DUPLEXVENT FLEXI
The ventilation units of the new original patented DUPLEXVENT FLEXI design range are intended for comfort ventilation with the highest heat recovery efficiency and hot-air heating in all kinds of civil and residential buildings. They are made in four sizes: DUPLEXVENT FLEXI DV1100, DV1600, DV2600 and DV3600. The units are available in multi-purpose design, i.e. for installation on the floor or beneath the ceiling. In addition the unit sides may be interchanged, i.e. supply and exhaust air ports can be used conversely, allowing installation flexibility. The units can optionally by fitted with a hot water heating coil or a chiller (water-based or direct) to be installed directly on the unit. The duct downstream the unit may be equipped with an electric re-heater; an electric pre-heater can also be installed upstream the unit. The DUPLEXVENT FLEXI DV1600 also includes alternative ports that can be interchanged and used on site as side ports. From the construction point of view all units are compact sets containing in a single cabinet two independently powered, highly efficient EC fans with flexibly mounted motors a counterflow high-efficiency heat recovery core with large heat-transfer area, a by-pass damper with an actuator, removable supply and extract air cartridge filters F5 or F7 and a condensate drain pan, all in the same housing. The front door enables easy access to all components. Inlet and outlet ports are round or rectangular based on the unit type. The housing is manufactured with white painted sheet metal panels with polyurethane insulation (U = 0,82 Wm-2K-1). As an option the units can be equipped with a complete control system, including a connection to the internet or to a third party management system – for detailed information see the section on controls.
Features of the DUPLEXVENT FLEXI: • low profile significantly simplifies installations such as ceiling-suspended applications • extreme compactness of new unit types ensures up to 60 % space reduction in comparison with modular units • low purchase cost • multipurpose unit design (floorstanding / ceilingsuspended installations) simplifies ordering and on-site installations • low power input – high EC fan efficiency • high heat recovery efficiency thanks to new generation heat recovery exchangers • low noise • light weight • different types of control systems based on application complexity; fully integrated into the unit • the units meet hygienic requirements in accordance with the VDI 6022 • The units meet stringent efficiency and effectiveness criteria and are certified by the renowned Passive House Institute (Germany).
DUPLEXVENT FLEXI
Compact ventilator units with heat recovery
OPERATING MODES
Unit ventilators, heat recovery – chapter 2.1. – issue 03/2013
i2 e2
i2 e2
e1
i1 1. equal-pressure ventilation with heat recovery
e1 ... outdoor air (ODA) e2 ... supply air (SUP)
i2 e2 e2
e1
i1 2. equal-pressure ventilation without heat recovery (through by-pass)
i1 i2
i1 3. equal-pressure ventilation with heating / cooling / or preheating
... extract air (ETA) ... exhaust air (EHA)
SELECTION SOFTWARE
For detailed selection of Duplexvent units, accessories and control system we recommend to use our special selection software. To select a heat recovery exchanger you can use our special selection software. Download it from our webpage www.airflow.com.
Airflow Developments Ltd. Aidelle House, Lancaster Road High Wycombe, Buckinghamshire HP12 3QP, United Kingdom Tel.: (Int +44) (UK 0) 1494 525252, Fax: (Int +44) (UK 0) 1494 461073
[email protected], www.airflow.com
e1
PERFORMANCE CURVES TECHNICAL DATA Unit m3h-1 Pa W
Nominal airflow Nominal external static pressure Power input at nominal operating point Recovery efficiency 1)
% kg
Weight Fan number Power supply Frequency
1)
DUPLEXVENT DV1600 1 500 280 893 see curve
DUPLEXVENT DV2600 2 500 260 1 732 see curve
DUPLEXVENT DV3600 3 500 250 2 535 see curve
147 2 230 50 780 3 400 F7 / F5
186 2 230 50 1 030 2 430 F7 / F5
226 2 230 50 1 760 2 200 F7 / F5
320 2 400 50 2 980 2 100 F7 / F5
– V Hz W
Max. power input Fan speed Filtration class 2)
DUPLEXVENT DV1100 1 000 230 696 see curve
min-1 –
based on air volume flow – see curve based on accessories
Available pressure pst (Pa)
PERFORMANCE CURVES
1 200 supply air section with F7 filter extract air section with F5 filter supply air section with F7 filter and hot-water coil
1 100 1 000 900 800 700 600
D
500
M V 10 36 3; S5 00 .A .H
400
100 0
0
500
1 000
1 M
200
00 .H 16 S4.A DV 01;
0 M1
00 11 B.H DV 7; S3.
