Preview only show first 10 pages with watermark. For full document please download

En Vision C Ommercial 0 .7 5-6 Tons Installation

   EMBED


Share

Transcript

Envision Commercial 0.75-6 Tons Installation Manual COMMERCIAL Geothermal/Water Source Heat Pump • R-410A Refrigerant • 0.75-6 Tons Single Speed • 2-6 Tons Dual Capacity Installation Information on Water Piping Connections ctions Hot Water Connections ons Electrical Startup Procedures Troubleshooting Preventive Maintenance nce IM1020AN 01/13 ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL Table of Contents Model Nomenclature. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 General Installation Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Vertical Dimensional Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-8 Horizontal Dimensional Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Installing Horizontal Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10 Hanger Bracket Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Duct System and Water Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Water Quality and Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 System Cleaning and Flushing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14 Open Loop Ground Water Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Hot Water Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16-17 Freeze Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18-19 Electronic Thermostat Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19 Auxiliary Heat Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19 Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20-21 Blower Performance Data and Setting Blower Speed . . . . . . . . . . . . . . . . . . . . . . . . . . . 22-23 Wiring Schematics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24-28 Envision Controls - Premier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29-32 Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Envision Controls - FX10 (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34-40 Unit Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41 Operating Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 Operating Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42-43 Pressure Drop. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 Compressor and Thermistor Resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 Refrigerant Circuit Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 Reference Calculations and Legend . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 Heat of Extraction/Rejection Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 Startup/Troubleshooting Form . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 Preventive Maintenance and Replacement Procedures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49 Service Parts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50-53 Revision Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54 ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL Model Nomenclature 1-2 3 4-6 7 8 9 10 11 12 13 14 15 16 17 18-19 20 NS V 022 T L 0 0 0 N B N N 2 1 SS A Model Type NS = Single Speed ND = Dual Capacity Vintage C = Painted Cabinet D = Unpainted Cabinet Cabinet Configuration H = Horizontal V = Vertical Non-Standard Option Details SS = Standard Option QP = 2 in. MERV 13 Filter SF = Stainless Steel Drain Pan SG = 2 in. MERV 13 Filter with Stainless Steel Drain Pan Unit Capacity Single Speed: 009, 012, 015, 018, 022, 030 036, 042, 048, 060, 070 Dual Capacity: 026, 038, 049, 064, 072 Air 1 2 3 4 Cabinet Configuration T = Vertical Top Discharge E = Horizontal End Discharge S = Horizontal Side Discharge B = Vertical Bottom Discharge (022-072) R = Vertical Rear Discharge 1 (022-072) Coil/Insulation Options = FormiShield/Extended Range = FormiShield/Standard Range = No Coating/Extended Range = No Coating/Standard Range Control Options 2 = Premier Microprocessor 1 4 = FX10 std. no communication 5 = FX10 w/Open N2 Com Card 6 = FX10 w/LonWorks Com Card 7 = FX10 w/BacNet Com Card Return Air Configuration L = Left R = Right Water Control N = None R = Water Flow Regulator (3 gpm/ton) V = 2-Way Valve P = Internal Pump (Secondary pumping) B = 2-Way Valve w/Water Flow Regulator Voltage 0 = 208-230/60/1 2 = 265-277/60/1 (009-036) 3 = 208-230/60/3 (026, 036-072) 4 = 460/60/3 (026, 036-072) 5 = 575/60/3 (042, 048, 060, 070, PSC only) Hot Water Options 0 = No Hot Water Generator, No IntelliStartTM 2 = Hot Water Generator, without pump, No IntelliStart 1, 3 (018-072) 3 = No Hot Water Generator, IntelliStart 2 (018-072) 5 = Hot Water Generator, without pump, IntelliStart 1, 2, 3 (018-072) Hot Gas Bypass/Reheat N = None G = Hot Gas Bypass (015-072) R = Hot Gas Reheat (015-072) B = Hot Gas Bypass w/Hot Gas Reheat (015-072) Sound Kit A = None B = Sound Kit Blower Options 0 = PSC Blower 4 1 = Variable Speed ECM Blower (015-072) 2 = High Static Variable Speed ECM Blower Option (036, 038, 042, 048, 049) 3 = High Static PSC Blower Option 4 (022, 030, 036, 042, 048) Coax Options C = Copper N = Cupronickel Rev.: 09 January 2013D NOTES: 1 Not available with Hot Gas Reheat 2 Only on 208-230/60/1 3 Field installed external pump kit (DPK4 or DPK5) required for hot water generation 4 Not available on dual capacity models 4 ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL General Installation Information Unit Location Safety Considerations Locate the unit in an indoor area that allows for easy removal of the filter and access panels. Location should have enough space for service personnel to perform maintenance or repair. Provide sufficient room to make water, electrical and duct connection(s). If the unit is located in a confined space, such as a closet, provisions must be made for return air to freely enter the space by means of a louvered door, etc. Any access panel screws that would be difficult to remove after the unit is installed should be removed prior to setting the unit. On horizontal units, allow adequate room below the unit for a condensate drain trap and do not locate the unit above supply piping. Care should be taken when units are located in unconditioned spaces to prevent damage from frozen water lines and excessive heat that could damage electrical components. WARNING: Before performing service or maintenance operations on a system, turn off main power switches to the indoor unit. If applicable, turn off the accessory heater power switch. Electrical shock could cause personal injury. Installing and servicing heating and air conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair or service heating and air conditioning equipment. Untrained personnel can perform the basic maintenance functions of cleaning coils and cleaning and replacing filters. All other operations should be performed by trained service personnel. When working on heating and air conditioning equipment, observe precautions in the literature, tags and labels attached to the unit and other safety precautions that may apply. Installing Vertical Units Follow all safety codes. Wear safety glasses and work gloves. Use a quenching cloth for brazing operations and have a fire extinguisher available. Prior to setting the unit in place, remove and discard the compressor hold down shipping bolt located at the front of the compressor mounting bracket. Moving and Storage Vertical units are available in left or right air return configurations. Top flow vertical units should be mounted level on a vibration absorbing pad slightly larger than the base to provide isolation between the unit and the floor. It is not necessary to anchor the unit to the floor (see right). Move units in the normal “up” orientation. Horizontal units may be moved and stored per the information on the packaging. Do not stack more than three units in total height. Vertical units may be stored one upon another to a maximum height of two units. Do not attempt to move units while stacked. When the equipment is received, all items should be carefully checked against the bill of lading to be sure all crates and cartons have been received. Examine units for shipping damage, removing the units from the packaging if necessary. Units in question should also be internally inspected. If any damage is noted, the carrier should make the proper notation on the delivery receipt, acknowledging the damage. Bottom flow units should be mounted level and sealed well to floor to prevent air leakage. Bottom flow units require the supply air opening to be cut at least 1/2 in. larger than the unit’s air outlet. Protect the edges of combustible flooring with sheet metal over-wrap or other noncombustible material. Figure 1: Vertical Unit Mounting 2” Extruded Polystyrene 5 ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL Vertical Dimensional Data Top Air Discharge LEFT RETURN Field Installed Duct Flange L Filter Rack Width Legend AP BP CP CMP B N = Alternate Service Panel = Blower Service Panel = Control Access Panel = Compressor Service Panel O Access Panels AIR COIL 2´ [61cm] Alternate Service Access Left Return (Right Return opposite side) B N O AP BP FRONT A M FRONT CMP 2´ [61cm] Service Access Left Return (Right Return opposite side) M A AP CP P Q AIR COIL SIDE AIR COIL SIDE TOP VIEW - RIGHT RETURN TOP VIEW - LEFT RETURN S S R 2´ [61cm] Service Access 1.00˝ (25.4 mm) R U U BP FILTER RACK CONNECTION FILTER RACK CONNECTION AIR COIL T T C C 1.6˝ (4.1 cm) CONDENSATE 3/4"˝ PVC GLUE SOCKET POWER SUPPLY 3/4˝ (19.1 mm) KNOCKOUT 4 CP 3 1.3˝(3.3 cm) 5 CMP 5 LOW VOLTAGE 1/2˝ (12.7 mm) KNOCKOUT FRONT BACK BACK FRONT AP J F K I E 1 D CMP LEFT VIEW - LEFT RETURN RIGHT VIEW - RIGHT RETURN Overall Cabinet Vertical Models 009012 015018 022030 036072 FRONT VIEW Water Connections 1 2 3 4 5 G H 2 Electrical Knockouts I 1/2” cond J 1/2” cond K 3/4” cond Low Voltage Ext Pump Power Supply A Width B Depth C Height* D In E Out F HWG In G HWG Out H Condensate Loop Water FPT HWG FPT in. 22.2 22.5 34.5 2.34 5.3 11.9 14.9 8.6 1/2" 1/2" 3.8 9.7 11.7 cm. 56.4 57.2 87.6 5.9 13.5 30.2 37.8 21.8 12.7 mm 12.7 mm 9.7 24.6 in. 22.5 26.5 39.4 2.3 5.3 13.4 16.4 9.6 3/4" 1/2" 5.1 10.8 cm. 57.2 67.3 100.1 5.8 13.5 34.0 41.7 24.3 19.05 mm 12.7 mm 13.0 in. 22.5 26.5 48.4 2.3 7.3 13.4 16.4 10.4 3/4" 1/2" cm. 57.2 67.3 122.9 5.8 18.5 34.0 41.7 26.4 19.05 mm in. 25.5 31.2 58.5 2.3 7.3 15.9 18.9 11.6 1" cm. 64.8 79.2 148.6 5.8 18.5 40.4 48.0 29.5 25.4 mm L Filter Rack Width Discharge Connection duct flange installed (±0.10 in) Return Connection using std deluxe filter rack (±0.10 in) M Supply Width N Supply Depth O P Q R S Return Depth T Return Height U 2.2 10.0 10.0 6.1 8.8 11.8 2.4 18.1 14.2 1.7 29.7 5.6 25.4 25.4 15.5 22.4 30.0 6.1 46.0 36.1 4.4 12.8 2.2 14.0 14.0 6.3 7.8 5.8 2.3 22.0 18.0 2.0 27.4 32.5 5.6 35.6 35.6 16.0 19.8 14.7 5.8 55.9 45.7 5.1 5.1 10.8 12.8 2.2 14.0 14.0 6.3 7.7 5.8 2.3 22.0 26.0 2.0 12.7 mm 13.0 27.4 32.5 5.5 35.6 35.6 16.0 19.6 14.7 5.8 55.9 66.0 5.1 1/2" 5.6 11.4 13.4 2.2 18.0 18.0 6.6 6.4 3.7 1.4 28.1 34.0 1.7 12.7 mm 14.2 29.0 34.0 5.5 45.7 45.7 16.8 16.3 9.4 3.6 71.4 86.4 4.3 10/1/10 Condensate is 3/4 in. PVC female glue socket and is switchable from front to side. Vertical unit shipped with deluxe 1 in. (field adjustable to 2 in.) duct collar/filter rack extending from unit 3.25 in. and is suitable for duct connection. Discharge flange is field installed and extends 1 in. [25.4 mm] from cabinet. 6 ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL Vertical Dimensional Data cont. Bottomflow RIGHT RETURN LEFT RETURN CMP AP 1.70 (4.3 cm) 4 3 CP C C 2 FILTER RACK CONNECTION CMP FILTER RACK CONNECTION CP S 1 S K BP F I D B B LEFT SIDE RIGHT SIDE Q R 1.90 (4.7 cm) R 5 Q A Optional 2´ [61cm] Service Access Right Return L 2´ [61cm] Service Access L O Legend O LEFT BOTTOM DISCHARGE FLOOR FOOT PRINT A B C Width Depth Height RIGHT BOTTOM DISCHARGE FLOOR FOOT PRINT Water Connections Overall Cabinet AP =Alternate Service Panel BP =Blower Service Panel CP =Control Access Panel CMP=Compressor Service Panel P N M Bottomflow Models H FRONT N (Opposite Side for Left Return) G E BP T T AP J 1 2 3 4 5 D In E Out F HWG In G HWG Out H Condensate Electrical Knockouts Loop Water FPT HWG FPT 3/4" 1/2" I 1/2” cond Low Voltage J 1/2” cond Ext Pump K 3/4” cond Power Supply Discharge Connection duct flange installed (±0.10 in) L M N Supply Width O Supply Depth Return Connection using std deluxe filter rack (±0.10 in) P 022030 in. 22.5 26.5 52.5 35.2 40.2 46.7 49.7 3.6 cm. 57.2 67.3 133.4 89.4 102.1 118.6 126.2 9.1 036072 in. 25.5 31.5 62.5 43.4 48.4 57.0 60.0 3.1 1" 1/2" 47.1 54.9 56.9 9.1 4.8 13.3 13.6 1.5 cm. 64.8 80.0 158.8 110.2 122.9 144.8 152.4 7.9 25.4 mm 12.7 mm 119.6 139.4 144.5 23.1 12.2 33.8 34.5 3.8 19.05 mm 12.7 mm Q R Return Depth S Return Height T 39.2 47.0 49.0 8.6 6.0 9.3 10.5 1.0 2.2 22.1 26.0 5.6 99.6 119.4 124.5 21.8 15.2 23.6 26.7 2.5 5.6 56.1 66.0 14.2 1.7 28.1 34.0 5.6 4.3 71.4 86.4 14.2 10/1/10 Condensate is 3/4 in. PVC female glue socket and is switchable from side to front. Vertical bottomflow unit shipped with deluxe 1 in. (field adjustable to 2 in.) duct collar/filter rack extending from unit 3.25 in. and is suitable for duct connection. 036-072 bottomflow units use 30 in. x 36 in. air filter. 7 ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL Vertical Dimensional Data cont. Rear Air Discharge AIR COIL Legend AP BP CP CMP BP = Alternate Service Panel = Blower Service Panel = Control Access Panel = Compressor Service Panel BP AP CP AP 1.6 4 Power Supply 3/4" (19.1 mm) HV Knockout 3 5 1/2" (12.7 mm) LV Knockout K G F J 2 CP I H E 1 D Primary FRONT VIEW Right Return 2 ft [61cm] Service Access Points 1.00 B R Secondary A S L 1.00 A Q B L P S R U U N N FILTER RACK CONNECTION FILTER RACK CONNECTION M C C FRONT C C O AIR COIL T M O FRONT T AIR COIL Power Supply 3/4" (19.1 mm) HV Knockout 1.3 5 1/2" (12.7 mm) LV Knockout AP J H CMP SIDE VIEW Right Return REAR VIEW Right Return Water Connections Overall Cabinet 1 Vertical Models 022- in. 030 cm. 036- in. 072 cm. A Width B C Depth Height* REAR VIEW Left Return D In 2 E Out 3 F HWG In 4 G H HWG CondOut ensate SIDE VIEW Left Return Electrical Knockouts 5 Loop Water FPT HWG FPT 3/4" 1/2" 22.3 26.5 48.4 2.3 7.3 13.4 16.4 10.4 56.7 67.3 123.0 5.8 18.5 34.0 41.7 26.4 25.5 31.2 58.4 2.3 7.3 15.9 18.9 11.6 1" 64.8 79.3 148.4 5.8 18.5 40.4 48.0 29.5 25.4 mm I 1/2” cond Low Voltage J 1/2” cond Ext Pump K 3/4” cond Power Supply KK 3/4” cond Power Supply K I L Filter Rack Width Discharge Connection duct flange installed (±0.10 in) M N Supply Supply Width Depth O P Return Connection using std deluxe filter rack (±0.10 in) Q R S Return Depth T Return Height U 2.0 5.1 10.8 12.8 N/A 2.2 9.5 10.4 37.0 8.5 6.5 2.1 22.0 26.0 13.0 27.4 32.5 N/A 5.5 24.1 26.4 94.0 21.6 16.5 5.3 55.9 66.1 5.1 1/2" 5.6 11.4 13.4 3.7 2.2 13.3 13.6 43.4 9.1 8.1 1.6 28.1 34.0 1.7 12.7 mm 14.2 29.0 34.0 9.4 5.5 33.8 34.6 110.3 23.1 20.6 4.1 71.4 86.4 4.3 19.05 mm 12.7 mm 10/1/10 Condensate is 3/4 in. PVC female glue socket and is switchable from side to front. Vertical unit shipped with deluxe 1 in. (field adjustable to 2 in.) duct collar/filter rack extending from unit 3.25 in. and is suitable for duct connection. Discharge flange is field installed and extends 1 in. [25.4 mm] from cabinet. 