Your Climate. We're There.
TM: MDB – B – 2140B
Ducted Split Systems Models: MDB 075B MDB 075B/B
- MDB750B - MDB500BR
®
REGISTERED
Air Conditioning
Contents Nomenclature System ........................................................................................................ 2 Features ............................................................................................................................. 2 General Specifications ...................................................................................................3 - 5 Specifications................................................................................................................6 - 12 Performance Characteristics...................................................................................... 13 - 15 Drive Package Selection Example ............................................................................. 16 - 17 Blower Performance Curves ...................................................................................... 18 -20 Outlines And Dimensions (Indoor) ............................................................................ 21 - 27 Outlines And Dimensions (Outdoor) ......................................................................... 28 - 30 Wiring Diagrams (heat pump) .................................................................................... 31 - 35 Wiring Diagrams (cooling).......................................................................................... 36 - 53 Installation (Indoor) ........................................................................................................... 54 Installation (Outdoor) .................................................................................................55 - 59 Servicing And Maintenance ..............................................................................................60 Operation ...................................................................................................................61 - 63 Troubleshooting ........................................................................................................ 63 - 65
Note : Installation and maintenance are to be performed only by qualified personnel who are familiar with local codes and regulations, and experienced with this type of equipment. Caution: Sharp edges and coil surfaces are a potential injury hazard. Avoid contact with them.
Warning : Moving machinery and electrical power hazard. May cause severe personal injury or death. Disconnect and lock off power before servicing equipment.
"McQuay" is a registered trademark of McQuay International. All rights reserved throughout the world. 2001 McQuay International "Bulletin illustrations cover the general appearance of McQuay International products at the time of publication and we reserve the right to make changes in design and construction at any time without notice."
1
Nomenclature system M
DB
BRAND
STATIC BLOWER
150
150,000 BTU/HR
B
GENERATION
2
NUMBER OF REFRIGERANT CIRCUIT
Features Easy Maintenance The simple design concept has maintenance and servicing in mind. Access to the internal part of the unit can be from either side of the unit by loosening a few screws.
Only for model MDB 060B, 070B and 100B with additional servicing panel from bottom
Flexibility In Installation MDB 040B - MDB 150B models come with standard horizontal air discharge whereas MDB 200B - MDB 750B models come with standard vertical air discharge. However, the range from MDB 125B - MDB 750B are designed to cater for either horizontal or vertical air discharge application.
Versatility Multiple rooms can be cooled together at the same time by using just one unit of fan coil unit.
Fresh Air For Healthy Living Fresh air can be introduced into the building through the design of fresh air intakes. This will help to improve the indoor air quality.
Superior Air Distribution For Comfortable Living The conditioned air can be effectively distributed to every corner of the room through the ducting and this ensure a more pleasant environment for comfort living.
Flexibility Of Air Supply McQuay MDB series using belt driven fan such as that the air volume and static required can be adjusted according to the requirement. This flexibility allow for wider application. 2
General Specifications Unit The casing is constructed with electro-galvanised mild steel sheet which provides a rigid cabinet. The internal components are easily accessible by removing the front panel. The finishing of the casing is a long-lasting epoxy polyester powder coating.
Condenser Coil Each coil consists of staggered rows of 3/8" OD seamless copper tubes, mechanically expanded into die-formed corrugated aluminium fins. Each coil provided with integral sub-cooling circuit to maximize energy efficiency and promote superior match-system operating performance when connected to suitably sized DX Evaporator-blower unit. Coils are leak and pressure tested to 450 psig, evacuated and dehydrated.
Condenser Fan and Motor The propeller fan is of acryl styrene resin construction, direct driven by weatherproof single phase PSC motor. Fan motor has class E insulation. Fan is protected with plastic outer nozzle.
Compressor High efficiency, refrigerant-cooled, reciprocating/scroll hermetic compressor has internal suspension system to eliminate noise, vibration and further resiliently isolated from unit base. Compressor has internal overload protection. Units are provided with manual reset high-low pressure cut-outs and crankcase heater for off-cycle operation to guard against compressor valve plate damage during start-up. Compressor is covered with sound shield to further reduce noise level.
Safety Controls Manual reset high pressure and low pressure cut-outs to guard against compressor damage due to high discharge head pressure and system leakage respectively. Crankcase heater for each compressor to prevent liquid migration, which can damage compressor valve plates, during off-cycle and eases start-up.
Sequential Controller Functions (Standard for heatpump units and optional for cooling only units) 1. Sequential controller LCD display
A B C D E F G H I
: Time display : Error indication : Compressor running display (up to 4 compressors) : Key lock display : Heater display (up to 2 heaters) : Energy saving mode display : Compressor defrost cycle display (up to 4 compressors) : Operation mode display : Temperature set display 3
2. Operating Guide 2.1 ON/OFF key Press once to start the air conditioning unit. Press again to stop the unit. The operation lamp next to the key lights up and goes off respectively when the unit is running or not running. Caution : In the case when the ON/OFF key is pressed immediately after the operation is stopped, the unit will not restart until 3 minutes later to protect the compressor. 2.2 Selecting Operation Mode Press the MODE key to select the type of operating mode. Consecutive press of the key switches the operation over "COOL", "HEAT", "AUTO" and "FAN" 2.3 SAVE Mode Press the SAVE key to select the energy saving function. This option is only available for "COOL", "HEAT" and "AUTO" modes. 2.4 Auxiliary Electric Heater If the "HEAT" mode provides insufficient heating to a room even at the highest temperature setting (30°C), press the HEATER key to activate the auxiliary electric heater. For models with two heaters, consecutive press of the key allows the selection of one or both heaters active. 2.5 Temperature Setting To set the desired room temperature, press or to increase or decrease the set temperature in the range of 16°C to 30°C. Press both and simultaneously to toggle between °C and °F setting. 2.6 Time Setting Real time Clock Press the CLOCK key once to activate set clock mode. Press again to disable set clock mode. Under set clock mode, the time of the present day can be set by pressing the respective MINUTE, HOUR and DAY key. 7-days timer Press the ON TIMER key to activate auto-ON timer mode. Under this mode, press the respective MINUTE, HOUR and DAY key to select the time of the week when the air-conditioning unit is to automatically start running. Press the ON TIMER key again to save the setting. Press the OFF TIMER key to activate auto-OFF timer mode. Under this mode, press the respective MINUTE, HOUR and DAY key to select the time of the week when the air-conditioning unit is to automatically stop running. Press the ON TIMER key again to save the setting. Then to activate the 7-days timer, press and hold the TIMER ACTIVE key until the word "TIMER ACTIVE" appears on the LCD screen. Repeat the same step to disable the 7-days timer.
2.7 Other Function Key Lock Press the MINUTE key 3 times consecutively to activate the key lock. A "KEY LOCK" symbol will appear on the LCD screen. At this point, only the ON/OFF key is valid. To disable the key lock, again press the MINUTE key 3 times consecutively. Test run Press the TEST key 2 times consecutively to test run the unit. 3. Error Code When the system is on and an error occurs, the ON/OFF LED on the LCD panel will blink and an error code is shown. When the system is off and there is a thermistor error, the ON/OFF LED is off but the error code is still displayed. Each error code represents different message as below
4
Error code E01 E02 E03 E04 E05 E06 E07 E08 E09 E10 E11 E12 E13 E14 E15 E16 E17 E18
Possible fault Require manual reset (possible causes) Compressor 1 high temperature (overload) Compressor 2 high temperature(overload) Compressor 3 high temperature(overload) Compressor 4 high temperature(overload) Compressor 1 high pressure trip / contact open Compressor 2 high pressure trip / contact open Compressor 3 high pressure trip / contact open Compressor 4 high pressure trip / contact open Compressor 1 trip / low R-22 / outdoor abnormal Compressor 2 trip / low R-22 / outdoor abnormal Compressor 3 trip / low R-22 / outdoor abnormal Compressor 4 trip / low R-22 / outdoor abnormal Room sensor short Room sensor open Indoor coil sensor 1 short Indoor coil sensor 2 short Indoor coil sensor 3 short
Error code E19 E20 E21 E22 E23 E24 E25 E26 E27 E28 E29 E30 E31 E32 E33 E34 E35
Possible fault Indoor coil sensor 4 short Indoor coil sensor 1 open Indoor coil sensor 2 open Indoor coil sensor 3 open Indoor coil sensor 4 open Outdoor coil sensor 1 short Outdoor coil sensor 2 short Outdoor coil sensor 3 short Outdoor coil sensor 4 short Outdoor coil sensor 1 open Outdoor coil sensor 2 open Outdoor coil sensor 3 open Outdoor coil sensor 4 open Compressor 1 de-ice Compressor 2 de-ice Compressor 3 de-ice Compressor 4 de-ice
4. Installation of LCD remote controller 4.1Accessories The following accessories are included. If any part is missing, contact your dealer immediately. 1 Remote controller 2 Wooden screw 4.1 x 16 (2 pieces) 3 Instruction manual 4.2 Step-by-step guide i) First, open up the casing of the LCD remote controller into its top and bottom case using a screwdriver. To do this, insert the screwdriver into the lower slot and slide it in the outward direction. ii) Fix the bottom case onto the wall with the 2 wooden screws provided. Then, insert the 4 connecting wires (from the main board) through the slot on the lower right. iii) Connect one end in each of the 4 wires to the terminal block behind the top case as shown below. The wire that goes into the "GND" terminal at the top case must be connected at the other end to the “GND" terminal at the main board. The same goes for the "+5V", "B" and "A" connection. iv) Fasten back the top and bottom case into place. Hook the two upper claws into their respective slots and snap the lower part shut.
5
Specifications Cooling only MODEL TOTAL COOLING CAPACITY CASING
DIMENSION
INDOOR UNIT OUTDOOR UNIT OUTDOOR 35 °CDB MATERIAL FINISHING INSULATION HEIGHT (H) WIDTH (W) DEPTH (D)
NET WEIGHT NOISE LEVEL EVAPORATOR COIL TYPE TUBE
OUTDOOR UNIT
INDOOR UNIT
FIN
MATERIAL WALL THICKNESS OUTER DIAMETER MATERIAL THICKNESS ROWS FIN PER INCH
CAPACITY STEP FACE AREA FACE VELOCITY EVAPORATOR BLOWER TYPE / DRIVE BLOWER MATERIAL QUANTITY BLOWER DIAMETER BLOWER LENGTH AIR FLOW EXTERNAL STATIC PRESSURE EVAPORATOR BLOWER MOTOR TYPE POWER SUPPLY NUMBER x RATED RUNNING CURRENT NUMBER x RATED OUTPUT NUMBER x RATED INPUT MOTOR POLES REFRIGERANT TYPE TYPE OF GAS PRECHARGED CONTROL PIPE CONNECTION PIPE SIZE LIQUID GAS DRAIN PIPE CONNECTION AIR FILTER TYPE SIZE LENGTH x HEIGHT DEPTH QUANTITY CASING MATERIAL FINISHING HEIGHT (H) DIMENSION WIDTH (W) DEPTH (D) NET WEIGHT NOISE LEVEL CONDENSER COIL TYPE MATERIAL TUBE WALL THICKNESS OUTER DIAMETER MATERIAL FIN THICKNESS NUMBER x ROWS FIN PER INCH FACE AREA FACE VELOCITY CONDENSER FAN TYPE / DRIVE BLADE MATERIAL QUANTITY BLADE DIAMETER POWER SUPPLY NUMBER x RATED RUNNING CURRENT NUMBER x RATED INPUT MOTOR POLES AIR FLOW COMPRESSOR TYPE POWER SUPPLY RATED RUNNING CURRENT RATED INPUT MAXIMUM STARTING CURRENT PROTECTION DEVICE STAGE OF CAPACITY CONTROL STARTER TYPE REFRIGERANT TYPE TYPE OF GAS PRECHARGED
MDB075B MMC075B
MDB100B MMC075C
MMC100B
75,000 18,900 21,975
Btu/h kcal/h W
MMC100C 100,000 25,200 29,300
ELECTRO GALVANIZED MILD STEEL EPOXY POLYESTER POWDER COATING PE 572 (22.51) 1,502 (59.13) 761 (29.96) 96 (211) 66
mm (in) mm (in) mm (in) kg (lb) dBA
572 (22.51) 1,502 (59.13) 761 (29.96) 100 (220) 71 CROSS FINNED TUBES SEAMLESS COPPER 0.35 (0.013) 9.52 (3/8) ALUMINUM 0.127 (0.005)
mm (in) mm (in) mm (in)
% 2 2 m (ft ) m/min (FPM)
3 12 100-0 0.54 (5.82) 130.75 (429)
mm (in) mm (in) CMM (CFM) mm wg (in wg)
2 282.70 (11.13) 203.00 (8.00) 70.82 (2,500) 10.16 (0.40)
4 12 100-0 0.54 (5.82) 167.64 (550) CENTRIFUGAL / DIRECT COLD ROLLED STEEL 2 282.70 (11.13) 203.20 (8.00) 90.65 (3,200) 10.16 (0.40) PERMANENT SPLIT CAPACITOR 220 - 240 / 1 / 50 / 60
V / Ph / Hz A W W
2 x 1.70 2 x 248 2 x 350 6
2 x 1.63 2 x 373 2 x 436 6 R22 NITROGEN HOLDING THERMOSTAT EXPANSION VALVE BRAZING
12.70 (1/2) 25.40 (1.00)
mm (in) mm (in) mm (in)
15.88 (5/8) 28.58 (1 - 1/8) 25.40 (1.00) WASHABLE SARAN NET
622 x 433 12.70 (1/2) 2
mm mm (in)
mm (in) mm (in) mm (in) kg (lb) dBA
946 (37.24) 1,116 (43.93) 939 (36.96) 162 (357) 70
ELECTRO GALVANIZED MILD STEEL EPOXY POLYESTER POWDER 946 (37.24) 946 (37.24) 1,300 (51.18) 1,116 (43.93) 500 (19.68) 939 (36.96) 163 (359) 193 (425) 70 72
971 (38.23) 1,393 (54.84) 500 (19.68) 176 (387) 75
2x1 16 1.76 (19.00) 112.16 (368)
CROSS FINNED TUIBES SEAMLESS COPPER 0.35 (0.013) 9.52 (3/8) ALUMINIUM 0.127 (0.005) 1x2 2x2 14 12 1.23 (13.25) 1.76 (19.00) 138.07 (453) 112.16 (368)
1x3 14 1.35 (14.54) 146.60 (481)
1 660.40 (26) 380-415/3/50 1.4 708 6 198.30 (7,000)
PERMANENT SPLIT CAPACITOR / PROPELLER / DIRECT ALUMINIUM 1 1 660.40 (26) 660.40 (26) 220-240/1/50 380-415/3/50 3 1.5 680 660 6 6 169.97 (6,000) 198.30 (7,000)
1 762.00 (30) 380-415/3/50 3.35 1,100 8 198.30 (7,000)
mm (in) mm (in) mm (in)
m2 (ft2) m/min (FPM)
mm (in) V / Ph / Hz A W CMM (CFM)
V / Ph / Hz A W A
622 x 433 12.70 (1/2) 2
SCROLL 380-415/3/50 13.6 13.6 16.9 16.9 6,810 6,810 9,040 9,040 95.0 95.0 125.0 125.0 OVERLOAD PROTECTION & MANUAL RESET HIGH / LOW PRESSURE SWITCH ON / OFF AUTO-TRANSFORMER R22 NITROGEN HOLDING
NOTES : 1.ALL UNITS ARE BEING TESTED AND COMPLY TO ARI210/240-89. 2.NOMINAL COOLING CAPACITIES ARE BASED ON THE FOLLOWING CONDITIONS. INDOOR 26.7 °CDB, 19.4 °CWB, OUTDOOR 35 °CDB. 3.ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY MANUFACTURER WITHOUT PRIOR NOTICE. 4.AIR FILTER IS AN OPTIONAL ITEM.
