Transcript
DSXC16
Split System Air Conditioner Up to 16 SEER Cooling Capacity: 24,000 - 57,000 BTU/h Contents Nomenclature........................................ 2 Product Specifications........................... 3 Expanded Cooling Data......................... 4 AHRI Ratings......................................... 20 Dimensions.......................................... 30 Wiring Diagram.................................... 31 Accessories........................................... 32
Standard Features
Cabinet Features
• R-410A chlorine-free refrigerant • Two-Stage Copeland® UltraTech™ scroll compressor • High-density foam compressor sound blanket • ComfortNet™ Communications System compatible • Expanded ComfortAlert™ diagnostics • Set-up capable with 2 lowvoltage wires to outdoor unit • Diagnostic indicator lights and storage of 6 fault codes • Color-coded terminal strip for non-communicating set-up • High- and low-pressure switches • Factory-installed filter drier • Coil and ambient temperature sensors • Two-speed, quiet condenser fan motor • AHRI Certified; ETL Listed
• • • • •
SS-DSXC16
www.goodmanmfg.com
Wire fan discharge grille Steel louver coil guard Baked-on powder paint finish Top and side maintenance access Single-panel access to controls with space provided for field-installed accessories • When properly anchored, meets 2010 Florida Building Code unit integrity requirements for hurricane-type winds (Anchor bracket kits available.)
* Complete warranty details available from your local dealer or at www.goodmanmfg.com. To receive the Lifetime Compressor Limited Warranty (good for as long as you own your home), 10-Year Unit Replacement Limited Warranty and 10-Year Parts Limited Warranty, online registration must be completed within 60 days of installation. Online registration is not required in California or Québec.
3/14 Supersedes 2/14
Product Specifications
Nomenclature D
S
X
C
16
036
1
A
A
1
2
3
4
5,6
7,8,9
10
11
12
Brand D Goodman® Brand
Engineering * Minor Revision
Product Category S Split System
Engineering * Major Revision
Unit Type C Condenser R-22 X Condenser R-410A H Heat Pump R-22 Z Heat Pump R-410A Communication Feature C ComfortNet 4-wire communications ready Efficiency 13 13 SEER 14 14 SEER
Electrical 208/230 V, 1 Phase, 60 Hz 220/240 V, 1 Phase, 50 Hz 208/230 V, 3 Phase, 60 Hz 460 V, 3 Phase, 60 Hz 380/415 V, 3 Phase, 50 Hz
1 2 3 4 5 018 024 030 036 042
16 16 SEER 18 18 SEER
1½ Tons 2 Tons 2½ Tons 3 Tons 3½ Tons
Nominal Capacity 048 4 Tons 060 5 Tons 090 7½ tons 120 10 Tons
* Neither used for order entry or inventory management.
2
www.goodmanmfg.com
SS-DSXC16
Product Specifications
Specifications DSXC16 0241AA/B
DSXC16 0241AC
DSXC16 0361AA/B
DSXC16 0361AC
DSXC16 0481B*
DSXC16 0601B*
24,000
24,000
36,000
36,000
48,000
60,000
71
71
70.4/70.9
70.4/70.9
74
75
RLA
10.3
11.7
16.7
15.3
21.2
28.8
LRA
52.0
58.0
82.0
83.0
104.0
152.9
Cooling Capacity Nominal Cooling (BTU/h) Decibels Compressor
Condenser Fan Motor Horsepower (RPM)
1/6
1/6
1/6
1/6
1/6
1/6
FLA
1.1
1.1
0.9
0.9
1.2
1.0
Liquid Line Size (“O.D.)
⅜"
⅜"
⅜"
⅜"
⅜"
⅜"
Suction Line Size (“O.D.)
¾"
¾"
⅞"
⅞"
1⅛"
1⅛"
⅜"
⅜"
⅜"
⅜"
⅜"
⅜"
Refrigeration System Refrigerant Line Size¹
Refrigerant Connection Size Liquid Valve Size (“O.D.) Suction Valve Size (“O.D.) Valve Connection Type Refrigerant Charge
¾"
¾"
¾"
¾"
⅞"
⅞"
Sweat
Sweat
Sweat
Sweat
Sweat
Sweat
97
97
107
107
132
197
208/230-60
208/230-60
208/230-60
208/230-60
208/230-60
208/230-60
14.0
15.7
21.8
20.0
27.7
37.2
20
20
35
35
45
60
Electrical Data Voltage-Hz Minimum Circuit Ampacity ² Max. Overcurrent Protection ³ Min / Max Volts
197/253
197/253
197/253
197/253
197/253
197/253
Power Supply
½" or ¾"
½" or ¾"
½" or ¾"
½" or ¾"
½" or ¾"
½" or ¾"
Eqipment Weight (lbs)
181
181
184
184
219
279
Ship Weight (lbs)
198
198
202
202
241
301
¹ Tested and rated in accordance with ARI Standard 210/240 ² Wire size should be determined in accordance with National Electrical Codes; extensive wire runs will require larger wire sizes ³ Must use time-delay fuses or HACR-type circuit breakers of the same size as noted. Notes • Always check the S&R plate for electrical data on the unit being installed. • Installer will need to supply ⅞” to 1⅛” adapters for suction line connections. • Unit is charged with refrigerant for 15’ of ⅜” liquid line. System charge must be adjusted per Installation Instructions Final Charge Procedure. • Installation of these units requires the specified TXV Kit to be installed on the indoor coil. THE SPECIFIED TXV IS DETERMINED BY THE OUTDOOR UNIT, NOT THE INDOOR COIL.
SS-DSXC16
www.goodmanmfg.com
3
4
www.goodmanmfg.com
18.3 0.85 21 1.10 4.5 228 122 17.8 0.81 22 1.09 4.4 226 120 16.4 0.78 22 1.08 4.4 223 119
MBh S/T ∆T kW Amps HI PR Lo PR MBh S/T ∆T kW Amps HI PR Lo PR MBh S/T ∆T kW Amps HI PR Lo PR
525
600
675
59 18.0 0.75 18 1.10 4.5 228 122 17.5 0.71 19 1.09 4.4 226 120 16.1 0.69 19 1.08 4.4 223 119
Airflow MBh S/T ∆T kW 675 Amps HI PR Lo PR MBh S/T ∆T kW 600 Amps HI PR Lo PR MBh S/T ∆T 525 kW Amps HI PR Lo PR
18.8 0.76 20 1.12 4.6 245 125 18.3 0.73 20 1.11 4.5 243 124 16.9 0.70 21 1.10 4.5 240 123
63 18.7 0.63 16 1.12 4.6 245 125 18.1 0.60 17 1.11 4.5 243 124 16.7 0.58 17 1.10 4.5 240 123 20.4 0.58 16 1.16 4.7 248 137 19.8 0.55 17 1.15 4.7 246 136 18.3 0.53 17 1.14 4.6 244 134
67 20.4 0.43 12 1.16 4.7 248 137 19.8 0.41 13 1.15 4.7 246 136 18.3 0.40 13 1.14 4.6 244 134 21.9 0.37 11 1.20 4.9 254 146 21.3 0.35 12 1.19 4.8 251 144 19.6 0.34 12 1.18 4.8 249 143
71 17.9 0.88 21 1.19 4.8 258 125 17.4 0.84 22 1.18 4.8 255 124 16.0 0.81 23 1.17 4.7 252 123
59 17.6 0.78 19 1.19 4.8 258 125 17.1 0.74 19 1.18 4.8 255 124 15.8 0.71 20 1.17 4.7 252 123 18.4 0.79 20 1.21 4.9 277 129 17.9 0.75 21 1.20 4.9 274 128 16.5 0.73 21 1.19 4.8 271 127
63 18.2 0.65 16 1.21 4.9 277 129 17.7 0.62 17 1.20 4.9 274 128 16.3 0.60 17 1.19 4.8 271 127 19.9 0.60 16 1.25 5.1 281 141 19.3 0.57 17 1.24 5.0 278 140 17.9 0.55 17 1.23 5.0 275 138
67 20.0 0.45 12 1.25 5.1 281 141 19.4 0.43 13 1.24 5.0 278 140 17.9 0.41 13 1.23 5.0 275 138
75ºF
IDB = Entering Indoor Dry Bulb Temperature High and low pressures are measured at the liquid and suction service valves.
75
70
IDB
65ºF
21.4 0.38 11 1.30 5.3 287 150 20.8 0.37 12 1.29 5.2 284 149 19.2 0.35 12 1.27 5.2 281 147
71 17.5 0.90 22 1.26 5.2 293 129 16.9 0.86 22 1.25 5.2 290 128 15.6 0.83 23 1.24 5.1 287 127
59 17.2 0.80 19 1.26 5.2 293 129 16.7 0.76 19 1.25 5.2 290 128 15.4 0.73 20 1.24 5.1 287 127 18.0 0.81 20 1.29 5.3 315 133 17.4 0.77 21 1.28 5.3 312 132 16.1 0.74 21 1.27 5.3 309 131
19.4 0.61 16 1.34 5.5 319 146 18.9 0.58 17 1.33 5.5 316 144 17.4 0.56 17 1.31 5.4 313 143
20.9 0.39 11 1.38 5.7 326 155 20.3 0.38 12 1.37 5.7 323 154 18.7 0.36 12 1.36 5.6 320 152
17.5 0.84 20 1.37 5.7 359 137 17.0 0.80 21 1.35 5.7 355 136 15.7 0.77 21 1.34 5.6 352 134
19.0 0.63 16 1.41 5.9 364 150 18.4 0.60 17 1.40 5.8 360 148 17.0 0.58 17 1.39 5.8 357 147
20.4 0.41 11 1.46 6.1 372 159 19.8 0.39 12 1.45 6.1 368 158 18.2 0.37 12 1.44 6.0 364 156
71 16.2 0.97 21 1.39 5.9 375 135 15.7 0.92 22 1.38 5.9 372 134 14.5 0.89 23 1.37 5.8 368 133
59 15.9 0.85 18 1.39 5.9 375 135 15.4 0.81 19 1.38 5.9 372 134 14.3 0.78 20 1.37 5.8 368 133
Shaded area reflects ACCA (TVA) conditions
17.0 0.93 22 1.33 5.6 334 133 16.5 0.89 23 1.32 5.5 330 132 15.3 0.86 23 1.31 5.5 327 130
Outdoor Ambient Temperature 85ºF 95ºF Entering Indoor Wet Bulb Temperature 63 67 71 59 63 67 17.8 19.5 16.7 17.4 19.0 0.66 0.46 0.82 0.69 0.48 16 12 19 16 12 1.29 1.34 1.33 1.37 1.41 5.3 5.5 5.6 5.7 5.9 315 319 334 359 364 133 146 133 137 150 17.3 18.9 16.3 16.8 18.5 0.63 0.44 0.78 0.65 0.45 17 13 20 17 13 1.28 1.33 1.32 1.35 1.40 5.3 5.5 5.5 5.7 5.8 312 316 330 355 360 132 144 132 136 148 15.9 17.5 15.0 15.6 17.0 0.61 0.42 0.76 0.63 0.44 17 13 20 17 13 1.27 1.31 1.31 1.34 1.39 5.3 5.4 5.5 5.6 5.8 309 313 327 352 357 131 143 130 134 147 16.7 0.87 20 1.43 6.1 404 140 16.2 0.83 20 1.41 6.0 400 138 14.9 0.80 21 1.40 6.0 396 137
63 16.5 0.71 16 1.43 6.1 404 140 16.0 0.68 17 1.41 6.0 400 138 14.8 0.65 17 1.40 6.0 396 137 18.0 0.66 16 1.48 6.3 409 153 17.5 0.63 17 1.46 6.2 405 151 16.2 0.60 17 1.45 6.2 401 150
67 18.1 0.49 12 1.48 6.3 409 153 17.5 0.47 13 1.46 6.2 405 151 16.2 0.45 13 1.45 6.2 401 150
105ºF
15.0 0.98 20 1.44 6.3 420 139 14.5 0.93 21 1.43 6.2 416 137 13.4 0.90 21 1.42 6.2 412 136
59 14.7 0.86 17 1.44 6.3 420 139 14.3 0.82 18 1.43 6.2 416 137 13.2 0.79 18 1.42 6.2 412 136 15.4 0.87 18 1.48 6.4 452 143 15.0 0.83 19 1.47 6.4 447 142 13.8 0.80 19 1.45 6.3 443 140
63 15.3 0.72 15 1.48 6.4 452 143 14.8 0.68 16 1.47 6.4 447 142 13.7 0.66 16 1.45 6.3 443 140 16.7 0.66 15 1.53 6.6 458 156 16.2 0.63 16 1.52 6.6 454 155 15.0 0.61 16 1.50 6.5 449 153
67 16.7 0.50 11 1.53 6.6 458 156 16.2 0.47 12 1.52 6.6 454 155 15.0 0.46 12 1.50 6.5 449 153 17.9 0.43 10 1.58 6.9 468 166 17.4 0.41 11 1.57 6.8 464 165 16.1 0.39 11 1.56 6.8 459 163
71 -
kW = Total system power Amps = outdoor unit amps (comp.+fan)
19.3 0.42 11 1.53 6.5 418 162 18.8 0.40 12 1.51 6.4 414 161 17.3 0.39 12 1.50 6.4 410 159
71 -
115ºF
Product Specifications
Expanded Cooling Data — DSXC160241**/ CA*F3636C6C*+TXV/ MBVC1200** Low Stage
SS-DSXC16
SS-DSXC16
www.goodmanmfg.com
19.0 0.98 25 1.10 4.5 228 122 18.4 0.93 26 1.09 4.4 226 120 17.0 0.90 26.8 1.08 4.4 223 119
MBh S/T ∆T kW Amps HI PR Lo PR MBh S/T ∆T kW Amps HI PR Lo PR MBh S/T ∆T kW Amps HI PR Lo PR
525
600
675
59 18.6 0.93 24 1.10 4.5 228 122 18.1 0.89 25 1.09 4.4 226 120 16.7 0.86 25 1.08 4.4 223 119
Airflow MBh S/T ∆T kW 675 Amps HI PR Lo PR MBh S/T ∆T kW 600 Amps HI PR Lo PR MBh S/T ∆T 525 kW Amps HI PR Lo PR
19.3 0.94 25 1.12 4.6 245 125 18.8 0.90 26 1.11 4.5 243 124 17.3 0.87 26 1.10 4.5 240 123
63 19.0 0.88 23 1.12 4.6 245 125 18.5 0.84 24 1.11 4.5 243 124 17.1 0.81 24 1.10 4.5 240 123 20.2 0.85 23 1.16 4.7 248 137 19.6 0.81 24 1.15 4.7 246 136 18.1 0.78 25 1.14 4.6 244 134
67 20.3 0.71 20 1.16 4.7 248 137 19.7 0.68 21 1.15 4.7 246 136 18.2 0.66 21 1.14 4.6 244 134 21.6 0.69 20 1.20 4.9 254 146 21.0 0.66 21 1.19 4.8 251 144 19.3 0.64 22 1.18 4.8 249 143
71 21.7 0.53 16 1.20 4.9 254 146 21.1 0.51 16 1.19 4.8 251 144 19.5 0.49 17 1.18 4.8 249 143 18.5 1.00 25 1.19 4.8 258 125 18.0 0.97 27 1.18 4.8 255 124 16.6 0.93 27 1.17 4.7 252 123
59 18.2 0.97 24 1.19 4.8 258 125 17.7 0.92 25 1.18 4.8 255 124 16.3 0.89 25 1.17 4.7 252 123 18.9 0.98 25 1.21 4.9 277 129 18.3 0.93 26 1.20 4.9 274 128 16.9 0.90 27 1.19 4.8 271 127
63 18.6 0.91 23 1.21 4.9 277 129 18.1 0.87 24 1.20 4.9 274 128 16.7 0.83 24 1.19 4.8 271 127 19.8 0.88 24 1.25 5.1 281 141 19.2 0.84 25 1.24 5.0 278 140 17.7 0.81 25 1.23 5.0 275 138
67 19.9 0.74 20 1.25 5.1 281 141 19.3 0.70 21 1.24 5.0 278 140 17.8 0.68 21 1.23 5.0 275 138
75ºF
IDB = Entering Indoor Dry Bulb Temperature High and low pressures are measured at the liquid and suction service valves.
85
80
IDB
65ºF
21.1 0.72 21 1.30 5.3 287 150 20.5 0.68 21 1.29 5.2 284 149 18.9 0.66 22 1.27 5.2 281 147
71 21.2 0.55 16 1.30 5.3 287 150 20.6 0.53 17 1.29 5.2 284 149 19.0 0.51 17 1.27 5.2 281 147 18.1 1.00 25 1.26 5.2 293 129 17.5 0.99 27 1.25 5.2 290 128 16.2 0.96 27 1.24 5.1 287 127
59 17.8 1.00 24 1.26 5.2 293 129 17.2 0.95 25 1.25 5.2 290 128 15.9 0.91 25 1.24 5.1 287 127 18.4 1.00 25 1.29 5.3 315 133 17.9 0.96 26 1.28 5.3 312 132 16.5 0.92 27 1.27 5.3 309 131
19.3 0.91 24 1.34 5.5 319 146 18.7 0.86 25 1.33 5.5 316 144 17.3 0.83 25 1.31 5.4 313 143
20.6 0.73 21 1.38 5.7 326 155 20.0 0.70 21 1.37 5.7 323 154 18.4 0.68 22 1.36 5.6 320 152
18.0 1.00 24 1.37 5.7 359 137 17.4 0.99 26 1.35 5.7 355 136 16.1 0.95 27 1.34 5.6 352 134
18.8 0.93 24 1.41 5.9 364 150 18.3 0.89 25 1.40 5.8 360 148 16.9 0.86 25 1.39 5.8 357 147
20.1 0.76 21 1.46 6.1 372 159 19.5 0.72 22 1.45 6.1 368 158 18.0 0.70 22 1.44 6.0 364 156
71 20.2 0.58 16 1.46 6.1 372 159 19.6 0.56 17 1.45 6.1 368 158 18.1 0.54 17 1.44 6.0 364 156 16.8 1.00 23 1.39 5.9 375 135 16.3 1.00 25 1.38 5.9 372 134 15.0 1.00 26 1.37 5.8 368 133
59 16.5 1.00 22 1.39 5.9 375 135 16.0 1.00 24 1.38 5.9 372 134 14.8 0.98 25 1.37 5.8 368 133
Shaded area reflects AHRI (TVA) conditions
17.6 1.00 24 1.33 5.6 334 133 17.1 1.00 26 1.32 5.5 330 132 15.8 0.99 27 1.31 5.5 327 130
Outdoor Ambient Temperature 85ºF 95ºF Entering Indoor Wet Bulb Temperature 63 67 71 59 63 67 18.1 19.4 20.7 17.3 17.7 18.9 0.93 0.76 0.57 1.00 0.96 0.78 23 20 16 24 23 20 1.29 1.34 1.38 1.33 1.37 1.41 5.3 5.5 5.7 5.6 5.7 5.9 315 319 326 334 359 364 133 146 155 133 137 150 17.6 18.8 20.1 16.8 17.2 18.4 0.89 0.72 0.54 0.98 0.92 0.75 24 21 17 25 24 21 1.28 1.33 1.37 1.32 1.35 1.40 5.3 5.5 5.7 5.5 5.7 5.8 312 316 323 330 355 360 132 144 154 132 136 148 16.3 17.4 18.6 15.5 15.9 17.0 0.86 0.70 0.52 0.94 0.88 0.72 24 21 17 26 25 21 1.27 1.31 1.36 1.31 1.34 1.39 5.3 5.4 5.6 5.5 5.6 5.8 309 313 320 327 352 357 131 143 152 130 134 147 17.1 1.00 23 1.43 6.1 404 140 16.6 1.00 25 1.41 6.0 400 138 15.3 0.99 26 1.40 6.0 396 137
63 16.8 1.00 23 1.43 6.1 404 140 16.3 0.95 24 1.41 6.0 400 138 15.1 0.92 24 1.40 6.0 396 137 17.9 0.97 24 1.48 6.3 409 153 17.4 0.93 25 1.46 6.2 405 151 16.0 0.89 25 1.45 6.2 401 150
67 18.0 0.81 20 1.48 6.3 409 153 17.4 0.77 21 1.46 6.2 405 151 16.1 0.75 21 1.45 6.2 401 150
105ºF
15.5 1.00 21 1.44 6.3 420 139 15.1 1.00 23 1.43 6.2 416 137 13.9 1.00 24 1.42 6.2 412 136
59 15.2 1.00 21 1.44 6.3 420 139 14.8 1.00 23 1.43 6.2 416 137 13.7 0.99 24 1.42 6.2 412 136 15.8 1.00 22 1.48 6.4 452 143 15.4 1.00 24 1.47 6.4 447 142 14.2 1.00 25 1.45 6.3 443 140
63 15.6 1.00 21 1.48 6.4 452 143 15.1 0.96 22 1.47 6.4 447 142 14.0 0.92 23 1.45 6.3 443 140 16.6 0.98 22 1.53 6.6 458 156 16.1 0.93 23 1.52 6.6 454 155 14.8 0.90 23 1.50 6.5 449 153
67 16.6 0.82 19 1.53 6.6 458 156 16.2 0.78 19 1.52 6.6 454 155 14.9 0.75 20 1.50 6.5 449 153 17.7 0.79 19 1.58 6.9 468 166 17.2 0.76 20 1.57 6.8 464 165 15.8 0.73 20 1.56 6.8 459 163
71 17.8 0.61 15 1.58 6.9 468 166 17.3 0.58 15 1.57 6.8 464 165 15.9 0.56 16 1.56 6.8 459 163
kW = Total system power Amps = outdoor unit amps (comp.+fan)
19.1 0.79 20 1.53 6.5 418 162 18.5 0.75 21 1.51 6.4 414 161 17.1 0.72 22 1.50 6.4 410 159
71 19.2 0.61 16 1.53 6.5 418 162 18.7 0.58 17 1.51 6.4 414 161 17.2 0.56 17 1.50 6.4 410 159
115ºF
Product Specifications
Expanded Cooling Data — DSXC160241**/ CA*F3636C6C*+TXV/ MBVC1200** Low Stage (cont.)
5
6
www.goodmanmfg.com
23.9 0.86 21 1.50 5.9 237 122 23.2 0.82 22 1.49 5.9 234 120 21.4 0.79 22 1.48 5.8 232 119
MBh S/T ∆T kW Amps HI PR Lo PR MBh S/T ∆T kW Amps HI PR Lo PR MBh S/T ∆T kW Amps HI PR Lo PR
700
800
900
59 23.5 0.76 18 1.50 5.9 237 122 22.8 0.72 19 1.49 5.9 234 120 21.1 0.70 19 1.48 5.8 232 119
Airflow MBh S/T ∆T kW 900 Amps HI PR Lo PR MBh S/T ∆T kW 800 Amps HI PR Lo PR MBh S/T ∆T 700 kW Amps HI PR Lo PR
24.6 0.77 19 1.53 6.0 255 125 23.9 0.73 20 1.52 6.0 252 124 22.1 0.71 21 1.51 5.9 249 123
63 24.4 0.63 16 1.53 6.0 255 125 23.7 0.60 16 1.52 6.0 252 124 21.8 0.58 17 1.51 5.9 249 123 26.7 0.58 16 1.58 6.2 258 137 25.9 0.56 17 1.57 6.2 256 136 23.9 0.54 17 1.56 6.1 253 134
67 26.7 0.44 12 1.58 6.2 258 137 25.9 0.42 12 1.57 6.2 256 136 23.9 0.40 13 1.56 6.1 253 134 28.6 0.37 11 1.63 6.5 264 146 27.8 0.36 11 1.62 6.4 261 144 25.6 0.34 12 1.61 6.3 259 143
71 23.4 0.89 21 1.62 6.4 268 125 22.7 0.85 22 1.61 6.3 265 124 20.9 0.82 23 1.59 6.3 262 123
59 23.0 0.78 18 1.62 6.4 268 125 22.3 0.75 19 1.61 6.3 265 124 20.6 0.72 20 1.59 6.3 262 123 24.1 0.80 20 1.65 6.5 288 129 23.4 0.76 20 1.64 6.5 285 128 21.6 0.73 21 1.63 6.4 282 127
63 23.8 0.66 16 1.65 6.5 288 129 23.1 0.63 17 1.64 6.5 285 128 21.3 0.60 17 1.63 6.4 282 127 26.0 0.60 16 1.71 6.7 292 141 25.3 0.58 17 1.69 6.7 289 140 23.3 0.56 17 1.68 6.6 286 138
67 26.1 0.45 12 1.71 6.7 292 141 25.3 0.43 13 1.69 6.7 289 140 23.4 0.42 13 1.68 6.6 286 138
75ºF
IDB = Entering Indoor Dry Bulb Temperature High and low pressures are measured at the liquid and suction service valves.
