LBA. *8 Refer to the E5@C Digital Temperature Controllers User’s Manual (Cat. No. H174) for information on the PV change rate alarm. *9 When heating/cooling control is performed, the MV absolutevalue upper-limit alarm functions only for the heating operation and the MV absolute-value lower-limit alarm functions only for the cooling operation.
E5DC Characteristics Thermocouple: (±0.3 % of indication value or ±1°C, whichever is greater) ±1 digit max.*1 Indication accuracy Platinum resistance thermometer: (±0.2 % of indication value or ±0.8°C, whichever is greater) ±1 digit max. (when mounted individually, ambiAnalog input: ±0.2% FS ±1 digit max. ent temperature of 23°C) CT input: ±5% FS ±1 digit max. Influence of temperature *2 Thermocouple input (R, S, B, W, PL II): (±1% of indication value or ±10°C, whichever is greater) ±1 digit max. Other thermocouple input: (±1% of indication value or ±4°C, whichever is greater) ±1 digit max. *3 Platinum resistance thermometer: (±1% of indication value or ±2°C, whichever is greater) ±1 digit max. Influence of voltage *2 Analog input: ±1% FS ±1 digit max. CT input: ±5% FS ±1 digit max. R, S, B, W, or PLII thermocouple: (±1% of PV or ±10°C, whichever is greater) ±1 digit max. Installation influence (E5DC only) Other thermocouple: (±1% of PV or ±4°C, whichever is greater) ±1 digit max. *3 Input sampling period 50 ms Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F) Hysteresis Analog input: 0.01% to 99.99% FS (in units of 0.01% FS) Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F) Proportional band (P) Analog input: 0.1% to 999.9% FS (in units of 0.1% FS) Integral time (I) 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4 Derivative time (D) 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4 Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F) Proportional band (P) for cooling Analog input: 0.1% to 999.9% FS (in units of 0.1% FS) Integral time (I) for cooling 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4 Derivative time (D) for cooling 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4 Control period 0.1, 0.2, 0.5, 1 to 99 s (in units of 1 s) Manual reset value 0.0% to 100.0% (in units of 0.1%) Alarm setting range −1,999 to 9,999 (decimal point position depends on input type) Influence of signal source resisThermocouple: 0.1°C/Ω max. (100 Ω max.), Platinum resistance thermometer: 0.1°C/Ω max. (10 Ω max.) tance Insulation resistance 20 MΩ min. (at 500 VDC) Dielectric strength 3,000 VAC, 50/60 Hz for 1 min between terminals of different charge Malfunction 10 to 55 Hz, 20 m/s2 for 10 min each in X, Y and Z directions Vibration Resistance 10 to 55 Hz, 20 m/s2 for 2 hr each in X, Y, and Z directions Malfunction 100 m/s2, 3 times each in X, Y, and Z directions Shock Resistance 300 m/s2, 3 times each in X, Y, and Z directions Weight Controller: Approx. 120 g Degree of protection Main unit: IP20, Terminal unit: IP00 Memory protection Non-volatile memory (number of writes: 1,000,000 times) Setup Tool CX-Thermo version 4.6 or higher E5DC bottom panel: An E58-CIFQ2 USB-Serial Conversion Cable is used to connect a USB port on the computer. *5 Setup Tool port E5DC front panel: An E58-CIFQ2 USB-Serial Conversion Cable and E58-CIFQ2-E Conversion Cable are used together to connect a USB port on the computer.*5 Approved standards UL 61010-1, Korean Radio Waves Act (Act 10564) Standards Conformed standards EN 61010-1 (IEC 61010-1): Pollution Degree 2 , overvoltage category II EMI: EN61326 Radiated Interference Electromagnetic Field Strength: EN55011 Group 1, class A Noise Terminal Voltage: EN55011 Group 1, class A EMS: EN61326 ESD Immunity: EN61000-4-2 EMC Electromagnetic Field Immunity: EN61000-4-3 Burst Noise Immunity: EN61000-4-4 Conducted Disturbance Immunity: EN61000-4-6 Surge Immunity: EN61000-4-5 Voltage Dip/Interrupting Immunity: EN61000-4-11 *1 The indication accuracy of K thermocouples in the −200 to 1,300°C range, T and N thermocouples at a temperature of −100°C max., and U and L thermocouples at any temperature is ±2°C ±1 digit max. The indication accuracy of B thermocouples at a temperature of 400°C max. is not specified. The indication accuracy of B thermocouples at a temperature of 400 to 800°C is ±3°C max. The indication accuracy of R and S thermocouples at a temperature of 200°C max. is ±3°C ±1 digit max. The indication accuracy of W thermocouples is (±0.3% of PV or ±3°C, whichever is greater) ±1 digit max. The indication accuracy of PLII thermocouples is (±0.3% of PV or ±2°C, whichever is greater) ±1 digit max. *2 Ambient temperature: −10°C to 23°C to 55°C, Voltage range: −15% to 10% of rated voltage *3 K thermocouple at −100°C max.: ±10°C max. *4 The unit is determined by the setting of the Integral/Derivative Time Unit parameter. *5 External serial communications (RS-485) and USB-Serial Conversion Cable communications can be used at the same time.
57
E5DC USB-Serial Conversion Cable Windows XP, Vista, or 7
Applicable software
CX-Thermo version 4.6 or higher
Applicable models
E5@C-T Series, E5@C Series, and E5CB Series
USB interface standard
Conforms to USB Specification 2.0
DTE speed
38,400 bps
Connector specifications
Computer: USB (Type A plug) Digital Temperature Controller: Special serial connector
Power supply
Bus power (Supplied from the USB host controller) *
Power supply voltage
5 VDC
Current consumption
450 mA max.
Output voltage
4.7±0.2 VDC (Supplied from USB-Serial Conversion Cable to the Digital Temperature Controller.)
Output current
250 mA max. (Supplied from USB-Serial Conversion Cable to the Digital Temperature Controller.)
Ambient operating temperature
0 to 55°C (with no condensation or icing)
Ambient operating humidity
10% to 80%
Dielectric strength
1,000 VAC for 1 min
Storage temperature
−20 to 60°C (with no condensation or icing)
Vibration resistance
50 Hz, 98 m/s2
Storage humidity
10% to 80%
Weight
E54-CT1: Approx. 11.5 g, E54-CT3: Approx. 50 g
Altitude
2,000 m max.
Weight
Approx. 120 g
Accessories (E54-CT3 only)
Armatures (2) Plugs (2)
Windows is a registered trademark of Microsoft Corporation in the United States and or other countries. Use a high-power port for the USB port.
Note: A driver must be installed on the computer. Refer to the Instruction Manual included with the Cable for the installation procedure.
Communications Specifications
MELSEC is a registered trademark of Mitsubishi Electric Corporation. KEYENCE is a registered trademark of Keyence Corporation. *1 A Temperature Controller with version 2.1 or higher is required for the FX Series or the KV Series. *2 Both the programless communications and the component communications support the copying.
Current Transformer (Order Separately) Ratings
Heater Burnout Alarms and SSR Failure Alarms CT input (for heater current detection)
Models with detection for single-phase heaters: One input
Maximum heater current
50 A AC
Input current indication accuracy
±5% FS ±1 digit max.
Transmission line connection method
RS-485: Multidrop
Heater burnout alarm setting range *1
0.1 to 49.9 A (in units of 0.1 A) Minimum detection ON time: 100 ms *3
Communications
RS-485 (two-wire, half duplex)
Synchronization method
Start-stop synchronization
SSR failure alarm setting range *2
0.1 to 49.9 A (in units of 0.1 A) Minimum detection OFF time: 100 ms *4
Protocol
CompoWay/F, or Modbus
Baud rate*
9,600, 19,200, 38,400, or 57,600 bps
Transmission code
ASCII
Data bit length *
7 or 8 bits
Stop bit length *
1 or 2 bits
Error detection
Vertical parity (none, even, odd) Block check character (BCC) with CompoWay/F or CRC-16 with Modbus
Flow control
None
Interface
RS-485
Retry function
None
Communications buffer
217 bytes
Communications response wait time
0 to 99 ms Default: 20 ms
* The baud rate, data bit length, stop bit length, and vertical parity can be individually set using the Communications Setting Level.
Communications Functions You can use the memory in the PLC to read and write E5@C parameters, start and stop operation, etc. The E5@C automatically performs communications with PLCs. No communications programming is required. Number of connected Digital Temperature Controllers: 32 Programless max. (Up to 16 for the FX Series) communica- Applicable PLCs: OMRON PLCs tions *1 CS Series, CJ Series, or CP Series Mitsubishi Electric PLCs MELSEC Q Series, L Series, or FX Series (compatible with the FX2 or FX3 (excluding the FX1S)) KEYENCE PLCs KEYENCE KV Series
58
When Digital Temperature Controllers are connected, the parameters can be copied from the Digital Temperature Controller that is set as the master to the Digital Temperature Controllers that are set as slaves.
Copying*2
*1 *2 *3 *4
For heater burnout alarms, the heater current will be measured when the control output is ON, and the output will turn ON if the heater current is lower than the set value (i.e., heater burnout detection current value). For SSR failure alarms, the heater current will be measured when the control output is OFF, and the output will turn ON if the heater current is higher than the set value (i.e., SSR failure detection current value). The value is 30 ms for a control period of 0.1 s or 0.2 s. The value is 35 ms for a control period of 0.1 s or 0.2 s.
Electrical Life Expectancy Curve for Control Output Relay (Reference Values) Life (× 104 operations)
*
When Digital Temperature Controllers are connected, set points and RUN/STOP commands can be sent from the DigiComponent tal Temperature Controller that is set as the master to the DigCommunica- ital Temperature Controllers that are set as slaves. tions*1 Slope and offsets can be set for the set point. Number of connected Digital Temperature Controllers: 32 max. (including master)
Applicable OS
500 300
100 50 30
10 5
E5DC 250 VAC, 30 VDC (resistive load) cosφ = 1
3
1 0
1
2
3
4
5
6
Switching current (A)
E5DC
External Connections E5DC Control output
Auxiliary outputs 1, 2
Relay output 250 VAC, 3 A (resistive load) Voltage output (for driving SSR) 12 VDC, 21 mA Linear current output 0 to 20 mA DC 4 to 20 mA DC Load: 500 Ω max.
The E5DC is set for a K-type thermocouple (input type = 5) by default. An input error (s.err) will occur if the input type setting does not agree with the temperature sensor. Check the input type.
Relay outputs 250 VAC: 2 A (resistive load)
SM
E5DC
Control output
24 VAC/DC
100 to 240 VAC
RX
5 6
2
2
(no polarity)
1
5
9
2
6
10
Options 002 Communications and 1 CT B(+) RS-485 A(-)
3 4
A(-)
5 6
R
+Q -
1 linear current output
5 6
+ C -
Auxiliary Outputs 9 10
11
11
CT1
Auxiliary output 2 Auxiliary output 1
8
Sensor (Temperature/Analog) Input
3
7
4
8
016 One event input -
3
7
+
4
8
EV1
CX
1 voltage output (for driving SSR)
7
015 Communications B(+) RS-485
QX
1 relay output
1
1
Options
Control Output
Input Power Supply
12 3
7
13
4
8
14
TC 12 -
13 + 14
A B B
Pt 12 13 14
I + 12 mA 13 14
V 12 V
- 13 14 +
Do not connect anything to the terminals that are shaded gray.
017 One event input and one CT -
3
+
4
EV1
7
CT1
8
Note: 1. The application of the terminals depends on the model. 2. Do not wire the terminals that are shown with a gray background. 3. When complying with EMC standards, the cable that connects the sensor must be 30 m or less. If the cable length exceeds 30m, compliance with EMC standards will not be possible. 4. Connect M3 crimped terminals.
Isolation/Insulation Block Diagrams Sensor input and CT input Communications and event input Power supply
Voltage output (for driving SSR) and linear current output Relay output Auxiliary outputs 1 and 2
: Reinforced insulation : Functional isolation
Note: Auxiliary outputs 1 to 2 are not insulated.
59
E5DC
Nomenclature E5DC
Front panel
Bottom View of E5DC
No. 1 display PV or specified parameter
Operation indicators
No.2 display SP or specified parameter value Press O Key once to go to Adjustment Level.
Use the M Key to change to another parameter.
Press O Key for at least 3 seconds to go to Initial Setting Level.
Use the U D Keys to set the parameter.
Use S Key to change the digit (default setting).
Bottompanel Setup Tool port
Front-panel Setup Tool port
Dimensions
(Unit: mm)
Controllers E5DC
(85) 81
4 22.5
22.5
96
35 110
91
4
Mounting Adapter (Accessory: Sold separately)
The Setup Tool ports are on the front and bottom of the Digital Temperature Controller. It is used to connect the Temperature Controller to the computer to use the Setup Tool. The E58-CIFQ2 USB-Serial Conversion Cable is required to make the connection. Refer to the instructions that are provided with the USB-Serial Conversion Cable for the connection procedure.
Note: Do not leave the USB-Serial Conversion Cable connected when you use the Digital Temperature Controller.
Mounted Separately
Two-Unit Mounting
92 +0.8 0
Group Mounted (22.5 × number of units) +1.0
22.7 +0.3 0
0
45 +0.6 0
92 +0.8 0
92 +0.8 0
120 min
• Recommended panel thickness is 1 to 8 mm. • Group mounting is not possible in the vertical direction. (Maintain the specified mounting space between Controllers.) • When two or more Digital Temperature Controllers are mounted, make sure that the surrounding temperature does not exceed the allowable operating temperature specified in the specifications.
60
E5DC Accessories (Order Separately) ● USB-Serial Conversion Cable E58-CIFQ2
(2110) 250
263
1510
LED (RD)
USB connector (type A plug)
Serial connector
LED (PWR) LED (SD)
● Conversion Cable E58-CIFQ2-E Conversion Cable
Connecting to the E58-CIFQ2 USB-Serial Conversion Cable (2110)
(1510)
250
263
1510
E58-CIFQ2 (Order separately)
Note: Always use this product together with the E58-CIFQ2.
Conversion Cable
● Current Transformers E54-CT1 21 15
Thru-current (Io) vs. Output Voltage (Eo) (Reference Values) E54-CT1
2.8 5.8 dia. 7.5
3
Output voltage (Eo) V (r.m.s.)
25
Maximum continuous heater current: 50 A (50/60 Hz) Number of windings: 400±2 Winding resistance: 18±2 Ω
10.5 40 Two, 3.5 dia. 10 30
100V
Frequency: 50 Hz ∞ 1kΩ
10
Distortion factor 10%
1
3% 1% 100mV 100Ω
10
E54-CT3
2.36 dia. 30
RL=10Ω
1
12 dia. 9
100μV 10 1
40 × 40
10
100mA
1
10
100 1,000A
Thru-current (Io) A (r.m.s.)
Two , M3 holes (depth: 4)
30
Connection Example Armature Plug
Approx. 3 dia.
Lead
18
Output voltage (Eo) V (r.m.s.)
Maximum continuous heater current: 120 A (50/60 Hz) (Maximum continuous heater current for an OMRON Digital Temperature Controller is 50 A.) Number of windings: 400±2 Winding resistance: 8±0.8 Ω
15
E54-CT3 Accessories • Armature
Thru-current (Io) vs. Output Voltage (Eo) (Reference Values) E54-CT3
100V
Frequency: 50 Hz Distortion factor 10% 3% 1%
∞ 1kΩ 500Ω
10
1
100mV 100Ω 50Ω
10
RL=10Ω
• Plug
1
Approx. 6 dia.
100μV
(22)
10 1
10
100mA
1
10
100 1,000A
Thru-current (Io) A (r.m.s.)
61
E5DC ● Mounting Adapters Y92F-53 (Two included.)
● Short Bars Y92S-P11 (Four included.)
This accessory is not included with the product. Order it separately to mount the product to a panel.
Use this product to connect between terminals (for power supplies, communications, etc.) when you use multiple E5DC Controllers. 27.5 34.7
2.4
22.5
12 24.8
11.8 9.4
0.8
3 5
● DIN Tracks PFP-100N PFP-50N
● End Plate PFP-M 10 6.2 M4×8 pan head screw
1.8
1
50
35.5 35.3 1.8
11.5 10 M4 spring washer
7.3±0.15
1.3 4.8
4.5 35±0.3
15
25
10
25
25 1000 (500)*
*
10
25
15 (5)*
1
Dimensions in parentheses are for the PFP-50N.
● Unit Labels Y92S-L2
● Spacer PFP-S 16 12
5
The Unit Labels for the Digital Panel Meter are used. Use either the °C or °F label from the sheet. 34.8
44.3
16.5
● End Cover Y92F-54 (Two included.) 3.9
96
62
27±0.15
68
5.3
Use the End Cover when you mount the E5DC to a panel to hide the gap between the Controller and the panel.
MEMO
63
Programmable Temperature Controller (Digital Controller)
E5CC-T
(48 × 48 mm)
Programmable Controllers Join the E5C Series! Program up to 256 segments can handle a wide variety of applications. • Set up to 8 Programs (Patterns) with 32 Segments (Steps) Each • The white PV display with a height of 15.2 mm improves visibility. • High-speed sampling at 50 ms. • Models are available with up to 3 auxiliary outputs, up to 4 event inputs, and a transfer output to cover a wide range of applications. • Short body with depth of only 60 mm. • Set up the Controller without wiring the power supply by connecting to the computer with a Communications Conversion Cable (sold separately). Setup is easy with the CX-Thermo (sold separately). • Easy connections to a PLC with programless communications. Use component communications to link Temperature Controllers to each other.
48 × 48 mm E5CC-T Refer to your OMRON website for the most recent information on applicable safety standards. Refer to Safety Precautions on page 104.
Main I/O Functions Sensor Input Universal input • Thermocouple • Pt • Analog current/voltage
E5CC-T Dual displays: PV/SV
Control Output 1 • Relay output • Voltage output (for driving SSR) • Linear current output
Indication Accuracy • Thermocouple input: ±0.3% of PV • Pt input: ±0.2% of PV • Analog input: ±0.2% of FS
Control Output 2 • None • Voltage output (for driving SSR)
Sampling Period • 50 ms Event Inputs • None •2 •4 Serial Communications • None • RS-485
4-digit displays
• PF (shift) Key • Temperature status display • Operating and editing the program • Independent heating and cooling PID control • Parameter mask setting • Display brightness setting
Auxiliary Outputs •3 Transfer Output • None •1
This datasheet is provided as a guideline for selecting products. Be sure to refer to the following manuals for application precautions and other information required for operation before attempting to use the product. E5@C-T Digital Temperature Controllers Programmable Type User’s Manual (Cat. No. H185) E5@C-T Digital Temperature Controllers Programmable Type Communications Manual (Cat. No. H186)
64
E5CC-T
Model Number Legend and Standard Models Model Number Legend ●Models with Screw Terminals E5CC-T @@3 @5 M -@@@ (Example: E5CC-TRX3A5M-000) −−−−−− −−− A BC D E F A Model
Control outputs 1 and 2
B
C
D
No. of Power Terminal auxiliary supply type outputs voltage
E
F
Input type
Options
E5CC-T RX QX *1 CX QQ CQ 3 A D 5 M
*1
000 001
*1
003
*3
004 005 006
Meaning 48 × 48 mm Programmable Type Control output 1 Control output 2 Relay output None Voltage output None (for driving SSR) Linear current output *2 None Voltage output Voltage output (for driving SSR) (for driving SSR) Voltage output Linear current output *2 (for driving SSR) 3 (one common) 100 to 240 VAC 24 VAC/DC Screw terminals (with cover) Universal input HB alarm CommunicaEvent Transfer and HS tions inputs output alarm --------1 --2 --2 (for 3-phase RS-485 ----heaters) --RS-485 2 ------4 ------2 Provided.