6
MODEL TOTAL COOLING CAPACITY CASING
DIMENSION
INDOOR UNIT OUTDOOR UNIT OUTDOOR 35 °CDB MATERIAL FINISHING INSULATION HEIGHT (H) WIDTH (W) DEPTH (D)
NET WEIGHT NOISE LEVEL EVAPORATOR COIL TYPE TUBE
OUTDOOR UNIT
INDOOR UNIT
FIN
MATERIAL WALL THICKNESS OUTER DIAMETER MATERIAL THICKNESS ROWS FIN PER INCH
CAPACITY STEP FACE AREA FACE VELOCITY EVAPORATOR BLOWER TYPE / DRIVE BLOWER MATERIAL BLOWER DIAMETER BLOWER LENGTH AIR FLOW EXTERNAL STATIC PRESSURE BLOWER PULLEY DIAMETER MOTOR PULLEY DIAMETER PULLEY EVAPORATOR BLOWER MOTOR TYPE POWER SUPPLY NUMBER x RATED RUNNING CURRENT NUMBER x RATED OUTPUT NUMBER x RATED INPUT MOTOR POLES REFRIGERANT TYPE TYPE OF GAS PRECHARGED CONTROL PIPE CONNECTION PIPE SIZE LIQUID GAS DRAIN PIPE CONNECTION AIR FILTER TYPE SIZE LENGTH x HEIGHT DEPTH QUANTITY CASING MATERIAL FINISHING HEIGHT (H) DIMENSION WIDTH (W) DEPTH (D) NET WEIGHT NOISE LEVEL CONDENSER COIL TYPE MATERIAL TUBE WALL THICKNESS OUTER DIAMETER MATERIAL FIN THICKNESS NUMBER x ROWS FIN PER INCH FACE AREA FACE VELOCITY CONDENSER FAN DRIVE TYPE BLADE MATERIAL BLADE DIAMETER POWER SUPPLY NUMBER x RATED RUNNING CURRENT NUMBER x RATED INPUT MOTOR POLES AIR FLOW COMPRESSOR TYPE POWER SUPPLY RATED RUNNING CURRENT RATED INPUT MAXIMUM STARTING CURRENT PROTECTION DEVICE STAGE OF CAPACITY CONTROL STARTER TYPE REFRIGERANT TYPE TYPE OF GAS PRECHARGED
MDB125B
MDB150B2 MMC075B x 2 MMC075C x 2 150,000 37,800 43,950 ELECTRO GALVANIZED MILD STEEL EPOXY POLYESTER POWDER COATING PE 885 (34.84) 736 (28.97) 1,640 (64.54) 1,640 (64.56) 1,040 (40.94) 965 (37.99) 145 (319) 174 (383) 78.6 78.1 MDB125C
MMC125B Btu/h kcal/h W
125,000 31,500 36,625
125,000 31,500 36,625
mm (in) mm (in) mm (in) kg (lb) dBA
885 (34.84) 1,640 (64.56) 1,040 (40.94) 140 (308) 76.8
4 12 100-0 0.79 (8.60) 148.73 (488)
4 14 100-50-0 0.90 (9.80) 142.94 (469)
394.97 (15.55) 381.00 (15.00) 118.98 (4,200) 15.24 (0.60) 1 SPZ 160 1 SPZ 85 B1
CENTRIFUGAL / BELT DRIVEN ZINC COATED STEEL 394.97 (15.55) 381.00 (15.00) 130.31 (4,600) 15.24 (0.60) 1 SPZ 160 1 SPZ 80 B1
394.97 (15.55) 381.00 (15.00) 130.31 (4,600) 15.24 (0.60) 2 SPZ 125 2 SPZ 71 B1
3.39 1,500 1,100 4
SQUIRREL CAGE INDUCTION 400 / 3 / 50 3.39 1,500 1,630 4
4.65 2,200 1,682 4
mm (in)
% m2 (ft2) m/min (FPM)
mm (in) mm (in) CMM (CFM) mm wg (in wg) mm mm TYPE
V / Ph / Hz A W W
394.97 (15.55) 381.00 (15.00) 118.98 (4,200) 15.24 (0.60) 1 SPZ 160 1 SPZ 80 B1
3.39 1,500 1,100 4
mm (in) mm (in) mm (in)
19.05 (3/4) 28.58 (1-1/8)
mm mm (in)
457 x 738 50.8 (2.00) 3
mm (in) mm (in) mm (in) kg (lb) dBA
R22 NITROGEN HOLDING THERMOSTAT EXPANSION VALVE BRAZING 12.70 (1/2) 15.88 (5/8) 25.40 (1.00) 31.75 (1 1/4) 25.40 (1.00)
946 (37.24) 1,116 (43.93) 939 (36.96) 224 (493) 75
946 (37.24) 1,116 (43.93) 939 (36.96) 162 (357) 70
946 (37.24) 1,300 (51.18) 500 (19.68) 163 (359) 70
2x2 16 1.76 (19.00) 112.16 (368)
CROSS FINNED TUIBES SEAMLESS COPPER 0.35 (0.013) 9.52 (3/8) ALUMINIUM 0.127 (0.005) 2x1 1x2 16 14 1.76 (19.00) 1.23 (13.25) 112.16 (368) 138.07 (453)
2x1 16 1.76 (19.00) 112.16 (368)
1x2 14 1.23 (13.25) 138.07 (453)
660.40 (26) 380-415/3/50 1.40 780 6 198.30 (7,000)
660.40 (26) 220-240/1/50 3.00 680 6 169.97 (6,000)
mm (in)
2
m (ft ) m/min (FPM)
mm (in) V / Ph / Hz A W CMM (CFM)
15.88 (5/8) 34.92 (1-3/8)
WASHABLE VILEDON 457 x 738 50.8 (2.00) 3 ELECTRO GALVANIZED MILD STEEL EPOXY POLYESTER POWDER 946 (37.24) 946 (37.24) 1,116 (43.93) 1,300 (51.18) 939 (36.96) 500 (19.68) 162 (357) 163 (359) 70 70
457 x 589 50.8 (2.00) 3
mm (in) mm (in)
2
736 (28.97) 1,819 (71.61) 965 (37.99) 188 (414) 79.4
CROSS FINNED TUBES SEAMLESS COPPER 0.35 (0.013) 9.52 (3/8) ALUMINUM 0.127 (0.005) 4 12 100-50-0 1.00 (10.82) 129.54 (425)
mm (in) mm (in)
3 14 100-0 1.00 (10.82) 118.26 (388)
MDB150C2 MMC075B x 2 MMC075C x 2 150,000 37,800 43,950
660.40 (26) 380-415/3/50 1.43 640 6 198.30 (7,000)
PROPELLER / DIRECT PERMANENT SPLIT CAPACITOR ALUMINIUM 660.40 (26) 660.40 (26) 380-415/3/50 220-240/1/50 1.40 3.00 708 680 6 6 198.30 (7,000) 169.97 (6,000)
516.5 x 589 50.8 (2.00) 3
SCROLL 380-415/3/50 17.9 13.6 13.6 13.6 10,200 6,810 6,810 6,810 110.0 95.0 95.0 95.0 OVERLOAD PROTECTION AND MANUAL RESET HIGH / LOW PRESSURE SWITCH ON / OFF AUTO-TRANSFORMER
V / Ph / Hz A W A
R22 NITROGEN HOLDING
NOTES : 1. ALL UNITS ARE BEING TESTED AND COMPLY TO ARI210/240-89. 2. NOMINAL COOLING CAPACITIES ARE BASED ON THE FOLLOWING CONDITIONS. INDOOR 26.7 °CDB, 19.4 °CWB, OUTDOOR 35 °CDB. 3. ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY MANUFACTURER WITHOUT PRIOR NOTICE. 4. AIR FILTER IS AN OPTIONAL ITEM.
7
13.6 6,810 95.0
MODEL TOTAL COOLING CAPACITY CASING
DIMENSION
INDOOR UNIT OUTDOOR UNIT OUTDOOR 35 °CDB MATERIAL FINISHING INSULATION HEIGHT (H) WIDTH (W) DEPTH (D)
NET WEIGHT NOISE LEVEL EVAPORATOR COIL TYPE TUBE
OUTDOOR UNIT
INDOOR UNIT
FIN
MATERIAL WALL THICKNESS OUTER DIAMETER MATERIAL THICKNESS ROWS FIN PER INCH
CAPACITY STEP FACE AREA FACE VELOCITY EVAPORATOR BLOWER TYPE / DRIVE BLOWER MATERIAL BLOWER DIAMETER BLOWER LENGTH AIR FLOW EXTERNAL STATIC PRESSURE BLOWER PULLEY DIAMETER MOTOR PULLEY DIAMETER PULLEY EVAPORATOR BLOWER MOTOR TYPE POWER SUPPLY NUMBER x RATED RUNNING CURRENT NUMBER x RATED OUTPUT NUMBER x RATED INPUT MOTOR POLES REFRIGERANT TYPE TYPE OF GAS PRECHARGED CONTROL PIPE CONNECTION PIPE SIZE LIQUID GAS DRAIN PIPE CONNECTION AIR FILTER TYPE SIZE LENGTH x HEIGHT DEPTH QUANTITY CASING MATERIAL FINISHING HEIGHT (H) DIMENSION WIDTH (W) DEPTH (D) NET WEIGHT NOISE LEVEL CONDENSER COIL TYPE MATERIAL TUBE WALL THICKNESS OUTER DIAMETER MATERIAL FIN THICKNESS NUMBER x ROWS FIN PER INCH FACE AREA FACE VELOCITY CONDENSER FAN DRIVE TYPE BLADE MATERIAL BLADE DIAMETER POWER SUPPLY NUMBER x RATED RUNNING CURRENT NUMBER x RATED INPUT MOTOR POLES AIR FLOW COMPRESSOR TYPE POWER SUPPLY RATED RUNNING CURRENT RATED INPUT MAXIMUM STARTING CURRENT PROTECTION DEVICE STAGE OF CAPACITY CONTROL STARTER TYPE REFRIGERANT TYPE TYPE OF GAS PRECHARGED
MDB150B1
MDB200B2 MMC100B x 2 MMC100C x 2 200,000 150,000 50,400 37,800 58,600 43,950 ELECTRO GALVANIZED MILD STEEL EPOXY POLYESTER POWDER COATING PE 945 (37.20) 736 (28.97) 1,894 (74.56) 1,819 (71.61) 980 (38.58) 965 (37.99) 180 (396) 188 (414) 85 79.4 MDB150C1
MMC150C Btu/h kcal/h W
150,000 37,800 43,950
mm (in) mm (in) mm (in) kg (lb) dBA
885 (34.84) 1,640 (64.56) 1,040 (40.94) 145 (319) 78.6
MDB250B2 MMC125B x 2 250,000 63,000 73,250
1,291 (50.82) 1,866 (73.46) 1,199 (47.20) 250 (551) 87.1
% m2 (ft2) m/min (FPM)
4 12 100-50-0 1.00 (10.82) 129.54 (425)
4 14 100-50-0 0.90 (9.80) 142.94 (469)
CROSS FINNED TUBES SEAMLESS COPPER 0.35 (0.013) 9.52 (3/8) ALUMINIUM 0.127 (0.005) 4 12 100-50-0 1.20 (12.92) 150.87 (495)
mm (in) mm (in) CMM (CFM) mm wg (in wg) mm mm TYPE
394.97 (15.55) 381.00 (15.00) 130.31(4,600) 15.24 (0.60) 1 SPZ 160 1 SPZ 80 B1
394.97 (15.55) 381.00 (15.00) 130.31 (4,600) 15.24 (0.60) 2 SPZ 125 2 SPZ 71 B1
CENTRIFUGAL / BELT DRIVEN ZINC COATED STEEL 394.97 (15.55) 381.00 (15.00) 181.30 (6,400) 15.24 (0.60) 2 SPZ 140 2 SPZ 80 B1
469.90 (18.50) 459.99 (18.11) 226.62 (8,000) 20.32 (0.80) 2 SPZ 180 2 SPZ 90 B2
3.39 1,500 1,630 4
4.65 2,200 1,682 4
SQUIRREL CAGE INDUCTION 400 / 3 / 50 6.15 3,000 2,730 4
8.00 4,000 3,370 4
mm (in) mm (in) mm (in)
V / Ph / Hz A W W
mm (in) mm (in) mm (in)
15.88 (5/8) 34.92 (1-3/8)
mm mm (in)
457 x 738 50.8 (2.00) 3
mm (in) mm (in) mm (in) kg (lb) dBA
R22 NITROGEN HOLDING THERMOSTAT EXPANSION VALVE BRAZING 15.88 (5/8) 15.88 (5/8) 28.58 (1-1/8) 34.92 (1-3/8) 25.40 (1.00)
1,041 (40.98) 1,116 (43.93) 939 (36.96) 258 (568) 77
946 (37.24) 1,116 (43.93) 939 (36.96) 224 (493) 75
2x2 14 1.24 (13.38) 131.97 (433)
CROSS FINNED TUIBES SEAMLESS COPPER 0.35 (0.013) 9.52 (3/8) ALUMINIUM 0.127 (0.005) 2x2 1x3 12 14 1.76 (19.00) 1.35 (14.54) 112.16 (368) 146.60 (481)
2x2 16 1.76 (19.00) 112.16 (368)
INDUCTION
P. SPLIT CAPACITOR
mm (in)
mm (in) V / Ph / Hz A W CMM (CFM)
V / Ph / Hz A W A
15.88 (5/8) 31.75 (1 1/4)
WASHABLE VILEDON 542 x 738 50.8 (2.00) 3 ELECTRO GALVANIZED MILD STEEL EPOXY POLYESTER POWDER 946 (37.24) 971.4 (38.24) 1,116 (43.93) 1,393 (54.84) 939 (36.96) 500 (19.68) 193 (425) 176 (387) 72 75
516.5 x 589 50.8 (2.00) 3
mm (in) mm (in)
m2 (ft2) m/min (FPM)
4 14 100-50-0 1.48 (16.01) 152.40 (500)
762.00 (30) 380-415 / 3 / 50 4.35 3,200 6 328.61 (11,600)
PROPELLER / DIRECT INDUCTION ALUMINIUM 660.40 (26) 762.00 (30) 380-415/3/50 380-415/3/50 1.50 3.35 660 1,100 6 8 198.30 (7,000) 198.30 (7,000)
533 x 532 50.8 (2.00) 6
PERMANENT SPLIT CAPACITOR 660.40 (26) 380-415/3/50 1.43 640 6 198.30 (7,000)
SCROLL 380-415/3/50 23.5 17.9 16.9 16.9 13,300 10,200 9,040 9,040 198.0 110.0 125.0 125.0 OVERLOAD PROTECTION AND MANUAL RESET HIGH / LOW PRESSURE SWITCH ON / OFF AUTO-TRANSFORMER R22 NITROGEN HOLDING
NOTES : 1. ALL UNITS ARE BEING TESTED AND COMPLY TO ARI210/240-89. 2. NOMINAL COOLING CAPACITIES ARE BASED ON THE FOLLOWING CONDITIONS. INDOOR 26.7 °CDB, 19.4 °CWB, OUTDOOR 35 °CDB. 3. ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY MANUFACTURER WITHOUT PRIOR NOTICE. 4. AIR FILTER IS AN OPTIONAL ITEM.