300
1 500
D
M1 V2 02 60 ;S 0 4.A .H
2 000
2 500
3 000
Note: the curves apply for clean filters; dirty filter pressure loss is considered at 200 Pa or at an air flow reduction of max. 20 % (in accord. EN 13053)
3 500
4 000
Volume flow rate (m3/h)
Heating capacity QT (kW)
HEATING AND COOLING CAPACITY, RECOVERY EFFICIENCY
30 Max. heating capacity of HW coils applies to water with temperature drop of 70/50 °C, inlet air (downstream of recovery core) +10 °C, rh 10 % Max. cooling capacities of CD chillers are stated for coolant R407C, evaporation temperature of +5 °C and inlet air 32 °C, 40 % rh.
25 20
DV3600
15 DV2600
10 DV1600
5
max. cooling capacity CD max. heating capacity HW
DV1100
Heat recovery efficiency φ (%)
0 100 Lower limit is without condensation and with equal air volume flow rate (Mi = Me). Upper limit in conditions te1 = -15 °C, ti1 = +20 °C, rhi1 = 40 % (Mi = Me).
90
1600 Flexi
80
70
0
500
1 000
1 500
3600 Flexi
2600 Flexi
1100 Flexi
2 000
2 500
3 000
3 500
4 000 3
Volume flow rate (m /h)
DIMENSIONS AND CONNECTION PORTS DUPLEXVENT FLEXI DV1100, DV1600 (CIRCULAR PORTS)
UNIT WITH HEATING COIL AND / OR CHILLER L
BD2
D
G E
C
UT1,2 CH1,2
H
BD1
K
K
K
A
D
150
A
K
D
doors
685 310
CH1,2 UT1,2
K
D
K
FA*
685 EA* 310
GA*
H1 x B1
370 275
F
CA*
140
B
60
UNIT ONLY
K
K
K
K ... Condensate drain Unit
L
H
B
D
BD1
BD2
A
C
G
E
F
H1
B1
CA*
GA*
EA*
DV1100 FLEXI
1 700
1 100
395
250
175
159
220
359
246
402
290
575
350
–
–
–
FA* –
DV1600 FLEXI
2 020
1 270
490
315
210
210
240
418
283
478
343
700
440
227
362
283
418
UT1,2 ... Heating coil connection; CH1,2 ... Chiller connection * ... port / heater position possible only in DUPLEXVENT FLEXI DV1600
ROUND CONNECTION PORTS Basic port (inlet, outlet)
Port with a flexible connection (inlet, outlet; delivered separately)
80
alter.
Port with a damper (inlet only; delivered separately)
max. 215
Port with a damper and flexible connection (inlet only; delivered separately)
265
alter.
400
Note: For detailed design and technical data we recommend using our dedicated selection software.
DUPLEXVENT FLEXI DV2600, DV3600
(RECTANGULAR PORTS)
UNIT WITH HEATING COIL AND / OR CHILLER L
B
LC
C
140
370 275
BY
LC
LH CH1,2 UT1,2
K
UT1,2 CH1,2
H1 x B1
Xx Y
Xx Y
H
doors
Xx Y
D
K
LH 65
UNIT ONLY
K
XxY
Xx Y A
150
K
K
K
K
K
K
K ... Condensate drain
thread M6 for 20 mm flange Unit
L
H
B
X
Y
BY
A
C
D
LH
LC
H1
B1
DV2600 FLEXI
2 150
1 570
570
500
250
90
100
160
228
410
890
825
520
DV3600 FLEXI
2 450
1 660
780
600
300
163
75
145
178
450
970
825
730
LH ... Stand-alone heating coil; LC ... Stand-alone chiller or heating coil with chiller; X x Y ... Connecting port dimensions UT1,2 ... Heating coil connection; CH1,2 ... Chiller connection
RECTANGULAR CONNECTION PORTS Basic port (inlet, outlet)
rectangular duct
alter.
Port with a flexible connection (inlet, outlet; delivered separately)
max. 150
alter.
Port with a damper (inlet only; delivered separately)
Note: For detailed design and technical data we recommend using our dedicated selection software.
110
Port with a damper and flexible connection (inlet only; delivered separately)
max. 260
INSTALLATION CONFIGURATION INSTALLATION POSITIONS AND PORT CONFIGURATIONS
The units are available in multipurpose design, allowing the unit to be installed on the floor or beneath the ceiling. For both the floor and ceiling-suspended installation, the standard support steel legs are used. Chillers must always be suspended separately. Each unit is fitted with several condensate drain pipes as standard. During installation the respective drain should be selected. Chillers have their own condensate drains. The condensate drains used must be connected into a sewer system. During installation the respective drain should be selected. In addition, unit sides can be interchanged, i.e. supply and exhaust air ports can be used conversely. This ensures high installation flexibility on site.
