Transcript
Strand Lighting Offices Philips Strand Lighting - Dallas 10911 Petal Street Dallas, TX 75238 Tel: 214-647-7880 Fax: 214-647-8031
Philips Strand Lighting - Auckland 19-21 Kawana Street Northcote, Auckland 0627 New Zealand Tel: +64 9 481 0100 Fax: +64 9 481 0101
Philips Strand Lighting - New York 267 5th Ave, 4th Floor New York, NY 10016 Tel: 212-213-8219 Fax: 212-532-2593
Philips Strand Lighting - Europe Marssteden 152 Enschede 7547 TD The Netherlands Tel: +31 53 4500424 Fax: +31 53 4500425
Philips Strand Lighting - Asia Limited Room 6-10, 20/F Delta House 3 On Yiu Street Shatin, N.T. Hong Kong Tel: + 852 2757 3033 Fax: + 852 2757 1767
Website: www.strandlighting.com
The material in this manual is for information purposes only and is subject to change without notice. Philips Strand Lighting assumes no responsibility for any errors or omissions which may appear in this manual. For comments and suggestions regarding corrections and/or updates to this manual, please visit the Philips Strand Lighting web site at www.strandlighting.com or contact your nearest Philips Strand Lighting office. El contenido de este manual es solamente para información y está sujeto a cambios sin previo aviso. Philips Strand Lighting no asume responsabilidad por errores o omisiones que puedan aparecer. Cualquier comentario, sugerencia o corrección con respecto a este manual, favor de dirijirlo a la oficina de Philips Strand Lighting más cercana. Der Inhalt dieses Handbuches ist nur für Informationszwecke gedacht, Aenderungen sind vorbehalten. Philips Strand Lighting uebernimmt keine Verantwortung für Fehler oder Irrtuemer, die in diesem Handbuch auftreten. Für Bemerkungen und Verbesserungsvorschlaege oder Vorschlaege in Bezug auf Korrekturen und/oder Aktualisierungen in diesem Handbuch, moechten wir Sie bitten, Kontakt mit der naechsten Philips Strand LightingNiederlassung aufzunehmen. Le matériel décrit dans ce manuel est pour information seulement et est sujet à changements sans préavis. La compagnie Philips Strand Lighting n'assume aucune responsibilité sur toute erreur ou ommission inscrite dans ce manuel. Pour tous commentaires ou suggestions concernant des corrections et/ou les mises à jour de ce manuel, veuillez s'il vous plait contacter le bureau de Philips Strand Lighting le plus proche.
Note: Information contained in this document may not be duplicated in full or in part by any person without prior written approval of Philips Strand Lighting. Its sole purpose is to provide the user with conceptual information on the equipment mentioned. The use of this document for all other purposes is specifically prohibited.
Document Number: 85-6386 Version as of: 18 March 2013
E3D20 Pre-Wired Dimming Cabinet Installation & User’s Guide ©2013 Philips Group. All rights reserved.
E3D20 Pre-Wired Dimming Cabinet
Installation & User’s Guide
IMPORTANT INFORMATION Warnings and Notices When using electrical equipment, basic safety precautions should always be followed including the following: a. READ AND FOLLOW ALL SAFETY INSTRUCTIONS. b. For indoor, dry locations use only. Do not use outdoors. c. Do not mount near gas or electric heaters. d. Equipment should be mounted in locations and at heights where it will not readily be subjected to tampering by unauthorized personnel. e. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition. f. Not for residential use. Do not use this equipment for other than its intended use. g. All Environ3 devices require a neutral connection (no common neutrals). Each circuit-feeding dimmers and dimmed loads require a separate neutral. Shared neutrals will result in undesirable flashing of controlled loads. h. Use VA dimmers to control incandescent, low-voltage with magnetic transformers, neon, cold cathode, or general inductive loads. When calculating a magnetic low-voltage load, a 25% transformer loss must be factored (i.e. actual lamp wattage plus 25% equals total load). i. Use Quiet Electronic (QE) Dimmers to control only low-voltage fixtures that have electronic, solidstate transformers, and regular incandescent loads. Not for use with Magnetic Low Voltage fixtures. j. Use HDF Direct Drive Dimmers to control fluorescent lighting loads at 120V with approved PowerSpec HDF Electronic Ballasts only and Dimming Amplifiers. k. Use Electronic Ballast (EB) Direct Drive Dimmers to control Advance Mark 10 Dimmable Electronic Ballast. l. Environ3 Dimmers or Switches may be fed individually or in groups, regardless of phase. m. Environ3 Masters draw approximately one watt and may be fed through any circuit. Multiple masters may be interconnected. The total number of dimmers and masters are not to exceed 30. An unlimited number of channel remotes (61228) may be used. n. HDF Dimmers can be connected to a Dimming Amplifier. Please consult interface and amplifier instructions for wiring. Non-dim switches can be connected to Environ3 relay modules for 277V loads. o. Line voltage must not be supplied by a GFI breaker. p. Refer service to qualified personnel. SAVE THESE INSTRUCTIONS.
