Transcript
Data 110-2 12/17/2009
Eclipse RatioMatic Burners Model RM100 Version 3 Specification Parameter
Maximum Input, BTU/hr (kW)
Frequency
60 Hz Packaged Burner
Note: Contact factory for varying chamber pressures or pressures outside the range -2.0 to 2.0" w.c. (-5,0 to 5,0 mbar) 50 Hz Packaged Blower
Minimum Input On-Ratio, BTU/hr (kW)
Maximum Chamber Temperature, °F (°C) Flame Detection Fuel
"w.c. (mbar)
1,295,00 (379)
-2.0 (-5,0)
1,210,000 (354)
-1.0 (-2,5)
1,120,000 (328)
0.0 (0,0)
1,020,000 (298)
1.0 (2,5)
915,000 (268)
2.0 (5,0)
1,375,000 (403)
-2.0 (-5,0)
1,295,000 (379)
-1.0 (-2,5)
1,210,000 (354)
0.0 (0,0)
1,120,000 (328)
1.0 (2,5)
1,020,000 (298)
2.0 (5,0)
with high turndown ratio regulator
30,000 (9)
with standard ratio regulator
40,000 (12)
Main Gas Inlet Pressure, "w.c. (mbar) • Fuel pressure at ratio regulator inlet High Fire Flame Length, inches (mm) • Measured from the outlet end of the combustor
BTU/hr (kW)
10 to 20 (25 to 50) Natural Gas
32 (813)
Propane / Butane
38 (965)
Alloy Tube
1500 (820)
SiC Tube
1900 (1040) Flame rod or UV scanner
Natural Gas, Propane, Butane (For any other mixed gas, contact Eclipse Inc.)
• All information is based on laboratory testing. Different chamber size and conditions will affect the data. • Maximum inputs are given for the standard combustion air blower without an air filter. • All inputs based upon gross calorific values and standard conditions; 1 atmosphere, 70°F (21°C). • Eclipse reserves the right to change the construction and/or configuration of our products at any time without being obliged to adjust earlier supplies accordingly.
Performance Graphs Control & Operation Zone
NOX Emission Data
100
1000
100
Propane/Butane
NOX ppm
% Excess Air
90 Typical Control Ratio
70 60
10
Natural Gas
Input and excess air at low fire changes with ratio regulator adjustment. 1
80
0
200
400
600
50
800
1000
40
1200
0
200
Input (x 1000 BTU/hr) 0
50
100
150
200
250
400
600
800
1000
1200
Input (x 1000 BTU/hr) 300
350
0
50
100
150
200
250
300
350
Input (kW)
Input (kW)
NOX emission data is given for: • Ambient combustion air ~70°F (20°C) • Less than 700°F (370°C) firing chamber • Minimal process air velocity • Low fire input adjusted to 40,000 BTU/hr (12 kW) • ppm volume, dry @ 3% O2 • Neutral chamber pressure Emissions are influenced by: • Chamber conditions • Fuel type • Firing rate • Ratio regulator adjustment • Combustion air temperature CO emission is largely influenced by chamber conditions. Contact your local Eclipse Combustion representative for an estimate of CO emission on your application
Fuel Orifice ∆p vs. Input ∆p Measured Between Taps B & D
5.0 3.7 2.5
5.0
12
3.0 2.5 2.0 1.5
10 8 6
Air ∆p ("w.c.)
6.2
3.5
Air ∆p (mbar)
7.5
14
Butane (13.5 mm Orifice) Propane (15.0 mm Orifice) Natural Gas (19.0 mm Orifice)
4.0
Fuel Orifice ∆p (" w.c.)
Fuel Orifice ∆p (mbar)
10.0 8.7
6.0
4.5
11.2
Air ∆p vs. Air Flow High Fire Air ∆p 5.9" w.c. (14.7 mbar) (Neutral Chamber)
4.0 3.0 2.0
4 1.0
1.2
0.5
0.0
0.0
2 0
200
400
600
800
1000
1200
0
1.0 0.0 0
2000
0
50
100
150
200
Input (kW)
2
250
4000
6000
8000
10000 12000
Air Flow X 1000 scfh
Input (x 1000 BTU/hr) 300
350
0
50
100
150
200
250
300
350
Air Flow Nm ³/hr
Eclipse RatioAir RM100, V3, Data 110-2, 12/17/2009
Dimensions & Specifications Dimensions in Inches (mm) 771 (30.4)
341 (13.4) 236 (9.3)
Filter housing
290 (11.4)
C
Blower housing
Filter/silencer option shown in gray.
B
Low Fire Premix Line Propane/Butane
35 (1.4)
Tap C
1" NPT or BSP gas inlet
Gas inlet centerline
1/2" NPT Pilot Option 428 (16.8)
D
Tap B Tap D
300 (11.8)
87 (3.4)
185 (7.3)
A
Flame rod or UV scanner 1/2" NPT 2.5" NPT or Rc
Weights
lbs
kg
Packaged Burner
75
35
Filter Silencer
41
125.5 (4.94)
19
A
B
C
D
50 Hz
485 (19.1) 530 (20.9)
N/A
N/A
60 Hz
425 (16.7) 475 (18.7)
10 (0.4)
23 (0.9)
Less Blower Option
Combustor Types SiC Tube
Alloy Tube
4 x Ø 12 (0.47)
4 x Ø 12 (0.47) nozzle
F
9 (0.4)
Ø 114 (4.5) OD
190 (7.5)
Ø 165 (6.49) bolt circle
Ø 120 (4.7) OD
Ø 165 (6.49) bolt circle
320 (12.6)
E 20 (0.8)
E
F
255 (10.0)
84 (3.3)
330 (13.0)
160 (6.3)
406 (16.0)
236 (9.3)
Eclipse RatioAir RM100, V3, Data 110-2, 12/17/2009
3
Burner Configuration
Inverted right hand piping
Inverted left hand piping
Upright left hand piping
Data 110-2, 12/17/2009
Upright right hand piping