8
MODEL TOTAL COOLING CAPACITY CASING
DIMENSION
INDOOR UNIT OUTDOOR UNIT OUTDOOR 35 °CDB MATERIAL FINISHING INSULATION HEIGHT (H) WIDTH (W) DEPTH (D)
NET WEIGHT NOISE LEVEL EVAPORATOR COIL TYPE TUBE
OUTDOOR UNIT
INDOOR UNIT
FIN
MATERIAL WALL THICKNESS OUTER DIAMETER MATERIAL THICKNESS ROWS FIN PER INCH
CAPACITY STEP FACE AREA FACE VELOCITY EVAPORATOR BLOWER TYPE / DRIVE BLOWER MATERIAL BLOWER DIAMETER BLOWER LENGTH AIR FLOW EXTERNAL STATIC PRESSURE BLOWER PULLEY DIAMETER MOTOR PULLEY DIAMETER PULLEY EVAPORATOR BLOWER MOTOR TYPE POWER SUPPLY NUMBER x RATED RUNNING CURRENT NUMBER x RATED OUTPUT NUMBER x RATED INPUT MOTOR POLES REFRIGERANT TYPE TYPE OF GAS PRECHARGED CONTROL PIPE CONNECTION PIPE SIZE LIQUID GAS DRAIN PIPE CONNECTION AIR FILTER TYPE SIZE LENGTH x HEIGHT DEPTH QUANTITY CASING MATERIAL FINISHING HEIGHT (H) DIMENSION WIDTH (W) DEPTH (D) NET WEIGHT NOISE LEVEL CONDENSER COIL TYPE MATERIAL TUBE WALL THICKNESS OUTER DIAMETER MATERIAL FIN THICKNESS NUMBER x ROWS FIN PER INCH FACE AREA FACE VELOCITY CONDENSER FAN DRIVE TYPE BLADE MATERIAL BLADE DIAMETER POWER SUPPLY NUMBER x RATED RUNNING CURRENT NUMBER x RATED INPUT MOTOR POLES AIR FLOW COMPRESSOR TYPE POWER SUPPLY RATED RUNNING CURRENT RATED INPUT MAXIMUM STARTING CURRENT PROTECTION DEVICE STAGE OF CAPACITY CONTROL STARTER TYPE REFRIGERANT TYPE TYPE OF GAS PRECHARGED
Btu/h kcal/h W
mm (in) mm (in) mm (in) kg (lb) dBA
MDB300B3 MDB350B3 MMC100B x 3 MMC100C x 3 MMC100B x 1 MMC100C x 1 300,000 350,000 75,600 88,200 87,900 102,550 ELECTRO GALVANIZED MILD STEEL EPOXY POLYESTER POWDER COATING FIBREGLASS / PE 1,291 (50.82) 1,546 (60.86) 1,866 (73.46) 2,122 (83.54) 1,199 (47.20) 1,199 (47.20) 270 (595) 320 (705) 89.4 91.7
MMC125B x 2
CROSS FINNED TUBES SEAMLESS COPPER 0.35 (0.013) 9.52 (3/8) ALUMINIUM 0.127 (0.005)
mm (in) mm (in) mm (in) 5 12 100-67-33-0 1.62 (17.50) 156.66 (514)
% m2 (ft2) m/min (FPM)
4 12 100-67-33-0 2.38 (25.62) 124.96 (410) CENTRIFUGAL / BELT DRIVEN ZINC COATED STEEL
469.90 (18.50) 459.99 (18.11) 254.95(9,000) 20.32 (0.80) 2 SPZ 180 2 SPZ 95 B2
mm (in) mm (in) CMM (CFM) mm wg (in wg) mm mm TYPE
469.90 (18.50) 459.99 (18.11) 297.45 (10,500) 20.32 (0.80) 2 SPZ 250 2 SPZ 125 B2 SQUIRREL CAGE INDUCTION 400 / 3 / 50
V / Ph / Hz A W W
8.00 4,000 4,000 4
10.90 5,500 4,510 4
mm (in) mm (in) mm (in)
15.88 (5/8) 28.58 (1-1/8)
mm mm (in)
533 x 532 50.8 (2.00) 6
R22 NITROGEN HOLDING THERMOSTAT EXPANSION VALVE BRAZING 15.88 (5/8) AND 19.05 (3/4) 28.58 (1-1/8) / 31.75 (1 1/4) 25.40 (1.00) WASHABLE VILEDON
946 (37.24) 1,116 (43.93) 939 (36.96) 193 (425) 72
617 x 661 50.8 (2.00) 6 ELECTRO GALVANIZED MILD STEEL EPOXY POLYESTER POWDER 971.4 (38.24) 946 (37.24) 971.4 (38.24) 1,393 (54.84) 1,116 (43.93) 1,393 (54.84) 500 (19.68) 939 (36.96) 500 (19.68) 176 (387) 193 (425) 176 (387) 75 72 75
946 (37.24) 1,116 (43.93) 939 (36.96) 224 (493) 75
2x2 12 1.76 (19.00) 112.16 (368)
1x3 14 1.35 (14.54) 146.60 (481)
CROSS FINNED TUIBES SEAMLESS COPPER 0.35 (0.013) 9.52 (3/8) ALUMINIUM 0.127 (0.005) 2x2 12 1.76 (19.00) 112.16 (368)
1x3 14 1.35 (14.54) 146.60 (481)
2x2 16 1.76 (19.00) 112.16 (368)
PERMANENT SPLIT CAPACITOR
INDUCTION
PERMANENT SPLIT CAPACITOR
INDUCTION
PERMANENT SPLIT CAPACITOR
CMM (CFM)
ALUMINIUM 660.40 (26) 380-415/3/50 1.50 660 6 198.30 (7,000)
762.00 (30) 380-415/3/50 3.35 1,110 8 198.30 (7,000)
660.40 (26) 380-415/3/50 1.50 660 6 198.30 (7,000)
762.00 (30) 380-415/3/50 3.35 1,110 8 198.30 (7,000)
660.40 (26) 380-415/3/50 1.43 640 6 198.30 (7,000)
V / Ph / Hz A W A
16.9 9,040 125.0
mm (in) mm (in) mm (in) kg (lb) dBA
mm (in) mm (in) mm (in)
2
2
m (ft ) m/min (FPM)
PROPELLER / DIRECT
mm (in) V / Ph / Hz A W
SCROLL 380-415/3/50 16.9 16.9 16.9 17.9 9,040 9,040 9,040 10,200 125.0 125.0 125.0 110.0 OVERLOAD PROTECTION AND MANUAL RESET HIGH / LOW PRESSURE SWITCH ON / OFF AUTO-TRANSFORMER R22 NITROGEN HOLDING
NOTES : 1. ALL UNITS ARE BEING TESTED AND COMPLY TO ARI210/240-89. 2. NOMINAL COOLING CAPACITIES ARE BASED ON THE FOLLOWING CONDITIONS. INDOOR 26.7 °CDB, 19.4 °CWB, OUTDOOR 35 °CDB. 3. ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY MANUFACTURER WITHOUT PRIOR NOTICE. 4. AIR FILTER IS AN OPTIONAL ITEM.
9
MODEL TOTAL COOLING CAPACITY CASING
DIMENSION
INDOOR UNIT OUTDOOR UNIT OUTDOOR 35 °CDB MATERIAL FINISHING INSULATION HEIGHT (H) WIDTH (W) DEPTH (D)
NET WEIGHT NOISE LEVEL EVAPORATOR COIL TYPE TUBE
OUTDOOR
INDOOR UNIT
FIN
MATERIAL WALL THICKNESS OUTER DIAMETER MATERIAL THICKNESS ROWS FIN PER INCH
CAPACITY STEP FACE AREA FACE VELOCITY EVAPORATOR BLOWER TYPE / DRIVE BLOWER MATERIAL BLOWER DIAMETER BLOWER LENGTH AIR FLOW EXTERNAL STATIC PRESSURE BLOWER PULLEY DIAMETER MOTOR PULLEY DIAMETER PULLEY EVAPORATOR BLOWER MOTOR TYPE POWER SUPPLY NUMBER x RATED RUNNING CURRENT NUMBER x RATED OUTPUT NUMBER x RATED INPUT MOTOR POLES REFRIGERANT TYPE TYPE OF GAS PRECHARGED CONTROL PIPE CONNECTION PIPE SIZE LIQUID GAS DRAIN PIPE CONNECTION AIR FILTER TYPE SIZE LENGTH x HEIGHT DEPTH QUANTITY CASING MATERIAL FINISHING HEIGHT (H) DIMENSION WIDTH (W) DEPTH (D) NET WEIGHT NOISE LEVEL CONDENSER COIL TYPE MATERIAL TUBE WALL THICKNESS OUTER DIAMETER MATERIAL FIN THICKNESS NUMBER x ROWS FIN PER INCH FACE AREA FACE VELOCITY CONDENSER FAN DRIVE TYPE BLADE MATERIAL BLADE DIAMETER POWER SUPPLY NUMBER x RATED RUNNING CURRENT NUMBER x RATED INPUT MOTOR POLES AIR FLOW COMPRESSOR TYPE POWER SUPPLY RATED RUNNING CURRENT RATED INPUT MAXIMUM STARTING CURRENT PROTECTION DEVICE STAGE OF CAPACITY CONTROL STARTER TYPE REFRIGERANT TYPE TYPE OF GAS PRECHARGED
Btu/h kcal/h W
MDB400B4 MMC100B x 4 MMC100C x 4 400,000 100,800 117,200
mm (in) mm (in) mm (in) kg (lb) dBA
1,546 (60.86) 2,274 (89.52) 1,466 (57.71) 330 (727) 90.3
MDB450B3 MDB500B4 MMC150C x 3 MMC125B x 4 450,000 500,000 113,400 126,000 131,850 146,500 ELECTRO GALVANIZED MILD STEEL EPOXY POLYESTER POWDER COATING FIBREGLASS / PE 1,546 (60.86) 1,546 (60.86) 2,274 (89.52) 2,274 (89.52) 1,466 (57.71) 1,466 (57.71) 339 (747) 350 (771) 93.4 96.3
MDB600B4 MMC150C x 4 600,000 151,200 175,800
MDB750B5 MMC150C x 5 750,000 189,000 219,750
1,977 (77.83) 2,274 (89.52) 1,905 (75.00) 999 (2,202) 89.1
2,257 (88.85) 2,274 (89.52) 1,905 (75.00) 1,084 (2,389) 93.2
4 14 100-75-50-25-0 2.38 (25.62) 142.94 (468)
CROSS FINNED TUBES SEAMLESS COPPER 0.35 (0.013) 9.52 (3/8) ALUMINIUM 0.127 (0.005) 4 5 14 12 100-67-33-0 100-75-50-25-0 2.58 (27.78) 2.55 (27.45) 147.82 (485) 166.42 (546)
6 12 100-75-50-25-0 3.37 (36.32) 150.87 (495)
6 12 100-80-60-40-20-0 3.97 (42.73) 160.32 (526)
591.82 (23.30) 563.88 (22.20) 339.94 (12,000) 20.32 (0.80) 2 SPA 250 2 SPA 106 B3
CENTRIFUGAL / BELT DRIVEN ZINC COATED STEEL 591.82 (23.30) 591.82 (23.30) 563.88 (22.20) 563.88 (22.20) 382.43 (13,500) 424.92 (15,000) 25.40 (1.00) 25.40 (1.00) 2 SPA 250 2 SPA 315 2 SPA 112 2 SPA 150 B3 B3
785.00 (30.90) 706.00 (27.79) 509.91 (18,000) 30.48 (1.20) 3 SPA 400 3 SPA 132 B3
785.00 (30.90) 706.00 (27.79) 637.39 (22,500) 35.56 (1.40) 3 SPA 400 3 SPA 140 B3
10.90 5,500 4,835 4
SQUIRREL CAGE INDUCTION 400 / 3 / 50 14.40 20.70 7,500 11,000 6,302 8,035 4 4
20.70 11,000 9,200 4
28.10 15,000 11,683 4
15.88 (5/8) 34.92 (1-3/8)
15.88 (5/8) 34.92 (1-3/8)
mm (in) mm (in) mm (in)
% m2 (ft2) m/min (FPM)
mm (in) mm (in) CMM (CFM) mm wg (in wg) mm mm TYPE
V / Ph / Hz A W W
mm (in) mm (in) mm (in)
15.88 (5/8) 28.58 (1-1/8)
mm mm (in)
668 x 661 50.8 (2.00) 6
mm (in) mm (in) mm (in) kg (lb) dBA
946 (37.24) 1,116 (43.93) 939 (36.96) 193 (425) 72
R22 NITROGEN HOLDING THERMOSTAT EXPANSION VALVE BRAZING 15.88 (5/8) 15.88 (5/8) 34.92 (1-3/8) 31.75 (1-1/4) 25.40 (1.00)
668 x 579 50.8 (2.00) 9
668 x 672 50.8 (2.00) 9
971.4 (38.24) 1,393 (54.84) 500 (19.68) 176 (387) 75
WASHABLE VILEDON 668 x 661 668 x 661 50.8 (2.00) 50.8 (2.00) 6 6 ELECTRO GALVANIZED MILD STEEL EPOXY POLYESTER POWDER 1,041 (40.98) 946 (37.24) 1,116 (43.93) 1,116 (43.93) 939 (36.96) 939 (36.96) 258 (568) 224 (493) 77 75
1,041 (40.98) 1,116 (43.93) 939 (36.96) 258 (568) 77
1,041 (40.98) 1,116 (43.93) 939 (36.96) 258 (568) 77
1x3 14 1.35 (14.54) 146.60 (481)
CROSS FINNED TUIBES SEAMLESS COPPER 0.35 (0.013) 9.52 (3/8) ALUMINIUM 0.127 (0.005) 2x2 2x2 14 16 1.24 (13.38) 1.76 (19.00) 131.97 (433) 112.16 (368)
2x2 14 1.24 (13.38) 131.97 (433)
2x2 14 1.24 (13.38) 131.97 (433)
INDUCTION
INDUCTION
762.00 (30) 380-415/3/50 4.35 3,200 6 328.61 (11,600)
762.00 (30) 380-415/3/50 4.35 3,200 6 328.61 (11,600)
mm (in) mm (in) mm (in)
2
2
m (ft ) m/min (FPM)
2x2 12 1.76 (19.00) 112.16 (368)
PROPELLER / DIRECT INDUCTION
P. SPLIT CAPACITOR
mm (in) V / Ph / Hz A W CMM (CFM)
V / Ph / Hz A W A
660.40 (26) 380-415/3/50 1.50 660 6 198.30 (7,000)
762.00 (30) 380-415/3/50 3.35 1,110 8 198.30 (7,000)
P. SPLIT CAPACITOR
ALUMINIUM 762.00 (30) 660.40 (26) 380-415/3/50 380-415/3/50 4.35 1.43 3,200 640 6 6 328.61 (11,600) 198.30 (7,000) SCROLL 380-415/3/50
16.9 9,040 125.0
16.9 23.5 17.9 23.5 9,040 13,300 10,200 13,300 125.0 198.0 110.0 198.0 OVERLOAD PROTECTION AND MANUAL RESET HIGH / LOW PRESSURE SWITCH ON / OFF AUTO-TRANSFORMER R22 NITROGEN HOLDING
NOTES : 1. ALL UNITS ARE BEING TESTED AND COMPLY TO ARI210/240-89. 2. NOMINAL COOLING CAPACITIES ARE BASED ON THE FOLLOWING CONDITIONS. INDOOR 26.7 °CDB, 19.4 °CWB, OUTDOOR 35 °CDB. 3. ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY MANUFACTURER WITHOUT PRIOR NOTICE. 4. AIR FILTER IS AN OPTIONAL ITEM.
