Transcript
DRC VARIZON® Displacement unit with adjustable spread pattern
DRC
Quick facts
►► Adjustable spread pattern and affected area
Quick guide A I R F L O W – S O U N D L E V E L
►► Suitable for all types of rooms
DRC
►► Simple installation
Size
25 dB(A)
30 dB(A)
35 dB(A)
►► Cleanable
200
200 (150)
230 (175)
270 (210)
250
300 (240)
350 (275)
425 (330)
315
450 (360)
510 (410)
600 (490)
400
630 (520)
740 (600)
880 (700)
200-600
510 (440)
610 (500)
710 (590)
250-800
810 (600)
950 (700)
1150 (800)
►► Air volume measuring point ►► Available in alternative colours
l/s
Sound level is valid at 150 m² equivalent sound absorption area at distance of 2 m from terminal. Values in brackets are valid at a an equivalent sound absorption area of 10 m2. All values are valid without disturbance on straight duct section.
1
DRC
Technical description Design The DRC is a complete, rectangular displacement unit with rounded corners. It is designed to stand on the floor. The body consists of side, top and bottom plates and an air distribution plate equipped with a number of adjustable discs. The top plate has a circular inlet for size 200 to 400. Sizes 200-600 and 250-800 have a rectangular inlet spigot. The diffusion plate has an access hatch for access to the duct system. The base plate is equipped with four feet. There are one or more perforated front plates on the front of the body, attached with screws. Sizes 200 and 250 have one front plates. Sizes 315, 400, 200-600 and 250-800 have three front plates. The measuring point is in the top of the displacement unit.
Materials and surface treatment The displacement unit is manufactured in galvanized sheet steel and aluminium profiles. It is coated with our pure white standard paint, RAL 9003/NCS S 0500-N. The unit is also available in other standard colours: Dusty grey 7037, white aluminium RAL 9006, jet black RAL 9005, grey aluminium RAL 9007 and white RAL 9010.
Special versions In addition to the standard sizes, these displacement units are available in special dimensions, with reinforced front plates etc. Please contact your nearest sales office for further information.
Commissioning The measurement outlet is placed on the top of the displacement unit. The k-factor of the unit is included in the product marking. The k-factor can also be found at www.swegon.com in the relevant k-factor guide. It is recommended that the a measurement unit and commissioning is used to regulate the air flow. This should be placed at least 3 - 4 duct diameters away from the displacement unit inlet. See Figure 1.
Accessories Plinth plate: DRCT 2 - for the aesthetic concealment of the space between the feet of the unit.
Planning
K-FACTOR
It is possible to modify the affected area by adjusting the deflectors behind the front plate. This does not affect the air flow, pressure drop or sound level. This flexibility simplifies any future changes in the furnishings of the room etc. N.B. The sound level in he engineering diagram's is valid at 150 m2 equivalent sound absorption area. This fact makes it important to check the air velocities in the connecting ducts to the terminals. Extra consideration has to be taken on how the ducts can be connected to the terminals. See figure 3.
Installation The terminal is placed on the floor and if necessary can be screwed to the wall using angle brackets. See Figure 1.
Figure 1. Installation. Commissioning.
2
We reserve the right to alter specifications.
20140107
www.swegon.com
DRC Maintenance
Table – Duct connections Effects on sound levels (dB) for different duct connections and different air velocities in straight duct section.
The displacement unit can be cleaned when necessary using lukewarm water with detergent added. The duct system is accessible by removing the perforated front plate and the access hatch. See Figure 2.
Duct connections (values in dB)
v (m/s)
A
B
C
D
4-5
+2
+6
+3
+3
6-8
+4
+ 10
+6
+6
Sound data Sound power level L w (dB) (150 m2 Sabine) Table KOK Size DRC
Mid-frequency (octave band) Hz 63 125
250
500
200
17
18
16
13
10
5
-3
-5
250
14
18
17
13
10
5
-2
-3
315
14
20
18
13
10
3
-4
-4
400
15
18
16
14
10
2
-6
-6
200-600
11
18
18
14
9
1
-8
-8
250-800
11
18
18
15
8
0
-9
-9
Tol. ±
2
2
2
2
2
2
2
2
Sound attenuation DL (dB) (150 m2 Sabine) Table DL
Figure 2. Maintenance.
Size
• Sound level dB(A) applies to rooms of 150 m2 equivalent absorption area, measured 2 m from the displacement unit and with at a straight section without disturbance on straight duct section. • Recommended maximum under temperature 6 K. • To calculate the width of the spread pattern, air velocities in the zone of occupation or sound levels in rooms with other dimensions, please refer to our calculation programme ProAir web, which is available for download at www.swegon.com.
Mid-frequency (octave band) Hz
DRC
63
125
250
500
200
15
12
6
2
1000 2000 4000 8000 2
3
5
4
250
13
10
5
2
2
3
4
5
315
12
9
4
1
0
1
2
2
400
10
6
4
1
1
1
1
1
200-600
8
4
1
0
0
0
0
0
250-800
6
3
1
0
0
0
0
0
Tol. ±
2
2
2
2
2
2
2
2
Figure 3. E.g. of how different duct connections affects the sound level of the terminal.
