Transcript
ELECTRICAL NOTES: 1.
ELECTRICAL CONTRACTOR (EC) SHALL FURNISH LABOR, MATERIAL, TOOLS, AND EQUIPMENT TO INSTALL ELECTRICAL SYSTEMS AS INDICATED ON DRAWINGS. ALL ELECTRICAL ITEMS THAT ARE NOT SHOWN OR INCLUDED BUT ARE NECESSARY TO SATISFY THE INTENT AND SCOPE OF THESE DRAWINGS SUCH AS GOOD GENERAL PRACTICE, MANUFACTURER'S RECOMMENDATIONS, CODES, ETC., SHALL BE CONSIDERED A PART OF THESE DRAWINGS IN ORDER TO PROVIDE COMPLETE AND OPERATIONAL SYSTEMS.
2.
ELECTRICAL DRAWINGS ARE GENERALLY DIAGRAMMATIC AND ARE INTENDED TO CONVEY THE SCOPE OF WORK AND INDICATE GENERAL ARRANGEMENT OF EQUIPMENT. INSTALL EQUIPMENT AND MATERIAL FOR MAINTENANCE ACCESSIBILITY PURPOSES AND KEEPING IN STRICT COMPLIANCE WITH NEC "WORKING SPACE" AND "CLEARANCE" REQUIREMENTS.
3.
EC SHALL CAREFULLY EXAMINE ARCHITECTURAL, STRUCTURAL, PLUMBING, AND MECHANICAL DRAWINGS PERTAINING TO THE CONSTRUCTION BEFORE INSTALLING THE ELECTRICAL WORK IN ORDER TO AVOID CONFLICT WITH OTHER TRADES. EC IS OBLIGED TO BE FAMILIAR WITH THE REQUIREMENTS AND DETAILS OF ALL OTHER TRADES INSOFAR AS HIS WORK IS AFFECTED THEREBY. CONSULT OTHER TRADES DRAWINGS AND EQUIPMENT ROUGHING DRAWINGS FOR EXACT LOCATIONS OF CONDUIT TURN-UPS, CONNECTIONS AND SIMILAR TERMINATIONS. SINCE ROUGHING LOCATIONS AND TYPES OF CONNECTIONS VARY WITH DIFFERENT MANUFACTURERS, PROVIDE CONNECTIONS TO SUIT ACTUAL EQUIPMENT TO BE INSTALLED. IF THE ELECTRICAL TRADE INSTALLS HIS WORK BEFORE COORDINATING WITH OTHER TRADES OR SO AS TO CAUSE INTERFERENCE WITH WORK OF OTHER TRADES, HE SHALL MAKE NECESSARY CHANGES IN HIS WORK TO CORRECT THE CONDITION WITHOUT EXTRA CHARGE.
4.
5.
6.
EC SHALL VISIT THE SITE TO BE FAMILIAR WITH THE "SCOPE OF WORK" IN CONNECTION THEREWITH, AND DETAILS OF CONDITIONS UNDER WHICH ELECTRICAL WORK WILL HAVE TO BE EXECUTED. PARTICULAR ATTENTION SHOULD BE MADE CONCERNING CONDITIONS BEARING ON TRANSPORTATION, DISPOSAL, HANDLING AND STORAGE OF MATERIALS, AVAILABILITY OF LABOR, LABOR CONDITIONS, WATER , ELECTRICAL POWER, ROADS OR SIMILAR PHYSICAL CONDITIONS AT THE SITE, THE CHARACTER OF EQUIPMENT AND FACILITIES NEEDED PRELIMINARY TO AND DURING THE EXECUTION OF THE WORK AND ALL OTHER MATTERS UPON WHICH INFORMATION IS REASONABLY OBTAINABLE AND WHICH IN ANY CASE CAN AFFECT THE WORK OR THE COST THEREOF UNDER THESE SPECIFICATIONS. LACK OF SUCH KNOWLEDGE WILL NOT BE ACCEPTED AS VALID EXCUSE FOR GRANTING EXTRA COMPENSATION OR FOR FAILURE TO NEGLECT OR REFUSAL TO PERFORM ANY OR ALL WORK UNDER THESE SPECIFICATIONS. EQUIPMENT, MATERIAL, AND INSTALLATIONS SHALL MEET THE REQUIREMENTS OF THE LATEST EDITION OF THE APPLICABLE CODES AND STANDARDS OF THE FOLLOWING ORGANIZATIONS: A) ANSI: AMERICAN NATIONAL STANDARDS INSTITUTE B) ANSI C2: NATIONAL ELECTRIC SAFETY CODE C) IEEE: INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS D) NEC: NATIONAL ELECTRIC CODE WITH AMENDMENTS BY STATE AND LOCAL AUTHORITIES E) NEMA: NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION F) NETA: NATIONAL ELECTRIC TESTING ASSOCIATION G) NFPA: NATIONAL FIRE PROTECTION ASSOCIATION H) OSHA: OCCUPATIONAL SAFETY AND HEALTH ACT I) UL: UNDERWRITER'S LABORATORY ALL ELECTRICAL EQUIPMENT AND MATERIALS SHALL BE NEW, EXCEPT WHERE EXISTING EQUIPMENT IS DESIGNATED FOR REUSE. ALL EQUIPMENT AND MATERIAL SHALL BE "APPROVED", "LABELED" OR "LISTED" BY AN ORGANIZATION THAT IS ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION.