10
23.5 13,300 198.0
Specifications Heatpump MODEL
INDOOR UNIT OUTDOOR UNIT
NORMINAL COOLING CAPACITY TOTAL HEATING CAPACITY CASING
DIMENSION
MATERIAL FINISHING INSULATION HEIGHT (H) WIDTH (W) DEPTH (D)
NET WEIGHT NOISE LEVEL EVAPORATOR COIL TYPE TUBE
OUTDOOR UNIT
INDOOR UNIT
FIN
Btu/h kcal/h W Btu/h kcal/h W
MDB075BR MMC075CR 74,000 18,650 21,688 74,000 18,650 21,688
mm (in) mm (in) mm (in) kg (lb) dBA
572 (22.51) 1,502 (59.13) 761 (29.96) 96 (211) 66
MDB100BR MMC100BR 98,800 24,899 28,957 96,560 24,333 28,300 ELECTRO GALVANIZED MILD STEEL EPOXY POLYESTER POWDER COATING PE 572 (22.51) 1,502 (59.13) 761 (29.96) 100 (220) 71
MDB125CR MMC125BR 116,000 29,234 33,998 120,000 30,242 35,170
736 (28.97) 1,640 (64.56) 965 (37.99) 174 (383) 78.1
CROSS FINNED TUBES MATERIAL WALL THICKNESS OUTER DIAMETER MATERIAL THICKNESS ROWS FIN PER INCH
CAPACITY STEP FACE AREA FACE VELOCITY EVAPORATOR BLOWER TYPE / DRIVE BLOWER MATERIAL QUANTITY BLOWER DIAMETER BLOWER LENGTH AIR FLOW EXTERNAL STATIC PRESSURE BLOWER PULLEY DIAMETER MOTOR PULLEY DIAMETER PULLEY EVAPORATOR BLOWER MOTOR TYPE POWER SUPPLY NUMBER x RATED RUNNING CURRENT NUMBER x RATED OUTPUT NUMBER x RATED INPUT MOTOR POLES REFRIGERANT TYPE TYPE OF GAS PRECHARGED PIPE CONNECTION PIPE SIZE LIQUID GAS DRAIN PIPE CONNECTION AIR FILTER TYPE SIZE LENGTH x HEIGHT DEPTH QUANTITY CASING MATERIAL FINISHING HEIGHT (H) DIMENSION WIDTH (W) DEPTH (D) NET WEIGHT NOISE LEVEL CONDENSER COIL TYPE MATERIAL TUBE WALL THICKNESS OUTER DIAMETER MATERIAL FIN THICKNESS NUMBER x ROWS FIN PER INCH FACE AREA FACE VELOCITY CONDENSER FAN TYPE / DRIVE BLADE MATERIAL QUANTITY BLADE DIAMETER POWER SUPPLY NUMBER x RATED RUNNING CURRENT NUMBER x RATED OUTPUT NUMBER x RATED INPUT MOTOR POLES AIR FLOW COMPRESSOR TYPE POWER SUPPLY RATED RUNNING CURRENT (COOLING) RATED RUNNING CURRENT (HEATING) RATED INPUT (COOLING) RATED INPUT (HEATING) MAXIMUM STARTING CURRENT PROTECTION DEVICE STAGE OF CAPACITY CONTROL REFRIGERANT TYPE CONTROL
SEAMLESS COPPER 0.35 (0.013)
mm (in) mm (in)
INNER GROOVE 0.36 (0.014) 9.52 (3/8) ALUMINUM 0.127 (0.005) 4 12 100-0 0.54 (5.82) 167.64 (550)
mm (in)
% 2 2 m (ft ) m/min (FPM)
3 12 100-0 0.54 (5.82) 130.75 (429)
mm (in) mm (in) CMM (CFM) mm wg (in wg) mm mm TYPE
2 282.70 (11.13) 203.00 (8.00) 70.82 (2,500) 10.16 (0.40) -
V / Ph / Hz A W W
CENTRIFUGAL / DIRECT ZINC COATED STEEL 2 282.70 (11.13) 203.20 (8.00) 90.60 (3,200) 10.16 (0.40) -
PERMANENT SPLIT CAPACITOR 220 - 240 / 1 / 50 3.7 496 830 6
mm (in) mm (in) mm (in)
12.70 (1/2) 25.40 (1.00)
mm mm (in)
622 x 433 12.70 (1/2) 2
mm (in) mm (in) mm (in) kg (lb) dBA
946 (37.24) 1,300 (51.18) 500 (19.68) 170 (374) 70
4.0 746 872 6
mm (in)
m 2 (ft2) m/min (FPM)
mm (in) V / Ph / Hz A W W CMM (CFM)
V / Ph / Hz A A W W A
1x2 14 1.23 (13.25) 138.07 (453)
CENTRIFUGAL / BELT DRIVEN 1 394.97 (15.55) 381.00 (15.00) 118.98 (4,200) 15.24 (0.60) 1 SPZ 160 1 SPZ 85 B1 SQUIRREL CAGE INDUCTION 400 / 3 / 50 3 1,500 1,500 4
R22 NITROGEN HOLDING BRAZING 15.88 (5/8) 28.58 (1-1/8) 25.40 (1.00) WASHABLE SARAN NET
mm (in) mm (in)
4 12 100-0 0.79 (8.60) 148.73 (488)
622 x 433 12.70 (1/2) 2 ELECTRO GALVANIZED MILD STEEL EPOXY POLYESTER POWDER 946 (37.24) 1,116 (43.93) 939 (36.96) 205 (451) 72
15.88 (5/8) 34.92 (1-3/8)
WASHABLE VILEDON 457 x 589 50.8 (2.00) 3
CROSS FINNED TUIBES SEAMLESS COPPER 0.35 (0.013) 9.52 (3/8) ALUMINIUM 0.127 (0.005) 2x2 12 1.76 (19.00) 112.16 (368) PROPELLER / DIRECT ALUMINIUM 1 660.40 (26)
1 660.40 (26) 220 - 240 / 1 / 50 1 x 3.00 1 x 480 1 x 680 6 169.97 (6,000)
1 x 3.40 1 x 373 1 x 700 6 198.30 (7,000)
12.7 11.8 6,583 5,820 91.1
RECIPROCATING HERMETIC 380-415/3/50 16.3 14.6 9,550 8,050 104.0 OVERLOAD PROTECTION & AUTO RESET HIGH PRESSURE SWITCH ON / OFF R22 CAPILLARY TUBE (INDOOR & OUTDOOR)
NOTES : 1. ALL UNITS ARE BEING TESTED AND COMPLY TO ARI210/240-89. 2. NOMINAL COOLING CAPACITIES ARE BASED ON THE FOLLOWING CONDITIONS. INDOOR 26.7 °CDB, 19.4 °CWB, OUTDOOR 35 °CDB. 3. ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY MANUFACTURER WITHOUT PRIOR NOTICE. 4. AIR FILTER IS AN OPTIONAL ITEM.
11
1,041 (40.98) 1,116 (43.93) 939 (36.96) 224 (494) 77
INNER GROOVE 0.36 (0.014)
2x2 18 1.76 (19.00) 144.38 (474)
1 762.00 (30) 380-415 / 3 / 50 4.35 1,250 1,720 6 254.84 (9,000)
20.7 17.7 12,230 9,696 135.0
MODEL
INDOOR UNIT OUTDOOR UNIT
NORMINAL COOLING CAPACITY TOTAL HEATING CAPACITY CASING
DIMENSION
MATERIAL FINISHING INSULATION HEIGHT (H) WIDTH (W) DEPTH (D)
NET WEIGHT NOISE LEVEL EVAPORATOR COIL TYPE TUBE
INDOOR UNIT
FIN
MATERIAL WALL THICKNESS OUTER DIAMETER MATERIAL THICKNESS ROWS FIN PER INCH
CAPACITY STEP FACE AREA FACE VELOCITY EVAPORATOR BLOWER TYPE / DRIVE BLOWER MATERIAL BLOWER DIAMETER BLOWER LENGTH AIR FLOW EXTERNAL STATIC PRESSURE BLOWER PULLEY DIAMETER MOTOR PULLEY DIAMETER PULLEY EVAPORATOR BLOWER MOTOR TYPE POWER SUPPLY RATED RUNNING CURRENT RATED OUTPUT POWER NOMINAL RUNNING CURRENT NOMINAL INPUT POWER MOTOR POLES REFRIGERANT TYPE TYPE OF GAS PRECHARGED PIPE CONNECTION PIPE SIZE LIQUID GAS DRAIN PIPE CONNECTION AIR FILTER TYPE SIZE LENGTH x HEIGHT DEPTH QUANTITY CASING
DIMENSION
MATERIAL FINISHING HEIGHT (H) WIDTH (W) DEPTH (D)
NET WEIGHT NOISE LEVEL CONDENSER COIL TYPE TUBE
OUTDOOR UNIT
FIN
MATERIAL WALL THICKNESS OUTER DIAMETER MATERIAL THICKNESS NUMBER x ROWS FIN PER INCH
FACE AREA FACE VELOCITY CONDENSER FAN TYPE / DRIVE BLADE MATERIAL QUANTITY BLADE DIAMETER POWER SUPPLY RATED RUNNING CURRENT RATED OUTPUT POWER RATED INPUT POWER MOTOR POLES AIR FLOW COMPRESSOR TYPE POWER SUPPLY RATED RUNNING CURRENT (COOLING) RATED RUNNING CURRENT (HEATING) RATED INPUT (COOLING) RATED INPUT (HEATING) MAXIMUM STARTING CURRENT PROTECTION DEVICE STAGE OF CAPACITY CONTROL REFRIGERANT TYPE CONTROL
Btu/h kcal/h W Btu/h kcal/h W
MDB150BR2 MMC075CR x 2 148,000 37,298 43,376 148,000 37,298 43,376
MDB200BR2 MMC100BR x 2 197,600 49,798 57,913 193,120 48,669 56,600
mm (in) mm (in) mm (in) kg (lb) dBA
885 (34.84) 1,640 (64.54) 1,040 (40.94) 145 (319) 79
945 (37.20) 1,894 (74.56) 980 (38.58) 180 (396) 85
MDB350BR3 MDB300BR3 MMC100BR x 3 MMC100BR MMC125BR x 2 330,800 296,400 83,367 74,698 96,952 86,870 336,560 289,680 84,819 73,004 98,640 84,900 ELECTRO GALVANIZED MILD STEEL EPOXY POLYESTER POWDER COATING EXPANDED CLOSED CELL PE FOAM 1,546 (60.86) 1,291 (50.82) 1,291 (50.82) 2,122 (83.54) 1,866 (73.46) 1,866 (73.46) 1,199 (47.20) 1,199 (47.20) 1,199 (47.20) 320 (705) 250 (551) 270 (595) 91.7 87 89
MDB250BR2 MMC125BR x 2 232,000 58,468 67,995 240,000 60,484 70,340
MDB400BR4 MMC100BR x 4 395,200 99,597 115,826 386,240 97,339 113,200
MDB500BR4 MMC125BR x 4 464,000 116,935 135,991 480,000 120,968 140,680
1,546 (60.86) 2,274 (89.52) 1,466 (57.71) 330 (727) 90
1,546 (60.86) 2,274 (89.52) 1,466 (57.71) 350 (771) 96
4 14 100-75-50-25-0 2.38 (25.62) 142.94 (468)
5 12 100-75-50-25-0 2.55 (27.45) 166.42 (546)
591.82 (23.30) 563.88 (22.20) 339.94 (12,000) 20.32 (0.80) 2 SPA 250 2 SPA 106 B3
591.8 (23.30) 563.88 (22.20) 424.92 (15,000) 25.40 (1.00) 2 SPA 315 2 SPA 150 B3
11 5,500 8.7 4,835 4
21 11,000 14.7 8,035 4
15.88 (5/8) 28.58 (1-1/8)
15.88 (5/8) 34.92 (1-3/8)
668 x 661 50.8 (2.00) 6
668 x 661 50.8 (2.00) 6
946 (37.24) 1,116 (43.93) 939 (36.96) 205 (451) 72
1,041 (40.98) 1,116 (43.93) 939 (36.96) 224 (493) 77
INNER GROOVE 0.36 (0.014)
BARE TUBE 0.35 (0.013)
INNER GROOVE 0.36 (0.014)
2x2 18 1.76 (19.00) 144.38 (474)
2x2 12 1.76 (19.00) 112.16 (368)
2x2 18 1.76 (19.00) 144.38 (474)
% m2 (ft2 ) m/min (FPM)
4 12 100-50-0 1.00 (10.82) 129.54 (425)
4 12 100-50-0 1.20 (12.92) 150.87 (495)
4 14 100-50-0 1.48 (16.01) 152.40 (500)
CROSS FINNED TUBES SEAMLESS COPPER 0.35 (0.013) 9.52 (3/8) ALUMINIUM 0.127 (0.005) 4 5 12 12 100-67-33-0 100-67-33-0 2.38 (25.62) 1.62 (17.50) 124.96 (410) 156.66 (514)
mm (in) mm (in) CMM (CFM) mm wg (in wg) mm mm TYPE