Hot water heating coil HW.2 and /or a water-based or direct chiller (to be fitted directly on to the unit) or an EPO-V electric heating coil (to be installed in to the duct) may be optionally connected to the unit. Note: The chiller may not be fitted to units with spigots in upward position e2. In addition the DUPLEXVENT FLEXI DV1600 unit includes alternative ports (e2 and i2) that can be interchanged on site and used as side ports. For a detailed unit design we recommend a special DUPLEXVENT selection software be used; available at www.airflow.com.
FLOOR-STANDING POSITION – the unit is installed using the adjustable legs supplied
K ... Condensate drain e1 ... outdoor air (ODA) e2 ... supply air (SUP)
e2 e2
i1
e1
K
i2
i1
e1
K
DV1100, DV1600 DV2600, DV3600
... extract air (ETA) ... exhaust air (EHA)
e2
i2
e2
i1
e1
K
DV1600
i1
e2
i2
i1
K
e1
K
DV1600
DV1600
-
-
e2
e1
i1 i2
i2
i2
... Chiller not to be fitted in this position
-
i2
i2
e2
e2
i2
e1
i1
K
DV1100, DV1600 DV2600, DV3600
e1
i1
K
DV1600
e1
i1
K
DV1600
DV1600
-
-
CEILING-SUSPENDED POSITION – the unit is installed using supplied hangers
i2
K
K
i2
e2
i1
e1
e2
e1 DV1100, DV1600 DV2600, DV3600
i2
e2
e2
i1
e1
DV1600
K
e2
K
i1
e1
i2 i2
i1
e2
K
DV1600
K
e2
i1
e1
DV1100, DV1600 DV2600, DV3600
i2
DV1600
e2
K
i2
K
i2
i1
e1 DV1600
i1
e1 DV1600
i1
e1 DV1600
MANIPULATION SPACE MANIPULATION SPACE
When installing DUPLEXVENT units it is necessary to allow for the recommended free space around the unit for manipulation. A minimum space of 150 mm is needed under the unit to install a DN 32 condensate drain pipe. A trap with a minimum height of 150 mm must be installed before connecting the pipe to a building sewer. The recommended space is easily ensured when the standard support steel legs are used. Space in front of the unit is required for opening the door, filter changing and access to all components that require service.
Minimum manipulation space required for the hinged door is marked on respective drawings. For all units 600 mm free manipulation space from an electric control panel, is required in accordance with respective standards.
Manipulation space, unit configuration
L / 2 + 100
140
FORNT VIEW
min. 600
min. B + 30
CEILING-SUSPENDED POSITION
FLOOR-STANDING POSITION
K
K
min. 600 view with installation opening
K
23
23 L/2
L/2 floor 35
Z2 11 L/2 - 225 L + 50
L/2 - 225
door
25
min. L / 2 + 100 73
TOP VIEW
Z3
23
25
Z1
50
Unit
H - 50
50
Support legs
Suspension point - Chiller
Suspension point - Unit
Suspension point - Chiller
DV1100
4 pcs
1 pc
4 pcs (in corners)
2 pcs
DV1600
5 pcs
1 pc
4 pcs (in corners)
2 pcs
DV2600
6 pcs
1 pc
4 pcs (in corners)
2 pcs
DV3600
6 pcs
1 pc
6 pcs (in corners and in the middle)
2 pcs
L
Z1
Z2
Z3
B
H
DV1100
Unit
1 700
418
625
392
395
1 100
DV1600
2 020
418
750
392
490
1 270
DV2600
2 150
566
875
540
570
1 570
DV3600
2 450
625
875
600
780
1 660
ACOUSTICS, BASIC UNIT S O U N D P O W E R L E V E L L W( A ) ( d B )
1 000
DUPLEXVENT FLEXI DV1600
1
External pressure pst (Pa)
External pressure pst (Pa)
DUPLEXVENT FLEXI DV1100
4
800 600
7 2
400
5
200
8 3
0
6
9
1 000 800
1
600 4
400
2
3
0 300
0
600
1 200
900
7
5
200 8 6
9
500
0
1 000
3
Volume flow rate (m /h)
DUPLEXVENT FLEXI DV3600
1 000
External pressure pst (Pa)
External pressure pst (Pa)
DUPLEXVENT FLEXI DV2600
800
1
600
4
400
7 2
200
5 8 3 6
0 0
9
500
1 000 1
800
4
600 7
400
2 5
200
8 3
0 1 000
2 000
1 500 3
Volume flow rate (m /h)
1 500 2 000 2 500 3 000 Volume flow rate (m3/h)
DUPLEXVENT FLEXI DV1100 point
outlet (dB(A))
inlet (dB(A))
surround (dB(A))
6
9
DUPLEXVENT FLEXI DV1600