7.
ALL ELECTRICAL EQUIPMENT SHALL BE UL LISTED AND INSTALLED IN ACCORDANCE WITH ITS LISTING.
8.
EC SHALL BE RESPONSIBLE TO GROUND AND BOND ELECTRICAL SYSTEMS, CIRCUIT CONDUCTORS, AND ELECTRICAL EQUIPMENT IN ACCORDANCE WITH ARTICLE 250 OF THE NEC.
9.
EC SHALL PROVIDE ALL ITEMS SPECIFIED ON ELECTRICAL DRAWINGS UNLESS NOTED OTHERWISE. MANUFACTURERS SPECIFIED ARE TO ESTABLISH STANDARD QUALITY REQUIRED FOR THIS PROJECT. OTHER MANUFACTURERS MAY BE CONSIDERED FOR APPROVAL. SUBMIT SHOP DRAWINGS OF ALL SPECIFIED ITEMS TO THE DESIGN ENGINEER, AS INDICATED IN THE PROJECT SPECIFICATIONS. SUBSTITUTIONS OF EQUIPMENT OTHER THAN THOSE SPECIFIED OR A CHANGE IN THE METHOD OF INSTALLATION OF ANY MATERIAL MAY BE MADE ONLY WITH WRITTEN PERMISSION OF THE DESIGN ENGINEER. SUCH PERMISSION IS GRANTED ONLY UPON CONDITION THAT THE EC WILL ASSUME RESPONSIBILITY FOR THE COST OF ANY CHANGES REQUIRED IN THE WORK OF HIS CONTRACT, OR THAT OF ANY OTHER CONTRACTOR, SUBCONTRACTOR, OR MATERIAL SUPPLIER AS NECESSITATED BY THE USE OF SUCH SUBSTITUTED MATERIAL AND/OR METHOD OF INSTALLATION. THIS ALSO INCLUDES COSTS OF THE ENGINEERS OF RECORD TO MAKE CHANGES TO ALL CONSTRUCTION DOCUMENTS ASSOCIATED WITH THE SUBSTITUTION, INCLUDING, BUT NOT LIMITED TO, ARCHITECTURAL, STRUCTURAL, MECHANICAL, ELECTRICAL, AND FIRE PROTECTION.
10.
11. 12. 13.
ALL SUSPENDED CEILING MOUNTED LIGHT FIXTURES SHALL BE SEISMICALLY SUPPORTED PER CISCA 3-4 GUIDELINES AS REFERENCED IN IBC 1621.2.5. LIGHT FIXTURES SHALL BE POSITIVELY ATTACHED TO THE SUSPENSION SYSTEM AND THE ATTACHMENT DEVICE MUST BE ABLE TO WITHSTAND 100% OF THE WEIGHT OF THE FIXTURE ACTING IN ANY DIRECTION. IN ADDITION, FIXTURES WEIGHING 56 POUNDS OR LESS SHALL HAVE TWO 12 GAUGE WIRES ATTACHED, AT DIAGONAL CORNERS, TO THE STRUCTURE ABOVE. THESE WIRES MAY BE SLACK. FIXTURES WEIGHING IN EXCESS OF 56 POUNDS SHALL BE INDEPENDENTLY SUPPORTED BY ATTACHMENT TO THE BUILDING STRUCTURE. PENDANT MOUNTED LIGHT FIXTURES SHALL BE SUPPORTED DIRECTLY FROM THE STRUCTURE USING 9 GAUGE WIRES. THE CEILING SUSPENSION SYSTEM MAY NOT BE USED FOR SUPPORT. THE INSTALLATION OF ALL ELECTRICAL COMPONENTS SHALL MEET THE SEISMIC PROVISIONS FOR THE AREA WHERE THE INSTALLATION IS LOCATED. EC SHALL PROVIDE POWER AND CONTROL WIRING, INCLUDING, BUT NOT LIMITED TO, BOXES, CONDUIT, WIRE, AND CONNECTIONS TO ALL UNITS OF MECHANICAL, PLUMBING, AND OTHER EQUIPMENT AS INDICATED. PROVIDE ALL DISCONNECTS, EXCEPT WHERE NOTED OTHERWISE. EC SHALL INSTALL CONTROL EQUIPMENT THAT IS FURNISHED BY OTHERS AND FURNISH CONTROL POWER TO CONTROL EQUIPMENT. TRANSFORMERS TO FURNISH CONTROL VOLTAGE SHALL BE FURNISHED AS A PART OF THE CONTROL EQUIPMENT.
