Transcript
NEW!
LIGHTING CONTROLS
WATTSTOPPER DUAL-TECHNOLOGY OCCUPANCY AND LIGHT SENSOR DT-300 SERIES
DESCRIPTION
The low-profile DT-300 dual-technology occupancy sensor with light level sensor combines the benefits of passive infrared (PIR) and ultrasonic technologies. The sensor mounts in the ceiling with a flat, unobtrusive appearance and provides 360 degrees of coverage. Using SmartSet™ technology, the DT-300 requires no adjustment at installation. SmartSet™ continuously monitors the controlled space to identify usage patterns. Using this information, it automatically adjusts the time delay and sensitivity settings for optimal performance and energy efficiency. The sensor assigns short delays (as low as 5 minutes) for times when the space is usually vacant, and longer delays (up to 30 minutes) for busier times. The DT-305 is a lower cost version of the DT-300 without isolated relay or light level sensor. DT-300
FEATURES • • • • •
SmartSet™ adjusts sensitivity and time delay Walk-through mode turns lights off Ultrasonic diffusion technology LED occupancy indication Pluggable terminal wiring
11
OPERATION In normal operation, the DT-300 turns lighting on when both the PIR and ultrasonic technologies detect occupancy.
LIGHTING CONTROLS
It can also work with a low voltage switch for manual-on operation. PIR technology senses the difference between infrared energy from a human body in motion and the background space. Ultrasonic technology uses the Doppler principle and high frequency (40 KHz) ultrasound to sense motion. Once lighting is on, detection by either technology holds lighting on. When no occupancy is detected for the length of the time delay, lighting turns off. The DT-300 can also be configured so that one or both technologies are needed to turn lighting on or hold lighting on.
SPECIFICATIONS Supply Voltage DT300 DT305 Switch Input Relay Output DT300 Ambient Light DT300
Time Delay Adjust 24 VDC/VAC ±10% 43 mA 24 VDC/VAC ±10% 35 mA Low voltage, momentary for manual ON or OFF operation Isolated SPDT contacts rated for 1A @ 30 VAC/VDC
10 to 300 footcandles (108 to 3230 lux) Coverage Pattern Up to 1000 ft2 (92.9 m2) Sensitivity Adjustment SmartSet™ (automatic) or reduced sensitivity (for PIR sensitivity); ultrasonic sensitivity is variable with trimpot March 2014
SmartSet™ (automatic), fixed (5, 10,15, 20, or 30 minutes), walkthrough, test-mode Ultrasonic Frequency 40kHz Mounting Ceiling tile 4" square junction box with double gang mud ring Dimensions 4.50"Ø x 1.02"D (114.3mm x 25.9mm) Approvals UL and CUL listed file E101196 Weight 1.0 lb (0.46 kg) Warranty 5 years
WE MAKE IT EASY.
kele.com
888-397-5353 USA
629
NEW!
LIGHTING CONTROLS
WATTSTOPPER DUAL-TECHNOLOGY OCCUPANCY AND LIGHT SENSOR DT-300 SERIES WIRING
Trigger
Switch
(red) Load
Isolated relay outputs Common Normally open contact Normally closed contact
Auxiliary relay pack
Lighting load
Occupancy Logic
(black) (blue)
Hot
Power Pack
(black)
(white)
(red)
N
(blue)
Relay common N.O. N.C.
Light level (24VDC) out
= ON = OFF
Manual switch +24V (in) Common
(black)
OFF switch
Light level lighting load
(red) load
N
Occupancy
DT-300 Terminals Hot
DT300 Occupancy
Power pack Switch
Lighting load
11
Either(5)
Both
Both
Both(5)
PIR
PIR
PIR(5)
Ultra
Ultra
Ultra(5)
Man. Either Either(30)
Man.
Both
Both(30)
Switch#
Logic 1 2 3 Standard Option 1 Option 2 Option 3 Option 4 Option 5 Option 6 Option 7
= walk-through mode
LEDs 7 Disabled Enabled
Control (24VDC) out Momentary switch
Manual switch +24V (in) Common
PIR Sensitivity 8 Minimum Maximum/SmartSet
DT-305 Terminals
DT305
LIGHITING CONTROLS
Either(5)
Either
5 sec/SmartSet 5 min 10 min 10 min 15 min 15 min 20 min 30 min
(blue)
(red) Load (black)
(black)
(red)
(white)
Hot
Either(5)
PIR
Time Delay 4 5 6
(white) Neutral (red) Line N
Both Either
Either Either
Standard Option 1 Option 2 Option 3 Option 4 Option 5 Option 6 Option 7
= Factory Setting
Control (24VDC) out Momentary Switch
Re-trigger (seconds duration)
(white) Neutral (red) Line
Initial Occupancy Maintain Occupancy
DIP SWITCH SETTINGS
Occupancy and Light Level Controlled Lighting
Notes: Exceeding voltage rating may damage sensor. Shown with BZ-50 power pack (optional).
COVERAGE
MOUNTING
4" Octagonal J-Box (at least 1.5" deep) Ceiling
Ceiling
Depluggable terminal
PIR Coverage
44' (13.4m)
Depluggable terminal Spring clips (2) Rear housing
Rear Housing
Front cover
Screws Front Cover
Ultrasonic Coverage
J-Box Mount
Ceiling Mount
40' x 40' (12m x 12m)
ORDERING INFORMATION MODEL DT-300 DT-305
630
888-397-5353 USA
DESCRIPTION Dual technology occupancy sensor with isolated relay and light level actuation Dual technology occupancy sensor with 24 VDC control output only (no light level or relay)
kele.com
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
March 2014