Transcript
Satchwell
URC-41N-10X* URC-51N-10X*
UNIFACT ®PRO – TERMINAL UNIT CONTROLLER Order Types: URC-41N-10X URC-51N-10X URC-IR-100 URC-SET-100
- Controller with S-Link support and on/off fan control, with preset applications (see page 2) - Controllers with S-Link support and fan speed control, with preset applications (see page 2) - Infra-red/RS 232 receiver for commissioning. - NCP Palm commissioning software.
The Unifact Pro terminal unit controllers have been designed to meet most fan-coil heating/cooling applications. The controllers can be used as standalone devices or can be networked to an IC-Unifact for use in Satchwell Σ (Sigma) systems. The URC-41N-10X models include one relay for on/off fan control. The URC-51N-10X models include three relays for fan-speed control. Commissioning should require less than ten minutes. The required application can be easily selected and set up locally using the NCP Palm tool, which can run on a laptop computer or on a PC. Communications between NCP Palm and the controller can be via an infra-red/RS 232 link to the URC-IR-100, which connects to a socket on the end of the controller. The controller has three main modes: comfort (day), night (off) and economy. The controller can be switched into any of these three modes from the Satchwell Σ (Sigma) PC (if used). When used standalone, the controller can be switched between two modes: either comfort and economy, or comfort and night, as selected during commissioning. A voltage-free input (activated from, for example, a timer switch or PIR) is used to switch between the two modes. A second voltage-free digital input is available for connection to a thermostat, which enables automatic changeover between cooling and heating modes for 2-pipe fan coil unit (FCU) applications. A DU/DUS/DDU sensor can be used to measure temperature. A DUS sensor can be used to adjust the comfort setpoint. S-Link sensors can also be used to measure temperature and offset the comfort setpoint and to display the controller operation modes.
*X = 0, 1, 2 or 3 depending on application.
FEATURES • Selectable control applications for most fan-coil applications. • Low installation cost. • Simple setup using laptop computer or PC via infra-red or RS 232 link. • Designed to maximise energy savings. • Optional networking to an Sigma system. • Supports DU 4301 and DUS 4302 room sensors, and DDU 0001 return-air sensor. • Automatic on/off or 3-speed fan control with URC-51N-10X models using three 230Vac, 5A relay outputs. • Fan on/off control with URC-41N-10X using one 230Vac, 5A relay output.
Data Sheets DS 13.303A - Wiring and Commissioning Information Sensors DS 1.020 - DU, DUS DS 1.030 - DDU DS 10.000 - MN Sx Actuators DS 3.005 - AVUX DS 3.010 - AVU Valves DS 24.020 - AVX Multi-Lingual Instructions MLI 13.303 - Mounting Information
• Digital S-Link sensors can be used to display operational conditions and to provide manual overrides. • One S-Link sensor can support multiple controllers/zones. • Voltage-free input to switch between comfort and economy/night modes • Voltage-free input for auto changeover between heating and cooling modes for 2-pipe FCU applications. • Built-in frost protection. • 15Vdc supply output for DU/DUS sensor or PIR. • 24Vac supply and four triac outputs for control of valves, dampers, heaters, etc. • User settings permanently stored in E2PROM. • Plastic enclosure.
SPECIFICATIONS
INPUTS/OUTPUTS
Order URC-41N-100 - Controller with on/off fan control, with 4-pipe Types: FCU application
Triac Outputs:
Four, 0V switched triacs.
Actuator Supply Outputs:
Two 24Vac outputs. 2.4VA maximum power consumption in total (e.g. 2.4VA per cooling valve and/or heating valve as only one valve is opening at a time).
DU/DUS/DDU Sensor Inputs/Outputs:
15Vdc power output (30mA max). Resistive input (0-10,000Ω) for temp. measurement - 'T-type'. Analogue (0-10Vdc) input for setpoint adjustment. All analogue inputs smoothed.
Controller Mode Input (DI1):
Voltage-free input to override controller from comfort mode to economy or night mode, depending on control application (see Note 1). Normal input is closed (to 0V). Open circuit selects economy/night mode (see Note 2).
Changeover Sensor Input (DI2):
Voltage-free thermostat input for 2-pipe auto changeover control applications. Open circuit selects cooling mode (see Note 3).
