Transcript
Envision Commercial 0.75-6 Tons Installation Manual
COMMERCIAL Geothermal/Water Source Heat Pump • R-410A Refrigerant • 0.75-6 Tons Single Speed • 2-6 Tons Dual Capacity
Installation Information on Water Piping Connections ctions Hot Water Connections ons Electrical Startup Procedures Troubleshooting Preventive Maintenance nce
IM1020AN 01/13
ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL
Table of Contents Model Nomenclature. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 General Installation Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Vertical Dimensional Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-8 Horizontal Dimensional Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Installing Horizontal Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10 Hanger Bracket Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Duct System and Water Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Water Quality and Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 System Cleaning and Flushing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14 Open Loop Ground Water Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Hot Water Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16-17 Freeze Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18-19 Electronic Thermostat Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19 Auxiliary Heat Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19 Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20-21 Blower Performance Data and Setting Blower Speed . . . . . . . . . . . . . . . . . . . . . . . . . . . 22-23 Wiring Schematics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24-28 Envision Controls - Premier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29-32 Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Envision Controls - FX10 (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34-40 Unit Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41 Operating Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 Operating Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42-43 Pressure Drop. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 Compressor and Thermistor Resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 Refrigerant Circuit Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 Reference Calculations and Legend . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 Heat of Extraction/Rejection Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 Startup/Troubleshooting Form . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 Preventive Maintenance and Replacement Procedures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49 Service Parts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50-53 Revision Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL
Model Nomenclature 1-2 3 4-6 7 8 9 10 11 12 13 14 15 16 17 18-19 20 NS V 022 T L 0 0 0 N B N N 2 1 SS A Model Type NS = Single Speed ND = Dual Capacity
Vintage C = Painted Cabinet D = Unpainted Cabinet
Cabinet Configuration H = Horizontal V = Vertical
Non-Standard Option Details SS = Standard Option QP = 2 in. MERV 13 Filter SF = Stainless Steel Drain Pan SG = 2 in. MERV 13 Filter with Stainless Steel Drain Pan
Unit Capacity Single Speed: 009, 012, 015, 018, 022, 030 036, 042, 048, 060, 070 Dual Capacity: 026, 038, 049, 064, 072
Air 1 2 3 4
Cabinet Configuration T = Vertical Top Discharge E = Horizontal End Discharge S = Horizontal Side Discharge B = Vertical Bottom Discharge (022-072) R = Vertical Rear Discharge 1 (022-072)
Coil/Insulation Options = FormiShield/Extended Range = FormiShield/Standard Range = No Coating/Extended Range = No Coating/Standard Range
Control Options 2 = Premier Microprocessor 1 4 = FX10 std. no communication 5 = FX10 w/Open N2 Com Card 6 = FX10 w/LonWorks Com Card 7 = FX10 w/BacNet Com Card
Return Air Configuration L = Left R = Right
Water Control N = None R = Water Flow Regulator (3 gpm/ton) V = 2-Way Valve P = Internal Pump (Secondary pumping) B = 2-Way Valve w/Water Flow Regulator
Voltage 0 = 208-230/60/1 2 = 265-277/60/1 (009-036) 3 = 208-230/60/3 (026, 036-072) 4 = 460/60/3 (026, 036-072) 5 = 575/60/3 (042, 048, 060, 070, PSC only) Hot Water Options 0 = No Hot Water Generator, No IntelliStartTM 2 = Hot Water Generator, without pump, No IntelliStart 1, 3 (018-072) 3 = No Hot Water Generator, IntelliStart 2 (018-072) 5 = Hot Water Generator, without pump, IntelliStart 1, 2, 3 (018-072)
Hot Gas Bypass/Reheat N = None G = Hot Gas Bypass (015-072) R = Hot Gas Reheat (015-072) B = Hot Gas Bypass w/Hot Gas Reheat (015-072) Sound Kit A = None B = Sound Kit
Blower Options 0 = PSC Blower 4 1 = Variable Speed ECM Blower (015-072) 2 = High Static Variable Speed ECM Blower Option (036, 038, 042, 048, 049) 3 = High Static PSC Blower Option 4 (022, 030, 036, 042, 048)
Coax Options C = Copper N = Cupronickel
Rev.: 09 January 2013D NOTES: 1 Not available with Hot Gas Reheat 2 Only on 208-230/60/1 3 Field installed external pump kit (DPK4 or DPK5) required for hot water generation 4 Not available on dual capacity models
4
ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL
General Installation Information Unit Location
Safety Considerations
Locate the unit in an indoor area that allows for easy removal of the filter and access panels. Location should have enough space for service personnel to perform maintenance or repair. Provide sufficient room to make water, electrical and duct connection(s). If the unit is located in a confined space, such as a closet, provisions must be made for return air to freely enter the space by means of a louvered door, etc. Any access panel screws that would be difficult to remove after the unit is installed should be removed prior to setting the unit. On horizontal units, allow adequate room below the unit for a condensate drain trap and do not locate the unit above supply piping. Care should be taken when units are located in unconditioned spaces to prevent damage from frozen water lines and excessive heat that could damage electrical components.
WARNING: Before performing service or maintenance operations on a system, turn off main power switches to the indoor unit. If applicable, turn off the accessory heater power switch. Electrical shock could cause personal injury. Installing and servicing heating and air conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair or service heating and air conditioning equipment. Untrained personnel can perform the basic maintenance functions of cleaning coils and cleaning and replacing filters. All other operations should be performed by trained service personnel. When working on heating and air conditioning equipment, observe precautions in the literature, tags and labels attached to the unit and other safety precautions that may apply.
Installing Vertical Units Follow all safety codes. Wear safety glasses and work gloves. Use a quenching cloth for brazing operations and have a fire extinguisher available.
Prior to setting the unit in place, remove and discard the compressor hold down shipping bolt located at the front of the compressor mounting bracket.
Moving and Storage
Vertical units are available in left or right air return configurations. Top flow vertical units should be mounted level on a vibration absorbing pad slightly larger than the base to provide isolation between the unit and the floor. It is not necessary to anchor the unit to the floor (see right).
Move units in the normal “up” orientation. Horizontal units may be moved and stored per the information on the packaging. Do not stack more than three units in total height. Vertical units may be stored one upon another to a maximum height of two units. Do not attempt to move units while stacked. When the equipment is received, all items should be carefully checked against the bill of lading to be sure all crates and cartons have been received. Examine units for shipping damage, removing the units from the packaging if necessary. Units in question should also be internally inspected. If any damage is noted, the carrier should make the proper notation on the delivery receipt, acknowledging the damage.
Bottom flow units should be mounted level and sealed well to floor to prevent air leakage. Bottom flow units require the supply air opening to be cut at least 1/2 in. larger than the unit’s air outlet. Protect the edges of combustible flooring with sheet metal over-wrap or other noncombustible material.