8 ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL Horizontal Dimensional Data Legend Optional 2´ [61cm] Service Access AP BP CP CMP AP FRONT = Alternate Service Panel = Blower Service Panel = Control Access Panel = Compressor Service Panel CMP FRONT Optional 2´ [61cm] Service Access RIGHT RETURN LEFT RETURN 2ft [61cm] Service Access ß [5.3 cm] ß [5.3 cm] AP CMP Optional 2´ [61cm] Service Access POWER SUPPLY 3/4" KNOCKOUT H 1.9(4.8 cm) 5 H 1.9(4.8 cm) LOW VOLTAGE 1/2" KNOCKOUT 4 CONDENSATE CONDENSATE 5 3 SIDE DISCHARGE END DISCHARGE CP K I LOW VOLTAGE 1/2" KNOCKOUT 2.9 (7.3 cm) N SIDE DISCHARGE G F 2 J E 1 D A FRONT VIEW BP O END DISCHARGE O 2.9(7.3 cm) N H C C Blower Outlet M Filter Rack M Blower Outlet Air Coil Side Filter Rack Air Coil Side L H L 2.1 (5.3 cm) BP A RIGHT RETURN END DISCHARGE 2.1 (5.3 cm) A LEFT RETURN END DISCHARGE BP CMP FRONT Blower Outlet M FRONT L AP M Blower Outlet L BP N N LEFT RETURN SIDE DISCHARGE RIGHT RETURN SIDE DISCHARGE FRONT FILTER RACK CONNECTION 1.8(4.6 cm) T T AP Q S S Q C P R CMP FILTER RACK CONNECTION R B C FRONT P B AIR COIL RIGHT RETURN RIGHT VIEW AIR COIL LEFT RETURN LEFT VIEW NOTE: *Only models 009 - 030 require four (4) hangers. Overall Cabinet Horizontal Models A Width B C Depth Height* Water Connections 1 2 3 4 5 D In E Out F HWG In G HWG Out H Condensate Electrical Knockouts Loop Water FPT HWG FPT I K J 1/2” cond 3/4” cond 1/2” cond Low Power Ext Pump Voltage Supply Condensate Return Connection using std deluxe filter rack (±0.10 in) 5 Discharge Connection duct flange installed (±0.10 in) L M N Supply Supply Height Depth O P Q R Return Return Depth Height S T PVC Size 009012 in. 22.5 44.0 17.3 2.3 5.3 11.9 14.9 0.8 1/2" 1/2" 3.8 9.7 11.7 5.9 7.3 9.7 5.8 5.8 17.8 14.6 1.7 1.4 1/2" cm. 57.2 111.8 43.9 5.8 13.5 30.2 37.8 2.1 12.7 mm 12.7 mm 9.7 24.6 29.7 15.0 18.5 24.6 14.7 14.7 45.2 37.1 4.3 3.6 12.7 mm 015018 in. 22.5 53.0 19.3 2.3 5.3 13.8 16.8 0.8 3/4" 1/2" cm. 57.2 134.6 49.0 5.8 13.5 35.1 42.7 2.1 022030 in. 22.5 63.0 19.3 2.3 5.3 13.8 13.8 0.8 cm. 57.2 160.0 49.0 5.8 13.5 35.1 35.1 2.1 036038 in. 25.5 72.0 21.3 2.2 7.2 15.8 18.8 0.8 cm. 64.8 182.9 54.1 5.6 18.3 40.2 47.8 2.1 042049 in. 25.5 77.0 21.3 2.2 7.2 15.8 18.8 0.8 cm. 64.8 195.6 54.1 5.6 18.3 40.2 47.8 2.1 060072 in. 25.5 82.0 21.3 2.2 7.2 15.8 18.8 0.8 cm. 64.8 208.3 54.1 5.6 18.3 40.2 47.8 2.1 19.05 mm 12.7 mm 3/4" 1/2" 19.05 mm 12.7 mm 1" 1/2" 25.4 mm 12.7 mm 1" 1/2" 25.4 mm 12.7 mm 1" 1/2" 25.4 mm 12.7 mm 5.9 11.6 13.6 7.0 10.5 9.5 8.2 8.2 21.8 16.5 2.2 1.5 1/2" 14.9 29.5 34.5 17.8 26.7 24.1 20.8 20.8 55.4 41.9 5.6 3.8 12.7 mm 5.9 13.7 15.7 6.5 10.5 9.4 6.5 5.8 30.5 16.5 2.8 1.4 3/4" 14.9 34.7 39.8 16.6 26.5 23.8 16.5 14.6 77.3 41.9 7.1 3.6 19.05 mm 5.9 13.7 15.7 4.9 13.6 13.2 4.6 6.8 35.5 18.7 2.8 1.3 3/4" 14.9 34.7 39.8 12.4 34.6 33.5 11.6 17.2 90.0 47.5 7.1 3.3 19.05 mm 5.9 13.7 15.7 4.9 13.6 13.2 4.6 6.8 40.5 18.5 2.8 1.4 3/4" 14.9 34.7 39.8 12.4 34.6 33.5 11.6 17.2 102.7 47.0 7.1 3.6 19.05 mm 5.9 13.7 15.7 4.9 13.6 13.2 4.6 6.8 45.5 18.6 2.8 1.4 3/4" 14.9 34.7 39.8 12.4 34.6 33.5 11.6 17.2 115.4 47.2 7.1 3.6 19.05 mm Horizontal unit shipped with deluxe 1 in. (field adjustable to 2 in.) duct collar/filter rack extending from unit 2.88 in. and is suitable for duct connection. 9 10/1/10 ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL Installing Horizontal Units on the underside of the bottom panel. When attaching the hanger rods to the bracket, a double nut is required since vibration could loosen a single nut. To allow filter access, one bracket on the filter side should be installed 180° from the position shown in the figure below. The unit should be pitched approximately 1/4 in. towards the drain in both directions to facilitate the removal of condensate. Use only the bolts provided in the kit to attach hanger brackets. The use of longer bolts could damage internal parts. Remove and discard the compressor hold down shipping bolt located at the front of the compressor mounting bracket prior to setting the unit in place. Horizontal units are available with side or end discharge. NOTES: 1) Left (Right) Return Side Discharge cannot be converted to Left (Right) Return End Discharge or vice versa, without additional custom sheet metal parts. Horizontal units are normally suspended from a ceiling by four (009-030 models) or six (036-072 models) 3/8 in. diameter threaded rods. The rods are usually attached to the unit by hanger bracket kits furnished with each unit. 2) In some applications, it is difficult to service the filter with the central hanger bracket, located near the air coil, installed. In these instances, it is permissible to suspend the unit with the five remaining hanger brackets. Some applications require the installation of horizontal units on an attic floor. In this case, the unit should be set in a full size secondary drain pan on top of a vibration absorbing pad. The secondary drain pan prevents possible condensate overflow or water leakage damage to the ceiling. The secondary drain pan is usually placed on a plywood base isolated from the ceiling joists by additional layers of vibration absorbing material. Lay out the threaded rods per the dimensions below. Assemble the hangers to the unit as shown. Securely tighten the brackets to the unit using the weld nuts located CAUTION: Do not use rods smaller than 3/8-inch diameter since they may not be strong enough to support the unit. The rods must be securely anchored to the ceiling. Figure 2: Horizontal Unit Mounting Flexible Duct Collar Threaded Rods Hanging Brackets (Included) Insulate supply plenum and use at least one 90 O elbow to reduce noise To Line Power Hose Kits To Thermostat Electrical Disconnect Line Voltage s Valve Ball Building Water Loop 10 ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL Hanger Bracket Locations Figure 3: Hanger Location and Assembly @WUVb :STb / 4  !&BV`SORSR @]RPg]bVS`a ! DWP`ObW]\ 7a]ZOb]` /W`1]WZ  " 1 0 EOaVS` " /W`1]WZ 0]ZbO\R :]QYEOaVS` 2 Weight Distribution Table Hanger Dimensions Single Speed 015-018 022-030 036 042-048 060-070 Dual Capacity 026 038 049 064 072 cm. in. cm. in. cm. in. cm. in. cm. in. cm. in. cm. in. cm. in. cm. in. cm. in. cm. 99S500A04 99S500A04 99S500A04 99S500A03 99S500A03 99S500A03 99S500A04 99S500A03 99S500A03 99S500A03 99S500A03 A B C D 44.7 25.1 21.4 n/a 113.5 63.8 54.4 n/a 53.7 25.1 21.4 n/a 136.4 63.8 54.4 n/a 63.4 24.8 21.1 n/a 161.0 63.0 53.6 n/a 72.4 27.8 24.1 29.3 183.9 70.6 61.2 74.4 77.4 27.8 24.1 29.3 196.6 70.6 61.2 74.4 82.4 27.8 24.1 29.3 209.3 70.6 61.2 74.4 63.4 24.8 21.1 n/a 161.0 63.0 53.6 n/a 72.4 27.8 24.1 29.3 183.9 70.6 61.2 74.4 77.4 27.8 24.1 29.3 196.6 70.6 61.2 74.4 82.4 27.8 24.1 29.3 209.3 70.6 61.2 74.4 82.4 27.8 24.1 29.3 209.3 70.6 61.2 74.4 Model 009 012 015 018 Single Speed 009-012 in. Unit Hanger Dimensions 022 030 036 042 048 060 070 026 10/1/10 Dual Capacity Hanger Kit Part Number Model ! 6Sf 600 PSI Lockout Low Pressure < 40 PSI Lockout ECM2 RPM < 100 rpm Lockout Microprocessor malfunction* HWL thermistor > 130°F DHW pump switch off Current Fault Status Not Used 3 Not Used 8 Pink 1 Pink 12 Yellow 5 Yellow 13 Blue 6 Blue 7 Black 14 Black Inputs Outputs #1 Off, #6 On, #7 On #6 Off, #7 On #6 On, #7 Off Drain pan overflow Y1 Compressor Lo FD thermistor (loop<15°F, well<30°F) Y2 Compressor Hi High Pressure > 600 PSI O RV Low Pressure < 40 PSI G FAN ECM2 RPM < 100 rpm W Not Used SL1 Loop Pump 1 HWL thermistor > 130°F SL2 Loop Pump 2 -DHW pump switch off -- *Green LED not flashing RV Switch - High pressure Orange 10 Diagnostic Modes LED Capacitor w/ bleed resistor Not Used Outputs2 #6 Off, #7 Off Blower Lo Blower Med Blower Hi Aux Heat #1 Aux Heat #2 AuxHeat #3 Aux Heat #4 -- Switch - Low pressure T Switch -Hot Water On/Off HWL P T 2 3 1 Polarized connector FD LP HP CA CC CO CR1 CR2CR3 CR4 CS F1 and F2 HE HP ER1 to ER4 LP PB1, PB2 PS RV SW1 SW2 SW3 SW4 TS HWL SC SR FD - Comfort Alert Compressor Contactor Condensate overflow sensor DHW pump relay Loop pump relay PSC Fan Speed Relay PSC Fan Power Relay Compressor Solenoid Fuses Heater element High pressure switch Aux heat stage relays Low pressure switch Power blocks Power strip Reversing Valve coil DIP package 12 position DIP package 8 position DIP package 5 position Hot water pump enable switch Thermal limit switch Hot water limit sensor Start Contactor Start Relay Freeze Detection Sensor 97P774-11 12/05/06 24 Notes: 25 CC CO CP CP DA DF/FP DH ES HP HWL LP - Field wire lug 1 3 2 OS PB1, PB2 RCP RV SW1 SW2 SW3 SW4 TB TS FD - Open Jumper Occupied Switch Power blocks Rectified Solenoid Compressor Plug Reversing Valve coil DIP package 12 position DIP package 8 position DIP package 5 position Hot water pump enable switch Terminal Board Thermal limit switch Freeze Detection Closed Jumper PB2 NOTE 1 Blue (32) LP OS ES NOTE 8 DF/FP 9VDC DI1 DI2 56 55 Orange (30) 54 DI3 DI4 Pink (25) 53 Blk/Wht (29) Blue (27) 52 DI5 51 Gray (26) DI6 50 Red (24) DI 3/4/5/6/ Com Violet (23) 49 DI7 48 Yellow (21) Black (22) DI8 DI9 DI10 47 Blue (72) 46 44 45 Black (5) Orange (71) Green (70) DI12 24VAC Com DI11 J9 J10 43 Gray/Wht (14) 42 PWM2 PWM1 PWM2 Com J7 A11 Blue (10) 1 2 3 CP 41 40 39 5VDC 38 A13 A23 Compressor Contactor Condensate Overflow Sensor Compressor Proving Compressor Solenoid Discharge Air Temperature Sensor Dirty Filter or Fan Proving Dehumidification Switch or Humidistat Emergency Shutdown High Pressure Switch Hot water limit sensor Low Pressure Switch Compressor Solenoid Rectified Compressor Solenoid Plug Polarized connector Gray (68) Yellow (50) LED 37 L1 T1 C Blk Yellow (50) Blue (10) Black (5) Yellow (35) Blk/Wht (36) Violet (15) G 265-277/60/1 Unit Power Supply Yellow (18) Johnson FX-10 A31 Relay ContactsN.O., N.C. P 36 J2 35 Orange (66) AI1 + 5VDC 34 Yellow/Red (53) Orange/Wht (67) 31 AI2 + Gray (65) 33 AI4 + 32 29 Yellow (51) 28 Black (63) Blk/Red (64) AI5 + AI3 + Yellow/Wht (52) 27 AI6 + 26 30 25 Wht/Blue (42) 1K 23 24 White (62) R Green/Yel (37) A21 Ground NOTE 6 T 11K Brown (61) Brown (60) 5VDC L2 T2 A12 Switch - High pressure NOTE 7 DA FD T CO J8 A14 A22 Switch - Low pressure B Orange (66) Orange/Wht (67) A15 A25 Switch - Condensate overflow 7 15 Blue (72) Gray (65) Black (73) CC Red Blue(55) A32 A24 Capacitor w/ bleed resistor Relay coil 4 14 Yellow (21) RB White S Cap GROUND A35 Quick connect terminal T Legend Temp Occ (TO) Thermistor Black (RS) Black (44) Black (AIC) AI Com (AIC) Room Sensor (RS) Sensor Com (SC) Black (Y2) Black (SS) Comp (Y2) Setpoint Shift (SS) 10 Orange (71) Green (70) Yellow (18) Violet (15) Brown (13) Black P3 Cap Blu A33 RCP L1 Black (Y1) Comp (Y1) Red (33) Black (34) H M L Wh Brn Compressor 24VAC Com A34 Internal junction Black (O) Black (31) 2 Black (G) Fan (G) Rev Valve (O) 9 13 NOTE 3 Acc 2 (X2) 5 12 Black (X2) Black (L) Black (X1) NOTE 2 Alarm (L) Acc 1 (X1) 1 6 3 Air flow Settings NOTE 1 Grn PSC Fan Motor 24VAC Factory Low voltage wiring Factory Line voltage wiring Field low voltage wiring Field line voltage wiring Optional block DC Voltage PCB traces Field Zone Sensor Wiring Zone Sensor Terminal 6 Zone Sensor Terminal 5 Zone Sensor Terminal 2 Zone Sensor Terminal 3 Zone Sensor Terminal 1 Black (R) Black (C) Green/Yel (38) 24V COM (C) 24VAC (R) NOTE 4 TB 1 – Disconnect for 15 degree freeze protection. 2 – Acc 1 output is cycled with the compressor. 3 – Acc 2 output is cycled with the fan. 4 – R, C, Y1, Y2, and G inputs are for use with a wall mounted thermostat . TO, SC, RS, AIC, and SS are for use with a TAXXJ02 zone sensor. 5 – Network controllable 24VAC output. 6 – Network controllable PWM output. 7 – Wires 51, 52, & 53 can be configured for a field installable humidity sensor or an A99 temperature sensor. 8 – Network configurable input. 9 – Not Used – Bundled in the air handler. D01 D02 D03 10 D04 1 2 3 4 5 6 7 8 9 11 12 13 14 15 16 D05 D06 D07 18 D08 17 19 20 D09 Brown (13) Black (34) A Black (F1) Black (F2) Black (F3) Black (F4) Black (F5) Black (F6) Black (F7) Black (F8) Black (F9) Black (F10) Black (F11) Black (F12) Black (F13) Black (F14) Black (F15) Black (F16) 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 Black (F17) 19 Black (F19) 20 Black (F18) Black (F20) Red (33) Black (1) Yellow (J1) Violet (3) White (4) Black (5) Black (6) Orange (7) Yellow (J1) Yellow (J2) Blue (10) Gray (11) Yellow (12) Brown (13) Violet (15) Yellow (J2) Yellow (17) Yellow (18) Gray (19) Yellow (20) 265V 277V HP NOTE 5 Blue Violet (3) CC Orange (40) RV NOTE 5 Black (34) Red (33) Transformer RB Black (74) 97P774-18 Blk/Wht (43) 1 2 3 PB1 Yellow Blk/Wht Yellow (50) 2/16/07 Violet (28) P12 10 15 12 3 1 NOTE 9 Grn/Yel (57) ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL Wiring Schematics cont. FX10 Control 265-270/60/1 - PSC Motor NOTE 7 Optional Electronic Air-Filter Optional Remote Unit Without Loop Pump SL1 Out SL1 In C NOTE 2 NOTE 9 L1 G O W Y2 Y1 C R Blue Blue Violet(2) Blk(1) Thermostat CC RCP CS NOTE 11 Used 3 R G Y R R R R R 3 2 2 Acc NO 1 1 Acc NC 7 Acc Com P3 NOTE 3 6 5 Not 4 SL1 In SL1 Out P4 On LED Drain Water Flow High Press Low Press / Comp Air Flow Status DHW Limit DHW off *Green LED not flashing SW1 1 2 3 4 5 Diagnostic Modes Inputs P5 Outputs Not Used Black #6 Off, #7 Off Blower Lo Blower Med Blower Hi Aux Heat #1 Aux Heat #2 AuxHeat #3 Aux Heat #4 -- Outputs2 Black 7 14 Blue Blue 13 6 Pink Yellow 5 Pink Yellow 1 8 12 Orange Not Used Not Used 2 3 Orange Tan 10 9 4 11 #1 Off, #6 On, #7 On #6 Off, #7 On #6 On, #7 Off Drain pan overflow Y1 Compressor Lo FD thermistor (loop<15°F, well<30°F) Y2 Compressor Hi High Pressure > 600 PSI O RV Low Pressure < 40 PSI G FAN ECM RPM < 100 rpm W Not Used SL1 Loop Pump 1 HWL thermistor > 130°F SL2 Loop Pump 2 -DHW pump switch off -- Current Fault Status Main Logic PCB 2 Speed / 1 Speed Normal / Finish on 2nd (Note 6) No RPM / RPM Electric Heat / Normal (Note 8) N or R Series / E Series or Premier Field Selection Dips - #1 On, #6 On, #7 On Drain pan overflow Lockout FD thermistor (loop<15°F,well<30°F) Lockout High Pressure > 600 PSI Lockout Low Pressure < 40 PSI Lockout ECM RPM < 100 rpm Lockout Microprocessor malfunction* HWL thermistor > 130°F DHW pump switch off Normal Display Mode Test / Norm Loop / Well Fan / Comp Dehum / Norm No Htg3 / Htg3 Inputs / Norm Outputs / Norm Pulse L / Constant L (NOTE 9) On 2 SW3 Not Used 16 1 C 1 2 3 4 5 6 7 8 Red On Tan 3 11 P2 Shut Down SW2 White 1 1 2 3 4 5 6 7 8 9 10 11 12 Pink 2 NOTE 10 Blue 3 Orange C Not Used ECM2 Air Flow Settings Violet Blue Yellow 4 5 7 Black Not Used 9 8 LO C Not Used G P6 8 13 R 6 7 O COM 15 6 W CR4 Premier 2 Microprocessor Logic Control (DC Voltage) COM NC 10 5 Y2 CR3 NO Gray 4 COM NC 240V L1 Brown 3 Y1 CR2 NO F1-10A 240V 240V L2 12 2 C COM NO 240V L2 Brn(8) Gry/Wht(5) Blk/Wht(4) NOTE 4 14 1 P1 R CC-GND CC CCHI CR1 NO Fused L2 Org(7) L1 3 PS 1 2 T T RV Yel Blk Blk/Wh 24V HP LP FD HWL CO Transformer Red Blu 208V 240V L1 CA CC CO CR1 CR2CR3 CR4 CS F1 and F2 HE HP ER1 to ER4 LP - Transformer Switch NOTE 1 208V 240V Blk/Wht (6) 2 3 C2 3 P11 8 P 2 Legend 15 16 10 Comfort Alert Compressor Contactor Condensate overflow sensor DHW pump relay Loop pump relay PSC Fan Speed Relay PSC Fan Power Relay Compressor Solenoid Fuses Heater element High pressure switch Aux heat stage relays Low pressure switch Fuse Relay ContactsN.O., N.C. Ground Field wire lug Wire nut 5 ECM Fan Motor 4 Factory Low voltage wiring Factory Line voltage wiring Field low voltage wiring Field line voltage wiring Optional block DC Voltage PCB traces Internal junction Quick connect terminal 1 Grn Org Brn 1 PB1, PB2 PS RV SW1 SW2 SW3 SW4 TS HWL SC SR FD - 3 G T 6 5 4 3 2 P10 1 P12 Thermistor Power blocks Power strip Reversing Valve coil DIP package 12 position DIP package 8 position DIP package 5 position Hot water pump enable switch Thermal limit switch Hot water limit sensor Start Contactor Start Relay Freeze Detection Sensor Polarized connector Switch -Hot Water On/Off Switch - Low pressure Switch - High pressure Switch - Condensate overflow Capacitor w/ bleed resistor Relay coil Light emitting diode - Green Red Tan White Pink Blue Orange Gray Blue Yellow Violet Black Org Brn 1 Grn 2 C2 3 3 5 ECM Fan Motor 4 P4 15 16 10 1 2 3 P11 N.O. P12 6 7 C Y1 Y2 W O G 5 1 2 3 CR3- Com N.C. N.O. 8 2 C 1 Shut Down SW2 Off On 1 2 3 4 5 6 7 8 P2 C 3 Microprocessor 4 SL1 IN 6 SL1 SL2 Out IN 5 SW3 Off On 1 2 3 4 5 5 Blk 4 P2 Premier 2 Logic Board 1 2 3 4 5 6 7 8 9 10 11 12 L SW1 Off On R 4 N.O. CR2- Loop Pump 2 P1 F1 P10 Yel Or Pink Brn L2 4 L4 5 3 2 E-Series Logic Board - Physical Layout 1 3 C C R R CC-GND CC CCLO CCHI CR1- DHW Pump 8 Violet Blu Grn 1 P9 G SL2 Out 7 6 1 Gray L1 L1 NO ER4 NO ER3 NO ER2 NO ER1 1 3 4 5 6 1 2 2 3 4 5 6 7 8 2 7 P3 8 9 10 11 12 13 14 9 10 11 12 13 14 15 16 Com 3 ACC ACC ACC NO NC COM 1 CR4- N.O. F1 L3 PB2 EA Series PCB F2 NOTE 5 L2 P8 P5 P6 Yel Pink HE4 HE3 HE2 HE1 TS4 TS3 TS2 TS1 L2 L1 L2 Unit Power 208-230/60/1 97P774-12 12/05/06 9 – SW2-8 must be in the OFF position for pulsed “L” lockout signal and in the ON position for constant “L” lockout signal. 