URC-41N-101 - Controller with on/off fan control, with two-pipe autochangeover application URC-41N-102 - Controller with on/off fan control, with DX cooling and electric heater application URC-41N-103 - Controller with on/off fan control, with airside control application URC-51N-100 - Controller with fan speed control, with 4-pipe FCU application. URC-51N-101 - Controller with fan speed control, with 2-pipe autochangeover application. URC-51N-102 - Controller with fan speed control, with DX cooling and electric heater application. URC-51N-103 - Controller with fan speed control, with airside control application. URC-IR-100
- Infra-red/RS 232 receiver.
URC-SET-100 - NCP Palm commissioning software. Control Range:
0 to 40°C.
Control Accuracy:
±0.1°C 18-24°C; ±0.5°C 14-18°C and 24-28°C; ±1°C other ranges.
Power Supply:
230Vac (+10% to –10%).
Fuse:
230Vac supply fused, 100mA.
Consumption:
230Vac @ 12VA maximum including outputs.
Power Failure Reserve:
E2PROM
Ambient Temperature Limits:
Operating: 0 to +50°C. Storage/Transit: –20 to +65°C.
Humidity Limits:
Up to 95% relative humidity non-condensing.
Terminals:
All input terminals accept one 2.5 mm2 wire unshrouded.
Sensor Types:
DU 4301, DUS 4302 or DDU 0001 (return air). MN-S1, MN-S2, MN-S3, MN-S4, MN-S4-FCS (MN-S5 not supported).
Actuator Compatibility:
AVU, AVUX, AVX (AVX must be connected via an external transformer; AVX7201 not compatible in Pulse Width Modulation applications)
Setpoint Adjustment:
Comfort, economy heating and economy cooling setpoints individually settable to ±1°C using NCP Palm. DUS 4302 sensor enables the comfort setpoint to be offset by ±3°C. Economy heating setpoint = 10-24°C. Economy cooling setpoint = 21-35°C. The MN-S3, MN-S4 and MN-S4-FCS sensors enable the comfort setpoint to be offset (by an amount within limits set in NCP Palm) when Comfort Setpoint Offset Mode is enabled at the S-Link sensor.
Control Algorithm
Proportional + integral, or proportional only. Proportional band and integral action time adjustable.
IR Receiver
Read range 30cm.
Frost Limit:
Adjustable (default +10°C).
LVD Compliance:
EN60730-1 (Safety) Pollution degree 2, Impulse voltage 2.5kV, Class II.
Network Interface:
RS 485 for optional networking to an IC-Unifact on an Sigma network.
Relay Outputs:
230Vac, 5A resistive. Three relays on URC-51N-10X; one on URC-41N-100. Note: See Wiring Precautions.
NCP Palm Communications Port:
RS 485 port for connection to infra-red/RS 232 receiver module.
preserves configuration data and user
settings.
Note: Frost protection is active in all modes (comfort, economy or night). When the room temperature falls below the frost limit temperature (default 10°C) heating begins. Heating ends when the temperature increases 2°C over the frost limit (default 12°C).
CONSTRUCTION Case:
Moulded polycarbonate plastic case. Fire resistant to UL94V-0.
Protection Class:
IP 10.
Conduit Entries:
Not Applicable.
Mounting:
On or in a Control appliance.
2
DI2 can also be used for all applications except the two-pipe FCU application as an additional controller mode input (which has the same effect as DI1 set with zero delay). DI2 is typically used for a time or window switch.
Notes: 1. The controller can be set up with a delay value applied to input DI1 to prevent a PIR or other occupancy sensor from continually switching the controller between modes during the day. 2. If the DI1 input is not required, no 0V link is required, since the input can be disabled from NCP Palm. 3. The controller can be configured to operate only in heating mode.