394.97 (15.55) 381.00 (15.00) 130.31 (4,600) 15.24 (0.60) 1 SPZ 160 1 SPZ 80 B1
394.97 (15.55) 381.00 (15.00) 181.30 (6,400) 15.24 (0.60) 2 SPZ 140 2 SPZ 80 B1
469.90 (18.50) 459.99 (18.11) 226.62 (8,000) 20.32 (0.80) 2 SPZ 180 2 SPZ 90 B2
CENTRIFUGAL / BELT DRIVEN ZINC COATED STEEL 469.90 (18.50) 469.90 (18.50) 459.99 (18.11) 459.99 (18.11) 297.45 (10,500) 254.95 (9,000) 20.32 (0.80) 20.32 (0.80) 2 SPZ 250 2 SPZ 180 2 SPZ 125 2 SPZ 95 B2 B2
mm (in) mm (in) mm (in)
V / Ph / Hz A W A W
3 1,500 3.1 1,630 4
6 3,000 5.0 2,730 4
SQUIRREL CAGE INDUCTION 400 / 3 / 50 10.9 8 5,500 4,000 8.4 7.1 4,510 4,000 4 4
8 4,000 6.3 3,370 4
R22 NITROGEN HOLDING BRAZING 15.88 (5/8) 15.88 (5/8) 28.58 (1-1/8) 28.58 (1-1/8) 25.40 (1.00)
mm (in) mm (in) mm (in)
12.70 (1/2) 25.40 (1.00)
15.88 (5/8) 28.58 (1-1/8)
15.88 (5/8) 34.92 (1-3/8)
mm mm (in)
457 x 738 50.8 (2.00) 3
542 x 738 50.8 (2.00) 3
533 x 532 50.8 (2.00) 6
mm (in) mm (in) mm (in) kg (lb) dBA
946 (37.24) 1,300 (51.18) 500 (16.98) 170 (374) 70
946 (37.24) 1,116 (43.93) 939 (36.96) 205 (451) 72
1,041 (40.98) 1,116 (43.93) 939 (36.96) 224 (493) 77
BARE TUBE 0.35 (0.013)
mm (in) mm (in)
INNER GROOVE 0.36 (0.014)
mm (in) 1x2 14 1.23 (13.25) 138.07 (453)
2x2 12 1.76 (19.00) 112.16 (368)
CMM (CFM)
1 660.40 (26) 220-240 / 1 / 50 3 480 680 6 169.97 (6,000)
1 660.40 (26) 220-240 / 1 / 50 3.4 373 700 6 198.30 (7,000)
V / Ph / Hz A A W W A
12.7 11.8 6,583 5,820 91.1
16.3 14.6 9,550 8,050 104.0
2
2
m (ft ) m/min (FPM)
mm (in) V / Ph / Hz A W W
2x2 18 1.76 (19.00) 144.38 (474)
15.88 (5/8) 34.92 (1-3/8)
WASHABLE VILEDON 617 x 661 533 x 532 50.8 (2.00) 50.8 (2.00) 6 6 ELECTRO GALVANIZED MILD STEEL EPOXY POLYESTER POWDER 946 (37.24) 946 (37.24) 1,041 (40.98) 1,116 (43.93) 1,116 (43.93) 1,116 (43.93) 939 (36.96) 939 (36.96) 939 (36.96) 205 (451) 205 (451) 224 (493) 72 72 77 CROSS FINNED TUIBES BARE TUBE 0.35 (0.014) 9.52 (3/8) ALUMINIUM 0.127 (0.005) 2x2 2x2 12 12 1.76 (19.00) 1.76 (19.00) 112.16 (368) 112.16 (368)
PROPELLER / DIRECT ALUMINIUM 1 1 1 1 660.40 (26) 660.40 (26) 762.00 (30) 660.40 (26) 220-240 / 1 / 50 220-240 / 1 / 50 380-415 / 3 / 50 220-240 / 1 / 50 3.4 3.4 4.35 3.4 373 373 1,250 373 700 700 1,720 700 6 6 6 6 198.30 (7,000) 198.30 (7,000) 254.84 (9,000) 198.30 (7,000) . RECIPROCATING HERMETIC 380-415/3/50 20.7 16.3 16.3 20.7 16.3 17.7 14.6 14.6 17.7 14.6 12,230 9,550 9,550 12,230 9,550 9,696 8,050 8,050 9,696 8,050 135.0 104.0 104.0 135.0 104.0 OVERLOAD PROTECTION AND AUTO RESET HIGH PRESSURE SWITCH ON / OFF 1 762.0 (30) 380-415 / 3 / 50 4.35 1,250 1,720 6 254.84 (9,000)
R22 CAPILLARY TUBE (INDOOR & OUTDOOR)
NOTES : 1. ALL UNITS ARE BEING TESTED AND COMPLY TO ARI210/240-89. 2. NOMINAL COOLING CAPACITIES ARE BASED ON THE FOLLOWING CONDITIONS. INDOOR 26.7 °CDB, 19.4 °CWB, OUTDOOR 35 °CDB. 3. ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY MANUFACTURER WITHOUT PRIOR NOTICE. 4. AIR FILTER IS AN OPTIONAL ITEM.
12
1 762.00 (30) 380-415 / 3 / 50 4.35 1,250 1,720 6 254.84 (9,000)
20.7 17.7 12,230 9,696 135.0
Performance characteristics System Cooling Capacity AIR ON EVAPORATOR
MODEL MDB075B / MMC075C
MDB100B / MMC100B
MDB125B / MMC125B
MDB125B / MMC125B
MDB125B / MMC125B
MDB150B / MMC150C
MDB150B / MMC150C
MDB150B / MMC150C
MDB200B2 / 2 X MMC100B
MDB200B2 / 2 X MMC100B
MDB200B2 / 2 X MMC100B
KEY :
EDB EWB TC TSC
AIR VOL.
EDB
EWB
CFM
°F
°F
2500
3200
5000
4600
4200
5000
4600
4200
6800
6400
6000
80
80
80
80
80
80
80
80
80
80
80
DRY BULB TEMPERATURE (DEG F) - AIR ENTERING CONDENSER 80
85
95
100
105
115
TC TSC 1000 BTU/H
TC TSC 1000 BTU/H
TC TSC 1000 BTU/H
TC TSC 1000 BTU/H
TC TSC 1000 BTU/H
TC TSC 1000 BTU/H
57
72.42
72.42
70.92
70.91
67.26
67.26
65.31
65.31
63.17
63.16
59.08
58.28
62
75.05
67.77
73.47
66.17
68.76
63.80
66.37
63.71
64.03
61.44
59.30
58.66
67
82.08
57.00
80.35
55.64
75.00
56.25
72.16
53.23
69.61
51.55
64.45
49.21
72
89.56
45.56
87.65
44.48
82.08
42.53
79.29
41.88
75.54
40.38
70.91
38.46
57
96.56
96.56
94.30
94.30
89.44
89.44
86.85
86.85
84.00
84.00
78.56
78.56
62
100.07
90.13
97.70
88.00
91.44
84.85
88.26
84.72
85.15
81.70
78.85
78.00
67
109.44
75.80
106.85
74.00
100.00
75.00
95.97
70.79
92.56
68.30
85.70
65.44
72
119.41
60.59
116.56
59.15
109.15
56.56
105.44
55.70
101.70
53.70
94.30
51.15
57
128.04
128.04
125.04
125.04
118.60
118.60
115.17
115.17
111.38
111.38
104.17
104.17
62
132.69
119.51
129.56
116.69
121.25
112.51
117.04
112.34
112.91
108.34
104.56
103.43
67
145.12
100.52
141.69
98.12
132.60
106.08
127.25
93.86
122.73
90.56
113.64
86.78
72
158.34
80.34
154.56
78.43
144.73
75.00
139.82
73.86
134.86
71.21
125.04
67.82
57
124.22
124.22
121.31
121.31
115.07
115.07
111.74
111.74
108.07
108.07
101.06
101.06
62
128.73
115.95
125.70
113.21
117.64
109.16
113.55
108.99
109.54
105.11
101.44
100.35
67
140.80
97.52
137.47
95.20
128.65
96.50
123.46
91.07
119.08
87.86
110.26
84.19
72
153.62
77.95
149.95
76.09
140.42
72.76
135.65
71.66
130.84
69.09
121.31
65.80
57
118.82
118.82
116.04
116.04
110.07
110.07
106.88
106.88
103.37
103.37
96.67
96.67
62
123.14
110.92
120.24
108.29
112.53
104.42
108.62
104.26
104.78
100.55
97.04
95.99
67
134.68
93.28
131.49
91.06
125.00
87.50
118.10
87.11
113.90
84.04
105.47
80.53
72
146.95
74.56
143.44
72.79
134.32
69.60
129.76
68.55
125.16
66.09
116.04
62.94
57
154.15
154.15
150.54
150.54
142.80
142.80
138.66
138.66
134.11
134.11
125.42
125.42
62
159.75
143.89
155.99
140.49
145.99
135.17
140.91
135.26
135.94
130.44
125.89
124.53
67
174.73
121.02
170.59
118.14
159.65
122.93
153.21
113.01
147.77
109.03
136.83
104.48
72
190.64
96.73
186.08
94.43
174.25
90.29
168.34
88.93
162.37
85.74
150.54
81.66
57
144.84
144.84
141.44
141.44
134.16
134.16
130.28
130.28
126.00
126.00
117.84
117.84
62
150.10
135.20
146.56
132.00
137.16
127.28
132.39
127.08
127.72
122.56
118.28
117.00 98.16
67
164.16
113.70
160.28
111.00
150.00
106.50
143.95
106.18
138.84
102.44
128.56
72
179.11
90.89
174.84
88.72
163.72
84.84
158.16
83.56
152.56
80.56
141.44
76.72
57
135.52
135.52
132.34
132.34
125.53
125.53
121.90
121.90
117.89
117.89
110.26
110.26
62
140.44
126.50
137.13
123.51
128.34
119.09
123.88
118.91
119.50
114.67
110.67
109.47
67
153.60
106.39
149.97
103.86
140.35
91.23
134.69
99.35
129.90
95.85
120.29
91.85
72
167.59
85.04
163.59
83.01
153.19
79.38
147.99
78.18
142.74
75.37
132.34
71.79
57
202.29
202.29
197.55
197.55
187.38
187.38
181.69
181.96
175.98
175.98
164.58
164.58
62
209.64
188.82
204.69
184.36
191.57
177.77
184.91
177.49
178.38
171.17
165.20
163.41
67
229.28
158.81
223.86
155.03
209.50
165.52
201.05
148.30
193.91
143.08
179.55
137.10
72
250.16
126.94
244.19
123.91
228.66
118.49
220.90
116.70
213.07
112.51
197.55
107.15
57
195.05
195.05
190.48
190.48
180.67
180.67
175.44
175.44
169.68
169.68
158.69
158.69
62
202.13
182.06
197.36
177.76
184.71
171.40
178.29
171.14
172.00
165.04
159.28
157.56
67
221.07
153.12
215.84
149.48
200.00
140.00
193.85
142.99
186.97
137.96
173.12
132.19
72
241.21
122.39
235.45
119.48
220.48
114.25
212.99
112.52
205.44
108.48
190.48
103.32
57
187.78
187.78
183.39
183.39
173.95
173.95
168.91
168.91
163.36
163.36
152.78
152.78
62
194.61
175.29
190.02
171.14
177.84
165.02
171.65
164.77
165.59
158.90
153.35
151.69
67
212.84
147.42
207.81
143.92
194.48
141.96
186.64
137.67
180.01
132.82
166.68
127.27
72
232.23
117.84
226.68
115.03
212.27
109.99
205.06
108.33
197.80
104.45
183.39
99.47
- ENTERING DRY BULB - ENTERING WET BULB - TOTAL COOLING CAPACITY - TOTAL SENSIBLE COOLING CAPACITY
13
System Cooling Capacity AIR ON EVAPORATOR
MODEL MDB250B2 / 2X MMC125B
MDB250B2 / 2X MMC125B
MDB250B2 / 2X MMC125B
MDB300B2 / 2X MMC150C
MDB300B2 / 2X MMC150C
MDB300B2 / 2X MMC150C
MDB300B2 MMC150Cx2
MDB350B3 / 1X MMC100B + 2X MMC125B MDB350B3 / 1X MMC100B + 2X MMC125B MDB350B3 / 1X MMC100B + 2X MMC125B KEY : EDB EWB TC TSC
DRY BULB TEMPERATURE (DEG F) - AIR ENTERING CONDENSER 80
85
95
100
105
115
AIR VOL.