Figure 1: Vertical Unit Mounting
2” Extruded Polystyrene
5
ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL
Vertical Dimensional Data Top Air Discharge
LEFT RETURN Field Installed Duct Flange L Filter Rack Width
Legend AP BP CP CMP
B N
= Alternate Service Panel = Blower Service Panel = Control Access Panel = Compressor Service Panel
O
Access Panels
AIR COIL
2´ [61cm] Alternate Service Access Left Return (Right Return opposite side)
B N
O
AP
BP
FRONT
A M
FRONT
CMP
2´ [61cm] Service Access Left Return (Right Return opposite side)
M A
AP
CP P
Q
AIR COIL SIDE
AIR COIL SIDE
TOP VIEW - RIGHT RETURN
TOP VIEW - LEFT RETURN
S
S
R
2´ [61cm] Service Access 1.00˝ (25.4 mm)
R
U
U
BP FILTER RACK CONNECTION
FILTER RACK CONNECTION
AIR COIL
T
T
C
C
1.6˝ (4.1 cm) CONDENSATE 3/4"˝ PVC GLUE SOCKET POWER SUPPLY 3/4˝ (19.1 mm) KNOCKOUT
4
CP
3
1.3˝(3.3 cm) 5
CMP
5
LOW VOLTAGE 1/2˝ (12.7 mm) KNOCKOUT
FRONT
BACK
BACK
FRONT
AP
J
F
K
I
E
1
D
CMP
LEFT VIEW - LEFT RETURN
RIGHT VIEW - RIGHT RETURN
Overall Cabinet Vertical Models
009012 015018 022030 036072
FRONT VIEW
Water Connections 1
2
3
4
5
G
H
2
Electrical Knockouts I 1/2” cond
J 1/2” cond
K 3/4” cond
Low Voltage
Ext Pump
Power Supply
A Width
B Depth
C Height*
D In
E Out
F HWG In
G HWG Out
H Condensate
Loop Water FPT
HWG FPT
in.
22.2
22.5
34.5
2.34
5.3
11.9
14.9
8.6
1/2"
1/2"
3.8
9.7
11.7
cm.
56.4
57.2
87.6
5.9
13.5
30.2
37.8
21.8
12.7 mm
12.7 mm
9.7
24.6
in.
22.5
26.5
39.4
2.3
5.3
13.4
16.4
9.6
3/4"
1/2"
5.1
10.8
cm.
57.2
67.3
100.1
5.8
13.5
34.0
41.7
24.3
19.05 mm
12.7 mm
13.0
in.
22.5
26.5
48.4
2.3
7.3
13.4
16.4
10.4
3/4"
1/2"
cm.
57.2
67.3
122.9
5.8
18.5
34.0
41.7
26.4
19.05 mm
in.
25.5
31.2
58.5
2.3
7.3
15.9
18.9
11.6
1"
cm.
64.8
79.2
148.6
5.8
18.5
40.4
48.0
29.5
25.4 mm
L Filter Rack Width
Discharge Connection duct flange installed (±0.10 in)
Return Connection using std deluxe filter rack (±0.10 in)
M Supply Width
N Supply Depth
O
P
Q
R
S Return Depth
T Return Height
U
2.2
10.0
10.0
6.1
8.8
11.8
2.4
18.1
14.2
1.7
29.7
5.6
25.4
25.4
15.5
22.4
30.0
6.1
46.0
36.1
4.4
12.8
2.2
14.0
14.0
6.3
7.8
5.8
2.3
22.0
18.0
2.0
27.4
32.5
5.6
35.6
35.6
16.0
19.8
14.7
5.8
55.9
45.7
5.1
5.1
10.8
12.8
2.2
14.0
14.0
6.3
7.7
5.8
2.3
22.0
26.0
2.0
12.7 mm
13.0
27.4
32.5
5.5
35.6
35.6
16.0
19.6
14.7
5.8
55.9
66.0
5.1
1/2"
5.6
11.4
13.4
2.2
18.0
18.0
6.6
6.4
3.7
1.4
28.1
34.0
1.7
12.7 mm
14.2
29.0
34.0
5.5
45.7
45.7
16.8
16.3
9.4
3.6
71.4
86.4
4.3 10/1/10
Condensate is 3/4 in. PVC female glue socket and is switchable from front to side. Vertical unit shipped with deluxe 1 in. (field adjustable to 2 in.) duct collar/filter rack extending from unit 3.25 in. and is suitable for duct connection. Discharge flange is field installed and extends 1 in. [25.4 mm] from cabinet.
6
ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL
Vertical Dimensional Data cont. Bottomflow RIGHT RETURN
LEFT RETURN
CMP
AP
1.70 (4.3 cm) 4
3
CP
C
C
2 FILTER RACK CONNECTION
CMP
FILTER RACK CONNECTION
CP
S
1
S
K
BP
F I
D
B
B
LEFT SIDE
RIGHT SIDE Q
R
1.90 (4.7 cm)
R
5
Q A
Optional 2´ [61cm] Service Access Right Return
L
2´ [61cm] Service Access
L
O
Legend
O
LEFT BOTTOM DISCHARGE FLOOR FOOT PRINT
A B C Width Depth Height
RIGHT BOTTOM DISCHARGE FLOOR FOOT PRINT
Water Connections
Overall Cabinet
AP =Alternate Service Panel BP =Blower Service Panel CP =Control Access Panel CMP=Compressor Service Panel
P
N
M
Bottomflow Models
H
FRONT N
(Opposite Side for Left Return)
G
E
BP
T
T AP
J
1
2
3
4
5
D In
E Out
F HWG In
G HWG Out
H Condensate
Electrical Knockouts Loop Water FPT
HWG FPT
3/4"
1/2"
I 1/2” cond Low Voltage
J 1/2” cond Ext Pump
K 3/4” cond Power Supply
Discharge Connection duct flange installed (±0.10 in) L
M
N Supply Width
O Supply Depth
Return Connection using std deluxe filter rack (±0.10 in) P
022030
in.
22.5
26.5
52.5
35.2
40.2
46.7
49.7
3.6
cm.
57.2
67.3
133.4
89.4
102.1
118.6
126.2
9.1
036072
in.
25.5
31.5
62.5
43.4
48.4
57.0
60.0
3.1
1"
1/2"
47.1
54.9
56.9
9.1
4.8
13.3
13.6
1.5
cm.
64.8
80.0
158.8
110.2
122.9
144.8
152.4
7.9
25.4 mm
12.7 mm
119.6
139.4
144.5
23.1
12.2
33.8
34.5
3.8
19.05 mm 12.7 mm
Q
R Return Depth
S Return Height
T
39.2
47.0
49.0
8.6
6.0
9.3
10.5
1.0
2.2
22.1
26.0
5.6
99.6
119.4
124.5
21.8
15.2
23.6
26.7
2.5
5.6
56.1
66.0
14.2
1.7
28.1
34.0
5.6
4.3
71.4
86.4
14.2 10/1/10
Condensate is 3/4 in. PVC female glue socket and is switchable from side to front. Vertical bottomflow unit shipped with deluxe 1 in. (field adjustable to 2 in.) duct collar/filter rack extending from unit 3.25 in. and is suitable for duct connection. 036-072 bottomflow units use 30 in. x 36 in. air filter.
7
ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL
Vertical Dimensional Data cont. Rear Air Discharge
AIR COIL
Legend AP BP CP CMP
BP
= Alternate Service Panel = Blower Service Panel = Control Access Panel = Compressor Service Panel
BP
AP
CP
AP
1.6
4
Power Supply 3/4" (19.1 mm) HV Knockout
3 5
1/2" (12.7 mm) LV Knockout K
G F
J
2
CP
I
H E
1
D
Primary
FRONT VIEW Right Return
2 ft [61cm] Service Access Points
1.00
B R
Secondary
A
S
L
1.00
A
Q
B
L
P
S
R
U
U
N
N
FILTER RACK CONNECTION
FILTER RACK CONNECTION M
C
C
FRONT
C
C
O
AIR COIL
T
M
O
FRONT
T
AIR COIL
Power Supply 3/4" (19.1 mm) HV Knockout 1.3 5
1/2" (12.7 mm) LV Knockout
AP
J
H
CMP
SIDE VIEW Right Return
REAR VIEW Right Return
Water Connections
Overall Cabinet 1 Vertical Models
022- in. 030 cm. 036- in. 072 cm.