10 - Air Flow Configuration Example: SW1 configured for dip 1 as low, dip 3 as medium, and dip 5 as high Speed ECM2 fan 11 – Dual Capacity units only. 4 - The blk/wh and gray/wh wires are removed when Aux Heat is installed . 5 - Buss lugs L1 and L2 can be removed and dual power wire sets connected directly to box lugs L 1, L2, and L3, L4. 6 - This Switch allows the unit to down stage with the t -stat when OFF and finish on second stage when ON. Finish second stage reduces stage changing in recip dual capacity compressors and should be ON for unzoned Dual Cap E -Series or Premier 2 speed units. 7 - When optional electronic air -filter is installed, power for the electronic air-filter is provided by P2-2 and 24 VAC. 8 – SW3-4 should be in the OFF position when using the 17P501A01 electric heat board and should be ON when using the 17P514A01 electric heat board . Notes: L2 Circuit Breakers L1 Aux Elect Power 208-230/60/1 L1 Breaker box furnished by installer Single Disconnect Power 208-230/60/1 CSA installed units only Local codes may require a single source of power supply Pink Yel Blk Gray 1 - Place switch to 208V position to operate unit at 208V. 2 - Connection of remote unit that does not have a loop pump for slave operation . 3 - 24V Accessory relay (see SW2 - 3 for description of operation ) Pink Yel 3 4 Blk Gray Gray Blk Yel Pink 2 1 P7 1 Gray Blk 2 Gray 3 Blk 4 Yel Pink G Premier Control 208-230/60/1 - ECM Motor SW4 Status LED PCB L2 F1-10A 240V Blue (10) On/Off Run Capacitor RPM Fused L2 G PWM T1 RPM grnd T2 CC On/Off Unit Power 208-230/60/1 RPM Black PWM 240V - L1 Red Fused L1 Blue Fused L2 26 Fused L2 RPM grnd 240V - L1 Auxiliary Electric Heat Power 208-230/60/1 Fused L2 With optional ' EA' Series Auxiliary ElectricHeat Typical schematic shown Fused L2 T1 240V - L2 T3 240V - L2 T2 ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL Wiring Schematics cont. Blk(1) G Wht(4) Yel(6) Blk(5) Pump 2 7 8 Y2 W O G LO Y2 W O G L1 NOTE 10 Optional Electronic Air-Filter Optional Remote Unit Without Loop Pump SL1 Out SL1 In C NOTE 2 NOTE 9 7 SW4 Y R G R R R R R 3 Acc NO 2 2 Acc NC 1 1 Acc Com P3 NOTE 3 6 Not Used 5 3 2 4 C C SL1 In SL1 Out LED 1 2 3 4 5 6 7 8 1 2 3 4 5 2 Speed / 1 Speed Normal / Finish on 2nd (Note 12) No RPM / RPM Old EH & ECM / Normal (Note 8) Envision / E Series or Premier Field Selection Dips - #1 On, #6 On, #7 On Drain Drain pan overflow Lockout Water Flow FD thermistor(loop<15°F,well<30°F) Lockout High Press High Pressure Low Press/CA Low Pressure / Comfort Alert Air Flow ECM RPM < 100 rpm Lockout Status Microprocessor malfunction* DHW Limit HWL thermistor > 130°F DHW off DHW pump switch off *Green LED not flashing Normal Display Mode Inputs Outputs #1 Off, #6 On, #7 On #6 Off, #7 On #6 On, #7 Off Y1 Compressor Lo Drain pan overflow FD thermistor (loop <15°F, well<30 °F) Y2 Compressor Hi High Pressure O RV Low Pressure / Comfort Alert G FAN ECM RPM < 100 rpm W DHW Pump Not Used SL1 Loop Pump1 HWL thermistor> 130°F SL2 Loop Pump 2 -DHW pump switch off -- Current Fault Status #6 Off, #7Off Blower Lo Blower Med Blower Hi Aux Heat #1 Aux Heat #2 Aux Heat #3 Aux Heat #4 -- Outputs2 Black T T HP LP FD HWL Comfort Alert Status Description Module Has Power Y1 Present But Compressor Not Running Long Run Time System Pressure Trip Short Cycling Locked Rotor Open Circuit Open Start Circuit Open Run Circuit Welded Contactor Low Voltage Comfort Alert LED Flash Code Green Solid Red Solid Code 1 Code 2 Code 3 Code 4 Yellow Code 5 Code 6 Code 7 Code 8 Code 9 Black 7 14 Blue Blue 13 6 Pink Yellow 5 Pink Yellow 1 Not Used 3 8 12 Orange Not Used L NOTE 11 2 Orange Tan 10 9 4 P5 Diagnostic Modes L1 Thermistor CA CC CO CR1 CR2CR3 CR4 CS F1 and F2 FD HE HP ER1 to ER4 - Comfort Alert Compressor Contactor Condensate overflow sensor DHW pump relay Loop pump relay PSC Fan Speed Relay PSC Fan Power Relay Compressor Solenoid Fuses Freeze drotection sensor Heater element High pressure switch Aux heat stage relays Fuse Relay ContactsN.O., N.C. Ground Field wire lug Wire nut P 2 Pink 2 1 6 5 LP PB1, PB2 PS RV SW1 SW2 SW3 SW4 TS HWL SC SR - 3 G T Blue 9 11 Main Logic PCB Legend Pink Orange 10 Factory Low voltage wiring Factory Line voltage wiring Field low voltage wiring Field line voltage wiring Optional block DC Voltage PCB traces Internal junction Quick connect terminal Blue 3 Not Used 6 15 Light emitting diode - Green Low pressure switch Power blocks Power strip Reversing Valve coil DIP package 12 position DIP package 8 position DIP package 5 position Hot water pump enable switch Thermal limit switch Hot water limit sensor Start Contactor Start Relay Polarized connector Switch-Hot Water On/Off Switch- Low pressure Switch- High pressure Switch- Condensate overflow Capacitor w/ bleed resistor Relay coil Red Tan White 2 Not Used 12 4 Orange P10 1 Gray Brown 14 Gray Blue Blue 5 P12 Violet RV 8 Black NOTE 7 Test / Norm Loop / Well Fan / Comp Dehum / Norm No Htg3 / Htg3 Inputs/ Norm Outputs/ Norm Pulse L / Constant L P11 Yellow SW1 On 5 ECM Fan Motor 4 3 15 16 10 3 Violet 2 Black CO Transformer 1 Grn Yellow Not Used Blk/Wh 24V Red Blu 208V 240V Org Brn 4 Yel Blk Org Brn P4 2 3 C2 1 2 3 1 Grn 3 5 ECM Fan Motor 4 With optional ' EA' Series Auxiliary Electric Heat Typical schematic shown 7 P6 8 PS 3 1 2 Common Start Active C2 13 C R Red On Fused L1 NOTE 1 Not Used SW3 COM 240V L1 Brn(15) Gry/Wht(10) Blk/Wht(11) Pink NOTE 4 16 1 2 3 4 5 6 7 8 9 10 11 12 Blk(7) NC F1-10A 240V 240V L2 Org(14 ) T1 L1 11 On CR4 Premier 2 Microprocessor Logic Control (DC Voltage) COM NO T2 L2 Shut Down CR3 NC 240V L2 Tan (16) Tan SW2 COM NO Fused L2 Gry(9) Run Capacitor Black White ECM2 Air Flow Settings CR2 NO Fused L2 Yel(8) G CC 3 P4 NOTE 6 Pink(13) Pink DHW Pump Blu 1 Unit Power 208-230/60/1 1 1 COM Blu(17) 1 2 P2 3 6 5 4 3 1 C Y1 C R Y1 CC-GND CC CCHI CR1 NO 3A Fuse P1 R Thermostat CC Violet(3) Violet(2) Comfort C Alert Y2Y R Pump PB1 2 F1-10A 240V Blue RPM CS PWM + - IntelliStart On/Off Run Winding IntelliStart RPM grnd DC SOL Red 15 16 10 P11 2 3 4 P1 8 5 F1 6 N.O. P10 Com N.C. N.O. CR3- 1 8 1 2 3 4 5 6 7 8 9 10 11 12 2 C 1 Shut Down SW2 Off On 1 2 3 4 5 6 7 8 P2 C 3 Microprocessor 4 SL1 Out 5 SW3 Off On SL 1 IN 2 3 SL2 IN 6 1 2 3 4 5 SL 2 Out 7 P2 5 ACC NO 1 CR4- L1 L1 NO ER4 NO ER3 NO ER2 NO ER1 PB2 L3 3 P5 P6 EA Series PCB ACC ACC NC COM 2 1 2 3 4 5 6 7 16 8 8 1 9 2 10 3 11 4 12 5 13 6 14 7 P3 9 10 11 12 13 14 15 Com 6 1 F2 NOTE 5 L2 Gray N.O. F1 4 Blk Or L2 Brn Yel L4 4 Pink G Auxiliary Electric Heat Power 208-230/60/1 5 3 2 P9 1 Premier 2 Logic Board CR2- Loop Pump 7 Grn Logic Board - Physical Layout SW 1 Off On P12 R C Y1 Y2 W O G L 1 C C R R CC-GND CC CCLO CCHI CR1- DHW Pump N.O. Blu Violet PWM Comfort Alert 1 On/Off 240V - L1 RPM grnd Ext Pump 1/2 hp Total 208-230/60/1 Status LED PCB RPM 240V - L1 Red Fused L1 Black Fused L2 27 Fused L2 PB2 2 Fused L2 C Fused L2 S 240V - L2 R 240V - L2 Blue P8 Pink 4 C R L Y Y2 Pink Yel Blk Gray TS1 TS4 TS3 TS2 L2 L2 L2 Unit Power 208 -230/60/1 L1 Circuit Breakers L1 Aux Elect Power 208-230/60/1 L1 Breaker box furnished by installer Single Disconnect Power 208-230/60/1 CSA installed units only Local codes may require a single source of power supply HE4 HE3 HE2 HE1 97P774-51 2/23/09 Notes: 1 - Switch Blue and Red wires for 208V operation. 2 - Connection of remote unit that does not have a loop pump for slave operation. 3 - 24V Accessory relay (see SW2 -3 for description of operation) 4 - The blk/wh and gray/wh wires are removed when Aux Heat is installed. 5 - Buss lugs L1 and L2 can be removed and dual power wire sets connected directly to box lugs L1, L2, and L3, L4. 6 - DHW pump only in models with hot water generation option. 7 - Air Flow Configuration Example: SW1 configured for dip 1 as low, dip 3 as medium, and dip 5 as high Speed ECM2 fan 8 - SW3-4 should be in the OFF position when using ECM motor and 17P501A01 electric heat board and should be ON when using ECM2 with 17P514A01 electric heat board 9 - SW2-8 must be in the OFF position for pulsed “L” lockout signal and in the ON position for constant “L” lockout signal. 10 - When optional electronic air-filter is installed, power for the electronic air-filter is provided by P2-2 and 24 VAC. 11 - Comfort Alert fault output to Premier Control Board 12 - This Switch allows the unit to down stage with the t-stat when OFF and finish on second stage when ON. Finish second stage reduces stage changing in recip dual capacity compressors and should be ON for unzoned Dual Cap E-Series or Premier 2 speed units. ALERT TRIP DC Sol Data Port POWER Pink Yel Comfort Alert Physical Layout Yel Blk 3 Gray Gray Blk Yel Pink 2 1 P7 1 Gray Blk 2 Blk Gray 3 4 Yel Pink G ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL Wiring Schematics cont. Premier Control 208-230/60/1 with IntelliStart - ECM Motor 28 CC CO CP CP DA DF/FP DH ES HP HWL LP - Factory Low voltage wiring Factory Line voltage wiring Field low voltage wiring Field line voltage wiring Optional block DC Voltage PCB traces Field Zone Sensor Wiring Relay ContactsN.O., N.C. Compressor Solenoid 1 3 2 OS PB1, PB2 RCP RV SW1 SW2 SW3 SW4 TB TS FD - Occupied Switch Power blocks Rectified Solenoid Compressor Plug Reversing Valve coil DIP package 12 position DIP package 8 position DIP package 5 position Hot water pump enable switch Terminal Board Thermal limit switch Freeze Detection Sensor Closed Jumper Open Jumper Polarized connector PB2 3 1 2 NOTE 1 Blue (32) LP OS ES NOTE 9 DF/FP CP NOTE 6 29 Yellow (51) 46 J9 DI10 44 45 Black (5) Green (70) Orange (71) DI5 DI1 9VDC 56 55 Blk/Wht (29) Orange (30) DI2 DI3 54 53 Pink (25) Blue (27) DI4 DI6 51 52 50 Gray (26) Red (24) DI 3/4/5/6/ Com Violet (23) 49 DI7 48 Yellow (21) Black (22) DI8 47 Blue (72) DI9 DI11 24VAC Com PWM2 DI12 42 41 43 Gray/Wht (14) Gray (68) 40 J10 38 Orange/Wht (67) PWM1 PWM2 Com LED 5VDC 36 37 Orange (66) 39 AI1 + 33 35 Yellow/Red (53) Yellow (50) AI2 + 5VDC 32 34 Yellow/Wht (52) A13 A23 Compressor Contactor Condensate Overflow Sensor Compressor Proving Compressor Solenoid Discharge Air Temperature Sensor Dirty Filter or Fan Proving Dehumidification Switch or Humidistat Emergency Shutdown High Pressure Switch Hot water limit sensor Low Pressure Switch P Switch - Low pressure Switch - High pressure 28 30 Black (63) Blk/Red (64) 31 AI6 + 27 Gray (65) AI4 + 26 AI5 + 25 White (62) AI3 + 5VDC Brown (61) J2 J8 Wht/Blue (42) 1K 23 24 A21 Switch - Condensate overflow T T CO 11K A12 A22 Capacitor w/ bleed resistor NOTE 7 DA FD Brown (60) L2 Green/Yel (37) L3 A25 Relay coil Black (44) Orange/Wht (67) L1 A14 Quick connect terminal T Thermistor Temp Occ (TO) B 15 Orange (66) N A15 A24 A11 J7 Violet (15) Blue (10) Blue Yellow (50) Black (5) Yellow (35) Blk/Wht (36) Yellow (18) Johnson FX-10 A31 Rectified Compressor Solenoid Plug Black (RS) Room Sensor (RS) 7 Gray (65) PB3 A32 A35 Ground Black (AIC) AI Com (AIC) 14 Blue (72) Yellow (21) Red (56) Blue (55) Black (54) G 24VAC Com Field wire lug Black (SS) 4 10 L1 Unit Power 460/60/3 With Neutral A33 RCP L1 Black (Y2) Comp (Y2) Yellow (18) Green (70) Orange (71) L2 L3 CC T1 Black GROUND A34 Internal junction Black (Y1) Comp (Y1) Setpoint Shift (SS) Black (31) Black (O) Sensor Com (SC) 2 Black (G) 9 13 Black (X2) Violet (15) Brown (13) Black (34) Red (33) T2 C 24VAC Legend Zone Sensor Terminal 6 Zone Sensor Terminal 5 Zone Sensor Terminal 2 Zone Sensor Terminal 3 Zone Sensor Terminal 1 NOTE 3 Fan (G) Rev Valve (O) Acc 2 (X2) 5 Black (X1) NOTE 2 Acc 1 (X1) 1 12 Black (L) 6 Black (C) Black (R) Alarm (L) Green/Yel (38) 24V COM (C) 24VAC (R) NOTE 4 TB S Blue T3 Red R D01 D02 D03 1 2 3 4 5 6 7 8 9 11 10 D04 12 13 14 15 16 D05 D06 D07 18 D08 17 19 20 Black (34) D09 Brown (13) Black (F1) Black (F2) Black (F3) Black (F4) Black (F5) Black (F6) Black (F7) Black (F8) Black (F9) Black (F10) Black (F11) Black (F12) Black (F13) Black (F14) Black (F15) Black (F16) 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 Black (F17) 19 Black (F19) 20 A Black (F18) Black (F20) Red (33) Black (1) Yellow (J1) Violet (3) White (4) Black (5) Black (6) Orange (7) Yellow (J1) Yellow (J2) Blue (10) Gray (11) Yellow (12) Brown (13) Violet (15) Yellow (J2) Yellow (17) Yellow (18) Gray (19) Yellow (20) HP NOTE 5 Black Blue 460V RV CC Orange (40) NOTE 5 Black (34) Red (33) Transformer Violet (3) Black/Wht (43) 1 2 3 PB1 Yellow Blk/Wht Blue Blue CS NOTE 8 97P774-23 RCP Violet (28) Orange 2 1 C1 Grn/Yel (57) 1 Green Brown 3 4 5 ECM Fan Motor P11 12 15 P12 Yellow (50) 10 2/16/07 Violet (28) 3 R 1 – Disconnect for 15 degree freeze detection. 2 – Acc 1 output is cycled with the compressor. 3 – Acc 2 output is cycled with the fan. 4 – R, C, Y1, Y2, and G inputs are for use with a wall mounted thermostat . TO, SC, RS, AIC, and SS are for use with a TAXXJ02 zone sensor. 5 – Network controllable 24VAC output. 6 – Network controllable PWM output. 7 – Wires 51, 52, & 53 can be configured for a field installable humidity sensor or an A99 temperature sensor. 