Transcript
USER‘s guide EE660 - Transmitter for Very Low Air Velocity GENERAL The EE660 transmitters are designed for the exact measurement of air velocity. The measuring method is based on the hot film anemometer principle. The special construction of the sensor mounting provides a very small directional derivate within a wide range, thus allows easy mounting. Using the mounting device the penetration depth is infinitely adjustable. By changing a jumper on the PCB the measuring range and the response time can be set. The transmitters are designed for applications within the HVAC industry, in clean room applications and laminar flow control. For special applications do not hesitate to contact the manufacturer or the corresponding distributor.
CAUTION • The accurate and reliable determination of the air velocity depends on the correct positioning of the probe. Accurate measurements are only possible if the probe is installed in a location with approximate laminar flow. • For duct mounting the required inlet and outlet paths have to be observed. More information can be found on www.epluse.com. • Extreme mechanical, unspecified strain, corrosive environments and condensation must be avoided.
V
CONNECTING DIAGRAM EE660 - Current output 4-20 mA
EE660 - Voltage output 0-10 V Power supply 24 V AC/DC ±20% 1 ... V+ = supply voltage 2 ... GND = ground 3 ... AV_U = voltage output air velocity t90 HI MED LO
Power supply 24 V AC/DC ±20%
V+ GND AV_U AV_I
V
1 ... V+ = supply voltage 2 ... GND = ground 4 ... AV_I = current output air velocity
V+ GND AV_U AV_I
Selection of the response time t90 mA t90 HI MED LO t90
t90 t90 HI HI MEDMED LO LO
HI
jumper t90MED LO SLOW ca. 4 sec. (factory setting)
t90 t90 HI HI MEDMED LO LO
t90 t90 HI HI MEDMED LO LO
no jumper FAST
ca. 1 sec.
t90 t90 HI HI MEDMED LO LO
t90 t90 t90 HI HI HI MEDMEDMED LO LO LO
t90 t90 t90 HI HI HI MEDMEDMED LO LO LO
t90 t90 t90 HI HI HI MEDMEDMED LO LO LO
t90 HI MED LO
t90 HI MED LO
Selection of the working range t90 t90 HI HI MEDMED LO LO
mA
V+ GND AV_U AV_I
t90 HI MED LO
SETTINGS
t90 HI MED LO
V+ GND AV_U AV_I
t90 t90 HI HI MEDMED LO LO
t90 HI MED LO
t90 HI (factory setting) MED By using the Configuration Software (EE-PCS) to change the output scaling, the jumper has to be on HI. LO jumper HI 0...2 m/s
jumper MED 0...1.5 m/s
no Jumper 0...1 m/s
t90 HI MED LO
t90 HI MED LO
TECHNICAL DATA
(Modification rights reserved)
Measuring values
Working range 1) Output 0...1 m/s / 0...1.5 m/s / 0...2 m/s Accuracy at 20 °C (68 °F), 45 % RH, 1013 hPa Response time τ90 1) 2)
0...1 m/s (0...200ft/min) 0...1.5 m/s (0...300ft/min) 0...2 m/s (0...400ft/min) 0 - 10 V -1 mA < IL < 1 mA 4 - 20 mA RL< 450 Ω (linear, 3-wires) 0.15...1 m/s (30...200 ft/min) ± (0.04 m/s (7.9 ft/min) + 2 % of mv) 0.15...1.5 m/s (30...300 ft/min) ± (0.05 m/s (9.8 ft/min) + 2 % of mv) 0.15...2 m/s (30...400 ft/min) ± (0.06 m/s (11.8 ft/min) + 2 % of mv) typ. 4 sec or typ. 1 sec (at constant temperature)
Power supply Current consumption for AC supply for DC supply Angular dependence Electrical connection Cable gland Electromagnetic compatibility Housing material Protection class Temperature range Working range humidity
24V AC/DC ± 20%
General
max. 180 mA rms (with Display), 74 mA rms (without Display) max. 85 mA (with Display), 41 mA (without Display) < 3% of the measured value at | ∆α | < 10° screw terminals max. 1.5 mm (AWG 16) M16x1.5 EN61326-1 EN61326-2-3 Industrial Environment Polycarbonate, UL94V-0 (with Display UL94HB) approved Enclosure IP65 / NEMA4, remote probe IP20 working temperature probe -25 ... +50 °C (-13...122°F) working temperature electronic -10 ... +50 °C (14...122°F) storage temperature -30 ... +60 °C (-22...140°F) 5...95 % RH (non-condensing) 2
1) Selectable by jumper 2) Response time τ90 is measured from the beginning of a step change of air velocity to the moment of reaching 90% of the step.
DIMENSIONS MM (INCH) 90 (3.54)
90 (3.54) Cable gland M20x1.5 (cabel Ø 5-10 mm / 0.2-0.39")
Type B duct mounting
Ø > 13 (0.51)
~11 (~4 0 or 2 .33 1 or 8 0 .27 )
FOR CONDUIT INSTALLATION
5 (0.2) GASKET
Ø > 16 (0.63)
Cable gland M16x1.5
6 (0.24)
12 (0.47)
46 (1.8 1)
15 (0.5 9)
155
.98)
101 (3
80.6 (3.17)
Type A wall mounting
~110 or 210 (~4.33 or 8.27)
60 (2.36)
(6.1
)
155
Type C remote probe
(6.1
)
19 (0.75)
Cable gland M16x1.5
SETUP AND ADJUSTMENT The EE660 is ready for use immediately and requires no configuration set-up by the customer. If required, the optional E+E Product Configuration Adapter (EE-PCA) and the E+E Product Configuration Software (EE-PCS) can be used for customer adjustment of the air velocity. Various display settings such as backlighting and orientation can also be changed.
HA011062
PC
V03
EE-PCA
For product data sheets EE-PCS and EE-PCA please see www.epluse.com. The E+E Product Configuration Software (EE-PCS) is free and can be downloaded from www.epluse.com/configurator
MOUNTING Bore for mounting flange:
CORRECT
drilling in the wall of the duct:
INCORRECT
>16 (0.63") Air Velocity
60 (2.4")
Immersion depth = 30% - 50% of the pipe diameter pipe diameter
The mounting flange allows for an infinite variation of the depth of the sensor probe. It is important to ensure that the sensor head is completely submerged into the flow.
Air Velocity
If the sensor probe is installed without a mounting flange, make sure the air velocity sensor is aligned parallel with the air stream.
CORRECT
Air Velocity
INCORRECT
Information
+43 7235 605 0 /
[email protected]
E+E Elektronik Ges.m.b.H. Langwiesen 7 • A-4209 Engerwitzdorf Tel: +43 7235 605-0 • Fax: +43 7235 605-8
[email protected] • www.epluse.com
LG Linz Fn 165761 t • UID-Nr. ATU44043101 Place of Jurisdiction: A-4020 Linz • DVR0962759
BA_EE660_e // v1.0 // Modification rights reserved