EDB
EWB
CFM
°F
°F
1000 BTU/H 1000 BTU/H 1000 BTU/H 1000 BTU/H 1000 BTU/H 1000 BTU/H
57
252.29 252.29 246.37 246.37 233.70 233.70 226.93 226.93
219.48
219.48 205.25 205.25
62
261.45 235.49 255.28 229.93 238.92 221.70 230.61 221.36
222.47
213.48 206.03 203.80
67
285.95 198.06 279.18 193.35 261.28 209.02 250.74 184.95
241.83
178.44 223.93 170.09
72
311.99 158.31 304.54 154.54 285.18 147.77 275.50 145.55
265.73
140.32 246.37 133.64
57
243.32 243.32 237.62 237.62 225.40 225.40 218.87 218.87
211.68
211.68 197.96 197.96
62
252.17 227.13 246.22 221.76 230.44 213.83 222.42 213.50
214.57
205.90 198.71 196.56
67
275.80 191.02 269.27 186.48 250.00 175.00 241.84 178.38
233.24
172.10 215.98 164.92
72
300.91 152.69 293.72 149.05 275.05 142.52 265.72 140.38
256.30
135.34 237.62 128.89
57
230.52 230.52 225.12 225.12 213.54 213.54 207.35 207.35
200.54
200.54 187.55 187.55
62
238.90 215.18 233.26 210.09 218.31 202.58 210.72 202.26
203.28
195.06 188.25 186.22
67
261.28 180.97 255.10 176.67 238.74 169.50 229.11 169.00
220.97
163.05 204.61 156.24
72
285.08 144.65 278.27 141.21 260.58 135.03 251.73 132.99
242.81
128.22 225.12 122.11
57
302.61 302.61 295.52 295.52 280.31 280.31 272.20 272.20
263.26
263.26 246.20 246.20
62
313.61 282.47 306.21 275.79 286.58 265.93 276.61 265.52
266.85
256.06 247.12 244.45
67
342.99 237.57 334.88 231.92 313.40 225.65 300.76 221.85
290.07
214.04 268.60 205.10
72
374.23 189.89 365.29 185.37 342.07 177.25 330.46 174.58
318.74
168.31 295.52 160.30
57
289.36 289.36 282.58 282.58 268.04 268.04 260.28 260.28
251.73
251.73 235.42 235.42
62
299.88 270.11 292.80 263.72 274.04 254.29 264.50 253.89
255.17
244.85 236.31 233.75
67
327.98 227.17 320.22 221.76 300.00 210.00 287.59 212.13
277.38
204.67 256.84 196.12
72
357.85 181.58 349.30 177.25 327.09 169.49 315.99 166.94
304.79
160.94 282.58 153.28
57
277.79 277.79 271.28 271.28 257.32 257.32 249.87 249.87
241.66
241.66 226.00 226.00
62
287.88 259.30 281.09 253.17 263.07 244.11 253.92 243.73
244.96
235.06 226.85 224.40
67
314.86 218.08 307.40 212.89 288.54 181.25 276.09 203.65
266.28
196.48 246.56 188.27
72
343.53 174.31 335.32 170.16 314.01 162.71 303.35 160.26
292.59
154.50 271.28 147.15
57
289.36 289.36 282.58 282.58 268.04 268.04 260.28 260.28
51.73
251.73 235.42 235.42
62
299.88 270.11 292.80 263.72 274.04 254.29 264.50 253.89
255.17
244.85 236.31 233.75
67
327.98 227.17 320.22 221.76 300.00 210.00 287.59 212.13
277.38
204.67 256.84 196.12
72
357.85 181.58 349.30 177.25 327.09 169.49 315.99 166.94
304.79
160.94 282.58 153.28
57
308.40 308.40 301.18 301.18 285.68 285.68 277.41 277.41
268.30
268.30 250.91 250.91
62
319.61 287.88 312.07 281.07 292.07 271.02 281.91 270.60
271.96
260.97 251.85 249.13
67
349.56 242.12 341.29 236.36 319.40 219.00 306.52 226.09
295.63
218.13 273.74 209.02
72
381.40 193.52 372.28 188.92 348.62 180.64 336.78 177.92
324.85
171.53 301.18 163.37
57
337.95 337.95 330.03 330.03 313.05 313.05 303.98 303.98
294.00
294.00 274.95 274.95
62
350.23 315.46 341.97 308.00 320.05 296.98 308.92 296.52
298.02
285.97 275.93 273.00
67
383.05 265.31 373.98 259.00 350.00 255.50 335.98 247.75
323.95
239.03 299.97 229.05
72
417.93 212.07 407.95 207.02 382.02 197.95 369.05 194.97
355.97
187.97 330.03 179.02
57
358.42 358.42 350.02 350.02 332.01 332.01 322.40 322.40
311.81
311.81 291.60 291.60
62
371.44 334.57 362.68 326.66 339.44 314.97 327.63 314.49
316.07
303.29 292.70 289.54
67
406.25 281.38 396.64 274.69 371.20 292.00 356.23 262.76
343.57
253.51 318.14 242.92
72
443.25 224.91 432.66 219.56 405.16 209.94 391.40 206.78
377.53
199.35 350.02 189.86
8600
8000
7400
9600
9000
8400
9000
9000
10500
12000
80
80
80
TC
TSC
TC
TSC
TC
TSC
TC
TSC
TC
TSC
TC
TSC
80
80
80
80
80
80
80
- ENTERING DRY BULB - ENTERING WET BULB - TOTAL COOLING CAPACITY - TOTAL SENSIBLE COOLING CAPACITY
14
System Cooling Capacity AIR ON EVAPORATOR AIR VOL.
EDB
EWB
CFM
°F
°F
MODEL MDB400B4 /4X MMC100B
MDB400B4 /4X MMC100B
MDB400B4 /4X MMC100B
MDB500B4 /4X MMC125B
MDB500B4 /4X MMC125B
MDB500B4 /4X MMC125B
MDB600B4 /4X MMC150C
MDB600B4 /4X MMC150C
MDB600B4 /4X MMC150C
MDB750B5 /5X MMC150C
MDB750B5 /5X MMC150C
MDB750B5 /5X MMC150C
KEY :
10000
12000
14000
11000
13000
15000
16000
18000
20000
21000
22500
23500
EDB EWB TC TSC
80
80
80
80
80
80
80
80
80
80
80
80
DRY BULB TEMPERATURE (DEG F) - AIR ENTERING CONDENSER 80 TC
85 TSC
1000 BTU/H
TC
95 TSC
1000 BTU/H
TC
100 TSC
1000 BTU/H
TC
105 TSC
1000 BTU/H
TC
115 TSC
1000 BTU/H
TC
TSC
1000 BTU/H
57
339.88
339.88
331.92
331.92
314.84
314.84
305.72
305.72
295.68
295.68
276.52
276.52
62
352.23
317.26
343.92
309.76
321.88
298.68
310.68
298.22
299.72
287.60
277.56
274.56
67
385.24
266.83
376.12
260.48
352.00
243.00
337.80
249.17
325.80
240.40
301.68
230.36
72
420.32
213.28
410.28
208.20
384.20
199.08
371.16
196.08
358.00
189.04
331.92
180.04
57
386.23
386.23
377.18
377.18
357.77
357.77
347.41
347.41
336.00
336.00
314.23
314.23
62
400.26
360.52
390.82
352.00
365.77
339.41
353.05
338.89
340.59
326.82
315.41
312.00
67
437.77
303.21
427.41
96.00
400.00
291.60
383.87
283.15
370.23
273.18
342.82
261.77
72
477.64
242.36
466.23
236.59
436.59
226.23
421.77
222.82
406.82
214.82
377.18
204.59
57
412.59
412.59
402.92
402.92
382.19
382.19
371.12
371.12
358.93
358.93
335.68
335.68
62
427.58
385.13
417.49
376.02
390.73
362.57
377.14
362.01
363.84
349.13
336.94
333.29
67
467.65
323.91
456.58
316.20
427.30
340.20
410.07
302.47
395.50
291.82
366.22
279.64
72
510.24
258.90
498.05
252.74
466.39
241.67
450.56
238.03
434.59
229.48
402.92
218.55
57
402.16
402.16
392.74
392.74
372.53
372.53
361.74
361.74
349.86
349.86
327.19
327.19
62
416.77
375.40
406.94
366.52
380.86
353.41
367.61
352.86
354.64
340.30
328.42
324.87
67
455.83
315.72
445.04
308.21
416.50
267.70
399.70
294.83
385.50
284.45
356.96
272.57
72
497.34
252.36
485.46
246.35
454.60
235.56
439.17
232.01
423.60
223.68
392.74
213.03
57
441.75
441.75
431.40
431.40
409.20
409.20
397.35
397.35
384.30
384.30
359.40
359.40
62
457.80
412.35
447.00
402.60
418.35
388.20
403.80
387.60
389.55
373.80
360.75
356.85
67
500.70
345.80
488.85
338.55
457.50
316.30
439.05
323.85
423.45
312.45
392.10
299.40
72
546.30
277.20
533.25
270.60
499.35
285.75
482.40
254.85
465.30
245.70
431.40
234.00
57
482.79
482.79
471.48
471.48
447.21
447.21
434.26
434.26
420.00
420.00
392.79
392.79
62
500.33
450.66
488.52
440.00
457.21
424.26
441.31
423.61
452.74
408.52
394.26
390.00
67
547.21
379.02
534.26
370.00
500.00
365.00
479.84
353.93
462.79
341.48
428.52
327.21
72
597.05
302.95
582.79
295.74
545.74
282.79
527.21
278.52
508.52
268.52
471.48
255.74
57
509.27
509.27
497.34
497.34
471.75
471.75
458.09
458.09
443.04
443.04
414.34
414.34
62
527.79
475.39
515.33
464.15
482.31
447.55
465.52
446.85
449.10
430.94
415.91
411.40
67
577.24
399.82
563.59
390.30
528.00
369.60
506.16
373.35
488.19
360.22
452.04
345.17
72
629.82
319.58
614.77
311.96
575.68
298.30
556.14
293.81
536.43
283.25
497.34
269.77
57
578.72
578.72
565.16
565.16
536.08
536.08
520.56
520.56
503.46
503.46
470.84
470.84
62
599.76
540.22
585.60
527.44
548.08
508.58
529.00
507.78
510.34
489.70
472.62
467.50
67
655.96
454.34
640.44
443.52
600.00
420.00
575.18
424.26
554.76
409.34
513.68
392.24
72
715.70
363.16
698.60
354.50
654.18
338.98
631.98
333.88
609.58
321.88
565.16
306.56
57
607.66
607.66
593.42
593.42
562.88
562.88
546.59
546.59
528.63
528.63
494.38
494.38
62
629.75
567.23
614.88
553.81
575.48
534.01
555.45
533.17
535.86
514.19
496.25
490.88
67
688.76
477.06
672.46
465.70
630.00
441.00
603.94
445.47
582.50
429.81
539.36
411.85
72
751.49
381.32
733.53
372.23
686.89
355.93
663.58
350.57
640.06
337.97
593.42
321.89
57
687.38
687.38
670.76
670.76
636.73
636.73
618.30
618.30
597.99
597.99
559.25
559.25
62
712.37
641.65
695.55
626.47
650.98
604.07
628.32
603.12
606.16
581.65
561.36
555.28
67
779.11
539.64
760.68
526.79
712.50
498.75
683.17
503.92
658.92
486.19
610.13
465.88
72
850.07
431.35
829.77
421.06
777.01
402.63
750.63
396.57
724.03
382.32
671.27
364.12
57
723.56
723.56
706.60
706.60
670.24
670.24
650.84
650.84
629.46
629.46
588.68
588.68
62
749.86
675.42
732.16
659.44
685.24
635.86
661.39
634.86
638.06
612.26
590.90
584.50
67
820.12
568.04
800.72
554.52
750.00
525.00
719.13
530.44
693.60
511.78
642.24
490.40
72
894.81
454.05
873.44
443.22
817.90
423.82
790.14
417.44
762.14
402.44
706.60
383.28
57
759.74
759.73
741.66
741.36
703.75
703.75
683.38
683.38
660.93
660.93
618.11
618.11
62
787.35
709.19
768.77
692.41
719.50
667.65
694.46
666.60
669.96
642.87
620.45
613.73
67
861.13
596.44
840.76
582.25
787.50
551.25
755.09
556.96
728.28
537.37
674.35
514.92
72
939.55
476.75
917.11
465.38
858.80
445.06
829.65
438.31
800.25
422.56
741.93
402.44
- ENTERING DRY BULB - ENTERING WET BULB - TOTAL COOLING CAPACITY - TOTAL SENSIBLE COOLING CAPACITY
15
Drive package selection example For MDB250B2, given conditions : Supply Air Quantity
= 8,000 CFM
External Static Pressure = 0.8 in. wg. Step 1:
Find the velocity pressure (Hd). From blower performance curve of SB250B2, The velocity pressure at 8,000 CFM supply air = 0.55 in. wg.
Step 2:
Find total external static pressure (Ht). Total external static pressure = External static pressure + Velocity pressure (Hd) = 0.8 in. wg. + 0.55 in.wg. = 1.35 in. wg.
Step 3:
Find fan operating speed and brake kW Read from blower performance curve of MDB250B2, a) Fan speed
= 725 RPM
b) Brake kW
= 2.75 kW
c) Fan efficiency = 72.4 % d) Motor kW
= Brake kW x Safety factor (1.2) = 2.75 kW x 1.2 = 3.3 kW
≅ 4.0 kW Step 4:
Assuming change motor pulley only. Calculate motor pulley diameter (X). X = [ Blower speed (RPM) x Blower pulley diameter (in) ] / Motor speed (RPM) Fix blower pulley diameter = 12 in Read from Motor and Blower Specifications table, a) Motor speed
= 1440 RPM
b) X
= [ 725 x 12 ] / 1440 = 6.04 in
∴Choose 6.5” ( the next pulley size which is bigger than 6.04”) Step 5:
Calculate V-belt size. Read from Motor and Blower Specifications table, A = Motor to blower centre point ( 623 mm ) x 2 = 1,246 mm B = Motor pulley diameter ( 6.5” or 165.1 mm ) + Blower pulley diameter ( 12” or 304.8 mm) = 469.9 mm Belt size = A + B × pi / 2 = 1984.1 mm or 78.1 in ≅ 78 in Summary i) Fan Motor kW
= 4kW
ii) Motor Pulley Diameter
= 6.5 in
iii) V-Belt Size
= 78 in
16
Motor And Blower Specifications For 50Hz Models Models Description Motor kW
Unit kW
RPM
MDB125B
MDB150B2/ B1
MDB200B2/B1 MDB250B2/B1
MDB300B3/ B2
MDB350B3
1.5
1.5
3.0
4.0
4.0
5.5
1425
1425
1430
1440
1440
1445 2 SPZ/125/1610/38
Motor pulley size
in
1 SPZ/80/1210/24
1 SPZ/80/1210/24
2 SPZ/80/1210/28
2 SPZ/90/1610/28
2 SPZ/95/1610/28
Motor shaft size
mm
24
24
28
28
28
38
in
1 SPZ/160/1610/25
1 SPZ/160/1610/25
2 SPZ/140/1610/25
2 SPZ/180/2012/25
2 SPZ/180/2012/25
2 SPZ/250/2012/25
Blower pulley size Blower shaft size
mm
25
25
25
25
25
25
Air flow
CFM
4200
4600
6400
8000
9000
10500
Horizontal air discharge Motor to blower centre point V-Belt size
mm
319
319
314
599
599
840
in
SPZ1060
SPZ1060
SPZ1000
SPZ1650
SPZ1650
SPZ2287
Vertical air discharge Motor to blower centre point V-Belt size
Description
mm
340
340
330
623
623
870
in
SPZ1080
SPZ1080
SPZ1010
SPZ1700
SPZ1700
SPZ2360
Unit
Models MDB400B4/ B2
Motor kW
kW
RPM
MDB450 B3
MDB500B4 /B2
MDB600B4 /B3
MDB750B5 /B3
MDB125C
MDB150C1
5.5
7.5
11.0
11.0
15.0
1.5
2.2
1445
1445
1445
1450
1455
1425
1425 2SPZ/71/1108/28
Motor pulley size
in
2 SPA/106/1610/38
2 SPA/112/1610/38
2 SPA/150/2012/42
3 SPA/132/2012/42
3 SPA/140/2517/42
1SPZ/85/1210/24
Motor shaft size
mm
38
38
42
42
42
24
28
in
2 SPA/250/2517/35
2 SPA/250/2517/35
2 SPA/315/2517/35
3 SPA/400/3020/40
3 SPA/400/3020/40
1SPZ/160/1610/25
2SPZ/125/1610/25
Blower pulley size Blower shaft size
mm
35
35
35
40
40
25
25
Air flow
CFM
12000
13500
15000
18000
22500
4200
4600
Horizontal air discharge Motor to blower centre point V-Belt size
mm
732
738
700
300
300
185
185
in
SPA2060
SPA2060
SPA2182
SPA1507
SPA1507
SPZ 760
SPZ 670
Vertical air discharge Motor to blower centre point V-Belt size
mm
782
768
751
490
490
-
-
in
SPA2160
SPA2160
SPA2270
SPA1850
SPA1850
-
-
17
Blower performance curves Model: MDB 075B / BR (Double Blowers)
Model: MDB 100B / BR (Double Blowers)
18
Blower Performance Curves Model: MDB 125B, 150B2, 150B1/BR1, 200B2/BR2, 125C/CR, 150C2/CR2, 150C1
Model: MDB 250B2/BR2, 300B3/BR3, 350B3/BR3
19
Blower Performance Curves Model: MDB 400B4/BR4, 450B3, 500B4/BR4
Model: MDB 600B4, 750B5
20
Outlines and dimensions (indoor) Model: MDB 075/ 100 B/BR
Model: MDB 125B/BR (Convertible Horizontal / Vertical Air Discharge)
21
Model: MDB 125C (Horizontal Air Discharge Only)
Model: MDB 150B1 (Convertible Horizontal / Vertical Air Discharge)
22
Model: MDB 150B2/BR2 (Convertible Horizontal / Vertical Air Discharge)
Model: MDB 150C1 (Horizontal Air Discharge Only)
23
Model: MDB 200B2/BR2 (Convertible Horizontal / Vertical Air Discharge)
Model: MDB 250/300 B2/BR2 (Convertible Horizontal / Vertical Air Discharge)
24
Model: MDB 300B3/BR3 (Convertible Horizontal / Vertical Air Discharge)
Model: MDB 350B3/BR3 (Convertible Horizontal / Vertical Air Discharge)
25
Model: MDB 400 / 500 B4/BR4 (Convertible Horizontal / Vertical Air Discharge)
Model: MDB 600B4 (Convertible Horizontal / Vertical Air Discharge)
26
Model: MDB 750B5 (Convertible Horizontal / Vertical Air Discharge)
27
Outlines and dimensions (outdoor) (outdoor) Model: MMC 075B, 100/125 B/BR (Standard Vertical Air Discharge)
Model: MMC 075B, 100/125 B/BR (Optional Horizontal Air Discharge)
28
Model: MMC 075C/CR
Model: MMC 100C
29
Model: MMC 150C
30
Wiring diagrams (heat pump) Indoor (Export) Model : MDB 075/100BR (C3.0B)
Model : MDB 125CR (Export)
31
Model : MDB 150/ 200/ 250 BR2 (Export)
Model : MDB 300/ 350 BR3 (Export)
32
Model : MDB 400/ 500 BR4 (Export)
33
Wiring diagrams (heat pump) Outdoor (Export) Model : MMC 075CR / 100BR (for sequential controller)
Note : With auto pressure control DANFOSS magnetic contactor Headline outdoor fan motor (single phase)
Model : MMC 125BR (Export) (for sequential controller)
Note : With auto pressure control DANFOSS magnetic contactor Headline outdoor fan motor
34
Indoor to Outdoor Wiring Diagram (heat pump) Model : MMC 075CR / 100BR/ 125BR (Outdoor) & MDB 075 / 100BR / 125CR (Indoor)
Model : MMC 075CR / 100BR/ 125BR (Outdoor) & MDB 150 / 200 / 250BR2 / 300BR3 / 350BR3 / 400BR4 / 500BR4 (Indoor)
35
Wiring Diagram (cooling) Model : MDB 075B – MMC 075C
Symbol DOL BM 51 BM SW AUX. TH TDR
Description Direct on line Blower motor Blower motor overload relay Switch Auxiliary control Thermostat control Time delay relay
Important note : A manual reset circuit must be provided at the field supplied external starter board for all protective devices.