8 – Dual Capacity only. 9 – Network configurable input. G Compressor C2 WARNING: Neutral wire required. PWM Notes: ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL Wiring Schematics cont. FX10 Control 460/60/3 - ECM Motor ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL Envision Controls - Premier Shutdown Mode A 24VAC common signal to the “shutdown” input on the control board puts the unit into shutdown mode. Compressor, hot water pump and blower operation are suspended. Safety Controls The Envision control receives separate signals for a high pressure switch for safety, a low pressure switch to prevent loss of charge damage, and a low suction temperature thermistor for freeze sensing. Upon a continuous 30-second measurement of the fault (immediate for high pressure), compressor operation is suspended, the appropriate lockout LED begins flashing. (Refer to the “Fault Retry” section below). Standard Premier Microprocessor The Premier control system is a microprocessor-based printed circuit board conveniently located in the unit control box for accessibility. The microprocessor control is specifically designed for the Envision Series heat pumps and integrate single speed and dual capacity compressors, variable speed ECM blower motors and advanced features needed in geothermal applications. All variable speed ECM airflow selections are conveniently configured on the control via DIP switches. The microprocessor provides control of the entire unit as well as outputs for status modes, faults, and diagnostics. Removable low voltage thermostat terminal strips provide convenient field connections. LEDs are located on the front of the cabinet for quick inspection without removing any access panels. Testing The Envision control allows service personnel to shorten most timing delays for faster diagnostics. Fault Retry All faults (except for low RPM faults with the ECM blower motor) are retried twice before finally locking the unit out. An output signal is made available for a fault LED at the thermostat. The “fault retry” feature is designed to prevent nuisance service calls. Diagnostics The Envision control board allows all inputs and outputs to be displayed on the LEDs for fast and simple control board diagnosis. Startup The unit will not operate until all the inputs and safety controls are checked for normal conditions. At first powerup, a four minute delay is employed before the compressor is energized. Resistance Heat Control (208-230 Units) Component Sequencing Delays The electric heat control module contains the appropriate high-voltage control relays. Control signals energize the relays in the proper sequence, and the LED display board indicates which stages are energized. Components are sequenced and delayed for optimum space conditioning performance. Heating Operation Heat, 1st Stage (Y1) Accessory Relay An accessory relay on the control board allows for field connection of solenoid valves, electronic air cleaners, etc. The accessory relay has a normally open output and a normally closed output. The blower motor is started on low speed immediately (PSC ON), the loop pump is energized 5 seconds after the “Y1” input is received, and the compressor is energized on low capacity 10 seconds after the “Y1” input. The blower is switched to medium speed 15 seconds after “Y1” input (ECM only). Short Cycle Protection Heat, 2nd Stage (Y1,Y2) Single-Speed Units The control employs a minimum “off” time of four minutes to provide for short cycle protection of the compressor. Blower changes to high speed 15 seconds after the “Y2” input (ECM only). Condensate Overflow Protection Heat, 2nd Stage (Y1,Y2) Dual Capacity Units The Envision control board incorporates an impedance sensing liquid sensor at the top of the drain pan. Upon a continuous 30-second sensing of the condensate, compressor operation is suspended (see Fault Retry), and the condensate overflow lockout LED begins flashing. The second stage compressor will be activated 5 seconds after receiving a “Y2” input as long as the minimum first stage compressor run time of 1 minute has expired. The ECM blower changes from medium to high speed 15 seconds after the “Y2” input. 29 ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL Envision Controls - Premier cont. NOTE: Blower speed can change automatically only with an ECM Motor. Heat, 3rd Stage (Y1,Y2,W) Single-Speed Units The first stage of resistance heat is energized 10 seconds after “W” input, and with continuous 3rd stage demand, the additional stages of resistance heat engage sequentially every 5 minutes. ECM Airflow Selection DIP Switches (SW1) A 12-position DIP switch package on the Envision control allows the airflow levels to be set for low, medium and high speed. (Refer to Blower Performance Data - ECM Motor). Only three of the DIP switches can be in the “on” position. The first “on” switch (the lowest position number) determines the “low speed blower” setting. The second “on” switch determines the “medium speed blower” setting, and the third “on” switch determines the “high speed blower” setting. Heat, 3rd Stage (Y1,Y2,W) Dual Capacity Units The 1st stage of resistance heat is energized 10 seconds after “W” input, and with continuous 3rd stage demand, the additional stages of resistance heat engage sequentially every 5 minutes. Emergency Heat (W only) The blower is started on high speed, and the first stage of resistance heat is energized 10 seconds after the “W” input. Continuing demand will engage the additional stages of resistance heat sequentially every 2 minutes. Lockout Conditions During lockout mode, the appropriate unit and thermostat lockout LEDs will illuminate. The compressor, loop pump, hot water pump, and accessory outputs are de-energized. Unless the lockout is caused by an ECM low RPM fault, the blower will continue to run on low speed. If the thermostat calls for heating, emergency heat operation will occur. Cooling Operation In all cooling operations, the reversing valve directly tracks the “O” input. Thus, anytime the “O” input is present, the reversing valve will be energized. All lockout modes can be reset at the thermostat after turning the unit off, then on, which restores normal operation but keeps the unit lockout LED illuminated. Interruption of power to the unit will reset a lockout without a waiting period and clear all lockout LEDs. Cool, 1st Stage (Y1,O) The blower motor and hot water pump are started immediately, the loop pump(s) is energized 5 seconds after the “Y1” input is received. The compressor will be energized (on low capacity for Dual Capacity units) 10 seconds after the “Y1” input. The ECM blower will shift from low to medium speed 15 seconds after the “Y1” input (85% of medium speed if in dehumidification mode). High Pressure This lockout mode occurs when the normally closed safety switch is opened momentarily (set at 600 psi). Low Pressure Cool, 2nd Stage (Y1, Y2, O) Single Speed Units This lockout mode occurs when the normally closed low pressure switch is opened for 30 continuous seconds (set at 40 psi). The blower changes to high speed (85% of high speed if in dehumidification mode) 15 seconds after the “Y2” input (ECM only). Freeze Detection (Water Flow) Cool, 2nd Stage (Y1, Y2, O) Dual Capacity Units The second stage compressor will be activated 5 seconds after receiving a “Y2” input as long as the minimum first stage compressor run time of 1 minute has expired. The ECM blower changes to high speed 15 seconds after the “Y2” input. (85% of high speed if in dehumidification mode). This lockout mode occurs when the freeze thermistor temperature is at or below the selected freeze sensing point (well 30°F or loop 15°F) for 30 continuous seconds. Condensate Overflow Blower (G only) This lockout mode occurs when the condensate overflow level has been reached for 30 continuous seconds. The blower starts on low speed (PSC ON). Regardless of blower input “G” from thermostat, the blower will remain on low speed for 30 seconds at the end of each heating, cooling or emergency heat cycle. Blower RPM The control board monitors blower RPM to sense operation. This lockout mode occurs if the blower RPM falls below the low RPM limit (100 RPM) for 30 continuous seconds (ECM only). A DIP switch on the Envision control allows field selection of 15% reduced blower speeds for cooling in the dehumidification mode or medium and high blower speeds for cooling in the normal mode. 30 ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL Envision Controls - Premier cont. DIP Switch Settings Prior to powering unit, ensure that all DIP switches on SW2 and SW3 are set properly according to the tables below. FACTORY SETUP DIP SWITCHES (SW3) DIP SWITCH NUMBER DESCRIPTION OFF POSITION ON POSITION SW 3- 1 Dual Capacity/Single-Speed Configures the control for single-speed compressor operation or dual capacity operation. Dual Capacity Operation Single-Speed Operation SW 3- 2 Zoned/Finish on Second Stage This switch allows the unit to down stage with the thermostat when off and finish with second stage when on. Finish on second stage reduces stage changing in reciprocating dual capacity compressors. Normal - All Other Systems Finish on 2nd - Unzoned Dual Capacity E Series or Premier 2 Speed SW 3- 3 No RPM/RPM Configures the control to monitor the RPM output of an variable speed ECM blower motor. When using IntelliZone or a PSC blower motor, the control should be configured for “NO RPM” sensing. PSC Blower/RPM Monitoring Disabled ECM Blower/RPM Monitoring Enabled SW 3- 4 Electric heat and Variable Speed ECM Allows backward compatibility with older P Series. In the Off position this switch allows older electric heat board (17P501A01) and older ECM (square end) compatibility. On is for all newer EH board (17P514A01) and ECM (round end). Old EH and Old ECM Normal SW 3- 5 On dual capacity units this switch allows stage change: on the fly when off, and 1 minute delay when on. A delay is required on all reciprocating dual capacity units. Envision E Series or P Series FACTORY SETUP DIP SWITCHES (SW3) DIP SWITCH NUMBER DESCRIPTION OFF POSITION ON POSITION SW 2- 1 Service Test Mode On the control, allows field selection of “NORMAL” or “TEST” operational modes. Test mode accelerates most timing functions 16 times to allow faster troubleshooting. Test mode also allows viewing the “CURRENT” status of the fault inputs on the LED display. Test Mode Normal Speed Operation SW 2- 2 Freeze Detection Sensing This DIP switch allows field selection of low source water thermistor fault sensing for well water (30°F) or antifreeze-protected (15°F) earth loops. Loop Water Freeze Detection 15° F Well Water Freeze Detection 30° F SW 2- 3 Accessory Relay Allows field selection of the accessory relay to operate with the compressor or blower. Acc Relay Tracks Blower Acc Relay Tracks Compressor SW 2- 4 Blower Speed Control Allows field selection of reduced blower speed (85% of selected medium and high speed – variable speed ECM only) for cooling in the dehumidification mode. Dehumidification Blower Speeds Normal Blower Speeds SW 2- 5 Auxiliary Off Disables 3rd-stage Heating. Full emergency heat would still be available if needed. Disable Heating Stage 3 Enable Heating Stage 3 SW 2- 6 Diagnostics Inputs Allows viewing the inputs from the thermostat to the control board such as Y1, Y2, O, G, W, SL1-In on the LED display. Diagnostic Inputs Viewed at LEDs Normal Display Viewed at LEDs SW 2- 7 Diagnostics Outputs Allows viewing the outputs from the control board such as compressor, reversing valve, blower, hot water pump, and loop pump on the LED display. Diagnostic Outputs Viewed at LEDs Normal Display Viewed at LEDs SW 2- 8 Thermostat Selection Configures the control for a pulsed lockout signal (ComforTalk and FaultFlash thermostats) or continuous 5 VAC lockout signal. Pulsed “L” signal Continuous “L” signal 31 ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL Envision Controls - Premier cont. Operation Logic Data Table OPERATION LOGIC STG1 HEATING STG2 STG3 EMERG COOLING STG1 STG2 Blower ON SL1 - IN ON SINGLE SPEED UNITS Compressor ECM Normal ECM Dehumidify On On On Off On On - - Med Med High High High High High High Med 85% Med High 85% High Low Low - PSC On On On On On On On Rev Valve Loop Pump Off Off Off Off On On - - On On On Off On On - On Aux Heater Off On Off On Staged On Staged Off Off On Off On - - Off Y1 Off Off Off Y1, Y2, W On W Off Y1, Y2 Y1, O Y1, Y2, O Off G - On Off Med Med Off On Off On Off Off Y1 Off On High High Off On Off On On Off Y1, Y2 Off On High High Off On Staged On On Off Y1, Y2, W Off Off High High Off Off Staged Off Off On W On Off Med 85% Med On On Off On Off Off Y1, O Off On High 85% High On On Off On On Off Y1, Y2, O Low Low G On - Secondary 1- Out Emerg LED T-Stat Signal DUAL CAPACITY UNITS Compressor-Lo Compressor-Hi ECM Normal ECM Dehumidify Rev Valve Loop Pumps Aux Heater Secondary 1- Out Secondary 2- Out Emerg LED T-Stat Signal Thermostat Displays ComforTalk Fault Flash When using a TP32U03, 04 or 05 thermostat and SW2-8 is in the pulsing “L” position, ComforTalk will enable the user to view the thermostat and determine the fault. The thermostat can be configured to show either lockout text or lockout codes. When using a TA32W01 or TP32W02 thermostat and SW28 is in the pulsing “L” position, FaultFlash will enable a user to view the thermostat and count the fault indicator flashes to determine the lockout condition the unit is experiencing. The following tables show the codes that will be displayed on the different ComforTalk and FaultFlash thermostats. FaultFlash Thermostats ComforTalk Thermostats TA32W01 and TP32W02 Thermostats Thermostat Display Lockout Code 2 Flashes 3 Flashes 4 Flashes 5 Flashes 6 Flashes 7 Flashes 8 Flashes 9 Flashes 10 Flashes TP32U03, TP32U04 and TP32U05 Thermostats Thermostat Display Lockout Code Lockout Description High Pressure Fault Low Pressure Fault Not Applicable Water Flow Fault Not Applicable Condensate Fault Voltage out of Range RPM Fault Not Available "High Pressure" or "E2" "Low Pressure" or "E3" "E4" "Water Flow" or "E5" "E6" "Condensate" or "E7" "Voltage Range" or "E8" "RPM" or "E9" "Comfort Alert" or "E10" Lockout Description High Pressure Fault Low Pressure Fault Not Applicable Water Flow Fault Not Applicable Condensate Fault Voltage out of Range RPM Fault Not Avaialble These thermostats can be configured to display the lockout condition "text" or error number. * A slow flash of 1 second on and off means the heat pump microprocessor SW2-1 is configured for "Test Mode" or thermostat is miswired. 32 ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL Troubleshooting 4) Standard Microprocessor Controls To check the unit control board for proper operation: 1) Disconnect thermostat wires at the control board. 2) Jumper the desired test input (Y1, Y2, W, O or G) to the R terminal to simulate a thermostat signal. 