1
Installation & User’s Guide
E3D20 Pre-Wired Dimming Cabinet
Warnings and Notices (continued) WARNING: You must have access to a main circuit breaker or other power disconnect device before installing any wiring. Be sure that power is disconnected by removing fuses or turning the main circuit breaker off before installation. Installing the device with power on may expose you to dangerous voltages and damage the device. A qualified electrician must perform this installation. WARNING: Refer to National Electrical Code® and local codes for cable specifications. Failure to use proper cable can result in damage to equipment or danger to personnel. WARNING: This equipment is intended for installation in accordance with the National Electric Code® and local regulations. It is also intended for installation in indoor applications only. Before any electrical work is performed, disconnect power at the circuit breaker or remove the fuse to avoid shock or damage to the control. It is recommended that a qualified electrician perform this installation. WARNING: Line voltage must not be supplied by a GFI breaker.
Philips Strand Lighting Limited Two-Year Warranty Philips Strand Lighting offers a two-year limited warranty of its products against defects in materials or workmanship from the date of delivery. A copy of Philips Strand Lighting two-year limited warranty containing specific terms and conditions can be obtained from the Philips Strand Lighting web site at www.strandlighting.com or by contacting your local Philips Strand Lighting office.
2
IMPORTANT INFORMATION
E3D20 Pre-Wired Dimming Cabinet
Installation & User’s Guide
TABLE OF CONTENTS Strand Lighting Offices....................................................................................................... Inside Front Cover
IMPORTANT INFORMATION Warnings and Notices ..................................................................................................................................... 1 Philips Strand Lighting Limited Two-Year Warranty .................................................................................... 2
TABLE OF CONTENTS PREFACE About this Manual .................................................................................................................................................. 4 Product Description ................................................................................................................................................ 4 Technical Specifications ......................................................................................................................................... 4 Electrical Specifications.................................................................................................................................. 4 Environmental Specifications ......................................................................................................................... 4 Mechanical Specifications............................................................................................................................... 4 Getting Started........................................................................................................................................................ 5 Unpack E3D20 Pre-Wired Dimming Cabinet................................................................................................. 5 E3D20 Pre-Wired Dimming Cabinet Features ....................................................................................................... 5 E3D20 Pre-Wired Dimming Cabinet Dimensions ................................................................................................. 6
INSTALLATION Power Requirements............................................................................................................................................... 7 Cabinet Installation................................................................................................................................................. 7 Typical Connections to Feeder Circuits ................................................................................................................. 8 Connecting Multiple Dimming Cabinets................................................................................................................ 9 Master Control Station and Dimmer Operation ..................................................................................................... 9
3
E3D20 Pre-Wired Dimming Cabinet
Installation & User’s Guide
PREFACE 1. About this Manual The document provides installation and operation instructions for the following products: • E3D20 Pre-Wired Dimming Cabinet Please read all instructions before installing or using this product. Retain this manual for future reference. Additional product information and descriptions may be downloaded at www.strandlighting.com.