75
70
IDB
65ºF
27.9 0.39 11 1.77 7.0 298 150 27.1 0.37 12 1.75 6.9 295 149 25.0 0.36 12 1.74 6.8 292 147
71 22.8 0.91 21 1.72 6.9 304 129 22.1 0.87 22 1.71 6.8 301 128 20.4 0.84 23 1.69 6.8 298 127
59 22.4 0.80 18 1.72 6.9 304 129 21.8 0.77 19 1.71 6.8 301 128 20.1 0.74 20 1.69 6.8 298 127 23.5 0.82 20 1.76 7.1 327 134 22.8 0.78 20 1.75 7.0 324 132 21.0 0.75 21 1.73 6.9 321 131
25.4 0.62 16 1.82 7.3 332 146 24.7 0.59 17 1.80 7.2 329 144 22.8 0.57 17 1.79 7.2 325 143
27.3 0.40 11 1.88 7.6 339 155 26.5 0.38 12 1.87 7.5 336 154 24.4 0.37 12 1.85 7.4 332 152
22.9 0.84 20 1.86 7.5 373 137 22.2 0.81 21 1.84 7.5 369 136 20.5 0.78 21 1.82 7.4 365 134
24.8 0.64 16 1.92 7.8 378 150 24.1 0.61 17 1.90 7.7 374 148 22.2 0.59 17 1.89 7.6 370 147
26.6 0.41 11 1.98 8.1 386 159 25.8 0.39 12 1.97 8.0 382 158 23.8 0.38 12 1.95 7.9 379 156
71 21.1 0.98 21 1.89 7.8 390 136 20.5 0.93 22 1.88 7.8 386 134 18.9 0.90 22 1.86 7.7 382 133
59 20.8 0.86 18 1.89 7.8 390 136 20.2 0.82 19 1.88 7.8 386 134 18.6 0.79 19 1.86 7.7 382 133
Shaded area reflects ACCA (TVA) conditions
22.2 0.94 21 1.81 7.4 347 133 21.6 0.90 22 1.80 7.3 343 132 19.9 0.87 23 1.78 7.2 340 130
Outdoor Ambient Temperature 85ºF 95ºF Entering Indoor Wet Bulb Temperature 63 67 71 59 63 67 23.2 25.5 21.9 22.7 24.8 0.67 0.47 0.83 0.69 0.48 16 12 19 16 12 1.76 1.82 1.81 1.86 1.92 7.1 7.3 7.4 7.5 7.8 327 332 347 373 378 134 146 133 137 150 22.6 24.7 21.2 22.0 24.1 0.64 0.44 0.79 0.66 0.46 17 13 19 17 13 1.75 1.80 1.80 1.84 1.90 7.0 7.2 7.3 7.5 7.7 324 329 343 369 374 132 144 132 136 148 20.8 22.8 19.6 20.3 22.3 0.62 0.43 0.76 0.64 0.44 17 13 20 17 13 1.73 1.79 1.78 1.82 1.89 6.9 7.2 7.2 7.4 7.6 321 325 340 365 370 131 143 130 134 147 21.8 0.88 19 1.94 8.0 419 140 21.1 0.84 20 1.92 7.9 415 138 19.5 0.81 21 1.90 7.9 411 137
63 21.5 0.72 16 1.94 8.0 419 140 20.9 0.69 17 1.92 7.9 415 138 19.3 0.66 17 1.90 7.9 411 137 23.6 0.66 16 2.00 8.3 425 153 22.9 0.63 17 1.98 8.2 421 151 21.1 0.61 17 1.97 8.1 417 150
67 23.6 0.50 12 2.00 8.3 425 153 22.9 0.48 13 1.98 8.2 421 151 21.1 0.46 13 1.97 8.1 417 150
105ºF
19.6 0.99 20 1.96 8.3 437 139 19.0 0.94 21 1.94 8.2 432 138 17.5 0.91 21 1.93 8.1 428 136
59 19.3 0.87 17 1.96 8.3 437 139 18.7 0.83 18 1.94 8.2 432 138 17.3 0.80 18 1.93 8.1 428 136 20.2 0.88 18 2.01 8.5 470 143 19.6 0.84 19 1.99 8.4 465 142 18.1 0.81 19 1.97 8.3 460 140
63 20.0 0.73 15 2.01 8.5 470 143 19.4 0.69 15 1.99 8.4 465 142 17.9 0.67 16 1.97 8.3 460 140 21.8 0.67 15 2.07 8.7 476 156 21.2 0.64 16 2.06 8.7 471 155 19.6 0.62 16 2.04 8.6 467 153
67 21.9 0.50 11 2.07 8.7 476 156 21.2 0.48 12 2.06 8.7 471 155 19.6 0.46 12 2.04 8.6 467 153 23.4 0.43 10 2.15 9.1 487 167 22.7 0.41 11 2.13 9.0 482 165 21.0 0.40 11 2.11 8.9 477 163
71 -
kW = Total system power Amps = outdoor unit amps (comp.+fan)
25.3 0.43 11 2.07 8.6 435 163 24.5 0.41 11 2.05 8.5 430 161 22.7 0.39 12 2.04 8.4 426 159
71 -
115ºF
Product Specifications
Expanded Cooling Data — DSXC160241**/ CA*F3636C6C*+TXV/ MBVC1200** High Stage
SS-DSXC16
SS-DSXC16
www.goodmanmfg.com
24.8 0.99 25 1.50 5.9 237 122 24.0 0.94 26 1.49 5.9 234 120 22.2 0.91 26.5 1.48 5.8 232 119
MBh S/T ∆T kW Amps HI PR Lo PR MBh S/T ∆T kW Amps HI PR Lo PR MBh S/T ∆T kW Amps HI PR Lo PR
700
800
900
59 24.3 0.94 23 1.50 5.9 237 122 23.6 0.90 24 1.49 5.9 234 120 21.8 0.87 25 1.48 5.8 232 119
Airflow MBh S/T ∆T kW 900 Amps HI PR Lo PR MBh S/T ∆T kW 800 Amps HI PR Lo PR MBh S/T ∆T 700 kW Amps HI PR Lo PR
25.2 0.96 25 1.53 6.0 255 125 24.5 0.91 26 1.52 6.0 252 124 22.6 0.88 26 1.51 5.9 249 123
63 24.9 0.89 22 1.53 6.0 255 125 24.1 0.84 23 1.52 6.0 252 124 22.3 0.81 24 1.51 5.9 249 123 26.4 0.86 23 1.58 6.2 258 137 25.7 0.82 24 1.57 6.2 256 136 23.7 0.79 25 1.56 6.1 253 134
67 26.6 0.72 20 1.58 6.2 258 137 25.8 0.69 20 1.57 6.2 256 136 23.8 0.66 21 1.56 6.1 253 134 28.2 0.70 20 1.63 6.5 264 146 27.4 0.67 21 1.62 6.4 261 144 25.3 0.64 21 1.61 6.3 259 143
71 28.4 0.54 16 1.63 6.5 264 146 27.6 0.51 16 1.62 6.4 261 144 25.5 0.50 17 1.61 6.3 259 143 24.2 1.00 25 1.62 6.4 268 125 23.5 0.98 26 1.61 6.3 265 124 21.7 0.94 27 1.59 6.3 262 123
59 23.8 1.00 24 1.62 6.4 268 125 23.1 0.93 25 1.61 6.3 265 124 21.3 0.90 25 1.59 6.3 262 123 24.7 0.99 25 1.65 6.5 288 129 23.9 0.94 26 1.64 6.5 285 128 22.1 0.91 26 1.63 6.4 282 127
63 24.3 0.92 23 1.65 6.5 288 129 23.6 0.88 24 1.64 6.5 285 128 21.8 0.84 24 1.63 6.4 282 127 25.8 0.89 24 1.71 6.7 292 141 25.1 0.85 25 1.69 6.7 289 140 23.1 0.82 25 1.68 6.6 286 138
67 26.0 0.75 20 1.71 6.7 292 141 25.2 0.71 21 1.69 6.7 289 140 23.3 0.69 21 1.68 6.6 286 138
75ºF
IDB = Entering Indoor Dry Bulb Temperature High and low pressures are measured at the liquid and suction service valves.
85
80
IDB
65ºF
27.6 0.72 20 1.77 7.0 298 150 26.8 0.69 21 1.75 6.9 295 149 24.7 0.67 22 1.74 6.8 292 147
71 27.7 0.56 16 1.77 7.0 298 150 26.9 0.53 16 1.75 6.9 295 149 24.9 0.51 17 1.74 6.8 292 147 23.6 1.00 24 1.72 6.9 304 129 22.9 1.00 26 1.71 6.8 301 128 21.2 0.97 27 1.69 6.8 298 127
59 23.2 1.00 24 1.72 6.9 304 129 22.5 0.96 25 1.71 6.8 301 128 20.8 0.92 25 1.69 6.8 298 127 24.1 1.00 25 1.76 7.1 327 134 23.4 0.97 26 1.75 7.0 324 132 21.6 0.93 26 1.73 6.9 321 131
25.2 0.92 24 1.82 7.3 332 146 24.5 0.87 25 1.80 7.2 329 144 22.6 0.84 25 1.79 7.2 325 143
26.9 0.74 20 1.88 7.6 339 155 26.1 0.71 21 1.87 7.5 336 154 24.1 0.68 22 1.85 7.4 332 152
23.5 1.00 24 1.86 7.5 373 137 22.8 1.00 26 1.84 7.5 369 136 21.0 0.96 27 1.82 7.4 365 134
24.6 0.95 24 1.92 7.8 378 150 23.9 0.90 25 1.90 7.7 374 148 22.0 0.87 25 1.89 7.6 370 147
26.2 0.77 21 1.98 8.1 386 159 25.5 0.73 21 1.97 8.0 382 158 23.5 0.71 22 1.95 7.9 379 156
71 26.4 0.59 16 1.98 8.1 386 159 25.7 0.56 17 1.97 8.0 382 158 23.7 0.54 17 1.95 7.9 379 156 21.9 1.00 22 1.89 7.8 390 136 21.2 1.00 24 1.88 7.8 386 134 19.6 1.00 26 1.86 7.7 382 133
59 21.5 1.00 22 1.89 7.8 390 136 20.9 1.00 24 1.88 7.8 386 134 19.3 0.99 25 1.86 7.7 382 133
Shaded area reflects AHRI (TVA) conditions
23.0 1.00 24 1.81 7.4 347 133 22.4 1.00 26 1.80 7.3 343 132 20.6 1.00 27 1.78 7.2 340 130
Outdoor Ambient Temperature 85ºF 95ºF Entering Indoor Wet Bulb Temperature 63 67 71 59 63 67 23.7 25.3 27.1 22.6 23.1 24.7 0.94 0.77 0.57 1.00 1.00 0.79 23 20 16 23 24 20 1.76 1.82 1.88 1.81 1.86 1.92 7.1 7.3 7.6 7.4 7.5 7.8 327 332 339 347 373 378 134 146 155 133 137 150 23.0 24.6 26.3 22.0 22.5 24.0 0.90 0.73 0.55 0.99 0.93 0.75 24 21 16 25 24 21 1.75 1.80 1.87 1.80 1.84 1.90 7.0 7.2 7.5 7.3 7.5 7.7 324 329 336 343 369 374 132 144 154 132 136 148 21.3 22.7 24.3 20.3 20.7 22.2 0.87 0.70 0.53 0.95 0.89 0.73 24 21 17 25 24 21 1.73 1.79 1.85 1.78 1.82 1.89 6.9 7.2 7.4 7.2 7.4 7.6 321 325 332 340 365 370 131 143 152 130 134 147 22.3 1.00 23 1.94 8.0 419 140 21.7 1.00 25 1.92 7.9 415 138 20.0 1.00 26 1.90 7.9 411 137
63 22.0 1.00 22 1.94 8.0 419 140 21.3 0.96 24 1.92 7.9 415 138 19.7 0.93 24 1.90 7.9 411 137 23.4 0.98 23 2.00 8.3 425 153 22.7 0.94 24 1.98 8.2 421 151 20.9 0.90 25 1.97 8.1 417 150
67 23.5 0.82 20 2.00 8.3 425 153 22.8 0.78 21 1.98 8.2 421 151 21.0 0.75 21 1.97 8.1 417 150
105ºF
20.3 1.00 21 1.96 8.3 437 139 19.7 1.00 23 1.94 8.2 432 138 18.2 1.00 24 1.93 8.1 428 136
59 19.9 1.00 20 1.96 8.3 437 139 19.3 1.00 22 1.94 8.2 432 138 17.9 1.00 23 1.93 8.1 428 136 20.7 1.00 21 2.01 8.5 470 143 20.1 1.00 23 1.99 8.4 465 142 18.5 1.00 24 1.97 8.3 460 140
63 20.4 1.00 21 2.01 8.5 470 143 19.8 0.97 22 1.99 8.4 465 142 18.2 0.93 22 1.97 8.3 460 140 21.6 0.99 22 2.07 8.7 476 156 21.0 0.94 23 2.06 8.7 471 155 19.4 0.91 23 2.04 8.6 467 153
67 21.8 0.83 18 2.07 8.7 476 156 21.1 0.79 19 2.06 8.7 471 155 19.5 0.76 19 2.04 8.6 467 153 23.1 0.80 19 2.15 9.1 487 167 22.4 0.77 20 2.13 9.0 482 165 20.7 0.74 20 2.11 8.9 477 163
71 23.3 0.62 15 2.15 9.1 487 167 22.6 0.59 15 2.13 9.0 482 165 20.8 0.57 16 2.11 8.9 477 163
kW = Total system power Amps = outdoor unit amps (comp.+fan)
24.9 0.80 20 2.07 8.6 435 163 24.2 0.76 21 2.05 8.5 430 161 22.3 0.73 21 2.04 8.4 426 159
71 25.1 0.61 16 2.07 8.6 435 163 24.4 0.58 16 2.05 8.5 430 161 22.5 0.56 17 2.04 8.4 426 159
115ºF
Product Specifications
Expanded Cooling Data — DSXC160241**/ CA*F3636C6C*+TXV/ MBVC1200** High Stage (cont.)
7
8
www.goodmanmfg.com
25.3 0.81 21 1.50 5.8 220 119 24.6 0.78 22 1.49 5.8 218 118 22.7 0.75 22 1.47 5.7 216 117
MBh S/T ∆T kW Amps HI PR Lo PR MBh S/T ∆T kW Amps HI PR Lo PR MBh S/T ∆T kW Amps HI PR Lo PR
696
800
904
59 24.9 0.72 18 1.50 5.8 220 119 24.2 0.68 19 1.49 5.8 218 118 22.3 0.66 19 1.47 5.7 216 117
Airflow MBh S/T ∆T kW 904 Amps HI PR Lo PR MBh S/T ∆T kW 800 Amps HI PR Lo PR MBh S/T ∆T 696 kW Amps HI PR Lo PR
26.1 0.73 19 1.53 6.0 237 123 25.3 0.69 20 1.52 5.9 234 122 23.4 0.67 21 1.51 5.9 232 121
63 25.8 0.60 16 1.53 6.0 237 123 25.1 0.57 16 1.52 5.9 234 122 23.1 0.55 17 1.51 5.9 232 121 28.2 0.55 16 1.58 6.2 240 134 27.4 0.53 17 1.57 6.1 238 133 25.3 0.51 17 1.55 6.0 235 132
67 28.3 0.41 12 1.58 6.2 240 134 27.5 0.40 12 1.57 6.1 238 133 25.3 0.38 13 1.55 6.0 235 132 30.3 0.35 11 1.63 6.4 245 143 29.4 0.34 11 1.62 6.3 243 142 27.2 0.33 12 1.60 6.3 241 140
71 24.7 0.84 21 1.61 6.3 249 123 24.0 0.80 22 1.60 6.2 246 122 22.2 0.78 23 1.59 6.2 244 120
59 24.3 0.74 18 1.61 6.3 249 123 23.6 0.71 19 1.60 6.2 246 122 21.8 0.68 20 1.59 6.2 244 120 25.5 0.75 20 1.65 6.4 268 127 24.7 0.72 20 1.64 6.4 265 125 22.8 0.69 21 1.62 6.3 262 124
63 25.2 0.62 16 1.65 6.4 268 127 24.5 0.59 17 1.64 6.4 265 125 22.6 0.57 17 1.62 6.3 262 124 27.6 0.57 16 1.70 6.6 271 138 26.8 0.54 17 1.69 6.6 269 137 24.7 0.53 17 1.67 6.5 266 136
67 27.6 0.43 12 1.70 6.6 271 138 26.8 0.41 13 1.69 6.6 269 137 24.8 0.39 13 1.67 6.5 266 136
75ºF
IDB = Entering Indoor Dry Bulb Temperature High and low pressures are measured at the liquid and suction service valves.
75
70
IDB
65ºF
29.6 0.37 11 1.76 6.9 277 147 28.7 0.35 12 1.74 6.8 275 146 26.5 0.34 12 1.73 6.8 272 144
71 24.2 0.87 21 1.72 6.8 283 127 23.5 0.83 22 1.70 6.7 280 126 21.6 0.80 23 1.69 6.7 277 125
59 23.8 0.76 18 1.72 6.8 283 127 23.1 0.73 19 1.70 6.7 280 126 21.3 0.70 20 1.69 6.7 277 125 24.9 0.77 20 1.75 7.0 304 131 24.1 0.74 20 1.74 6.9 301 130 22.3 0.71 21 1.73 6.8 298 128
26.9 0.59 16 1.81 7.2 309 143 26.1 0.56 17 1.80 7.1 306 142 24.1 0.54 17 1.78 7.1 303 140
28.9 0.38 11 1.87 7.4 315 152 28.0 0.36 12 1.86 7.4 312 151 25.9 0.35 12 1.84 7.3 309 149
24.3 0.80 20 1.85 7.4 347 135 23.6 0.76 21 1.83 7.4 343 133 21.7 0.73 21 1.82 7.3 340 132
26.3 0.60 16 1.91 7.7 352 147 25.5 0.58 17 1.89 7.6 348 145 23.5 0.56 17 1.88 7.5 345 144
28.2 0.39 11 1.97 7.9 359 156 27.4 0.37 12 1.96 7.9 356 155 25.3 0.36 12 1.94 7.8 352 153
71 22.4 0.93 21 1.88 7.7 348 133 21.7 0.88 22 1.87 7.6 345 132 20.1 0.85 23 1.85 7.6 341 130
59 22.0 0.82 18 1.88 7.7 348 133 21.4 0.78 19 1.87 7.6 345 132 19.7 0.75 20 1.85 7.6 341 130
Shaded area reflects ACCA (TVA) conditions
23.6 0.89 21 1.81 7.3 322 130 22.9 0.85 22 1.79 7.2 319 129 21.1 0.82 23 1.78 7.1 316 128
Outdoor Ambient Temperature 85ºF 95ºF Entering Indoor Wet Bulb Temperature 63 67 71 59 63 67 24.6 27.0 23.2 24.0 26.3 0.64 0.44 0.79 0.66 0.45 16 12 19 16 12 1.75 1.81 1.81 1.85 1.91 7.0 7.2 7.3 7.4 7.7 304 309 322 347 352 131 143 130 135 147 23.9 26.2 22.5 23.3 25.5 0.61 0.42 0.75 0.63 0.43 17 13 19 17 13 1.74 1.80 1.79 1.83 1.89 6.9 7.1 7.2 7.4 7.6 301 306 319 343 348 130 142 129 133 145 22.1 24.2 20.8 21.5 23.6 0.58 0.40 0.72 0.60 0.42 17 13 20 17 13 1.73 1.78 1.78 1.82 1.88 6.8 7.1 7.1 7.3 7.5 298 303 316 340 345 128 140 128 132 144 23.0 0.83 19 1.93 7.9 374 137 22.4 0.79 20 1.91 7.8 371 136 20.7 0.76 21 1.89 7.8 367 134
63 22.8 0.68 16 1.93 7.9 374 137 22.2 0.65 17 1.91 7.8 371 136 20.4 0.63 17 1.89 7.8 367 134 24.9 0.63 16 1.99 8.1 380 150 24.2 0.60 17 1.97 8.1 376 148 22.4 0.58 17 1.96 8.0 372 147
67 25.0 0.47 12 1.99 8.1 380 150 24.3 0.45 13 1.97 8.1 376 148 22.4 0.43 13 1.96 8.0 372 147
105ºF
20.7 0.93 20 1.95 8.2 413 136 20.1 0.89 21 1.93 8.1 409 135 18.6 0.86 21 1.92 8.0 404 134
59 20.4 0.82 17 1.95 8.2 413 136 19.8 0.78 18 1.93 8.1 409 135 18.3 0.76 18 1.92 8.0 404 134 21.4 0.84 18 2.00 8.3 444 141 20.7 0.80 19 1.98 8.3 439 139 19.1 0.77 19 1.96 8.2 435 138
63 21.1 0.69 15 2.00 8.3 444 141 20.5 0.65 15 1.98 8.3 439 139 18.9 0.63 16 1.96 8.2 435 138 23.1 0.63 15 2.06 8.6 450 153 22.4 0.60 16 2.04 8.5 446 152 20.7 0.58 16 2.03 8.5 441 150
67 23.2 0.48 11 2.06 8.6 450 153 22.5 0.45 12 2.04 8.5 446 152 20.8 0.44 12 2.03 8.5 441 150 24.8 0.41 10 2.13 8.9 460 163 24.1 0.39 11 2.11 8.9 455 162 22.2 0.37 11 2.10 8.8 451 160
71 -
kW = Total system power Amps = outdoor unit amps (comp.+fan)
26.8 0.40 11 2.06 8.4 388 160 26.0 0.38 12 2.04 8.4 384 158 24.0 0.37 12 2.02 8.3 380 156
71 -
115ºF
Product Specifications
Expanded Cooling Data — DSXC160361** / CA*F3743*6A* +TXV / MBVC1600** Low Stage
SS-DSXC16
SS-DSXC16
www.goodmanmfg.com
26.2 0.94 25 1.50 5.8 220 119 25.5 0.89 26 1.49 5.8 218 118 23.5 0.86 26.7 1.47 5.7 216 117
MBh S/T ∆T kW Amps HI PR Lo PR MBh S/T ∆T kW Amps HI PR Lo PR MBh S/T ∆T kW Amps HI PR Lo PR
696
800
904
59 25.8 0.89 23 1.50 5.8 220 119 25.0 0.85 24 1.49 5.8 218 118 23.1 0.82 25 1.47 5.7 216 117
Airflow MBh S/T ∆T kW 904 Amps HI PR Lo PR MBh S/T ∆T kW 800 Amps HI PR Lo PR MBh S/T ∆T 696 kW Amps HI PR Lo PR
26.7 0.90 25 1.53 6.0 237 123 26.0 0.86 26 1.52 5.9 234 122 24.0 0.83 26 1.51 5.9 232 121
63 26.3 0.84 22 1.53 6.0 237 123 25.6 0.80 23 1.52 5.9 234 122 23.6 0.77 24 1.51 5.9 232 121 28.0 0.82 23 1.58 6.2 240 134 27.2 0.78 24 1.57 6.1 238 133 25.1 0.75 25 1.55 6.0 235 132
67 28.1 0.68 20 1.58 6.2 240 134 27.3 0.65 20 1.57 6.1 238 133 25.2 0.63 21 1.55 6.0 235 132 29.9 0.66 20 1.63 6.4 245 143 29.0 0.63 21 1.62 6.3 243 142 26.8 0.61 22 1.60 6.3 241 140
71 30.1 0.51 16 1.63 6.4 245 143 29.2 0.49 16 1.62 6.3 243 142 27.0 0.47 17 1.60 6.3 241 140 25.6 0.97 25 1.61 6.3 249 123 24.9 0.93 26 1.60 6.2 246 122 23.0 0.89 27 1.59 6.2 244 120
59 25.2 0.93 24 1.61 6.3 249 123 24.4 0.88 25 1.60 6.2 246 122 22.6 0.85 25 1.59 6.2 244 120 26.1 0.94 25 1.65 6.4 268 127 25.4 0.89 26 1.64 6.4 265 125 23.4 0.86 27 1.62 6.3 262 124
63 25.7 0.87 23 1.65 6.4 268 127 25.0 0.83 24 1.64 6.4 265 125 23.1 0.80 24 1.62 6.3 262 124 27.4 0.84 24 1.70 6.6 271 138 26.6 0.81 25 1.69 6.6 269 137 24.5 0.78 25 1.67 6.5 266 136
67 27.5 0.71 20 1.70 6.6 271 138 26.7 0.67 21 1.69 6.6 269 137 24.6 0.65 21 1.67 6.5 266 136
75ºF
IDB = Entering Indoor Dry Bulb Temperature High and low pressures are measured at the liquid and suction service valves.