3) If control functions properly: • Check for thermostat and field control wiring (use the diagnostic inputs mode). If control responds improperly: • Ensure that component being controlled is functioning (compressor, blower, reversing valve, etc.). • Ensure that wiring from control to the component is functioning (refer to the LED Definition table below and use the diagnostic outputs mode). • If steps above check properly, replace unit control. LED Definitions and Diagnostics Standard Microprocessor DIAGNOSTIC MODES LED NORMAL DISPLAY MODE CURRENT FAULT STATUS INPUTS OUTPUTS 1 OUTPUTS 2 Field Selection DIPS SW2- 1 On SW2- 1 Off SW2- 1 NA SW2- 6 On SW2- 6 On SW2- 6 Off SW2- 7 On SW2- 7 On SW2- 7 On SW2- 1 NA SW2- 1 NA SW2- 6 On SW2- 6 Off SW2- 7 Off SW2- 7 Off Drain Drain Pan Overflow Lockout Drain Pan Overflow Y1 Compressor (On or Low) Blower Low Water Flow Freeze Detection Thermistor (Loop <15°F, Well<30°F) Lockout Freeze Detection Thermistor (Loop <15°F, Well<30°F) Y2 Compressor (On or High) Blower Medium High Pressure High Pressure >600 psi Lockout High Pressure >600 O Reversing Valve Blower High Low Pressure Low Pressure <40 psi Lockout Low Pressure <40 G Blower Aux Heat 1 Airflow ECM RPM <100 RPM ECM RPM <100 RPM W DHW Pump Aux Heat 2 Status Microprocessor Malfunction Not Used SL1 Loop Pump(s) Aux Heat 3 DHW Limit HWL Thermistor >130° HWL Thermistor >130°F Not Used – Aux Heat 4 DHW Off DHW Pump Switch Off DHW Pump Switch Off – – – Refrigerant Systems numbers calculated. If superheat and subcooling are outside recommended ranges, an adjustment to the refrigerant charge may be necessary. To maintain sealed circuit integrity, do not install service gauges unless unit operation appears abnormal. Compare the change in temperature on the air side as well as the water side to the Unit Operating Parameters tables. If the unit’s performance is not within the ranges listed, and the airflow and water flow are known to be correct, gauges should then be installed and superheat and subcooling NOTE: Refrigerant tests must be made with hot water generator turned “OFF”. Verify that air and water flow rates are at proper levels before servicing the refrigerant circuit. 33 ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL Envision Controls - FX10 (optional) FX10 Advanced Control Overview The Johnson Controls FX10 board is specifically designed for commercial heat pumps and provides control of the entire unit as well as input ports for Open N2, LonTalk, BACnet (MS/TP @ 19,200 Baud rate) communication protocols as well as an input port for a user interface. The user interface is an accessory item that can be used to aid in diagnostics and unit setup. A 16-pin low voltage terminal board provides terminals for common field connections. The FX10 Control provides: • Operational sequencing • High and low-pressure switch monitoring • General lockout • Freeze Detection • Condensate overflow sensing • Lockout mode control • Emergency shutdown mode • Random start and short cycle protection Main FX 10 Board Optional Plug-in Communication Modules (compatible with standard BAS protocols) Short Cycle Protection • Open N2 • LonTalk • BACnet (MS/TP @ 19,200 Baud rate) Allows a minimum compressor “off” time of four minutes and a minimum “on” time of two minutes. Display Requires DLI Card/Kit. Up to 2 displays, either 1 local and 1 remote, or 2 remote. (A 2-display configuration requires identical displays.) Local display can be up to 3 meters from the controller, power supply, and data communication. Remote display can be up to 300 meters from the controller. Remote display must be independently powered with data communication done via 3 pole shielded cable. Random Start A delay of 1 to 120 seconds is generated after each powerup to prevent simultaneous startup of all units within a building after the release from an unoccupied cycle or power loss. Emergency Shutdown Control Timing and Fault Recognition Delays A field-applied dry contact can be used to place the control into emergency shutdown mode. During this mode, all outputs on the board are disabled. Lead compressor “ON” delay ..........................................90 seconds (not applicable for single compressor models) Minimum compressor “ON” time ...................................... 2 minutes (except for fault condition) Short cycle delay ..................................................................... 5 minutes Random start delay .......................................................0-120 seconds High pressure fault ................................................................. <1 second Low pressure fault ...............................................................30 seconds Freeze Detection fault........................................................30 seconds Condensate overflow fault ...............................................30 seconds Low pressure fault bypass ................................................... 2 minutes Freeze detection fault bypass ............................................ 2 minutes Freeze Detection Field selectable for 15° or 30°F (-9° or -1°C) Installation Options • Standalone controlled by standard room thermostat • Standalone with a Zone Temperature Sensor (must have user interface to change set points beyond the allowed +/- 5°F) • Integrated into BAS by adding communication module Accessory Outputs Quantity 2. One cycled with blower, other with compressor. User Interface 4 x 20 backlit LCD. 34 ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL Envision Controls - FX10 cont. An optional Medium User Interface (MUI) for control setup and advanced diagnostics is available with some mounting kits, MUIK3 - Panel mount version and the MUIK4 - Wall mount version. Optional FX10 Microprocessor and BAS S Interface Zone Sensors There are two options for zone sensors that can be used with the FX10 control. Both sensors use a Johnson controls A99 positive temperature coefficient type sensor. The TAXXJ02 has a set point adjustment now which will give the end user a +/- 5°F adjustment from the set point as well as a push button that can be used for temporary occupancy. The control leaves the factory set to operate with a TAXXJ02 sensor and can be changed to read the TAXXA04 sensor through a building automation system or with a user interface. The FX10 is a microprocessor based control that not only monitors and controls the heat pump but also can communicate any of this information back to the building automation system (BAS). This means that not only does the control monitor the heat pump at the unit you can also monitor and control many the features over the BAS. This clearly puts the FX10 in a class of its own. Standard Features • • • • • • • • • • The control will enumerate all fault conditions (HP, LP, CO, LOC, and Freeze Detection) over a BAS as well as display them on a medium user interface (MUI). HP, LP, CO and Freeze Detection faults can all be reset over a BAS. A Loss Of Charge fault can not be reset or bypassed until the problem has been corrected. A MUI is invaluable as a service tool for the building service team. Anti Short Cycle High Pressure Protection Low Pressure Protection Freeze Detection Loss Of Charge Detection Random Start Display for diagnostics Reset Lockout at disconnect or through BAS 2 Accessory outputs Optional BAS add-on controls DDC Operation and Connection The unit can be commanded to run by a typical heat pump thermostat or run based on heating and cooling set points supplied by a BAS. The control board is wired with quick connect harnesses for easy field change out of a bad control board. All ECM variable blower speed settings can be changed over a BAS or with a MUI. The control has an input programmed to enable field installed emergency heat in the event that the compressor is locked out. This input can also be commanded on from a BAS as needed. An alarm history can be viewed through the MUI and will be held in memory until the unit is power cycled. Relative humidity can be read by a 0-5VDC humidity sensor that is displayed over the network. If you are using an ECM blower motor the control can enable dehumidification mode based on a set point in the control. The dehumidification set point itself can also be changed over a BAS or with a MUI. Dehumidification mode can also be enabled by the BAS. Because the FX10 is not factory configured to read CO2 levels, contact the factory for application assistance. Other optional network protocol boards that can be added to the FX10 are: • Johnson Control N2 • LonWorks • BACnet - MS/TP @ 19,200 Baud rate - Limit devices to 30 on a single trunk line. Control and Safety Feature Details Emergency Shutdown The emergency shutdown mode can be activated by a command from a facility management system or a closed contact on BI-2. The default state for the emergency shutdown data point is off. When the emergency shutdown mode is activated, all outputs will be turned off immediately and will remain off until the emergency shutdown mode is de-activated. The first time the compressor starts after the emergency shutdown mode has been de-activated, there will be a random start delay present. The FX10 control has unused analog and digital inputs for field installed items such as air temperature, water temperature, CO2 or current status switches. The control has unused binary and PWM outputs that can be commanded over the BAS for field use. 35 ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL Envision Controls - FX10 cont. Lockout Mode Low Pressure (BI-3) Lockout mode can be activated by any of the following fault signals: refrigerant system high pressure, refrigerant system low pressure, freeze detection, and condensate overflow. When any valid fault signal remains continuously active for the length of its recognition delay, the controller will go into fault retry mode, which will turn off the compressor. After the Compressor short cycle delay, the compressor will attempt to operate once again. If three consecutive faults occur in 60 minutes during a single heating or cooling demand, the unit will go into lockout mode, turning off the compressor, enabling the alarm output, and setting the blower back to low speed operation until the controller is reset. If the control faults due to the low pressure input (BI-3) being open during the pre-compressor startup check, the control will go into lockout mode immediately, disabling the compressor from starting and enabling the alarm output (BO-6). The lockout condition can be reset by powering down the controller, by a command from the BAS, or by the holding the ESC and Return keys on the MUI for 5 seconds. The low-pressure switch shall be a normally closed (NC) switch that monitors the systems refrigerant pressure. The input shall be checked 15 seconds before compressor start up to be sure the pressure switch is closed and then ignored for the first 2 minutes after the compressor output (BO-2) is enabled. If the switch is open continuously for (30) seconds during compressor operation the compressor output (BO-2) will be disabled. The compressor will not restart until the compressor short cycle time delay has been satisfied. Condensate Overflow The condensate overflow sensing circuit will monitor the condensate level as a resistance input to AI-3. If the condensate water level rises resulting in the input resistance rising above the set point for the recognition delay period, the condition will be recognized as a fault. The condensate will be subjected to a (30) second lockout delay which requires that the fault be sensed for a continuous (30) seconds before suspending unit operation. Alarm Output (BO-6) The alarm output will be enabled when the control is in the lockout mode and will be disabled when the lockout is reset. Test Mode Raising the zone temperature input (AI-1) reading to 180–220°F or by holding the ESC and down arrow keys on the MUI for 5 seconds will put the control into test mode. In test mode the random start delay and the compressor fixed on delay time will both be shortened to 5 seconds and the reversing valve will be allowed to cycle with out shutting down the compressor. If an MUI is connected to the control LED 8 will flash and the words “Test Mode Enabled” will be shown on the LCD display when the control is in test mode. Test mode will be disabled after a power cycle, 30 minute timeout, or by holding the ESC and Up arrow keys on the MUI. Freeze Detection (AI-5) The freeze detection sensor will monitor the liquid refrigerant temperature entering the water coil in the heating mode. If the temperature drops below the freeze detection trip point for the recognition delay period, the condition will be recognized as a fault. The freeze detection trip point will be factory set for 30°F and will be field selectable for 15°F by removing a jumper wire on BI-5. The freeze detection fault condition will be bypassed 2 minutes at normal compressor startup, to allow the refrigeration circuit to stabilize. If the freeze detection sensor becomes unreliable at any time compressor operation will immediately be suspended until the problem is corrected. This should be displayed as an alarm on the BAS and the MUI. This alarm will be reported a “Water Low Temp Limit” fault. Sequence of Operation Power Fail Restart When the controller is first powered up, the outputs will be disabled for a random start delay. The delay is provided to prevent simultaneous starting of multiple heat pumps. Once the timer expires, the controller will operate normally. High Pressure (BI-11) The high-pressure switch shall be a normally closed (NC) switch that monitors the systems refrigerant pressure. If the input senses the high-pressure switch is open it must disable the compressor output immediately and count the fault. The compressor minimum on time does not apply if the highpressure switch opens. The compressor will not restart until the compressor short cycle time delay has been satisfied. 