14.
ELECTRICAL INTERLOCKING OF MECHANICAL EQUIPMENT SHALL BE AS INDICATED ON THE DRAWINGS.
15.
EC SHALL KEEP ACCURATE RECORDS OF UNDERGROUND AND CONCEALED ELECTRICAL LINES WHICH DEVIATE FROM THE DESIGN DRAWINGS ON A RED-LINE MARKED SET OF "AS-BUILT" DRAWINGS. TURN OVER "AS-BUILT" DRAWINGS TO THE DESIGN ENGINEER AT COMPLETION OF PROJECT.
16.
17.
18.
19.
20.
21.
22.
EC SHALL TAKE MEASUREMENTS AT THE SITE FOR ALL ITEMS REQUIRING FIELD MEASUREMENTS FOR THE NECESSARY FIT AND/OR INSTALLATION OF THE WORK WITH THE RESPONSIBILITY OF ACCURACY OF SUCH MEASUREMENTS RESTING WITH THE CONTRACTOR. EC SHALL GIVE NOTICE TO THE OWNER AND DESIGN ENGINEER IN AMPLE TIME SO THAT THE WORK CAN BE INSPECTED AS IT PROGRESSES, AND NO WORK SHALL BE CONCEALED UNTIL INSPECTED BY THE OWNER OR DESIGN ENGINEER. RACEWAYS PASSING FROM ONE AREA TO ANOTHER OF DIFFERENT TEMPERATURE SHALL BE SEALED. PROVIDE INTERNAL WATERTIGHT FITTING WITH APPROVED COMPOUND, OR IF THIS IS IMPRACTICAL, SUITABLE DRAINAGE FITTINGS SHALL BE INSTALLED. CONDUIT (OR OTHER RACEWAYS) SHALL BE INSTALLED WITH EXPANSION JOINTS TO ALLOW FOR THERMAL EXPANSION AND CONTRACTION OF CONDUIT SYSTEM AND MOVEMENT OF BUILDING (AT EXPANSION JOINTS) TO KEEP STRESSES WITHIN THE ALLOWABLE LIMITS OF THE CONDUIT. EXPANSION JOINTS SHALL BE LOCATED AS PER NEC REQUIREMENTS AND, AT A MINIMUM, AT ALL BUILDING EXPANSION JOINTS. IN ADDITION, FOR THERMAL EXPANSION, USE, AT A MINIMUM, EXPANSION JOINTS WHERE THE DEGREE-FEET OF CONDUIT EXCEEDS 600 DEGREE-FEET FOR RIGID NONMETALLIC CONDUIT AND 10,000 DEGREE-FEET FOR ALUMINUM AND STEEL CONDUIT IN STRAIGHT RUNS BETWEEN SECURELY MOUNTED ITEMS SUCH AS, BOXES, CABINETS, ELBOWS, OR OTHER CONDUIT TERMINATIONS (DEGREE-FEET ARE THE LENGTH OF CONDUIT RUN IN FEET MULTIPLIED BY THE TOTAL CHANGE IN TEMPERATURE THAT THE CONDUIT WILL BE EXPOSED TO IN DEGREES FAHRENHEIT). EXPANSION JOINTS SHALL ALLOW FOR THE REQUIRED AMOUNT OF MOVEMENT IN ORDER TO PREVENT BUCKLING OF CONDUIT OR PULLOUT AT FITTINGS. EXPANSION FITTINGS SHALL BE LISTED FOR GROUNDING AND SHALL BE MADE ELECTRICALLY CONTINUOUS BY HAVING EQUIPMENT BONDING JUMPERS INSTALLED AROUND THEM. INSTALL THE EXPANSION JOINTS PER MANUFACTURER'S SPECIFICATIONS AND LEAVE PIPE STRAPS LOOSE TO ALLOW MOVEMENT OF THE CONDUIT. MINIMUM CONDUIT SIZE SHALL BE 1/2" AND MINIMUM CONDUCTOR SIZE SHALL BE #12 AWG FOR POWER WIRING AND #14 AWG FOR CONTROL WIRING (UNLESS NOTED OTHERWISE). WIRING SHALL BE 600 VOLT STRANDED COPPER, RATED AT 90°C WITH THHN/THWN TYPE INSULATION (UNLESS NOTED OTHERWISE). METAL-CLAD CABLING (TYPE MC) MAY BE USED IN LIEU OF CONDUIT AND WIRE FOR INTERIOR BRANCH CIRCUIT WIRING WHERE CONCEALED ABOVE CEILING OR BEHIND DRYWALL FOR FINAL TERMINATIONS TO OUTLETS. TYPE MC CABLING MUST BE INSTALLED PER NEC CODE REQUIREMENTS AND SHALL NOT BE USED IN BLOCK WALLS OR FOR HOMERUNS TO PANELBOARD. A SEPARATE NEUTRAL CONDUCTOR SHALL BE INSTALLED FOR EACH BRANCH CIRCUIT. AN INSULATED EQUIPMENT GROUNDING CONDUCTOR SHALL BE INSTALLED WITH ALL FEEDERS AND BRANCH CIRCUITS. CONDUIT AND WIREWAY ROUTES ARE SHOWN FOR CLARITY ONLY. EC SHALL FIELD ROUTE AND INSTALL TO SUIT ACTUAL FIELD CONDITIONS. CONDUITS AND WIREWAYS SHALL BE INSTALLED PARALLEL AND PERPENDICULAR TO BUILDING STRUCTURAL MEMBERS OR ALONG CONVEYORS. CONDUITS AND WIREWAYS SHALL BE ROUTED ABOVE ALL PASSAGE AREAS.