*1. Options with HB and HS alarms (001 and 003) cannot be selected if a linear current output is selected for the control output. *2. The linear current output cannot be used as a transfer output. *3. Option 004 can be selected only when “CX” is selected for the control outputs.
Heating and Cooling Control ● Using Heating and Cooling Control A Control Output Assignment If there is no control output 2, an auxiliary output is used as the cooling control output. If there is a control output 2, the two control outputs are used for heating and cooling. (It does not matter which output is used for heating and which output is used for cooling.) B Control If PID control is used, you can set PID control separately for heating and cooling. This allows you to handle control systems with different heating and cooling response characteristics.
65
E5CC-T Optional Products (Order Separately) USB-Serial Conversion Cable Model E58-CIFQ2
Front Covers Type Hard Front Cover Soft Front Cover
Model Y92A-48H Y92A-48D
Terminal Covers CX-Thermo Support Software
Model E53-COV17 E53-COV23 (3pcs)
Model EST2-2C-MV4
Note: The Terminal Covers E53-COV23 are provided with the Digital Temperature Controller. The E53-COV10 cannot be used. Refer to page 75 for the mounted dimensions.
Waterproof Packing Model Y92S-P8 Note: The Waterproof Packing is provided with the Digital Temperature Controller.
Current Transformers (CTs) Hole diameter 5.8 mm 12.0 mm
Model E54-CT1 E54-CT3
Adapter Model Y92F-45 Note: Use this Adapter when the panel has already been prepared for an E5B@ Controller.
Waterproof Cover Model Y92A-48N
Mounting Adapter Model Y92F-49 Note: This Mounting Adapter is provided with the Digital Temperature Controller.
DIN Track Mounting Adapter Model Y92F-52
66
Note: CX-Thermo version 4.61 or higher is required for the E5CC-T. For the system requirements for the CX-Thermo, refer to information on the EST2-2C-MV4 on the OMRON website (www.ia.omron.com).
E5CC-T Specifications Ratings Power supply voltage Operating voltage range Power consumption
Sensor input
Input impedance Control method Relay output Control output
Auxiliary output
Voltage output (for driving SSR) Linear current output Number of outputs Output specifications Number of inputs
Event input External contact input specifications Transfer output
Number of outputs Output specifications
Setting method Indication method Bank switching Other functions
Ambient operating temperature Ambient operating humidity Storage temperature Altitude Recommended fuse Installation environment
A in model number: 100 to 240 VAC, 50/60 Hz D in model number: 24 VAC, 50/60 Hz; 24 VDC 85% to 110% of rated supply voltage 7.5 VA max. at 100 to 240 VAC, and 4.1 VA max. at 24 VAC or 2.3 W max. at 24 VDC Temperature input Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II Platinum resistance thermometer: Pt100 or JPt100 Infrared temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C Analog input Current input: 4 to 20 mA or 0 to 20 mA Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V Current input: 150 Ω max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB/THB.) 2-PID control (with auto-tuning) or ON/OFF control SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA (reference value) Output voltage: 12 VDC ±20% (PNP), max. load current: 21 mA, with short-circuit protection circuit 4 to 20 mA DC/0 to 20 mA DC, load: 500 Ω max., resolution: approx. 10,000 3 SPST-NO relay outputs, 250 VAC, Models with 3 outputs: 2 A (resistive load), Electrical life: 100,000 operations, Minimum applicable load: 10 mA at 5 V (reference value) 2 or 4 (depends on model) Contact input: ON: 1 kΩ max., OFF: 100 kΩ min. Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max. Current flow: Approx. 7 mA per contact 1 (only on models with a transfer output) Current output: 4 to 20 mA DC, load: 500 Ω max., resolution: approx. 10,000 Linear voltage output: 1 to 5 VDC, load: 1 kΩ min., resolution: Approx. 10,000 Digital setting using front panel keys 11-segment digital display and individual indicators Character height: PV: 15.2 mm, SV: 7.1 mm None Manual output, heating/cooling control, loop burnout alarm, other alarm functions, heater burnout (HB) alarm (including SSR failure (HS) alarm), 40% AT, 100% AT, MV limiter, input digital filter, robust tuning, PV input shift, protection functions, extraction of square root, MV change rate limit, logic operations, temperature status display, moving average of input value, and display brightness setting −10 to 55°C (with no condensation or icing), For 3-year warranty: −10 to 50°C with standard mounting (with no condensation or icing) 25% to 85% −25 to 65°C (with no condensation or icing) 2,000 m max. T2A, 250 VAC, time-lag, low-breaking capacity Installation Category II, Pollution Degree 2 (IEC 61010-1 compliant)
67
E5CC-T Input Ranges ●Thermocouple/Platinum Resistance Thermometer (Universal inputs) Sensor type
Platinum resistance thermometer
Sensor specification
Pt100
Infrared temperature sensor
Thermocouple
JPt100
K
J
T
E
L
U
N
R
S
B
W
PLII
10 to 70°C
60 to 120°C
115 to 165°C
120
165
140 to 260°C
2300
2300
1800
1800
1700
1700
1700
Temperature range (°C)
1600 1500 1400
1300
1300
1300
1300
1200 1100 1000 900
850
850
850
800 700
600
600
500.0
500
500.0
500.0 400.0
400
400
400.0
400
400.0 260
300 200
100.0
100
90 100
0
0.0
-100 -200
100.0
-200
-199.9
0
1
Set value
0.0 199.9
2
3
-20.0
-100
-20.0
6
7
8
-200
4
5
0
0
16
17
0
0
0
0
0
0
19
20
21
22
23
24
-100 -200
-199.9
-200
9
10
11
12
-200
-199.9
-200
13
14
15
18
Shaded settings are the default settings. The applicable standards for the input types are as follows: K, J, T, E, N, R, S, B: JIS C 1602-1995, IEC 60584-1 L: Fe-CuNi, DIN 43710-1985 U: Cu-CuNi, DIN 43710-1985 W: W5Re/W26Re, ASTM E988-1990
JPt100: JIS C 1604-1989, JIS C 1606-1989 Pt100: JIS C 1604-1997, IEC 60751 PL II: According to Platinel II electromotive force charts from BASF (previously Engelhard)
●Analog input Input type Input specification Setting range Set value
68
Current 4 to 20 mA 0 to 20 mA
Voltage 1 to 5 V
0 to 5 V
Usable in the following ranges by scaling: -1999 to 9999, -199.9 to 999.9, -19.99 to 99.99 or -1.999 to 9.999 25 26 27 28
0 to 10 V
29
E5CC-T Alarm Types Each alarm can be independently set to one of the following 17 alarm types. The default is 2: Upper limit. (see note.) Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified. Note: In the default settings for models with HB or HS alarms, alarm 1 is set to a heater alarm (HA) and the Alarm Type 1 parameter is not displayed. To use alarm 1, set the output assignment to alarm 1. Set value
Alarm type
0
Alarm function OFF
1
Upper- and lower-limit *1
2 Upper-limit (default) 3
Lower-limit
4
Upper- and lower-limit range *1
Alarm output operation Description of function When alarm value X When alarm value X is positive is negative Output OFF No alarm Set the upward deviation in the set point for the alarm upper L H limit (H) and the lower deviation in the set point for the alarm ON *2 OFF PV lower limit (L). The alarm is ON when the PV is outside this SP deviation range. Set the upward deviation in the set point by setting the alarm X X ON ON value (X). The alarm is ON when the PV is higher than the OFF PV OFF PV SP SP SP by the deviation or more. Set the downward deviation in the set point by setting the X X ON ON alarm value (X). The alarm is ON when the PV is lower than OFF PV OFF PV SP SP the SP by the deviation or more. Set the upward deviation in the set point for the alarm upper L H limit (H) and the lower deviation in the set point for the alarm ON *3 OFF PV lower limit (L). The alarm is ON when the PV is inside this deSP viation range.
Upper- and lower-limit with standby sequence *1 *5 Upper-limit with standby sequence
ON OFF
7
Lower-limit with standby sequence
ON OFF
8
Absolute-value upper-limit
ON OFF
9
Absolute-value lower-limit
ON OFF
10
Absolute-value upper-limit with standby sequence
ON OFF
11
Absolute-value lower-limit with standby sequence
ON OFF
12 13
LBA (alarm 1 type only) PV change rate alarm
14
SP absolute-value upper-limit alarm
ON OFF
15
SP absolute-value lower-limit alarm
ON OFF
5 6
L
H
X
ON OFF
SP
PV
ON OFF
PV
ON OFF
PV
ON OFF
PV
ON OFF
PV
ON OFF
PV
ON OFF
X SP X 0 X 0 X 0 X 0
ON OFF
MV absolute-value upper-limit alarm *9
X 0
PV
A standby sequence is added to the upper-limit alarm (2). *6
PV
A standby sequence is added to the lower-limit alarm (3). *6
X SP X 0
PV
X 0
PV
X 0
PV
X 0
PV
ON OFF
SP
ON OFF
X 0
The alarm will turn ON if the process value is smaller than the alarm value (X) regardless of the set point. A standby sequence is added to the absolute-value upperlimit alarm (8). *6 A standby sequence is added to the absolute-value lowerlimit alarm (9). *6
X 0
SP
X 0
SP
This alarm type turns ON the alarm when the set point (SP) is higher than the alarm value (X). This alarm type turns ON the alarm when the set point (SP) is lower than the alarm value (X).
Standard Control
X MV
0
The alarm will turn ON if the process value is larger than the alarm value (X) regardless of the set point.
*7 *8
SP
ON OFF
X 0
MV
X MV
0
Standard Control ON OFF
17
SP
This alarm type turns ON the alarm when the manipulated Heating/Cooling Heating/Cooling variable (MV) is higher than the alarm value (X). Control (Heating MV) Control (Heating MV) ON OFF
MV absolute-value lower-limit alarm *9
X
-
Standard Control
16
A standby sequence is added to the upper- and lower-limit alarm (1). *6
*4
PV
SP
X MV
0
Always ON Standard Control ON OFF
X 0
MV
This alarm type turns ON the alarm when the manipulated Heating/Cooling Heating/Cooling variable (MV) is lower than the alarm value (X). Control (Cooling MV) Control (Cooling MV) ON OFF
X 0
MV
Always ON
69
E5CC-T *1 *2
With set values 1, 4 and 5, the upper and lower limit values can be set independently for each alarm type, and are expressed as “L” and “H.” Set value: 1, Upper- and lower-limit alarm Case 2
Case 1
Case 3 (Always ON)
H<0, L<0 L
H SP
H<0, L>0 |H| < |L|
H
SP L H H>0, L<0 |H| > |L|
SP
L H<0, L>0 |H| ≥ |L|
L SP
H
SP H
*3
L
Set value: 4, Upper- and lower-limit range Case 1
L
Case 3 (Always OFF)
Case 2
H SP
H<0, L>0 |H| < |L|
SP L
H
H
H>0, L<0 |H| > |L|
H
SP
L
L SP SP H L
70
H>0, L<0 |H| ≤ |L|
H<0, L<0 H<0, L>0 |H| ≥ |L| H>0, L<0 |H| ≤ |L|
*4
Set value: 5, Upper- and lower-limit with standby sequence For Upper- and Lower-Limit Alarm Described Above *2 • Case 1 and 2 Always OFF when the upper-limit and lower-limit hysteresis overlaps. • Case 3: Always OFF *5. Set value: 5, Upper- and lower-limit with standby sequence Always OFF when the upper-limit and lower-limit hysteresis overlaps. *6 Refer to the E5@C-T Digital Temperature Controllers Programmable Type User's Manual (Cat. No. H185) for information on the operation of the standby sequence. *7 Refer to the E5@C-T Digital Temperature Controllers Programmable Type User's Manual (Cat. No. H185) for information on the loop burnout alarm (LBA). *8 Refer to the E5@C-T Digital Temperature Controllers Programmable Type User's Manual (Cat. No. H185) for information on the PV change rate alarm. *9 When heating/cooling control is performed, the MV absolute upper limit alarm functions only for the heating operation and the MV absolute lower limit alarm functions only for the cooling operation.
E5CC-T Characteristics Thermocouple: (±0.3% of indication value or ±1°C, whichever is greater) ±1 digit max. *1 Platinum resistance thermometer: (±0.2% of indication value or ±0.8°C, whichever is greater) ±1 digit max. Analog input: ±0.2% FS ±1 digit max. CT input: ±5% FS ±1 digit max. Transfer output accuracy ±0.3% FS max. Influence of temperature *2 Thermocouple input (R, S, B, W, PL II): (±1% of indication value or ±10°C, whichever is greater) ±1 digit max. Other thermocouple input: (±1% of indication value or ±4°C, whichever is greater) ±1 digit max. *3 Platinum resistance thermometer: (±1% of indication value or ±2°C, whichever is greater) ±1 digit max. Influence of voltage *2 Analog input: ±1%FS ±1 digit max. CT input: ±5% FS ±1 digit max. Input sampling period 50 ms Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F) Hysteresis Analog input: 0.01% to 99.99% FS (in units of 0.01% FS) Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F) Proportional band (P) Analog input: 0.1% to 999.9% FS (in units of 0.1% FS) Integral time (I) 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4 Derivative time (D) 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4 Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F) Proportional band (P) for cooling Analog input: 0.1% to 999.9% FS (in units of 0.1% FS) Integral time (I) for cooling 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4 Derivative time (D) for cooling 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4 Control period 0.1, 0.2, 0.5, 1 to 99 s (in units of 1 s) Manual reset value 0.0 to 100.0% (in units of 0.1%) Alarm setting range -1999 to 9999 (decimal point position depends on input type) Thermocouple: 0.1°C/Ω max. (100 Ωmax.) Influence of signal source resistance Platinum resistance thermometer: 0.1°C/Ω max. (10 Ω max.) Insulation resistance 20 MΩ min. (at 500 VDC) Dielectric strength 3,000 VAC, 50/60 Hz for 1 min between terminals of different charge Malfunction 10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions Vibration Resistance 10 to 55 Hz, 20 m/s2 for 2 hrs each in X, Y, and Z directions Malfunction 100 m/s2, 3 times each in X, Y, and Z directions Shock Resistance 300 m/s2, 3 times each in X, Y, and Z directions Weight Controller: Approx. 120 g, Adapter: Approx. 10 g Degree of protection Front panel: IP66, Rear case: IP20, Terminals: IP00 Memory protection Non-volatile memory (number of writes: 1,000,000 times) Setup Tool CX-Thermo version 4.61 or higher E5CC-T top panel: An E58-CIFQ2 USB-Serial Conversion Cable is used to connect to a USB port on Setup Tool port the computer. *5 Approved standards UL 61010-1, Korean Radio Waves Act (Act 10564) Standards Conformed standards EN 61010-1 (IEC 61010-1): Pollution Degree 2, overvoltage category II EMI: EN61326 Radiated Interference Electromagnetic Field Strength: EN 55011 Group 1, class A Noise Terminal Voltage: EN 55011 Group 1, class A EMS: EN 61326 ESD Immunity: EN 61000-4-2 EMC Electromagnetic Field Immunity: EN 61000-4-3 Burst Noise Immunity: EN 61000-4-4 Conducted Disturbance Immunity: EN 61000-4-6 Surge Immunity: EN 61000-4-5 Voltage Dip/Interrupting Immunity: EN 61000-4-11 Indication accuracy (at the ambient temperature of 23°C)
*1 The indication accuracy of K thermocouples in the −200 to 1300°C range, T and N thermocouples at a temperature of −100°C max., and U and L thermocouples at any temperatures is ±2°C ±1 digit max. The indication accuracy of the B thermocouple at a temperature of 400°C max. is not specified. The indication accuracy of B thermocouples at a temperature of 400 to 800°C is ±3°C max. The indication accuracy of the R and S thermocouples at a temperature of 200°C max. is ±3°C ±1 digit max. The indication accuracy of W thermocouples is (±0.3% of PV or ±3°C, whichever is greater) ±1 digit max. The indication accuracy of PL II thermocouples is (±0.3% of PV or ±2°C, whichever is greater) ±1 digit max. *2 Ambient temperature: −10°C to 23°C to 55°C, Voltage range: −15% to 10% of rated voltage *3 K thermocouple at −100°C max.: ±10°C max. *4 The unit is determined by the setting of the Integral/Derivative Time Unit parameter. *5 External communications (RS-485) and USB-serial conversion cable communications can be used at the same time.
71
E5CC-T Program Control Number of programs (patterns) Number of segments (steps) Segment setting method Segment times Alarm setting Reset operation Startup operation PID sets
Number of sets Setting method
Alarm SP function Program status control Wait operation
Time signals
Segment operation Program operation Wait method Wait width setting Number of outputs Number of ON/OFF Operations Setting method
Program status output PV start Program startup operation Operation end operation Program SP shift
72
Standby
8 32 Time setting (Segment set with set point and time.) Slope setting (Segment set with segment type, set point, slope, and time.) 0 h 0 min to 99 h 59 min 0 min 0 s to 99 min 59 s Set separately for each program. Select either stopping control or fixed SP operation. Select continuing, resetting, manual operation, or run mode. 8 Set separately for each program (automatic PID group selection also supported). Select from ramp SP and target SP. Advance, segment jump, hold, and wait Program repetitions and program links Waiting at segment ends Same wait width setting for all programs 2 1 each per output Set separately for each program. Program end output (pulse width can be set), run output, stage output Select from segment 1 set point, slope-priority PV start 0 h 0 min to 99 h 59 min 0 day 0 h to 99 day 23h Select from resetting, continuing control at final set point, and fixed SP control. Same program SP shift for all programs
E5CC-T USB-Serial Conversion Cable Applicable OS
Windows XP, Vista, or 7
Applicable software
CX-Thermo version 4.61 or higher
Applicable models
E5@C-T Series, E5@C Series, and E5CB Series
USB interface standard
Conforms to USB Specification 2.0.
DTE speed
38400 bps
Connector specifications
Computer: USB (type A plug) Digital Temperature Controller: Special serial connector
Power supply
Bus power (Supplied from USB host controller.)*
Power supply voltage
5 VDC
Current consumption
450 mA max.
Output voltage
4.7±0.2 VDC (Supplied from USB-Serial Conversion Cable to the Digital Temperature Controller.)