36 ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL Envision Controls - FX10 cont. medium speed and will operate in high speed when the compressor is operating at full capacity. Random Start Delay This delay will be used after every power failure, as well as the first time the compressor is started after the control exits the unoccupied mode or the emergency shutdown mode. The delay should not be less than 1 second and not longer than 120 seconds. If the control is in test mode the random start delay will be shortened to 5 seconds. Thermostat Control Mode In thermostat mode the compressor will be cycled based on Y1 and Y2 calls from a room thermostat. When the control receives a Y1 command (BI-7) from the thermostat the low capacity compressor output (BO2) will be enabled and the ECM blower will operate in medium speed. When the control receives a Y2 command (BI-8) from the thermostat the full capacity compressor output will be enabled and the ECM blower will operate in high speed. During the heating cycle the reversing valve will be commanded into the off position. Compressor Fixed On Delay Time The Compressor Fixed On Delay Time will ensure that the compressor output (B02) is not enabled for (90) seconds after the control receives a call to start the compressor. This delay is adjustable from 30 – 300 seconds over a BAS or a MUI. If the control is in test mode the Compressor Fixed On Delay Timer will be shortened to 5 seconds. Cooling Cycle On a call for cooling, the blower enable output and accessory output 2 will turn on immediately after the random start delay timer has been satisfied. If the compressor short cycle time delay has been satisfied, the compressor will turn on after the blower enable and accessory output 2 are on and the fixed compressor start delay timers have been satisfied. Compressor Minimum On Delay The compressor minimum on delay will ensure that the compressor output is enabled for a minimum of (2) minute each time the compressor output is enabled. This will apply in every instance except in the event the high pressure switch is tripped or emergency shutdown then the compressor output will be disable immediately. Set Point Control Mode In set point control mode the reversing valve output will be enabled. As the temperature falls below the cooling set point and begins to operate in the cooling proportional band, the low capacity compressor output (BO-2) will be enabled. A PI loop in the programming of the control will determine when the full capacity compressor output (BO-4) is to be enabled. The compressor must be operating in low capacity for a minimum of 30 seconds before the full capacity compressor output can be enabled. During low capacity compressor operation the ECM blower will operate in medium speed and will operate in high speed when the compressor is operating at full capacity. Compressor Short Cycle Delay Time The compressor short cycle time delay will ensure that the compressor output will not be enabled for a minimum of (5) minutes after it is disabled. This allows for the system refrigerant pressures to equalize after the compressor is disabled. Heating Cycle On a call for heating, the blower enable output and accessory output 2 will turn on immediately after the random start delay timer has been satisfied. If the compressor short cycle time delay has been satisfied, the compressor will turn on after the blower enable and accessory output 2 are on and the fixed compressor start delay timers have been satisfied. Thermostat Control Mode In thermostat mode the compressor will be cycled based on Y1 and Y2 calls from a room thermostat. When the control receives a Y1 command (BI-7) from the thermostat the low capacity compressor output (BO2) will be enabled and the ECM blower will operate in medium speed. When the control receives a Y2 command (BI-8) from the thermostat the full capacity compressor output will be enabled and the ECM blower will operate in high speed. During the cooling cycle the reversing valve will be commanded into the “ON” position. Auxiliary heat output can be controlled over the BAS. Set Point Control Mode In set point control mode the reversing valve output will be disabled. As the temperature drops below the heating set point and begins to operate in the heating proportional band, the low capacity compressor output (BO-2) will be enabled. A PI loop in the programming of the control will determine when the full capacity compressor output (BO-4) is to be enabled. The compressor must be operating in low capacity for a minimum of 30 seconds before the full capacity compressor output can be enabled. During low capacity compressor operation the ECM blower will operate in 37 ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL Envision Controls - FX10 cont. Variable Speed ECM Blower Operation Inputs and Outputs Configuration Blower speeds will be selected through the user interface or the facility management system. There will be a total of 12 speeds selectable with only three being selected at any one time. The lowest numbered speed selection set to ON will select the low-speed blower setting, the middle selection set to ON will select the medium-speed blower setting and the highest selection set to ON will select the high-speed blower setting. If all selections are set to OFF the software shall select speed setting 10 for low-speed, 11 for medium-speed, and will select speed setting 12 for high speed. If only one selection is set to ON, that selection will set the low-speed blower setting, the medium-speed setting will be 11, and the high-speed setting will be speed 12. The maximum low-speed setting will be speed 10 and the minimum high-speed setting will be speed 3. In addition there is a low limit setting in the software to prevent the ECM blower speed from being set below acceptable limits for each unit size. Field Selectable Options Freeze Detection Set Point (BI-5) The freeze detection set point input allows you to adjust the freeze detection set point (AI-5). When the jumper is installed on BI-5 (Wire #24) the freeze detection set point is factory set for 30°F. When the jumper on BI-5 (Wire #24) is removed the freeze detection set point will be 15°F. Accessory Outputs (BO-7 and BO-8) Accessory Output 1 will be energized 90 seconds prior to the compressor output being energized. Accessory Output 2 will be energized with the blower output (BO-1). When the corresponding compressor output is turned off the accessory output will be deactivated immediately. These outputs are selectable for normally open or normally closed operation through the Medium User interface or through the Building Automation System. SINGLE and DUAL STAGE WATER-TO-AIR ECM Blower air flow “Soft Switch Settings” A set of 12 “soft switches” accessible through the user interface or building automation system are used to select the three blower speed settings for the ECM blower motor. The 12 soft switches work in exactly the same way as the hardware switches used on the Premier control (Refer to Blower Performance Data - ECM Motor for proper settings). No more than three soft switches may be set to the “ON” position. The first “ON” switch (the lowest number switch) determines the “low speed blower” setting. The second determines the “medium speed blower” setting, and the third determines the “high speed blower” setting. Emergency Heat/Network Enabled Output (BO5) This output is set from the factory to enable/disable emergency heat. If a problem occurs with the unit resulting in the compressor being locked out in heating mode, the control will automatically enable this output to turn on field installed electric heat. This output is interlocked with the blower proving input BI-6 (Blower proving sensors must be field supplied and installed). BI-6 must be connected to PB2 position 3 (see unit schematic) in the field if no blower proving sensor is desired. There is a configurable parameter available through a BAS network that must be enabled if this output is to be commanded over the BAS network. Input Name Zone Temp 1 Relative Humidity Input Condensate Level Universal Temp Input Water Coil Low Temperature Limit Warm/Cool Adjust and Temp Occ Input AI 1 AI 2 AI 3 AI 4 AI 5 AI 6 Occupied Emergency Shutdown Stage 1 Low Pressure Network Viewable Input 1 Water Coil Low Temp Limit Set Point Network Viewable Input 2 Thermostat Y1 Thermostat Y2 Thermostat O Thermostat G Stage 1 High Pressure Compressor Proving XP10 Expansion Card Input Name Unused Unused Unused Unused BI 1 BI 2 BI 3 BI 4 BI 5 BI 6 BI 7 BI 8 BI 9 B10 BI11 BI12 Input AI 1 AI 2 AI 3 AI 4 Output Name Fan Enable Comp – Low Capacity Reversing Valve Comp – Full Capacity Network Output/EH Output Alarm Accessory 1 Output Accessory 2 Output Network Controlled Output Output BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 B09 Variable Speed ECM Blower Network Controlled Output PWM1 PWM2 Output Name Unused Unused Unused Unused Output BO 1 BO 2 BO 3 BO 4 Control Accessories Zone Sensors • TAXXJ02 Room Command Module • TAXXA04 LCD Room Command Module • A99 Sensor MUI Alarm History Reporting If a fault occurs the fault will be recorded in history for display on the medium user interface in the History Menu. Each fault type will be displayed in the history menu with a number between 0 and 3. A reading of 3+ will mean that fault has occurred more than three times in the past. The history menu can be cleared with a power cycle only. Alarm date and time are not included in the history. MUI (LCD User interface) for diagnostics and commissioning. • MUIK3 - Panel Mount, Portable • MUIK4 - Wall Mount 38 ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL Envision Controls - FX10 cont. FX10 User Interface (MUI) Physical Layout Alarm LED Power LED Up Arrow Right Arrow Escape (ESC) Button LED 1 Return Button LED 4 Left Arrow LED 8 Down Arrow Alarm LED - Indicates a Lock-Out or a bad Freeze Sensor LED 3 - On shows Fan running Power LED - Shows FX processor is operational LED 4 - On shows Reversing Valve in cool LED 1 - Flashing shows Compressor 1 running LED 8 - Flashing shows unit in ‘Test’ Mode LED 2 - Flashing shows Full Capacity Compressor running MUI Menu Navigation for Single Compressor - Envision Water-to-Air Welcome Info Status Info Temps Outputs Settings Maint Outputs Temps Status Alarms Alm-History Settings WFI Run Mode Auto Zone Temp 77.2 ºF nvoFanStatus ON Unit of Measure Envision Series Eff Occup’y Occ Dis Air Temp 51.0 ºF CmpCmd Status OFF Occ Clg Setpt 73.9 ºF PROFXENV-XX Y1 Input OFF Eff Clg Setpt 70.0°F Cmp Capacity OFF Occ Htg Setpt 69.9 ºF 3/8/07 Y2 Input OFF Eff Htg Setpt 66.0°F Rev Valve Heat Unocc Clg 84.0 ºF G Input OFF Water Coil 77.8°F X1 Output OFF Unocc Htg 60.0 ºF O Input OFF Low WC Limit 30.0°F X2 Output OFF DeHumSetpt 0% Occ Input Occ Humidity 56.7 %RH PWMOut 98% SensorSelect TAXXJ02 Temp Occ Inp OFF WarmCool AI 14.6 BO5 OFF Condensate NML WarmCoolAdj 0.2 BO9 OFF Emg Input Run AO2 Output 0% Lo Press ON Hi Press ON Rndm Tmr 0 BI-4 Input OFF 39 F ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL Envision Controls - FX10 cont. MUI Menu Navigation for Single Compressor - Envision Water-to-Air ECM Maintenance MinClgSetpt 60.0 ºF SW1 OFF MaxHtgSetpt 89.9 ºF SW2 OFF W Coil LoLim1 30.0 ºF SW3 ON W Coil LoLim2 15.0 ºF SW4 OFF TmpOccTime 120 min SW5 OFF SW6 OFF Rev Vlv Default Heating Press right arrow key one time from Maintenance Menu BO5 Mode Network SW7 ON CompStrtDly 90 sec SW8 OFF SpaceT Offset -1 ºF SW9 OFF DehumEnaDis Dis SW10 ON Acc1 Action On Comp SW11 OFF Acc2 Action On Fan SW12 OFF No more than three speeds should be “ON” at one time Alm-History Alarms ALARM SUMMARY ^/High Pressure Alarm #Events Condensate 0 Hi Pressure 0 Low Pressure 0 Low Temp 0 Bad Sensor 0 NOTE: This FX10 application implements an alarm history which is reset only by cycling power . This history shows on the Alm-History page. Any alarm showing 4+ events has occurred more than 4 times. Alarm lock-outs are reset by cycling power, by pressing the “ESC” and Return keys simultaneously for a minimum of 15 seconds, or by commanding the nviAlarmReset over the BAS network. Test mode is enabled by holding the ‘Esc’ and Down Arrow simultaneously for a minimum of 15 seconds and releasing. Test mode times out after 30 minutes, and may also be ended by pressing ‘ESC’ and Up Arrow simultaneously and releasing . Test Mode bypasses the On Delay (90 sec) and Random Start timers for quicker troubleshooting. It also allows cycling the reversing valve without compressor shutdown. 40 ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL Unit Startup 5. Before Powering Unit, Check The Following: NOTE: Remove and discard the two compressor hold down shipping bolts located at the front and rear of the compressor mounting bracket. The bolts can then be discarded. 6. • • • • • • • • • • • • • • • • • High voltage is correct and matches nameplate. Fuses, breakers and wire size correct. Low voltage wiring complete. Piping completed and water system cleaned and flushed. Air is purged from closed loop system. Isolation valves are open, water control valves or loop pumps wired. Condensate line open and correctly pitched. Transformer switched to 208V if applicable. Black/white and gray/white wires in unit control box have been removed if auxiliary heat has been installed. Dip switches are set correctly. DHW pump switch is “OFF” unless piping is completed and air has been purged. Blower rotates freely. Blower speed correct (dip switch is set correctly). Air filter/cleaner is clean and in position. Service/access panels are in place. Return air temperature is between 50-80ºF heating and 60-95ºF cooling. Check air coil cleanliness to insure optimum performance. Clean as needed according to maintenance guidelines. To obtain maximum performance the air coil should be cleaned before startup. A 10% solution of dishwasher detergent and water is recommended for both sides of coil, a thorough water rinse should follow. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. Startup Steps 17. NOTE: Complete the Equipment Start-Up/Commissioning Check Sheet during this procedure. Refer to thermostat operating instructions and complete the startup procedure. 1. 2. 3. 4. 18. Initiate a control signal to energize the blower motor. Check blower operation. Initiate a control signal to place the unit in the cooling mode. Cooling setpoint must be set below room temperature. First stage cooling will energize after a time delay. Check for correct rotation of scroll compressors in 3 phase applications Incorrect rotation will cause low refrigerant pressures and possibly unusual noise. Switch any two power leads at the compressor or contactor to reverse rotation. Be sure that the compressor and water control valve or loop pump(s) are activated. Verify that the water flow rate is correct by measuring the pressure drop through the heat exchanger using the P/T plugs and comparing to unit capacity data in specification catalog. Check the temperature of both the supply and discharge water (Refer to Unit Operating Parameters tables). Check for an air temperature drop of 15°F to 25°F across the air coil, depending on the blower speed and entering water temperature. Decrease the cooling set point several degrees and verify high-speed blower operation (ECM only). Adjust the cooling setpoint above the room temperature and verify that the compressor and water valve or loop pumpsdeactivate. 1Initiate a control signal to place the unit in the heating mode. Heating set point must be set above room temperature. First stage heating will energize after a time delay. Check the temperature of both the supply and discharge water (Refer to Unit Operating Parameters tables). Check for an air temperature rise of 20°F to 35°F across the air coil, depending on the blower speed and entering water temperature. If auxiliary electric heaters are installed, increase the heating setpoint until the electric heat banks are sequenced on. All stages of the auxiliary heater should be sequenced on when the thermostat is in the Emergency Heat mode. Check amperage of each element. Adjust the heating setpoint below room temperature and verify that the compressor and water valve or loop pumps deactivate. During all testing, check for excessive vibration, noise or water leaks. Correct or repair as required. Set system to desired normal operating mode and set temperature to maintain desired comfort level. Instruct the owner/operator in the proper operation of the thermostat and system maintenance. NOTE: Be certain to fill out and forward all warranty registration papers. 