23.
PROVIDE PULL WIRE IN ALL EMPTY CONDUITS. USE #10 AWG COPPER CONDUCTOR AND LEAVE AT LEAST 12" OF SLACK AT EACH END OF PULL WIRE.
24.
PROVIDE PROPER SIZED SLEEVES AND EXACT LOCATIONS OF CONDUIT RUNS THROUGH CONCRETE OR MASONRY WALLS (BLOCK AND FOUNDATION), CONCRETE SLABS, UNDER BUILDING FOOTINGS AND FOUNDATIONS, AND FIRE-RATED FLOOR AND WALL ASSEMBLIES TO THE GENERAL CONTRACTOR FOR HIS PLACEMENT. ALL HOLES THRU WALLS AND CEILINGS EXPOSED TO A FINISHED AREA SHALL HAVE ESCUTCHEONS FOR CONDUITS. SEAL ALL SLEEVES WITH ETHAFOAM BACK-UP ROD AND SILICON SEALANT AND USE 3M #CP 25WB+ CAULKING FOR PENETRATIONS THRU FIRE-RATED WALLS AND FLOORS. INSTALL IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS TO MAINTAIN INDICATED FIRE RATING OF WALLS, PARTITIONS, CEILINGS, AND FLOORS AT RACEWAY AND CABLE PENETRATIONS.
25.
EC SHALL REFER TO ARCHITECTURAL PLANS, ELEVATIONS, AND SECTIONS, WHERE APPLICABLE, FOR ACTUAL MOUNTING HEIGHTS AND LOCATION OF ELECTRICAL DEVICES OR EQUIPMENT.
26.
WIRING DEVICES AT DIFFERENT ELEVATIONS SHALL BE ALIGNED VERTICALLY AND WIRING DEVICES AT SAME ELEVATION SHALL BE UNDER ONE WALL PLATE, IF APPLICABLE. PROVIDE BARRIERS BETWEEN SWITCHES THAT ARE GANGED IN SAME BOX AND USED TO CONTROL 277 VOLT LIGHTING WHERE TWO OR MORE CONDUCTORS OF DIFFERENT PHASES ENTER THE BOX.
27.
PANELBOARDS SHALL BE AS DETAILED ON DRAWINGS. CIRCUIT BREAKERS SHALL BE 20 AMP SINGLE POLE, UNLESS NOTED OTHERWISE. PANELS SHALL HAVE AT A MINIMUM 100% SOLID NEUTRAL BUS AND GROUND BAR KIT. EC SHALL PROVIDE COMPLETE TYPE WRITTEN DIRECTORIES FOR LIGHTING AND POWER PANELS WITH ALL ROOM NUMBERS, EQUIPMENT, NAMES, ETC., POSITIVELY IDENTIFIED FOR EACH INDIVIDUAL CIRCUIT.
28.
PROVIDE FIRE ALARM SYSTEM AS INDICATED ON DRAWINGS. FIRE ALARM SYSTEM SHALL BE INSTALLED PER NFPA 72.
30.
PROVIDE ELECTRICAL EQUIPMENT IN ELEVATOR PIT PER CODE AND AS REQUIRED BY ELEVATOR MANUFACTURER. PROVIDE SWITCH AND RECEPTACLE AS INDICATED ON DETAIL. PROVIDE A DEDICATED 120 VOLT, 15 AMP, SINGLE PHASE CIRCUIT WITH GROUND FAULT CIRCUIT INTERRUPTER PROTECTION INCLUDING A NON-FUSED DISCONNECT FOR CAB LIGHTS AND ACCESSORIES. PROVIDE A THREE PHASE POWER CIRCUIT INCLUDING A FUSED DISCONNECT FOR MAIN POWER TO THE CONTROLLER. PROVIDE A DEDICATED TELEPHONE LINE TO THE CONTROLLER.
31.
EC SHALL BE RESPONSIBLE FOR ALL CONCRETE AND MASONRY CUTTING AND PATCHING ASSOCIATED WITH CONTRACTOR'S WORK. EC TO COORDINATE WITH PRECAST MANSUFACTURER FOR ALL ELECTRICAL ITEMS LOCATED IN PRECAST WALLS.
32.