A Width
B C Depth Height*
REAR VIEW Left Return
D In
2 E Out
3 F HWG In
4
G H HWG CondOut ensate
SIDE VIEW Left Return
Electrical Knockouts
5 Loop Water FPT
HWG FPT
3/4"
1/2"
22.3
26.5
48.4
2.3
7.3
13.4
16.4
10.4
56.7
67.3
123.0
5.8
18.5
34.0
41.7
26.4
25.5
31.2
58.4
2.3
7.3
15.9
18.9
11.6
1"
64.8
79.3
148.4
5.8
18.5
40.4
48.0
29.5
25.4 mm
I 1/2” cond Low Voltage
J 1/2” cond Ext Pump
K 3/4” cond Power Supply
KK 3/4” cond Power Supply
K
I
L Filter Rack Width
Discharge Connection duct flange installed (±0.10 in) M N Supply Supply Width Depth
O
P
Return Connection using std deluxe filter rack (±0.10 in)
Q
R
S Return Depth
T Return Height
U 2.0
5.1
10.8
12.8
N/A
2.2
9.5
10.4
37.0
8.5
6.5
2.1
22.0
26.0
13.0
27.4
32.5
N/A
5.5
24.1
26.4
94.0
21.6
16.5
5.3
55.9
66.1
5.1
1/2"
5.6
11.4
13.4
3.7
2.2
13.3
13.6
43.4
9.1
8.1
1.6
28.1
34.0
1.7
12.7 mm
14.2
29.0
34.0
9.4
5.5
33.8
34.6
110.3
23.1
20.6
4.1
71.4
86.4
4.3
19.05 mm 12.7 mm
10/1/10 Condensate is 3/4 in. PVC female glue socket and is switchable from side to front. Vertical unit shipped with deluxe 1 in. (field adjustable to 2 in.) duct collar/filter rack extending from unit 3.25 in. and is suitable for duct connection. Discharge flange is field installed and extends 1 in. [25.4 mm] from cabinet.
8
ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL
Horizontal Dimensional Data Legend Optional 2´ [61cm] Service Access
AP BP CP CMP
AP FRONT
= Alternate Service Panel = Blower Service Panel = Control Access Panel = Compressor Service Panel
CMP
FRONT
Optional 2´ [61cm] Service Access
RIGHT RETURN
LEFT RETURN 2ft [61cm] Service Access
ß [5.3 cm]
ß [5.3 cm]
AP
CMP Optional 2´ [61cm] Service Access
POWER SUPPLY 3/4" KNOCKOUT
H
1.9(4.8 cm)
5
H
1.9(4.8 cm)
LOW VOLTAGE 1/2" KNOCKOUT
4
CONDENSATE
CONDENSATE 5
3
SIDE DISCHARGE
END DISCHARGE
CP
K
I LOW VOLTAGE 1/2" KNOCKOUT 2.9 (7.3 cm) N
SIDE DISCHARGE
G
F
2
J
E
1
D
A
FRONT VIEW
BP
O
END DISCHARGE
O
2.9(7.3 cm)
N
H
C
C
Blower Outlet
M
Filter Rack
M
Blower Outlet
Air Coil Side
Filter Rack
Air Coil Side
L
H
L 2.1 (5.3 cm)
BP
A
RIGHT RETURN END DISCHARGE
2.1 (5.3 cm)
A
LEFT RETURN END DISCHARGE
BP
CMP
FRONT
Blower Outlet
M
FRONT
L
AP
M
Blower Outlet
L
BP N
N
LEFT RETURN SIDE DISCHARGE
RIGHT RETURN SIDE DISCHARGE
FRONT
FILTER RACK CONNECTION
1.8(4.6 cm)
T
T
AP
Q
S
S
Q
C
P
R
CMP
FILTER RACK CONNECTION
R
B
C
FRONT
P
B AIR COIL
RIGHT RETURN RIGHT VIEW
AIR COIL
LEFT RETURN LEFT VIEW
NOTE: *Only models 009 - 030 require four (4) hangers.
Overall Cabinet Horizontal Models
A Width
B C Depth Height*
Water Connections 1
2
3
4
5
D In
E Out
F HWG In
G HWG Out
H Condensate
Electrical Knockouts Loop Water FPT
HWG FPT
I K J 1/2” cond 3/4” cond 1/2” cond Low Power Ext Pump Voltage Supply
Condensate Return Connection using std deluxe filter rack (±0.10 in) 5
Discharge Connection duct flange installed (±0.10 in) L
M N Supply Supply Height Depth
O
P
Q R Return Return Depth Height
S
T
PVC Size
009012
in.
22.5
44.0
17.3
2.3
5.3
11.9
14.9
0.8
1/2"
1/2"
3.8
9.7
11.7
5.9
7.3
9.7
5.8
5.8
17.8
14.6
1.7
1.4
1/2"
cm.
57.2
111.8
43.9
5.8
13.5
30.2
37.8
2.1
12.7 mm
12.7 mm
9.7
24.6
29.7
15.0
18.5
24.6
14.7
14.7
45.2
37.1
4.3
3.6
12.7 mm
015018
in.
22.5
53.0
19.3
2.3
5.3
13.8
16.8
0.8
3/4"
1/2"
cm.
57.2
134.6
49.0
5.8
13.5
35.1
42.7
2.1
022030
in.
22.5
63.0
19.3
2.3
5.3
13.8
13.8
0.8
cm.
57.2
160.0
49.0
5.8
13.5
35.1
35.1
2.1
036038
in.
25.5
72.0
21.3
2.2
7.2
15.8
18.8
0.8
cm.
64.8
182.9
54.1
5.6
18.3
40.2
47.8
2.1
042049
in.
25.5
77.0
21.3
2.2
7.2
15.8
18.8
0.8
cm.
64.8
195.6
54.1
5.6
18.3
40.2
47.8
2.1
060072
in.
25.5
82.0
21.3
2.2
7.2
15.8
18.8
0.8
cm.
64.8
208.3
54.1
5.6
18.3
40.2
47.8
2.1
19.05 mm 12.7 mm 3/4"
1/2"
19.05 mm 12.7 mm 1"
1/2"
25.4 mm 12.7 mm 1"
1/2"
25.4 mm 12.7 mm 1"
1/2"
25.4 mm 12.7 mm
5.9
11.6
13.6
7.0
10.5
9.5
8.2
8.2
21.8
16.5
2.2
1.5
1/2"
14.9
29.5
34.5
17.8
26.7
24.1
20.8
20.8
55.4
41.9
5.6
3.8
12.7 mm
5.9
13.7
15.7
6.5
10.5
9.4
6.5
5.8
30.5
16.5
2.8
1.4
3/4"
14.9
34.7
39.8
16.6
26.5
23.8
16.5
14.6
77.3
41.9
7.1
3.6
19.05 mm
5.9
13.7
15.7
4.9
13.6
13.2
4.6
6.8
35.5
18.7
2.8
1.3
3/4"
14.9
34.7
39.8
12.4
34.6
33.5
11.6
17.2
90.0
47.5
7.1
3.3
19.05 mm
5.9
13.7
15.7
4.9
13.6
13.2
4.6
6.8
40.5
18.5
2.8
1.4
3/4"
14.9
34.7
39.8
12.4
34.6
33.5
11.6
17.2
102.7
47.0
7.1
3.6
19.05 mm
5.9
13.7
15.7
4.9
13.6
13.2
4.6
6.8
45.5
18.6
2.8
1.4
3/4"
14.9
34.7
39.8
12.4
34.6
33.5
11.6
17.2
115.4
47.2
7.1
3.6
19.05 mm
Horizontal unit shipped with deluxe 1 in. (field adjustable to 2 in.) duct collar/filter rack extending from unit 2.88 in. and is suitable for duct connection.