Note : For export spec.
36
Model : MDB 075B/100B – MMC 075B/100B/100C
Symbol DOL BM 51 BM SW AUX. TH TDR
Description Direct on line Blower motor Blower motor overload relay Switch Auxiliary control Thermostat control Time delay relay
Important note : A manual reset circuit must be provided at the field supplied external starter board for all protective devices.
Note : For export spec.
37
Model : MDB 125B – MMC 125B MDB 150B2 – MMC 075B X 2
Symbol DOL BM 51 BM SW AUX. TH TDR
Description Direct on line Blower motor Blower motor overload relay Switch Auxiliary control Thermostat control Time delay relay
Important note : A manual reset circuit must be provided at the field supplied external starter board for all protective devices.
Note : For export spec.
38
Model : MDB 150B1 – MMC 150C
Symbol DOL BM 51 BM SW AUX. TH TDR
Description Direct on line Blower motor Blower motor overload relay Switch Auxiliary control Thermostat control Time delay relay
Important note : A manual reset circuit must be provided at the field supplied external starter board for all protective devices.
Note : For export spec.
39
Model : MDB 200B2 – MMC 100B X 3 MDB 250B2 – MMC 125B X 2 MDB 300B3 – MMC 100B X 3 MDB 350B3 – MMC 125B X 2, MMC 100B MDB 400B4 – MMC 100B X 4 MDB 500B4 – MMC 125B X 4
Symbol DOL BM 51 BM SW AUX. TH TDR
Description Direct on line Blower motor Blower motor overload relay Switch Auxiliary control Thermostat control Time delay relay
Important note : A manual reset circuit must be provided at the field supplied external starter board for all protective devices.
Note : For export spec.
40
Model : MDB 300B2 – MMC 150C x 2 MDB 450B3 – MMC 150C x 3 MDB 600B4 – MMC 150C x 4 MDB 750B5 – MMC 150C x 5
Symbol SDS BM 51 BM SW AUX. TH TDR
Description Star delta starter Blower motor Blower motor overload relay Switch Auxiliary control Thermostat control Time delay relay
Important note : A manual reset circuit must be provided at the field supplied external starter board for all protective devices.
Note : For export spec.
41
Model : MDB 075B – MMC 075C
Important note : A manual reset circuit must be provided at the field supplied external starter board for all protective devices.
Note : 1) For export spec. 2) With SLM C3.0B CCT
42
Model : MDB 075B – MMC 075B MDB 100B – MMC 100B / 100C
Important note : A manual reset circuit must be provided at the field supplied external starter board for all protective devices.
Note : 1) For export spec. 2) With SLM C3.0B CCT
43
Model : MDB 150 / 200 / 250 / 300 B2
Important note :
1) For export spec 2) With sequential controller
Model : MDB 300 / 350 / 450 B3
Important note :
1) For export spec 2) With sequential controller
44
Model : MDB 400 / 500 / 600 B4
Important note :
1) For export spec 2) With sequential controller
45
Model : MDB 075B – MMC 075B MDB 100B – MMC 100B MDB 100B – MMC 100C
Symbol DOL BM 51 BM FM 51 FM A/ T COMP. 51 COMP. SW AUX. TH TDR
Important note :
Description Direct on line Blower motor Blower motor overload relay Fan motor Fan motor overload relay Auto transformer Compressor Compressor auto trans. starter Switch Auxiliary control Thermostat control Time delay relay
A manual reset circuit must be provided at the field supplied external starter board for all protective devices.
Note : For local spec.
46
Model : MDB 125B – MMC 125B MDB 150B2 – MMC 075 X 2
Symbol DOL BM 51 BM FM 51 FM A/ T COMP. 51 COMP. SW AUX. TH TDR
Description Direct on line Blower motor Blower motor overload relay Fan motor Fan motor overload relay Auto transformer Compressor Compressor auto trans. starter Switch Auxiliary control Thermostat control Time delay relay
Important note : A manual reset circuit must be provided at the field supplied external starter board for all protective devices.
Note : For local spec.
47
Model : MDB 200B2 – MMC 100B X 2 MDB 250B2 – MMC 125B X 2 MDB 300B3 – MMC 100B X 3 MDB 350B3 – MMC 125B X 2, MMC 100B X 1 MDB 400B4 – MMC 100B X 4 MDB 500B4 – MMC 125B X 4
Symbol
Description
DOL
Direct on line
BM
Blower motor
51 BM FM 51 FM A/ T COMP. 51 COMP. SW AUX. TH TDR
Blower motor overload relay Fan motor
Important note :
Fan motor overload relay Auto transformer
A manual reset circuit must be provided at the field supplied external starter board for all protective devices.
Compressor Compressor auto trans. starter Switch Auxiliary control
Note : For local spec.
Thermostat control Time delay relay
48
Model : MDB 075B – MMC 075C
Symbol
Description
DOL
Direct on line
BM
Blower motor
51 BM FM 51 FM A/ T COMP. 51 COMP. SW AUX. TH TDR
Blower motor overload relay Fan motor
Important note :
Fan motor overload relay Auto transformer
A manual reset circuit must be provided at the field supplied external starter board for all protective devices.
Compressor Compressor auto trans. starter Switch Auxiliary control
Note : For local spec.
Thermostat control Time delay relay
49
Model : MDB 150B1 – MMC 150C
Symbol
Description
DOL
Direct on line
BM
Blower motor
51 BM FM 51 FM A/ T COMP. 51 COMP. SW AUX. TH TDR
Blower motor overload relay Fan motor
Important note :
Fan motor overload relay Auto transformer
A manual reset circuit must be provided at the field supplied external starter board for all protective devices.
Compressor Compressor auto trans. starter Switch Auxiliary control
Note : For local spec.
Thermostat control Time delay relay
50
Model : MDB 300B2 – MMC 150C X 2 MDB 450B3 – MMC 150C X 3 MDB 600B4 – MMC 150C X 4 MDB 750B5 – MMC 150C X 5
Symbol
Description
DOL
Direct on line
BM
Blower motor
51 BM FM 51 FM A/ T COMP. 51 COMP. SW AUX. TH TDR
Blower motor overload relay Fan motor
Important note :
Fan motor overload relay Auto transformer
A manual reset circuit must be provided at the field supplied external starter board for all protective devices.
Compressor Compressor auto trans. starter Switch Auxiliary control
Note : For local spec.
Thermostat control Time delay relay
51
Model : MDB 075B – MMC 075C
Symbol
Description
DOL
Direct on line
BM
Blower motor
51 BM FM 51 FM A/ T COMP. 51 COMP. SW AUX. TH TDR
Blower motor overload relay Fan motor
Important note :
Fan motor overload relay Auto transformer
A manual reset circuit must be provided at the field supplied external starter board for all protective devices.
Compressor Compressor auto trans. starter Switch Auxiliary control
Note :
Thermostat control Time delay relay
52
1) For local spec. 2) With SLM C3.0B CCT
Model : MDB 075B – MMC 075B MDB 100B – MMC 100B MDB 100B – MMC 100C
Symbol
Description
DOL
Direct on line
BM
Blower motor
51 BM FM 51 FM A/ T COMP. 51 COMP. SW AUX. TH TDR
Blower motor overload relay Fan motor
Important note :
Fan motor overload relay Auto transformer
A manual reset circuit must be provided at the field supplied external starter board for all protective devices.
Compressor Compressor auto trans. starter Switch Auxiliary control
Note :
Thermostat control Time delay relay
53
1) For local spec. 2) With SLM C3.0B CCT
Installation (indoor) Preliminary Site Survey a) Electrical supply and installation is to confirm to local authority’s (e.g. National Electricity Board) codes and regulations. b) Voltage supply fluctuation must not exceed +/- 10% of rated voltage. Electricity supply line must be independent of welding transformers which can cause supply fluctuation. c) Ensure that the location is convenient for wiring and piping.
Mounting a) For ceiling mounted models, locate a position where piping and ducting work can be kept to a minimum. Ensure that overhead supports are strong enough to hold the unit’s weight. Position hanger rods and check for alignment with the unit. Check that hangers are secure and that the base of fan-coil unit is level in two horizontal directions.
Pipings Do not use contaminated or damaged copper tubings. If pipings, evaporator or condenser are exposed or had been opened for 15 seconds or more, vacuum and purge with field supplied refrigerant. Generally, do not remove plastic/rubber plugs/caps from fittings, tubings and coils until ready to connect suction or liquid line into fittings.
Operational Check After all electrical wiring is completed and the system is charged with refrigerant, make sure unit is operating properly. Check that: a) b) c) d)
Condenser fans are running, with warm air blowing off the condenser coil. Evaporator blowers are running and discharging cool air. Suction line inside condensing unit feels cool. Liquid line inside condensing unit feels warm.
Electrical Connection As wiring regulations differ from country to country, please refer to your LOCAL ELECTRICAL CODES for field wiring regulations and ensure that these are complied with. Besides, observe the following general precautions: a) Ensure that the rated voltage of the unit corresponds to that of the name plate before commencing wiring work. b) Provide a power outlet to be used exclusively for each unit. A power supply disconnect and a circuit breaker for over-current protection should be provided in the exclusive line. c) The unit must be GROUNDED to prevent possible hazard due to insulation failure. d) All wiring must be firmly connected. e) Electrical wiring must not touch the refrigerant piping, compressor and any moving parts of the fan motors.
54
Installation (outdoor) (outdoor) Location For Installation Of The Condensing Units As condensing temperature rises, evaporating temperature rises and cooling capacity drops. In order to achieve maximum cooling capacity, the location selected should fulfill the following requirements:a) Install the condensing (outdoor) unit in a way such that hot air distributed by the outdoor condensing unit cannot be drawn in again (as in the case of short circuit of hot discharge air). Allow sufficient space for maintenance around the unit.
55
b) Ensure that there is no obstruction of air flow into or out of the unit. Remove obstacle which block air intake or discharge.
c) The location must be well ventilated, so that the unit can draw and distribute plenty of air thus lowering the condensing temperature. d) A place capable of bearing the weight of the outdoor unit and isolating noise and vibration. e) A place protected from direct sunlight. Otherwise use an awning for protection, if necessary. f)
A place where the hot air discharge and operating sound level will not annoy the neighbors.
g) The location must not be susceptible to dust or oil mist. CAUTION: If the condensing unit is operated in an atmosphere containing oils (including machine oils), salt (coastal area), sulphide gas (near hot spring, oil refinery plant), such substances may lead to failure of the unit.
56
Field Piping To ensure satisfactory operation and performance, the following points should be noted for the field piping arrangements of the complete refrigerant cycle. a) Liquid loops or oil traps must be provided according to the position of the outdoor and the indoor units (depending on whether the indoor unit is above or below the outdoor unit). b) Field supplied filter dryer should be provided as close to the expansion valve(s) of the indoor unit (evaporator) as possible. c) Field supplied sight glass must be assembled and mounted as shown in the figure.