PROVIDE PHENOLIC LABEL FOR ALL ELECTRICAL EQUIPMENT, BLACK 1/4" LETTERS ON WHITE BACKGROUND. FASTEN WITH STAINLESS STEEL FASTENERS. INCLUDE EQUIPMENT NAME, SOURCE OF SUPPLY (PANELBOARD, OR MCC) AND CIRCUIT INFORMATION, AND SUPPLY VOLTAGE LEVEL.
33.
IDENTIFY EACH RECEPTACLE WITH PANELBOARD IDENTIFICATION AND CIRCUIT NUMBER. USE HOT, STAMPED, OR ENGRAVED MACHINE PRINTING WITH BLACK FILLED LETTERING ON FACE OF PLATE, AND DURABLE WIRE MARKERS OR TAGS INSIDE OUTLET BOXES.
34.
AT COMPLETION OF PROJECT, EC SHALL TEST THE ELECTRICAL SYSTEMS IN THEIR ENTIRETY UNDER THE DIRECTION OF THE OWNER TO ENSURE THE CONDITIONS OF THE SPECIFICATIONS HAVE BEEN MET BEFORE THE FINAL ACCEPTANCE OF THE WORK. THE ENTIRE SYSTEM SHALL TEST FREE FROM SHORT CIRCUITS AND UNINTENTIONAL GROUNDS, AND EACH PART SHALL FUNCTION PROPERLY. TESTS SHALL BE MADE IN THE PRESENCE OF THE OWNER'S REPRESENTATIVE.
36.
ONE POLE TWO POLE THREE POLE FOUR POLE ONE POLE, ONE WIRE ONE POLE, TWO WIRE TWO POLE, TWO WIRE TWO POLE, THREE WIRE THREE POLE, TWO WIRE THREE POLE, THREE WIRE THREE POLE, FOUR WIRE FOUR POLE, FOUR WIRE
A AC AF AFF AFG AIC AL AS AT ARCH ATS AUD A/V
AMPERE ALTERNATING CURRENT AMP FRAME ABOVE FINISHED FLOOR ABOVE FINISHED GRADE AMPERE INTERRUPTING CAPACITY ALUMINUM AMP SWITCH AMP TRIP ARCHITECT AUTOMATIC TRANSFER SWITCH AUDIOMETER BOX CONNECTION AUDIO VISUAL
BFG BLDG
BELOW FINISHED GRADE BUILDING
C CAM CAT CATV CB CKT CNTL COL C.T. CU C L
CONDUIT (GENERIC TERM FOR RACEWAY.) CAMERA CATALOG CABLE TELEVISION CIRCUIT BREAKER CIRCUIT CONTROL COLUMN CURRENT TRANSFORMER COPPER CENTER LINE
DC ∆ DISC DWG DT
DIRECT CURRENT DELTA DISCONNECT DRAWING DUSTTIGHT (*)
E EC EF EMT EOL EWC EWH EXIST
WIRED ON EMERGENCY CIRCUIT ELECTRICAL CONTRACTOR EXHAUST FAN ELECTRIC METALLIC TUBING END OF LINE ELECTRIC WATER COOLER ELECTRIC WATER HEATER EXISTING
L LAV LFMC LFNC LP LS LTG LV
LINE LAVATORY LIQUIDTIGHT FLEXIBLE METALLIC CONDUIT LIQUIDTIGHT FLEXIBLE NONMETALLIC CONDUIT LIGHTING PANELBOARD LIMIT SWITCH LIGHTING LOW VOLTAGE
MAU MC MC MCB MCC MDP MISC MLO MOD MTD MTG MTS
MAKE-UP AIR UNIT MECHANICAL CONTRACTOR METAL CLAD CABLE MAIN CIRCUIT BREAKER MOTOR CONTROL CENTER MAIN DISTRIBUTION PANEL MISCELLANEOUS MAIN LUGS ONLY MOTOR OPERATED DISCONNECT SWITCH MOUNTED MOUNTING MANUAL TRANSFER SWITCH
N N/A NC NEC NIC NL NM NO NRTL # NTS
NEUTRAL NOT APPLICABLE NORMALLY CLOSED NATIONAL ELECTRICAL CODE NOT IN CONTRACT NIGHT LIGHT NONMETALLIC SHEATHED CABLE NORMALLY OPEN NATIONALLY RECOGNIZED TESTING LAB NUMBER NOT TO SCALE
P PB PC PH ∅ PNL PIV PP PR PRI PT PVC PWR
POLE PULL BOX PLUMBING SYSTEM CONTRACTOR PHASE PANEL (BOARD) POST INDICATING VALVE POWER PANEL PAIR PRIMARY POTENTIAL TRANSFORMER POLYVINYL CHLORIDE CONDUIT POWER
REC RSC RT RTU S SEC SIG SN SP SPL SS STP STL SUSP SW SWBD
NL
3
a
EXTERIOR WALL MOUNTED LIGHT FIXTURE
CEILING
TC TCC TCI TEL / DATA TEL TERM TYP
TELEPHONE CABINET TEMPERATURE CONTROL CONTRACTOR TELECOMMUNICATIONS CABLING INSTALLER TELEPHONE / DATA TELEPHONE TERMINAL (S) TYPICAL
HH HP HV HVAC
UG UNO UTP
UNDERGROUND UNLESS NOTED OTHERWISE UNSHIELDED TWISTED PAIR
HZ
HAND HOLE HORSEPOWER HIGH VOLTAGE HEATING, VENTILATING, AND AIR CONDITIONING HERTZ (CYCLE) PER SECOND
V VT
VOLT VAPORTIGHT (*)
IAM IG IMC
INDIVIDUAL ADDRESSABLE MODULE ISOLATED GROUND INTERMEDIATE METAL CONDUIT
JB
JUNCTION BOX
W WH WP WT
WATT WATTHOUR WEATHERPROOF WATERTIGHT (*) TRANSFORMER EXPLOSION PROOF (*)
Y
WYE
ZAM
ZONE ADAPTER MODULE
SURFACE OR CHAIN HUNG
WALL MOUNTED LIGHT FIXTURE
PER ARCH. ELEV.