9
10/1/10
ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL
Installing Horizontal Units on the underside of the bottom panel. When attaching the hanger rods to the bracket, a double nut is required since vibration could loosen a single nut. To allow filter access, one bracket on the filter side should be installed 180° from the position shown in the figure below. The unit should be pitched approximately 1/4 in. towards the drain in both directions to facilitate the removal of condensate. Use only the bolts provided in the kit to attach hanger brackets. The use of longer bolts could damage internal parts.
Remove and discard the compressor hold down shipping bolt located at the front of the compressor mounting bracket prior to setting the unit in place. Horizontal units are available with side or end discharge. NOTES: 1) Left (Right) Return Side Discharge cannot be converted to Left (Right) Return End Discharge or vice versa, without additional custom sheet metal parts. Horizontal units are normally suspended from a ceiling by four (009-030 models) or six (036-072 models) 3/8 in. diameter threaded rods. The rods are usually attached to the unit by hanger bracket kits furnished with each unit. 2) In some applications, it is difficult to service the filter with the central hanger bracket, located near the air coil, installed. In these instances, it is permissible to suspend the unit with the five remaining hanger brackets.
Some applications require the installation of horizontal units on an attic floor. In this case, the unit should be set in a full size secondary drain pan on top of a vibration absorbing pad. The secondary drain pan prevents possible condensate overflow or water leakage damage to the ceiling. The secondary drain pan is usually placed on a plywood base isolated from the ceiling joists by additional layers of vibration absorbing material.
Lay out the threaded rods per the dimensions below. Assemble the hangers to the unit as shown. Securely tighten the brackets to the unit using the weld nuts located
CAUTION: Do not use rods smaller than 3/8-inch diameter since they may not be strong enough to support the unit. The rods must be securely anchored to the ceiling.
Figure 2: Horizontal Unit Mounting
Flexible Duct Collar
Threaded Rods Hanging Brackets (Included)
Insulate supply plenum and use at least one 90 O elbow to reduce noise
To Line Power
Hose Kits
To Thermostat
Electrical Disconnect Line Voltage
s Valve Ball
Building Water Loop
10
ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL
Hanger Bracket Locations Figure 3: Hanger Location and Assembly @WUVb
:STb
/
4
!&BV`SORSR @]RPg]bVS`a
!
DWP`ObW]\ 7a]ZOb]`
/W`1]WZ
" 1
0
EOaVS`
" /W`1]WZ
0]ZbO\R :]QYEOaVS`
2
Weight Distribution Table
Hanger Dimensions
Single Speed
015-018 022-030 036 042-048 060-070
Dual Capacity
026 038 049 064 072
cm. in. cm. in. cm. in. cm. in. cm. in. cm. in. cm. in. cm. in. cm. in. cm. in. cm.
99S500A04 99S500A04 99S500A04 99S500A03 99S500A03 99S500A03 99S500A04 99S500A03 99S500A03 99S500A03 99S500A03
A
B
C
D
44.7
25.1
21.4
n/a
113.5
63.8
54.4
n/a
53.7
25.1
21.4
n/a
136.4
63.8
54.4
n/a
63.4
24.8
21.1
n/a
161.0
63.0
53.6
n/a
72.4
27.8
24.1
29.3
183.9
70.6
61.2
74.4
77.4
27.8
24.1
29.3
196.6
70.6
61.2
74.4
82.4
27.8
24.1
29.3
209.3
70.6
61.2
74.4
63.4
24.8
21.1
n/a
161.0
63.0
53.6
n/a
72.4
27.8
24.1
29.3
183.9
70.6
61.2
74.4
77.4
27.8
24.1
29.3
196.6
70.6
61.2
74.4
82.4
27.8
24.1
29.3
209.3
70.6
61.2
74.4
82.4
27.8
24.1
29.3
209.3
70.6
61.2
74.4
Model
009 012 015 018 Single Speed
009-012
in.
Unit Hanger Dimensions
022 030 036 042 048 060 070 026
10/1/10
Dual Capacity
Hanger Kit Part Number
Model
!
6Sf 600 PSI Lockout Low Pressure < 40 PSI Lockout ECM2 RPM < 100 rpm Lockout Microprocessor malfunction* HWL thermistor > 130°F DHW pump switch off
Current Fault Status
Not Used
3
Not Used
8
Pink
1
Pink
12
Yellow
5
Yellow
13
Blue
6
Blue
7
Black
14
Black
Inputs
Outputs
#1 Off, #6 On, #7 On #6 Off, #7 On #6 On, #7 Off Drain pan overflow Y1 Compressor Lo FD thermistor (loop<15°F, well<30°F) Y2 Compressor Hi High Pressure > 600 PSI O RV Low Pressure < 40 PSI G FAN ECM2 RPM < 100 rpm W Not Used SL1 Loop Pump 1 HWL thermistor > 130°F SL2 Loop Pump 2 -DHW pump switch off --
*Green LED not flashing
RV
Switch - High pressure
Orange
10
Diagnostic Modes LED
Capacitor w/ bleed resistor
Not Used
Outputs2 #6 Off, #7 Off Blower Lo Blower Med Blower Hi Aux Heat #1 Aux Heat #2 AuxHeat #3 Aux Heat #4 --
Switch - Low pressure
T
Switch -Hot Water On/Off HWL P
T
2
3
1
Polarized connector
FD LP HP
CA CC CO CR1 CR2CR3 CR4 CS F1 and F2 HE HP ER1 to ER4 LP PB1, PB2 PS RV SW1 SW2 SW3 SW4 TS HWL SC SR FD -
Comfort Alert Compressor Contactor Condensate overflow sensor DHW pump relay Loop pump relay PSC Fan Speed Relay PSC Fan Power Relay Compressor Solenoid Fuses Heater element High pressure switch Aux heat stage relays Low pressure switch Power blocks Power strip Reversing Valve coil DIP package 12 position DIP package 8 position DIP package 5 position Hot water pump enable switch Thermal limit switch Hot water limit sensor Start Contactor Start Relay Freeze Detection Sensor
97P774-11 12/05/06
24
Notes:
25
CC CO CP CP DA DF/FP DH ES HP HWL LP -
Field wire lug
1
3
2
OS PB1, PB2 RCP RV SW1 SW2 SW3 SW4 TB TS FD -
Open Jumper
Occupied Switch Power blocks Rectified Solenoid Compressor Plug Reversing Valve coil DIP package 12 position DIP package 8 position DIP package 5 position Hot water pump enable switch Terminal Board Thermal limit switch Freeze Detection
Closed Jumper
PB2
NOTE 1 Blue (32) LP
OS
ES
NOTE 8
DF/FP
9VDC DI1
DI2 56
55 Orange (30)
54
DI3
DI4
Pink (25)
53
Blk/Wht (29)
Blue (27)
52
DI5 51
Gray (26)
DI6 50
Red (24)
DI 3/4/5/6/ Com
Violet (23)
49
DI7
48
Yellow (21)
Black (22)
DI8
DI9
DI10
47
Blue (72)
46
44 45
Black (5) Orange (71)
Green (70)
DI12
24VAC Com DI11
J9
J10
43
Gray/Wht (14)
42
PWM2
PWM1 PWM2 Com
J7
A11
Blue (10)
1
2
3
CP
41
40
39
5VDC
38
A13 A23
Compressor Contactor Condensate Overflow Sensor Compressor Proving Compressor Solenoid Discharge Air Temperature Sensor Dirty Filter or Fan Proving Dehumidification Switch or Humidistat Emergency Shutdown High Pressure Switch Hot water limit sensor Low Pressure Switch
Compressor Solenoid
Rectified Compressor Solenoid Plug
Polarized connector
Gray (68)
Yellow (50)
LED
37
L1
T1
C
Blk
Yellow (50) Blue (10)
Black (5)
Yellow (35)
Blk/Wht (36)
Violet (15)
G
265-277/60/1
Unit Power Supply
Yellow (18)
Johnson FX-10
A31
Relay ContactsN.O., N.C.