85
80
IDB
65ºF
29.2 0.69 20 1.76 6.9 277 147 28.3 0.65 21 1.74 6.8 275 146 26.2 0.63 22 1.73 6.8 272 144
71 29.4 0.53 16 1.76 6.9 277 147 28.5 0.50 17 1.74 6.8 275 146 26.3 0.49 17 1.73 6.8 272 144 25.0 0.99 25 1.72 6.8 283 127 24.3 0.95 26 1.70 6.7 280 126 22.4 0.91 27 1.69 6.7 277 125
59 24.6 0.95 24 1.72 6.8 283 127 23.9 0.90 25 1.70 6.7 280 126 22.0 0.87 25 1.69 6.7 277 125 25.5 0.96 25 1.75 7.0 304 131 24.8 0.92 26 1.74 6.9 301 130 22.8 0.88 27 1.73 6.8 298 128
26.7 0.87 24 1.81 7.2 309 143 25.9 0.83 25 1.80 7.1 306 142 23.9 0.80 25 1.78 7.1 303 140
28.5 0.70 20 1.87 7.4 315 152 27.7 0.67 21 1.86 7.4 312 151 25.5 0.65 22 1.84 7.3 309 149
24.9 0.99 25 1.85 7.4 347 135 24.2 0.94 26 1.83 7.4 343 133 22.3 0.91 27 1.82 7.3 340 132
26.1 0.89 24 1.91 7.7 352 147 25.3 0.85 25 1.89 7.6 348 145 23.3 0.82 25 1.88 7.5 345 144
27.8 0.73 21 1.97 7.9 359 156 27.0 0.69 21 1.96 7.9 356 155 24.9 0.67 22 1.94 7.8 352 153
71 28.0 0.56 16 1.97 7.9 359 156 27.2 0.53 17 1.96 7.9 356 155 25.1 0.51 17 1.94 7.8 352 153 23.2 1.00 24 1.88 7.7 348 133 22.5 1.00 26 1.87 7.6 345 132 20.8 0.98 27 1.85 7.6 341 130
59 22.8 1.00 23 1.88 7.7 348 133 22.1 0.97 25 1.87 7.6 345 132 20.4 0.93 25 1.85 7.6 341 130
Shaded area reflects AHRI (TVA) conditions
24.4 1.00 25 1.81 7.3 322 130 23.7 0.98 27 1.79 7.2 319 129 21.9 0.94 27 1.78 7.1 316 128
Outdoor Ambient Temperature 85ºF 95ºF Entering Indoor Wet Bulb Temperature 63 67 71 59 63 67 25.1 26.8 28.7 24.0 24.5 26.2 0.89 0.72 0.54 1.00 0.92 0.75 23 20 16 24 23 20 1.75 1.81 1.87 1.81 1.85 1.91 7.0 7.2 7.4 7.3 7.4 7.7 304 309 315 322 347 352 131 143 152 130 135 147 24.4 26.1 27.9 23.3 23.8 25.4 0.85 0.69 0.52 0.93 0.88 0.71 24 21 17 25 24 21 1.74 1.80 1.86 1.79 1.83 1.89 6.9 7.1 7.4 7.2 7.4 7.6 301 306 312 319 343 348 130 142 151 129 133 145 22.5 24.1 25.7 21.5 22.0 23.5 0.82 0.67 0.50 0.90 0.84 0.69 24 21 17 26 25 21 1.73 1.78 1.84 1.78 1.82 1.88 6.8 7.1 7.3 7.1 7.3 7.5 298 303 309 316 340 345 128 140 149 128 132 144 23.6 1.00 24 1.93 7.9 374 137 22.9 0.98 26 1.91 7.8 371 136 21.2 0.95 26 1.89 7.8 367 134
63 23.3 0.95 23 1.93 7.9 374 137 22.6 0.91 24 1.91 7.8 371 136 20.9 0.88 24 1.89 7.8 367 134 24.8 0.93 23 1.99 8.1 380 150 24.0 0.89 24 1.97 8.1 376 148 22.2 0.85 25 1.96 8.0 372 147
67 24.9 0.78 20 1.99 8.1 380 150 24.1 0.74 21 1.97 8.1 376 148 22.3 0.71 21 1.96 8.0 372 147
105ºF
21.5 1.00 22 1.95 8.2 413 136 20.8 1.00 24 1.93 8.1 409 135 19.2 0.99 25 1.92 8.0 404 134
59 21.1 1.00 21 1.95 8.2 413 136 20.5 0.98 23 1.93 8.1 409 135 18.9 0.94 24 1.92 8.0 404 134 21.9 1.00 22 2.00 8.3 444 141 21.3 0.99 24 1.98 8.3 439 139 19.6 0.95 25 1.96 8.2 435 138
63 21.6 0.96 21 2.00 8.3 444 141 20.9 0.92 22 1.98 8.3 439 139 19.3 0.88 23 1.96 8.2 435 138 22.9 0.94 22 2.06 8.6 450 153 22.3 0.89 23 2.04 8.5 446 152 20.5 0.86 23 2.03 8.5 441 150
67 23.0 0.78 18 2.06 8.6 450 153 22.4 0.75 19 2.04 8.5 446 152 20.6 0.72 20 2.03 8.5 441 150 24.5 0.76 19 2.13 8.9 460 163 23.7 0.72 20 2.11 8.9 455 162 21.9 0.70 20 2.10 8.8 451 160
71 24.6 0.58 15 2.13 8.9 460 163 23.9 0.56 15 2.11 8.9 455 162 22.1 0.54 16 2.10 8.8 451 160
kW = Total system power Amps = outdoor unit amps (comp.+fan)
26.4 0.75 20 2.06 8.4 388 160 25.6 0.72 21 2.04 8.4 384 158 23.7 0.69 22 2.02 8.3 380 156
71 26.6 0.58 16 2.06 8.4 388 160 25.8 0.55 16 2.04 8.4 384 158 23.8 0.53 17 2.02 8.3 380 156
115ºF
Product Specifications
Expanded Cooling Data — DSXC160361** / CA*F3743*6A* +TXV / MBVC1600** Low Stage (cont.)
9
10
www.goodmanmfg.com
34.5 0.82 19 2.14 8.1 232 116 33.5 0.78 20 2.12 8.0 230 115 30.9 0.75 20 2.10 8.0 227 114
MBh S/T ∆T kW Amps HI PR Lo PR MBh S/T ∆T kW Amps HI PR Lo PR MBh S/T ∆T kW Amps HI PR Lo PR
1043
1200
1356
59 33.9 0.72 17 2.14 8.1 232 116 32.9 0.68 17 2.12 8.0 230 115 30.4 0.66 18 2.10 8.0 227 114
Airflow MBh S/T ∆T kW 1356 Amps HI PR Lo PR MBh S/T ∆T kW 1200 Amps HI PR Lo PR MBh S/T ∆T 1043 kW Amps HI PR Lo PR
35.5 0.73 18 2.18 8.3 249 120 34.5 0.70 18 2.17 8.2 247 119 31.8 0.67 19 2.15 8.2 244 117
63 35.1 0.60 14 2.18 8.3 249 120 34.1 0.57 15 2.17 8.2 247 119 31.5 0.55 15 2.15 8.2 244 117 38.4 0.55 14 2.25 8.6 253 131 37.3 0.53 15 2.24 8.5 250 129 34.4 0.51 15 2.22 8.4 248 128
67 38.5 0.42 11 2.25 8.6 253 131 37.4 0.40 11 2.24 8.5 250 129 34.5 0.38 12 2.22 8.4 248 128 41.2 0.36 10 2.33 8.9 259 139 40.0 0.34 10 2.31 8.8 256 138 37.0 0.33 11 2.29 8.7 253 136
71 33.7 0.85 19 2.31 8.8 262 119 32.7 0.81 20 2.29 8.7 260 118 30.2 0.78 21 2.27 8.6 257 117
59 33.1 0.74 17 2.31 8.8 262 119 32.2 0.71 17 2.29 8.7 260 118 29.7 0.68 18 2.27 8.6 257 117 34.7 0.76 18 2.36 9.0 282 123 33.7 0.72 19 2.34 8.9 279 122 31.1 0.70 19 2.32 8.8 276 121
63 34.3 0.62 14 2.36 9.0 282 123 33.3 0.59 15 2.34 8.9 279 122 30.8 0.57 15 2.32 8.8 276 121 37.5 0.57 15 2.43 9.3 286 135 36.4 0.55 15 2.41 9.2 283 133 33.6 0.53 16 2.39 9.1 280 132
67 37.6 0.43 11 2.43 9.3 286 135 36.5 0.41 11 2.41 9.2 283 133 33.7 0.40 12 2.39 9.1 280 132
75ºF
IDB = Entering Indoor Dry Bulb Temperature High and low pressures are measured at the liquid and suction service valves.
75
70
IDB
65ºF
40.3 0.37 10 2.51 9.6 292 143 39.1 0.35 11 2.49 9.5 289 142 36.1 0.34 11 2.47 9.4 286 140
71 32.9 0.87 19 2.45 9.5 298 124 31.9 0.83 20 2.43 9.4 295 122 29.5 0.80 21 2.41 9.3 292 121
59 32.3 0.76 17 2.45 9.5 298 124 31.4 0.73 18 2.43 9.4 295 122 29.0 0.70 18 2.41 9.3 292 121 33.8 0.78 18 2.51 9.7 321 127 32.9 0.74 19 2.49 9.6 317 126 30.3 0.71 19 2.47 9.6 314 125
36.6 0.59 15 2.59 10.0 325 139 35.6 0.56 15 2.57 10.0 322 138 32.8 0.54 16 2.55 9.9 319 136
39.3 0.38 10 2.68 10.4 332 148 38.2 0.36 11 2.66 10.3 329 147 35.2 0.35 11 2.63 10.2 326 145
33.0 0.80 18 2.64 10.4 365 131 32.1 0.76 19 2.62 10.3 362 130 29.6 0.74 19 2.60 10.2 358 128
35.7 0.61 15 2.73 10.7 370 143 34.7 0.58 15 2.71 10.6 367 141 32.0 0.56 16 2.68 10.5 363 140
38.4 0.39 10 2.82 11.1 379 152 37.2 0.37 11 2.80 11.0 375 151 34.4 0.36 11 2.78 10.9 371 149
71 30.5 0.93 19 2.69 10.8 367 129 29.6 0.89 20 2.67 10.7 363 128 27.3 0.85 21 2.65 10.6 360 127
59 30.0 0.82 17 2.69 10.8 367 129 29.1 0.78 17 2.67 10.7 363 128 26.9 0.75 18 2.65 10.6 360 127
Shaded area reflects ACCA (TVA) conditions
32.1 0.90 19 2.58 10.1 340 127 31.1 0.85 20 2.56 10.1 336 126 28.7 0.82 21 2.54 10.0 333 124
Outdoor Ambient Temperature 85ºF 95ºF Entering Indoor Wet Bulb Temperature 63 67 71 59 63 67 33.5 36.7 31.5 32.7 35.8 0.64 0.44 0.79 0.66 0.46 14 11 17 15 11 2.51 2.59 2.58 2.64 2.73 9.7 10.0 10.1 10.4 10.7 321 325 340 365 370 127 139 127 131 143 32.5 35.6 30.6 31.7 34.8 0.61 0.42 0.75 0.63 0.43 15 11 18 15 12 2.49 2.57 2.56 2.62 2.71 9.6 10.0 10.1 10.3 10.6 317 322 336 362 367 126 138 126 130 141 30.0 32.9 28.3 29.3 32.1 0.59 0.41 0.72 0.61 0.42 16 12 18 16 12 2.47 2.55 2.54 2.60 2.68 9.6 9.9 10.0 10.2 10.5 314 319 333 358 363 125 136 124 128 140 31.4 0.83 18 2.76 11.1 394 133 30.5 0.79 19 2.73 11.0 390 132 28.1 0.76 19 2.71 10.9 387 131
63 31.1 0.68 14 2.76 11.1 394 133 30.2 0.65 15 2.73 11.0 390 132 27.8 0.63 15 2.71 10.9 387 131 34.0 0.63 14 2.85 11.4 400 146 33.0 0.60 15 2.82 11.3 396 144 30.4 0.58 16 2.80 11.2 392 143
67 34.0 0.47 11 2.85 11.4 400 146 33.0 0.45 11 2.82 11.3 396 144 30.5 0.44 12 2.80 11.2 392 143
105ºF
28.2 0.94 18 2.79 11.4 435 133 27.4 0.89 19 2.77 11.3 430 131 25.3 0.86 19 2.74 11.2 426 130
59 27.8 0.82 16 2.79 11.4 435 133 26.9 0.79 16 2.77 11.3 430 131 24.9 0.76 17 2.74 11.2 426 130 29.1 0.84 17 2.85 11.7 467 137 28.2 0.80 17 2.83 11.6 463 135 26.0 0.77 18 2.81 11.5 458 134
63 28.8 0.69 13 2.85 11.7 467 137 27.9 0.66 14 2.83 11.6 463 135 25.8 0.63 14 2.81 11.5 458 134 31.5 0.63 14 2.95 12.1 474 149 30.5 0.61 14 2.93 12.0 469 148 28.2 0.58 14 2.90 11.9 465 146
67 31.5 0.48 10 2.95 12.1 474 149 30.6 0.45 11 2.93 12.0 469 148 28.2 0.44 11 2.90 11.9 465 146 33.8 0.41 9 3.05 12.6 484 159 32.8 0.39 10 3.03 12.4 480 157 30.3 0.38 10 3.00 12.3 475 156
71 -
kW = Total system power Amps = outdoor unit amps (comp.+fan)
36.4 0.40 10 2.95 11.9 409 155 35.4 0.39 10 2.92 11.7 405 154 32.7 0.37 11 2.90 11.6 401 152
71 -
115ºF
Product Specifications
Expanded Cooling Data — DSXC160361** / CA*F3743*6A* +TXV / MBVC1600** High Stage
SS-DSXC16
SS-DSXC16
www.goodmanmfg.com
35.7 0.94 23 2.14 8.1 232 116 34.7 0.90 24 2.12 8.0 230 115 32.0 0.86 24 2.10 8.0 227 114
MBh S/T ∆T kW Amps HI PR Lo PR MBh S/T ∆T kW Amps HI PR Lo PR MBh S/T ∆T kW Amps HI PR Lo PR
1043
1200
1356
59 35.1 0.90 21 2.14 8.1 232 116 34.1 0.85 22 2.12 8.0 230 115 31.4 0.82 23 2.10 8.0 227 114
Airflow MBh S/T ∆T kW 1356 Amps HI PR Lo PR MBh S/T ∆T kW 1200 Amps HI PR Lo PR MBh S/T ∆T 1043 kW Amps HI PR Lo PR
36.4 0.91 22 2.18 8.3 249 120 35.3 0.86 23 2.17 8.2 247 119 32.6 0.83 24 2.15 8.2 244 117
63 35.9 0.84 20 2.18 8.3 249 120 34.8 0.80 21 2.17 8.2 247 119 32.1 0.77 22 2.15 8.2 244 117 38.1 0.82 21 2.25 8.6 253 131 37.0 0.78 22 2.24 8.5 250 129 34.2 0.75 23 2.22 8.4 248 128
67 38.3 0.68 18 2.25 8.6 253 131 37.2 0.65 19 2.24 8.5 250 129 34.3 0.63 19 2.22 8.4 248 128 40.7 0.66 18 2.33 8.9 259 139 39.5 0.63 19 2.31 8.8 256 138 36.4 0.61 20 2.29 8.7 253 136
71 41.0 0.51 14 2.33 8.9 259 139 39.8 0.49 15 2.31 8.8 256 138 36.7 0.47 15 2.29 8.7 253 136 34.9 0.97 23 2.31 8.8 262 119 33.9 0.93 24 2.29 8.7 260 118 31.3 0.89 25 2.27 8.6 257 117
59 34.3 0.93 22 2.31 8.8 262 119 33.3 0.88 23 2.29 8.7 260 118 30.7 0.85 23 2.27 8.6 257 117 35.6 0.94 23 2.36 9.0 282 123 34.5 0.90 24 2.34 8.9 279 122 31.9 0.86 24 2.32 8.8 276 121
63 35.0 0.87 21 2.36 9.0 282 123 34.0 0.83 22 2.34 8.9 279 122 31.4 0.80 22 2.32 8.8 276 121 37.2 0.85 21 2.43 9.3 286 135 36.1 0.81 22 2.41 9.2 283 133 33.4 0.78 23 2.39 9.1 280 132
67 37.4 0.71 18 2.43 9.3 286 135 36.3 0.68 19 2.41 9.2 283 133 33.5 0.65 19 2.39 9.1 280 132
75ºF
IDB = Entering Indoor Dry Bulb Temperature High and low pressures are measured at the liquid and suction service valves.
85
80
IDB
65ºF
39.7 0.69 19 2.51 9.6 292 143 38.6 0.66 19 2.49 9.5 289 142 35.6 0.63 20 2.47 9.4 286 140
71 40.0 0.53 14 2.51 9.6 292 143 38.8 0.50 15 2.49 9.5 289 142 35.8 0.49 15 2.47 9.4 286 140 34.0 1.00 23 2.45 9.5 298 124 33.1 0.95 24 2.43 9.4 295 122 30.5 0.92 25 2.41 9.3 292 121
59 33.5 0.95 22 2.45 9.5 298 124 32.5 0.91 23 2.43 9.4 295 122 30.0 0.87 23 2.41 9.3 292 121 34.7 0.96 23 2.51 9.7 321 127 33.7 0.92 24 2.49 9.6 317 126 31.1 0.89 24 2.47 9.6 314 125
36.3 0.87 21 2.59 10.0 325 139 35.3 0.83 22 2.57 10.0 322 138 32.6 0.80 23 2.55 9.9 319 136
38.8 0.70 19 2.68 10.4 332 148 37.6 0.67 19 2.66 10.3 329 147 34.7 0.65 20 2.63 10.2 326 145
33.9 0.99 23 2.64 10.4 365 131 32.9 0.95 24 2.62 10.3 362 130 30.3 0.91 24 2.60 10.2 358 128
35.5 0.90 22 2.73 10.7 370 143 34.4 0.86 23 2.71 10.6 367 141 31.8 0.82 23 2.68 10.5 363 140
37.8 0.73 19 2.82 11.1 379 152 36.7 0.69 20 2.80 11.0 375 151 33.9 0.67 20 2.78 10.9 371 149
71 38.1 0.56 14 2.82 11.1 379 152 37.0 0.53 15 2.80 11.0 375 151 34.1 0.52 16 2.78 10.9 371 149 31.6 1.00 21 2.69 10.8 367 129 30.6 1.00 23 2.67 10.7 363 128 28.3 0.98 24 2.65 10.6 360 127
59 31.0 1.00 21 2.69 10.8 367 129 30.1 0.97 22 2.67 10.7 363 128 27.8 0.94 23 2.65 10.6 360 127
Shaded area reflects AHRI (TVA) conditions
33.2 1.00 23 2.58 10.1 340 127 32.2 0.98 24 2.56 10.1 336 126 29.8 0.95 25 2.54 10.0 333 124
Outdoor Ambient Temperature 85ºF 95ºF Entering Indoor Wet Bulb Temperature 63 67 71 59 63 67 34.2 36.5 39.0 32.6 33.4 35.6 0.89 0.73 0.54 1.00 0.92 0.75 21 18 14 22 21 18 2.51 2.59 2.68 2.58 2.64 2.73 9.7 10.0 10.4 10.1 10.4 10.7 321 325 332 340 365 370 127 139 148 127 131 143 33.2 35.5 37.9 31.7 32.4 34.6 0.85 0.69 0.52 0.94 0.88 0.71 22 19 15 23 22 19 2.49 2.57 2.66 2.56 2.62 2.71 9.6 10.0 10.3 10.1 10.3 10.6 317 322 329 336 362 367 126 138 147 126 130 141 30.6 32.7 35.0 29.3 29.9 31.9 0.82 0.67 0.50 0.90 0.85 0.69 22 19 15 23 22 19 2.47 2.55 2.63 2.54 2.60 2.68 9.6 9.9 10.2 10.0 10.2 10.5 314 319 326 333 358 363 125 136 145 124 128 140 32.2 1.00 22 2.76 11.1 394 133 31.2 0.98 24 2.73 11.0 390 132 28.8 0.95 24 2.71 10.9 387 131
63 31.7 0.96 21 2.76 11.1 394 133 30.8 0.91 21 2.73 11.0 390 132 28.4 0.88 22 2.71 10.9 387 131 33.7 0.93 21 2.85 11.4 400 146 32.7 0.89 22 2.82 11.3 396 144 30.2 0.86 23 2.80 11.2 392 143
67 33.9 0.78 18 2.85 11.4 400 146 32.9 0.74 19 2.82 11.3 396 144 30.3 0.72 19 2.80 11.2 392 143
105ºF
29.2 1.00 20 2.79 11.4 435 133 28.4 1.00 22 2.77 11.3 430 131 26.2 0.99 23 2.74 11.2 426 130
59 28.7 1.00 19 2.79 11.4 435 133 27.9 0.98 21 2.77 11.3 430 131 25.7 0.95 21 2.74 11.2 426 130 29.8 1.00 20 2.85 11.7 467 137 28.9 0.99 22 2.83 11.6 463 135 26.7 0.96 22 2.81 11.5 458 134
63 29.4 0.96 19 2.85 11.7 467 137 28.5 0.92 20 2.83 11.6 463 135 26.3 0.89 21 2.81 11.5 458 134 31.2 0.94 20 2.95 12.1 474 149 30.3 0.89 21 2.93 12.0 469 148 28.0 0.86 21 2.90 11.9 465 146
67 31.4 0.78 17 2.95 12.1 474 149 30.4 0.75 17 2.93 12.0 469 148 28.1 0.72 18 2.90 11.9 465 146 33.3 0.76 17 3.05 12.6 484 159 32.3 0.73 18 3.03 12.4 480 157 29.8 0.70 18 3.00 12.3 475 156
71 33.5 0.59 13 3.05 12.6 484 159 32.5 0.56 14 3.03 12.4 480 157 30.0 0.54 14 3.00 12.3 475 156
kW = Total system power Amps = outdoor unit amps (comp.+fan)
35.9 0.75 18 2.95 11.9 409 155 34.9 0.72 19 2.92 11.7 405 154 32.2 0.69 20 2.90 11.6 401 152
71 36.2 0.58 14 2.95 11.9 409 155 35.1 0.55 15 2.92 11.7 405 154 32.4 0.53 15 2.90 11.6 401 152
115ºF
Product Specifications
Expanded Cooling Data — DSXC160361** / CA*F3743*6A* +TXV / MBVC1600** High Stage (cont.)
11
12
www.goodmanmfg.com
34.9 0.84 22 2.06 9.9 218 108 33.9 0.81 23 2.04 9.8 216 107 31.3 0.78 23 1.99 9.6 209 104
MBh S/T ∆T kW Amps HI PR LO PR MBh S/T ∆T kW Amps HI PR LO PR MBh S/T ∆T kW Amps HI PR LO PR
963
1100
1238
59 34.3 0.74 19 2.04 9.8 216 107 33.3 0.71 20 2.02 9.7 214 106 30.7 0.68 20 1.97 9.5 207 102
Airflow MBh S/T ∆T kW 1238 Amps HI PR LO PR MBh S/T ∆T kW 1100 Amps HI PR LO PR MBh S/T ∆T 963 kW Amps HI PR LO PR
35.9 0.76 20 2.10 10.0 235 115 34.9 0.72 21 2.08 10.0 232 114 32.2 0.69 21 2.03 9.7 225 110
63 35.5 0.62 16 2.08 10.0 232 114 34.5 0.59 17 2.07 9.9 230 112 31.9 0.57 17 2.02 9.7 223 109 38.9 0.57 17 2.17 10.3 248 125 37.7 0.55 17 2.15 10.2 245 124 34.8 0.53 17 2.10 10.0 238 120
67 38.9 0.43 12 2.15 10.2 245 124 37.8 0.41 13 2.13 10.2 243 123 34.9 0.40 13 2.08 9.9 235 119 41.7 0.37 11 2.24 10.6 258 133 40.5 0.35 12 2.22 10.6 256 132 37.4 0.34 12 2.17 10.3 248 128
71 34.1 0.88 22 2.22 10.5 245 114 33.1 0.84 23 2.20 10.4 242 113 30.5 0.81 23 2.14 10.2 235 109
59 33.5 0.77 19 2.20 10.4 242 113 32.5 0.73 20 2.18 10.4 240 112 30.0 0.71 20 2.13 10.1 232 108 35.1 0.78 20 2.27 10.7 263 121 34.1 0.75 21 2.25 10.6 261 120 31.4 0.72 22 2.19 10.4 253 116
63 34.7 0.64 17 2.25 10.6 261 120 33.7 0.61 17 2.23 10.6 258 119 31.1 0.59 18 2.17 10.3 250 115 38.0 0.59 17 2.34 11.0 278 132 36.9 0.57 17 2.32 10.9 275 131 34.0 0.55 18 2.26 10.7 267 127
67 38.0 0.45 13 2.32 10.9 275 131 36.9 0.43 13 2.30 10.9 272 130 34.1 0.41 13 2.24 10.6 264 126
75ºF
IDB = Entering Indoor Dry Bulb Temperature High and low pressures are measured at the liquid and suction service valves.