VOICE/DATA COMBINATION OUTLET INCLUDING (1) DATA AND (1) VOICE JACKS
+16" AFF TO BOTTOM
DATA ONLY OUTLET "X" INDICATES QUANTITY OF DATA JACKS, MINIMUM OF 1
+16" AFF TO BOTTOM
FLOOR BOX, SEE PLAN FOR INFORMATION
RECESSED DOWN LIGHT FIXTURE
CEILING
WAP
CEILING
WIRELESS ACCESS POINT
FIRE ALARM SYSTEM FACP
FIRE ALARM CONTROL PANEL
+72" AFF TO TOP
FIRE ALARM NOTIFICATION APPLIANCE CIRCUIT PANEL
+72" AFF TO TOP
FIRE ALARM ANNUNCIATOR PANEL
+72" AFF TO TOP, RECESSED
MANUAL PULL STATION, "WG" INDICATES DEVICE WIRE GUARD
+48" AFF TO TOP
S
SMOKE DETECTOR
CEILING
H
HEAT DETECTOR
CEILING
HORN/STROBE INDICATOR, WITH STROBE, STROBES ARE 15CD UNLESS NOTED OTHERWISE ON PLANS, "WG" INDICATES DEVICE WIRE GUARD
+80" AFF OR 6" BELOW FIN. CEILING WHICHEVER IS LOWER
STROBE ONLY INDICATOR, STROBES ARE 15CD UNLESS NOTED OTHERWISE ON PLANS, "WG" INDICATES DEVICE WIRE GUARD
+80" AFF OR 6" BELOW FIN. CEILING WHICHEVER IS LOWER
DUCT SMOKE DETECTOR, INCLUDING HOUSING, SMOKE DETECTOR, AND SAMPLING TUBE
"S" INDICATES SUPPLY DUCT "R" INDICATES RETURN DUCT
NAC
STANCHION MOUNTED FLAG POLE LIGHT FIXTURE CEILING/WALL
FAAP
CEILING/WALL F
EMERGENCY LIGHTING UNIT
WALL AT +84" AFF TO BOTTOM +48" AFF TO TOP
a
SINGLE POLE TOGGLE TYPE SWITCH. "a" INDICATES FIXTURE CONTROL GROUP
3
THREE-WAY TOGGLE TYPE SWITCH
+48" AFF TO TOP
4
FOUR-WAY TOGGLE TYPE SWITCH
+48" AFF TO TOP
K
KEYED SWITCH
+48" AFF TO TOP
P
TOGGLE TYPE SWITCH WITH PILOT LIGHT
+48" AFF TO TOP
WG
15CD F WG 15CD F
LCP
ON/RAISE/LOWER/OFF TYPE SWITCH
+48" AFF TO TOP
D
DIMMER SWITCH
+48" AFF TO TOP
S R
S
MC1 OCCUPANCY SENSOR CEILING MOUNT, "MC1" INDICATES TYPE, REFERENCE LIGHT EQUIPMENT SCHEDULE
CEILING
SWITCH TYPE OCCUPANCY SENSOR WALL MOUNTED, "WD" INDICATES TYPE, REFERENCE LIGHT EQUIPMENT SCHEDULE
+48" AFF TO TOP
WALL MOUNTED OCCUPANCY SENSOR FOR EXPOSED CEILING AREA, "W2" INDICATES TYPE, REFERENCE LIGHT EQUIPMENT SCHEDULE
+9'-0" AFF TO TOP
P2
POWER PACK FOR LIGHTING CONTROL
ABOVE CEILING/ON STRUCTURE
PC
PHOTOCELL
+6" ABOVE ROOF
WD
WG
TS
TAMPER SWITCH
FS
WATER FLOW SWITCH
F
FLOW ALARM BELL
+90" AFF TO BOTTOM
H
LARGE WALL PAGING SPEAKER
SEE PLAN
W2
M
MISC
POWER
C
D
WP
XFMR XP
+16" AFF TO BOTTOM
SEE PLAN
EXTERIOR POLE MOUNTED / STANCHION MOUNTED LIGHT FIXTURE
M
VOICE ONLY OUTLET
CEILING
STRIP FIXTURE
EMERGENCY EXIT SIGN/LIGHTING UNIT COMBO
MOUNTING HEIGHT UNLESS OTHERWISE NOTED
VOICE/DATA