Output current
250 mA max. (Supplied from USB-Serial Conversion Cable to the Digital Temperature Controller.)
Component Communications
When Digital Temperature Controllers are connected, set points and RUN/STOP commands can be sent from the Digital Temperature Controller that is set as the master to the Digital Temperature Controllers that are set as slaves. Slope and offsets can be set for the set point. Number of connected Digital Temperature Controllers: 32 max. (including master)
Copying*1
When Digital Temperature Controllers are connected, the parameters can be copied from the Digital Temperature Controller that is set as the master to the Digital Temperature Controllers that are set as slaves.
MELSEC is a registered trademark of Mitsubishi Electric Corporation. *1 Both the programless communications and the component communications support the copying.
Current Transformer (Order Separately) Ratings
Ambient operating temperature
0 to 55°C (with no condensation or icing)
Dielectric strength Vibration resistance
Ambient operating humidity
10% to 80%
Weight
Storage temperature
-20 to 60°C (with no condensation or icing)
Storage humidity
10% to 80%
Altitude
2,000 m max.
Weight
Approx. 120 g
Communications Specifications Transmission line connection method
RS-485: Multidrop
Communications
RS-485 (two-wire, half duplex)
Synchronization method
Start-stop synchronization
Protocol
CompoWay/F, or Modbus
Baud rate*
9600, 19200, 38400, or 57600 bps
Transmission code
ASCII
Data bit length*
7 or 8 bits
Stop bit length*
1 or 2 bits
Error detection
Vertical parity (none, even, odd) Block check character (BCC) with CompoWay/F or CRC-16 Modbus
Flow control
None
Interface
RS-485
Retry function
None
Communications buffer 217 bytes Communications response wait time
0 to 99 ms Default: 20 ms
* The baud rate, data bit length, stop bit length, and vertical parity can be individually set using the Communications Setting Level.
Communications Functions
Programless communications*1
You can use the memory in the PLC to read and write E5@C-T parameters, start and reset operation, etc. The E5@C-T automatically performs communications with PLCs. No communications programming is required. Number of connected Digital Temperature Controllers: 32 max. Applicable PLCs OMRON PLCs CS Series, CJ Series, or CP Series Mitsubishi Electric PLCs MELSEC Q Series, L Series
Heater Burnout Alarms and SSR Failure Alarms CT input (for heater current detection) Maximum heater current Input current indication accuracy Heater burnout alarm setting range *1 SSR failure alarm setting range *2
Models with detection for single-phase heaters: One input Models with detection for singlephase or three-phase heaters: Two inputs 50 A AC ±5% FS ±1 digit max. 0.1 to 49.9 A (in units of 0.1 A) Minimum detection ON time: 100 ms *3 0.1 to 49.9 A (in units of 0.1 A) Minimum detection OFF time: 100 ms *4
*1 For heater burnout alarms, the heater current will be measured when the control output is ON, and the output will turn ON if the heater current is lower than the set value (i.e., heater burnout detection current value). *2 For SSR failure alarms, the heater current will be measured when the control output is OFF, and the output will turn ON if the heater current is higher than the set value (i.e., SSR failure detection current value). *3 The value is 30 ms for a control period of 0.1 s or 0.2 s. *4 The value is 35 ms for a control period of 0.1 s or 0.2 s.
Electrical Life Expectancy Curve for Relays (Reference Values) Life (× 104 operations)
Windows is a registered trademark of Microsoft Corporation in the United States and or other countries. * Use a high-power port for the USB port. Note: A driver must be installed on the computer. Refer to the Instruction Manual included with the Cable for the installation procedure.
Accessories (E54-CT3 only)
1,000 VAC for 1 min 50 Hz, 98 m/s2 E54-CT1: Approx. 11.5 g, E54-CT3: Approx. 50 g Armatures (2) Plugs (2)
500 300
100 50 30
10 5
E5CC-T 250 VAC, 30 VDC (resistive load) cosφ = 1
3
1 0
1
2
3
4
5
6
Switching current (A)
73
E5CC-T External Connections E5CC-T Control output 1 Relay output 250 VAC, 3 A (resistive load) Voltage output (for driving SSR) 12 VDC, 21 mA Linear current output 0 to 20 mA DC 4 to 20 mA DC Load: 500 Ω max.
(1)
R
Auxiliary outputs
Control output 2 12 VDC, 21 mA
CX
OUT1
1 2 3
QQ
+Q −
1 2 3
CQ
Models with 2 Voltage Outputs (for Driving SSR)
Models with 1 Linear Current Output OUT1
+ C −
1 2 3
A B B
Pt 4 5 6
(6) Options 001 Event inputs 1 and 2, and CT1
−
13 + EV1
+ EV2
CT1
14
+ mA −
I 4 5 6
OUT1
V 4 − 5 V 6 +
+ C - OUT2 + Q
Auxiliary outputs 1, 2, and 3
1
13
7
2
14
3
8 9
4
15 16
10
5
17
11
6
18
12
7 Auxiliary output 3 8 Auxiliary output 2 9 Auxiliary output 1 10 (3) Input Power Supply 100 to 240 VAC
005
006
Communications (RS-485) and event inputs 3 and 4
Event inputs 1 to 4
Event inputs 1 and 2, and transfer output
B(+) A(−)
B(+)
13
RS-485
14
A(−)
15 16
CT1 COM
CT2
−
17 18
+
EV3 EV4
+
13
− +
14 15
+
16
−
17 18
EV1 EV2
+
EV3
+ EV4
Isolation/Insulation Block Diagrams Models with 3 Auxiliary Outputs Sensor input and CT inputs Communications and event inputs Voltage output (for driving SSR), linear current output, and transfer output Relay output Auxiliary outputs 1, 2, 3
: Reinforced insulation : Functional isolation
Note: Auxiliary outputs 1 to 3 are not insulated.
74
12 (no polarity)
13 14
−
15
+
+ EV1 EV2
13 14 15
16
16
17
17
18
18
+ +V I
Note: 1. The application of the terminals depends on the model. 2. Do not wire the terminals that are shown with a gray background. 3. When complying with EMC standards, the cable that connects the sensor must be 30 m or less. If the cable length exceeds 30 m, compliance with EMC standards will not be possible. 4. Connect M3 crimped terminals.
Power supply
11
12
004
RS-485
24 VAC/DC
11
Communications (RS-485), CT1, and CT2
16 18
(2) Auxiliary Outputs
OUT1
1 2 3
003
15 17
Models with 2 Outputs: Linear Current Output and Voltage (for Driving SSR)
+Q − OUT2 +Q
(5) Sensor (Temperature/Analog) Input TC 4 − 5 + 6
(6)
The E5CC-T is set for a K-type thermocouple (input type = 5) by default. An input error (s.err) will occur if the input type setting does not agree with the temperature sensor. Check the input type.
Relay output Models with 3 auxiliary outputs: 250 VAC: 2 A (resistive load)
Voltage output (for driving SSR)
Models with 1 Voltage Output (for Driving SSR)
OUT1
1 2 3
5M
(2) (3) (4) (5) Terminal type
(1) Control outputs 1, 2 RX QX Models with 1 Relay Output
3
E5CC T
Transfer output
−
E5CC-T Nomenclature E5CC-T
Front panel Temperature unit Operation indicators
No. 1 display
PV or specified monitor/setting parameter Top View of E5CC-T No. 2 display
Press O Key once to go to Program Setting Level.
SP or specified monitor/parameter value Top-panel Setup Tool port
Press O Key for at least 3 seconds to go to Initial Setting Level.
Use the UD Keys to set the parameter. Press U Key for at least 1 second when Process value/Set point parameter are displayed in Program SP Mode to go to Display Segment Selection parameter in Program Setting Level.
Use the M Key to change to another parameter. Press M and D Keys simultaneously for at least 1 second to switch between run and reset status. Use S Key to change the digit (default setting).
Dimensions
(Unit: mm)
Controllers E5CC-T
48 × 48
4 1
Panel Cutout Mounted Separately Group Mounted
(64) 60
(48 × number of units - 2.5)+1.0 0 48 × 48
58
45+0.6 0
Group mounting does not allow waterproofing.
60 min.
45+0.6 0
Waterproof Packing (Accessory)
Mounting Adapter (Accessory)
45+0.6 0
• Recommended panel thickness is 1 to 5 mm. The Setup Tool port is on the top of the Temperature Controller. It is used to connect the Temperature Controller to the computer • Group mounting is not possible in the vertical direction. (Maintain the specified mounting space between Controllers.) to use the Setup Tool. The E58-CIFQ2 USB-Serial Conversion Cable is required to • To mount the Controller so that it is waterproof, insert the make the connection. waterproof packing onto the Controller. Refer to the instructions that are provided with the USB-Serial • When two or more Controllers are mounted, make sure that the Conversion Cable for the connection procedure. surrounding temperature does not exceed the allowable operating Note: Do not leave the USB-Serial Conversion Cable temperature specified in the specifications. connected when you use the Temperature Controller. • Use a control panel thickness of 1 to 3 mm if the Y92A-48N and a USB-Serial Conversion Cable are used together.
75
E5CC-T Accessories (Order Separately) ● USB-Serial Conversion Cable E58-CIFQ2
(2110) 250
263
1510
LED (RD)
USB connector (type A plug)
Serial connector
LED (PWR) LED (SD)
● Terminal Covers E53-COV17
48
● Terminal Covers E53-COV23 (Three Covers provided.) 2
3.8
48.8
10 Terminal Cover (E53-COV23) 22
44.8
9.1
● Waterproof Packing Y92S-P8 (for DIN 48 × 48)
76
The Waterproof Packing is provided with the Temperature Controller. Order the Waterproof Packing separately if it becomes lost or damaged. The Waterproof Packing can be used to achieve an IP66 degree of protection. (Deterioration, shrinking, or hardening of the waterproof packing may occur depending on the operating environment. Therefore, periodic replacement is recommended to ensure the level of waterproofing specified in IP66. The time for periodic replacement depends on the operating environment. Be sure to confirm this point at your site. Consider three years as a rough standard.) The Waterproof Packing does not need to be attached if a waterproof structure is not required.
E5CC-T ● Current Transformers E54-CT1
21 15
Thru-current (Io) vs. Output Voltage (Eo) (Reference Values) E54-CT1
2.8 5.8 dia. 7.5
25
Maximum continuous heater current: 50 A (50/60 Hz) Number of windings: 400±2 Winding resistance: 18±2 Ω
3
Output voltage (Eo) V (r.m.s.)
10.5 40 Two, 3.5 dia. 10 30
100V
Frequency: 50 Hz ∞ 1kΩ
10
Distortion factor 10%
1
3% 1%
100mV 100Ω
10
E54-CT3 2.36 dia. 30
RL=10Ω
1 12 dia. 9
100μV 10 1
40 × 40
10
100mA
1
10
100 1,000A
Thru-current (Io) A (r.m.s.)
Thru-current (Io) vs. Output Voltage (Eo) (Reference Values) E54-CT3
Two, M3 (depth: 4) 15
E54-CT3 Accessories • Armature Approx. 3 dia.
Connection Example Plug
Armature
Lead
18
• Plug
Output voltage (Eo) V (r.m.s.)
Maximum continuous heater current: 120 A (50/60 Hz) (Maximum continuous heater current for an OMRON Digital Temperature Controller is 50 A.) Number of windings: 400±2 Winding resistance: 8±0.8 Ω
30
100V
Frequency: 50 Hz Distortion factor 10% 3% 1%
∞ 1kΩ 500Ω
10 1 100mV
100Ω 50Ω
10
RL=10Ω 1
Approx. 6 dia.
100μV (22) 10 1
10
100mA
1
10
100 1,000A
Thru-current (Io) A (r.m.s.)
77
E5CC-T ● Adapter Y92F-45
Note: 1. Use this Adapter when the Front Panel has already been prepared for the E5B@. 2. Only black is available. 3. You cannot use the E58-CIFQ2 USB-Serial Conversion Cable if you use the Y92F-45 Adapter. To use the USB-Serial Conversion Cable to make the settings, do so before you mount the Temperature Controller in the panel. Fixture (Accessory) 76
4.7
69.6 to 77.6 72 × 72
67 × 67 87
Mounted to E5CC-T
Panel (1 to 8 mm) 72 × 72
Mounting Adapter Y92F-30 (Accessory)
48 × 48
2.2
4.7 62.8 To back of the E5CC-T
● DIN Track Mounting Adapter Y92F-52
Note: This Adapter cannot be used together with the Terminal Cover. Remove the Terminal Cover to use the Adapter.
61
3.5 38
50
Mounted to E5CC-T
48
80.5
78
This Adapter is used to mount the E5CC-T to a DIN Track. If you use the Adapter, there is no need for a plate to mount in the panel or to drill mounting holes in the panel.
E5CC-T
● Watertight Cover
● Mounting Adapter
Y92A-48N
Y92F-49 21.9
14
The Mounting Adapter is provided with the Temperature Controller. Order this Adapter separately if it becomes lost or damaged.
(2)
87.7
69
79.2
12 67.6
● Protective Cover
● Protective Cover
Y92A-48D
Y92A-48H
Note: This Protective Cover cannot be used if the Waterproof Packing is installed. This Protective Cover is soft type. It is able to operate the controller with using this cover.
This Protective Cover is hard type. Please use it for the mis-operation prevention etc.
79
Programmable Temperature Controller (Digital Controller)
E5EC-T/E5AC-T
(48 × 96 mm/96 × 96 mm)
Programmable Controllers Join the E5C Series! Program up to 256 segments can handle a wide variety of applications. • Set up to 8 Programs (Patterns) with 32 Segments (Steps) Each • A white LCD PV display with a height of approx. 18 mm for the E5ECT and 25 mm for the E5AC-T improves visibility. • Tool ports are provided both on the top panel and the front panel. Set up the Controller without wiring the power supply by connecting to the computer with a Communications Conversion Cable (sold separately). Setup is easy with the CX-Thermo (sold separately). • High-speed sampling at 50 ms. • Models are available with up to 4 auxiliary outputs, up to 6 event inputs, and a transfer output to cover a wide range of applications. • Short body with depth of only 60 mm. • Easy connections to a PLC with programless communications. Use component communications to link Temperature Controllers to each other. • The new position-proportional control models allow you to control valves as well. (The position-proportional control models are scheduled to be released in May, 2014.)
48 × 96 mm E5EC-T
96 × 96 mm E5AC-T
Refer to your OMRON website for the most recent information on applicable safety standards.
Refer to Safety Precautions on page 104.
Main I/O Functions Sensor Input Universal input • Thermocouple • Pt • Analog current/voltage
E5EC-T
E5AC-T
Three-level Display Simultaneous display of the PV, SP, Program No., Segment No., etc.
4-digit displays
Indication Accuracy
Control Output 1 • Relay output • Voltage output (for driving SSR) • Linear current output
• Thermocouple input: ±0.3% of PV • Pt input: ±0.2% of PV • Analog input: ±0.2% of FS Sampling Period • 50 ms
Event Inputs • None •2 •4 •6 Serial Communications • None • RS-485
• PF (shift) Key • Setup Tool port on front panel • Temperature status display • Operating and editting the program • Independent heating and cooling PID control • Parameter mask setting • Display brightness setting
Control Output 2 • Voltage output (for driving SSR) • Relay output • Linear current output Auxiliary Outputs •4 Transfer Output • None •1
This datasheet is provided as a guideline for selecting products. Be sure to refer to the following manuals for application precautions and other information required for operation before attempting to use the product. E5@C-T Digital Temperature Controllers Programmable Type User’s Manual (Cat. No. H185) E5@C-T Digital Temperature Controllers Programmable Type Communications Manual (Cat. No. H186)
80
E5EC-T/E5AC-T
Model Number Legend and Standard Models Model Number Legend ●Models with Screw Terminals E5EC-T@@ 4 @ 5 M -@@@ (Example: E5EC-TRX4A5M-000) −−− − − − −−− A BC D E F
E5AC-T@@ 4 @ 5 M -@@@ (Example: E5AC-TRX4A5M-000) −−−− − − −−− A BC D E F A Model
Control outputs 1 and 2
B
C
D
E
F
No. of auxil- Power Terminal Input Options iary out- supply type type puts voltage
48 × 96 mm Programmable Type 96 × 96 mm Programmable Type Control output 1 Control output 2 Relay output None Voltage output None (for driving SSR) Linear current output None Voltage output Voltage output (for driving SSR) (for driving SSR) Voltage output Relay output (for driving SSR) Relay output Relay output Linear current output Linear current output Voltage output Linear current output (for driving SSR) Position-proportional relay out- Position-proportional reput lay output 4 (auxiliary outputs 1 and 2 with same common and auxiliary outputs 3 and 4 with same common) 100 to 240 VAC 24 VAC/DC Screw terminals (with cover) Universal input
E5EC-T E5AC-T RX QX *2 CX QQ QR RR *2 CC *2 CQ *3 PR 4 A D 5 Control outputs 1 and 2 For RX, For CX or QX, QQ, For PR QR, RR, or CC CQ Selectable Selectable Selectable Option Selectable Selectable selection Selectable conditions *1 Selectable Selectable Selectable Selectable Selectable Selectable
Meaning
M
HB alarm and HS alarm 000 004 005 008 010 019 021 022
------1 1 1 -----
Communications --RS-485 --RS-485 ------RS-485
Event Transfer output inputs --2 4 2 4 6 6 4
----------Provided. Provided. Provided.
*1. The options that can be selected depend on the type of control output. *2. The linear current output cannot be used as a transfer output. *3. Models with Position-proportional Control are scheduled for release in May 2014.
Heating and Cooling Control ●Using Heating and Cooling Control
A Control Output Assignment If there is no control output 2, an auxiliary output is used as the cooling control output. If there is a control output 2, the two control outputs are used for heating and cooling. (It does not matter which output is used for heating and which output is used for cooling.) B Control If PID control is used, you can set PID control separately for heating and cooling. This allows you to handle control systems with different heating and cooling response characteristics.
81
E5EC-T/E5AC-T Optional Products (Order Separately) USB-Serial Conversion Cable Model E58-CIFQ2
Communications Conversion Cable
Note: Always use this product together with the E58-CIFQ2. This Cable is used to connect to the front-panel Setup Tool port.
Terminal Covers Model E53-COV24 (3pcs) Note: The Terminal Covers E53-COV24 are provided with the Digital Temperature Controller.
Waterproof Packing Model Y92S-P9 Y92S-P10
Note: This Waterproof Packing is provided with the Digital Temperature Controller.
Waterproof Cover Applicable Controller E5EC-T E5AC-T
Model Y92A-49N Y92A-96N
Front Port Cover Model Y92S-P7 Note: This Front Port Cover is provided with the Digital Temperature Controller.
Mounting Adapter Model Y92F-51 (2pcs) Note: This Mounting Adapter is provided with the Digital Temperature Controller.