WIRING PRECAUTIONS
WARNINGS THIS DEVICE OPERATES AT 230Vac. LOCAL WIRING REGULATIONS AND USUAL SAFETY PRECAUTIONS MUST BE OBSERVED. DO NOT EXCEED RATED VOLTAGES. ALL RELAY OUTPUTS MUST USE A COMMON PHASE. DO NOT MIX PHASES. THIS IS REQUIRED TO PREVENT FLASHOVER BETWEEN DIFFERENT MAINS PHASES. ALL RELAY OUTPUTS MUST USE A COMMON VOLTAGE I.E. 230Vac OR 24Vac. DO NOT MIX VOLTAGES. THIS IS REQUIRED TO PREVENT THE POSSIBILITY OF FLASHOVER FROM 230Vac TO 24Vac. EXTERNAL RELAY(S) MUST BE USED TO SWITCH 24Vac WHEN THE COMMON VOLTAGE IS 230Vac. EXTERNAL RELAY(S) MUST BE USED TO SWITCH 230Vac WHEN THE COMMON VOLTAGE IS 24Vac. TO AVOID POSSIBLE CONTACT WITH MAINS VOLTAGES, WHEN WIRING IS COMPLETE, ENSURE THAT THE TERMINAL SHROUD IS CORRECTLY FITTED AND THAT THE MAINS AND RELAY TERMINALS ARE COVERED. Cautions Ensure that Terminal 13 (COM 0V) is securely connected to Earth. Do not route relay output wiring with any other controller wiring. Do not route triac output wiring with any other controller wiring. Do not route power and output wiring with signal wiring. Do not run Extra Low Voltage (24Vac or less) wiring in the same harness as mains wiring. The controller must be located as far away as possible (150mm minimum) from any contactors, switches and their associated cabling as they may cause interference when they operate. No connections can be made to the controller whilst ANY power is applied to it. This includes the relay outputs.
APPLICATIONS
IC UNIFACT FUNCTIONS
The following predefined control applications are available. For each application, fan-speed control is available with the URC-51N-10X models, and fan on/off control is available with the URC-41N-100. • Fan Coil Unit with Electric Heater and DX Cooling This is a simple fan coil unit application, with separate triac outputs for DX cooling and electric heater units, which are switched on or off based on the heating and cooling demand. • 2-Pipe Fan Coil Unit with Auto Changeover and Auxiliary Heater This uses a thermostat located in the water supply pipework to switch the controller between heating and cooling modes. The controller can be configured to operate in heating-only mode, if required. A triac output can be used to control an auxiliary heater to supply additional heat. • 4-Pipe Fan Coil Unit with Auxiliary Heater The 4-pipe FCU control application can control separate heating and cooling coils. A triac output can, if required, be used to control an auxiliary heater to supply additional heat if the heating coil cannot provide sufficient heat. • Air-Side Fan Coil Unit This application is for control of a modulating damper. The return air temperature is controller to the setpoint by altering the angle of the damper and therefore altering the bypass flow and the flow through the heating and cooling coils. In both comfort and economy mode, the fan speed is determined by the controller heating/cooling output.
Up to 80 Unifact Pro controllers can be networked to a single IC-Unifact in an Sigma network. The IC-Unifact enables several pre-programmed controller functions to be used, including the following: • Valve/fan exercise A signal from the IC-Unifact can be sent to controllers at a specified time to exercise the valves and fans. • Load shedding The IC-Unifact can limit the heating/cooling control output of a controller to a specified percentage of the maximum, based on the outside air temperature measured by a network sensor. In a simple 2-pipe system, for example, the valve position could be limited to 75% of its maximum. • Free cooling This is available if the fan coil has a fresh air inlet. The function enables a zone to be cooled by using fresh air that is at a lower temperature than the room temperature. The IC-Unifact receives the outside air temperature from a network sensor and, if appropriate, places the controller into free cooling mode. • Fire override Following a fire override signal from a Sigma front-end PC, the IC-Unifact forces the controller to stop the fan and all heating/cooling. • Summer/winter setpoint compensation The IC-Unifact receives the outside air temperature from a network sensor and can increase the controller’s comfort setpoint when the outside air temperature increases. This is based on the principle that the room temperature can be higher in summer, since people are using lighter clothing. • Temperature and fan speed updates The controller can receive temperature updates via the network or from a directly controlled sensor; also fan speed updates via the network.
GENERAL WIRING DIAGRAM Triac outputs 1-4 for actuators or heating/cooling units. Triac 4
1 DO4
18
L (230Vac)
Triac 3
2 DO3
19
N
Connect actuator or heating/cooling common to a 24Vac terminal. 2.4VA Max. Triac 2
5 DO2
Triac 1
6 DO1
4 24Vac
7 RS 485-
For controller networking.
230Vac
3 24Vac 20
RL1
21 22
RL2
8 RS 485+
Thermostat for 2-pipe autochangeover applications or window switch.
For connection to DUS/DU/DDU sensor (two twisted pairs) See Note 4.