2. Product Description Environ3 control systems are a revolutionary system of advanced digital wallbox dimmers for economical and flexible multi-scene, multi-channel control. Environ3 control systems provides flexible 13-scene preset dimming control for up to 30 devices, as well as, 12 adjustable fade rates up to one hour that are programmable by scene. The E3D20 Pre-Wired Dimming Cabinet facilitates design and installation by combining dimmers and controls into a common enclosure. Each cabinet is shipped assembled, pre-wired, and tested with its dimmers and/or master stations. The cabinet arrives at the job site ready to accept power and load wiring from the installer. This can significantly reduce installation time and potential wiring issues while providing a clean and consistent installation. For design flexibility, the cabinet accommodates several load types and device ratings. To best suit the application, the designer indicates where each device is located within the cabinet. The E3D20 Pre-Wired Dimming Cabinet is a UL508A listed enclosure designed to hold up to 20 Environ3 control system dimmers and masters, which can be configured into one or more individual rooms. Maximum wattage capacity is 20 dimmers at 1000W each (total 20,000 watts) or 10 dimmers at 1920W each (total 19,200 watts). For higher capacity applications, multiple cabinets (E3D20 and E3D56 cabinets) may be wired together. Note: A single Environ3 control system System (purple wire network) can accommodate up to 30 Environ3 control system dimmers and masters. When the total number of Environ3 control system devices exceeds the 30-device limit, use the dimming cabinet to accommodate one or more [30 devices] Environ3 Dimming Systems. Blank plates are provided to cover all unused spaces. The dimmer cabinet is surface or recess wall mounted. All dimmers and components are serviceable or removable from the front of the cabinet. The cabinet features a double-hinged, lockable latching cover. The cover is made from heavy gauge steel which prevents tampering of the devices. The E3D20 Pre-Wired Dimming Cabinet features air vents to maintain proper air flow through the dimmers. The cabinet shall insure satisfactory operation of the equipment within an ambient temperature range of 32 to 104ºF (0 to 40ºC). (No cooling fans are used.) For applications that require rough in prior to the dimmers being installed, order the Environ3 control system Cabinet Enclosure (E3D20ENC) and Cabinet Interior (E3D20INT). refer to the product specification sheet for more information.
3. Technical Specifications Electrical Specifications Input Voltage: Wattage:
108-132VAC, 60Hz 20,000 Watts (maximum)
Environmental Specifications Operating Temperature: Humidity: Markings:
32 to 104ºF / 0 to 40ºC 5% - 95% non-condensing UL508A
Mechanical Specifications Construction:
4
PREFACE
16 Gauge Steel Enclosure
E3D20 Pre-Wired Dimming Cabinet
Installation & User’s Guide
Finish: Weight:
White 80 lbs (empty cabinet, no dimmers or control stations)
Dimensions:
Refer to "E3D20 Pre-Wired Dimming Cabinet Dimensions" on page 6.
Note: For complete model specifications, features, etc., refer to the product specification sheet or visit the Philips Strand Lighting web site at www.strandlighting.com for more details.
4. Getting Started Unpack E3D20 Pre-Wired Dimming Cabinet Unpack the E3D20 Pre-Wired Dimming Cabinet from the packaging and check that all components are contained within and no parts of the cabinet are damaged. If any parts are missing, or damaged, please contact the carrier immediately and your nearest Philips Strand Lighting office.
5. E3D20 Pre-Wired Dimming Cabinet Features Figure 1 indicates all the features of the E3D20 Pre-Wired Dimming Cabinet and its components. Detail
Enclosure (See notes next page)
Load / Feed Knockouts (located top and bottom)
Interior (See notes next page)
Dimmer / Station Mounting Panel (See Detail)
Dimmer Cabinet Access Door Latch
Terminal Blocks (See descriptions below)
Ground Terminal Strips (upper and lower of cabinet)
Terminal Blocks Installed and positioned according to dimmer/master configuration for each cabinet. Dimmer Cabinet Access Door & Frame
Red Terminal Blocks: Load wire terminations Black Terminal Blocks: Power feed terminations Blue Terminal Block: Environ3 purple wire (control signal) terminations White Terminal Block: Neutral wire terminations Grey Terminal Block: PowerSpec HDF dimming ballast TAN wire termination (if dimmers installed) .
Figure 1: E3D20 Pre-Wired Dimming Cabinet Features
Getting Started
5
E3D20 Pre-Wired Dimming Cabinet
Installation & User’s Guide
NOTES: • Enclosure can be order separately for rough-in. Ordering number for just the enclosure is E3D20ENC. • If ordering the Enclosure separately, you must order the Interior separately. Ordering number for just the Interior is E3D20INT. The Interior includes the Terminal Blocks, Mounting Back Plane, Dimmer(s) Mounting Panel (with ordered dimmers), Access Door and Door Frame.
6. E3D20 Pre-Wired Dimming Cabinet Dimensions Figure 2 illustrates the overall dimensions of the E3D20 Pre-Wired Dimming Cabinet. Note: The E3D20 Pre-Wired Dimming Cabinet may be flush or surface mounted. Check local codes for installation requirements and reglulations.
NOTE: The E3D20 Pre-Wired Dimming Cabinet door has swinging radius of 21 inches. When installing, you must make provisions to allow door to fully swing open.