75
70
IDB
65ºF
40.7 0.38 12 2.42 11.4 290 141 39.6 0.36 12 2.40 11.3 287 139 36.5 0.35 12 2.34 11.0 278 135
71 33.3 0.90 22 2.36 11.3 278 118 32.3 0.86 23 2.34 11.2 275 117 29.8 0.83 24 2.28 10.9 267 114
59 32.7 0.79 19 2.34 11.2 275 117 31.7 0.75 20 2.32 11.1 273 116 29.3 0.73 20 2.26 10.8 264 113 34.2 0.80 20 2.41 11.5 299 126 33.2 0.77 21 2.39 11.4 296 125 30.7 0.74 22 2.33 11.2 287 121
37.1 0.61 17 2.49 11.8 316 137 36.0 0.58 17 2.47 11.8 313 136 33.2 0.56 18 2.41 11.5 304 132
39.8 0.39 12 2.57 12.2 330 146 38.6 0.37 12 2.55 12.1 326 145 35.6 0.36 12 2.49 11.8 317 141
33.4 0.83 21 2.54 12.2 341 132 32.4 0.79 21 2.52 12.1 338 131 29.9 0.76 22 2.45 11.8 327 127
36.2 0.63 17 2.62 12.6 360 144 35.1 0.60 18 2.60 12.5 356 143 32.4 0.58 18 2.54 12.2 346 139
38.8 0.40 12 2.71 13.0 375 154 37.7 0.38 12 2.69 12.9 372 152 34.8 0.37 12 2.62 12.6 361 148
71 30.8 0.96 22 2.59 12.6 356 130 29.9 0.92 23 2.57 12.5 353 129 27.6 0.88 23 2.50 12.2 342 125
59 30.3 0.85 19 2.57 12.5 353 129 29.4 0.81 20 2.55 12.4 349 128 27.2 0.78 20 2.48 12.1 339 124
Shaded area reflects ACCA (TVA) conditions
32.4 0.93 22 2.48 11.9 317 124 31.5 0.88 23 2.46 11.9 314 123 29.1 0.85 24 2.40 11.6 304 119
Outdoor Ambient Temperature 85ºF 95ºF Entering Indoor Wet Bulb Temperature 63 67 71 59 63 67 33.9 37.1 31.9 33.1 36.2 0.66 0.46 0.82 0.68 0.47 17 13 19 17 13 2.39 2.47 2.46 2.52 2.60 11.4 11.8 11.9 12.1 12.5 296 313 314 337 356 125 136 123 131 143 32.9 36.1 31.0 32.1 35.2 0.63 0.44 0.78 0.65 0.45 17 13 20 17 13 2.37 2.45 2.44 2.50 2.58 11.3 11.7 11.8 12.0 12.4 293 310 310 334 353 123 135 122 130 142 30.4 33.3 28.6 29.6 32.5 0.61 0.42 0.75 0.63 0.43 18 13 20 18 13 2.31 2.39 2.38 2.43 2.51 11.1 11.4 11.5 11.7 12.1 285 300 301 324 342 120 131 118 126 137 31.7 0.86 20 2.65 12.9 383 139 30.8 0.82 21 2.63 12.8 380 137 28.4 0.79 21 2.56 12.5 368 133
63 31.4 0.71 16 2.63 12.8 380 137 30.5 0.67 17 2.60 12.7 376 136 28.2 0.65 17 2.54 12.4 365 132 34.4 0.65 17 2.74 13.3 405 151 33.3 0.62 17 2.71 13.2 401 150 30.8 0.60 18 2.64 12.8 389 145
67 34.4 0.49 13 2.71 13.2 401 150 33.4 0.47 13 2.69 13.0 397 148 30.8 0.45 13 2.62 12.7 385 144
105ºF
28.6 0.97 21 2.68 13.3 394 135 27.7 0.93 21 2.66 13.2 390 133 25.6 0.89 22 2.59 12.8 378 129
59 28.1 0.85 18 2.66 13.2 390 133 27.3 0.81 19 2.64 13.1 386 132 25.2 0.78 19 2.57 12.7 374 128 29.4 0.87 19 2.74 13.6 424 143 28.5 0.83 20 2.72 13.4 420 142 26.3 0.80 20 2.65 13.1 407 138
63 29.1 0.71 15 2.72 13.4 419 142 28.3 0.68 16 2.70 13.3 415 141 26.1 0.66 16 2.63 13.0 403 136 31.8 0.66 16 2.83 14.0 447 157 30.9 0.63 16 2.81 13.8 443 155 28.5 0.60 16 2.74 13.5 430 150
67 31.9 0.49 12 2.81 13.8 443 155 31.0 0.47 12 2.79 13.7 439 153 28.6 0.45 12 2.71 13.4 425 149 34.2 0.42 11 2.93 14.4 467 167 33.2 0.40 11 2.91 14.3 462 165 30.6 0.39 11 2.83 14.0 448 160
71 -
kW = Total system power Amps = outdoor unit amps (comp.+fan)
36.9 0.42 11 2.83 13.7 422 161 35.8 0.40 12 2.81 13.6 418 160 33.0 0.39 12 2.73 13.3 406 155
71 -
115ºF
Product Specifications
Expanded Cooling Data — DSXC160481B* / CA*F4860*6**+TXV/MBVC2000** Low stage
SS-DSXC16
SS-DSXC16
www.goodmanmfg.com
36.1 0.97 26 2.09 10.0 222 110 35.1 0.93 27 2.07 9.9 220 109 32.4 0.89 28 2.02 9.7 214 106
MBh S/T ∆T kW Amps HI PR LO PR MBh S/T ∆T kW Amps HI PR LO PR MBh S/T ∆T kW Amps HI PR LO PR
963
1100
1238
59 35.5 0.93 24 2.07 9.9 220 109 34.5 0.88 25 2.06 9.9 218 108 31.8 0.85 26 2.01 9.6 211 105
Airflow MBh S/T ∆T kW 1238 Amps HI PR LO PR MBh S/T ∆T kW 1100 Amps HI PR LO PR MBh S/T ∆T 963 kW Amps HI PR LO PR
36.8 0.94 26 2.13 10.2 239 117 35.7 0.89 27 2.12 10.1 237 116 33.0 0.86 27 2.07 9.9 230 112
63 36.3 0.87 23 2.12 10.1 237 116 35.2 0.83 24 2.10 10.0 235 115 32.5 0.80 25 2.05 9.8 228 111 38.6 0.85 24 2.20 10.5 253 128 37.4 0.81 25 2.19 10.4 250 126 34.6 0.78 26 2.13 10.2 243 123
67 38.8 0.71 20 2.19 10.4 250 126 37.6 0.67 21 2.17 10.3 248 125 34.7 0.65 22 2.11 10.1 240 121 41.1 0.69 21 2.28 10.8 264 136 39.9 0.65 22 2.26 10.7 261 135 36.9 0.63 22 2.20 10.5 253 131
71 41.4 0.53 16 2.26 10.7 261 135 40.2 0.50 17 2.24 10.6 258 133 37.1 0.49 17 2.18 10.4 251 129 35.3 1.00 26 2.25 10.7 249 116 34.3 0.96 27 2.24 10.6 247 115 31.6 0.93 28 2.18 10.4 240 112
59 34.7 0.96 25 2.24 10.6 247 115 33.7 0.92 26 2.22 10.5 245 114 31.1 0.88 26 2.16 10.3 237 110 36.0 0.97 26 2.30 10.9 268 124 34.9 0.93 27 2.28 10.8 266 122 32.2 0.89 27 2.23 10.6 258 119
63 35.4 0.90 24 2.28 10.8 266 122 34.4 0.86 25 2.27 10.7 263 121 31.7 0.83 25 2.21 10.5 255 118 37.7 0.88 25 2.38 11.2 284 135 36.6 0.84 26 2.36 11.1 281 134 33.8 0.81 26 2.30 10.9 272 130
67 37.9 0.73 21 2.36 11.1 281 134 36.8 0.70 21 2.34 11.0 278 132 33.9 0.67 22 2.28 10.8 270 128
75ºF
IDB = Entering Indoor Dry Bulb Temperature High and low pressures are measured at the liquid and suction service valves.
85
80
IDB
65ºF
40.2 0.71 21 2.46 11.6 296 144 39.0 0.68 22 2.44 11.5 293 142 36.0 0.65 22 2.38 11.2 284 138
71 40.5 0.55 16 2.44 11.5 293 142 39.3 0.52 17 2.42 11.4 290 141 36.3 0.50 17 2.36 11.1 281 137 34.4 1.00 26 2.40 11.5 284 121 33.4 0.98 28 2.38 11.4 281 120 30.9 0.95 28 2.32 11.1 273 116
59 33.8 1.00 25 2.38 11.4 281 120 32.9 0.94 26 2.36 11.3 278 118 30.3 0.91 26 2.30 11.0 270 115 35.1 1.00 26 2.45 11.7 305 128 34.1 0.95 27 2.43 11.6 302 127 31.5 0.92 28 2.37 11.3 293 123
36.8 0.90 25 2.53 12.0 322 140 35.7 0.86 26 2.51 11.9 319 139 32.9 0.83 26 2.45 11.7 310 135
39.2 0.73 21 2.62 12.4 336 149 38.1 0.70 22 2.60 12.3 333 148 35.1 0.67 23 2.53 12.0 323 143
34.2 1.00 25 2.58 12.4 348 135 33.3 0.98 27 2.56 12.3 344 134 30.7 0.95 28 2.50 12.0 334 130
35.9 0.93 25 2.67 12.8 367 147 34.8 0.89 26 2.65 12.7 364 146 32.1 0.85 26 2.58 12.4 353 141
38.3 0.75 21 2.76 13.2 383 157 37.2 0.72 22 2.74 13.1 379 155 34.3 0.69 23 2.67 12.8 368 151
71 38.5 0.58 17 2.74 13.1 379 155 37.4 0.55 17 2.71 13.0 375 154 34.5 0.53 18 2.64 12.7 364 149 31.9 1.00 24 2.63 12.8 364 133 31.0 1.00 26 2.61 12.7 360 132 28.6 1.00 27 2.55 12.4 349 128
59 31.4 1.00 23 2.61 12.7 360 132 30.5 1.00 25 2.59 12.6 356 130 28.1 0.97 26 2.52 12.3 346 126
Shaded area reflects AHRI (TVA) conditions
33.6 1.00 25 2.53 12.1 323 127 32.6 1.00 27 2.50 12.0 320 126 30.1 0.98 28 2.44 11.8 310 122
Outdoor Ambient Temperature 85ºF 95ºF Entering Indoor Wet Bulb Temperature 63 67 71 59 63 67 34.6 37.0 39.5 33.0 33.7 36.1 0.92 0.75 0.56 1.00 0.95 0.78 24 21 16 25 24 21 2.43 2.51 2.60 2.50 2.56 2.65 11.6 11.9 12.3 12.0 12.3 12.7 302 319 333 320 344 364 127 139 148 126 134 146 33.6 35.9 38.4 32.1 32.8 35.0 0.88 0.72 0.54 0.97 0.91 0.74 25 21 17 26 25 22 2.41 2.49 2.57 2.48 2.54 2.62 11.5 11.8 12.2 12.0 12.2 12.6 299 316 330 317 341 360 126 137 146 124 132 144 31.0 33.1 35.4 29.6 30.2 32.3 0.85 0.69 0.52 0.93 0.88 0.71 25 22 17 26 25 22 2.35 2.43 2.51 2.42 2.48 2.56 11.2 11.6 11.9 11.7 11.9 12.3 290 307 320 307 331 349 122 133 142 121 128 140 32.5 1.00 24 2.69 13.1 391 141 31.6 1.00 26 2.67 13.0 387 140 29.2 0.98 27 2.60 12.7 376 136
63 32.1 1.00 24 2.67 13.0 387 140 31.1 0.94 25 2.65 12.9 384 139 28.7 0.91 25 2.58 12.6 372 134 34.1 0.96 24 2.78 13.5 413 154 33.1 0.92 25 2.76 13.4 409 153 30.5 0.89 26 2.69 13.0 397 148
67 34.2 0.81 20 2.76 13.4 409 153 33.3 0.77 21 2.74 13.3 405 151 30.7 0.74 22 2.67 12.9 393 147
105ºF
29.6 1.00 22 2.73 13.5 402 137 28.7 1.00 24 2.70 13.4 398 136 26.5 1.00 25 2.64 13.1 386 132
59 29.1 1.00 22 2.70 13.4 398 136 28.2 1.00 24 2.68 13.3 394 135 26.0 0.98 24 2.61 12.9 382 131 30.1 1.00 22 2.79 13.8 432 146 29.3 1.00 24 2.77 13.7 428 145 27.0 0.99 26 2.69 13.3 415 140
63 29.7 1.00 22 2.77 13.7 428 145 28.8 0.95 23 2.74 13.6 424 143 26.6 0.92 23 2.67 13.2 411 139 31.6 0.97 23 2.88 14.2 456 160 30.6 0.93 24 2.86 14.1 452 158 28.3 0.89 24 2.79 13.7 438 153
67 31.7 0.81 19 2.86 14.1 452 158 30.8 0.77 20 2.83 14.0 447 157 28.4 0.75 20 2.76 13.6 434 152 33.7 0.79 20 2.98 14.7 476 170 32.7 0.75 21 2.96 14.6 471 168 30.2 0.72 21 2.88 14.2 457 163
71 33.9 0.61 15 2.96 14.6 471 168 32.9 0.58 16 2.93 14.4 467 167 30.4 0.56 16 2.86 14.1 453 162
kW = Total system power Amps = outdoor unit amps (comp.+fan)
36.4 0.78 21 2.88 13.9 431 164 35.3 0.75 22 2.85 13.8 427 163 32.6 0.72 22 2.78 13.5 414 158
71 36.6 0.60 16 2.85 13.8 427 163 35.5 0.57 17 2.83 13.7 422 161 32.8 0.55 17 2.76 13.4 410 156
115ºF
Product Specifications
Expanded Cooling Data — DSXC160481B* / CA*F4860*6**+TXV/MBVC2000** Low stage (cont.)
13
14
www.goodmanmfg.com
46.8 0.84 20 3.06 14.7 237 105 45.5 0.81 21 3.03 14.6 235 104 42.0 0.78 21 2.96 14.3 228 101
MBh S/T ∆T kW Amps HI PR LO PR MBh S/T ∆T kW Amps HI PR LO PR MBh S/T ∆T kW Amps HI PR LO PR
1400
1600
1800
59 46.1 0.74 17 3.03 14.6 235 104 44.7 0.71 18 3.01 14.5 233 103 41.3 0.68 19 2.93 14.2 226 100
Airflow MBh S/T ∆T kW 1800 Amps HI PR LO PR MBh S/T ∆T kW 1600 Amps HI PR LO PR MBh S/T ∆T 1400 kW Amps HI PR LO PR
48.2 0.76 19 3.12 15.0 255 112 46.8 0.72 19 3.10 14.9 253 111 43.2 0.69 20 3.02 14.5 245 108
63 47.7 0.62 15 3.10 14.9 253 111 46.3 0.59 16 3.07 14.8 250 110 42.8 0.57 16 3.00 14.4 243 106 52.2 0.57 15 3.22 15.4 270 122 50.7 0.55 16 3.20 15.3 267 121 46.8 0.53 16 3.12 14.9 259 117
67 52.3 0.43 11 3.19 15.3 267 121 50.8 0.41 12 3.17 15.1 264 120 46.9 0.40 12 3.09 14.8 256 116 56.0 0.37 11 3.33 15.9 281 130 54.4 0.35 11 3.30 15.7 278 129 50.2 0.34 11 3.22 15.4 270 125
71 45.7 0.88 20 3.29 15.7 266 111 44.4 0.84 21 3.27 15.5 264 110 41.0 0.81 22 3.19 15.2 256 107
59 45.0 0.77 18 3.27 15.5 264 110 43.7 0.73 18 3.24 15.4 261 109 40.3 0.71 19 3.16 15.1 253 106 47.1 0.78 19 3.37 16.0 287 118 45.7 0.75 20 3.34 15.9 284 117 42.2 0.72 20 3.26 15.5 275 114
63 46.6 0.64 15 3.34 15.9 284 117 45.3 0.61 16 3.31 15.7 281 116 41.8 0.59 16 3.23 15.4 272 112 51.0 0.59 15 3.48 16.4 303 129 49.5 0.57 16 3.45 16.3 300 128 45.7 0.55 16 3.36 15.9 291 124
67 51.1 0.45 12 3.45 16.3 300 128 49.6 0.43 12 3.42 16.2 297 127 45.8 0.41 12 3.33 15.8 288 123
75ºF
IDB = Entering Indoor Dry Bulb Temperature High and low pressures are measured at the liquid and suction service valves.
75
70
IDB
65ºF
54.7 0.38 11 3.59 16.9 316 138 53.1 0.36 11 3.56 16.8 312 136 49.0 0.35 11 3.47 16.4 303 132
71 44.7 0.90 20 3.51 16.8 303 116 43.4 0.86 21 3.48 16.7 300 114 40.0 0.83 22 3.39 16.3 291 111
59 43.9 0.79 18 3.48 16.7 300 114 42.6 0.75 18 3.45 16.5 297 113 39.4 0.73 19 3.36 16.1 288 110 46.0 0.80 19 3.58 17.1 326 123 44.6 0.77 20 3.55 17.0 323 122 41.2 0.74 20 3.46 16.6 313 118
49.8 0.61 15 3.70 17.6 344 134 48.3 0.58 16 3.67 17.5 341 133 44.6 0.56 16 3.58 17.1 331 129
53.4 0.39 11 3.83 18.2 359 143 51.9 0.37 11 3.79 18.0 355 142 47.9 0.36 11 3.70 17.6 345 137
44.9 0.83 19 3.77 18.1 371 129 43.6 0.79 20 3.74 18.0 368 128 40.2 0.76 20 3.65 17.6 356 124
48.6 0.63 16 3.90 18.6 392 141 47.1 0.60 16 3.87 18.5 388 140 43.5 0.58 16 3.77 18.1 376 135
52.1 0.40 11 4.03 19.3 409 150 50.6 0.38 11 4.00 19.1 405 149 46.7 0.37 11 3.90 18.6 393 144
71 41.4 0.96 20 3.85 18.7 388 127 40.2 0.92 21 3.82 18.6 384 126 37.1 0.88 22 3.72 18.1 373 122
59 40.7 0.85 18 3.82 18.6 384 126 39.5 0.81 18 3.78 18.4 380 125 36.5 0.78 19 3.69 18.0 369 121
Shaded area reflects ACCA (TVA) conditions
43.6 0.93 21 3.69 17.8 345 121 42.3 0.88 21 3.66 17.6 342 120 39.0 0.85 22 3.57 17.2 331 117
Outdoor Ambient Temperature 85ºF 95ºF Entering Indoor Wet Bulb Temperature 63 67 71 59 63 67 45.5 49.9 42.8 44.4 48.7 0.66 0.46 0.82 0.68 0.47 15 12 18 15 12 3.55 3.67 3.66 3.74 3.87 17.0 17.5 17.6 18.0 18.5 323 341 341 367 388 122 133 120 128 140 44.2 48.4 41.6 43.1 47.2 0.63 0.44 0.78 0.65 0.45 16 12 19 16 12 3.52 3.64 3.63 3.71 3.83 16.9 17.3 17.5 17.8 18.4 319 337 338 364 384 120 132 119 127 138 40.8 44.7 38.4 39.8 43.6 0.61 0.42 0.75 0.63 0.43 16 12 19 16 12 3.44 3.55 3.54 3.62 3.74 16.5 16.9 17.1 17.4 17.9 310 327 328 353 373 117 128 115 123 134 42.6 0.86 19 3.94 19.1 418 135 41.4 0.82 20 3.90 19.0 413 134 38.2 0.79 20 3.80 18.5 401 130
63 42.2 0.71 15 3.90 19.0 413 134 41.0 0.67 16 3.87 18.8 409 133 37.8 0.65 16 3.77 18.4 397 129 46.1 0.65 15 4.07 19.7 441 148 44.8 0.62 16 4.03 19.5 437 146 41.3 0.60 16 3.93 19.1 423 142
67 46.2 0.49 12 4.03 19.5 437 146 44.9 0.47 12 4.00 19.4 432 145 41.4 0.45 12 3.90 18.9 419 140
105ºF
38.3 0.97 19 3.99 19.7 429 132 37.2 0.93 20 3.95 19.5 424 130 34.4 0.89 20 3.85 19.1 412 126
59 37.7 0.85 16 3.95 19.5 424 130 36.6 0.81 17 3.92 19.4 420 129 33.8 0.78 17 3.82 18.9 408 125 39.5 0.87 17 4.08 20.1 461 140 38.3 0.83 18 4.04 20.0 457 139 35.4 0.80 19 3.94 19.5 443 134
63 39.1 0.71 14 4.04 20.0 457 139 37.9 0.68 15 4.01 19.8 452 137 35.0 0.66 15 3.90 19.3 439 133 42.7 0.66 14 4.21 20.7 487 153 41.5 0.63 15 4.18 20.5 482 151 38.3 0.60 15 4.07 20.0 468 147
67 42.8 0.49 11 4.18 20.5 482 151 41.6 0.47 11 4.14 20.4 478 150 38.4 0.45 11 4.04 19.9 463 145 45.9 0.42 10 4.36 21.4 508 163 44.5 0.40 10 4.32 21.2 503 161 41.1 0.39 10 4.21 20.7 488 156
71 -
kW = Total system power Amps = outdoor unit amps (comp.+fan)
49.5 0.42 11 4.21 20.3 460 157 48.1 0.40 11 4.17 20.2 455 156 44.4 0.39 11 4.06 19.7 442 151
71 -
115ºF
Product Specifications
Expanded Cooling Data — DSXC160481B* / CA*F4860*6**+TXV/MBVC2000** High stage
SS-DSXC16
SS-DSXC16
www.goodmanmfg.com
48.5 0.97 24 3.11 14.9 242 107 47.1 0.93 25 3.08 14.8 240 106 43.5 0.89 25 3.01 14.5 233 103
MBh S/T ∆T kW Amps HI PR LO PR MBh S/T ∆T kW Amps HI PR LO PR MBh S/T ∆T kW Amps HI PR LO PR
1400
1600
1800
59 47.7 0.93 23 3.08 14.8 240 106 46.3 0.88 24 3.06 14.7 237 105 42.7 0.85 24 2.98 14.4 230 102
Airflow MBh S/T ∆T kW 1800 Amps HI PR LO PR MBh S/T ∆T kW 1600 Amps HI PR LO PR MBh S/T ∆T 1400 kW Amps HI PR LO PR
49.4 0.94 24 3.17 15.2 261 114 48.0 0.89 25 3.15 15.1 258 113 44.3 0.86 25 3.07 14.7 250 110
63 48.7 0.87 22 3.15 15.1 258 113 47.3 0.83 23 3.12 15.0 255 112 43.6 0.80 23 3.05 14.6 248 109 51.8 0.85 22 3.27 15.6 275 125 50.3 0.81 23 3.25 15.5 272 123 46.4 0.78 24 3.17 15.1 264 120
67 52.0 0.71 19 3.25 15.5 272 123 50.5 0.67 20 3.22 15.4 270 122 46.6 0.65 20 3.14 15.0 262 119 55.2 0.69 19 3.38 16.1 287 133 53.6 0.65 20 3.35 16.0 284 131 49.5 0.63 21 3.27 15.6 276 128
71 55.6 0.53 15 3.35 16.0 284 131 54.0 0.50 16 3.33 15.9 281 130 49.9 0.49 16 3.24 15.5 273 126 47.4 1.00 24 3.35 15.9 272 113 46.0 0.96 25 3.32 15.8 269 112 42.5 0.93 26 3.24 15.4 261 109
59 46.6 0.96 23 3.32 15.8 269 112 45.2 0.92 24 3.29 15.7 266 111 41.7 0.88 24 3.21 15.3 258 108 48.3 0.97 24 3.42 16.2 292 121 46.9 0.93 25 3.39 16.1 289 119 43.3 0.89 25 3.31 15.7 281 116
63 47.6 0.90 22 3.39 16.1 289 119 46.2 0.86 23 3.37 16.0 287 118 42.6 0.83 23 3.28 15.6 278 115 50.6 0.88 23 3.53 16.7 309 132 49.1 0.84 24 3.51 16.5 306 130 45.3 0.81 24 3.42 16.2 296 127
67 50.8 0.73 19 3.51 16.5 306 130 49.4 0.70 20 3.48 16.4 303 129 45.6 0.67 20 3.39 16.0 294 125
75ºF
IDB = Entering Indoor Dry Bulb Temperature High and low pressures are measured at the liquid and suction service valves.