82
Hole diameter 5.8 mm 12.0 mm
Model E54-CT1 E54-CT3
CX-Thermo Support Software
Model E58-CIFQ2-E
Applicable Controller E5EC-T E5AC-T
Current Transformers (CTs)
Model EST2-2C-MV4 Note: CX-Thermo version 4.61 or higher is required for the E5EC-T/ E5AC-T. For the system requirements for the CX-Thermo, refer to information on the EST2-2C-MV4 on the OMRON website (www.ia.omron.com).
E5EC-T/E5AC-T Specifications Ratings A in model number: 100 to 240 VAC, 50/60 Hz D in model number: 24 VAC, 50/60 Hz; 24 VDC Operating voltage range 85% to 110% of rated supply voltage E5EC-T 8.7 VA max. at 100 to 240 VAC, and 5.5 VA max. at 24 VAC or 3.2 W max. at 24 VDC Power consumption E5AC-T 9.0 VA max. at 100 to 240 VAC, and 5.6 VA max. at 24 VAC or 3.4 W max. at 24 VDC Temperature input Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II Platinum resistance thermometer: Pt100 or JPt100 Sensor input Infrared temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C Analog input Current input: 4 to 20 mA or 0 to 20 mA Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V Current input: 150 Ω max., Voltage input: 1 MΩ min. Input impedance (Use a 1:1 connection when connecting the ES2-HB/THB.) Control method 2-PID control (with auto-tuning) or ON/OFF control SPST-NO, 250 VAC, 5 A (resistive load), electrical life: 100,000 operations, Relay output minimum applicable load: 5 V, 10 mA (reference value) Control Voltage output Output voltage: 12 VDC ±20% (PNP), max. load current: 40 mA, with short-circuit protection circuit output (for driving SSR) (The maximum load current is 21 mA for models with two control outputs.) Linear current output 4 to 20 mA DC/0 to 20 mA DC, load: 500 Ω max., resolution: approx. 10,000 Number of outputs 4 Auxiliary SPST-NO. relay outputs, 250 VAC, Models with 4 outputs: 2 A (resistive load), output Output specifications Electrical life: 100,000 operations, Minimum applicable load: 10 mA at 5 V (reference value) Number of inputs 2, 4 or 6 (depends on model) Contact input: ON: 1 kΩ max., OFF: 100 kΩ min. Event input External contact input Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max. specifications Current flow: Approx. 7 mA per contact Number of outputs 1 (only on models with a transfer output) Transfer Current output: 4 to 20 mA DC, Load: 500 Ω max., Resolution: Approx. 10,000 output Output specifications Linear voltage output: 1 to 5 VDC, load: 1 kΩ min., Resolution: Approx. 10,000 Potentiometer input 100 Ω to 10 kΩ Setting method Digital setting using front panel keys 11-segment digital display and individual indicators Character height: E5EC-T: PV: 18.0 mm, SV: 11.0 mm, MV: 7.8 mm E5AC-T: PV: 25.0 mm, SV: 15.0 mm, MV: 9.5 mm Indication method Three displays. Contents: PV, SP, program No. and segment No., remaining segment time, or MV (valve opening) Numbers of digits: 4 digits Bank switching None Manual output, heating/cooling control, loop burnout alarm, other alarm functions, heater burnout (HB) alarm (including SSR failure (HS) alarm), 40% AT, 100% AT, MV limiter, input digital filter, robust tunOther functions ing, PV input shift, protection functions, extraction of square root, MV change rate limit, logic operations, temperature status display, moving average of input value, and display brightness setting −10 to 55°C (with no condensation or icing), For 3-year warranty: −10 to 50°C with standard mounting Ambient operating temperature (with no condensation or icing) Ambient operating humidity 25% to 85% Storage temperature −25 to 65°C (with no condensation or icing) Altitude 2,000 m max. Recommended fuse T2A, 250 VAC, time-lag, low-breaking capacity Installation environment Installation Category II, Pollution Degree 2 (IEC 61010-1 compliant) Power supply voltage
83
E5EC-T/E5AC-T Input Ranges ●Thermocouple/Platinum Resistance Thermometer (Universal inputs) Sensor type
Platinum resistance thermometer
Sensor specification
Pt100
Infrared temperature sensor
Thermocouple
JPt100
K
J
T
E
L
U
N
R
S
B
W
PLII
10 to 70°C
60 to 120°C
115 to 165°C
120
165
140 to 260°C
2300
2300
1800
1800
1700
1700
1700
Temperature range (°C)
1600 1500 1400
1300
1300
1300
1300
1200 1100 1000 900
850
850
850
800 700
600
600
500.0
500
500.0
500.0 400.0
400
400
400.0
400
400.0 260
300 200
100.0
100
90 100
0
0.0
-100 -200
100.0
-200
-199.9
0
1
Set value
0.0 199.9
2
3
-20.0
-100
-20.0
6
7
8
-200
4
5
0
0
16
17
0
0
0
0
0
0
19
20
21
22
23
24
-100 -200
-199.9
-200
9
10
11
12
-200
-199.9
-200
13
14
15
18
Shaded settings are the default settings. The applicable standards for the input types are as follows: K, J, T, E, N, R, S, B: JIS C 1602-1995, IEC 60584-1 L: Fe-CuNi, DIN 43710-1985 U: Cu-CuNi, DIN 43710-1985 W: W5Re/W26Re, ASTM E988-1990
JPt100: JIS C 1604-1989, JIS C 1606-1989 Pt100: JIS C 1604-1997, IEC 60751 PL II: According to Platinel II electromotive force charts from BASF (previously Engelhard)
●Analog input Input type Input specification Setting range Set value
84
Current 4 to 20 mA 0 to 20 mA
Voltage 1 to 5 V
0 to 5 V
Usable in the following ranges by scaling: -1999 to 9999, -199.9 to 999.9, -19.99 to 99.99 or -1.999 to 9.999 25 26 27 28
0 to 10 V
29
E5EC-T/E5AC-T Alarm Types Each alarm can be independently set to one of the following 17 alarm types. The default is 2: Upper limit. (see note.) Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified. Note: In the default settings for models with HB or HS alarms, alarm 1 is set to a heater alarm (HA) and the Alarm Type 1 parameter is not displayed. To use alarm 1, set the output assignment to alarm 1. Set value
Alarm type
0
Alarm function OFF
1
Upper- and lower-limit *1
2 Upper-limit (default) 3
Lower-limit
4
Upper- and lower-limit range *1
5 6
Alarm output operation Description of function When alarm value X When alarm value X is positive is negative Output OFF No alarm Set the upward deviation in the set point for the alarm upper L H limit (H) and the lower deviation in the set point for the alarm ON *2 OFF PV lower limit (L). The alarm is ON when the PV is outside this SP deviation range. Set the upward deviation in the set point by setting the alarm X X ON ON value (X). The alarm is ON when the PV is higher than the OFF PV OFF PV SP SP SP by the deviation or more. Set the downward deviation in the set point by setting the X X ON ON alarm value (X). The alarm is ON when the PV is lower than OFF PV OFF PV SP SP the SP by the deviation or more. Set the upward deviation in the set point for the alarm upper L H limit (H) and the lower deviation in the set point for the alarm ON *3 OFF PV lower limit (L). The alarm is ON when the PV is inside this deSP viation range.
Upper- and lower-limit ON with standby sequence *1 *5OFF Upper-limit with standby ON OFF sequence
7
Lower-limit with standby sequence
ON OFF
8
Absolute-value upper-limit
ON OFF
9
Absolute-value lower-limit
ON OFF
10
Absolute-value upper-limit with standby sequence
ON OFF
11
Absolute-value lower-limit with standby sequence
ON OFF
12 13
LBA (alarm 1 type only) PV change rate alarm
14
SP absolute-value upper-limit alarm
ON OFF
15
SP absolute-value lower-limit alarm
ON OFF
L
H
X SP
PV
ON OFF
PV
ON OFF
PV
ON OFF
PV
ON OFF
PV
ON OFF
X 0 X 0 X 0 X 0
ON OFF
MV absolute-value upper-limit alarm *9
X 0
PV
A standby sequence is added to the upper-limit alarm (2). *6
PV
A standby sequence is added to the lower-limit alarm (3). *6
X SP X 0
PV
X 0
PV
X 0
PV
X 0
PV
ON OFF
SP
ON OFF
X 0
The alarm will turn ON if the process value is smaller than the alarm value (X) regardless of the set point. A standby sequence is added to the absolute-value upperlimit alarm (8). *6 A standby sequence is added to the absolute-value lowerlimit alarm (9). *6
X 0
SP
X 0
SP
This alarm type turns ON the alarm when the set point (SP) is higher than the alarm value (X). This alarm type turns ON the alarm when the set point (SP) is lower than the alarm value (X).
Standard Control
X MV
0
The alarm will turn ON if the process value is larger than the alarm value (X) regardless of the set point.
*7 *8
SP
ON OFF
X 0
MV
X MV
0
Standard Control ON OFF
17
SP
This alarm type turns ON the alarm when the manipulated Heating/Cooling Heating/Cooling variable (MV) is higher than the alarm value (X). Control (Heating MV) Control (Heating MV) ON OFF
MV absolute-value lower-limit alarm *9
X
-
Standard Control
16
ON OFF
PV
X SP
A standby sequence is added to the upper- and lower-limit alarm (1). *6
*4
PV
SP
X MV
0
Always ON Standard Control ON OFF
X 0
MV
This alarm type turns ON the alarm when the manipulated Heating/Cooling Heating/Cooling variable (MV) is lower than the alarm value (X). Control (Cooling MV) Control (Cooling MV) ON OFF
X 0
MV
Always ON
85
E5EC-T/E5AC-T *1 *2
With set values 1, 4 and 5, the upper and lower limit values can be set independently for each alarm type, and are expressed as “L” and “H.” Set value: 1, Upper- and lower-limit alarm Case 2
Case 1
Case 3 (Always ON)
H<0, L<0 L
H SP
H<0, L>0 |H| < |L|
H
SP L H H>0, L<0 |H| > |L|
SP
L H<0, L>0 |H| ≥ |L|
L SP
H
SP H
*3
L
Set value: 4, Upper- and lower-limit range Case 1
L
Case 3 (Always OFF)
Case 2
H SP
H<0, L>0 |H| < |L|
SP L
H
H
H>0, L<0 |H| > |L|
H
SP
L
L SP SP H L
86
H>0, L<0 |H| ≤ |L|
H<0, L<0 H<0, L>0 |H| ≥ |L| H>0, L<0 |H| ≤ |L|
*4
Set value: 5, Upper- and lower-limit with standby sequence For Upper- and Lower-Limit Alarm Described Above *2 • Case 1 and 2 Always OFF when the upper-limit and lower-limit hysteresis overlaps. • Case 3: Always OFF *5. Set value: 5, Upper- and lower-limit with standby sequence Always OFF when the upper-limit and lower-limit hysteresis overlaps. *6 Refer to the E5@C-T Digital Temperature Controllers Programmable Type User's Manual (Cat. No. H185) for information on the operation of the standby sequence. *7 Refer to the E5@C-T Digital Temperature Controllers Programmable Type User's Manual (Cat. No. H185) for information on the loop burnout alarm (LBA). This setting cannot be used with a position-proportional model. *8 Refer to the E5@C-T Digital Temperature Controllers Programmable Type User's Manual (Cat. No. H185) for information on the PV change rate alarm. *9 When heating/cooling control is performed, the MV absolute upper limit alarm functions only for the heating operation and the MV absolute lower limit alarm functions only for the cooling operation.
E5EC-T/E5AC-T Characteristics Thermocouple: (±0.3% of indication value or ±1°C, whichever is greater) ±1 digit max. *1 Platinum resistance thermometer: (±0.2% of indication value or ±0.8°C, whichever is greater) ±1 digit max. Analog input: ±0.2% FS ±1 digit max. CT input: ±5% FS ±1 digit max. Potentiometer input: ±5% FS ±1 digit max. Transfer output accuracy ±0.3% FS max. Thermocouple input (R, S, B, W, PL II): (±1% of indication value or ±10°C, whichever is greater) ±1 digit Influence of temperature *2 max. Other thermocouple input: (±1% of indication value or ±4°C, whichever is greater) ±1 digit max. *3 Platinum resistance thermometer: (±1% of indication value or ±2°C, whichever is greater) ±1 digit max. Influence of voltage *2 Analog input: ±1%FS ±1 digit max. CT input: ±5% FS ±1 digit max. Input sampling period 50ms Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or°F) Hysteresis Analog input: 0.01% to 99.99% FS (in units of 0.01% FS) Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F) Proportional band (P) Analog input: 0.1 to 999.9% FS (in units of 0.1% FS) Standard, heating/cooling, or Position-proportional (Close): 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in Integral time (I) units of 0.1 s) Position-proportional (Floating): 1 to 9999 s (in units of 1 s), 0.1 to 999.9 s (in units of 0.1 s)*4 Derivative time (D) 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4 Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F) Proportional band (P) for cooling Analog input: 0.1 to 999.9% FS (in units of 0.1% FS) Integral time (I) for cooling 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4 Derivative time (D) for cooling 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4 Control period 0.1, 0.2, 0.5, 1 to 99 s (in units of 1 s) Manual reset value 0.0 to 100.0% (in units of 0.1%) Alarm setting range -1999 to 9999 (decimal point position depends on input type) Influence of signal source resisThermocouple: 0.1°C/Ω max. (100 Ω max.) tance Platinum resistance thermometer: 0.1°C/Ω max. (10 Ω max.) Insulation resistance 20 MΩ min. (at 500 VDC) Dielectric strength 3,000 VAC, 50/60 Hz for 1 min between terminals of different charge Malfunction 10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions Vibration Resistance 10 to 55 Hz, 20 m/s2 for 2 hrs each in X, Y, and Z directions Malfunction 100 m/s2, 3 times each in X, Y, and Z directions Shock Resistance 300 m/s2, 3 times each in X, Y, and Z directions E5EC-T Controller: Approx. 210 g, Adapter: Approx. 4 g × 2 Weight E5AC-T Controller: Approx. 250 g, Adapter: Approx. 4 g × 2 Degree of protection Front panel: IP66, Rear case: IP20, Terminals: IP00 Memory protection Non-volatile memory (number of writes: 1,000,000 times) Setup Tool CX-Thermo version 4.61 or higher E5EC-T/E5AC-T top panel: An E58-CIFQ2 USB-Serial Conversion Cable is used to connect to a USB port on the computer.*5 Setup Tool port E5EC-T/E5AC-T front panel: An E58-CIFQ2 USB-Serial Conversion Cable and E58-CIFQ2-E Conversion Cable are used together to connect to a USB port on the computer.*5 Approved standards UL 61010-1, Korean Radio Waves Act (Act 10564) Standards Conformed standards EN 61010-1 (IEC 61010-1): Pollution Degree 2, overvoltage category II EMI EN61326 Radiated Interference Electromagnetic Field Strength: EN 55011 Group 1, class A Noise Terminal Voltage: EN 55011 Group 1, class A EMS: EN 61326 ESD Immunity: EN 61000-4-2 EMC Electromagnetic Field Immunity: EN 61000-4-3 Burst Noise Immunity: EN 61000-4-4 Conducted Disturbance Immunity: EN 61000-4-6 Surge Immunity: EN 61000-4-5 Voltage Dip/Interrupting Immunity: EN 61000-4-11 Indication accuracy (at the ambient temperature of 23°C)
*1
*2 *3 *4 *5
The indication accuracy of K thermocouples in the -200 to 1300°C range, T and N thermocouples at a temperature of -100°C max., and U and L thermocouples at any temperatures is ±2°C ±1 digit max. The indication accuracy of the B thermocouple at a temperature of 400°C max. is not specified. The indication accuracy of B thermocouples at a temperature of 400 to 800°C is ±3°C max. The indication accuracy of the R and S thermocouples at a temperature of 200°C max. is ±3°C ±1 digit max. The indication accuracy of W thermocouples is (±0.3% of PV or ±3°C, whichever is greater) ±1 digit max. The indication accuracy of PL II thermocouples is (±0.3% of PV or ±2°C, whichever is greater) ±1 digit max. Ambient temperature: -10°C to 23°C to 55°C, Voltage range: -15% to 10% of rated voltage K thermocouple at -100°C max.: ±10°C max. The unit is determined by the setting of the Integral/Derivative Time Unit parameter. External communications (RS-485) and USB-serial conversion cable communications can be used at the same time.
87
E5EC-T/E5AC-T Program Control Number of programs (patterns) Number of segments (steps) Segment setting method Segment times Alarm setting Reset operation Startup operation PID sets
Number of sets Setting method
Alarm SP function Program status control Wait operation
Time signals
Segment operation Program operation Wait method Wait width setting Number of outputs Number of ON/OFF Operations Setting method
Program status output PV start Program startup operation Operation end operation Program SP shift
88
Standby
8 32 Time setting (Segment set with set point and time.) Slope setting (Segment set with segment type, set point, slope, and time.) 0 h 0 min to 99 h 59 min 0 min 0 s to 99 min 59 s Set separately for each program. Select either stopping control or fixed SP operation. Select continuing, resetting, manual operation, or run mode. 8 Set separately for each program (automatic PID group selection also supported). Select from ramp SP and target SP. Advance, segment jump, hold, and wait Program repetitions and program links Waiting at segment ends Same wait width setting for all programs 2 1 each per output Set separately for each program. Program end output (pulse width can be set), run output, stage output Select from segment 1 set point, slope-priority PV start 0 h 0 min to 99 h 59 min 0 day 0 h to 99 day 23h Select from resetting, continuing control at final set point, and fixed SP control. Same program SP shift for all programs
E5EC-T/E5AC-T USB-Serial Conversion Cable Applicable OS
Windows XP, Vista, or 7
Applicable software
CX-Thermo version 4.61 or higher
Applicable models
E5@C-T Series, E5@C Series, and E5CB Series
USB interface standard
Conforms to USB Specification 2.0.
DTE speed
38400 bps
Connector specifications
Computer: USB (type A plug) Digital Temperature Controller: Special serial connector
Power supply
Bus power (Supplied from USB host controller.)*
Power supply voltage
5 VDC
Current consumption
450 mA max.
Output voltage
4.7±0.2 VDC (Supplied from USB-Serial Conversion Cable to the Digital Temperature Controller.)
Output current
250 mA max. (Supplied from USB-Serial Conversion Cable to the Digital Temperature Controller.)
Component Communications
When Digital Temperature Controllers are connected, set points and RUN/STOP commands can be sent from the Digital Temperature Controller that is set as the master to the Digital Temperature Controllers that are set as slaves. Slope and offsets can be set for the set point. Number of connected Digital Temperature Controllers: 32 max. (including master)
Copying*1
When Digital Temperature Controllers are connected, the parameters can be copied from the Digital Temperature Controller that is set as the master to the Digital Temperature Controllers that are set as slaves.
MELSEC is a registered trademark of Mitsubishi Electric Corporation. *1 Both the programless communications and the component communications support the copying.