23
10 15Vdc
RL3
24Vac
24
11 RPW
25
230V
Fan Speed 2
9 COM 0V Fan Speed 3
230Vac + 24Vac
9 9 8
12 °C 13 COM 0V 14 DI2 15 DI1
Optional PIR or other occupancy switch to select economy/night mode (open circuit to select). Leave unconnected if not required.
Fan Speed 1
MN-Sx sensor using twisted pair cable.
16 S-LK/COM 0V 17 S-LK
230Vac WARNING OBSERVE WIRING PRECAUTIONS SHOWN ON Page 2. Relays 2 and 3 on URC-51N-10X only.
Notes: 1. Some of the above connections may not be needed, depending on the control application selected. Refer to DS 10.130A for details of the connections required for each control application. 2. Screened cable is required only for network (RS 485) connections. This screen must be earthed at one point only. At the UNIFACTPRO controller end, ensure that the screen runs continuously through to the next controller in the network. 3. The 15V output may also be used to power a PIR, where appropriate (30mA max.). 4. DDU uses terminals 9 & 12, DU uses terminals 9, 10 & 12, DUS uses terminals 9,10, 11 & 12.
3
TYPICAL SIGMA SYSTEM DIAGRAM Sigma Terminal
Sigma Terminal
DNN (DS 13.420) Bus-du-jour LAN (Sigma LAN, ARC NET, ETHERNET)
Bus-du-jour Backbone (ARCNET and/or ETHERNET)
UNC 596 (DS 13.323)
UNC 532 (DS 13.311) UNIFACTPRO Integration Controller (DS 13.304) Up to 80 controllers UNIFACTPRO Controllers
IR/RS 232 Receiver
S-Link Sensor (DS 10.000) DU/DUS/DDU Sensor (DS 1.020, DS 1.030)
NCP Palm on Laptop/PC
DIMENSION DRAWING
106
95
153
Dimensions in mm
135
WARNINGS ELECTRICAL SHOCK HAZARD, REMOVE ALL POWER FROM BOTH THE CONTROLLER AND RELAY OUTPUTS BEFORE MAKING TERMINATIONS. THIS DEVICE OPERATES AT 230Vac. LOCAL WIRING REGULATIONS AND USUAL SAFETY PRECAUTIONS MUST BE OBSERVED. DO NOT EXCEED RATED VOLTAGES. ALL RELAY OUTPUTS MUST USE A COMMON VOLTAGE I.E. 230Vac OR 24Vac. DO NOT MIX VOLTAGES. THIS IS REQUIRED TO PREVENT THE POSSIBILITY OF FLASHOVER FROM 230Vac TO 24Vac. ALL RELAY OUTPUTS MUST USE A COMMON PHASE. DO NOT MIX PHASES. THIS IS REQUIRED TO PREVENT FLASHOVER BETWEEN DIFFERENT MAINS PHASES. TO AVOID POSSIBLE CONTACT WITH MAINS VOLTAGES, WHEN WIRING IS COMPLETE, ENSURE THAT THE TERMINAL SHROUD IS CORRECTLY FITTED AND THAT THE MAINS AND RELAY TERMINALS ARE COVERED. Cautions • Ensure that Terminal 13 (COM 0V) is securely connected to Earth. • Do not apply any voltages until a qualified technician has checked the system and the commissioning procedures have been completed. • If any equipment covers have to be removed during the installation of this equipment, ensure that they are refitted after installation to comply with UL and CE safety requirements. • Wiring precautions shown on Page 2 must be observed. • Do not exceed maximum ambient temperature. • Interference with parts under sealed covers invalidates guarantee. • Design and performance of Schneider Electric equipment is subject to improvement and therefore liable to alteration without notice. • Information is given for guidance only and Schneider Electric does not accept responsibility for the selection and installation of its products unless information has been given by the Company in writing relating to a specific application. • A periodic system and tuning check of the control system is recommended. Please contact your local sales office for details.
On October 1st, 2009, TAC became the Buildings business of its parent company Schneider Electric. This document reflects the visual identity of Schneider Electric, however there remains references to TAC as a corporate brand in the body copy. As each document is updated, the body copy will be changed to reflect appropriate corporate brand changes. Copyright © 2010, Schneider Electric All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change without notice. All rights reserved.
DS 13.303
02/10
Schneider Electric Malmö, Sweden +46 40 38 68 50 Satchwell Helpline +44 (0) 1628 741100
[email protected] www.schneider-electric.com/buildings.com