P
36
J2
35
Orange (66)
AI1 +
5VDC
34
Yellow/Red (53) Orange/Wht (67)
31 AI2 +
Gray (65) 33
AI4 +
32
29
Yellow (51)
28
Black (63) Blk/Red (64)
AI5 +
AI3 +
Yellow/Wht (52)
27
AI6 +
26
30
25
Wht/Blue (42)
1K
23 24
White (62)
R
Green/Yel (37)
A21
Ground
NOTE 6
T
11K
Brown (61)
Brown (60)
5VDC
L2
T2
A12
Switch - High pressure
NOTE 7
DA
FD
T
CO
J8
A14 A22
Switch - Low pressure
B
Orange (66) Orange/Wht (67)
A15
A25
Switch - Condensate overflow
7 15
Blue (72) Gray (65)
Black (73)
CC
Red Blue(55)
A32
A24
Capacitor w/ bleed resistor
Relay coil
4 14
Yellow (21)
RB
White
S
Cap
GROUND A35
Quick connect terminal
T
Legend
Temp Occ (TO)
Thermistor
Black (RS)
Black (44)
Black (AIC)
AI Com (AIC)
Room Sensor (RS)
Sensor Com (SC)
Black (Y2) Black (SS)
Comp (Y2)
Setpoint Shift (SS)
10
Orange (71)
Green (70)
Yellow (18)
Violet (15)
Brown (13)
Black
P3
Cap
Blu
A33
RCP
L1
Black (Y1)
Comp (Y1)
Red (33) Black (34)
H M L
Wh
Brn
Compressor
24VAC Com A34
Internal junction
Black (O)
Black (31)
2
Black (G)
Fan (G)
Rev Valve (O) 9
13
NOTE 3
Acc 2 (X2)
5
12
Black (X2)
Black (L) Black (X1)
NOTE 2
Alarm (L)
Acc 1 (X1)
1
6
3 Air flow Settings
NOTE 1
Grn
PSC Fan Motor
24VAC
Factory Low voltage wiring Factory Line voltage wiring Field low voltage wiring Field line voltage wiring Optional block DC Voltage PCB traces Field Zone Sensor Wiring
Zone Sensor Terminal 6
Zone Sensor Terminal 5
Zone Sensor Terminal 2
Zone Sensor Terminal 3
Zone Sensor Terminal 1
Black (R) Black (C)
Green/Yel (38)
24V COM (C)
24VAC (R)
NOTE 4 TB
1 – Disconnect for 15 degree freeze protection. 2 – Acc 1 output is cycled with the compressor. 3 – Acc 2 output is cycled with the fan. 4 – R, C, Y1, Y2, and G inputs are for use with a wall mounted thermostat . TO, SC, RS, AIC, and SS are for use with a TAXXJ02 zone sensor. 5 – Network controllable 24VAC output. 6 – Network controllable PWM output. 7 – Wires 51, 52, & 53 can be configured for a field installable humidity sensor or an A99 temperature sensor. 8 – Network configurable input. 9 – Not Used – Bundled in the air handler.
D01
D02
D03
10
D04
1
2
3
4
5
6
7
8
9
11
12
13
14
15
16
D05
D06
D07
18
D08 17
19
20 D09
Brown (13)
Black (34)
A
Black (F1)
Black (F2)
Black (F3)
Black (F4)
Black (F5)
Black (F6)
Black (F7)
Black (F8)
Black (F9)
Black (F10)
Black (F11)
Black (F12)
Black (F13)
Black (F14)
Black (F15)
Black (F16)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18 Black (F17)
19
Black (F19)
20
Black (F18)
Black (F20)
Red (33)
Black (1)
Yellow (J1)
Violet (3)
White (4)
Black (5)
Black (6)
Orange (7)
Yellow (J1)
Yellow (J2)
Blue (10)
Gray (11)
Yellow (12)
Brown (13)
Violet (15)
Yellow (J2)
Yellow (17)
Yellow (18)
Gray (19)
Yellow (20)
265V 277V
HP
NOTE 5
Blue
Violet (3)
CC
Orange (40)
RV
NOTE 5
Black (34)
Red (33)
Transformer RB
Black (74)
97P774-18
Blk/Wht (43)
1
2
3
PB1
Yellow
Blk/Wht
Yellow (50)
2/16/07
Violet (28)
P12
10
15
12
3
1
NOTE 9
Grn/Yel (57)
ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL
Wiring Schematics cont.
FX10 Control 265-270/60/1 - PSC Motor
NOTE 7 Optional Electronic Air-Filter
Optional Remote Unit Without Loop Pump
SL1 Out
SL1 In
C
NOTE 2
NOTE 9
L1
G
O
W
Y2
Y1
C
R
Blue
Blue
Violet(2)
Blk(1)
Thermostat
CC
RCP
CS
NOTE 11
Used
3
R
G Y
R R
R R R
3
2
2
Acc NO
1
1
Acc NC
7
Acc Com
P3
NOTE 3
6
5
Not
4
SL1 In
SL1 Out
P4
On
LED
Drain Water Flow High Press Low Press / Comp Air Flow Status DHW Limit DHW off
*Green LED not flashing
SW1 1 2 3 4 5
Diagnostic Modes Inputs
P5
Outputs
Not Used
Black
#6 Off, #7 Off Blower Lo Blower Med Blower Hi Aux Heat #1 Aux Heat #2 AuxHeat #3 Aux Heat #4 --
Outputs2
Black
7 14
Blue
Blue
13 6
Pink Yellow
5
Pink Yellow
1
8 12
Orange Not Used Not Used
2
3
Orange
Tan
10
9
4
11
#1 Off, #6 On, #7 On #6 Off, #7 On #6 On, #7 Off Drain pan overflow Y1 Compressor Lo FD thermistor (loop<15°F, well<30°F) Y2 Compressor Hi High Pressure > 600 PSI O RV Low Pressure < 40 PSI G FAN ECM RPM < 100 rpm W Not Used SL1 Loop Pump 1 HWL thermistor > 130°F SL2 Loop Pump 2 -DHW pump switch off --
Current Fault Status
Main Logic PCB
2 Speed / 1 Speed Normal / Finish on 2nd (Note 6) No RPM / RPM Electric Heat / Normal (Note 8) N or R Series / E Series or Premier
Field Selection Dips - #1 On, #6 On, #7 On Drain pan overflow Lockout FD thermistor (loop<15°F,well<30°F) Lockout High Pressure > 600 PSI Lockout Low Pressure < 40 PSI Lockout ECM RPM < 100 rpm Lockout Microprocessor malfunction* HWL thermistor > 130°F DHW pump switch off
Normal Display Mode
Test / Norm Loop / Well Fan / Comp Dehum / Norm No Htg3 / Htg3 Inputs / Norm Outputs / Norm Pulse L / Constant L (NOTE 9)
On
2
SW3
Not Used
16
1
C
1 2 3 4 5 6 7 8
Red
On
Tan
3 11
P2
Shut Down
SW2
White
1
1 2 3 4 5 6 7 8 9 10 11 12
Pink
2
NOTE 10
Blue
3
Orange
C
Not Used
ECM2 Air Flow Settings
Violet Blue
Yellow
4 5
7
Black
Not Used
9
8
LO
C
Not Used
G
P6 8 13
R
6
7
O
COM
15
6
W
CR4
Premier 2 Microprocessor Logic Control (DC Voltage)
COM
NC
10
5
Y2
CR3
NO
Gray
4
COM
NC
240V L1
Brown
3
Y1
CR2
NO
F1-10A 240V
240V L2
12
2
C
COM
NO
240V L2
Brn(8)
Gry/Wht(5)
Blk/Wht(4)
NOTE 4
14
1
P1 R
CC-GND
CC
CCHI
CR1
NO
Fused L2
Org(7)
L1
3 PS
1
2
T
T
RV
Yel
Blk
Blk/Wh
24V
HP
LP
FD
HWL
CO
Transformer
Red Blu 208V 240V
L1
CA CC CO CR1 CR2CR3 CR4 CS F1 and F2 HE HP ER1 to ER4 LP -
Transformer Switch NOTE 1 208V 240V
Blk/Wht (6)
2
3
C2
3
P11
8
P
2
Legend
15 16 10
Comfort Alert Compressor Contactor Condensate overflow sensor DHW pump relay Loop pump relay PSC Fan Speed Relay PSC Fan Power Relay Compressor Solenoid Fuses Heater element High pressure switch Aux heat stage relays Low pressure switch
Fuse
Relay ContactsN.O., N.C.