41 ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL Operating Limits Cooling (°F) (°C) Operating Limits Air Limits Min. Ambient Air 45 Rated Ambient Air 80 Max. Ambient Air 100 Min. Entering Air 50 Rated Entering Air db/wb 80.6/66.2 Max. Entering Air db/wb 110/83 Water Limits Min. Entering Water 30 Normal Entering Water 50-110 Max. Entering Water 120 NOTE: Minimum/maximum limits are only for start-up conditions, and are meant for bringing the space up to occupancy temperature. Units are not designed to operate at the minimum/maximum conditions on a regular basis. The operating limits are dependant upon three primary factors: 1) water temperature, 2) return air temperature, and 3) ambient temperature. When any of the factors are at the minimum or maximum levels, the other two factors must be at the normal level for proper and reliable unit operation. Heating (°F) (°C) 7.2 26.7 37.8 10.0 27/19 43/28.3 45 70 85 40 68 80 7.2 21.1 29.4 4.4 20.0 26.7 -1.1 10-43.3 48.9 20 30-70 90 -6.7 -1.1 32.2 Operating Parameters Single Speed Models Cooling -- No Hot Water Generation Entering Water Temp °F Water Flow gpm/ton 1.5 Suction Pressure psig Discharge Pressure psig Superheat Subcooling Water Temp Rise °F Air Temp Drop °F DB 115 - 125 150 - 170 20 - 35 10 - 17 17 - 22 17 - 23 30 3.0 105 - 120 130 - 145 20 - 35 10 - 17 8 - 10 17 - 23 1.5 130 - 140 215 - 235 12 - 20 8 - 14 16 - 22 17 - 23 50 3.0 128 - 138 190 - 210 12 - 20 8 - 14 8 - 12 17 - 23 1.5 138 - 148 280 - 310 10 - 16 10 - 16 15 - 21 17 - 23 3.0 136 - 146 250 - 280 10 - 16 8 - 14 7 - 13 17 - 23 1.5 145 - 155 350 - 380 9 - 14 10 - 16 14 - 20 17 - 23 70 90 3.0 143 - 153 320 - 350 9 - 14 8 - 14 6 - 10 17 - 23 1.5 145 - 155 420 - 450 9 - 14 10 - 16 14 - 20 17 - 23 3.0 143 - 153 405 - 435 9 - 14 8 - 14 6 - 10 17 - 23 Suction Pressure psig Discharge Pressure psig Subcooling Water Temp Drop °F Air Temp Rise °F DB 1.5 73 - 85 270 - 305 8 - 14 3 - 10 6 - 10 15 - 21 3.0 77 - 90 280 - 315 8 - 14 3 - 10 4-8 17 - 23 110 Heating - No Hot Water Generation Entering Water Temp °F Water Flow gpm/ton Superheat 30 1.5 97 - 110 290 - 325 10 - 16 3 - 10 9 - 13 22 - 28 3.0 102 - 115 300 - 335 10 - 16 3 - 10 7 - 11 24 - 30 50 1.5 130 - 145 320 - 355 13 - 19 3 - 10 10 - 14 30 - 36 3.0 135 - 150 325 - 360 13 - 19 3 - 10 8 - 12 32 - 38 1.5 150 - 160 350 - 390 13 - 19 3 - 10 10 - 14 30 - 36 3.0 155 - 165 365 - 405 13 - 19 3 - 10 8 - 12 32 - 38 70 90 1.5 110 3.0 Cooling performance based on entering air temperatures of 80°F DB, 67°F WB. Heating performance based on entering air temperature of 70°F DB. 42 10/1/10 ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL Operating Parameters cont. Dual Capacity Models FIRST STAGE OPERATION Entering Water Temp °F 30 50 70 90 110 Entering Water Temp °F 30 50 70 90 110 Water Flow gpm/ton 1.5 3.0 1.5 3.0 1.5 3.0 1.5 3.0 1.5 3.0 Water Flow gpm/ton 1.5 3.0 1.5 3.0 1.5 3.0 1.5 3.0 1.5 3.0 Cooling -- No Hot Water Generation Suction Pressure psig 105 - 120 100 - 115 125 - 140 120 - 135 135 - 145 133 - 143 142 - 152 140 - 150 152 - 158 148 - 153 Discharge Pressure psig 140 - 155 115 - 130 205 - 225 180 - 200 280 - 290 250 - 260 345 - 355 330 - 340 405 - 435 390 - 420 Suction Pressure psig 76 - 84 80 - 88 100 - 115 105 - 120 135 - 150 140 - 155 155 - 165 160 - 170 Discharge Pressure psig 270 - 285 275 - 290 280 - 310 290 - 315 310 - 325 315 - 330 330 - 370 340 - 380 Superheat Subcooling 20 - 35 20 - 35 12 - 20 12 - 20 10 - 16 10 - 16 8 - 12 8 - 12 8 - 12 8 - 12 9 - 17 9 - 17 8 - 14 8 - 14 8 - 14 8 - 14 8 - 14 8 - 14 8 - 14 8 - 14 Water Temp Rise °F 17 - 21 8 - 12 17 - 21 8 - 12 16 - 20 9 - 13 14 - 20 8 - 12 14 - 20 8 - 12 Air Temp Drop °F DB 17 - 23 17 - 23 17 - 23 17 - 23 17 - 23 17 - 23 17 - 23 17 - 23 17 - 23 17 - 23 Water Temp Drop °F 5-9 3-7 7 - 11 5-9 8 - 12 6 - 10 8 - 12 6 - 10 Air Temp Rise °F DB 12 - 16 14 - 18 18 - 22 20 - 24 24 - 28 22 - 30 24 - 28 22 - 30 Heating -- No Hot Water Generation Superheat Subcooling 8 - 12 8 - 12 10 - 14 10 - 14 12 - 16 12 - 16 12 - 16 12 - 16 3 - 10 3 - 10 3 - 10 3 - 10 3 - 10 3 - 10 3 - 10 3 - 10 10/1/10 SECOND STAGE OPERATION Entering Water Temp °F 30 50 70 90 110 Entering Water Temp °F Water Flow gpm/ton 1.5 3.0 1.5 3.0 1.5 3.0 1.5 3.0 1.5 3.0 Water Flow gpm/ton Cooling -- No Hot Water Generation Suction Pressure psig 115 - 125 105 - 120 130 - 140 128 - 138 138 - 148 136 - 146 145 - 155 143 - 153 145 - 155 143 - 153 Discharge Pressure psig 150 - 170 130 - 145 215 - 235 190 - 210 280 - 310 250 - 280 350 - 380 320 - 350 420 - 450 405 - 435 Suction Pressure psig 73 - 85 77 - 90 97 - 110 102 - 115 130 - 145 135 - 150 150 - 160 155 - 165 Discharge Pressure psig 270 - 305 280 - 315 290 - 325 300 - 335 320 - 355 325 - 360 350 - 390 365 - 405 Superheat Subcooling 20 - 35 20 - 35 12 - 20 12 - 20 10 - 16 10 - 16 9 - 14 9 - 14 9 - 14 9 - 14 10 - 17 10 - 17 8 - 14 8 - 14 10 - 16 8 - 14 10 - 16 8 - 14 10 - 16 8 - 14 Air Temp Drop °F DB 17 - 23 17 - 23 17 - 23 17 - 23 17 - 23 17 - 23 17 - 23 17 - 23 17 - 23 17 - 23 Water Temp Drop °F 6 - 10 4-8 9 - 13 7 - 11 10 - 14 8 - 12 10 - 14 8 - 12 Air Temp Rise °F DB 15 - 21 17 - 23 22 - 28 24 - 30 30 - 36 32 - 38 30 - 36 32 - 38 Heating -- No Hot Water Generation Superheat 1.5 3.0 1.5 50 3.0 1.5 70 3.0 1.5 90 3.0 1.5 110 3.0 Cooling performance based on entering air temperatures of 80°F DB, 67°F WB. Heating performance based on entering air temperature of 70°F DB. 30 Water Temp Rise °F 17 - 22 8 - 10 16 - 22 8 - 12 15 - 21 7 - 13 14 - 20 6 - 10 14 - 20 6 - 10 43 8 - 14 8 - 14 10 - 16 10 - 16 13 - 19 13 - 19 13 - 19 13 - 19 Subcooling 3 - 10 3 - 10 3 - 10 3 - 10 3 - 10 3 - 10 3 - 10 3 - 10 10/1/10 ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL Pressure Drop Single Speed Model 009 012 015 018 022 030 036 042 048 060 070 GPM 1.5 2.0 3.0 4.0 1.5 2.5 3.5 4.5 2.0 3.0 4.0 5.0 3.0 4.0 5.0 6.0 3.0 4.5 6.0 8.0 4.0 6.0 8.0 10.0 5.0 7.0 9.0 12.0 5.0 8.0 11.0 14.0 6.0 9.0 12.0 16.0 9.0 12.0 15.0 20.0 12.0 15.0 18.0 24.0 30°F 1.9 3.5 6.9 12.0 0.3 1.0 1.7 2.5 0.6 1.6 2.6 3.7 1.6 2.9 4.2 6.0 0.9 1.7 2.8 4.7 1.5 3.0 5.1 7.7 1.0 2.1 3.6 6.3 0.8 2.1 4.2 7.6 1.1 2.3 3.9 6.7 2.4 3.9 5.7 9.5 3.0 4.4 6.0 9.7 Pressure Drop (psi) 50°F 70°F 90°F 1.8 1.7 1.6 3.4 3.2 3.1 6.5 6.3 6.0 11.4 11.0 10.8 0.3 0.3 0.3 1.0 1.0 1.0 1.7 1.7 1.6 2.4 2.4 2.4 0.6 0.6 0.6 1.6 1.6 1.6 2.6 2.6 2.6 3.7 3.6 3.6 1.6 1.5 1.5 2.9 2.8 2.8 4.2 4.1 4.0 5.8 5.7 5.6 0.9 0.8 0.7 1.6 1.5 1.4 2.7 2.5 2.3 4.4 4.1 3.9 1.4 1.3 1.2 2.8 2.7 2.5 4.8 4.5 4.2 7.2 6.8 6.3 1.0 0.9 0.8 1.9 1.8 1.7 3.3 3.0 2.8 5.9 5.5 5.1 0.7 0.7 0.7 2.1 1.9 1.8 4.1 3.8 3.5 6.7 6.3 5.8 1.0 1.0 0.9 2.1 2.0 1.9 3.7 3.4 3.2 6.3 5.9 5.5 2.2 2.1 2.0 3.6 3.4 3.2 5.3 5.0 4.7 8.9 8.3 7.8 2.8 2.6 2.4 4.0 3.8 3.5 5.5 5.1 4.8 9.1 8.5 7.9 Valve 110°F 1.5 3.0 5.7 10.5 0.3 1.0 1.6 2.3 0.6 1.6 2.5 3.5 1.4 2.7 3.9 5.5 0.7 1.3 2.2 3.6 1.1 2.3 3.9 5.8 0.8 1.6 2.6 4.8 0.6 1.7 3.3 5.4 0.8 1.7 3.0 5.1 1.8 2.9 4.3 7.2 2.2 3.3 4.4 7.3 10/1/10 1/2 in. 1/2 in. 3/4 in. 3/4 in. 3/4 in. 3/4 in. 1 in. 1 in. 1 in. 1 in. 1 in. GPM Cv 1.5 2.0 3.0 4.0 1.5 2.5 3.5 4.5 2.0 3.0 4.0 5.0 3.0 4.0 5.0 6.0 3.0 4.5 6.0 8.0 4.0 6.0 8.0 10.0 5.0 7.0 9.0 12.0 5.0 8.0 11.0 14.0 6.0 9.0 12.0 16.0 9.0 12.0 15.0 20.0 12.0 15.0 18.0 24.0 9.6 9.7 9.9 10.1 9.6 9.8 10.0 10.2 9.7 9.9 10.1 10.4 9.9 10.1 10.4 10.6 9.9 10.2 10.6 11.0 10.1 10.6 11.0 11.5 15.9 16.6 17.2 17.9 15.9 16.6 17.2 17.9 16.1 16.8 17.4 18.3 16.8 17.4 18.1 19.2 17.4 18.1 18.7 20.1 GPM Cv 4.0 6.0 8.0 10.0 5.0 7.0 9.0 12.0 6.0 9.0 12.0 15.0 9.0 12.0 16.0 20.0 12.0 15.0 18.0 24.0 10.1 10.6 11.0 11.5 10.4 10.8 11.2 11.9 16.1 16.8 17.4 18.1 16.8 17.4 18.3 19.2 17.4 18.1 18.7 20.1 Pressure Drop (psi) 0.02 0.04 0.09 0.16 0.02 0.06 0.12 0.19 0.04 0.09 0.16 0.23 0.09 0.16 0.23 0.32 0.09 0.19 0.32 0.53 0.16 0.32 0.53 0.76 0.10 0.23 0.41 0.61 0.10 0.23 0.41 0.61 0.14 0.29 0.47 0.76 0.29 0.47 0.69 1.09 0.47 0.69 0.92 1.43 10/1/10 Dual Capacity Model 026 038 049 064 072 GPM 4.0 6.0 8.0 10.0 5.0 7.0 9.0 11.0 6.0 9.0 12.0 15.0 8.0 12.0 16.0 20.0 12.0 15.0 18.0 21.0 30°F 1.4 2.8 4.7 7.0 1.2 2.2 3.4 4.9 1.2 2.4 3.9 5.7 1.8 3.8 6.5 9.7 3.2 4.5 6.0 7.8 Pressure Drop (psi) 50°F 70°F 90°F 1.3 1.2 1.1 2.6 2.4 2.3 4.4 4.1 3.8 6.6 6.2 5.8 1.2 1.1 1.0 2.1 1.9 1.8 3.2 3.0 2.8 4.6 4.3 4 1.2 1.1 1.0 2.2 2.1 2.0 3.6 3.4 3.2 5.3 5 4.7 1.7 1.6 1.4 3.5 3.3 3.0 6.0 5.6 5.2 9.1 8.5 8.0 3.0 2.8 2.6 4.2 4.0 3.7 5.7 5.3 4.9 7.3 6.8 6.4 Valve 110°F 1.0 2.1 3.5 5.3 1.0 1.7 2.6 3.7 1.0 1.8 2.9 4.3 1.3 2.8 4.8 7.4 2.4 3.4 4.6 5.9 10/1/10 3/4 in. 3/4 in. 1 in. 1 in. 1 in. 44 Pressure Drop (psi) 0.16 0.32 0.53 0.76 0.23 0.42 0.64 1.02 0.14 0.29 0.47 0.69 0.29 0.47 0.76 1.09 0.47 0.69 0.92 1.43 10/1/10 ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL Compressor and Thermistor Resistance Compressor Resistance Chart Dual Capacity Single Speed Model 009 012 015 018 022 030 036 042 048 060 070 026 038 049 064 072 208-230/60/1 Run Start 3.65 - 4.19 3.75 - 4.31 3.35 - 3.85 2.80 - 3.22 2.74 - 3.16 2.60 - 3.00 2.24 - 2.58 2.84 - 3.26 1.39 - 1.53 2.15 - 2.30 1.21 - 1.39 1.53 - 1.75 0.95 - 1.09 1.81 - 2.09 0.83 - 0.95 1.54 - 1.78 0.51 - 0.59 1.13 - 1.31 0.42 - 0.48 0.73 - 0.85 0.34 - 0.40 0.51 - 0.59 1.23 - 1.41 1.30 - 1.50 0.83 - 0.95 1.20 - 1.38 0.60 - 0.68 1.41 - 1.63 0.46 - 0.52 0.56 - 0.64 0.34 - 0.40 0.49 - 0.57 265/60/1 Run Start 3.73 - 4.27 4.45 - 5.13 3.73 - 4.27 4.45 - 5.13 3.03 - 3.49 2.39 - 2.75 3.03 - 3.49 2.39 - 2.75 1.66 - 1.91 1.66 - 1.91 1.38 - 1.58 2.02 - 2.32 1.24 - 1.42 2.42 - 2.78 n/a n/a n/a n/a 1.71 - 1.97 0.97 - 1.11 n/a n/a n/a n/a Thermistor Resistance Chart Thermistor Temperature (°F) 5 14 23 32 41 50 59 68 77 86 95 104 113 122 131 140 149 Microprocessor Resistance (Ohms) 75757-70117 57392-53234 43865-40771 33809-31487 26269-24513 20570-19230 16226-15196 12889-12093 10310-9688 8300-7812 6723-6337 5480-5172 4490-4246 3700-3504 3067-2907 2554-2424 2149-2019 FX10 Resistance (Ohms) 746-770 775-803 808-836 841-869 875-903 910-938 946-974 981-1013 1019-1051 1058-1090 1097-1129 1137-1169 1179-1211 1221-1253 1261-1297 1305-1341 1350-1386 7/6/10 45 208-230/60/3 460/60/3 575/60/3 n/a n/a n/a n/a n/a n/a 1.77 - 2.04 1.42 - 1.64 0.96 - 1.10 0.63 - 0.73 0.63 - 0.73 2.30 - 2.64 1.45 - 1.67 0.93 - 1.07 0.64 - 0.74 0.64 - 0.74 n/a n/a n/a n/a n/a n/a 7.57 - 8.71 5.46 - 6.28 3.88 - 4.46 2.98 - 3.42 2.30 - 2.64 5.60 - 6.44 3.88 - 4.46 3.88 - 4.46 2.60 - 3.00 2.60 - 3.00 n/a n/a n/a n/a n/a n/a n/a 8.26 - 9.50 5.88 - 6.76 4.96 - 5.70 3.31 - 3.81 n/a n/a n/a n/a n/a 10/1/10 ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL Refrigerant Circuit Guideline Head Pressure Under Charged System (Possible Leak) Low Over Charged System High Low Air Flow Heating High Low Air Flow Cooling Low Low Water Flow Heating Low/Normal Low Water Flow Cooling High High Air Flow Heating Low High Air Flow Cooling Low High Water Flow Heating Normal High Water Flow Cooling Low Low Indoor Air Temperature Heating Low Low Indoor Air Temperature Cooling Low High Indoor Air Temperature Heating High High Indoor Air Temperature Cooling High Restricted TXV (Check Service Advisory) High Insufficient Compressor (Possible Bad Valves) Low TXV - Bulb Loss of Charge Low Scaled Coaxial Heat Exchanger Heating Low Scaled Coaxial Heat Exchanger Cooling High Restricted Filter Drier Symptom Suction Compressor Air Temp. Water Temp. Superheat Subcooling Pressure Amp Draw Differential Differential Low Low High Low Low Low High High Normal High Normal/Low Normal High High High/Normal Low High Low Low Low Low/Normal High High Low Low/Normal Low Low High Low High High High High Low Low High Low Low Low High Low Low High Normal High Low Low Normal Low Normal High Normal Normal Low Low Low Low High Normal Low Low Low Normal High Normal Normal/High Low Low Normal/Low High Low Low High High Normal/High Normal/Low Low Normal High High High Low Low High Low Normal/Low High High Low Low High Low High Normal/High Low Low Low Low High High Low Low Low Low Normal/Low High Low Low High High Normal/Low Low Low Low Check temperature difference (delta T) across filter drier. 7/6/10 Reference Calculations Heating Calculations: Cooling Calculations: HR gpm x 500 LWT = EWT - HE gpm x 500 LWT = EWT + LAT = EAT + HC cfm x 1.08 LAT(DB) = EAT(DB) - SC cfm x 1.08 LC = TC - SC TH = HC + HWC S/T = SC TC Legend ABBREVIATIONS AND DEFINITIONS: cfm EWT gpm WPD EAT = = = = = HC TC SC kW HR = = = = = airflow, cubic feet/minute entering water temperature, Fahrenheit water flow in gallons/minute water pressure drop, psi and feet of water entering air temperature, Fahrenheit (dry bulb/wet bulb) air heating capacity, MBtu/h total cooling capacity, MBtu/h sensible cooling capacity, MBtu/h total power unit input, kilowatts total heat of rejection, MBtu/h HE = total heat of extraction, MBtu/h HWC = hot water generator capacity, MBtu/h EER = Energy Efficient Ratio = BTU output/Watt input COP = Coefficient of Performance = Btu output/Btu input LWT = leaving water temperature, °F LAT = leaving air temperature, °F TH = total heating capacity, MBtu/h LC = latent cooling capacity, MBtu/h S/T = sensible to total cooling ratio 46 ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL Heat of Extraction/Rejection Data Model 009 012 015 018 Single Speed 022 030 036 042 048 060 070 026 Lo 026 Hi 038 Lo Dual Capacity 038 Hi 049 Lo 049 Hi 064 Lo 064 Hi 072 Lo 072 Hi gpm 1.5 2.0 3.0 1.5 2.5 3.5 2.0 3.0 4.0 3.0 4.0 5.0 3.0 4.5 6.0 4.0 6.0 8.0 5.0 7.0 9.0 5.0 8.0 11.0 6.0 9.0 12.0 9.0 12.0 15.0 12.0 15.0 18.0 3.0 5.0 7.0 4.0 6.0 8.0 4.0 6.0 8.0 5.0 7.0 9.0 5.0 8.0 11.0 6.0 9.0 12.0 6.0 10.0 14.0 8.0 12.0 16.0 10.0 13.0 16.0 12.0 15.0 18.0 30°F 5.1 5.0 6.3 6.3 7.9 8.0 10.1 10.3 10.7 10.8 14.6 14.9 17.7 18.1 21.0 21.4 26.8 27.3 30.8 31.8 37.2 37.3 10.2 10.4 14.1 14.3 13.5 14.5 19.7 20.2 19.6 20.3 26.8 27.4 22.4 23.5 33.9 34.3 26.3 27.9 39.1 39.5 Heat Of Extraction (HE) - MBtu/h 50°F 70°F 90°F 6.5 8.6 11.3 6.7 8.9 11.6 7.1 9.3 11.8 7.8 10.0 12.8 8.2 10.5 13.4 8.5 11.0 13.5 9.7 12.4 15.7 10.1 13.0 16.4 10.5 13.5 16.5 12.4 16.0 20.4 12.8 16.3 20.5 13.2 16.6 20.7 14.7 19.4 23.6 15.6 20.5 24.8 15.9 20.9 25.3 20.0 26.0 31.0 20.8 27.1 32.3 21.3 27.6 32.8 23.8 31.3 37.6 24.9 32.6 39.2 25.5 33.2 39.8 27.2 33.7 40.0 28.5 35.5 42.4 29.3 36.6 43.9 35.1 43.9 51.2 36.7 46.3 54.3 37.7 47.7 56.2 43.1 55.1 63.7 44.4 56.2 67.6 45.3 58.6 68.5 51.4 65.6 76.5 52.7 68.4 81.2 53.2 69.5 83.0 14.1 18.9 23.0 14.9 20.0 24.2 15.2 20.3 24.6 18.7 24.5 29.8 19.8 25.9 31.4 20.2 26.3 32.0 18.6 24.1 29.0 19.4 25.3 30.7 20.4 26.0 30.7 26.3 32.8 37.6 27.5 34.6 40.2 28.2 35.7 41.6 24.5 30.0 34.3 27.0 33.2 38.2 28.0 35.0 40.6 34.4 41.8 47.4 35.8 44.1 50.6 36.8 45.5 52.4 32.1 40.4 47.4 32.4 42.1 51.0 33.6 42.9 51.1 43.2 55.6 68.0 46.2 58.0 69.1 47.2 59.8 72.0 37.8 48.3 56.7 38.2 50.3 61.2 39.7 51.3 61.3 50.5 65.5 78.6 54.0 68.2 79.9 55.1 70.4 83.2 47 30°F 13.3 12.9 17.8 18.0 18.0 17.1 22.1 21.4 26.2 26.4 30.0 30.4 34.7 35.0 47.0 47.3 56.3 56.6 80.2 80.8 83.4 83.8 24.3 24.6 33.2 33.5 32.5 33.0 45.2 45.5 41.7 41.1 57.5 57.6 58.3 58.1 76.2 76.6 63.6 63.2 82.5 83.1 Heat of Rejection (HR) - MBtu/h 50°F 70°F 90°F 13.0 12.4 12.1 13.0 12.4 12.1 13.1 12.4 11.6 17.1 16.7 16.5 17.1 16.7 16.5 17.2 16.7 16.3 19.3 18.3 17.6 19.4 18.3 