4 000 2 000 3 000 Volume flow rate (m3/h)
1000
0
DUPLEXVENT FLEXI DV2600
outlet (dB(A))
inlet (dB(A))
surround (dB(A))
outlet (dB(A))
DUPLEXVENT FLEXI DV3600
inlet (dB(A))
surround (dB(A))
outlet (dB(A))
inlet (dB(A))
surround (dB(A))
1
83,7
58,8
60,4
84,1
60,7
66,5
78,7
56,9
72,3
87,6
67,7
71,6
2
76,7
47,6
51,3
75,0
50,5
57,9
64,0
45,0
58,9
71,9
56,1
57,3
3
63,3
34,1
36,1
56,5
34,9
42,8
45,9
30,2
43,4
52,8
37,4
42,3
4
84,8
60,2
61,9
82,0
59,8
66,8
79,6
55,2
72,7
85,9
66,6
69,3
5
79,1
49,0
51,9
73,9
51,0
57,7
63,7
43,6
58,0
70,2
54,7
56,1
6
65,8
35,3
35,6
54,8
36,1
42,8
44,9
29,9
43,7
53,0
36,5
42,4
7
88,6
62,4
65,4
82,5
60,6
68,5
80,5
55,7
74,7
87,5
64,2
68,7
8
82,4
52,0
54,1
73,7
50,6
58,3
65,1
43,0
59,0
70,8
52,8
56,0
9
68,5
36,1
36,1
55,3
35,6
44,6
45,6
30,1
43,7
53,1
35,5
42,1
Note: for detailed calculation we recommend a special selection software be used.
DUPLEXVENT – BASIC UNIT
DUPLEXVENT xxxx Housing The housing unit is manufactured with panels of painted sheet metal and a polyurethane insulation of 30 mm thickness (U = 0,82 Wm-2K-1), T3 class, TB3. Front door enables easy access to all built-in components.
Me.xxx; Mi.xxx Fans For both the supply and exhaust air, high-performance EC fans are used (direct drive wheel in semispiral housing with fitted spring-mounted electric motor). Due to the fans; the units are highly efficient with very low specific power input. S3.B.H / S4.A.H / S5.A.H Heat recovery core The units are equipped with a newly designed high-performance heat recovery core. This is made of thin plastic plates with high recovery efficiency up to 93 %. B.x By-pass damper („B“) The heat recovery core bypass, includes an actuator. When opening the by-pass damper, airflow through the recovery core closes automatically to avoid heat transfer.
OPTIONAL ACCESSORIES OPTIONAL ACCESSORIES (BASIC OVERVIEW)
Ke.xxx; Ki.xxx S h u t o f f d a m p e r e 1; i 1 Shutoff dampers are fitted on inlet ports. The dampers are available in different sizes based on unit ports and actuator types – the standard type is LM 24A and the type with spring return is LF 24 (to be shut off in case of power cuts). An option delivered separately.
Fe.xxx; Fi.xxx Air filtration The DUPLEXVENT series are equipped with filter cartridges as standard (F7 / F5 class filters – supply / exhaust). Other available filter combinations are F5 / F5 and F7 / F7
H.P Flexible connection Flexible connection for round or rectangular ports in the unit port sizes. An option delivered separately.
HW.xxx HW hot-water Heating coils Separately, optionally delivered hot-water heating coils to be mounted on the housing unit. For systems up to 110 °C and 1,0 Mpa. An option delivered separately.
RE-HW.4; RE-HW.3 Heating coil hydraulic kit Its function is to control heating capacity of a heating coil. It consists of a three-speed pump, two globe shutoff valves and connection pipes. Further equipment depends on the type: –RE-HW.4 – three-way mixing valve with an actuator for digital control system –RE-HW.3 – three-way diverting valve with a thermostatic valve for electric control system
E l e c t r i c p r e h e a t e r s EPO-V EPO-V EPO-V electric heating coils to provide the antifreeze protection of the heat recovery exchanger when equal-pressure ventilation is continuously required. It is installed inside a duct on the outdoor supply air side of the unit (e1). Control is provided through the DUPLEXVENT (RD or DC) unit control system. When installing the heating coil requirements specified in a separate technical sheet must be adhered to. An option delivered separately.