Ground
Field wire lug
Wire nut
5
ECM Fan Motor
4
Factory Low voltage wiring Factory Line voltage wiring Field low voltage wiring Field line voltage wiring Optional block DC Voltage PCB traces Internal junction Quick connect terminal
1
Grn
Org
Brn
1
PB1, PB2 PS RV SW1 SW2 SW3 SW4 TS HWL SC SR FD -
3
G
T
6
5
4
3
2
P10 1
P12
Thermistor
Power blocks Power strip Reversing Valve coil DIP package 12 position DIP package 8 position DIP package 5 position Hot water pump enable switch Thermal limit switch Hot water limit sensor Start Contactor Start Relay Freeze Detection Sensor
Polarized connector
Switch -Hot Water On/Off
Switch - Low pressure
Switch - High pressure
Switch - Condensate overflow
Capacitor w/ bleed resistor
Relay coil
Light emitting diode - Green
Red
Tan
White
Pink
Blue
Orange
Gray
Blue
Yellow
Violet
Black
Org
Brn
1
Grn
2
C2 3
3
5
ECM Fan Motor
4
P4
15 16 10
1 2 3
P11
N.O.
P12
6
7 C Y1 Y2 W O G
5
1
2
3
CR3-
Com
N.C. N.O.
8
2 C
1 Shut Down
SW2 Off On 1 2 3 4 5 6 7 8
P2 C
3
Microprocessor
4 SL1 IN
6 SL1 SL2 Out IN
5
SW3 Off On 1 2 3 4 5
5
Blk
4
P2
Premier 2 Logic Board
1 2 3 4 5 6 7 8 9 10 11 12
L
SW1 Off On
R
4
N.O.
CR2- Loop Pump
2
P1
F1
P10
Yel
Or
Pink
Brn
L2
4
L4
5
3
2
E-Series Logic Board - Physical Layout
1
3
C C R R
CC-GND CC CCLO CCHI
CR1- DHW Pump
8
Violet
Blu
Grn
1
P9
G
SL2 Out
7
6
1
Gray
L1
L1
NO
ER4
NO
ER3
NO
ER2
NO
ER1
1
3 4 5 6
1 2
2 3 4 5 6 7 8
2
7 P3
8 9 10 11 12 13 14
9 10 11 12 13 14 15 16
Com
3 ACC ACC ACC NO NC COM
1
CR4-
N.O.
F1
L3
PB2
EA Series PCB
F2
NOTE 5 L2
P8
P5
P6
Yel
Pink
HE4
HE3
HE2
HE1
TS4
TS3
TS2
TS1
L2
L1
L2
Unit Power 208-230/60/1
97P774-12 12/05/06
9 – SW2-8 must be in the OFF position for pulsed “L” lockout signal and in the ON position for constant “L” lockout signal. 10 - Air Flow Configuration Example: SW1 configured for dip 1 as low, dip 3 as medium, and dip 5 as high Speed ECM2 fan 11 – Dual Capacity units only.
4 - The blk/wh and gray/wh wires are removed when Aux Heat is installed . 5 - Buss lugs L1 and L2 can be removed and dual power wire sets connected directly to box lugs L 1, L2, and L3, L4. 6 - This Switch allows the unit to down stage with the t -stat when OFF and finish on second stage when ON. Finish second stage reduces stage changing in recip dual capacity compressors and should be ON for unzoned Dual Cap E -Series or Premier 2 speed units. 7 - When optional electronic air -filter is installed, power for the electronic air-filter is provided by P2-2 and 24 VAC. 8 – SW3-4 should be in the OFF position when using the 17P501A01 electric heat board and should be ON when using the 17P514A01 electric heat board .
Notes:
L2
Circuit Breakers
L1
Aux Elect Power 208-230/60/1
L1
Breaker box furnished by installer
Single Disconnect Power 208-230/60/1
CSA installed units only Local codes may require a single source of power supply
Pink
Yel
Blk
Gray
1 - Place switch to 208V position to operate unit at 208V. 2 - Connection of remote unit that does not have a loop pump for slave operation . 3 - 24V Accessory relay (see SW2 - 3 for description of operation )
Pink
Yel
3 4
Blk
Gray
Gray
Blk
Yel
Pink
2
1
P7
1
Gray
Blk
2
Gray
3
Blk
4
Yel
Pink
G
Premier Control 208-230/60/1 - ECM Motor
SW4
Status LED PCB
L2
F1-10A 240V
Blue (10)
On/Off
Run Capacitor
RPM
Fused L2
G
PWM
T1
RPM grnd
T2 CC
On/Off
Unit Power 208-230/60/1
RPM
Black
PWM
240V - L1
Red
Fused L1
Blue
Fused L2
26
Fused L2
RPM grnd
240V - L1
Auxiliary Electric Heat Power 208-230/60/1
Fused L2
With optional ' EA' Series Auxiliary ElectricHeat Typical schematic shown
Fused L2
T1
240V - L2
T3
240V - L2
T2
ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL
Wiring Schematics cont.