Figure 2: E3D20 Pre-Wired Dimming Cabinet Dimensions
6
PREFACE
E3D20 Pre-Wired Dimming Cabinet
Installation & User’s Guide
INSTALLATION 1. Power Requirements • Cabinet is to be wired with individually breakered feeder circuits of the correct voltage (120VAC) and capacity of the installed dimmers. • Each circuit-feeding dimmers and dimmed loads require a separate neutral. Shared neutrals will result in undesirable flashing of controlled loads.You must provide a separate neutral connection for all loads (no common neutrals). • Access to the dimmers, stations, and line voltage wiring section is through the double-hinged front cover of the cabinet. Knockouts are provided on top and bottom of enclosure to run feed circuits and load wiring. • If normal power is lost, the dimmers will retain their presets and will return to their last state when power is restored. WARNING! Line voltage must not be supplied by a GFI breaker.
2. Cabinet Installation To install the dimmer cabinet: Step 1. Surface or recess mount on wall using appropriate wall anchors (not supplied, by others). As shown in Figure 3, unit may be mounted using indicated mounting / anchor points. • Use wall anchors capable of supporting up to 110 to 130 pounds. • Refer to "E3D20 Pre-Wired Dimming Cabinet Dimensions" on page 6 for additional information an space requirements.
Mounting/Anchor Points Rear of Cabinet
Mounting/Anchor Points
Figure 3: E3D20 Pre-Wired Dimming Cabinet Mounting / Anchor Points Note: All wiring should be in accordance with local regulations and the National Electrical Code. All wiring shall enter and exit the cabinet via the provided knockouts at the top or bottom of the cabinet. WARNING! Insure that feed wiring is completely de-energized at the source before connecting to cabinet. Serious injury or death may occur trying to connect live wiring. Step 2. Terminate 120VAC lines and neutrals to terminal blocks. Do not use common neutrals!
Power Requirements
7
E3D20 Pre-Wired Dimming Cabinet
Installation & User’s Guide
Step 3. Connect lighting loads to the load terminal block. Be sure to match proper load with the correct device (refer to device location sticker on front of cabinet). Step 4. Connect ground to dimming cabinet. Step 5. Connect network communication wiring (purple wire) to additional cabinets and/or exterior control stations (if applicable).
3. Typical Connections to Feeder Circuits Figure 4 shows typical E3D20 Pre-Wired Dimming Cabinet wiring scheme to a circuit breaker panel.
To Lighting Loads (One dimmed 120VAC Line / Neutral per circuit)
Up to 20 Circuits... 120VAC Line / Neutral A
B
C
D
120VAC Line / Neutral 120VAC Line / Neutral
1
120VAC Line / Neutral 120VAC Line / Neutral 120VAC Line / Neutral 120VAC Line / Neutral
2
120VAC Line / Neutral 120VAC Line / Neutral 120VAC Line / Neutral
3
120VAC Line / Neutral 120VAC Line / Neutral 120VAC Line / Neutral 4
120VAC Line / Neutral 120VAC Line / Neutral 120VAC Line / Neutral 120VAC Line / Neutral
5
120VAC Line / Neutral 120VAC Line / Neutral 120VAC Line / Neutral
Circuit Breaker Panel E3D20 Cabinet Figure 4: E3D20 Pre-Wired Dimming Cabinet Typical Feeder Connections
8
INSTALLATION
E3D20 Pre-Wired Dimming Cabinet
Installation & User’s Guide
4. Connecting Multiple Dimming Cabinets Figure 5 shows typical E3D20 Pre-Wired Dimming Cabinet connections to other E3D20 Pre-Wired Dimming Cabinets. Note: Up to 30 Environ3 dimmers / devices may be controlled as one system. WARNING! Only the communication (Purple) wire should be connected from cabinet to cabinet. Do not share feeder circuits or load wiring between cabinets.
E3D20 Cabinet
A
B
C
E3D20 Cabinet
D
A
1
1
2
2
3
3
4
4
5
5
B
C
D
Purple Wire Figure 5: Typical Connection to Other Dimming Cabinets
5. Master Control Station and Dimmer Operation For master control station and dimmer operation, including setting scenes, fade rates, etc., refer to the provided installation and operation manual for these devices. An electronic copy of these manuals can be found on the Strand Lighting web site at www.strandlighting.com in the Support Section of the web site.
Connecting Multiple Dimming Cabinets