We reserve the right to alter specifications.
20140107
www.swegon.com
3
DRC
Sizing
1000 2000 4000 8000
DRC Engineering graphs Air flow – Pressure drop – Sound level – Affected area • The graphs present data for sound levels in a room with an equivalent absorption area of 150 m2 and measured 2 m from the displacement unit and with at a straight section without distrurbance on straight duct section. See Figure 3 for how different duct connetions will affect the sound level. • At the equivalent room absorption area of 10 m2 and at 2 m from the unit, the noise level increases approx. by 10 dB(A). • The affected area refers to a displacement unit installed next to a wall, 100 mm on the floor. The affected area distance is related to the isovel limit of 0.2 m/s at Dt 3 K. • The graphs are not to be used for commissioning. • ∇ = min. air flow to obtain sufficient commissioning pressure. • The dB(C) value is normally 6-9 dB higher than the dB(A) value. • For Dt = 6 K the measurements a0,20 and b0,20 are increased by approx. 20%. DRC 200 (150 m2 Sabine) 200
Figure 4. Affected area.
DRC 250 (150 m2 Sabine)
pt Pa
pt Pa 40 dB(A)
100
40 dB(A) 100
35
35 30
50 40 30
30
50 40 30
25 20
25 20
20
20 10
10 5 4
100 300
200
400
300
500
400 l/s 500
5 4 3 100
3
1000
m /h
200
400
a0,2 m
300
500
400
1000
l/s
2000
1000
3
m /h
a0,2 m
1
2
3
4
5
2
b0,2 m
3
4
5
10
b0,2 m
2
3
4
5
10 ∆ t -3°
DRC 315 (150 m2 Sabine)
2
3
4
5
∆ t -3°
pt Pa 40 dB(A)
100
100
40 dB(A)
35 30
50 40 30
20
20
20
10
10
200
300
400
500
1000
1000
2000
3000
3
4
5
30 25 20
5 4 3 200
l/s
300
4000 m3/h
a0,2 m 2
35
50 40 30
25
5 4 3
10
DRC 400 (150 m2 Sabine)
pt Pa
400
500
1000
1000
2000
3000
4000
l/s
2000
5000 m3/h
a0,2 m
10
3
b0,2 m
4
5
10
20
b0,2 m 2
4
500
3
4
5
We reserve the right to alter specifications.
10
∆ t -3°
2
20140107
3
4
5
10
∆ t -3°
www.swegon.com
DRC DRC 200-600 (150 m2 Sabine)
DRC 250-800 (150 m2 Sabine)
pt Pa
pt Pa
100
100 40 dB(A) 35
50 40 30
25 20
20
40 dB(A)
50 40 30
30
35 30 25
20
10
20
10
5 4 3 200
300
400
500
1000
1000
2000
3000
l/s
4000
5 4 3 300
2000
400
500
3
5000 m /h
1000
2000
a0,2 m
3000
4000
2000
l/s
3000
3
5000
m /h
a0,2 m 2
3
4
5
10
20
3
b0,2 m
4
5
10
20
30
b0,2 m 2
3
4
5
10
2
∆ t -3°
3
4
5
10
∆ t -3°
Dimensions and weights Size
A
B
C
ØD
E
FxG
H
Weight (kg)
200
600
1200
300
200
115
–
0
25
250
600
2000
350
250
140
–
0
43
315
1200
2000
415
315
173
–
0
80
400
1200
2000
500
400
215
–
0
83
200-600
1200
2000
300
–
115
200x600
55
75
250-800
1200
2000
350
–
140
250x800
55
78
DRC with circular duct connection has a spigot for a duct joint.
DRC
Figure 5. DRC 200 to 400.
Figure 6. DRC 200-600, 250-800.
110 A
C
Figure 7. Plinth plate DRCT 2. We reserve the right to alter specifications.
20140107
www.swegon.com
5
DRC
Order key
Specification example
Product Rectangular displacement unit with a circular duct connection
DRC
e
-aaa
Version Size:
200 250 315 400
Rectangular displacement unit with rectangular duct connection
DRC
e
-aaa -bbb
SD XX Swegons VARIZON® rectangular displacement unit of type DRC, having the following functions: • • • • • •
Adjustable spread pattern and affected area Exchangeable front sections Non-fouling Air volume measuring point Cleanable Powder painted in white, RAL 9003/NCS S 0500-N
Version Size:
Accessories:
200-600 250-800
Accessories Plinth plate
DRCT 2
a
Plint plate:
DRCT 2a aaa - (bbb)
xx items
Size:
DRCe aaa - bbb
xx items
-aaa -bbb
Version Size:
6
200 250 315 400 200-600 250-800
We reserve the right to alter specifications.
20140107
www.swegon.com