85
80
IDB
65ºF
54.0 0.71 20 3.65 17.2 322 140 52.4 0.68 20 3.62 17.1 319 139 48.4 0.65 21 3.53 16.7 309 135
71 54.3 0.55 15 3.62 17.1 319 139 52.8 0.52 16 3.59 16.9 316 138 48.7 0.50 16 3.50 16.5 306 133 46.2 1.00 24 3.56 17.0 309 118 44.9 0.98 25 3.53 16.9 306 117 41.4 0.95 26 3.45 16.5 297 113
59 45.5 1.00 23 3.53 16.9 306 117 44.1 0.94 24 3.51 16.8 303 116 40.7 0.91 24 3.42 16.4 294 112 47.1 1.00 24 3.64 17.4 332 125 45.8 0.95 25 3.61 17.3 329 124 42.2 0.92 25 3.52 16.9 319 120
49.4 0.90 23 3.76 17.9 351 137 47.9 0.86 24 3.73 17.8 348 136 44.2 0.83 24 3.64 17.3 337 132
52.7 0.73 20 3.89 18.5 366 146 51.1 0.70 20 3.86 18.3 363 144 47.2 0.67 21 3.76 17.9 352 140
46.0 1.00 23 3.84 18.4 379 132 44.7 0.98 25 3.81 18.3 375 130 41.2 0.95 26 3.71 17.8 364 127
48.2 0.93 23 3.97 18.9 400 144 46.8 0.89 24 3.93 18.8 396 142 43.2 0.85 24 3.83 18.3 384 138
51.4 0.75 20 4.10 19.6 417 153 49.9 0.72 21 4.07 19.4 413 152 46.0 0.69 21 3.96 18.9 401 147
71 51.8 0.58 15 4.07 19.4 413 152 50.2 0.55 16 4.03 19.3 409 150 46.4 0.53 16 3.93 18.8 397 146 42.9 1.00 22 3.92 19.0 396 130 41.6 1.00 24 3.88 18.9 392 129 38.4 1.00 25 3.78 18.4 380 125
59 42.1 1.00 22 3.88 18.9 392 129 40.9 1.00 24 3.85 18.7 388 127 37.8 0.97 24 3.75 18.3 376 123
Shaded area reflects AHRI (TVA) conditions
45.1 1.00 23 3.75 18.0 352 124 43.8 1.00 25 3.72 17.9 348 123 40.4 0.98 26 3.63 17.5 338 119
Outdoor Ambient Temperature 85ºF 95ºF Entering Indoor Wet Bulb Temperature 63 67 71 59 63 67 46.4 49.6 53.0 44.3 45.3 48.4 0.92 0.75 0.56 1.00 0.95 0.78 22 19 15 23 22 19 3.61 3.73 3.86 3.72 3.81 3.93 17.3 17.8 18.3 17.9 18.3 18.8 329 348 363 348 375 396 124 136 144 123 130 142 45.1 48.2 51.5 43.1 44.0 47.0 0.88 0.72 0.54 0.97 0.91 0.74 23 20 16 24 23 20 3.58 3.70 3.83 3.69 3.77 3.90 17.1 17.6 18.2 17.8 18.1 18.7 326 344 359 345 371 392 123 134 143 121 129 141 41.6 44.5 47.5 39.7 40.6 43.4 0.85 0.69 0.52 0.93 0.88 0.71 23 20 16 24 23 20 3.49 3.61 3.73 3.60 3.68 3.80 16.7 17.2 17.7 17.3 17.7 18.2 316 334 348 335 360 380 119 130 139 118 125 137 43.7 1.00 22 4.00 19.4 426 138 42.4 1.00 24 3.97 19.3 422 137 39.2 0.98 25 3.87 18.8 409 133
63 43.0 1.00 22 3.97 19.3 422 137 41.8 0.94 23 3.94 19.1 418 135 38.6 0.91 23 3.84 18.7 405 131 45.8 0.96 23 4.14 20.0 450 151 44.4 0.92 23 4.10 19.8 445 149 41.0 0.89 24 4.00 19.4 432 145
67 46.0 0.81 19 4.10 19.8 445 149 44.7 0.77 20 4.07 19.7 441 148 41.2 0.74 20 3.96 19.2 428 143
105ºF
39.7 1.00 20 4.05 20.0 437 134 38.5 1.00 22 4.02 19.9 433 133 35.6 1.00 23 3.92 19.4 420 129
59 39.0 1.00 20 4.02 19.9 433 133 37.9 1.00 22 3.99 19.7 429 132 35.0 0.98 22 3.88 19.2 416 128 40.5 1.00 21 4.15 20.4 471 143 39.3 1.00 23 4.11 20.3 466 141 36.3 0.99 24 4.01 19.8 452 137
63 39.9 1.00 20 4.11 20.3 466 141 38.7 0.95 21 4.08 20.1 461 140 35.7 0.92 22 3.97 19.6 448 136 42.4 0.97 21 4.29 21.0 497 156 41.2 0.93 22 4.25 20.9 492 154 38.0 0.89 22 4.14 20.4 477 150
67 42.6 0.81 18 4.25 20.9 492 154 41.4 0.77 18 4.21 20.7 487 153 38.2 0.75 19 4.11 20.2 473 148 45.2 0.79 18 4.44 21.8 518 166 43.9 0.75 19 4.40 21.6 513 164 40.5 0.72 19 4.28 21.0 498 159
71 45.5 0.61 14 4.40 21.6 513 164 44.2 0.58 15 4.36 21.4 508 163 40.8 0.56 15 4.25 20.9 493 158
kW = Total system power Amps = outdoor unit amps (comp.+fan)
48.8 0.78 19 4.28 20.7 469 161 47.4 0.75 20 4.24 20.5 465 159 43.7 0.72 21 4.13 20.0 451 154
71 49.2 0.60 15 4.24 20.5 465 159 47.7 0.57 16 4.21 20.3 460 157 44.1 0.55 16 4.10 19.8 446 153
115ºF
Product Specifications
Expanded Cooling Data — DSXC160481B* / CA*F4860*6**+TXV/MBVC2000** High stage (cont.)
15
16
www.goodmanmfg.com
1050
1217
1350
67 44.6 0.42 13 2.57 10.4 244 124 43.9 0.41 13 2.56 10.4 242 124 40.5 0.39 14 2.49 10.1 235 120 44.49 0.56 17 2.59 10.5 246 126 43.8 0.54 18 2.58 10.5 244 125 40.5 0.52 18 2.51 10.2 237 121
MBh 39.92 41.10 S/T 0.83 0.75 ∆T 23 21 kW 2.45 2.51 Amps 10.0 10.2 HI PR 217 233 LO PR 108 115 MBh 39.3 40.5 S/T 0.80 0.71 ∆T 24 22 kW 2.44 2.49 Amps 9.9 10.1 HI PR 215 231 LO PR 108 114 MBh 36.3 37.4 S/T 0.77 0.69 ∆T 24 23 kW 2.38 2.43 Amps 9.6 9.9 HI PR 209 224 LO PR 104 111
59 39.3 0.73 20 2.43 9.9 214 107 38.7 0.70 21 2.42 9.8 213 106 35.7 0.68 21 2.36 9.5 207 103
63 40.7 0.61 17 2.49 10.1 231 114 40.1 0.59 18 2.47 10.0 229 113 37.0 0.57 18 2.41 9.8 222 110
Airflow MBh S/T ∆T kW 1350 Amps HI PR LO PR MBh S/T ∆T kW 1217 Amps HI PR LO PR MBh S/T ∆T 1050 kW Amps HI PR LO PR 47.75 0.36 12 2.68 10.9 257 134 47.0 0.35 12 2.67 10.9 255 133 43.4 0.34 13 2.60 10.6 247 129
71 38.99 0.86 23 2.65 10.8 243 114 38.4 0.83 24 2.64 10.7 241 114 35.5 0.80 25 2.57 10.4 234 110
59 38.3 0.76 20 2.63 10.7 241 113 37.8 0.73 21 2.62 10.6 239 112 34.9 0.70 21 2.55 10.3 232 109 40.14 0.77 21 2.72 11.0 262 122 39.6 0.74 22 2.70 11.0 260 121 36.5 0.71 23 2.63 10.7 252 117
63 39.7 0.63 17 2.69 10.9 259 120 39.2 0.61 18 2.68 10.9 257 120 36.1 0.59 19 2.61 10.6 249 116 43.45 0.58 17 2.81 11.4 276 133 42.8 0.56 18 2.79 11.3 274 132 39.5 0.54 19 2.72 11.0 266 128
67 43.5 0.44 13 2.78 11.3 273 132 42.9 0.42 14 2.77 11.2 271 131 39.6 0.41 14 2.69 10.9 263 127
75ºF
IDB = Entering Indoor Dry Bulb Temperature High and low pressures are measured at the liquid and suction service valves.
75
70
IDB
65ºF
46.64 0.38 12 2.90 11.8 288 142 45.9 0.36 13 2.89 11.7 286 141 42.4 0.35 13 2.81 11.4 277 136
71 38.06 0.89 23 2.83 11.7 276 119 37.5 0.85 24 2.81 11.6 274 118 34.6 0.82 25 2.74 11.3 266 115
59 37.4 0.78 20 2.81 11.6 274 118 36.9 0.75 21 2.79 11.5 272 117 34.0 0.72 21 2.72 11.2 264 113 39.19 0.79 21 2.90 12.0 297 126 38.6 0.76 22 2.88 11.9 295 126 35.6 0.73 23 2.80 11.6 286 122
42.42 0.60 17 3.00 12.4 314 138 41.8 0.57 18 2.98 12.3 312 137 38.6 0.55 19 2.90 12.0 303 133
37.13 0.91 23 2.99 12.5 315 125 36.6 0.88 24 2.97 12.4 313 124 33.8 0.84 25 2.89 12.1 303 120
38.23 0.82 21 3.06 12.8 339 133 37.7 0.78 22 3.04 12.7 336 132 34.8 0.76 23 2.96 12.4 326 128
41.38 0.62 17 3.16 13.2 358 145 40.8 0.59 18 3.14 13.1 355 144 37.6 0.57 19 3.06 12.8 345 140
44.41 0.40 12 3.27 13.7 373 154 43.8 0.38 13 3.25 13.6 370 153 40.4 0.37 13 3.17 13.3 359 149
71 35.28 0.95 23 3.12 13.3 354 131 34.8 0.91 24 3.10 13.2 352 130 32.1 0.88 25 3.02 12.9 341 126
59 34.7 0.83 20 3.09 13.2 351 130 34.2 0.80 21 3.07 13.1 348 129 31.5 0.77 21 2.99 12.7 338 125
Shaded area reflects ACCA (TVA) conditions
45.52 0.39 12 3.10 12.8 328 147 44.9 0.37 13 3.08 12.8 325 146 41.4 0.36 13 3.00 12.4 316 142
Outdoor Ambient Temperature 85ºF 95ºF Entering Indoor Wet Bulb Temperature 63 67 71 59 63 67 38.8 42.5 36.5 37.8 41.5 0.65 0.45 0.80 0.67 0.47 17 13 20 17 13 2.87 2.97 2.96 3.03 3.14 11.9 12.3 12.4 12.7 13.1 294 311 312 335 354 125 137 124 132 144 38.2 41.9 36.0 37.3 40.9 0.62 0.43 0.77 0.64 0.45 18 14 21 18 14 2.85 2.95 2.94 3.01 3.12 11.8 12.2 12.3 12.6 13.0 292 309 309 333 352 124 136 123 131 143 35.3 38.6 33.2 34.4 37.7 0.60 0.42 0.74 0.62 0.43 19 14 22 19 14 2.78 2.88 2.87 2.93 3.03 11.5 11.8 12.0 12.3 12.7 284 299 300 323 341 121 132 119 127 138 36.32 0.85 21 3.19 13.6 381 139 35.8 0.81 22 3.17 13.5 378 138 33.0 0.78 23 3.09 13.2 367 134
63 36.0 0.70 17 3.17 13.5 377 138 35.4 0.67 18 3.15 13.4 375 137 32.7 0.64 18 3.06 13.0 363 133 39.31 0.64 17 3.31 14.1 402 152 38.7 0.62 18 3.28 14.0 400 151 35.8 0.59 19 3.20 13.6 388 146
67 39.4 0.48 13 3.28 14.0 398 150 38.8 0.46 14 3.26 13.9 396 149 35.8 0.45 14 3.17 13.5 384 145
105ºF
32.68 0.96 21 3.24 14.1 391 135 32.2 0.92 22 3.22 14.0 389 134 29.7 0.88 23 3.13 13.6 377 130
59 32.1 0.84 18 3.21 14.0 387 134 31.7 0.81 19 3.19 13.9 385 133 29.2 0.78 20 3.10 13.5 373 129 33.64 0.86 20 3.31 14.4 421 144 33.1 0.82 21 3.29 14.4 418 143 30.6 0.79 21 3.20 14.0 406 139
63 33.3 0.70 16 3.28 14.3 417 143 32.8 0.67 17 3.26 14.2 414 142 30.3 0.65 17 3.18 13.8 401 137 36.42 0.65 16 3.43 14.9 445 157 35.9 0.62 17 3.41 14.8 442 156 33.1 0.60 17 3.32 14.4 428 151
67 36.5 0.49 12 3.40 14.8 440 156 35.9 0.47 13 3.38 14.7 437 155 33.2 0.45 13 3.29 14.3 424 150 39.08 0.42 11 3.55 15.5 464 167 38.5 0.40 12 3.53 15.4 461 166 35.5 0.38 12 3.43 15.0 447 161
71 -
kW = Total system power Amps = outdoor unit amps (comp.+fan)
42.19 0.41 12 3.42 14.6 420 162 41.6 0.40 12 3.40 14.5 417 161 38.4 0.38 13 3.31 14.1 404 156
71 -
115ºF
Product Specifications
Expanded Cooling Data — DSXC160601B* / CA*F4961*6A*+TXV / MBVC2000**-1** Low Stage
SS-DSXC16
SS-DSXC16
www.goodmanmfg.com 44.13 0.83 25 2.64 10.7 251 128 43.5 0.80 26 2.62 10.7 249 127 40.1 0.77 27 2.56 10.4 242 124
MBh 41.34 42.14 S/T 0.96 0.92 ∆T 27 27 kW 2.50 2.55 Amps 10.1 10.4 HI PR 221 238 LO PR 110 118 MBh 40.7 41.5 S/T 0.92 0.89 ∆T 28 28 kW 2.48 2.54 Amps 10.1 10.3 HI PR 219 236 LO PR 110 117 MBh 37.6 38.3 S/T 0.88 0.85 ∆T 29 29 kW 2.42 2.47 Amps 9.8 10.0 HI PR 213 229 LO PR 106 113
1050
1217
1350
67 44.35 0.70 21 2.62 10.6 249 127 43.7 0.67 22 2.60 10.6 247 126 40.3 0.64 23 2.53 10.3 239 122
Airflow 59 63 MBh 40.63 41.51 S/T 0.91 0.86 ∆T 25 24 kW 2.47 2.53 1350 Amps 10.1 10.3 HI PR 219 235 LO PR 109 116 MBh 40.0 40.9 S/T 0.88 0.82 ∆T 26 25 kW 2.46 2.52 1217 Amps 10.0 10.2 HI PR 217 234 LO PR 109 116 MBh 36.9 37.8 S/T 0.84 0.79 ∆T 27 26 1050 kW 2.40 2.45 Amps 9.7 10.0 HI PR 211 227 LO PR 105 112 47.08 0.68 22 2.73 11.1 262 137 46.4 0.65 23 2.71 11.1 260 136 42.8 0.63 23 2.64 10.8 252 132
40.38 0.99 27 2.70 11.0 248 117 39.8 0.95 29 2.68 10.9 246 116 36.7 0.92 29 2.62 10.6 239 112
41.16 0.96 27 2.76 11.2 267 124 40.5 0.92 28 2.75 11.2 265 123 37.4 0.88 29 2.67 10.9 257 120
71 59 63 47.41 39.68 40.55 0.52 0.95 0.89 17 26 25 2.70 2.68 2.74 11.0 10.9 11.1 259 245 264 135 116 123 46.7 39.1 39.9 0.50 0.91 0.85 18 27 26 2.69 2.66 2.72 11.0 10.8 11.1 257 244 262 134 115 122 43.1 36.1 36.9 0.48 0.87 0.82 18 28 26 2.62 2.59 2.65 10.7 10.5 10.8 250 236 254 130 111 118 43.11 0.86 25 2.86 11.6 282 136 42.5 0.83 27 2.84 11.5 280 135 39.2 0.80 27 2.77 11.2 271 131
67 43.32 0.72 21 2.83 11.5 279 134 42.7 0.69 22 2.81 11.4 277 133 39.4 0.67 23 2.74 11.1 269 129
75ºF
IDB = Entering Indoor Dry Bulb Temperature High and low pressures are measured at the liquid and suction service valves.
85
80
IDB
65ºF
45.99 0.70 22 2.96 12.0 294 144 45.3 0.67 23 2.94 12.0 292 143 41.8 0.65 24 2.86 11.6 283 139
39.41 1.00 27 2.88 11.9 282 121 38.8 0.98 29 2.86 11.8 280 120 35.8 0.94 30 2.79 11.5 272 117
71 59 46.31 38.74 0.54 0.97 17 26 2.93 2.86 11.9 11.8 291 279 143 120 45.6 38.2 0.52 0.93 18 27 2.91 2.84 11.8 11.7 289 277 142 119 42.1 35.2 0.50 0.90 18 28 2.84 2.77 11.5 11.4 280 269 138 116 40.18 0.98 27 2.95 12.2 303 129 39.6 0.94 28 2.93 12.1 301 128 36.5 0.91 29 2.85 11.8 292 124
42.08 0.89 25 3.05 12.6 320 141 41.5 0.85 27 3.03 12.5 318 140 38.3 0.82 27 2.95 12.2 309 136
44.89 0.72 22 3.16 13.1 334 150 44.2 0.69 23 3.14 13.0 332 149 40.8 0.66 24 3.05 12.6 322 145
39.20 1.00 27 3.11 13.0 346 136 38.6 0.97 28 3.09 13.0 343 135 35.6 0.94 29 3.01 12.6 333 131
41.05 0.92 26 3.22 13.5 365 148 40.4 0.88 27 3.20 13.4 362 147 37.3 0.85 28 3.12 13.0 352 143
43.80 0.74 22 3.33 14.0 381 158 43.1 0.71 23 3.31 13.9 378 157 39.8 0.69 24 3.22 13.5 367 152
71 44.11 0.57 17 3.30 13.9 377 156 43.5 0.55 18 3.28 13.8 374 155 40.1 0.53 19 3.20 13.4 363 150 36.53 1.00 25 3.18 13.6 361 134 36.0 1.00 27 3.16 13.5 359 133 33.2 1.00 29 3.07 13.1 348 129
59 35.90 1.00 24 3.15 13.4 358 132 35.4 1.00 27 3.13 13.3 355 131 32.6 0.96 27 3.05 13.0 345 127
Shaded area reflects AHRI (TVA) conditions
38.45 1.00 26 3.04 12.7 321 127 37.9 1.00 29 3.02 12.7 319 127 35.0 0.97 30 2.94 12.3 309 123
Outdoor Ambient Temperature 85ºF 95ºF Entering Indoor Wet Bulb Temperature 63 67 71 59 63 67 39.58 42.29 45.21 37.79 38.62 41.26 0.91 0.74 0.55 1.00 0.94 0.77 25 21 17 26 25 22 2.92 3.02 3.13 3.01 3.08 3.19 12.1 12.5 13.0 12.6 12.9 13.4 300 317 331 318 342 361 128 139 149 126 134 147 39.0 41.7 44.5 37.2 38.0 40.6 0.87 0.71 0.53 0.96 0.90 0.73 26 22 18 27 26 23 2.90 3.00 3.11 3.00 3.07 3.17 12.0 12.4 12.9 12.5 12.8 13.3 298 315 329 316 340 359 127 139 148 125 133 146 36.0 38.5 41.1 34.4 35.1 37.5 0.84 0.68 0.51 0.93 0.87 0.71 27 23 18 28 27 23 2.83 2.93 3.03 2.92 2.99 3.09 11.7 12.1 12.5 12.2 12.5 12.9 289 306 319 306 330 348 123 134 143 122 129 141 37.24 1.00 25 3.25 13.9 389 142 36.7 1.00 28 3.23 13.8 386 141 33.9 0.97 29 3.15 13.4 374 137
63 36.69 0.98 24 3.22 13.8 385 141 36.1 0.93 26 3.20 13.7 382 140 33.4 0.90 26 3.12 13.3 371 135 39.00 0.95 25 3.36 14.4 411 155 38.4 0.91 26 3.34 14.3 408 154 35.5 0.88 27 3.25 13.9 395 149
67 39.20 0.79 21 3.33 14.2 406 154 38.6 0.76 22 3.31 14.1 404 152 35.6 0.73 23 3.23 13.7 392 148
105ºF
33.84 1.00 23 3.29 14.4 399 138 33.3 1.00 25 3.27 14.3 396 137 30.8 1.00 27 3.19 13.9 385 133
59 33.26 1.00 23 3.26 14.2 395 137 32.8 1.00 25 3.24 14.1 392 136 30.2 0.97 26 3.16 13.7 381 132 34.49 1.00 23 3.37 14.7 430 147 34.0 1.00 26 3.35 14.6 427 146 31.4 0.98 27 3.26 14.2 414 142
63 33.98 0.98 23 3.34 14.6 425 145 33.5 0.94 24 3.32 14.5 422 144 30.9 0.91 25 3.23 14.1 410 140 36.13 0.96 24 3.49 15.2 454 160 35.6 0.92 25 3.47 15.1 450 159 32.9 0.88 25 3.38 14.7 437 155
67 36.31 0.80 20 3.46 15.1 449 159 35.8 0.77 21 3.44 15.0 446 158 33.0 0.74 21 3.35 14.6 433 153 38.54 0.78 20 3.61 15.8 473 171 38.0 0.74 21 3.59 15.7 470 170 35.0 0.72 22 3.49 15.3 456 165
71 38.81 0.60 16 3.58 15.6 468 169 38.2 0.57 17 3.56 15.5 465 168 35.3 0.55 17 3.46 15.1 451 163
kW = Total system power Amps = outdoor unit amps (comp.+fan)
41.61 0.77 22 3.48 14.9 428 165 41.0 0.74 23 3.46 14.8 425 164 37.8 0.71 24 3.37 14.4 412 159
71 41.90 0.59 17 3.45 14.8 424 164 41.3 0.57 18 3.43 14.7 421 162 38.1 0.55 18 3.34 14.3 408 158
115ºF
Product Specifications
Expanded Cooling Data — DSXC160601B*/CA*F4961*6A*+TXV / MBVC2000**-1** Low Stage (cont.)
17
18
www.goodmanmfg.com
1575
1800
2025
67 63.4 0.43 12 3.77 14.9 262 121 61.6 0.41 13 3.74 14.8 260 120 56.8 0.40 13 3.65 14.4 252 116 63.30 0.57 16 3.81 15.0 265 122 61.5 0.55 17 3.78 14.9 262 121 56.7 0.53 17 3.68 14.5 254 117
MBh 56.80 58.48 S/T 0.84 0.76 ∆T 22 20 kW 3.60 3.68 Amps 14.2 14.6 HI PR 233 251 LO PR 105 112 MBh 55.1 56.8 S/T 0.81 0.72 ∆T 23 21 kW 3.57 3.65 Amps 14.1 14.4 HI PR 231 248 LO PR 104 111 MBh 50.9 52.4 S/T 0.78 0.69 ∆T 23 21 kW 3.48 3.56 Amps 13.7 14.0 HI PR 224 241 LO PR 101 108
59 55.9 0.74 19 3.57 14.1 231 104 54.2 0.71 20 3.54 13.9 229 103 50.1 0.68 20 3.45 13.6 222 100
63 57.9 0.62 16 3.65 14.4 248 111 56.2 0.59 17 3.62 14.3 246 110 51.9 0.57 17 3.53 13.9 239 106
Airflow MBh S/T ∆T kW 2025 Amps HI PR LO PR MBh S/T ∆T kW 1800 Amps HI PR LO PR MBh S/T ∆T 1575 kW Amps HI PR LO PR 67.94 0.37 11 3.94 15.6 276 130 66.0 0.35 12 3.90 15.5 274 129 60.9 0.34 12 3.80 15.0 265 125
71 55.48 0.88 22 3.90 15.4 262 111 53.9 0.84 23 3.87 15.3 259 110 49.7 0.81 23 3.77 14.8 251 107
59 54.6 0.77 19 3.86 15.2 259 110 53.0 0.73 20 3.83 15.1 256 109 48.9 0.71 20 3.73 14.7 249 106 57.12 0.78 20 3.99 15.8 282 118 55.5 0.75 21 3.95 15.6 279 117 51.2 0.72 22 3.85 15.2 270 114
63 56.5 0.64 17 3.95 15.6 279 117 54.9 0.61 17 3.92 15.5 276 116 50.7 0.59 17 3.82 15.0 268 112 61.83 0.59 17 4.12 16.3 297 129 60.0 0.57 17 4.09 16.2 294 128 55.4 0.55 18 3.98 15.7 286 124
67 62.0 0.45 13 4.09 16.2 294 128 60.1 0.43 13 4.05 16.0 291 127 55.5 0.41 13 3.95 15.6 283 123
75ºF
IDB = Entering Indoor Dry Bulb Temperature High and low pressures are measured at the liquid and suction service valves.