Current Transformer (Order Separately) Ratings
Ambient operating temperature
0 to 55°C (with no condensation or icing)
Dielectric strength Vibration resistance
Ambient operating humidity
10% to 80%
Weight
Storage temperature
-20 to 60°C (with no condensation or icing)
Storage humidity
10% to 80%
Altitude
2,000 m max.
Weight
Approx. 120 g
Communications Specifications Transmission line connection method
RS-485: Multidrop
Communications
RS-485 (two-wire, half duplex)
Synchronization method
Start-stop synchronization
Protocol
CompoWay/F, or Modbus
Baud rate*
9600, 19200, 38400, or 57600 bps
Transmission code
ASCII
Data bit length*
7 or 8 bits
Stop bit length*
1 or 2 bits
Error detection
Vertical parity (none, even, odd) Block check character (BCC) with CompoWay/F or CRC-16 Modbus
Flow control
None
Interface
RS-485
Retry function
None
Communications buffer 217 bytes Communications response wait time
0 to 99 ms Default: 20 ms
* The baud rate, data bit length, stop bit length, and vertical parity can be individually set using the Communications Setting Level.
Communications Functions
Programless communications*1
You can use the memory in the PLC to read and write E5@C-T parameters, start and reset operation, etc. The E5@C-T automatically performs communications with PLCs. No communications programming is required. Number of connected Digital Temperature Controllers: 32 max. Applicable PLCs OMRON PLCs CS Series, CJ Series, or CP Series Mitsubishi Electric PLCs MELSEC Q Series, L Series
Heater Burnout Alarms and SSR Failure Alarms CT input (for heater current detection) Maximum heater current Input current indication accuracy Heater burnout alarm setting range *1 SSR failure alarm setting range *2
Models with detection for single-phase heaters: One input 50 A AC ±5% FS ±1 digit max. 0.1 to 49.9 A (in units of 0.1 A) Minimum detection ON time: 100 ms *3 0.1 to 49.9 A (in units of 0.1 A) Minimum detection OFF time: 100 ms *4
*1 For heater burnout alarms, the heater current will be measured when the control output is ON, and the output will turn ON if the heater current is lower than the set value (i.e., heater burnout detection current value). *2 For SSR failure alarms, the heater current will be measured when the control output is OFF, and the output will turn ON if the heater current is higher than the set value (i.e., SSR failure detection current value). *3 The value is 30 ms for a control period of 0.1 s or 0.2 s. *4 The value is 35 ms for a control period of 0.1 s or 0.2 s.
Electrical Life Expectancy Curve for Relays (Reference Values) Life (× 104 operations)
Windows is a registered trademark of Microsoft Corporation in the United States and or other countries. * Use a high-power port for the USB port. Note: A driver must be installed on the computer. Refer to the Instruction Manual included with the Cable for the installation procedure.
Accessories (E54-CT3 only)
1,000 VAC for 1 min 50 Hz, 98 m/s2 E54-CT1: Approx. 11.5 g, E54-CT3: Approx. 50 g Armatures (2) Plugs (2)
500 300 E5EC-T/E5AC-T 250 VAC, 30 VDC (resistive load) cosφ = 1
100 50 30
10 5 3
1 0
1
2
3
4
5
6
Switching current (A)
89
E5EC-T/E5AC-T External Connections E5EC-T/E5AC-T 4 E5EC T (1)
5M
(2) (3) (4) (5)
4
E5AC T (6)
(1)
5M
(2) (3) (4) (5)
Terminal type
(6)
Terminal type
Control output 1
Control output 2
Relay output 250 VAC, 5A (resistive load) Voltage output (for driving SSR) 12 VDC, 40 mA 21 mA if there are two control outputs Linear current output 0 to 20 mA DC 4 to 20 mA DC
Auxiliary outputs
Relay output 250 VAC, 5 A (resistive load) Voltage output (for driving SSR) 12 VDC, 21 mA Linear current output 0 to 20 mA DC 4 to 20 mA DC Load: 500 Ω max.
Load: 500 Ω max.
Relay output Models with 4 auxiliary outputs: 250 VAC, 2 A (resistive load)
(6) Options 005 008 004 Communications Four event inputs Communications, two and two event inputs event inputs, and one CT B(+) B(+) − 13 13 13 RS-485 RS-485 + 14 14 14 EV3 A(-) A(-) + 15 15 15 EV4 − − 16 16 16 − + + + 17 17 17 EV1 EV1 EV1 + + + 18 18 18 EV2 EV2 EV2 19 19 19 CT1 20 20 20 21 21 21
(1)Control Outputs RX
QX
Models with Models with 1 1 Relay Output Voltage Output (for Driving SSR) OUT1
3 4 5 6
R
OUT1 +Q −
3 4 5 6
CX
100 to 240 VAC
QR
QQ
Models with 1 Linear Current Output
RR/PR
OUT2
+Q −
OUT1
3 4 OUT2 5 R 6
R
2
1 2 3 4 5 6 7 8 9 10 11 12
+Q −
OUT2
R
CQ
Models with 2 Linear Current Outputs
1
2
(no polarity)
OUT1
3 4 5 6
CC
Models with 2 Relay Outputs
3 4 5 6
OUT1
+Q −
Models with 2 Output: Linear Current Output and Voltage (for Driving SSR)
OUT1
3 4 5 6
+ C −
OUT2 + C −
+ OUT1 - C + OUT2 - Q
25 26 27 28 29 30 31 32 33 34 35 36
13 14 15 16 17 18 19 20 21 22 23 24
(2) Auxiliary Outputs (5) Sensor (Temperature/Analog) Input
Auxiliary outputs 1 to 4 7 8 9 10 11 12
TC
Auxiliary output 4 Auxiliary output 3
22 23 + 24 −
Auxiliary output 2 Auxiliary output 1
Pt A B B
22 23 24
I + 22 mA 23 − 24
V − V +
22 23 24
− + EV3 + EV4 − + EV1 + EV2 CT1
13 14 15 16 17 18 19 20 21
24 VAC/DC
1
Models with Voltage Output (for Driving SSR) and Relay Output
Models with 2 Voltage Outputs (for Driving SSR)
OUT1 3 + C − 4 5 6
3 4 5 6
(3) Input Power Supply
010 Four event inputs and one CT
Potentiometer input 19 O 20 W 21 C
The E5@C-T is set for a K-type thermocouple (input type = 5) by default. An input error (s.err) will not occur if the input type setting does not agree with the temperature sensor. Check the input type.
019 Six event inputs, one CT, and transfer output − 13 + 14 + EV3 15 EV4 16 − 28 − + + 17 29 EV1 + EV5 30 + 18 EV2 EV6 19 31 + CT1 + Transfer V 20 32 I output 21 33 −
021 Six event inputs and transfer output − + EV3 + EV4 − 28 − + + 29 EV5 EV1 + 30 + EV6 EV2 + 31 Transfer V + 32 I output − 33
13 14 15 16 17 18 19 20 21
022 Communications, four event inputs, and transfer output B(+) 13 RS-485 14 A(-) 15 − 16 28 − + + 29 17 EV5 EV1 + 18 30 + EV6 EV2 19 + 31 + Transfer V 20 32 I output − 21 33
* The position-proportional control models (E5EC-TPR@@@M-@@@) will be released in May 2014.
Note: 1. The application of the terminals depends on the model. 2. Do not wire the terminals that are shown with a gray background. 3. When complying with EMC standards, the cable that connects the sensor must be 30 m or less. If the cable length exceeds 30 m, compliance with EMC standards will not be possible. 4. Connect M3 crimped terminals.
Isolation/Insulation Block Diagrams Models with 4 Auxiliary Outputs Sensor input, CT input, potentiometer input, and remote SP input Communications and event inputs Power Supply
Voltage output (for driving SSR), linear current output, and transfer output Relay output Auxiliary outputs 1, 2 Auxiliary outputs 3, 4 : Reinforced insulation : Functional isolation
Note: Auxiliary outputs 1 to 2 and 3 to 4 are not insulated.
90
E5EC-T/E5AC-T Nomenclature E5EC-T
Front panel
No. 1 display
Temperature unit
Top View of E5EC-T
PV or specified monitor/parameter Operation indicators No. 2 display
Top-panel Setup Tool port
SP or specified monitor/parameter value No. 3 display
Use S Key to change the digit (default setting).
Program No., segment No., remaining segment time, or MV (valve opening).
Use the U D Keys to set the parameter.
Front-panel Setup Tool port
Press U Key for at least 1 second when Process value/Set point parameter are displayed in Program SP Mode to go to Display Segment Selection parameter in Program Setting Level.
Press O Key once to go to Program Setting Level. Use the M Key to change to another parameter. Press O Key for at least 3 seconds to go to Initial Setting Level.
Press M and D Keys simultaneously for at least 1 second to switch between run and reset status.
E5AC-T Front Panel
Temperature unit Operation indicators
Top View of E5AC-T
No. 1 display PV or specified monitor/parameter No. 2 display SP or specified monitor/parameter value
Front-panel Setup Tool port
No. 3 display Program No. and segment No., remaining segment time, or MV (valve opening).
Press the O Key once to go to the Program Setting Level. Press the O Key for at least 3 seconds to go to the Initial Setting Level.
Press the M Key to switch to another parameter.
Press the U or D Key to set the parameter.
Top-panel Setup Tool port
Press U Key for at least 1 second when Process value/Set point parameter are displayed in Program SP Mode to go to Display Segment Selection parameter in Program Setting Level.
Press the S Key to change the digit (default setting).
Press M and D Keys simultaneously for at least 1 second to change between run and reset status.
91
E5EC-T/E5AC-T
Dimensions
(Unit: mm)
Controllers E5EC-T 48
(64) 60
4 1
44
96
The Setup Tool ports are on the front and top of the Digital Temperature Controller. It is used to connect the Temperature Controller to the computer to use the Setup Tool. The E58-CIFQ2 USB-Serial Conversion Cable is required to make the connection. 91 Refer to the instructions that are provided with the USB-Serial Conversion Cable for the connection procedure.
110
Note: Do not leave the USB-Serial Conversion Cable connected when you use the Temperature Controller. Waterproof Packing (Accessory) Mounting Adapter (Accessory)
Mounted Separately
Group Mounted *
(48 × number of units − 2.5)+1.0 0 45+0.6 0
*
Selections for Control Outputs 1 and 2: QQ, QR, RR, CC, PR, or CQ If you also specify 019, 021, 022 for the option selection and use group mounting, the ambient temperature must be 45°C or less. If the ambient temperature is 55°C, maintain the following mounting spaces between Controllers.
92+0.8 0
60 min. 45-0.6 0 Group mounting does not allow waterproofing.
120 min.
92+0.8 0 92-0.8 0
120 min.
• Recommended panel thickness is 1 to 8 mm. • Group mounting is not possible in the vertical direction. (Maintain the specified mounting space between Controllers.) • To mount the Controller so that it is waterproof, insert the waterproof packing onto the Controller. • When two or more Controllers are mounted, make sure that the surrounding temperature does not exceed the allowable operating temperature specified in the specifications.
92
E5EC-T/E5AC-T
E5AC-T
(64) 60 4 1
96 x 96
91 x 91
110
Waterproof Packing (Accessory)
Mounting Adapter (Accessory)
The Setup Tool ports are on the front and top of the Digital Temperature Controller. It is used to connect the Temperature Controller to the computer to use the Setup Tool. The E58-CIFQ2 USB-Serial Conversion Cable is required to make the connection. Refer to the instructions that are provided with the USB-Serial Conversion Cable for the connection procedure.
Note: Do not leave the USB-Serial Conversion Cable connected when you use the Temperature Controller. Group Mounted *
Mounted Separately
(96 × number of units − 3.5)+1.0 0 92+0.8 0
92+0.8 0
• Recommended panel thickness is 1 to 8 mm. • Group mounting is not possible in the vertical direction. (Maintain the specified mounting space between Controllers.) • To mount the Controller so that it is waterproof, insert the waterproof packing onto the Controller. • When two or more Controllers are mounted, make sure that the surrounding temperature does not exceed the allowable operating temperature specified in the specifications.
Group mounting does not allow waterproofing.
120 min.
92+0.8 0
Accessories (Order Separately) ● USB-Serial Conversion Cable E58-CIFQ2
(2110) 250
263
1510
LED (RD)
USB connector (type A plug)
Serial connector
LED (PWR) LED (SD)
● Conversion Cable E58-CIFQ2-E Conversion Cable
Connecting to the E58-CIFQ2 USB-Serial Conversion Cable (2110)
(1510)
250
263
E58-CIFQ2 (Order Separately)
1510
Conversion Cable
Note: Always use this product together with the E58-CIFQ2.
93
E5EC-T/E5AC-T ● Terminal Covers E53-COV24 (Three Covers provided.) 2
3.8
● Waterproof Packing Y92S-P9 (for DIN 48 × 96) The Waterproof Packing is provided with the Temperature Controller. Order the Waterproof Packing separately if it becomes lost or damaged. The degree of protection when the Waterproof Packing is used is IP66. Also, keep the Port Cover on the front-panel Setup Tool port of the E5EC-T/E5AC-T securely closed. To maintain an IP66 degree of protection, the Waterproof Packing and the Port Cover for the front-panel Setup Tool port must be periodically replaced because they may deteriorate, shrink, or harden depending on the operating environment. Y92S-P10 (for DIN 96 × 96) The replacement period will vary with the operating environment. Check the required period in the actual application. Use 3 years or sooner as a guideline. If a waterproof structure is not required, then the Waterproof Packing does not need to be installed.
10
91
● Setup Tool Port Cover for top panel Y92S-P7
Order this Port Cover separately if the Port Cover on the front-panel Setup Tool port is lost or damaged. The Waterproof Packing must be periodically replaced because it may deteriorate, shrink, or harden depending on the operating environment.
94
● Mounting Adapter Y92F-51 (Two Adapters provided.) One pair is provided with the Controller. Order this Adapter separately if it becomes lost or damaged.
E5EC-T/E5AC-T ● Watertight Cover Y92A-96N (96 × 96)
● Watertight Cover Y92A-49N (48 × 96) 21.9
21.9
(2)
(2)
131.7
131.7
67.6
115.6
29.4
29.4
● Current Transformers E54-CT1 21 15
Thru-current (Io) vs. Output Voltage (Eo) (Reference Values) E54-CT1
2.8 5.8 dia. 7.5
25
Maximum continuous heater current: 50 A (50/60 Hz) Number of windings: 400±2 Winding resistance: 18±2 Ω
3
Output voltage (Eo) V (r.m.s.)
10.5 40 Two, 3.5 dia. 10 30
100V
Frequency: 50 Hz ∞ 1kΩ
10
Distortion factor 10%
1
3% 1%
100mV 10
100Ω
1
RL=10Ω
E54-CT3 2.36 dia. 30 12 dia. 9
100μV 10 1
10
100mA
1
40 × 40
30
Connection Example Plug
Armature
Lead
18
Output voltage (Eo) V (r.m.s.)
Maximum continuous heater current: 120 A (50/60 Hz) (Maximum continuous heater current for an OMRON Digital Temperature Controller is 50 A.) Number of windings: 400±2 Winding resistance: 8±0.8 Ω
15
Approx. 3 dia.
100 1,000A
Thru-current (Io) vs. Output Voltage (Eo) (Reference Values) E54-CT3
Two, M3 (depth: 4)
E54-CT3 Accessories • Armature
10
Thru-current (Io) A (r.m.s.)
100V
Frequency: 50 Hz Distortion factor 10% 3% 1%
∞ 1kΩ 500Ω
10 1 100mV
100Ω 50Ω
10
RL=10Ω
• Plug
1
Approx. 6 dia.
100μV (22)
10 1
10
100mA
1
10
100 1,000A
Thru-current (Io) A (r.m.s.)
95
E5@C/E5@C-T
Operation Setting Levels Diagram E5C This diagram shows all of the setting levels. To move to the advanced function setting level and calibration level, you must enter passwords. Some parameters are not displayed depending on the protect level setting and the conditions of use. Control stops when you move from the operation level to the initial setting level. Press the O + M Keys for at least 1 s
Operation in progress
Only when Manual Mode was used just before power OFF
Power ON Press the O Key for at least 1 s or the S Key for at least 1 s*1
Press the O + M Keys for at least 3 s.*2
Level changes automatically.
Manual Control Level Used to set the MV manually.
Operation Level O Key for at least 3 s while a-m is displayed.*2
Press the O Key once.
Press the S Key.*3
Press the S Key.*3
S Key for at least 1 s*1
Press the O Key for at least 1 s.
Monitor/Setting Item Level Used to display specified monitor and setting items.
Initial Setting Level
Press the O Key for less than 1 s. (models with communications only).
Used to set the input type and other basic settings.
Stopped
Adjustment Level Used to change adjustment parameters (PID constants, adjustment sensitivity, etc.).
Used for SP, alarm values, and other basic settings and monitoring.
Press the O Key for at least 3 s*2
Release protection and then enter the password (−169) for the amoV (Move to Advanced Setting Level) Advanced parameter.
Press the O Key for at least 1 s.
Function Setting Level
Used to set application functions. Enter the password (1201) while cmov (Move to Calibration Level parameter) is displayed.
Calibration Level *1 Set the PF Setting parameter to a-m (Auto/Manual). *2 The No. 1 display will flash when the keys are pressed for 1 s or longer. *3 Set the PF Setting parameter to pfdp (monitor/setting items).
96
Protect Level Used to set protection for operations.
Communications Setting Level Used to set up communications.
E5@C/E5@C-T E5C-T This diagram shows all of the setting levels. To move to the advanced function setting level and calibration level, you must enter passwords. Some parameters are not displayed depending on the protect level setting and the conditions of use. Press O and M Keys for at least 1 s.
Protect Level Used to set protection for operations.
Starting in manual mode
Power ON Press O and M Keys for at least 3 s.*2
Operation in progress
Level changes automatically.
Manual Control Level
Press O or S Key for at least 1 s.*1
Press S Key.*3
Operation Level
Used to set the MV manually. Press O Key for at least 3 s while a-m is displayed.*2
Press O Key for less than 1 s.
Used for SPs and other basic settings and monitoring.
Press S Key for at least 1 s.*1
Program Setting Level Parameter and segment settings for all programs Press O Key for less than 1 s.
Press O Key for at least 1 s.
Press O Key for less than 1 s. Press O Key for less than 1 s.
PID Setting Level
Parameters for all PID sets (e.g., PID constants)
Adjustment Level Adjustment parameters (e.g., PID constants for current PID set) Press S Key.*3
Press O Key for at least 3 s.*2
Monitor/Setting Item Level Used to display specified monitor and setting items.
Control stops.
Initial Setting Level
Press O Key for less than 1 s (only models with communications).
Stopped
Used to set the input type and other basic settings.
Release protection and then enter the password (−169) for the amoV (Move to Advanced Function Setting Level) parameter.
Communications Setting Level Communications settings
Press O Key for at least 1 s.
Advanced Function Setting Level Advanced settings
Enter the password (1201) while cmov (Move to Calibration Level parameter) is displayed.