Blk(1)
G
Wht(4)
Yel(6) Blk(5)
Pump
2
7
8
Y2
W
O
G
LO
Y2
W
O
G
L1
NOTE 10 Optional Electronic Air-Filter
Optional Remote Unit Without Loop Pump
SL1 Out
SL1 In
C
NOTE 2
NOTE 9
7
SW4
Y R
G
R R
R
R
R
3
Acc NO
2
2
Acc NC
1
1
Acc Com
P3
NOTE 3
6
Not
Used
5
3
2
4
C
C
SL1 In
SL1 Out
LED
1 2 3 4 5 6 7 8
1 2 3 4 5
2 Speed / 1 Speed Normal / Finish on 2nd (Note 12) No RPM / RPM Old EH & ECM / Normal (Note 8) Envision / E Series or Premier
Field Selection Dips - #1 On, #6 On, #7 On Drain Drain pan overflow Lockout Water Flow FD thermistor(loop<15°F,well<30°F) Lockout High Press High Pressure Low Press/CA Low Pressure / Comfort Alert Air Flow ECM RPM < 100 rpm Lockout Status Microprocessor malfunction* DHW Limit HWL thermistor > 130°F DHW off DHW pump switch off *Green LED not flashing
Normal Display Mode
Inputs
Outputs
#1 Off, #6 On, #7 On #6 Off, #7 On #6 On, #7 Off Y1 Compressor Lo Drain pan overflow FD thermistor (loop <15°F, well<30 °F) Y2 Compressor Hi High Pressure O RV Low Pressure / Comfort Alert G FAN ECM RPM < 100 rpm W DHW Pump Not Used SL1 Loop Pump1 HWL thermistor> 130°F SL2 Loop Pump 2 -DHW pump switch off --
Current Fault Status #6 Off, #7Off Blower Lo Blower Med Blower Hi Aux Heat #1 Aux Heat #2 Aux Heat #3 Aux Heat #4 --
Outputs2
Black
T
T
HP
LP
FD
HWL
Comfort Alert Status Description Module Has Power Y1 Present But Compressor Not Running Long Run Time System Pressure Trip Short Cycling Locked Rotor Open Circuit Open Start Circuit Open Run Circuit Welded Contactor Low Voltage
Comfort Alert
LED Flash Code Green Solid Red Solid Code 1 Code 2 Code 3 Code 4 Yellow Code 5 Code 6 Code 7 Code 8 Code 9
Black
7 14
Blue
Blue
13 6
Pink Yellow
5
Pink Yellow
1
Not Used
3 8 12
Orange Not Used
L
NOTE 11
2
Orange
Tan
10
9
4
P5
Diagnostic Modes
L1
Thermistor
CA CC CO CR1 CR2CR3 CR4 CS F1 and F2 FD HE HP ER1 to ER4 -
Comfort Alert Compressor Contactor Condensate overflow sensor DHW pump relay Loop pump relay PSC Fan Speed Relay PSC Fan Power Relay Compressor Solenoid Fuses Freeze drotection sensor Heater element High pressure switch Aux heat stage relays
Fuse
Relay ContactsN.O., N.C.
Ground
Field wire lug
Wire nut
P
2
Pink
2
1
6
5
LP PB1, PB2 PS RV SW1 SW2 SW3 SW4 TS HWL SC SR -
3
G
T
Blue
9
11
Main Logic PCB
Legend
Pink
Orange
10
Factory Low voltage wiring Factory Line voltage wiring Field low voltage wiring Field line voltage wiring Optional block DC Voltage PCB traces Internal junction Quick connect terminal
Blue
3
Not Used
6 15
Light emitting diode - Green
Low pressure switch Power blocks Power strip Reversing Valve coil DIP package 12 position DIP package 8 position DIP package 5 position Hot water pump enable switch Thermal limit switch Hot water limit sensor Start Contactor Start Relay
Polarized connector
Switch-Hot Water On/Off
Switch- Low pressure
Switch- High pressure
Switch- Condensate overflow
Capacitor w/ bleed resistor
Relay coil
Red
Tan
White
2
Not Used
12
4
Orange
P10 1
Gray Brown
14
Gray
Blue
Blue
5
P12
Violet
RV
8
Black
NOTE 7
Test / Norm Loop / Well Fan / Comp Dehum / Norm No Htg3 / Htg3 Inputs/ Norm Outputs/ Norm Pulse L / Constant L
P11
Yellow
SW1
On
5
ECM Fan Motor
4
3 15 16 10
3
Violet
2
Black
CO
Transformer
1
Grn
Yellow
Not Used
Blk/Wh
24V
Red Blu 208V 240V
Org
Brn
4
Yel
Blk
Org
Brn
P4
2
3
C2
1 2 3
1
Grn
3
5
ECM Fan Motor
4
With optional ' EA' Series Auxiliary Electric Heat Typical schematic shown
7
P6 8
PS
3
1
2
Common
Start
Active
C2
13
C
R
Red
On
Fused L1
NOTE 1
Not Used
SW3
COM
240V L1
Brn(15)
Gry/Wht(10)
Blk/Wht(11)
Pink
NOTE 4
16
1 2 3 4 5 6 7 8 9 10 11 12
Blk(7)
NC
F1-10A 240V
240V L2
Org(14 )
T1
L1
11
On
CR4
Premier 2 Microprocessor Logic Control (DC Voltage)
COM
NO
T2
L2
Shut Down
CR3
NC
240V L2
Tan (16)
Tan
SW2
COM
NO
Fused L2
Gry(9)
Run Capacitor
Black
White
ECM2 Air Flow Settings
CR2
NO
Fused L2
Yel(8)
G
CC
3
P4
NOTE 6
Pink(13)
Pink
DHW Pump
Blu
1
Unit Power 208-230/60/1
1
1
COM
Blu(17)
1
2
P2
3
6
5
4
3
1
C
Y1
C
R
Y1
CC-GND
CC
CCHI
CR1
NO
3A Fuse
P1 R
Thermostat
CC
Violet(3) Violet(2)
Comfort C Alert Y2Y
R
Pump
PB1
2
F1-10A 240V
Blue
RPM
CS
PWM
+ -
IntelliStart
On/Off
Run Winding IntelliStart
RPM grnd
DC SOL
Red
15 16 10
P11
2
3
4
P1
8
5
F1
6
N.O.
P10
Com
N.C. N.O.
CR3-
1
8
1 2 3 4 5 6 7 8 9 10 11 12
2 C
1 Shut Down
SW2 Off On
1 2 3 4 5 6 7 8
P2 C
3
Microprocessor
4
SL1 Out
5
SW3 Off On
SL 1 IN
2
3
SL2 IN
6
1 2 3 4 5
SL 2 Out
7
P2
5
ACC NO
1
CR4-
L1
L1
NO
ER4
NO
ER3
NO
ER2
NO
ER1
PB2
L3
3
P5
P6
EA Series PCB
ACC ACC NC COM
2
1 2 3 4 5 6 7 16 8 8 1 9 2 10 3 11 4 12 5 13 6 14 7 P3
9 10 11 12 13 14 15
Com
6
1
F2
NOTE 5 L2
Gray
N.O.
F1
4
Blk
Or
L2
Brn
Yel
L4
4
Pink
G
Auxiliary Electric Heat Power 208-230/60/1
5
3
2
P9 1
Premier 2 Logic Board
CR2- Loop Pump
7
Grn
Logic Board - Physical Layout
SW 1 Off On
P12
R C Y1 Y2 W O G L
1
C C R R
CC-GND CC CCLO CCHI
CR1- DHW Pump
N.O.