75
70
IDB
65ºF
66.36 0.38 11 4.27 16.9 310 138 64.4 0.36 12 4.23 16.8 307 136 59.5 0.35 12 4.12 16.3 298 132
71 54.16 0.90 22 4.16 16.8 298 116 52.6 0.86 23 4.12 16.6 295 114 48.5 0.83 23 4.02 16.1 286 111
59 53.3 0.79 19 4.12 16.6 295 114 51.7 0.75 20 4.09 16.5 292 113 47.7 0.73 20 3.98 16.0 283 110 55.76 0.80 20 4.26 17.2 320 123 54.1 0.77 21 4.22 17.0 317 122 50.0 0.74 22 4.11 16.5 308 118
60.36 0.61 17 4.40 17.8 338 134 58.6 0.58 17 4.36 17.6 335 133 54.1 0.56 18 4.25 17.1 325 129
52.84 0.93 22 4.39 18.0 339 121 51.3 0.88 23 4.35 17.8 336 120 47.3 0.85 24 4.24 17.3 326 117
54.40 0.83 20 4.49 18.4 365 129 52.8 0.79 21 4.45 18.2 361 128 48.8 0.76 22 4.34 17.7 350 124
58.89 0.63 17 4.65 19.0 385 141 57.2 0.60 17 4.61 18.9 381 140 52.8 0.58 18 4.49 18.3 370 135
63.20 0.40 12 4.81 19.8 402 150 61.4 0.38 12 4.77 19.6 398 149 56.6 0.37 12 4.64 19.0 386 144
71 50.20 0.96 22 4.59 19.1 381 127 48.7 0.92 23 4.55 19.0 378 126 45.0 0.88 23 4.43 18.4 366 122
59 49.4 0.85 19 4.55 19.0 377 126 47.9 0.81 20 4.51 18.8 374 125 44.2 0.78 20 4.39 18.2 363 121
Shaded area reflects ACCA (TVA) conditions
64.78 0.39 12 4.56 18.5 353 143 62.9 0.37 12 4.52 18.3 349 142 58.1 0.36 12 4.40 17.8 339 137
Outdoor Ambient Temperature 85ºF 95ºF Entering Indoor Wet Bulb Temperature 63 67 71 59 63 67 55.2 60.5 52.0 53.9 59.0 0.66 0.46 0.82 0.68 0.47 17 13 19 17 13 4.22 4.36 4.35 4.45 4.61 17.0 17.6 17.8 18.2 18.9 317 335 336 361 381 122 133 120 128 140 53.6 58.7 50.4 52.3 57.3 0.63 0.44 0.78 0.65 0.45 17 13 20 17 13 4.18 4.33 4.31 4.41 4.57 16.9 17.4 17.6 18.1 18.7 314 331 332 357 377 120 132 119 127 138 49.5 54.2 46.6 48.3 52.9 0.61 0.42 0.75 0.63 0.43 18 13 20 18 13 4.07 4.21 4.20 4.30 4.45 16.4 16.9 17.1 17.5 18.1 304 321 322 347 366 117 128 115 123 134 51.68 0.86 20 4.70 19.6 410 135 50.2 0.82 21 4.65 19.4 406 134 46.3 0.79 21 4.53 18.9 394 130
63 51.2 0.71 16 4.65 19.4 406 134 49.7 0.67 17 4.61 19.2 402 133 45.8 0.65 17 4.49 18.7 390 129 55.94 0.65 17 4.86 20.3 433 148 54.3 0.62 17 4.82 20.1 429 146 50.1 0.60 18 4.69 19.5 416 142
67 56.1 0.49 12 4.82 20.1 429 146 54.4 0.47 13 4.77 19.9 425 145 50.2 0.45 13 4.65 19.3 412 140
105ºF
46.50 0.97 20 4.76 20.3 421 132 45.1 0.93 21 4.71 20.1 417 130 41.7 0.89 22 4.59 19.5 405 126
59 45.7 0.85 18 4.71 20.1 417 130 44.4 0.81 18 4.67 19.9 413 129 41.0 0.78 19 4.55 19.4 401 125 47.87 0.87 19 4.87 20.8 453 140 46.5 0.83 20 4.83 20.6 449 139 42.9 0.80 20 4.70 20.0 435 134
63 47.4 0.71 15 4.83 20.6 449 139 46.0 0.68 16 4.78 20.4 444 137 42.5 0.66 16 4.66 19.8 431 133 51.82 0.66 15 5.04 21.5 479 153 50.3 0.63 16 5.00 21.3 474 151 46.4 0.60 16 4.86 20.7 460 147
67 51.9 0.49 12 4.99 21.3 474 151 50.4 0.47 12 4.95 21.1 469 150 46.5 0.45 12 4.82 20.5 455 145 55.62 0.42 11 5.22 22.4 499 163 54.0 0.40 11 5.17 22.2 494 161 49.8 0.39 11 5.03 21.5 480 156
71 -
kW = Total system power Amps = outdoor unit amps (comp.+fan)
60.04 0.42 11 5.03 21.1 452 157 58.3 0.40 12 4.99 20.9 447 156 53.8 0.39 12 4.85 20.3 434 151
71 -
115ºF
Product Specifications
Expanded Cooling Data — DSXC160601B* / CA*F4961*6A*+TXV / MBVC2000**-1** High Stage
SS-DSXC16
SS-DSXC16
www.goodmanmfg.com 62.80 0.85 24 3.87 15.3 270 125 61.0 0.81 25 3.84 15.2 268 123 56.3 0.78 26 3.74 14.8 260 120
MBh 58.82 59.96 S/T 0.97 0.94 ∆T 26 26 kW 3.66 3.75 Amps 14.5 14.8 HI PR 238 256 LO PR 107 114 MBh 57.1 58.2 S/T 0.93 0.89 ∆T 27 27 kW 3.63 3.72 Amps 14.3 14.7 HI PR 236 253 LO PR 106 113 MBh 52.7 53.7 S/T 0.89 0.86 ∆T 27 27 kW 3.54 3.62 Amps 13.9 14.3 HI PR 228 246 LO PR 103 110
1575
1800
2025
67 63.11 0.71 20 3.84 15.2 268 123 61.3 0.67 21 3.81 15.1 265 122 56.6 0.65 21 3.71 14.6 257 119
Airflow 59 63 MBh 57.81 59.07 S/T 0.93 0.87 ∆T 24 23 kW 3.63 3.72 2025 Amps 14.3 14.7 HI PR 236 253 LO PR 106 113 MBh 56.1 57.4 S/T 0.88 0.83 ∆T 25 24 kW 3.60 3.68 1800 Amps 14.2 14.6 HI PR 233 251 LO PR 105 112 MBh 51.8 52.9 S/T 0.85 0.80 ∆T 26 25 1575 kW 3.51 3.59 Amps 13.8 14.2 HI PR 226 243 LO PR 102 109 67.00 0.69 21 4.01 15.9 282 133 65.0 0.65 22 3.97 15.8 279 131 60.0 0.63 22 3.87 15.3 271 128
57.45 1.00 26 3.97 15.7 267 113 55.8 0.96 27 3.93 15.5 264 112 51.5 0.93 28 3.83 15.1 256 109
58.57 0.97 26 4.06 16.1 287 121 56.9 0.93 27 4.02 15.9 284 119 52.5 0.89 27 3.92 15.5 276 116
71 59 63 67.47 56.47 57.70 0.53 0.96 0.90 16 25 24 3.97 3.93 4.02 15.8 15.5 15.9 279 264 284 131 112 119 65.5 54.8 56.0 0.50 0.92 0.86 17 26 25 3.94 3.90 3.99 15.6 15.4 15.8 276 262 282 130 111 118 60.5 50.6 51.7 0.49 0.88 0.83 17 26 25 3.84 3.80 3.88 15.2 15.0 15.3 268 254 273 126 108 115 61.34 0.88 24 4.20 16.6 303 132 59.6 0.84 25 4.16 16.5 300 130 55.0 0.81 26 4.05 16.0 291 127
67 61.65 0.73 21 4.16 16.5 300 130 59.9 0.70 21 4.12 16.3 297 129 55.2 0.67 22 4.02 15.9 288 125
75ºF
IDB = Entering Indoor Dry Bulb Temperature High and low pressures are measured at the liquid and suction service valves.
85
80
IDB
65ºF
65.44 0.71 21 4.34 17.3 316 140 63.5 0.68 22 4.30 17.1 313 139 58.6 0.65 22 4.19 16.6 304 135
56.09 1.00 25 4.23 17.1 304 118 54.5 0.98 27 4.20 16.9 301 117 50.3 0.95 28 4.09 16.4 292 113
71 59 65.90 55.12 0.55 1.00 16 25 4.30 4.20 17.1 16.9 313 301 139 117 64.0 53.5 0.52 0.94 17 26 4.27 4.16 16.9 16.8 310 298 138 116 59.1 49.4 0.50 0.91 17 26 4.16 4.05 16.5 16.3 301 289 133 112 57.17 1.00 26 4.33 17.5 327 125 55.5 0.95 27 4.29 17.3 323 124 51.2 0.92 27 4.18 16.9 314 120
59.88 0.90 24 4.48 18.1 345 137 58.1 0.86 25 4.44 17.9 342 136 53.7 0.83 26 4.33 17.4 331 132
63.88 0.73 21 4.64 18.8 360 146 62.0 0.70 22 4.60 18.6 356 144 57.2 0.67 22 4.48 18.1 346 140
55.78 1.00 25 4.57 18.8 372 132 54.2 0.98 27 4.53 18.6 368 130 50.0 0.95 28 4.41 18.1 357 127
58.42 0.93 25 4.73 19.4 393 144 56.7 0.89 26 4.69 19.2 389 142 52.3 0.85 26 4.57 18.7 377 138
62.32 0.75 21 4.90 20.2 410 153 60.5 0.72 22 4.86 20.0 406 152 55.8 0.69 23 4.73 19.4 394 147
71 62.76 0.58 17 4.86 20.0 406 152 60.9 0.55 17 4.81 19.8 402 150 56.2 0.53 18 4.69 19.2 390 146 51.98 1.00 24 4.67 19.5 389 130 50.5 1.00 26 4.63 19.3 385 129 46.6 1.00 27 4.51 18.8 374 125
59 51.09 1.00 23 4.63 19.3 385 129 49.6 1.00 25 4.59 19.1 381 127 45.8 0.97 26 4.47 18.6 370 123
Shaded area reflects AHRI (TVA) conditions
54.72 1.00 25 4.47 18.3 346 124 53.1 1.00 27 4.43 18.1 342 123 49.0 0.98 28 4.31 17.6 332 119
Outdoor Ambient Temperature 85ºF 95ºF Entering Indoor Wet Bulb Temperature 63 67 71 59 63 67 56.33 60.18 64.33 53.78 54.95 58.71 0.92 0.75 0.56 1.00 0.95 0.78 24 21 16 24 24 21 4.29 4.44 4.60 4.43 4.53 4.69 17.3 17.9 18.6 18.1 18.6 19.2 323 342 356 342 368 389 124 136 144 123 130 142 54.7 58.4 62.5 52.2 53.4 57.0 0.88 0.72 0.54 0.97 0.91 0.74 25 21 17 26 25 22 4.26 4.40 4.56 4.39 4.49 4.65 17.2 17.8 18.5 18.0 18.4 19.0 320 338 353 339 365 385 123 134 143 121 129 141 50.5 53.9 57.6 48.2 49.2 52.6 0.85 0.69 0.52 0.93 0.88 0.71 25 22 17 26 25 22 4.15 4.29 4.44 4.28 4.38 4.53 16.7 17.3 17.9 17.4 17.9 18.5 311 328 342 329 354 374 119 130 139 118 125 137 52.99 1.00 24 4.78 20.0 419 138 51.4 1.00 26 4.74 19.8 414 137 47.5 0.98 27 4.61 19.2 402 133
63 52.20 1.00 24 4.74 19.8 414 137 50.7 0.94 24 4.70 19.6 410 135 46.8 0.91 25 4.57 19.1 398 131 55.50 0.96 24 4.95 20.7 442 151 53.9 0.92 25 4.90 20.5 438 149 49.7 0.89 26 4.77 19.9 425 145
67 55.77 0.81 20 4.90 20.5 438 149 54.2 0.77 21 4.86 20.3 433 148 50.0 0.74 22 4.73 19.7 420 143
105ºF
48.15 1.00 22 4.84 20.7 430 134 46.7 1.00 24 4.80 20.5 426 133 43.1 1.00 25 4.67 19.9 413 129
59 47.32 1.00 21 4.80 20.5 426 133 45.9 1.00 23 4.76 20.3 421 132 42.4 0.98 24 4.63 19.7 409 128 49.08 1.00 22 4.96 21.2 463 143 47.7 1.00 24 4.91 21.0 458 141 44.0 0.99 25 4.78 20.4 444 137
63 48.36 1.00 22 4.91 21.0 458 141 46.9 0.95 23 4.87 20.8 453 140 43.3 0.92 23 4.74 20.2 440 136 51.41 0.97 23 5.13 22.0 488 156 49.9 0.93 24 5.09 21.7 484 154 46.1 0.89 24 4.95 21.1 469 150
67 51.66 0.81 19 5.09 21.7 484 154 50.2 0.77 20 5.04 21.5 479 153 46.3 0.75 20 4.91 20.9 464 148 54.84 0.79 20 5.31 22.8 509 166 53.2 0.75 20 5.27 22.6 504 164 49.1 0.72 21 5.13 21.9 489 159
71 55.23 0.61 15 5.27 22.6 504 164 53.6 0.58 16 5.22 22.4 499 163 49.5 0.56 16 5.08 21.7 484 158
kW = Total system power Amps = outdoor unit amps (comp.+fan)
59.21 0.78 21 5.12 21.5 461 161 57.5 0.75 22 5.08 21.3 457 159 53.1 0.72 22 4.94 20.7 443 154
71 59.62 0.60 16 5.08 21.3 457 159 57.9 0.57 17 5.03 21.1 452 157 53.4 0.55 17 4.90 20.5 438 153
115ºF
Product Specifications
Expanded Cooling Data — DSXC160601B*/CA*F4961*6A*+TXV / MBVC2000**-1** High Stage (cont.)
19
Product Specifications
AHRI Ratings Indoor Units
Outdoor Unit
Coils/Air Handlers
Cooling Ratings Furnaces
AHRI #
12.50
830
5924460
14.50
12.00
820
5357193
16.00
13.00
820
4392752 5038827
Sens.¹
SEER²
EER³
AVPTC30C14A*
23,000
16,800
16.00
CA*F3636*6D*+EEP+TXV
24,000
17,600
CA*F3636*6D*+MBVC1200**-1A*+TXV
24,000
17,600
CA*F3636*6D*+TXV
G*VC80604B*B*
24,000
17,600
16.00
13.00
820
CA*F3636*6D*+TXV
A*VC80604B*B*
24,000
17,600
16.00
13.00
820
5039091
CA*F3636*6D*+TXV
G*VC950453BXB*
24,000
17,600
16.00
13.00
820
5620613
CA*F3636*6D*+TXV
G*VC950704CXB*
24,000
17,600
16.00
13.00
800
5620620
CA*F3636*6D*+TXV
A*VC950714CXB*
24,000
17,600
16.00
13.00
800
5620626
CA*F3636*6D*+TXV
G*VC950714CXB*
24,000
17,600
16.00
13.00
800
5620627
CA*F3636*6D*+TXV
G*VM960603BXB*
24,000
17,600
16.00
13.00
820
5620630
CA*F3636*6D*+TXV
A*VM960604CXB*
24,000
17,600
16.00
13.00
800
5620635
CA*F3636*6D*+TXV
G*VM960604CXB*
24,000
17,600
16.00
13.00
800
5620636
CA*F3636*6D*+TXV
A*VC950453BXB*
24,000
17,600
16.00
13.00
820
6497619
CA*F3636*6D*+TXV
A*VC950704CXB*
24,000
17,600
16.00
13.00
800
6497620
CA*F3636*6D*+TXV
A*VM960603BXB*
24,000
17,600
16.00
13.00
820
6497621
CA*F3636*6D*+TXV
ADVC80603B*B*
24,000
17,600
16.00
13.00
810
6497622
24,000
17,600
14.50
12.00
820
5357194
CA*F3642*6D*+TXV
A*VC80604B*B*
24,000
17,600
16.00
13.00
820
5039010
CA*F3642*6D*+TXV
G*VC80604B*B*
24,000
17,600
16.00
13.00
820
5039220
CA*F3642*6D*+TXV
G*VC950453BXB*
24,000
17,600
16.00
13.00
820
5620614
CA*F3642*6D*+TXV
G*VC950704CXB*
24,000
17,600
16.00
13.00
800
5620621
CA*F3642*6D*+TXV
A*VC950714CXB*
24,000
17,600
16.00
13.00
800
5620628
CA*F3642*6D*+TXV
G*VC950714CXB*
24,000
17,600
16.00
13.00
800
5620629
CA*F3642*6D*+TXV
G*VM960603BXB*
24,000
17,600
16.00
13.00
820
5620631
CA*F3642*6D*+TXV
A*VM960604CXB*
24,000
17,600
16.00
13.00
800
5620637
CA*F3642*6D*+TXV
G*VM960604CXB*
24,000
17,600
16.00
13.00
800
5620638
CA*F3642*6D*+TXV
A*VC950704CXB*
24,000
17,600
16.00
13.00
800
6497623
CA*F3642*6D*+TXV
A*VC950905CXB*
24,000
17,600
16.00
13.00
800
6497624
CA*F3642*6D*+TXV
A*VC950915DXB*
24,000
17,600
16.00
13.00
800
6497625
CA*F3642*6D*+TXV
A*VM960805CXB*
24,000
17,600
16.00
13.00
800
6497626
CA*F3642*6D*+TXV
A*VM960805DXB*
24,000
17,600
16.00
13.00
800
6497627
CA*F3642*6D*+TXV
G*VC950905CXB*
24,000
17,600
16.00
13.00
800
6497628
CA*F3642*6D*+TXV
G*VC950915DXB*
24,000
17,600
16.00
13.00
800
6497629
CA*F3642*6D*+TXV
G*VM960805CXB*
24,000
17,600
16.00
13.00
800
6497630
CA*F3642*6D*+TXV
G*VM960805DXB*
24,000
17,600
16.00
13.00
800
6497631
24,000
17,600
14.50
12.00
820
5357195
CA*F3642*6D*+EEP+TXV
DSXC16 0241A*
CFM
Total¹
CHPF3636B6C*+EEP+TXV CHPF3636B6C*+MBVC1200**-1A*+TXV
24,000
17,600
16.00
13.00
820
3653937
CHPF3636B6C*+TXV
G*VC80604B*B*
24,000
17,600
16.00
13.00
820
5039090
CHPF3636B6C*+TXV
A*VC80604B*B*
24,000
17,600
16.00
13.00
820
5039103
CHPF3636B6C*+TXV
G*VC950453BXB*
24,000
17,600
16.00
13.00
820
5620615
CHPF3636B6C*+TXV
G*VM960603BXB*
24,000
17,600
16.00
13.00
820
5620632
CHPF3636B6C*+TXV
A*VM960604CXB*
24,000
17,600
16.00
12.50
800
5620639
CHPF3636B6C*+TXV
G*VM960604CXB*
24,000
17,600
16.00
12.50
800
5620640
CHPF3636B6C*+TXV
A*VC950453BXB*
24,000
17,600
16.00
13.00
820
6497632
CHPF3636B6C*+TXV
A*VC950704CXB*
24,000
17,600
16.00
12.50
800
6497633
See Notes on Page 29.
20
www.goodmanmfg.com
SS-DSXC16
Product Specifications
AHRI Ratings (cont.) Indoor Units
Outdoor Unit
DSXC16 0241A* (cont.)
Coils/Air Handlers
Cooling Ratings Furnaces
Sens.¹
SEER²
EER³
24,000
17,600
16.00
13.00
CFM
AHRI #
820
6497634
CHPF3636B6C*+TXV
A*VM960603BXB*
CHPF3636B6C*+TXV
G*VC950704CXB*
24,000
17,600
16.00
12.50
800
6497635
CHPF3642C6C*+TXV
G*VC950453BXB*
24,000
17,600
16.00
13.00
820
5620616
CHPF3642C6C*+TXV
G*VC950704CXB*
24,000
17,600
16.00
13.00
800
5620622
CHPF3642C6C*+TXV
G*VM960603BXB*
24,000
17,600
16.00
13.00
820
5620633
CHPF3642C6C*+TXV
A*VM960604CXB*
24,000
17,600
16.00
13.00
800
5620641
CHPF3642C6C*+TXV
G*VM960604CXB*
24,000
17,600
16.00
13.00
800
5620642
CHPF3642C6C*+TXV
A*VC950453BXB*
24,000
17,600
16.00
13.00
820
6497636
CHPF3642C6C*+TXV
A*VC950704CXB*
24,000
17,600
16.00
13.00
800
6497637
CHPF3642C6C*+TXV
A*VM960603BXB*
24,000
17,600
16.00
13.00
820
6497638
CHPF3743C6B*+TXV
G*VC950453BXB*
24,000
17,600
16.00
12.50
820
5620617
CHPF3743C6B*+TXV
G*VC950704CXB*
24,000
17,600
16.00
12.50
800
5620623
CHPF3743C6B*+TXV
G*VM960603BXB*
24,000
17,600
16.00
12.50
820
5620634
CHPF3743C6B*+TXV
A*VM960604CXB*
24,000
17,600
16.00
12.50
800
5620643
CHPF3743C6B*+TXV
G*VM960604CXB*
24,000
17,600
16.00
12.50
800
5620644
CHPF3743C6B*+TXV
A*VC950453BXB*
24,000
17,600
16.00
12.50
820
6497639
CHPF3743C6B*+TXV
A*VC950704CXB*
24,000
17,600
16.00
12.50
800
6497640
CHPF3743C6B*+TXV
A*VM960603BXB*
24,000
17,600
16.00
12.50
820
6497641
CSCF3036N6D*+TXV
G*VC950453BXB*
24,000
17,600
15.50
12.50
800
5620618
CSCF3036N6D*+TXV
G*VC950704CXB*
24,000
17,600
16.00
13.00
875
5620624
CSCF3036N6D*+TXV
A*VC80604B*B*
24,000
17,600
16.00
13.00
820
6497642
CSCF3036N6D*+TXV
A*VC950453BXB*
24,000
17,600
15.50
12.50
800
6497643
CSCF3036N6D*+TXV
A*VC950704CXB*
24,000
17,600
16.00
13.00
875
6497644
CSCF3036N6D*+TXV
A*VC950905CXB*
24,000
17,600
16.00
13.00
800
6497645
CSCF3036N6D*+TXV
G*VC80604B*B*
24,000
17,600
16.00
13.00
820
6497646
CSCF3036N6D*+TXV
G*VC950905CXB*
24,000
17,600
16.00
13.00
800
6497647
24,000
17,600
14.50
12.00
820
5357196
CSCF3642N6D*+TXV
G*VC950453BXB*
24,000
17,600
16.00
13.00
800
5620619
CSCF3642N6D*+TXV
G*VC950704CXB*
24,000
17,600
16.00
13.00
875
5620625
CSCF3642N6D*+TXV
A*VC80604B*B*
24,000
17,600
16.00
13.00
820
5948539
CSCF3642N6D*+TXV
G*VC80604B*B*
24,000
17,600
16.00
13.00
820
5948540
CSCF3642N6D*+TXV
A*VC950453BXB*
24,000
17,600
16.00
13.00
800
6497648
CSCF3642N6D*+TXV
A*VC950704CXB*
24,000
17,600
16.00
13.00
875
6497649
CSCF3642N6D*+TXV
A*VC950905CXB*
24,000
17,600
16.00
13.00
800
6497650
CSCF3642N6D*+TXV
G*VC950905CXB*
CSCF3642N6D*+EEP+TXV
24,000
17,600
16.00
13.00
800
6497651
AVPTC42D14A*
35,000
25,200
16.00
12.00
1,200
5924363
AVPTC48D14A*
36,000
25,800
16.00
12.50
1,200
5924364
CA*F3642*6D*+MBVC1600**-1A*+TXV
35,000
25,200
16.00
12.50
1,200
3880067
34,000
24,400
16.00
12.00
1,220
5038810
CA*F3642*6D*+TXV DSXC16 0361A*
Total¹
A*VC80604B*B*
CA*F3642*6D*+TXV
G*VC80604B*B*
34,000
24,400
16.00
12.00
1,220
5039092
CA*F3642*6D*+TXV
G*VC950704CXB*
34,600
24,800
16.00
12.00
1,100
5620651
CA*F3642*6D*+TXV
A*VC950714CXB*
34,600
24,800
16.00
12.00
1,100
5620658
CA*F3642*6D*+TXV
G*VC950714CXB*
34,600
24,800
16.00
12.00
1,100
5620659
CA*F3642*6D*+TXV
A*VC950905CXB*
34,600
24,800
15.50
12.00
1,150
5620664
CA*F3642*6D*+TXV
G*VC950905CXB*
34,600
24,800
15.50
12.00
1,150
5620665
See Notes on Page 29.