Maximum Pipe Length And Maximum Number Of Bends When the pipe is too long, the required refrigerant quantity increases. Both the capacity and reliability drops as a result. As the number of bends increases, system piping resistance to the refrigerant flow increases, thus lowering the cooling capacity and the compressor may become defective. If the height difference between the evaporator and the condenser is excessive, the cooling capacity drops, the lubricating oil return is retarded, affecting the compressor efficiency adversely. Always choose the shortest piping path and follow the recommendations as shown below : Model MMC 075B MMC 100B/BR MMC 125B/BR MMC 075C/CR MMC 100C MMC 150C
Max. Elevation, m (ft.) 20(65.6) 20(65.6) 20(65.6) 20(65.6) 20(65.6) 20(65.6)
Max. Total Length, m (ft.) 35(115) 35(115) 35(115) 35(115) 35(115) 35(115)
Max. of Bends 8 8 8 8 8 8
CAUTION: 1) Our guarantee on the performance of our air-conditioners is strictly revoked if the height, length and/or the number of bends of the refrigerant piping system installed is beyond the limit above. 2) Bendings must be carefully made so as not to crush the pipe. Use a pipe bender to bend a pipe as far as possible.
Maximum Allowable Piping Length & Elevation Difference
57
Installation Clearance A) For MMC – B/BR series (Single/Multiple Condensing Unit) When two or more outdoor units are installed in a location, they must be positioned such that one unit will not be taking the hot discharge air from another. This also applies when two or more units are installed one above the other. The units must all face the same direction or opposite direction (back to back), such that hot air short circuit does not occur.
Model
MMC 075B
MMC 100B/BR
MMC 125B/BR
2X MMC 075B
2X MMC 100B/BR
A (mm)
500
500
500
700
700
B (mm)
300
300
300
300
300
C (mm)
1,200
1,200
1,200
1,500
1,500
Model
2X MMC 125B/BR
3X MMC 100B/BR
MMC 100B/BR + 2 X MMC 125B/BR
4X MMC 100B/BR
4X MMC 125B/BR
A (mm)
700
1,000
1,000
1,000
1,000
B (mm)
300
300
300
300
300
C (mm)
1,500
2,000
2,000
2,000
2,000
58
B) For MMC – C/CR series Model MMC 075C/CR A (mm) 1,200 B (mm) 500 C (mm) 300
MMC 100C 1,200 500 300
MMC 075C/CR / 100C
MMC 150C 1,200 500 300
MMC 150C
Vacuuming And Charging Vacuuming is necessary to eliminate all moisture and air from the system. The Series II Condensing Unit is provided with Quik Lok fittings and charging nipples.
Vacuuming After the system pipings are properly connected, connect the flexible hoses to the correct charging nipples as shown in the diagrams. Ensure that flexible hose from charging nipples are connected to vacuum pump via standard servicing valves and pressure gauges (gauge manifold). Vacuum the air conditioner system to at least 500 microns Hg.
Charging Before charging, the vacuum must be held at 500 microns Hg for at least 15 minutes, then break vacuum by charging R-22 refrigerant. Operate the unit for 15 minutes and ensure that refrigerant charges is of correct quantity by monitoring running current and suction and liquid line pressures. Suction and discharge pipe pressures should be in the region of 75 psig and 275 psig generally. After ensuring the system is correctly charged, remove flexible hose from charging nipples and replace caps.
59
Servicing and maintenance The design concept of the Condensing Unit is such that all servicing can be done from the front and side of the unit. Upon removal of front and side panel, all the electrical "terminal box", fan and motor assembly and compressor are easily accessible. Under normal circumstances, these outdoor units only require a check and cleaning of air intake coil surfaces once quarterly. However, if a unit is installed in area subjected to much oil, mist and dust, the coil must be regularly cleaned by qualified Air Conditioner Service Technicians to ensure sufficient heat exchange and proper operation. Otherwise, the systems life span might be shortened. CAUTION When the compressor is to be stopped for a long time, the crankcase heater should be energized for at least 6 hours before start of operation. Do not charge OXYGEN, ACETYLENE or other flammable and poisonous gases into the refrigeration cycle when performing a leakage test or an airtight-test. These types of gases are extremely dangerous, because explosion can occur. It is recommended that nitrogen or refrigerant be charged for these types of tests.
Caution For Use Bear the following points in mind to safeguard against malfunction and breakdown. Do not stick rods or other objects through the air outlet during operation since this may result to damage or injury
The air conditioner must not re-start within 3 minutes after shutdown. (These models are equipped with a crankcase heater with the compressor).
Make sure the air conditioner is properly grounded by checking the ground terminal.
Maintenance For superb performance and lasting durability, please do not forget to conduct proper and regular maintenance. Cleaning The Outdoor Unit Heat Exchanger If you use your air conditioner for prolonged period of time, the outdoor unit heat exchanger will become dirty impairing its function and reducing the performance of the air conditioned. Consult your local dealer about the cleaning of the heat exchanger.
60
Operation Electrical Connection Wiring regulations about wire diameter differs from country to country. Please refer to your LOCAL ELECTRICAL CODES for field wiring rules. Be sure that installation comply with such rules and regulations.
General Precaution Ensure that the rated voltage of the unit correspond to the name plate before carrying out proper wiring according to the wiring diagram. Provide a power outlet to be used exclusively for each unit. A power supply disconnect and a circuit breaker for over-current protection should be provided in the exclusive line. The unit must be GROUNDED to prevent possible hazard due to insulation failures Every wiring must be firmly connected. Every wiring should not touch the refrigerant piping, compressor and any moving parts of fan motor.
Operational Check After all wiring is completed and the system is charged with refrigerant, make sure the unit is operating properly. Check that :Condenser fans are running with warm air blowing off the condensing unit. Evaporator blowers are running and discharging cool air from ducts. Suction line and liquid line pressures are in the region of 75 psig and 275 psig respectively.
Sequential Controller It is allowed to configure the controller to suit individual’s need with details below : Model Selection 1. Number of Compressor The control can be configured into 6 main types base on number of compressors by changing “R42” values :
a. b. c. d. e. f.
Number of Compressor Cooling / heater* 2 Compressor Cooling / heater* 3 Compressor Cooling / heater* 4 Compressor Heat pump 2 compressors Heat pump 3 compressors Heat pump 4 compressors
R42 value 20k 47k Open 1k 3.3k 9.1k
Note : * Cooling or heater model depending on SW1 and SW2 setting. Factory setting for number of compressor is based on air conditioner models. 2. Number of Heater Number of Heater
SW1(dip1)
SW2(dip2)
a. No heater (0 heater)
off
off
b. 1 heater
on
off
on / off
on
c.
2 heaters
Note : Factory preset : SW1 = off; SW2 = off ~ no heater
61
3. Auto Mode Selection SW5(dip 5) off on
a. Auto mode off b. Auto mode on Note : Factory preset : SW5 = off ~ auto mode off
4. Stage Differential Temperature Differential temperature is the temperature difference between turning on or off 1 compressor to another compressor in thermostat cycle. The stage differential temperature can be selected from the range shown below :
a. Default b. 0.5°C c. 1.0°C d. 1.5°C
Dip switch 3 off on off on
Dip switch 4 off off on on
note that 1.5°C only valid for 2 and 3 compressors model. For 4 compressors model, maximum allowed is 1.0°C. The default differential temperature is base on number of compressor model, the setting is as below : Model Diff. Temperature 1 compressor Not applicable 2 compressor 1.5°C 3 compressor 1.0°C 4 compressors 0.5°C 5. Hot Keep Option Dip switch 6 off on
a. Fan off b. Fan on
6. Operating Modes The system has 4 operating modes to select with respect to each model selection: Model SQCn SQHnh SQHnh Where
Auto X
Cool X X X
Heat X X
Fan X X X
(Dip switch 5 = off) (Dip switch 5 = on)
x denotes modes available n = number of compressor(s) h = number of heater(s)
7. Last Memory Functions The power up settings for either with or without the last memory backup is based on the JH1 setting. a. Last memory backup b. Without last memory backup
JH1 Setting JH1 Plugged JH1 Removed
62
8. Sequential Control For Cool Mode The starting sequence for indoor fan, outdoor fan and compressors is shown as below: 2 seconds Start
Indoor fan 15 seconds
2 seconds outdoor fan 1
15 seconds
compressor 1* 2 seconds
outdoor fan 2 15 seconds
compressor 2* 2 seconds
outdoor fan 3 15 seconds
compressor 3* 2 seconds
outdoor fan 4
compressor 4*
* if available and applicable The compressors will be turned on one by one depending on the on/off conditions shown in the above 9. Sequential control for heat mode The starting sequence for indoor fan, outdoor fan and compressors is as shown below : 2 seconds Start
2 seconds Indoor fan
15 seconds
all 4 way valves 2 seconds
outdoor fan 1 15 seconds
compressor 1* 2 seconds
outdoor fan 2 15 seconds
compressor 2* 2 seconds
outdoor fan 3 15 seconds
compressor 3* 2 seconds
outdoor fan 4
15 seconds
15 seconds
compressor 4*
Heater 1*
Heater 2*
* if available and applicable The compressors will be turned on one by one depending on the on/off conditions shown in the above.
Troubleshooting When any air conditioner malfunction is noted, immediately switch off the power supply to the unit and contact the local dealer, if necessary. Some simple trouble shooting tips are given below : Trouble 1. Fan does not work
1. 2. 3. 4.
Probable Cause No power supply Fan capacitor faulty Fan motor faulty Switch faulty
1. 2. 3. 4.
Suggested Action Check power supply Contact local dealer Contact local dealer Change switch
2. Fan works, but compressor does not work
1. 2. 3. 4.
Thermostat setting too high Dual pressure control trip Compressor faulty Compressor contactor faulty
1. 2. 3. 4.
Reset thermostat .Reset Pressure Control Contact local dealer Contact local dealer
3. Both fan and compressor does not work
1. Power failure 2. Starter trip 3. Fuse blown in power switch or operating unit
1. Operate when power supply resume 2. Reset starter 3. Check and replace fuse
4. Air-conditioner works but cooling not satisfactory
1. 2. 3. 4.
1. 2. 3. 4.
Thermostat setting too high Doors and/or windows not closed Condenser coil dirty Some objects blocking the inlet and/or outlet of the unit 5. Insufficient refrigerant charge.
63
Reset thermostat Close doors and/or windows Contact local dealer Remove the object
5. Contact local dealer
The following charts are efficient checking procedures for troubleshooting when these fan-coil units are combined with condensing units with the unit standard wiring. For dual circuited models, perform the procedures for each.
No Cooling
: Faulty
: Check
: Cause
Remedy
No Cooling ( Compresor Does Not Start )
Evaporator Fan Motor
Stop
Unit Power Supply
Running
Faulty
Single-Phase
Fuse For Operation Circuit
Blown
Overcurrent Relay For Evaporator Fan
Tripped
Evaporator Fan Contactor
No Voltage or Low Voltage
Components Shorted Connections Loose High Volage or Low Voltage Single-Phase
Faulty
Coil Burnt Contact Faulty Faulty Fan Motor Defective Operation Switch
Condenser Fan Motor
Get the Right Voltage Repair the Power Line Repair or Replace The Components Tighten The Connections Get The Right Voltage Check The Power Supply To The Motor : Repair When Necessary
Change The Contactor Repair The Contacts Repair Or Change The Motor Repair Or Replace The Switch
Stop
Overcurrent Relay For Condenser Fan
Tripped
High Voltage or Low Voltage Single-Phase
Running Condenser Fan Contactor
Faulty
Coil Burnt Contact Faulty Fan Motor Faulty Other Electrical Component Faulty
Compressor Contactor
Faulty
Coil Burnt Contact Faulty Open Compressor Windings Incorrect Wiring
64
Get The Right Voltage Check The Power Supply To The Motor : Repair Connections When Necessary Change The Contactor Change The Contacts Repair or Change The Motor Repair or Change If Necessary Change The Contactor Repair The Contacts Change The Compressor Correct The Wiring
Insufficient Cooling Insufficient Cooling
Compressor Cycling
Cycling On
Dual Pressure Switch
Tripping
High Discharge Pressure or Low Suction Pressure Clogged Capillary or Pressure Switch Switch Faulty
Running
Overcurrent Relay For Compressor
Tripping
High Voltage or Low Voltage Single-Phase High Discharge Pressure And High Suction Pressure Loose Connections
Discharge Gas Thermostat or Internal Thermostat
Tripping
High Discharge Pressure And Low Suction Pressure Refrigerant Short Charge or Refrigerant Leakage High Suction Pressure High Discharge Pressure or Low Suction Pressure
See "High Discharge Pressure" or "Low Suction Pressure" Repair Clogging and Replace The Switch If Required Repair or Change If Necessary
Get The Right Voltage Check The Power Line To The Compressor : Repair When Necessary See "High Discharge Pressure" or "High Suction Pressure" Tighten The Connections See "High Discharge Pressure" or "Low Suction Pressure" Add Refrigerant. Repair Leakage If Detected. See "High Suction Pressure" See "High Discharge Pressure" or "Low Suction Pressure"
High Discharge Pressure High Discharge Pressure Restricted Condenser Air Flow
Clogged Condenser Coil Low Fan Speed
Condenser Air Inlet Temperature
High
Malfunction Of Fan Cycling System Circulating Air Flow Overcharged Refrigerant Non-Condensable Gas Restricted Liquid Line High Suction Pressure
Clean The Condenser Check The Voltage And Get The Right Voltage Check The System And Repair If Required Secure Space For Required Air Flow Purge The Refrigerant Purge The Gas Remove The Restriction See "High Suction Pressure"
Low Discharge Pressure Low Discharge Pressure
Condenser Air Flow
Excessive
Malfunction Of Fan Cycling System Low Refrigerant Charge Low Ambient Temperature
65
Check The System And Repair The Components If Required Add Refrigerant See The Unit Working Range
High Suction Pressure High Suction Pressure
Low
Evaporator Air Inlet Temperature
Excessive Fresh Air Intake
Reduce The Fresh Air Intake
Insufficient Duct Insulation
Reinforce The Duct Insulation
Defective Compressor Valve Overcharged Refrigerant
Change Or Repair The Compressor Purge The Refrigerant
Low Suction Pressure Low Suction Pressure
Evaporator Air Flow
Restricted
Evaporator Air Inlet Temperature
Clogged Air Filter
Low
Clean The Air Filter
Restricted Duct
Remove The Restriction
Low Fan Speed
Adjust The Fan Speed
Short Cycling Faulty Thermostat Restricted Liquid LIne And Suction Line Low Refrigerant Charge Low Discharge Pressure
Remove Obstacles To Air Circulation Repair Or Replace If Necessary Remove The Restriction Add Refrigerant See "Low Discharge Pressure"
Noisy Operation Noisy Operation Compressor
Noisy Shipping Bolt(s)
Noisy
Unremoved Shipping Bolt(s) Overcharged Refrigerant
Liquid Refrigerant Backing Up
Low Suction Pressure Worn Compressor Parts
Evaporator Fan
Liquid Line
Noisy
Knocking Runner
Noisy
Strainer Whistling
Worn Bearing
Remove The Bolt(s) Purge The Refrigerant See "Low Suction Pressure" Replace Or Repair The Compressor Fix The Runner Or Casing Properly Change The Bearing
Partially Clogged
Clean The Dryer
Refrigerant Short Charge
Add Refrigerant
Loose Fixed Screws Inadequate Duct Work
66
Tighten All Fixed Screws Check Flexible Ducts