17.6 19.5 18.4 17.6 23.3 21.9 20.7 23.3 21.9 20.8 23.3 21.9 21.1 28.2 27.8 26.2 28.3 27.9 26.1 28.4 28.0 26.2 35.1 35.4 33.1 35.0 35.3 33.0 35.3 35.5 33.2 41.2 42.4 40.6 41.1 42.3 40.5 41.5 42.6 40.7 50.3 51.4 48.9 50.5 51.7 49.3 50.8 51.9 49.4 60.7 60.7 57.3 60.9 61.0 57.6 61.3 61.3 57.7 84.6 82.7 77.7 84.4 83.0 77.5 84.7 82.6 77.7 92.7 91.1 84.3 92.8 91.0 84.0 93.5 91.9 85.0 26.3 26.2 24.0 26.4 26.3 24.0 26.6 26.4 24.1 34.4 34.5 33.1 34.5 34.6 33.0 34.7 34.7 33.1 35.3 34.5 32.4 35.6 34.7 32.5 36.1 35.2 32.9 48.3 48.5 45.8 48.8 49.2 46.7 49.1 49.6 47.0 46.1 47.3 45.2 46.2 47.0 44.5 46.1 47.4 45.4 61.7 61.7 57.8 61.8 62.3 58.8 62.0 62.7 59.0 62.6 61.4 57.4 62.5 61.5 57.7 62.5 61.6 58.0 83.7 85.7 79.1 84.2 86.2 79.4 84.7 86.7 79.8 69.8 69.3 64.5 69.7 69.3 64.8 69.6 69.6 65.1 91.4 92.4 86.4 91.8 92.8 86.6 92.4 93.4 87.1 110°F 11.9 11.1 16.5 16.2 17.3 16.7 20.0 19.8 24.3 24.3 29.3 29.4 37.8 38.0 46.1 46.1 54.0 54.0 73.0 73.1 77.9 78.8 22.1 22.1 30.9 30.9 30.3 30.7 43.6 43.8 41.5 42.5 54.1 54.4 54.1 54.4 73.9 74.1 60.0 60.4 79.4 79.7 10/1/10 ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL DEALER: PHONE #: DATE: PROBLEM: MODEL #: Startup/Troubleshooting Form SERIAL #: COOLING CYCLE ANALYSIS PSI = SAT °F °F Unit Amp Draw: °F AIR COIL Loop: Open Closed Line Voltage: °F SUCTION COMPRESSOR COAX COAX EXPANSION VALVE LOAD REVERSING VALVE SOURCE DISCHARGE Hot Water Generator °F °F LIQUID LINE °F °F °F °F PSI PSI PSI PSI °F BRINE IN BRINE IN BRINE OUT SAT °F PSI = Superheat °F Subcooling BRINE OUT Water to Water Application Heat of Extraction/Rejection = GPM x 500 (485 for water/antifreeze) x ∆T Note: DO NOT hook up pressure gauges unless there appears to be a performance problem. HEATING CYCLE ANALYSIS PSI = SAT °F °F Loop: Unit Amp Draw: °F AIR COIL Open Closed Line Voltage: °F SUCTION COMPRESSOR COAX EXPANSION VALVE LOAD REVERSING VALVE COAX SOURCE DISCHARGE Hot Water Generator °F °F LIQUID LINE PSI = °F °F °F °F PSI PSI PSI PSI °F BRINE IN BRINE OUT BRINE IN °F SAT °F Superheat Subcooling BRINE OUT Water to Water Application WFS37 10/07 48 ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL Preventive Maintenance Water Coil Maintenance Condensate Drain 1. In areas where airborne bacteria produce a slime in the drain pan, it may be necessary to treat chemically to minimize the problem. The condensate drain can pick up lint and dirt, especially with dirty filters. Inspect twice a year to avoid the possibility of overflow. 2. Keep all air out of the water. An open loop system should be checked to ensure that the well head is not allowing air to infiltrate the water line. Lines should always be airtight. Keep the system under pressure at all times. It is recommended in open loop systems that the water control valve be placed in the discharge line to prevent loss of pressure during off cycles. Closed loop systems must have positive static pressure. Blower Motors Blower motors are equipped with sealed ball bearings and require no periodic oiling. NOTE: On open loop systems, if the installation is in an area with a known high mineral content (125 ppm or greater) in the water, it is best to establish with the owner a periodic maintenance schedule so the coil can be checked regularly. Should periodic coil cleaning be necessary, use standard coil cleaning procedures which are compatible with either the cupronickel or copper water lines. Generally, the more water flowing through the unit the less chance for scaling. Hot Water Generator Coil See Water Coil Maintenance section. Air Coil The air coil must be cleaned to obtain maximum performance. Check once a year under normal operating conditions and, if dirty, brush or vacuum (with a brush attachment) clean. Care must be taken not to damage the aluminum fins while cleaning. Other Maintenance Filters CAUTION: Fin edges are sharp. Filters must be clean to obtain maximum performance. They should be inspected monthly under normal operating conditions and be replaced when necessary. Units should never be operated without a filter. Replacement Procedures Obtaining Parts In-Warranty Material Return When ordering service or replacement parts, refer to the model number and serial number of the unit as stamped on the serial plate attached to the unit. If replacement parts are required, mention the date of installation of the unit and the date of failure, along with an explanation of the malfunctions and a description of the replacement parts required. Material may not be returned except by permission of authorized warranty personnel. Contact your local distributor for warranty return authorization and assistance. 49 ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL Service Parts Single Speed Vertical Units Part Description Compressor 009 012 015 018 022 34P592-01 34P593-01 34P581-01 265/60/1 34P590-02 34P591-02 34P592-02 34P593-02 34P581-02 34P582-02 34P583-02 ECM Motor & Blower PSC Motor & Blower Refrigeration Components 048 060 070 Not Available Not Available 34P582-03 34P583-03 34P578-03 34P579-03 34P580-03 34P561-06 460/60/3 Not Available 34P582-04 34P583-04 34P578-04 34P579-04 34P580-04 34P561-07 575/60/3 Not Available 34P578-05 34P579-05 34P580-05 34P561-08 Run Capacitor 208-230/60/1 16P002D17 16P002D18 16P002D19 16P002D19 16P002-18 16P002-20 Sound Jacket 92P504A05 92P504A01 16P002-21 16P002-25 16P002-24 92P504A16 11P521A01 11P781-01 Not Available ECM Motor 208-230/60/1 Not Available 14S551-01 ECM Motor 265/60/1 Not Available 14S551-02 ECM Motor 230/60/3 Not Available 14S551-01 ECM Motor 460/60/3 Not Available ECM Blower Housing Not Available ECM Harness Not Available ECM Power Harness Not Available 14S552-01 14S553-01 14S552-02 14S551-02 Not Available 14S552-01 14S553-01 14S552-02 14S553-02 53P500B01 53P501B01 11P607B02 11P585B02 PSC Motor 208-230/60/1 14P506B01 14P507B01 14P508B01 14P509B01 PSC Motor 265/60/1 14P506B02 14P507B02 14P508B02 14P510B02 14P510B02 14P511B01 14P512B01 14P514B01 Not Available PSC Motor 230/60/3 Not Available 14P511B01 14P512B01 14P514B01 PSC Motor 460/60/3 Not Available 14P511B02 14P512B02 14P514B02 14P511B03 14P514B03 PSC Motor 575/60/3 PSC Blower & Housing Hot Water Generator 042 34P582-01 34P583-01 34P578-01 34P579-01 34P580-01 34P561-05 230/60/3 Solenoid Harness Not Available 53P502B01 53P500B01 61P500C02 61P501C02 Coax 62P501B01 62P502B01 62P503B01 62P503B01 62P504B01 62P541-01 TXV 33P608-12 33P608-13 33P608-02 33P608-02 33P608-02 Reversing Valve 33P502-05 33P506-04 Filter Drier 36P500B01 How Water Generator 61P502C02 53P517-01 Air Coil Comfort Alert 61S548C02 61S505C02 53P501B01 61S506C02 62P542B01 61S547-02 62P543B01 Not Available 33P503-05 33P526-04 62P516-03 19P571-01 13P004A03 Transformer 208-230/60/1 15P501B01 Transformer 265/60/1 15P507B01 Not Available Transformer 230/60/3 Not Available 15P501B01 Transformer 460/60/3 Not Available 15P505B01 Transformer 575/60/3 3 Pole Power Block Not Available 15P506B01 Not Available 12P503-06 2 Pole Screw Term. Block 12P500A01 Status Light Board 17P503-02 Premier Board 17P513-03 17P513-07 Freeze Protection Thermistor 12P505B01 12P505B03 HWL Thermistor 33P608-10 36P500B02 62P516-05 Not Available 62P555-01 33P608-09 33P608-05 33P608-04 36P500B01 Contactor Electrical 036 34P590-01 34P591-01 Power Harness Sensors & Safeties 030 Compressor 208-230/60/1 Not Available 12P505B02 High Pressure Switch 35P506B02 Low Pressure Switch 35P506B01 Part numbers subject to change 01/09/13 50 ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL Service Parts cont. Dual Capacity Vertical Units Part Description 026 038 049 064 072 34P585-01 34P573-01 34P574-01 34P575-01 34P586-01 230/60/3 Not available 34P573-03 34P574-03 34P575-03 Not Available 460/60/3 Not available 34P573-04 34P574-04 34P575-04 Not Available Compressor 208-230/60/1 Compressor 265/60/1 Not available 575/60/3 Run Capacitor 208-230/60/1 Not available 16P002-19 16P002-20 16P002-21 ECM Motor & Blower Sound Jacket Power Harness 11P781-01 Solenoid Harness 11P782-01 ECM Motor 208-230/60/1 14S551-01 ECM Motor 265/60/1 14S551-02 14S552-01 14S551-01 14S552-01 14S553-01 ECM Motor 460/60/3 14S551-02 14S552-02 14S553-02 ECM Blower Housing 53P500B01 53P501B01 ECM Harness 11P607B01 11P585B01 PSC Motor & Blower Not available PSC Motor 265/60/1 Not available PSC Motor 230/60/3 Not available PSC Motor 460/60/3 Not available PSC Motor 575/60/3 Not available Refrigeration Components PSC Blower & Housing Hot Water Generator Not Available ECM Motor 230/60/3 ECM Power Harness Not available Air Coil 61S548-02 61S505C02 Coax 62P504B01 62P542B01 TXV 33P608-02 33P608-03 Reversing Valve 33P506-04 33P503-05 Filter Drier How Water Generator 61S506C02 61S547-02 62P543B01 33P608-04 62P555-01 33P608-10 33P608-11 33P526-04 36P500B01 36P500B02 62P516-05 Comfort Alert 62P516-03 19P571-02 Contactor 13P004A03 Transformer 208-230/60/1 15P501B01 Transformer 265/60/1 Electrical 14S553-01 14S552-02 PSC Motor 208-230/60/1 Not available Transformer 230/60/3 Not available 15P501B01 Not available Transformer 460/60/3 Not available 15P505B01 Not available Transformer 575/60/3 Not available 3 Pole Power Block 12P503-06 2 Pole Screw Term. Block 12P500A01 Status Light Board 17P503-02 Premier Board Sensors & Safeties 16P002-24 92P504A16 Freeze Protection Thermistor 17P513-07 12P505B03 HWL Thermistor 12P505B02 High Pressure Switch 35P506B02 Low Pressure Switch 35P506B01 Part numbers subject to change 01/09/13 51 ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL Service Parts cont. Single Speed Horizontal Units Part Description Compressor 009 012 015 018 022 Not Available 460/60/3 ECM Motor & Blower PSC Motor & Blower 060 070 Run Capacitor 208-230/60/1 Not Available 34P582-03 34P583-03 34P578-03 34P579-03 34P580-03 34P561-06 Not Available 575/60/3 34P582-04 34P583-04 34P578-04 34P579-04 34P580-04 34P561-07 Not Available Not Available 16P002D17 16P002D18 16P002D19 16P002D19 16P002-18 34P578-05 34P579-05 34P580-05 34P561-08 16P002-20 92P504A01 16P002-21 16P002-25 16P002-24 92P504A05 92P504A16 11P521A01 11P781-01 Not Available ECM Motor 208-230/60/1 Not Available 14S551-01 ECM Motor 265/60/1 Not Available 14S551-02 ECM Motor 230/60/3 Not Available 14S551-01 ECM Motor 460/60/3 14S552-01 Not Available ICM Harness Not Available ICM Power Harness Not Available 14S553-01 14S552-02 Not Available ECM Blower Housing 14S551-02 Not Available 14S552-01 14S553-01 14S552-02 14S553-02 53P500B01 53P501B01 11P607B02 11P585B02 PSC Motor 208-230/60/1 14P506B01 14P507B01 14P508B01 14P509B01 14P511B01 PSC Motor 265/60/1 14P506B02 14P507B02 14P508B02 14P510B02 14P510B02 14P512B01 14P514B01 Not Available PSC Motor 230/60/3 Not Available Not Available 14P511B01 14P512B01 14P514B01 PSC Motor 460/60/3 Not Available Not Available 14P511B02 14P512B02 14P514B02 14P511B03 14P514B03 PSC Motor 575/60/3 PSC Blower & Housing Refrigeration Components 048 34P590-02 34P591-02 34P592-02 34P593-02 34P581-02 34P582-02 34P583-02 230/60/3 Solenoid Harness Hot Water Generator 042 265/60/1 Power Harness Not Available 53P502B01 Not Available 53P500B01 53P517-01 Air Coil 61P500C02 61P501C02 61P508C02 61P508C02 Coax 62P501B01 62P502B01 62P503B01 62P503B01 62P504B01 62P541-01 TXV 61P510C02 33P608-12 33P608-13 33P608-02 33P608-02 33P608-02 Reversing Valve 33P502-05 33P506-04 Filter Dryer 36P500B01 Hot Water Generator Comfort Alert 61P511C02 62P542B01 33P608-09 53P501B01 61P512C02 33P60804 61P513C02 62P543B01 Not Available 33P503-05 33P526-04 62P516-03 19P571-01 13P004A03 Transformer 208-230/60/1 15P501B01 Transformer 265/60/1 15P507B01 Not Available Transformer 230/60/3 Not Available Not available 15P501B01 Transformer 460/60/3 Not Available Not available 15P505B01 Transformer 575/60/3 Not Available 3 Pole Power Block Not Available Not available 15P506B01 12P503-06 2 Pole Screw Term. Block 12P500A01 Status Light Board 17P503-02 Premier Board 17P513-03 17P513-07 Freeze Protection Thermistor 12P505B01 12P505B03 HWL Thermistor 33P608-10 36P500B02 62P516-05 Not Available 62P555-01 33P608-05 36P500B01 Contactor Electrical 036 34P590-01 34P591-01 34P592-01 34P593-01 34P581-01 34P582-01 34P583-01 34P578-01 34P579-01 34P580-01 34P561-05 Sound Jacket Sensors & Safeties 030 Compressor 208-230/60/1 Not Available 12P505B02 High Pressure Switch 35P506B02 Low Pressure Switch 35P506B01 Part numbers subject to change 01/09/13 52 ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL Service Parts cont. Dual Capacity Horizontal Units Part Description 026 038 049 064 072 34P585-01 34P573-01 34P574-01 34P575-01 34P586-01 230/60/3 Not available 34P573-03 34P574-03 34P575-03 Not Available 460/60/3 Not available 34P573-04 34P574-04 34P575-04 Not Available Compressor 208-230/60/1 Compressor 265/60/1 Not available Not available 575/60/3 Run Capacitor 208-230/60/1 16P002-19 16P002-20 16P002-21 ECM Motor & Blower Sound Jacket Power Harness 11P781-01 Solenoid Harness 11P782-01 ECM Motor 208-230/60/1 14S551-01 ECM Motor 265/60/1 14S551-02 14S552-01 Not Available ECM Motor 230/60/3 14S551-01 14S552-01 14S553-01 ECM Motor 460/60/3 14S551-02 14S552-02 14S553-02 ECM Blower Housing 53P500B01 53P501B01 ICM Harness 11P607B02 11P585B02 PSC Motor & Blower PSC Motor 208-230/60/1 Not available PSC Motor 265/60/1 Not available PSC Motor 230/60/3 Not available PSC Motor 460/60/3 Not available PSC Motor 575/60/3 Not available Hot Water Generator Refrigeration Components PSC Blower & Housing Not available Air Coil 61P510C02 61P511C02 Coax 62P504B01 62P542B01 TXV 33P608-02 33P608-03 Reversing Valve 33P506-04 33P503-05 61P549-01 62P543B01 33P608-05 62P555-01 33P608-10 33P608-11 33P526-04 36P500B01 Filter Dryer Hot Water Generator 61P512C02 36P500B02 62P516-05 62P516-03 Comfort Alert 19P571-02 Contactor 13P004A03 Transformer 208-230/60/1 15P501B01 Transformer 265/60/1 Electrical 14S553-01 14S552-02 ICM Power Harness Not available Transformer 230/60/3 Not available 15P501B01 Not available Transformer 460/60/3 Not available 15P505B01 Not available Transformer 575/60/3 Not available 3 Pole Power Block 12P503-06 2 Pole Screw Term. Block 12P500A01 Status Light Board 17P503-02 Premier Board Sensors & Safeties 16P002-24 92P504A16 17P513-07 Freeze Protection Thermistor 12P505B03 HWL Thermistor 12P505B02 High Pressure Switch 35P506B02 Low Pressure Switch 35P506B01 Part numbers subject to change 01/09/13 53 ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL Revision Guide Pages: Description: Date: By: All Updated Nomenclature to Reflect new ECM Blower Motor 09 Jan 2013 DS All Removed FX10 & BACnet Variables Tables 09 Jan 2013 DS 11 Updated Weight Distribution Table 09 Jan 2013 DS Updated Parts Lists 09 Jan 2013 DS Added Revision Guide 09 Jan 2013 DS 50-53 54 54 Manufactured by WaterFurnace International, Inc. 9000 Conservation Way Fort Wayne, IN 46809 www.waterfurnace.com IM1020AN 01/13 Product: Type: Size: Document: Envision Series Geothermal/Water Source Heat Pump Commercial 0.75-6 Tons Installation Manual ©2013 WaterFurnace International, Inc., 9000 Conservation Way, Fort Wayne, IN 46809-9794. WaterFurnace has a policy of continual product research and development and reserves the right to change design and specifications without notice.