PD
EMERGENCY EXIT SIGN
DESCRIPTION
SYMBOL
x
EWC
DUPLEX RECEPTACLE
+16" AFF
S
PAGING SPEAKER
CEILING
DUPLEX RECEPTACLE, "C" INDICATES ABOVE COUNTER TOP
+6" ABOVE COUNTER TO BOTTOM, HORIZONTALLY
TD
TEACHER STATION - INCLUDES QUAD RECEPTACLE, VOICE/DATA COMBINATION OUTLET INCLUDING (1) DATA AND (1) VOICE JACKS, AND A ROUGH-IN FOR A/V SYSTEM
ELEVATION 3, DRAWING E-502
PR
PROJECTOR - INCLUDES DUPLEX RECEPTACLE AND A ROUGH-IN FOR A/V SYSTEM
ELEVATION 3, DRAWING E-502
MD
MONITOR/TV
SEE PLAN
ES
ELECTRIC DOOR STRIKE
DETAIL 6, DRAWING E-502
DC
DOOR CONTACT
DETAIL 6, DRAWING E-502
CR
CARD READER
DETAIL 6, DRAWING E-502
KP
ALARM KEY PAD
SEE PLAN
PB
PUSH BUTTON
SEE PLAN
MOTOR
B
BUZZER
SEE PLAN
EXOTHERMIC WELD TO COLUMN OR EQUIPMENT
C
CCTV WALL MOUNT CAMERA
SEE PLAN
EXOTHERMIC WELD TEE TO GROUND GRID
C
CCTV CEILING MOUNT CAMERA
CEILING
DUPLEX RECEPTACLE, "D" INDICATES DEDICATED RECEPTACLE
+16" AFF, UNO
GROUND FAULT CIRCUIT INTERRUPTING DUPLEX RECEPTACLE, "WP" INDICATES WEATHERPROOF COVERPLATE
INTERIOR - +16" AFF TO BOTTOM EXTERIOR - +24" AFF TO BOTTOM, HORIZONTAL
ELECTRIC WATER COOLER. REFER TO MAN'F. REQUIREMENTS FOR ROUGH-IN LOCATION
PER EWC MAN'F REQUIREMENTS
DOUBLE DUPLEX RECEPTACLE
+16" AFF TO BOTTOM
SINGLE RECEPTACLE
AS NOTED
SPECIAL RECEPTACLE - REFERENCE PLANS
AS NOTED
HARDWIRED CONNECTION 30/3 F15
(*) REFER TO NEMA DESIGNATION SPECIFIED.
DISCONNECT SAFETY SWITCH, 30/3 INDICATES DISCONNECT SIZE, F15 INDICATES FUSE RATING COMBINATION MAGNETIC STARTER AND DISCONNECT SAFETY SWITCH
GROUNDING
3/4" DIAM X 10' LONG GROUND ROD
BURIED #4/0 AWG STRANDED BARE CU CONDUCTOR
GND
TEST WELL
GENERAL SURFACE MOUNTED PANELBOARD
D C B A
04/07/16 03/18/16 02/29/16 02/05/16
ISSUED FOR BIDDING ISSUED FOR OWNER REVIEW ISSUED FOR 50% BID ISSUED FOR 30% BID
PCIS PCIS PCIS PCIS
ISSUE
DATE
DESCRIPTION
APP BY
RECESSED PANELBOARD
JUNCTION BOX
J R
RELAY
T
THERMOSTAT
AS REQ'D
401 N.W. First St. Evansville, IN 47708
+54" AFF TO BOTTOM
812 425 4264
PROPOSED HIGH SCHOOL
EVANSVILLE CHRISTIAN SCH.
EC SHALL INSTRUCT THE OWNER'S REPRESENTATIVE IN THE PROPER OPERATION OF ALL NEW, REVISED, OR MODIFIED SYSTEMS INSTALLED UNDER THIS CONTRACT. EC SHALL PROVIDE ALL OPERATING INSTRUCTIONS, MAINTENANCE REQUIREMENTS, WIRING DIAGRAMS, SPARE PARTS LIST, ETC. IN A BOUND BOOKLET TO THE OWNER FOR ALL EQUIPMENT INSTALLED BY THE CONTRACTOR UNDER THIS CONTRACT.