Calibration Level *1 Set the PF Setting parameter to a-m (Auto/Manual). *2 The No. 1 display will flash when the keys are pressed for 1 s or longer. *3 Set the PF Setting parameter to pfdp (monitor/setting items).
97
E5@C/E5@C-T Operation Parameters E5@C The following pages describe the parameters set in each level. Pressing the M (Mode) Key at the last parameter in each level returns to the top parameter in that level. Some parameters may not be displayed depending on the model and other settings. Press the S Key*2 Power ON Starting in Manual Mode.
Manual Control Level Press the S Key for at least 1 s. *1
C
Press the O Key or the S Key for at least 1 s. *1
PID Control only
25 0
PV/MV
Adjustment Level l.adj
Adjustment Level Display Displayed only once when entering adjustment level.
at
AT Execute/Cancel
off
cmwt off
Communications Writing
spmd
SP Mode
lsp
ins 0.0
Process Value Input Shift
ct1 0.0
Heater Current 1 Value Monitor
Heater Burnout Detection 1
Heater Current 2 Value Monitor
0.0
Heater Burnout Detection 2
lcr1 0.0
Leakage Current 1 Monitor
p
HS Alarm 1
i
d
Leakage Current 2 Monitor
HS Alarm 2
50.0
SP 0
chys
Manual Reset Value
Hysteresis (Heating)
0
soak
Hysteresis (Cooling)
0
wt-b
SP 4
w3of
mv-e sprt sprl
SP Ramp Fall Value
MV Upper Limit
0.0
M
Work Bit 4 ON Delay
Work Bit 4 OFF Delay
Work Bit 5 ON Delay
al-3
lcr1
Heater Current 1 Value Monitor
M
r-s
0
M Leakage Current 1 Monitor
al-4
Leakage Current 2 Monitor
al4h
Program Start
al4l
0
o
0.0
RUN/STOP
c-o 0.0
M
Alarm Value 1
v-m
0.0
M
M
off
M
M off
Communications Monitor
chgp Changed Parameters Only off
M
pmsk
Parameter Mask Enable
on
prlp 0
M
Displayed only for models with communications. Changes are effective after cycling power or after a software reset.
Password to Move to Protect Level
Alarm 2 Hysteresis
M * Used with programless communications
up 1 Protocol Setting: Switches between cwf CompoWay/F and Modbus.
psel
M M
Communications Unit No.
7
Communications Baud Rate
M *3
area adrh
Communications Data Length
adrl 0
rwat 1000
M
prty
unit
M
M
Communications even Parity Send Data Wait 20 Time
M
0
M
up13 0
M 31
First Address Upper Word
M
dn13 75
First Address Lower Word
off
Receive Data Wait Time
*3
sps 1.000
Communications Node Number
Upload Setting 1
Upload Setting 13
Download Setting 1
Download Setting 13
M
copy
M Communications Stop Bits
1
dn 1
M 0
M
sdwt
Area
M
M 2
Highest Communications 0 Unit No.
maxu
0
M
sbit
M
0.2
Communications Setting Level
len
pfpt PF Key Protect
Alarm 2 Type
M alh2
Press the O Key less than 1 s.
9.6
wtpt Setting Change Protect
Alarm 1
0.2 Hysteresis
M alt2 2
bps
M
2
M alh1
Valve Opening Monitor
1
Initial Setting/Communications
1
M alt1 Alarm 1 Type
MV Monitor (Cooling)
u-no
0
icpt Protect
or-r
MV Monitor (Heating)
Press the O and M Keys for at least 1 s.
M
Control Period (Cooling)
M orev Direct/Reverse Operation
M
Move to Protect Level: Displayed only when a password is set.
Control Period (Heating)
20
Alarm Value Lower Limit
M
Operation/Adjustment Protect Work Bit 7 OFF Delay
20
M c-cp
M
oapt
M
Alarm Value Upper Limit
0 4
Protect Level
0
off
M cp
0 4
The time taken to move to the protect level can be adjusted by changing the "Move to protect level time" setting.
pmov Work Bit 7 ON Delay
Alarm Value 4
M
Press the O and M Keys for at least 3 s.
Work Bit 6 OFF Delay
on
M ptrn Program Pattern
M
Soak Time Remain
Standard or Heating/Cooling
M st ST (Self-tuning)
Alarm Value Lower Limit 0 3
M
Work Bit 6 ON Delay
stnd
M
M
al-1
M s-hc
al3l
M
sktr
onof
Alarm Value Upper Limit 0 3
M
prst
M cntl PID ON/OFF
Alarm Value 3
al3h
Heater Current 2 Value Monitor
M
98
0
SP Lower Limit
-200
M
M
lcr2
M sl-l
M
M
Work Bit 5 OFF Delay
M
M
Set Point During SP Ramp
run
M
0
MV Lower Limit
M
ct2
1300
Alarm Value Lower Limit 0 2
al2l
0
M
plcm
M
ct1
M sl-h SP Upper Limit
M Remote SP Monitor
Temperature Unit
c
Alarm Value Upper Limit 0 2
rset
w8of
100.0
ol-l
Work Bit 3 OFF Delay
Work Bit 8 0 OFF Delay
M
M
Alarm Value 2
al2h
M
sp-m
0
M d-u
M
Multi-SP
0.0
0.0
Work Bit 8 0 ON Delay
same
ol-h
Work Bit 3 ON Delay
w8on
M SP 7
al-2
0
0.0
M
0
Auto/Manual Switch
M
rsp
Alarm Value Lower Limit
M
M
m-sp
M
w7of SP Ramp Set Value
off
M
Press the O Key for at least 3 s.
M Decimal Point dp
0 1
0
M
w5on
0
0.0
SP 6
a-m
M
w4of
al1l
0.0
Work Bit 2 OFF Delay
M
w4on
w7on MV at PV Error
M
0
M
MV at Stop
M SP 5
0
0
0
w6of
0.0
M
sp-7
mv-s
Work Bit 2 ON Delay
M
0
M
sp-6
w3on
0
Wait Band
off
0
sp-5
0
w6on
M
sp-4
w2of
Process Value/ Set Point 2
Scaling Lower Limit
0
M
0.0
M
0
Soak Time
M SP 3
w2on
al1h
M
0
M
w5of
1
M
M
0
M SP 2
M Bit 1 w1on Work ON Delay
0
1.0
M
M Extraction of Root sqrp Square Low-cut Point
0
M SP 1
0
sp-3
Dead Band
M
hys
0
Dead Band
M oc-h Open/Close Hysteresis
0
1.0
M
sp-2
Derivative Time (Cooling)
M
0
2.0
M
Integral Time 233 (Cooling)
of-r
25
M in-l
Alarm Value Upper Limit 0 1
M
M db Position Proportional
0
50.0
M
sp-1
Derivative Time
0.0
M
MV Change Rate Limit
Work Bit 1 0 OFF Delay
c-i
c-db
0.0
Value/ 25 Process 0 Set Point 1
w1of
Proportional Band 8.0 (Cooling)
M
sp-0
Integral Time
c-p
c-d
orl
0
40
M
hs2
Proportional Band
233
40
0.0
M in-h Scaling Upper Limit 100
0.0
8.0
50.0
lcr2
Remote SP Input Slope Coefficient
M
M
hs1
rsrt
M
M
5
0.8
M
M
hb2
0.0
M
M 0.0
rss
Remote SP Input Shift
M
0.0
ct2
Process Value Slope 1.000 Coefficient
M
M
hb1
inrt
1.000
M
in-t Input Type
Press the O Key less than 1 s.
M
M
Press the O Key for less than 1 s.
Operation Level
M
M
Initial Setting Level Press the O Key for at least 1 s.
Press the O Key less than 1 s.
M
M
Press the O Key for at least 3 s. Press the S Key*2 Other than the Auto/Manual Switch display
Starting in Automatic Mode.
M
spos 0.0
Copy
*3 SP Slope
*3 SP Offset
*3
M
*1. When the PF Setting parameter is set to A-M. *2. When the PF Setting parameter is set to PFDP. *3. Used with component communications.
E5@C/E5@C-T
Monitor/Setting Item Level 25 0
Monitor/Setting Item Display 1
S
Monitor/Setting Item Display 2
S
Monitor/Setting Item Display 3
Monitor/Setting Item Display 4
S
S
Monitor/Setting Item Display 5
Note: The monitor/setting items to be displayed is set in the Monitor/Setting Item 1 to 5 parameters (advanced function setting level).
Press the O Key for at least 1 s.
Advanced Function Setting Level alt3
Alarm 3 Type
2
M alh3 0.2
Alarm 3 Hysteresis
M alt4 Alarm 4 Type 2
M
alh4
Alarm 4
0.2 Hysteresis
M o1st
Control Output 1 Signal
4-20
M
o2st
Control Output 2 Signal
4-20
M trst Transfer Output Signal 4-20
M
tr-t
Transfer Output Type
off
M
tr-h 100.0
Transfer Output Upper Limit
init
Parameter Initialization
ret
M mspu Number of Multi-SP
M brgt
M spru SP Ramp Time Unit
M a1lt
M Sequence rest Standby Reset
M a2lt
M sb1n Auxiliary Output 1
M a3lt
M sb2n Auxiliary Output 2
M a4lt
M Output 3 sb3n Auxiliary Open in Alarm
M prlt
off Points
m
a
n-o Open in Alarm
n-o Open in Alarm
n-o
M sb4n
Auxiliary Output 4 Open in Alarm
n-o
M a3on
M st-b ST Stable Range
M a4on
M alfa
M a1of
0.0
M ev-1 msp0
M ev-2 stop
Event Input Assignment 1
Event Input Assignment 2
M Input ev-3 Event Assignment 3 none
M ev-4
Event Input Assignment 4
none
M Input ev-5 Event Assignment 5 none
M ev-6 none
M clfl
Event Input Assignment 6
Close/Floating
Motor Calibration
Travel Time
30
M of Square sqr Extraction Root Enable off
M Move to Advanced Function Level: amov Setting Displayed when initial 0
α
0.65
0.8
M lcma Limit Cycle MV 20.0 Amplitude
setting/communications
M protect is set to 0.
Alarm 4 ON Delay
Alarm 1 OFF Delay
Alarm 2 OFF Delay
M mav Moving Average Count
M mant
Control Output 1 Assignment
M Output 2 out2 Control Assignment
sub1
Minimum Output ON/OFF Band
1.0
M pf
PF Setting
shft
M pfd1
Monitor/Setting Item 1
1
pfd2
Monitor/Setting Item 2
0
M Auxiliary Output 2 sub2 Assignment
M pfd3 Monitor/Setting Item 3
M Output 3 sub3 Auxiliary Assignment
M pfd4 Monitor/Setting Item 4
M Output 4 sub4 Auxiliary Assignment
M pfd5 Monitor/Setting Item 5
M alma Integrated Alarm
M No. 1 Display spd1 PV/SP Selection
M t-u Soak Time Unit
M PV/SP No. 2 Display spd2 Selection
m
Alarm 4 OFF Delay
Heating/Cooling Tuning Method
off
M Auxiliary Output 1 Assignment
M alsp
Alarm SP Selection
sp-m
0
0
0
4
0
M MV Display Selection odsl o
M Remote SP Input
M PV Decimal Point pvdp Display
MV at Stop and Error Addition
rs-t
Auto/Manual Select Addition
M rspu Remote SP Enable
M PV Status Display pvst Function
M SP rsph Remote Upper Limit
M Status Display svst SV Function
M SP rspl Remote Lower Limit
M Display Refresh d.ref Period
Manual Output Method
hold
M mani M 0.0 M
o
PV Rate of Change Calculation Period
20
M ompw
out1
Direct Setting of Position Proportional MV
off
M lbab LBA Band 3.0
Manual MV Limit Enable
off
M hctm
49 Assignment
Alarm 3 OFF Delay
0
M lbal LBA Level
alm4 (E5EC/E5AC only)
M off
M pvrp
alm3
M
amad
M lba LBA Detection Time
alm2
0
M inf Input Digital Filter
M MV Display o-dp off M M
Alarm 3 ON Delay
0
off
M pmvd
alm1
0
mvse
M hsh HS Alarm Hysteresis
M Alarm 2 ON Delay
0
M a4of
M manl
none
0
M at-h AT Hysteresis
0.8
Alarm 1 ON Delay
0
M a3of
M hsl HS Alarm Latch
M
0
M at-g AT Calculated Gain
1 Time Unit
Move to Protect Level Time
M
M a2of
M p-db PV Dead Band
8.0
0
M tidu Integral/Derivative
off
off
M mot
15.0
0.0
flot
M calb
0.1
Alarm 4 Latch
Cold Junction Compensation on Method
M Burnout hbh Heater Hysteresis
M hsu HS Alarm Use
0
M
M Transfer o1tl Simple Ouptut 1 Lower Limit
off
Alarm 3 Latch
SP Tracking
sptr off
0.1
cjc
a2on
100.0
Alarm 2 Latch
off
M hbl Heater Burnout Latch
RT
off
off
off
M Transfer o1th Simple Output 1 Upper Limit
on
Alarm 1 Latch
off
3
rt
on
off
M a1on
0.0
Display Brightness
3
M hbu HB ON/OFF
M Output tr-l Transfer Lower Limit
Automatic Display
off Return Time
off
4-20
off
1300
Manual MV Initial Value
-200
M
on
off
off
0.25
M Cooling Output lcmt LCT Minimum ON Time 0.2
M to Calibration cmov Move Level 0
M
Move by setting password (−169).
99
E5@C/E5@C-T
E5@C-T Some parameters may not be displayed depending on the model and other settings. Starting in manual mode
Monitor/Setting Item Level
25
PF Monitor/
Power ON
Manual Control Level
25 Setting Item 0
S
PF Monitor/Setting Item display 2 to 5
display 1
* The monitor/setting items to display are set in the Monitor/Setting Item 1 to 5 parameters (Advanced Function Setting Level).
PV/Manual MV
50.0
Press S Key.*2
Press S Key.*2
Press O or S Key for at least 1 s.*1
Press O Key for at least 3 s while a-m is displayed. Press S Key for at least 1 s.*1
Program Setting Level U
Operation Level d.prg
01
25 0
prgt
Process Value/Set Point 1
0.00
M
Elapsed Program Time Monitor
M
25 0
rptm
Process Value/Set Point 2
0.00
ct1
Auto/Manual Switch
0.0
lcr1 r-r rst
Hold
o
0.0
M Segment Number
c-o
0
0.0
Remaining Standby Time Monitor
v-m 0.0
d.pid
U
M
1.i
233
PID 1 Integral Time
40
1.c-p 8.0
233
40
M
100
al1l
PID 1 Integral Time (Cooling)
Press O Key for less than 1 s.
0.0
PID 1 Dead Band
1.ofr 1.olh
Alarm Lower Limit 1 to 4
1.oll 0.0
1.aut
1320
1.lba 0
M
Adjustment Level Display Displayed only once when entering Adjustment Level.
AT Execute/Cancel
M
cmwt
67
D
M
styp
Segment n Format
on1 0.00
sp
Segment n SP
0
pr
Segment n Slope
0
Time Signal 1 to 2 ON Time
M
of1
M
M Time Signal 1 to 2 Set Segment
Time Signal 1 to 2 OFF Time
M
time
Segment n Time
0.00 M
Press O Key for less than 1 s.
lcr1 0.0
Leakage Current 1 to 2 Value Monitor
1.000
M
wt-b
Wait Band
0
M
c-p
Proportional Band (Cooling)
8.0
c-i
Integral Time (Cooling)
233 M
Standby Time
c-d
Derivative Time (Cooling)
40
0.00
psps
Derivative Time
M
M
M Heater Burnout Detection 1 to 2
d
M PV Input Slope Coefficient
M
stb
Integral Time
40
off
Heater Current 1 to 2 Value Monitor
i
M PV Input Shift
M Fixed SP
M
0.0
inrt
Proportional Band
233
M SP Mode
M
hb1
ins
p
8.0 M
HS Alarm 1 to 2
0.0
M
fsp
hs1 M
Communications Writing
M
spmd
0.0
PID 1 LBA Detection Time
0
50.0
off
ct1 PID 1 Automatic Selection Range Upper Limit
ts1s
M
at
0
PID 1 MV Lower Limit
Program Link Destination
end
M
psp
PID 1 MV Upper Limit
link M
Alarm Upper Limit 1 to 4
45
ramp
Adjustment Level
off
PID 1 Manual Reset Value
0
3 12
M
M
1.cdb
Program Repetitions
0.00
1234
M PID 1 Derivative Time (Cooling)
Alarm Value 1 to 4
M
Valve Opening Monitor
rpt M
M
0
M
M
1.c-d
al1h
MV Monitor (Cooling)
M
M
1.c-i
0
l.adj
100.0
PID 1 Proportional Band (Cooling)
PID Set No.
M
0
M
M
For 0 to 7
al-1
Display PID Selection
s0.0
PID 1 Derivative Time
M
M
MV Monitor (Heating)
0
D
1
Run/Reset (of the program)
M
M
1.d
For end
pid
M PID 1 Proportional Band
d.seg
end
Leakage Current 1 to 2 Value Monitor
Press O Key for less than 1 s.
1 2 3 4 5 6 7 8 D
8.0
U
M
PID Setting Level
Press the U Key for at least 1 s in Program SP Mode.
Display Segment Selection END or 0 to Number of segments used − 1
d.seg
M
M
1.p
Number of Segments Used
Process Value/Set Point 1 or Process Value/Set Point 2 in Operation Level
U Heater Current 1 to 2 Value Monitor
M
M
0.00
8
M
off
stbm
0
M
M Program Number
0
seg
s-no
0.0
M
hold
25
D
M
M Program No. Monitor/ Segment No. Monitor
M
prg
Display Program Selection
M
M
pgsg
7
0
M
a-m
Program Execution Repetitions Monitor
Press O Key for less than 1 s.
23
6 45
Program SP Shift Value
c-db 0.0
M
Dead Band
E5@C/E5@C-T
Press O Key for at least 1 s.
Protect Level Press O + M Key for at least 3 s.
M
pmov
oapt 0
0
Operation/Adjustment Protect
pfpt
Initial Setting/ Communications Protect
pmsk
Setting Change Protect
prlp
M
Move to Protect Level
icpt
Press O + M Key for at least 3 s. (The key pressing time can be changed in the Move to Protect Level Time parameter (Advanced Function Setting Level).)
1
M
M
0
off
Press O + M Key for at least 1 s.