SS-DSXC16
www.goodmanmfg.com
21
Product Specifications
AHRI Ratings (cont.) Indoor Units
Outdoor Unit
Coils/Air Handlers CA*F3642*6D*+TXV
DSXC16 0361A* (cont.)
Cooling Ratings Furnaces G*VC951155DXB*
Total¹
Sens.¹
SEER²
EER³
34,600
24,800
16.00
12.30
CFM
AHRI #
1,150
5620683
CA*F3642*6D*+TXV
A*VM960604CXB*
34,600
24,800
16.00
12.00
1,100
5620694
CA*F3642*6D*+TXV
G*VM960604CXB*
34,600
24,800
16.00
12.00
1,100
5620695
CA*F3642*6D*+TXV
A*VM960805CXB*
34,600
24,800
15.50
12.00
1,150
5620708
CA*F3642*6D*+TXV
G*VM960805CXB*
34,600
24,800
15.50
12.00
1,150
5620709
CA*F3642*6D*+TXV
G*VM961005DXB*
34,600
24,800
16.00
12.30
1,150
5620727
CA*F3642*6D*+TXV
G*VM961155DXB*
34,600
24,800
16.00
12.30
1,150
5620735
CA*F3642*6D*+TXV
A*VC80805C*B*
35,000
25,200
16.00
12.50
1,190
6497652
CA*F3642*6D*+TXV
A*VC950453BXB*
34,000
24,400
15.50
12.00
1,130
6497653
CA*F3642*6D*+TXV
A*VC950704CXB*
34,600
24,800
15.50
12.00
1,100
6497654
CA*F3642*6D*+TXV
A*VC950905DXB*
34,600
24,800
16.00
12.25
1,150
6497655
CA*F3642*6D*+TXV
A*VC950915DXB*
34,600
24,800
15.50
12.00
1,150
6497656
CA*F3642*6D*+TXV
A*VC951155DXB*
34,600
24,800
16.00
12.30
1,150
6497657
CA*F3642*6D*+TXV
A*VM960603BXB*
34,000
24,400
15.50
12.00
1,130
6497658
CA*F3642*6D*+TXV
A*VM960805DXB*
34,600
24,800
15.50
12.00
1,150
6497659
CA*F3642*6D*+TXV
A*VM961005DXB*
34,600
24,800
16.00
12.30
1,150
6497660
CA*F3642*6D*+TXV
A*VM961155DXB*
34,600
24,800
16.00
12.30
1,150
6497661
CA*F3642*6D*+TXV
ADVC80603B*B*
34,000
24,400
16.00
12.50
1,190
6497662
CA*F3642*6D*+TXV
ADVC80805C*B*
35,000
25,200
16.00
12.50
1,190
6497663
CA*F3642*6D*+TXV
G*VC80805C*B*
35,000
25,200
16.00
12.50
1,190
6497664
CA*F3642*6D*+TXV
G*VC950453BXB*
34,000
24,400
16.00
12.20
1,130
6497665
CA*F3642*6D*+TXV
G*VC950905DXB*
34,600
24,800
16.00
12.25
1,150
6497666
CA*F3642*6D*+TXV
G*VC950915DXB*
34,600
24,800
15.50
12.00
1,150
6497667
CA*F3642*6D*+TXV
G*VM960603BXB*
34,000
24,400
16.00
12.20
1,130
6497668
CA*F3642*6D*+TXV
G*VM960805DXB*
34,600
24,800
15.50
12.00
1,150
6497669
34,000
24,400
14.50
11.50
1,200
5357197
CA*F3743*6D*+EEP+TXV CA*F3743*6D*+MBVC1600**-1A*+TXV
35,000
25,200
16.00
12.50
1,100
4415027
CA*F3743*6D*+TXV
G*VC91155DXA*
34,600
24,800
15.50
12.20
1,150
4415037
CA*F3743*6D*+TXV
A*VC80604B*B*
34,000
24,400
16.00
12.50
1,220
5038932
CA*F3743*6D*+TXV
G*VC80604B*B*
34,000
24,400
16.00
12.50
1,220
5039113
CA*F3743*6D*+TXV
G*VC950704CXB*
34,600
24,800
16.00
12.30
1,100
5620652
CA*F3743*6D*+TXV
A*VC950714CXB*
34,600
24,800
16.00
12.30
1,100
5620660
CA*F3743*6D*+TXV
G*VC950714CXB*
34,600
24,800
16.00
12.30
1,100
5620661
CA*F3743*6D*+TXV
A*VC950905CXB*
34,600
24,800
16.00
12.00
1,150
5620666
CA*F3743*6D*+TXV
G*VC950905CXB*
34,600
24,800
16.00
12.00
1,150
5620667
CA*F3743*6D*+TXV
G*VC950905DXB*
34,600
24,800
16.00
12.50
1,150
5620674
CA*F3743*6D*+TXV
A*VC950915DXB*
34,600
24,800
16.00
12.50
1,150
5620679
CA*F3743*6D*+TXV
G*VC950915DXB*
34,600
24,800
16.00
12.50
1,150
5620680
CA*F3743*6D*+TXV
G*VC951155DXB*
34,600
24,800
16.00
12.50
1,150
5620684
CA*F3743*6D*+TXV
A*VM960604CXB*
34,600
24,800
16.00
12.50
1,100
5620696
CA*F3743*6D*+TXV
G*VM960604CXB*
34,600
24,800
16.00
12.50
1,100
5620697
CA*F3743*6D*+TXV
A*VM960805CXB*
34,600
24,800
16.00
12.00
1,150
5620710
CA*F3743*6D*+TXV
G*VM960805CXB*
34,600
24,800
16.00
12.00
1,150
5620711
CA*F3743*6D*+TXV
G*VM960805DXB*
34,600
24,800
16.00
12.50
1,150
5620720
CA*F3743*6D*+TXV
G*VM961005DXB*
34,600
24,800
16.00
12.50
1,150
5620728
See Notes on Page 29.
22
www.goodmanmfg.com
SS-DSXC16
Product Specifications
AHRI Ratings (cont.) Indoor Units
Outdoor Unit
Coils/Air Handlers
Cooling Ratings Furnaces
Sens.¹
SEER²
EER³
CFM
AHRI #
CA*F3743*6D*+TXV
G*VM961155DXB*
34,600
24,800
16.00
12.50
1,150
5620736
CA*F3743*6D*+TXV
A*VC950453BXB*
34,000
24,400
15.50
12.00
1,130
5696602
CA*F3743*6D*+TXV
A*VC80805C*B*
34,000
24,400
16.00
12.50
1,190
6497670
CA*F3743*6D*+TXV
A*VC950704CXB*
34,000
24,400
16.00
12.50
1,150
6497671
CA*F3743*6D*+TXV
A*VC950905DXB*
34,000
24,400
16.00
12.50
1,150
6497672
CA*F3743*6D*+TXV
A*VC951155DXB*
34,000
24,400
16.00
12.50
1,150
6497673
CA*F3743*6D*+TXV
A*VM961005DXB*
34,000
24,400
16.00
12.50
1,150
6497674
CA*F3743*6D*+TXV
A*VM961155DXB*
34,000
24,400
16.00
12.50
1,150
6497675
CA*F3743*6D*+TXV
ADVC80805C*B*
34,000
24,400
16.00
12.50
1,190
6497676
CA*F3743*6D*+TXV
G*VC80805C*B*
34,000
24,400
16.00
12.50
1,190
6497677
CA*F3743*6D*+TXV
A*VM960603BXB*
34,000
24,400
15.50
12.00
1,130
6603420
CA*F3743*6D*+TXV
G*VM960603BXB*
34,000
24,400
15.50
12.00
1,130
6603421
35,000
25,200
14.50
11.50
1,200
5357198
CA*F4860*6D*+EEP+TXV
DSXC16 0361A* (cont.)
Total¹
CA*F4860*6D*+TXV
G*VC91155DXA*
35,000
25,200
15.50
12.20
1,100
3880423
CA*F4860*6D*+TXV
A*VC80604B*B*
34,600
24,800
16.00
12.50
1,220
5039011
CA*F4860*6D*+TXV
G*VC80604B*B*
34,600
24,800
16.00
12.50
1,220
5039221
CA*F4860*6D*+TXV
G*VC950453BXB*
34,600
24,800
16.00
12.20
1,130
5620645
CA*F4860*6D*+TXV
G*VC950704CXB*
34,600
24,800
16.00
12.30
1,100
5620653
CA*F4860*6D*+TXV
A*VC950714CXB*
34,600
24,800
16.00
12.30
1,100
5620662
CA*F4860*6D*+TXV
G*VC950714CXB*
34,600
24,800
16.00
12.30
1,100
5620663
CA*F4860*6D*+TXV
G*VC950905CXB*
35,000
25,200
15.50
12.00
1,150
5620668
CA*F4860*6D*+TXV
G*VC950905DXB*
35,000
25,200
16.00
12.50
1,150
5620675
CA*F4860*6D*+TXV
A*VC950915DXB*
35,000
25,200
16.00
12.50
1,150
5620681
CA*F4860*6D*+TXV
G*VC950915DXB*
35,000
25,200
16.00
12.50
1,150
5620682
CA*F4860*6D*+TXV
G*VC951155DXB*
34,600
24,800
16.00
12.50
1,150
5620685
CA*F4860*6D*+TXV
G*VM960603BXB*
34,600
24,800
16.00
12.20
1,130
5620689
CA*F4860*6D*+TXV
A*VM960604CXB*
34,600
24,800
16.00
12.30
1,100
5620698
CA*F4860*6D*+TXV
G*VM960604CXB*
34,600
24,800
16.00
12.30
1,100
5620699
CA*F4860*6D*+TXV
G*VM960805CXB*
35,000
25,200
15.50
12.00
1,150
5620712
CA*F4860*6D*+TXV
G*VM960805DXB*
35,000
25,200
16.00
12.50
1,150
5620721
CA*F4860*6D*+TXV
G*VM961005DXB*
34,600
24,800
16.00
12.50
1,150
5620729
CA*F4860*6D*+TXV
G*VM961155DXB*
34,600
24,800
16.00
12.50
1,150
5620737
CA*F4860*6D*+TXV
A*VC80805C*B*
35,000
25,200
16.00
12.50
1,190
6497678
CA*F4860*6D*+TXV
A*VC950453BXB*
35,000
25,200
16.00
12.20
1,130
6497679
CA*F4860*6D*+TXV
A*VC950704CXB*
34,600
24,800
16.00
12.20
1,100
6497680
CA*F4860*6D*+TXV
A*VC950905CXB*
35,000
25,200
15.50
12.00
1,150
6497681
CA*F4860*6D*+TXV
A*VC950905DXB*
35,000
25,200
16.00
12.50
1,150
6497682
CA*F4860*6D*+TXV
A*VC951155DXB*
35,000
25,200
16.00
12.50
1,150
6497683
CA*F4860*6D*+TXV
A*VM960603BXB*
35,000
25,200
16.00
12.20
1,130
6497684
CA*F4860*6D*+TXV
A*VM960805CXB*
35,000
25,200
15.50
12.00
1,150
6497685
CA*F4860*6D*+TXV
A*VM960805DXB*
35,000
25,200
15.50
12.00
1,150
6497686
CA*F4860*6D*+TXV
A*VM961005DXB*
35,000
25,200
16.00
12.50
1,150
6497687
CA*F4860*6D*+TXV
A*VM961155DXB*
35,000
25,200
16.00
12.50
1,150
6497688
CA*F4860*6D*+TXV
ADVC80805C*B*
35,000
25,200
16.00
12.50
1,190
6497689
CA*F4860*6D*+TXV
G*VC80805C*B*
35,000
25,200
16.00
12.50
1,190
6497690
CA*F4961*6D*+TXV
A*VM960805CXB*
35,000
25,200
16.00
12.50
1,200
5620713
CA*F4961*6D*+TXV
G*VM960805CXB*
35,000
25,200
16.00
12.50
1,200
5620714
CAPT3743*4A*
A*VM960603BXB*
34,000
24,400
15.50
12.00
1,130
6603422
CAPT3743*4A*
G*VM960603BXB*
34,000
24,400
15.50
12.00
1,130
6603423
See Notes on Page 29.
SS-DSXC16
www.goodmanmfg.com
23
Product Specifications
AHRI Ratings (cont.) Indoor Units
Outdoor Unit
Coils/Air Handlers
Cooling Ratings Furnaces
CHPF3642C6C*+MBVC1600**-1A*+TXV CHPF3642C6C*+TXV
G*VC80604B*B*
Sens.¹
SEER²
EER³
CFM
AHRI #
34,600
24,800
16.00
12.50
1,200
3654024
34,000
24,400
15.50
12.00
1,220
5038934
CHPF3642C6C*+TXV
A*VC80604B*B*
34,000
24,400
15.50
12.00
1,220
5039093
CHPF3642C6C*+TXV
G*VC950453BXB*
34,000
24,400
15.50
12.00
1,130
5620646
CHPF3642C6C*+TXV
G*VC950704CXB*
34,600
24,800
16.00
12.00
1,100
5620654
CHPF3642C6C*+TXV
G*VC950905CXB*
34,600
24,800
16.00
12.00
1,150
5620669
CHPF3642C6C*+TXV
G*VM960603BXB*
34,000
24,400
15.50
12.00
1,130
5620690
CHPF3642C6C*+TXV
A*VM960604CXB*
34,600
24,800
16.00
12.00
1,100
5620700
CHPF3642C6C*+TXV
G*VM960604CXB*
34,600
24,800
16.00
12.00
1,100
5620701
CHPF3642C6C*+TXV
G*VM960805CXB*
34,600
24,800
16.00
12.00
1,150
5620715
CHPF3642C6C*+TXV
G*VM960805DXB*
34,600
24,800
16.00
12.50
1,150
5620722
CHPF3642C6C*+TXV
G*VM961005DXB*
34,600
24,800
16.00
12.50
1,150
5620730
CHPF3642C6C*+TXV
G*VM961155DXB*
34,600
24,800
16.00
12.50
1,150
5620738
CHPF3642C6C*+TXV
A*VC950453BXB*
34,000
24,400
15.50
12.00
1,130
5696601
CHPF3642C6C*+TXV
A*VC80805C*B*
34,600
24,800
16.00
12.50
1,190
6497691
CHPF3642C6C*+TXV
A*VC950704CXB*
34,600
24,800
16.00
12.00
1,100
6497692
CHPF3642C6C*+TXV
G*VC80805C*B*
34,600
24,800
16.00
12.50
1,190
6497693
35,000
25,200
16.00
12.80
1,200
3654036
G*VC950905CXB*
34,600
24,800
16.00
12.00
1,150
5620670
CHPF3642D6C*+MBVC2000**-1A*+TXV CHPF3642D6C*+TXV
DSXC16 0361A* (cont.)
Total¹
CHPF3642D6C*+TXV
G*VC950905DXB*
34,600
24,800
16.00
12.50
1,150
5620676
CHPF3642D6C*+TXV
G*VC951155DXB*
34,600
24,800
16.00
12.50
1,150
5620686
CHPF3642D6C*+TXV
G*VM960805CXB*
34,600
24,800
16.00
12.00
1,150
5620716
CHPF3642D6C*+TXV
G*VM960805DXB*
34,600
24,800
16.00
12.50
1,150
5620723
CHPF3642D6C*+TXV
G*VM961005DXB*
34,600
24,800
16.00
12.50
1,150
5620731
CHPF3642D6C*+TXV
G*VM961155DXB*
34,600
24,800
16.00
12.50
1,150
5620739
CHPF3642D6C*+TXV
A*VC950905CXB*
34,600
24,800
16.00
12.00
1,150
6497694
CHPF3642D6C*+TXV
A*VC950905DXB*
34,600
24,800
16.00
12.50
1,150
6497695
CHPF3642D6C*+TXV
A*VC951155DXB*
34,600
24,800
16.00
12.50
1,150
6497696
CHPF3642D6C*+TXV
A*VM960805CXB*
34,600
24,800
16.00
12.00
1,150
6497697
CHPF3642D6C*+TXV
A*VM960805DXB*
34,600
24,800
16.00
12.00
1,150
6497698
CHPF3642D6C*+TXV
A*VM961005DXB*
34,600
24,800
16.00
12.50
1,150
6497699
CHPF3642D6C*+TXV
A*VM961155DXB*
34,600
24,800
16.00
12.50
1,150
6497700
CHPF3743C6B*+EEP+TXV
34,000
24,400
14.50
11.50
1,200
5357199
CHPF3743C6B*+MBVC1600**-1A*+TXV
34,600
24,800
16.00
12.50
1,200
3654042
CHPF3743C6B*+MBVC2000**-1A*+TXV
35,000
25,200
16.00
12.80
1,200
6497701
34,000
24,400
15.50
12.00
1,220
5038935
CHPF3743C6B*+TXV
G*VC80604B*B*
CHPF3743C6B*+TXV
A*VC80604B*B*
34,000
24,400
15.50
12.00
1,220
5039222
CHPF3743C6B*+TXV
G*VC950453BXB*
34,000
24,400
16.00
12.50
1,130
5620647
CHPF3743C6B*+TXV
G*VC950704CXB*
34,600
24,800
16.00
12.00
1,100
5620655
CHPF3743C6B*+TXV
G*VC950905CXB*
34,600
24,800
16.00
12.00
1,150
5620671
CHPF3743C6B*+TXV
G*VM960603BXB*
34,000
24,400
16.00
12.50
1,130
5620691
CHPF3743C6B*+TXV
A*VM960604CXB*
34,600
24,800
16.00
12.00
1,100
5620702
CHPF3743C6B*+TXV
G*VM960604CXB*
34,600
24,800
16.00
12.00
1,100
5620703
CHPF3743C6B*+TXV
G*VM960805CXB*
34,600
24,800
16.00
12.00
1,150
5620717
CHPF3743C6B*+TXV
G*VM960805DXB*
34,600
24,800
16.00
12.50
1,150
5620724
CHPF3743C6B*+TXV
G*VM961005DXB*
34,600
24,800
16.00
12.50
1,150
5620732
CHPF3743C6B*+TXV
G*VM961155DXB*
34,600
24,800
16.00
12.50
1,150
5620740
CHPF3743C6B*+TXV
A*VC80805C*B*
34,600
24,800
16.00
12.50
1,190
6497702
CHPF3743C6B*+TXV
A*VC950453BXB*
34,000
24,400
16.00
12.20
1,130
6497703
See Notes on Page 29.
24
www.goodmanmfg.com
SS-DSXC16
Product Specifications
AHRI Ratings (cont.) Indoor Units
Outdoor Unit
Coils/Air Handlers
Cooling Ratings Furnaces
Sens.¹
SEER²
EER³
CFM
AHRI #
CHPF3743C6B*+TXV
A*VC950704CXB*
34,600
24,800
16.00
12.00
1,100
6497704
CHPF3743C6B*+TXV
A*VC950905CXB*
34,600
24,800
16.00
12.00
1,150
6497705
CHPF3743C6B*+TXV
A*VC950905DXB*
34,600
24,800
16.00
12.50
1,150
6497706
CHPF3743C6B*+TXV
A*VC951155DXB*
34,600
24,800
16.00
12.50
1,150
6497707
CHPF3743C6B*+TXV
A*VM960603BXB*
34,000
24,400
16.00
12.20
1,130
6497708
CHPF3743C6B*+TXV
A*VM960805CXB*
34,600
24,800
16.00
12.00
1,150
6497709
CHPF3743C6B*+TXV
A*VM960805DXB*
34,600
24,800
16.00
12.00
1,150
6497710
CHPF3743C6B*+TXV
A*VM961005DXB*
34,600
24,800
16.00
12.50
1,150
6497711
CHPF3743C6B*+TXV
A*VM961155DXB*
34,600
24,800
16.00
12.50
1,150
6497712
CHPF3743C6B*+TXV
G*VC80805C*B*
34,600
24,800
16.00
12.50
1,190
6497713
35,000
25,200
16.00
12.80
1,200
3654056
34,000
24,400
16.00
12.50
1,220
5038828
CHPF3743D6B*+MBVC2000**-1A*+TXV CHPF3743D6B*+TXV
DSXC16 0361A* (cont.)
Total¹
G*VC80604B*B*
CHPF3743D6B*+TXV
A*VC80604B*B*
34,000
24,400
16.00
12.50
1,220
5039094
CHPF3743D6B*+TXV
G*VC950453BXB*
34,000
24,400
16.00
12.50
1,130
5620648
CHPF3743D6B*+TXV
G*VC950704CXB*
34,000
24,400
16.00
12.50
1,100
5620656
CHPF3743D6B*+TXV
G*VC950905CXB*
34,600
24,800
16.00
12.00
1,150
5620672
CHPF3743D6B*+TXV
G*VC950905DXB*
34,600
24,800
16.00
12.50
1,150
5620677
CHPF3743D6B*+TXV
G*VC951155DXB*
34,600
24,800
16.00
12.50
1,150
5620687
CHPF3743D6B*+TXV
G*VM960603BXB*
34,000
24,400
16.00
12.50
1,130
5620692
CHPF3743D6B*+TXV
A*VM960604CXB*
34,000
24,400
16.00
12.30
1,100
5620704
CHPF3743D6B*+TXV
G*VM960604CXB*
34,000
24,400
16.00
12.50
1,100
5620705
CHPF3743D6B*+TXV
G*VM960805CXB*
34,600
24,800
16.00
12.00
1,150
5620718
CHPF3743D6B*+TXV
G*VM960805DXB*
34,600
24,800
16.00
12.50
1,150
5620725
CHPF3743D6B*+TXV
G*VM961005DXB*
34,600
24,800
16.00
12.50
1,150
5620733
CHPF3743D6B*+TXV
G*VM961155DXB*
34,600
24,800
16.00
12.50
1,150
5620741
CHPF3743D6B*+TXV
A*VC80805C*B*
34,000
24,400
16.00
12.50
1,190
6497714
CHPF3743D6B*+TXV
A*VC950453BXB*
34,000
24,400
16.00
12.20
1,130
6497715
CHPF3743D6B*+TXV
A*VC950704CXB*
34,000
24,400
16.00
12.20
1,100
6497716
CHPF3743D6B*+TXV
A*VC950905CXB*
34,600
24,800
16.00
12.00
1,150
6497717
CHPF3743D6B*+TXV
A*VC950905DXB*
34,600
24,800
16.00
12.50
1,150
6497718
CHPF3743D6B*+TXV
A*VC951155DXB*
34,600
24,800
16.00
12.50
1,150
6497719
CHPF3743D6B*+TXV
A*VM960603BXB*
34,000
24,400
16.00
12.20
1,130
6497720
CHPF3743D6B*+TXV
A*VM960805CXB*
34,600
24,800
16.00
12.00
1,150
6497721
CHPF3743D6B*+TXV
A*VM960805DXB*
34,600
24,800
16.00
12.00
1,150
6497722
CHPF3743D6B*+TXV
A*VM961005DXB*
34,600
24,800
16.00
12.50
1,150
6497723
CHPF3743D6B*+TXV
A*VM961155DXB*
34,600
24,800
16.00
12.50
1,150
6497724
CHPF3743D6B*+TXV
G*VC80805C*B*
34,000
24,400
16.00
12.50
1,190
6497725
35,000
25,200
14.50
11.50
1,200
5357200
CHPF4860D6D*+EEP+TXV CHPF4860D6D*+TXV
G*VC80604B*B*
34,600
24,800
16.00
12.50
1,220
5038829
CHPF4860D6D*+TXV
A*VC80604B*B*
34,600
24,800
16.00
12.50
1,220
5039095
CHPF4860D6D*+TXV
G*VC950453BXB*
34,600
24,800
16.00
12.50
1,130
5620649
CHPF4860D6D*+TXV
G*VC950704CXB*
35,000
25,200
16.00
12.50
1,100
5620657
CHPF4860D6D*+TXV
G*VC950905CXB*
35,000
25,200
16.00
12.00
1,150
5620673
CHPF4860D6D*+TXV
G*VC950905DXB*
35,000
25,200
16.00
12.50
1,150
5620678
CHPF4860D6D*+TXV
G*VC951155DXB*
35,000
25,200
16.00
12.50
1,150
5620688
CHPF4860D6D*+TXV
G*VM960603BXB*
34,600
24,800
16.00
12.50
1,130
5620693
CHPF4860D6D*+TXV
A*VM960604CXB*
35,000
25,200
16.00
12.30
1,100
5620706
CHPF4860D6D*+TXV
G*VM960604CXB*
35,000
25,200
16.00
12.50
1,100
5620707
CHPF4860D6D*+TXV
G*VM960805CXB*
35,000
25,200
16.00
12.00
1,150
5620719
See Notes on Page 29.