RECESSED LED LIGHT FIXTURE. "LA" INDICATES TYPE PER LIGHT FIXTURE SCHEDULE, "3" INDICATES CIRCUIT, "a" INDICATES SWITCH CONTROL GROUP; "NL" INDICATES NON-SWITCHED NIGHT LIGHT
RECESSED EMERGENCY LED LIGHT FIXTURE WITH BATTERY BACK-UP
SURFACE MOUNTED SECONDARY SIGNAL SOLID NEUTRAL SPARE SPLICE STAINLESS STEEL SHIELDED TWISTED PAIR CARBON STEEL SUSPENDED SWITCH SWITCHBOARD
GENERAL CONTRACTOR GROUND FAULT CIRCUIT INTERRUPTER GROUND FAULT PROTECTION EQUIPMENT GROUND GALVANIZED RIGID CONDUIT
KILOVOLT AMPERE REACTIVE KILOWATT
LA
M
GC GFCI GFPE GND GRC
KVAR KW
LIGHTING
RECESSED RIGID STEEL CONDUIT RAINTIGHT (*) ROOF TOP UNIT
FLUSH FIRE ALARM FURNISHED BY OTHERS FIRE PROTECTION CONTRACTOR FOUNDATION FULL LOAD AMPS FLEXIBLE METAL CONDUIT FIBERGLASS REINFORCED EPOXY CONDUIT
THOUSAND CIRCULAR MILS KNOCK-OUT KILOVOLT AMPERE
MOUNTING HEIGHT UNLESS OTHERWISE NOTED
LAEM
F FA FBO FC FDN FLA FMC FRE
KCMIL K/O KVA
DESCRIPTION
SYMBOL
PROVIDE VOICE AND DATA COMMUNICATION CABLING INCLUDING UNSHIELDED TWISTED-PAIR CABLING, AND WORKSTATION OUTLETS. PROVIDE A 4" SQUARE X 2-1/2" DEEP BOX WITH SINGLE DEVICE PLASTER RING (UNLESS NOTED OTHERWISE) ROUGHED-IN AND 1" CONDUIT STUBBED UP AND TURNED OUT ABOVE ACCESSIBLE CEILING WITH BUSHED END. HORIZONTAL COPPER CABLING TO WORKSTATIONS TO BE #24 AWG, 100 OHM, FOUR PAIR, UTP, CAT 6. OUTLETS TO BE 100 OHM, FOUR PAIR, MODULAR RJ-45 COMPLYING WITH TIA/EIA-568-B.1, IN SINGLE WALL PLATE.
29.
35.
1P 2P 3P 4P 1P1W 1P2W 2P2W 2P3W 3P2W 3P3W 3P4W 4P4W
COMMUNICATION / ALARM SYSTEMS LEGEND
LIGHTING AND POWER LEGEND:
ELECTRICAL ABBREVIATIONS
LP1-1
F200 1"
PWR 1"
HOMERUN TO PANELBOARD. "LP1-1" INDICATES PANEL LP1, CIRCUIT 1 - MINIMUM 2-1/C #12 & 1-1/C #12 GRD IN 1/2" C FEEDER DESCRIPTION - F200 INDICATES FEEDER NUMBER PER FEEDER SCHEDULE, 1" INDICATES CONDUIT SIZE
CONDUIT DESCRIPTION. "PWR" INDICATES ELECTRICAL SYSTEM, 1" INDICATES CONDUIT SIZE
CONDUIT TURNING DOWN
WARRICK COUNTY NEWBURGH, IN The drawings, specifications and other documents, including those in electronic form prepared by PCI Skanska Inc. for this project are Instruments of Service, and may be used solely with respect to this project. The documents may not be reproduced without first obtaining the express written consent of PCI Skanska Inc. Authorized use of electronic media or file does not guarantee that these files contain complete and accurate information. In order to insure the accuracy of the information contained and that no changes or modifications have been made, either intentional or unintentional, these files must be compared to the project's contract documents with stamped and sealed certification and applicable approved modifications. There shall be no unauthorized use or material modification of such drawings, specifications and other documents, including those in electronic form prepared by PCI Skanska Inc. for this project. By and through any use, including any unauthorized use, or any material modification, or in connection with, related to, or arising out of such use or modification, the user agrees that: PCI Skanska Inc. will not be liable or responsible for such use or modification; the user will not assert a claim or file any suit, including for contribution or indemnification, against PCI Skanska Inc. for such use or modification; and the user will indemnify and hold PCI Skanska Inc. harmless from any loss, damage, liability or cost including reasonable attorney's fees. CREATED BY:
CONDUIT TURNING UP CONDUIT STUB, TERMINATE WITH BUSHING OR CAP OFF IF UNDERGROUND UNDERGROUND OR EMBEDDED CONDUIT
CHECKED BY:
DATE:
SLC
PRINTED DATE:
HLH
PROJECT NUMBER:
01/04/16 4/8/2016 7:58:51 AM
20150351.00.00
ELECTRICAL NOTES AND SYMBOL LEGENDS
E-001 SHEET NUMBER
ISSUE
D 04/07/16
ISSUED FOR BIDDING/NOT FOR CONSTRUCTION