Parameter Mask Enable
on
M
wtpt
PF Key Protect
off
M
Password to Move to Protect Level
M
Initial Setting Level Press O Key for at least 3 s.
in-t
Input Type
Press O Key for at least 1 s.
eset
SP Lower Limit
rst
M
M
in-h
Scaling Upper Limit
t-u
Scaling Lower Limit
0
t-pr time
M Decimal Point
0
pru m
M
tspu 0
c
Temperature Unit
rtsm
SP Upper Limit
p-on
cntl
Reset Operation
s-hc
1300 M
2
alh1 0.2
Standard or Heating/Cooling
stnd
stop
o1st
4-20
M
cp
Startup Operation
cont
20
M
M
trst
4-20
tr-l 0.0
ev-1
rr-1
mot
Transfer Output Lower Limit
vl-c
Event Input Assignment 1
vl-o
ev-2
Event Input Assignment 2
pms
adv
M
ev-3
Event Input Assignment 3 to 6
sqr
none
0
Valve Completely Closed Position
M Valve Completely Open Position
9999 M
Potentiometer Specification Setting
0
M Extraction of Square Root Enable
off M
M
clfl
Travel Time
30
M
M Transfer Output Signal
Motor Calibration
off M
M Control output 1 to 2 Signal
M Control Period (Heating)
Transfer Output Upper Limit
M Alarm 1 to 4 Hysteresis
M
M
calb
M Alarm 1 to 4 Type
M PID ON/OFF
tr-h 100.0
M
alt1
Transfer Output Type
M Direct/Reverse Operation
or-r
All PID AT Upper Limit SP
tr-t
off
M
pid
M
M
sl-h
orev
M Time Unit of Ramp Rate
M
d-u
PV Start
Control Period (Cooling)
20
M Step Time/Rate of Rise Programming
M
dp
c-cp
sp
M
M
in-l
Operation End Operation
M
pvst
Program Time Unit
h-m
100
Press O Key for at least 3 s.
sl-l -200
5
Close/Floating
flot
amov 0
Moves to Advanced Function Setting Level
Enter password (−169) to move.
M
M
Press O Key for less than 1 s.
Communications Setting Level
psel
Protocol Setting
Manual Reset Value
M
hys
Hysteresis (Heating)
Hysteresis (Cooling)
MV at Reset
M
0.0
sqrp
Communications Baud Rate
area
len 7
Extraction of Square Root Low-cut Point
sbit 2
Work Bit 1 to 8 ON Delay
w1of
Work Bit 1 to 8 OFF Delay
prty even M
0
Area
dn 1
Communications Parity
rwat
Download Setting 1 to 43
0
First Address Upper Word
M
copy
Copy
M off
M
adrl
Upload Setting 1 to 23
0
M
0
Communications Stop Bits
Communications Node Number
M
0
adrh
0
up 1
M Communications Data Length
unit
Highest Communications Unit No.
M
First Address Lower Word
M
0
M
M
w1on
0
100.0
M
Open/Close Hysteresis
M MV Upper Limit
maxu
M
0
M
bps 9.6
M MV at PV Error
0.0
ol-l
oc-h
0.0
M
ol-h
Position Proportional Dead Band
M
0.0
Communications Unit No.
M
0.8
M
mv-e
1
M
1.0
u-no M
db 2.0
M
mv-r
MV Change Rate Limit
M
1.0
chys
orl 0.0
50.0
Send Data Wait Time
M
M
of-r
sdwt 20
cwf
Receive Data Wait Time
1000 M
Models with communications only: Changes to settings are applied when the power is cycled or a software reset is performed.
M MV Lower Limit
plcm 0
M
Communications Monitor
*1 When PF Setting = A-M. *2 When PF Setting = PFDP.
101
E5@C/E5@C-T
Advanced Function Setting Level
init off
Parameter Initialization
mant
Program End ON Time
mani
Standby Time Unit
Standby Sequence Reset
n-o
Auxiliary Output 1 to 4 Open in Alarm
hsh
Heater Burnout Latch
lba
Heater Burnout Hysteresis
0.1
8.0
M
M
alfa
α
Integral/Derivative Time Unit
o
1
AT Calculated Gain
none
0.8
M
at-h
alm1
M
alm2
M
0.0
off
off
Moving Average Count
Automatic Display Return Time
Display Brightness
Move to Protect Level Time
Cold Junction Compensation Method
Alarm 1 to 4 ON Delay
0
pidh 0.50
p-db
Alarm 1 to 4 OFF Delay
Auxiliary Output 4 Assignment
off M
burn up
Burnout Method
pmst
Parameter Mask Setting
off M
Integrated Alarm Assignment
cmov 0
M Alarm SP Selection
SP Tracking
PID Set Automatic Selection Data
PID Set Automatic Selection Hysteresis
PV Dead Band
0
manl
Display Refresh Period
0.25
M
M
M
0
pv
d.ref M
Auxiliary Output 3 Assignment
M
M
M
pidi
SV Status Display Function
off M
Auxiliary Output 2 Assignment
M
M
a1of
sptr
PV Status Display Function
off M
M
3
a1on
svst
off
M
on
Auxiliary Output 1 Assignment
M Alarm 1 to 4 Latch
PV/SP No. 2 Display Selection
M
sp-m
off
cjc
alsp
PV/SP No. 1 Display Selection
7
pvst
M
3
prlt
49
spd2
Control Output 2 Assignment
alm4
alma
spd1 M
Control Output 1 Assignment
M
M
a1lt
sub4
PF Monitor/ Setting Item 2 to 5
6
M
M
brgt
sub3 alm3
M
ret
LBA Band
M Input Digital Filter
M
mav
sub2
pfd2 0
M Limit Cycle MV Amplitude
20.0
inf
sub1
PF Monitor/Setting Item 1
M
M AT Hysteresis
0.8
lcma
out2
pfd1 M
LBA Level
M
M
at-g
out1
PF Setting
1
M
M
tidu
lbab
pf M
LBA Detection Time
3.0
0.65
102
lbal
LCT Cooling Output Min. ON Time
shft
0.1
M
M
Minimum Output ON/OFF Band
M HS Alarm Hysteresis
0
off
lcmt 0.2
M
M
hbh
HS Alarm Latch
off
HB ON/OFF
on
hbl
1.0
M
M
hbu
hsl
ompw M
M
M
Heating/Cooling Tuning Method
M HS Alarm Use
on
a
sb1n
hsu
hctm 0
M
M
PV Rate of Change Calculation Period
M RT
off
h-m
rest
rt
pvrp 20
M
M
s-u
Direct Setting of Position Proportional MV
M Manual MV Initial Value
0.0
0.0
pmvd off
M
M
pend
Manual Output Method
hold
Manual MV Limit Enable
Move to Calibration Level
E5@C/E5@C-T
Error Displays (Troubleshooting) When an error occurs, the No. 1 display or No. 2 display shows the error code. Take necessary measure according to the error code, referring the following table. Display
Name
Meaning The input value exceeded the control range.* The input type is not set correctly. The sensor is disconnected or shortcircuited. The sensor is not wired correctly. The sensor is not wired.
s.err
Input error
[[[[ Display range exceeded
]]]]
* Control Range Temperature resistance thermometer or thermocouple input: SP Lower Limit - 20°C to SP Upper Limit + 20°C (SP Lower Limit - 40°F to SP Upper Limit + 40°F) ESIB input: Same as specified input range. Analog input: Scaling range -5% to 105% This is not an error. It is displayed when the Below -1,999 control range is wider than the display range and the PV exceeds the display range. The PV is displayed for the range that is given on Above 9,999 the left (the number without the decimal point).
e333
A/D converter error
There is an error in the internal circuits.
e111
Memory error
There is an error in the internal memory operation.
Action
Operation After the error occurs and it is Check the wiring for input to be sure displayed, the alarm output will it is wired correctly, not broken, and operate as if the upper limit was not shorted. Also check the input exceeded. type. It will also operate as if transfer If there are no problems in the wiring output exceeded the upper limit. or input type settings, cycle the If an input error is assigned to a power supply. control output or auxiliary output, the If the display remains the same, output will turn ON when the input replace the Digital Temperature error occurs. Controller. The error message will appear in the If the display is restored to normal, display for the PV. then the probable cause is external noise affecting the control system. Note: 1. The heating and cooling Check for external noise. control outputs will turn OFF. Note: For a temperature resistance 2. When the manual MV, MV thermometer, the input is at stop, MV at reset, or MV considered disconnected if at error is set, the control the A, B, or B’ line is broken. output is determined by the set value.
-
After checking the input error, turn the power OFF then back ON again. If the display remains the same, the controller must be repaired. If the display is restored to normal, then a probable cause can be external noise affecting the control system. Check for external noise. First, cycle the power supply. If the display remains the same, the controller must be repaired. If the display is restored to normal, then a probable cause can be external noise affecting the control system. Check for external noise.
ffff
Overcurrent
This error is displayed when the peak current exceeds 55.0 A.
-
ct1 ct2 lcr1 lcr2
HB or HS alarm
If there is a HB or HS alarm, the No. 1 display will flash in the relevant setting level.
-
----
"----" will be displayed for the Valve Opening Monitor parameter if any of the following error occurs. • Motor calibration has not been Potentiometer performed. Input Error • The wiring of the potentiometer is (Positionincorrect or broken. proportional Models Only) • The potentiometer input value is incorrect (e.g., the input is out of range or the potentiometer has failed).
Check for the above errors.
Control continues and operation is normal. The value will appear in the display for the PV. Refer to the E5@C Digital Temperature Controllers User’s Manual (Cat. No. H174) or the E5@C-T Digital Temperature Controllers Programmable Type User’s Manual (Cat. No. H185) for information on the controllable range. The control outputs, auxiliary outputs, and transfer outputs turn OFF. (A current output will be approx. 0 mA and a linear voltage output will be approx. 0V.)
The control outputs, auxiliary outputs, and transfer outputs turn OFF. (A current output will be approx. 0 mA and a linear voltage output will be approx. 0V.) Control continues and operation is normal. The error message will appear for the following displays. Heater Current Value 1 Monitor Heater Current Value 2 Monitor Leakage Current Value 1 Monitor Leakage Current Value 2 Monitor The No. 1 display for the following parameter flashes in Operation Level or Adjustment Level. Heater Current Value 1 Monitor Heater Current Value 2 Monitor Leakage Current Value 1 Monitor Leakage Current Value 2 Monitor However, control continues and operation is normal.
Close control: The control output is OFF or the value that is set for the MV at PV Error parameter is output. Floating control: Operation will be normal.
103
E5@C/E5@C-T
Safety Precautions ● Be sure to read the precautions for all E5@C/E5@C-T models in the website at: http://www.ia.omron.com/. Warning Indications CAUTION
Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury or in property damage.
Precautions for Safe Use
Supplementary comments on what to do or avoid doing, to use the product safely.
Precautions for Correct Use
Supplementary comments on what to do or avoid doing, to prevent failure to operate, malfunction or undesirable effect on product performance.
Meaning of Product Safety Symbols Used to warn of the risk of electric shock under specific conditions.
Used for general prohibitions for which there is no specific symbol. Used to indicate prohibition when there is a risk of minor injury from electrical shock or other source if the product is disassembled. Used for general CAUTION, WARNING, or DANGER precautions for which there is no specified symbol. (This symbol is also used as the alerting symbol, but shall not be used in this meaning on the product.) Used for general mandatory action precautions for which there is no specified symbol.
CAUTION Do not touch the terminals while power is being supplied. Doing so may occasionally result in minor injury due to electric shock. Electric shock may occur. Do not touch any cables or connectors with wet hands.
Electric shock, fire, or malfunction may occasionally occur. Do not allow metal objects, conductors, cuttings from installation work, or moisture to enter the Digital Temperature Controller or the Setup Tool port or ports. Attach the cover to the front-panel Setup Tool port whenever you are not using it to prevent foreign objects from entering the port. Do not use the Digital Temperature Controller where subject to flammable or explosive gas. Otherwise, minor injury from explosion may occasionally occur. Not doing so may occasionally result in fire. Do not allow dirt or other foreign objects to enter the Setup Tool port or ports, or between the pins on the connectors on the Setup Tool cable.
104
Minor electric shock or fire may occasionally occur. Do not use any cables that are damaged.
Never disassemble, modify, or repair the product or touch any of the internal parts. Minor electric shock, fire, or malfunction may occasionally occur. CAUTION - Risk of Fire and Electric Shock a. This product is UL listed*1 as Open Type Process Control Equipment. It must be mounted in an enclosure that does not allow fire to escape externally. b. More than one disconnect switch may be required to deenergize the equipment before servicing the product. c. Signal inputs are SELV, limited energy. *2 d. Caution: To reduce the risk of fire or electric shock, do not interconnect the outputs of different Class 2 circuits. *3 If the output relays are used past their life expectancy, contact fusing or burning may occasionally occur. Always consider the application conditions and use the output relays within their rated load and electrical life expectancy. The life expectancy of output relays varies considerably with the output load and switching conditions. Even if you replace only the Main Unit of the E5DC, check the condition of the Terminal Unit. If corroded terminals are used, contact failure in the terminals may cause the temperature inside the Digital Temperature Controller to increase, possibly resulting in fire. If the terminals are corroded, replace the Terminal Unit as well. Tighten the terminal screws to the rated torque of between 0.43 and 0.58 N•m. *4 Loose screws may occasionally result in fire. Set the parameters of the product so that they are suitable for the system being controlled. If they are not suitable, unexpected operation may occasionally result in property damage or accidents. A malfunction in the product may occasionally make control operations impossible or prevent alarm outputs, resulting in property damage. To maintain safety in the event of malfunction of the product, take appropriate safety measures, such as installing a monitoring device on a separate line. *1. E5CC, E5EC, E5AC, and E5DC Digital Temperature Controllers that were shipped through November 2013 are UL recognized.
*2. An SELV (separated extra-low voltage) system is one with a power supply that has double or reinforced insulation between the primary and the secondary circuits and has an output voltage of 30 V r.m.s. max. and 42.4 V peak max. or 60 VDC max. *3. A class 2 circuit is one tested and certified by UL as having the current and voltage of the secondary output restricted to specific levels. *4. The specified torque is 0.5 N·m for the E5CC-U.
E5@C/E5@C-T
Precautions for Safe Use Be sure to observe the following precautions to prevent malfunction or adverse affects on the performance or functionality of the product. Not doing so may occasionally result in faulty operation. Do not handle the Digital Temperature Controller in ways that exceed the ratings. 1. This product is specifically designed for indoor use only. Do not use this product in the following places: • Places directly subject to heat radiated from heating equipment. • Places subject to splashing liquid or oil atmosphere. • Places subject to direct sunlight. • Places subject to dust or corrosive gas (in particular, sulfide gas and ammonia gas). • Places subject to intense temperature change. • Places subject to icing and condensation. • Places subject to vibration and large shocks. 2. Use and store the product within the rated ambient temperature and humidity. Gang-mounting two or more Digital Temperature Controllers, or mounting Digital Temperature Controllers above each other may cause heat to build up inside the Digital Temperature Controllers, which will shorten their service life. In such a case, use forced cooling by fans or other means of air ventilation to cool down the Digital Temperature Controllers. 3. To allow heat to escape, do not block the area around the Digital Temperature Controller. Do not block the ventilation holes on the Digital Temperature Controller. 4. Be sure to wire properly with correct signal name and polarity of terminals. 5. Use the specified size of crimped terminals (M3, width of 5.8 mm or less) to wire the E5CC, E5EC, E5AC, E5DC, or E5@C-T. To connect bare wires to the terminal block of the E5CC, E5EC, E5AC, E5DC, or E5@C-T, use copper braided or solid wires with a gage of AWG24 to AWG18 (equal to a cross-sectional area of 0.205 to 0.823 mm2). (The stripping length is 6 to 8 mm.) Up to two wires of the same size and type, or two crimped terminals can be inserted into a single terminal. Use the specified size of crimped terminals (M3.5, width of 7.2 mm or less) to wire the E5CC-U. To connect bare wires to the terminal block of the E5CC-U, use copper braided or solid wires with a gage of AWG24 to AWG14 (equal to a cross-sectional area of 0.205 to 2.081 mm2). (The stripping length is 5 to 6 mm.) Up to two wires of the same size and type, or two crimped terminals can be inserted into a single terminal. Use the specified size of crimped terminals (M3, width of 5.8 mm or less) to wire the E5GC.* To connect bare wires to the terminal block of the E5GC, use copper braided or solid wires with a gauge of AWG24 to AWG18 (equal to a cross-sectional area of 0.205 to 0.823 mm2). (The stripping length for Digital Temperature Controllers with screw terminal blocks is 6 to 8 mm. The stripping length for Digital Temperature Controllers with screwless clamp terminal blocks is 8 to 12 mm.) Up to two wires of the same size and type, or two crimped terminals can be inserted into a single terminal. When connecting two wires into one terminal of a Digital Temperature Controller with a screwless clamp terminal block, use ferrules with a diameter of 0.8 to 1.4 mm and an exposed conductor length of 8 to 12 mm that two wires are crimped for a ferrule.* * The Digital Temperature Controller with screwless clamp terminals underwent UL testing with one braided wire connected. 6. Do not wire the terminals that are not used. 7. Use a commercial power supply for the power supply voltage input to a Digital Temperature Controller with AC input specifications. Do not use the output from an inverter as the power supply. Depending on the output characteristics of the inverter, temperature increases in the Digital Temperature Controller may cause smoke or fire damage even if the inverter has a specified output frequency of 50/60 Hz. 8. To avoid inductive noise, keep the wiring for the product’s terminal block away from power cables carry high voltages or large currents. Also, do not wire power lines together with or parallel to product wiring. Using shielded cables and using separate conduits or ducts is recommended. Attach a surge suppressor or noise filter to peripheral devices that
generate noise (in particular, motors, transformers, solenoids, magnetic coils, or other equipment that have an inductance component). When a noise filter is used at the power supply, first check the voltage or current, and attach the noise filter as close as possible to the product. Allow as much space as possible between the product and devices that generate powerful high frequencies (high-frequency welders, high-frequency sewing machines, etc.) or surge. 9. Use this product within the rated load and power supply. 10.Make sure that the rated voltage is attained within two seconds of turning ON the power using a switch or relay contact. If the voltage is applied gradually, the power may not be reset or output malfunctions may occur. 11.Make sure that the Digital Temperature Controller has 30 minutes or more to warm up after turning ON the power before starting actual control operations to ensure the correct temperature display. 12.When executing self-tuning with E5@C, turn ON power to the load (e.g., heater) at the same time as or before supplying power to the product. If power is turned ON to the product before turning ON power to the load, self-tuning will not be performed properly and optimum control will not be achieved. 13.A switch or circuit breaker must be provided close to the product. The switch or circuit breaker must be within easy reach of the operator, and must be marked as a disconnecting means for this unit. 14.Use a soft and dry cloth to clean the product carefully. Do not use organic solvent, such as paint thinner, benzine or alcohol to clean the product. 15.Design the system (e.g., control panel) considering the 2 seconds of delay that the product's output to be set after power ON. 16.The output may turn OFF when you move to the initial setting level. Take this into consideration when performing control operations. 17.The number of non-volatile memory write operations is limited. Therefore, use RAM write mode when frequently overwriting data during communications or other operations. 18.Always touch a grounded piece of metal before touching the Digital Temperature Controller to discharge static electricity from your body. 19.Use suitable tools when taking the Digital Temperature Controller apart for disposal. Sharp parts inside the Digital Temperature Controller may cause injury. 20.For compliance with Lloyd’s standards, the E5CC, E5CC-U, E5EC, and E5AC must be installed under the conditions that are specified in Shipping Standards. 21.For the Digital Temperature Controller with two Setup Tool ports (E5EC/E5AC/E5DC/E5GC), do not connect cables to both ports at the same time. The Digital Temperature Controller may be damaged or may malfunction. 22.Do not place heavy object on the Conversion Cable, bend the cable past its natural bending radius, or pull on the cable with undue force. 23.Do not disconnect the Communications Conversion Cable or the USB-Serial Conversion Cable while communications are in progress. Damage or malfunction may occur. 24.Do not touch the external power supply terminals or other metal parts on the Digital Temperature Controller. 25.Refer to the E5@C Digital Temperature Controllers User’s Manual (Cat. No. H174) for information on the communications distances and cables for the E5@C. For details on the E5@C-T, refer to the E5@C-T Digital Temperature Controllers Programmable Type User’s Manual (Cat. No. H185). 26.Do not bend the communications cables past their natural bending radius. Do not pull on the communications cables. 27.Do not turn the power supply to the Digital Temperature Controller ON or OFF while the USB-Serial Conversion Cable is connected. The Digital Temperature Controller may malfunction. 28.Make sure that the indicators on the USB-Serial Conversion Cable are operating properly. Depending on the application conditions, deterioration in the connectors and cable may be accelerated, and normal communications may become impossible. Perform periodic inspection and replacement. 29.Connectors may be damaged if they are inserted with excessive force. When connecting a connector, always make sure that it is oriented correctly. Do not force the connector if it does not connect smoothly.