A.MFF Tube manometers Accessory for filters for simple view of current pressure drop. The tube manometers are obligatory for hygienic unit design in accordance with the VDI 6022. An option delivered separately.
EPO-V Electric heating coils EPO-V Heating coils for round or rectangular ducts to be connected to DUPLEXVENT units. All switching elements are included as standard. Control is provided through the DUPLEX (RD or DC) unit control system. For capacities, dimensions and installation requirements see separate technical sheets. An option delivered separately.
NFK.x Spare cartridge filters Replacement filter cartridges in different sizes based on the unit type. Available in F5 and F7 filtration class.
A.CF.XXX Constant air flow and pressure Manometers reading fan pressure together with controls, enables intelligent fan control of preselected airflow. This accessory assumes the unit is equipped with digital controls of DC or RD type. Using a second manometer (optional accessory) in the supply air duct enables the user to control constant pressure in the supply duct. An option delivered separately.
CW.xxx Water chiller CW Water chillers can be installed externally on to the unit´s casing, to either a chamber with a hot water heating coil or a free chamber. For systems up to 1.0 MPa. An option delivered separately.
CD.xxx Direct chillers CD Direct chillers can be installed externally on to the unit´s casing, to either a chamber with a hot water heating coil or a free chamber. An option delivered separately.
R-CW.3 Control modes for water chillers Designed to control the cooling capacity of water chillers. The R-CW.3 with a 3-way fitting has a 3-way Belimo ball valve with a Belimo TR24-SR servo drive and two ball stop valves. An option delivered separately.
VK.xxx Free chamber VK A chamber to be installed on to the unit´s casing on the supply air outlet e2. It is intended for homogenizing air flow upstream the chiller, and it is used only when no HW hot water heating coil is installed. An option delivered separately.
CONTROLS The DUPLEXVENT FLEXI ventilator units can be equipped with built-in controls providing complete functionality of the unit with its accessories. Thanks to integration of the controls into the unit simple commisioning of the unit and full functionality is guaranteed. There is no risk with compatability of components during installation. The controls enable connection to management systems – more information in the description of the respective
controls and the sellection software. Units do not have to be equipped with controls – individual components are only connected to a terminal block. A special DUPLEXVENT selection software may be used to generate all control type selection including drawings printouts.
SUMMARY OF DUPLEXVENT FLEXI CONTROL SYSTEMS
Type
Use
Controller
„Without controls“
– all components with power supply are connected to a terminal block outside the unit – more components are included upon customer's request (exact actuator type, sensors, thermostats, pressure switches etc.) – good for applications where third party control is supplied separately – e.g. large buildings with building management systems
– not applicable
„RD4“ controls
Standard functions of the „RD4“ controls – EC fan speed control (based on selected mode) – automatic by-pass damper position (heat and cool recovery) – evaluates and prevents emergency limits based on measured temperature – ventilation and temperature weekly program setting – A web server and an Ethernet interface built in as standard connection for remote internet communication – inputs for switching using 230 V (4 inputs – 3 delayed, 1 instantenious) – switch e.g. from bathrooms etc. – optional connection of CO2 or RH sensor – max. 2 sensors with a switch or 0 – 10 V output – outputs for electric preheater and heater control (pulse 10 V) or hot-water control (0 – 10 V)
CP 18 RD installation in the standard recessed dual box on the wall
Additional RD-IO modules – optional manometer connection to ensure constant airflow control (see Constant airflow and pressure control on previous page) – constant pressure control – cooling control outputs (DX- or chilled-water cooling)
„DC“ controls
Standard functions of the „DC“ controls – EC fan speed control (based on selected mode) – automatic by-pass damper position (heat and cool recovery) – evaluates and prevents emergency limits based on measured temperature – ventilation weekly program setting – connection of CO2 or RH sensors – max. 1 sensor with 0 – 10 V output – outputs for electric preheater and heater control (pulse 10 V) or hot-water control (0 – 10 V) – based on CAREL control modules – cooling control outputs (direct or chilled water cooling) – inputs for constant airflow control (see Constant airflow and pressure control on previous page) Additional communication modules – DC-WEB – Ethernet for remote communication via Internet or connection to a BMS via the BACnet protocol – DC-KNX – connection to a BMS via the KNX / EIB protocol – DC-RS – connection to a BMS via the Modbus protocol – serial interface
CP 19 RD installation on wall
Web server (Standard)
DC-p1
DC-p2 (DC-p2h)
Application for Smartphones