SS-DSXC16
www.goodmanmfg.com
25
Product Specifications
AHRI Ratings (cont.) Indoor Units
Outdoor Unit
DSXC16 0361A* (cont.)
Coils/Air Handlers
Cooling Ratings Furnaces
Sens.¹
SEER²
EER³
CFM
AHRI #
CHPF4860D6D*+TXV
G*VM960805DXB*
35,000
25,200
16.00
12.50
1,150
5620726
CHPF4860D6D*+TXV
G*VM961005DXB*
35,000
25,200
16.00
12.50
1,150
5620734
CHPF4860D6D*+TXV
G*VM961155DXB*
35,000
25,200
16.00
12.50
1,150
5620742
CHPF4860D6D*+TXV
A*VC80805C*B*
34,600
24,800
16.00
12.50
1,190
6497726
CHPF4860D6D*+TXV
A*VC950453BXB*
34,600
24,800
16.00
12.20
1,130
6497727
CHPF4860D6D*+TXV
A*VC950704CXB*
35,000
25,200
16.00
12.20
1,100
6497728
CHPF4860D6D*+TXV
A*VC950905CXB*
35,000
25,200
16.00
12.00
1,150
6497729
CHPF4860D6D*+TXV
A*VC950905DXB*
35,000
25,200
16.00
12.50
1,150
6497730
CHPF4860D6D*+TXV
A*VC951155DXB*
35,000
25,200
16.00
12.50
1,150
6497731
CHPF4860D6D*+TXV
A*VM960603BXB*
34,600
24,800
16.00
12.20
1,130
6497732
CHPF4860D6D*+TXV
A*VM960805CXB*
35,000
25,200
16.00
12.00
1,150
6497733
CHPF4860D6D*+TXV
A*VM960805DXB*
35,000
25,200
16.00
12.00
1,150
6497734
CHPF4860D6D*+TXV
A*VM961005DXB*
35,000
25,200
16.00
12.50
1,150
6497735
CHPF4860D6D*+TXV
A*VM961155DXB*
35,000
25,200
16.00
12.50
1,150
6497736
CHPF4860D6D*+TXV
G*VC80805C*B*
34,600
24,800
16.00
12.50
1,190
6497737
CSCF3642N6D*+TXV
G*VC950453BXB*
34,000
24,400
16.00
12.00
1,200
5620650
CSCF3642N6D*+TXV
A*VC950453BXB*
34,000
24,400
16.00
12.00
1,200
6497738
CSCF3642N6D*+TXV
A*VC950704CXB*
34,200
24,600
16.00
12.00
1,225
6497739
CSCF3642N6D*+TXV
A*VC950905CXB*
34,600
24,800
16.00
12.00
1,150
6497740
CSCF3642N6D*+TXV
A*VC950905DXB*
34,600
24,800
16.00
12.00
1,150
6497741
CSCF3642N6D*+TXV
A*VC951155DXB*
34,600
24,800
16.00
12.00
1,225
6497742
CSCF4860N6D*+EEP+TXV
35,000
25,200
14.50
11.50
1,200
5357202
AVPTC48D14A*
46,000
34,600
15.50
12.00
1,575
5924365
AVPTC60D14A*
45,500
34,200
16.00
12.00
1,430
6687799
CA*F4860*6D*+EEP+TXV
47,000
35,200
14.50
12.00
1,675
5357203
CA*F4860*6D*+MBVC1600**-1A*+TXV
46,000
34,600
15.00
12.00
1,600
6497743
CA*F4860*6D*+MBVC2000**-1A*+TXV CA*F4860*6D*+TXV
DSXC16 0481B*
Total¹
G*VC91155DXA*
47,000
35,200
16.00
12.50
1,600
4559576
45,500
34,200
15.50
11.50
1,400
4172484
CA*F4860*6D*+TXV
A*VC81005C*B*
46,000
34,600
16.00
12.00
1,370
5038813
CA*F4860*6D*+TXV
A*VC80805C*B*
46,000
34,600
16.00
12.30
1,390
5038832
CA*F4860*6D*+TXV
G*VC80604B*B*
45,500
34,200
15.00
12.00
1,400
5039096
CA*F4860*6D*+TXV
G*VC81005C*B*
46,000
34,600
16.00
12.00
1,370
5039097
CA*F4860*6D*+TXV
ADVC80805C*B*
46,000
34,600
16.00
12.30
1,380
5039098
CA*F4860*6D*+TXV
ADVC81005C*B*
46,000
34,600
16.00
12.00
1,410
5039099
CA*F4860*6D*+TXV
A*VC80604B*B*
45,500
34,200
15.00
12.00
1,400
5039115
CA*F4860*6D*+TXV
G*VC80805C*B*
46,000
34,600
16.00
12.30
1,390
5039223
CA*F4860*6D*+TXV
A*VC950704CXB*
45,500
34,200
15.00
12.00
1,400
5620743
CA*F4860*6D*+TXV
G*VC950704CXB*
45,500
34,200
15.00
12.00
1,400
5620744
CA*F4860*6D*+TXV
A*VC950905DXB*
46,000
34,600
16.00
12.30
1,400
5620749
CA*F4860*6D*+TXV
G*VC950905DXB*
46,000
34,600
16.00
12.30
1,400
5620750
CA*F4860*6D*+TXV
A*VC951155DXB*
46,000
34,600
16.00
12.50
1,400
5620755
CA*F4860*6D*+TXV
G*VC951155DXB*
46,000
34,600
16.00
12.30
1,400
5620756
CA*F4860*6D*+TXV
A*VM961005DXB*
46,000
34,600
16.00
12.50
1,400
5620761
CA*F4860*6D*+TXV
G*VM961005DXB*
46,000
34,600
16.00
12.30
1,400
5620762
CA*F4860*6D*+TXV
A*VM961155DXB*
46,000
34,600
16.00
12.50
1,400
5620767
CA*F4860*6D*+TXV
G*VM961155DXB*
46,000
34,600
16.00
12.30
1,400
5620768
CA*F4860*6D*+TXV
A*VC950915DXB*
46,000
34,600
15.00
11.50
1,400
6497744
See Notes on Page 29.
26
www.goodmanmfg.com
SS-DSXC16
Product Specifications
AHRI Ratings (cont.) Indoor Units
Outdoor Unit
DSXC16 0481B* (cont.)
Coils/Air Handlers
Cooling Ratings Furnaces
Total¹
Sens.¹
SEER²
EER³
CFM
AHRI #
CA*F4860*6D*+TXV
G*VC950905CXB*
46,000
34,600
15.00
11.50
1,400
6497745
CA*F4860*6D*+TXV
G*VC950915DXB*
46,000
34,600
15.00
11.50
1,400
6497746
CA*F4961*6D*+EEP+TXV
48,000
36,000
14.50
12.00
1,675
5357204
CA*F4961*6D*+MBVC1600**-1A*+TXV
46,000
34,600
15.00
12.00
1,400
4431661
CA*F4961*6D*+MBVC2000**-1A*+TXV
47,000
35,200
16.00
12.50
1,400
4431662
CA*F4961*6D*+TXV
G*VC91155DXA*
45,500
34,200
15.50
12.00
1,350
4431704
CA*F4961*6D*+TXV
ADVC80805C*B*
47,000
35,200
16.00
12.50
1,380
5038811
CA*F4961*6D*+TXV
A*VC80805C*B*
47,000
35,200
16.00
12.50
1,390
5038814
CA*F4961*6D*+TXV
G*VC80805C*B*
47,000
35,200
16.00
12.50
1,390
5038933
CA*F4961*6D*+TXV
ADVC81005C*B*
46,500
35,000
16.00
12.00
1,410
5038936
CA*F4961*6D*+TXV
G*VC81005C*B*
46,500
35,000
16.00
12.00
1,370
5039012
CA*F4961*6D*+TXV
G*VC80604B*B*
46,000
34,600
16.00
12.30
1,400
5039100
CA*F4961*6D*+TXV
A*VC80604B*B*
46,000
34,600
16.00
12.30
1,400
5039101
CA*F4961*6D*+TXV
A*VC81005C*B*
46,500
35,000
16.00
12.00
1,370
5039225
CA*F4961*6D*+TXV
A*VC950704CXB*
46,500
35,000
15.00
12.00
1,350
5620745
CA*F4961*6D*+TXV
G*VC950704CXB*
46,500
35,000
15.00
12.00
1,350
5620746
CA*F4961*6D*+TXV
A*VC950905DXB*
47,000
35,200
16.00
12.50
1,350
5620751
CA*F4961*6D*+TXV
G*VC950905DXB*
47,000
35,200
16.00
12.50
1,350
5620752
CA*F4961*6D*+TXV
A*VC951155DXB*
47,000
35,200
16.00
12.50
1,350
5620757
CA*F4961*6D*+TXV
G*VC951155DXB*
47,000
35,200
16.00
12.50
1,350
5620758
CA*F4961*6D*+TXV
A*VM961005DXB*
47,000
35,200
16.00
12.50
1,350
5620763
CA*F4961*6D*+TXV
G*VM961005DXB*
47,000
35,200
16.00
12.50
1,350
5620764
CA*F4961*6D*+TXV
A*VM961155DXB*
47,000
35,200
16.00
12.50
1,350
5620769
CA*F4961*6D*+TXV
G*VM961155DXB*
47,000
35,200
16.00
12.50
1,350
5620770
CA*F4961*6D*+TXV
A*VM960805CXB*
47,000
35,200
15.50
12.00
1,350
6497747
CHPF4860D6D*+EEP+TXV
48,000
36,000
14.50
12.00
1,675
5357205
CHPF4860D6D*+MBVC1600**-1A*+TXV
46,000
34,600
15.00
12.00
1,400
4172507
CHPF4860D6D*+MBVC2000**-1A*+TXV
47,000
35,200
16.00
12.50
1,400
4172508
45,500
34,200
15.50
12.00
1,400
5038812
CHPF4860D6D*+TXV
G*VC80604B*B*
CHPF4860D6D*+TXV
G*VC81005C*B*
45,500
34,200
15.50
12.00
1,370
5038830
CHPF4860D6D*+TXV
A*VC80805C*B*
45,500
34,200
15.50
12.00
1,390
5038833
CHPF4860D6D*+TXV
A*VC80604B*B*
45,500
34,200
15.50
12.00
1,400
5039102
CHPF4860D6D*+TXV
G*VC80805C*B*
45,500
34,200
15.50
12.00
1,390
5039224
CHPF4860D6D*+TXV
A*VC81005C*B*
45,500
34,200
15.50
12.00
1,370
5039226
CHPF4860D6D*+TXV
A*VC950704CXB*
46,000
34,600
15.50
12.00
1,350
5620747
CHPF4860D6D*+TXV
G*VC950704CXB*
46,000
34,600
15.50
12.00
1,350
5620748
CHPF4860D6D*+TXV
A*VC950905DXB*
47,000
35,200
16.00
12.30
1,350
5620753
CHPF4860D6D*+TXV
G*VC950905DXB*
47,000
35,200
16.00
12.30
1,350
5620754
CHPF4860D6D*+TXV
A*VC951155DXB*
47,000
35,200
16.00
12.30
1,350
5620759
CHPF4860D6D*+TXV
G*VC951155DXB*
47,000
35,200
16.00
12.30
1,350
5620760
CHPF4860D6D*+TXV
A*VM961005DXB*
47,000
35,200
16.00
12.30
1,350
5620765
CHPF4860D6D*+TXV
G*VM961005DXB*
47,000
35,200
16.00
12.30
1,350
5620766
CHPF4860D6D*+TXV
A*VM961155DXB*
47,000
35,200
16.00
12.30
1,350
5620771
CHPF4860D6D*+TXV
G*VM961155DXB*
47,000
35,200
16.00
12.30
1,350
5620772
CHPF4860D6D*+TXV
G*VC950905CXB*
47,000
35,200
16.00
12.25
1,350
6497748
48,000
36,000
14.50
12.00
1,675
5357206
CSCF4860N6D*+EEP+TXV See Notes on Page 29.
SS-DSXC16
www.goodmanmfg.com
27
Product Specifications
AHRI Ratings (cont.) Indoor Units
Outdoor Unit
Coils/Air Handlers
Cooling Ratings Furnaces
AVPTC60D14A* CA*F4860*6D*+MBVC2000**-1A*+TXV CA*F4860*6D*+TXV
DSXC16 0601B*
G*VC91155DXA*
Total¹
Sens.¹
SEER²
EER³
57,000
42,500
15.50
12.00
CFM
AHRI #
1,780
5924366
55,500
41,000
15.50
12.00
1,800
3880338
55,500
41,000
15.50
12.00
1,575
3880462
CA*F4860*6D*+TXV
ADVC81005C*B*
55,500
41,000
15.50
12.00
1,550
5038834
CA*F4860*6D*+TXV
A*VC80805C*B*
55,500
41,000
15.50
12.00
1,590
5038937
CA*F4860*6D*+TXV
A*VC81005C*B*
55,500
41,000
15.50
12.00
1,610
5038965
CA*F4860*6D*+TXV
G*VC80805C*B*
55,500
41,000
15.50
12.00
1,590
5039104
CA*F4860*6D*+TXV
ADVC80805C*B*
55,500
41,000
15.50
12.00
1,580
5039105
CA*F4860*6D*+TXV
G*VC81005C*B*
55,500
41,000
15.50
12.00
1,610
5039227
CA*F4860*6D*+TXV
A*VC950905CXB*
55,500
41,000
15.00
11.50
1,575
5620773
CA*F4860*6D*+TXV
G*VC950905CXB*
55,500
41,000
15.00
11.50
1,575
5620774
CA*F4860*6D*+TXV
A*VC950905DXB*
55,500
41,000
15.50
12.00
1,575
5620779
CA*F4860*6D*+TXV
G*VC950905DXB*
55,500
41,000
15.50
12.00
1,575
5620780
CA*F4860*6D*+TXV
A*VC950915DXB*
55,500
41,000
15.50
11.50
1,575
5620785
CA*F4860*6D*+TXV
G*VC950915DXB*
55,500
41,000
15.50
11.50
1,575
5620786
CA*F4860*6D*+TXV
A*VC951155DXB*
55,500
41,000
15.50
12.00
1,575
5620789
CA*F4860*6D*+TXV
G*VC951155DXB*
55,500
41,000
15.50
12.00
1,575
5620790
CA*F4860*6D*+TXV
A*VM960805CXB*
55,500
41,000
15.00
11.50
1,575
5620795
CA*F4860*6D*+TXV
G*VM960805CXB*
55,500
41,000
15.00
11.50
1,575
5620796
CA*F4860*6D*+TXV
A*VM960805DXB*
55,500
41,000
15.50
11.50
1,575
5620801
CA*F4860*6D*+TXV
G*VM960805DXB*
55,500
41,000
15.50
11.50
1,575
5620802
CA*F4860*6D*+TXV
A*VM961005DXB*
55,500
41,000
15.50
12.00
1,575
5620807
CA*F4860*6D*+TXV
G*VM961005DXB*
55,500
41,000
15.50
12.00
1,575
5620808
CA*F4860*6D*+TXV
A*VM961155DXB*
55,500
41,000
15.50
12.00
1,575
5620813
CA*F4860*6D*+TXV
G*VM961155DXB*
55,500
41,000
15.50
12.00
1,575
5620814
56,000
41,500
14.00
11.80
1,550
5357207
CA*F4961*6D*+EEP+TXV CA*F4961*6D*+MBVC2000**-1A*+TXV
57,000
42,500
16.00
12.30
1,800
4431664
CA*F4961*6D*+TXV
G*VC91155DXA*
56,000
41,500
15.50
12.00
1,575
4431724
CA*F4961*6D*+TXV
G*VC80805C*B*
56,000
41,500
15.50
12.30
1,590
5038815
CA*F4961*6D*+TXV
A*VC81005C*B*
56,000
41,500
15.50
12.00
1,610
5038835
CA*F4961*6D*+TXV
G*VC81005C*B*
56,000
41,500
15.50
12.00
1,610
5038964
CA*F4961*6D*+TXV
A*VC80805C*B*
56,000
41,500
15.50
12.30
1,590
5038966
CA*F4961*6D*+TXV
ADVC81005C*B*
56,000
41,500
15.50
12.00
1,550
5039013
CA*F4961*6D*+TXV
ADVC80805C*B*
56,000
41,500
15.50
12.30
1,580
5039116
CA*F4961*6D*+TXV
A*VC950905CXB*
56,000
41,500
15.50
11.50
1,575
5620775
CA*F4961*6D*+TXV
G*VC950905CXB*
56,000
41,500
15.50
11.50
1,575
5620776
CA*F4961*6D*+TXV
A*VC950905DXB*
56,000
41,500
15.50
12.30
1,575
5620781
CA*F4961*6D*+TXV
G*VC950905DXB*
56,000
41,500
15.50
12.30
1,575
5620782
CA*F4961*6D*+TXV
A*VC950915DXB*
56,000
41,500
15.50
12.30
1,575
5620787
CA*F4961*6D*+TXV
G*VC950915DXB*
56,000
41,500
15.50
12.30
1,575
5620788
CA*F4961*6D*+TXV
A*VC951155DXB*
56,000
41,500
15.50
12.00
1,575
5620791
CA*F4961*6D*+TXV
G*VC951155DXB*
56,000
41,500
15.50
12.00
1,575
5620792
CA*F4961*6D*+TXV
A*VM960805CXB*
56,000
41,500
15.50
11.50
1,575
5620797
CA*F4961*6D*+TXV
G*VM960805CXB*
56,000
41,500
15.50
11.50
1,575
5620798
CA*F4961*6D*+TXV
A*VM960805DXB*
56,000
41,500
15.50
12.30
1,575
5620803
See Notes on Page 29.
28
www.goodmanmfg.com
SS-DSXC16
Product Specifications
AHRI Ratings (cont.) Outdoor Unit
Indoor Units Coils/Air Handlers CA*F4961*6D*+TXV
Cooling Ratings Furnaces G*VM960805DXB*
Sens.¹
SEER²
EER³
56,000
41,500
15.50
12.30
CFM
AHRI #
1,575
5620804
CA*F4961*6D*+TXV
A*VM961005DXB*
56,000
41,500
15.50
12.00
1,575
5620809
CA*F4961*6D*+TXV
G*VM961005DXB*
56,000
41,500
15.50
12.00
1,575
5620810
CA*F4961*6D*+TXV
A*VM961155DXB*
56,000
41,500
15.50
12.00
1,575
5620815
CA*F4961*6D*+TXV
G*VM961155DXB*
56,000
41,500
15.50
12.00
1,575
5620816
56,000
41,500
14.00
11.80
1,550
5357208
CHPF4860D6D*+EEP+TXV CHPF4860D6D*+MBVC2000**-1A*+TXV
DSXC16 0601B* (cont.)
Total¹
57,000
42,500
15.50
12.30
1,800
3798903
CHPF4860D6D*+TXV
A*VC81005C*B*
56,000
41,500
15.50
12.00
1,610
5038967
CHPF4860D6D*+TXV
G*VC80805C*B*
56,000
41,500
15.50
12.30
1,590
5039014
CHPF4860D6D*+TXV
A*VC80805C*B*
56,000
41,500
15.50
12.30
1,590
5039106
CHPF4860D6D*+TXV
G*VC81005C*B*
56,000
41,500
15.50
12.00
1,610
5039117
CHPF4860D6D*+TXV
A*VC950905CXB*
56,000
41,500
15.50
11.50
1,575
5620777
CHPF4860D6D*+TXV
G*VC950905CXB*
56,000
41,500
15.50
11.50
1,575
5620778
CHPF4860D6D*+TXV
A*VC950905DXB*
56,000
41,500
15.50
12.30
1,575
5620783
CHPF4860D6D*+TXV
G*VC950905DXB*
56,000
41,500
15.50
12.30
1,575
5620784
CHPF4860D6D*+TXV
A*VC951155DXB*
56,000
41,500
15.50
12.00
1,575
5620793
CHPF4860D6D*+TXV
G*VC951155DXB*
56,000
41,500
15.50
12.00
1,575
5620794
CHPF4860D6D*+TXV
A*VM960805CXB*
56,000
41,500
15.50
11.50
1,575
5620799
CHPF4860D6D*+TXV
G*VM960805CXB*
56,000
41,500
15.50
11.50
1,575
5620800
CHPF4860D6D*+TXV
A*VM960805DXB*
56,000
41,500
15.50
11.50
1,575
5620805
CHPF4860D6D*+TXV
G*VM960805DXB*
56,000
41,500
15.50
11.50
1,575
5620806
CHPF4860D6D*+TXV
A*VM961005DXB*
56,000
41,500
15.50
12.00
1,575
5620811
CHPF4860D6D*+TXV
G*VM961005DXB*
56,000
41,500
15.50
12.00
1,575
5620812
CHPF4860D6D*+TXV
A*VM961155DXB*
56,000
41,500
15.50
12.00
1,575
5620817
CHPF4860D6D*+TXV
G*VM961155DXB*
56,000
41,500
15.50
12.00
1,575
5620818
56,000
41,500
14.00
11.80
1,550
5357209
CSCF4860N6D*+EEP+TXV ¹ BTU/h ² Seasonal Energy Efficiency Ratio; Certified per AHRI 210/240 @ 80°F/ 67°F/ 95°F ³ Energy Efficiency Ratio @ 80°F/ 67°F/ 95°F
Notes • Always check the S&R plate for electrical data on the unit being installed. • When matching the outdoor unit to the indoor unit, use the piston supplied with the outdoor unit or that specified on the piston kit chart supplied with the indoor unit. • EEP - Order from Service Dept. Part No. B13707-38 or new Solid State Board B13707-35S. Part No. B13707-38 is not interchangeable with B13707-35S. The Goodman Gas Furnace contains the EEP cooling time delay
SS-DSXC16
www.goodmanmfg.com
29
Product Specifications
Dimensions
Model
30
Dimensions W"
D"
H"
DSXC160241A*
29
29
32¼
DSXC160361A*
29
29
38¼
DSXC160481B*
35½
35½
36¼
DSXC160601B*
35½
35½
38¼
www.goodmanmfg.com
SS-DSXC16
Wiring is subject to change. Always refer to the wiring diagram or the unit for the most up-to-date wiring.
⚠
Warning
High Voltage: Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury, or death.
⚡
Product Specifications
Wiring Diagram
SS-DSXC16
www.goodmanmfg.com
31
Product Specifications
Accessories Model
Description
DSXC16 024**
DSXC16 036**
DSXC16 048**
DSXC16 060**
ABK-20
Anchor Bracket Kit^
X
X
X
X
ASC-01
Anti-Short Cycle Kit
X
X
X
X
B1141643¹
24V Transformer
X
X
X
X
CSR-U-1
Hard-start Kit
X
X
X
CSR-U-2
Hard-start Kit
CSR-U-3
Hard-start Kit
FSK01A²
Freeze Protection Kit
X
X
X
X
LSK02A
Liquid Line Solenoid Valve
X
X
X
X
OT18-60A³
Outdoor Thermostat/Lockout Thermostat
X
X
X
X
TX2N4
TXV Kit
X
TX2N4A
TXV Kit
X
TX3N4⁴
TXV Kit
TX5N4
TXV Kit
X
X
X X
X
^ Contains 20 brackets; four brackets needed to anchor unit to pad ¹ This component is included in the CTK01AA communicating thermostat kit. ² Installed on indoor coil ³ Available in 24V legacy mode only. This feature is integrated in the communicating mode. Note: Maximum number of installed accessories at the same time is limited by the size of the unit’s control box.
Goodman Manufacturing Company, L.P., reserves the right to discontinue, or change at any time, specifications or designs without notice or without incurring obligations. © 2014 • Goodman Manufacturing Company, L.P. • Houston, Texas • Printed in the USA.
32
www.goodmanmfg.com
SS-DSXC16