105
E5@C/E5@C-T 30.Noise may enter on the USB-Serial Conversion Cable, possibly causing equipment malfunctions. Do not leave the USB-Serial Conversion Cable connected constantly to the equipment. 31.For the E5DC, when you attach the Main Unit to the Terminal Unit, make sure that the hooks on the Main Unit are securely inserted into the Terminal Unit. 32.For the E5CC-U, when you attach the Main Unit to the socket, make sure that the hooks on the socket are securely inserted into the Main Unit. 33.Install the DIN Track vertically to the ground. 34.For the E5DC, always turn OFF the power supply before connecting the Main Unit to or disconnecting the Main Unit from the Terminal Unit, and never touch nor apply shock to the terminals or electronic components. When connecting or disconnecting the Main Unit, do not allow the electronic components to touch the case. 35.Observe the following precautions when you remove the terminal block or pulling out the interior of the product of the E5GC. • Always follow the instructions provided in the E5@C Digital Temperature Controllers User’s Manual (Cat. No. H174). • Turn OFF the power supply before you start and never touch nor apply shock to the terminals or electric components. When you insert the interior body of the Digital Temperature Controller, do not allow the electronic components to touch the case. • Check for any corrosion on the terminals. • When you insert the interior body into the rear case, confirm that the hooks on the top and bottom are securely engaged with the case.
Shipping Standards The E5CC, E5CC-U, E5EC, and E5AC comply with Lloyd's standards. When applying the standards, the following installation requirements must be met in the application.
Application Conditions ● Installation Location The E5CC, E5CC-U, E5EC, and E5AC comply with installation category ENV1 and ENV2 of Lloyd's standards. Therefore, they must be installed in a location equipped with air conditioning. They cannot be used on the bridge or decks, or in a location subject to strong vibration.
Precautions for Correct Use ● Service Life 1. Use the product within the following temperature and humidity ranges: Temperature: -10 to 55°C (with no icing or condensation) Humidity: 25% to 85% If the product is installed inside a control board, the ambient temperature must be kept to under 55°C, including the temperature around the product. 2. The service life of electronic devices like Digital Temperature Controllers is determined not only by the number of times the relay is switched but also by the service life of internal electronic components. Component service life is affected by the ambient temperature: the higher the temperature, the shorter the service life and, the lower the temperature, the longer the service life. Therefore, the service life can be extended by lowering the temperature of the Digital Temperature Controller. 3. When two or more Digital Temperature Controllers are mounted horizontally close to each other or vertically next to one another, the internal temperature will increase due to heat radiated by the Digital Temperature Controllers and the service life will decrease. In such a case, use forced cooling by fans or other means of air ventilation to cool down the Digital Temperature Controllers. When providing forced cooling, however, be careful not to cool down the terminals sections alone to avoid measurement errors.
● Measurement Accuracy 1. When extending or connecting the thermocouple lead wire, be sure to use compensating wires that match the thermocouple types. 2. When extending or connecting the lead wire of the platinum resistance thermometer, be sure to use wires that have low resistance and keep
106
the resistance of the three lead wires the same. 3. Mount the product so that it is horizontally level. 4. If the measurement accuracy is low, check to see if input shift has been set correctly.
● Waterproofing (Not applicable to the E5CC-U/ E5DC.) The degree of protection is as shown below. Sections without any specification on their degree of protection or those with IP@0 are not waterproof. Front panel: IP66, Rear case: IP20, Terminal section: IP00 When waterproofing is required, insert the Waterproof Packing on the backside of the front panel. Keep the Port Cover on the front-panel Setup Tool port of the E5EC/E5AC/E5EC-T/E5AC-T securely closed. The degree of protection when the Waterproof Packing is used is IP66. To maintain an IP66 degree of protection, the Waterproof Packing and the Port Cover for the front-panel Setup Tool port must be periodically replaced because they may deteriorate, shrink, or harden depending on the operating environment. The replacement period will vary with the operating environment. Check the required period in the actual application. Use 3 years or sooner as a guideline. If the Waterproof Packing and Port Cover are not periodically replaced, waterproof performance may not be maintained. If a waterproof structure is not required, then the Waterproof Packing does not need to be installed.
● Operating Precautions 1. When using self-tuning, turn ON power for the load (e.g., heater) at the same time as or before supplying power to the Digital Temperature Controller. If power is turned ON for the Digital Temperature Controller before turning ON power for the load, selftuning will not be performed properly and optimum control will not be achieved. When starting operation after the Digital Temperature Controller has warmed up, turn OFF the power and then turn it ON again at the same time as turning ON power for the load. (Instead of turning the Digital Temperature Controller OFF and ON again, switching from STOP mode to RUN mode can also be used.) 2. Avoid using the Digital Temperature Controller in places near a radio, television set, or wireless installing. These devices can cause radio disturbances which adversely affect the performance of the Controller.
● Others 1. Do not Connect or disconnect the Conversion Cable connector repeatedly over a short period of time. The computer may malfunction. 2. After connecting the Conversion Cable to the computer, check the COM port number before starting communications. The computer requires time to recognize the cable connection. This delay does not indicate failure. 3. Do not connect the Conversion Cable through a USB hub. Doing so may damage the Conversion Cable. 4. Do not use an extension cable to extend the Conversion Cable length when connecting to the computer. Doing so may damage the Conversion Cable.
E5@C/E5@C-T ● Mounting
E5EC/E5AC/E5EC-T/E5AC-T Adapter
Mounting to a Panel E5GC
Adapter
Panel
Adapter Terminal Cover (E53-COV24)
Waterproof Packing
Terminal Cover (E53-COV24)
Panel Water Proof Packing
1. For waterproof mounting, waterproof packing must be installed on the Digital Temperature Controller. Waterproofing is not possible when group mounting several Digital Temperature Controllers. Waterproof packing is not necessary when there is no need for the waterproofing function. 2. Insert the E5GC into the mounting hole in the panel. 3. Use two Mounting Adapters, either on the top and bottom or on the right and left. 4. Push the Adapters from the terminals up to the panel, and temporarily fasten the E5GC. 5. Tighten the two fastening screws on the Adapter. Alternately tighten the two screws little by little to maintain a balance. Tighten the screws to a torque of 0.29 to 0.39 N·m.
E5CC/E5CC-T
1. For waterproof mounting, waterproof packing must be installed on the Digital Temperature Controller. Waterproofing is not possible when group mounting several Digital Temperature Controllers. Waterproof packing is not necessary when there is no need for the waterproofing function. 2. Insert the E5EC/E5AC/E5EC-T/E5AC-T into the mounting hole in the panel. 3. Push the adapter from the terminals up to the panel, and temporarily fasten the E5EC/E5AC/E5EC-T/E5AC-T. 4. Tighten the two fastening screws on the adapter. Alternately tighten the two screws little by little to maintain a balance. Tighten the screws to a torque of 0.29 to 0.39 N·m.
E5DC Adapter
There are two models of Terminal Covers that you can use with the E5CC/ E5CC-T. Terminal Cover (E53-COV17) (Sold separately)
Adapter
Panel
Terminal Cover (E53-COV23)
Terminal Unit Main Unit Water Proof Packing Panel
E5CC-U For the Wiring Socket for the E5CC-U, purchase the P2CF-11 or PG3A-11 separately.
1. Insert the E5DC into the mounting hole in the panel. (Attach the Terminal Unit after you insert the Main Unit.) 2. Push the Adapter from the Terminal Unit up to the panel, and temporarily fasten the E5DC. 3. Tighten the two fastening screws on the Adapter. Alternately tighten the two screws little by little to maintain a balance. Tighten the screws to a torque of 0.29 to 0.39 N·m.
Mounting to and Removing from DIN Track E5DC
1. For waterproof mounting, waterproof packing must be installed on the Digital Temperature Controller. Waterproofing is not possible when group mounting several Digital Temperature Controllers. Waterproof packing is not necessary when there is no need for the waterproofing function. The E5CC-U cannot be waterproofed even if the Waterproof Packing is inserted. 2. Insert the E5CC/E5CC-U/E5CC-T into the mounting hole in the panel. 3. Push the adapter from the terminals up to the panel, and temporarily fasten the E5CC. 4. Tighten the two fastening screws on the adapter. Alternately tighten the two screws little by little to maintain a balance. Tighten the screws to a torque of 0.29 to 0.39 N·m.
• Mounting a Unit Pull down the DIN Track hook on the Terminal Unit and catch the top hook on the DIN Track. Press the Unit onto the DIN Track until the DIN Track hooks are locked in place. 2. Catch the top hook on the DIN Track.
3. Press the Unit onto the DIN Track. 1. Pull down the hook.
4. Make sure that the hooks are locked in place.
107
E5@C/E5@C-T • Removing a Unit Pull down on the DIN Track Hook with a flat-blade screwdriver and lift up the Unit.
Mounting the DIN Track Attach the DIN Track to the inside of the control panel with screws to at least three locations. • DIN Track (sold separately) PFP-50N (50 cm) and PFP-100N (100 cm)
Install the DIN Track vertically to the ground.
Removing the Main Unit Press in the two hooks on the Main Unit and remove the Main Unit from the Terminal Unit.
(1)
Horizontal: NG
Vertical: OK
(2)
Mounting the Terminal Cover E5CC/E5CC-T
(1)
End Plate Installation Make sure to attach PFP-M End Plates to the ends of the Units. B
A
Slightly bend the E53-COV23 Terminal Cover to attach it to the terminal block as shown in the following diagram. The Terminal Cover cannot be attached in the opposite direction. E53-COV17 Terminal Cover can be also attached. Make sure that the "UP" mark is facing up, and then attach the E53COV17 Terminal Cover to the holes on the top and bottom of the Digital Temperature Controller. E53-COV17
E53-COV23
Adapter
Individual Mounting
Group Mounting
Terminal Cover (E53-COV17) (Sold separately)
Enlarged illustration of Terminal Section
E5EC/E5AC/E5EC-T/E5AC-T Slightly bend the E53-COV24 Terminal Cover to attach it to the terminal block as shown in the following diagram. The Terminal Cover cannot be attached in the opposite direction.
Slightly bend the E53-COV24 Terminal Cover in the direction shown by the arrows to attach it to the terminal block.
Enlarged illustration of the terminal part
108
E5@C/E5@C-T Attaching the End Cover E5DC
4. Secure the End Cover so that the double-sided tape is firmly attached.
1. Install the E5DC in a panel.
2. Peel off the release paper from the double-sided tape on the End Cover.
Double-sided tape
Removing the Digital Temperature Controller from the case E5GC You can use the Y92F-55 Draw-out Jig to remove the interior body of the Digital Temperature Controller from the case to perform maintenance without removing the terminal wiring. This is possible only for the E5GC. It is NOT possible for the E5CC, E5CC-U, E5EC, E5AC, E5DC, or E5@C-T. Check the specifications of the case and Digital Temperature Controller before removing the Digital Temperature Controller from the case. Draw-out Jig insertion hole
Panel
3. Align the tabs on the End Cover with the depressions on the E5DC and attach the End Cover.
Mounting Adapter
Y92F-55 Draw-out Jig Hook
1 3 1 Draw-out Jig insertion hole
2
Hook
1. Insert the Y92F-55 Draw-out Jig securely into the Draw-out Jig insertion holes (one hole each on the top and bottom) and press it in firmly until the hooks engage on the top and bottom. 2. Pull out the Y92F-55 Draw-out Jig together with the front panel. Do not apply unnecessary force. 3. When inserting the body of the Temperature Controller into the case, make sure the PCBs are parallel to each other, make sure that the sealing rubber is in place, and press the E5GC toward the rear case into position. While pushing the E5GC into place, push down on the hooks on the top and bottom surfaces of the rear case so that the hooks are securely locked in place. Be sure that electronic components do not come into contact with the case. Sealing rubber
PCBs Keep the PCBs parallel to each other and inset them into the rear case.
Right Side View of the E5GC
109
E5@C/E5@C-T ● Precautions when Wiring • Separate input leads and power lines in order to prevent external noise. • Use a shielded, AWG24 to AWG18 (cross-sectional area of 0.205 to 0.8231 mm2) twisted-pair cable. Use a shielded, AWG24 to AWG14 (cross-sectional area of 0.205 to 2.081 mm2) twisted-pair cable for the E5CC-U. The stripping length is 6 to 8 mm for the E5CC, E5EC, E5AC, E5DC, or E5CC-T and 5 to 6 mm for the E5CC-U. The E5GC stripping length is 6 to 8 mm for models with screw terminal blocks and 8 to 12 mm for models with screwless clamp terminal blocks. • Use crimp terminals when wiring the terminals. • Use the suitable wiring material and crimp tools for crimp terminals. • Tighten the terminal screws to a torque of 0.43 to 0.58 N·m. The specified torque is 0.5 N·m for the E5CC-U. • For the E5GC, E5CC, E5EC, E5AC, E5DC, or E5@C-T, use the following types of crimp terminals for M3 screws.
• For E5GC Controllers with screwless clamp terminal blocks, use braided or solid wires with a gauge of AWG24 to AWG18 (equal to a cross-sectional area of 0.205 to 0.823 mm2). The length of the conductive portion inserted into the terminal must be 8 to 12 mm. Ferrules must be 0.8 to 1.4 mm in diameter.. 0.8 to 1.4 mm
8 to 12 mm
Ferrules
• For the E5CC-U, use the following types of crimp terminals for M3.5 screws. 7.2 mm max.
7.2 mm max.
Three-year Guarantee ● Period of Guarantee The guarantee period of the Unit is three years starting from the date the Unit is shipped from the factory.
Scope of Guarantee The Unit is guaranteed under the following operating conditions. Top 1. Average Operating Temperature (see note): −10°C to 50°C 2. Mounting Method: Standard mounting Bottom Note: Average Operating Temperature Refer to the process temperature of the Unit mounted to a control panel and connected to peripheral devices on condition that the Unit is in stable operation, sensor input type K is selected for the Unit, the positive and negative thermocouple input terminals of the Unit are short-circuited, and the ambient temperature is stable. Should the Unit malfunction during the guarantee period, OMRON shall repair the Unit or replace any parts of the Unit at the expense of OMRON.
110
wires
• Recommended Ferrules for E5GC Screwless Clamp Terminals Manufacturer Altech Corp.
Model number 2623.0
Daido Solderless Terminal Mfg. Co.
AVA-0.5
J.S.T. Mfg. Co.
TUB-0.5
5.8 mm max.
5.8 mm max.
8 to 12 mm
Single (1 wire)
TGNTC-1.25-9T TGVTC-1.25-11T TGNTC-1.25-11T TC0.3-9.5 TC1.25-11S-ST TC1.25-11S TC2-11S
Double (2 wires)
TGWVTC-1.25-9T TGWVTC-1.25-11T
Nichifu Co.
Terms and Conditions Agreement Read and understand this catalog. Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments.
Warranties. (a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron). Omron disclaims all other warranties, express or implied. (b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS. BUYER ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the Products or otherwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obligation hereunder shall be, at Omron’s election, to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or replacement thereof) the non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount equal to the purchase price of the non-complying Product; provided that in no event shall Omron be responsible for warranty, repair, indemnity or any other claims or expenses regarding the Products unless Omron’s analysis confirms that the Products were properly handled, stored, installed and maintained and not subject to contamination, abuse, misuse or inappropriate modification. Return of any Products by Buyer must be approved in writing by Omron before shipment. Omron Companies shall not be liable for the suitability or unsuitability or the results from the use of Products in combination with any electrical or electronic components, circuits, system assemblies or any other materials or substances or environments. Any advice, recommendations or information given orally or in writing, are not to be construed as an amendment or addition to the above warranty. See http://www.omron.com/global/ or contact your Omron representative for published information.
Limitation on Liability; Etc. OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY. Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted.
Suitability of Use. Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the combination of the Product in the Buyer’s application or use of the Product. At Buyer’s request, Omron will provide applicable third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine, system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product with respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases. NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
Programmable Products. Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence thereof.
Performance Data. Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate it to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations of Liability.
Change in Specifications. Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our practice to change part numbers when published ratings or features are changed, or when significant construction changes are made. However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers may be assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at any time to confirm actual specifications of purchased Product.
Errors and Omissions. Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is assumed for clerical, typographical or proofreading errors or omissions.
OMRON Corporation
Industrial Automation Company
Authorized Distributor:
Tokyo, JAPAN
Contact: www.ia.omron.com Regional Headquarters OMRON EUROPE B.V. Wegalaan 67-69-2132 JD Hoofddorp The Netherlands Tel: (31)2356-81-300/Fax: (31)2356-81-388
OMRON ELECTRONICS LLC One Commerce Drive Schaumburg, IL 60173-5302 U.S.A. Tel: (1) 847-843-7900/Fax: (1) 847-843-7787
OMRON ASIA PACIFIC PTE. LTD. No. 438A Alexandra Road # 05-05/08 (Lobby 2), Alexandra Technopark, Singapore 119967 Tel: (65) 6835-3011/Fax: (65) 6835-2711
OMRON (CHINA) CO., LTD. Room 2211, Bank of China Tower, 200 Yin Cheng Zhong Road, PuDong New Area, Shanghai, 200120, China Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200
© OMRON Corporation 2011-2014 All Rights Reserved. In the interest of product improvement, specifications are subject to change without notice. Cat. No. H177-E1-07
0314 (1111)