Blu Violet
PWM
Comfort Alert
1
On/Off
240V - L1
RPM grnd
Ext Pump 1/2 hp Total 208-230/60/1
Status LED PCB
RPM
240V - L1
Red
Fused L1
Black
Fused L2
27
Fused L2
PB2 2
Fused L2
C
Fused L2
S
240V - L2
R
240V - L2
Blue
P8
Pink
4
C
R
L
Y
Y2
Pink
Yel
Blk
Gray TS1
TS4
TS3
TS2
L2
L2
L2
Unit Power 208 -230/60/1
L1
Circuit Breakers
L1
Aux Elect Power 208-230/60/1
L1
Breaker box furnished by installer
Single Disconnect Power 208-230/60/1
CSA installed units only Local codes may require a single source of power supply
HE4
HE3
HE2
HE1
97P774-51
2/23/09
Notes: 1 - Switch Blue and Red wires for 208V operation. 2 - Connection of remote unit that does not have a loop pump for slave operation. 3 - 24V Accessory relay (see SW2 -3 for description of operation) 4 - The blk/wh and gray/wh wires are removed when Aux Heat is installed. 5 - Buss lugs L1 and L2 can be removed and dual power wire sets connected directly to box lugs L1, L2, and L3, L4. 6 - DHW pump only in models with hot water generation option. 7 - Air Flow Configuration Example: SW1 configured for dip 1 as low, dip 3 as medium, and dip 5 as high Speed ECM2 fan 8 - SW3-4 should be in the OFF position when using ECM motor and 17P501A01 electric heat board and should be ON when using ECM2 with 17P514A01 electric heat board 9 - SW2-8 must be in the OFF position for pulsed “L” lockout signal and in the ON position for constant “L” lockout signal. 10 - When optional electronic air-filter is installed, power for the electronic air-filter is provided by P2-2 and 24 VAC. 11 - Comfort Alert fault output to Premier Control Board 12 - This Switch allows the unit to down stage with the t-stat when OFF and finish on second stage when ON. Finish second stage reduces stage changing in recip dual capacity compressors and should be ON for unzoned Dual Cap E-Series or Premier 2 speed units.
ALERT TRIP
DC Sol
Data Port
POWER
Pink
Yel
Comfort Alert Physical Layout
Yel
Blk 3
Gray
Gray
Blk
Yel
Pink
2
1
P7
1
Gray
Blk
2
Blk
Gray
3
4
Yel
Pink
G
ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL
Wiring Schematics cont.
Premier Control 208-230/60/1 with IntelliStart - ECM Motor
28
CC CO CP CP DA DF/FP DH ES HP HWL LP -
Factory Low voltage wiring Factory Line voltage wiring Field low voltage wiring Field line voltage wiring Optional block DC Voltage PCB traces Field Zone Sensor Wiring
Relay ContactsN.O., N.C.
Compressor Solenoid
1
3
2
OS PB1, PB2 RCP RV SW1 SW2 SW3 SW4 TB TS FD -
Occupied Switch Power blocks Rectified Solenoid Compressor Plug Reversing Valve coil DIP package 12 position DIP package 8 position DIP package 5 position Hot water pump enable switch Terminal Board Thermal limit switch Freeze Detection Sensor
Closed Jumper
Open Jumper
Polarized connector
PB2 3
1
2
NOTE 1 Blue (32) LP
OS
ES
NOTE 9
DF/FP
CP
NOTE 6
29
Yellow (51)
46
J9
DI10
44 45
Black (5) Green (70) Orange (71)
DI5
DI1
9VDC
56
55
Blk/Wht (29) Orange (30)
DI2
DI3
54
53
Pink (25)
Blue (27)
DI4
DI6
51 52
50
Gray (26)
Red (24)
DI 3/4/5/6/ Com
Violet (23)
49
DI7
48
Yellow (21)
Black (22)
DI8
47
Blue (72)
DI9
DI11
24VAC Com
PWM2
DI12
42
41
43
Gray/Wht (14)
Gray (68)
40
J10
38
Orange/Wht (67)
PWM1 PWM2 Com
LED 5VDC
36 37
Orange (66)
39
AI1 +
33 35
Yellow/Red (53)
Yellow (50)
AI2 + 5VDC
32 34
Yellow/Wht (52)
A13 A23
Compressor Contactor Condensate Overflow Sensor Compressor Proving Compressor Solenoid Discharge Air Temperature Sensor Dirty Filter or Fan Proving Dehumidification Switch or Humidistat Emergency Shutdown High Pressure Switch Hot water limit sensor Low Pressure Switch
P
Switch - Low pressure
Switch - High pressure
28 30
Black (63) Blk/Red (64) 31
AI6 +
27
Gray (65)
AI4 +
26
AI5 +
25
White (62)
AI3 +
5VDC
Brown (61)
J2
J8
Wht/Blue (42)
1K
23 24
A21
Switch - Condensate overflow
T
T
CO
11K
A12 A22
Capacitor w/ bleed resistor
NOTE 7
DA
FD
Brown (60)
L2
Green/Yel (37)
L3
A25
Relay coil
Black (44)
Orange/Wht (67)
L1
A14
Quick connect terminal
T
Thermistor
Temp Occ (TO)
B
15
Orange (66)
N
A15
A24 A11 J7
Violet (15)
Blue (10) Blue
Yellow (50)
Black (5)
Yellow (35)
Blk/Wht (36)
Yellow (18)
Johnson FX-10
A31
Rectified Compressor Solenoid Plug
Black (RS)
Room Sensor (RS)
7
Gray (65)
PB3
A32
A35
Ground
Black (AIC)
AI Com (AIC)
14
Blue (72)
Yellow (21)
Red (56)
Blue (55)
Black (54)
G
24VAC Com
Field wire lug
Black (SS)
4
10
L1
Unit Power 460/60/3 With Neutral
A33
RCP
L1
Black (Y2)
Comp (Y2)
Yellow (18) Green (70) Orange (71)
L2
L3
CC
T1
Black
GROUND A34
Internal junction
Black (Y1)
Comp (Y1)
Setpoint Shift (SS)
Black (31)
Black (O)
Sensor Com (SC)
2
Black (G) 9
13
Black (X2)
Violet (15)
Brown (13)
Black (34)
Red (33)
T2
C
24VAC
Legend
Zone Sensor Terminal 6
Zone Sensor Terminal 5
Zone Sensor Terminal 2
Zone Sensor Terminal 3
Zone Sensor Terminal 1
NOTE 3
Fan (G)
Rev Valve (O)
Acc 2 (X2)
5
Black (X1)
NOTE 2
Acc 1 (X1)
1 12
Black (L)
6
Black (C)
Black (R)
Alarm (L)
Green/Yel (38)
24V COM (C)
24VAC (R)
NOTE 4 TB
S Blue
T3
Red
R
D01
D02
D03
1
2
3
4
5
6
7
8
9
11 10
D04
12
13
14
15
16
D05
D06
D07
18
D08 17
19
20
Black (34)
D09
Brown (13)
Black (F1)
Black (F2)
Black (F3)
Black (F4)
Black (F5)
Black (F6)
Black (F7)
Black (F8)
Black (F9)
Black (F10)
Black (F11)
Black (F12)
Black (F13)
Black (F14)
Black (F15)
Black (F16)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
Black (F17)
19
Black (F19)
20
A
Black (F18)
Black (F20)
Red (33)
Black (1)
Yellow (J1)
Violet (3)
White (4)
Black (5)
Black (6)
Orange (7)
Yellow (J1)
Yellow (J2)
Blue (10)
Gray (11)
Yellow (12)
Brown (13)
Violet (15)
Yellow (J2)
Yellow (17)
Yellow (18)
Gray (19)
Yellow (20)
HP
NOTE 5
Black Blue 460V
RV
CC
Orange (40)
NOTE 5
Black (34)
Red (33)
Transformer Violet (3)
Black/Wht (43)
1
2
3
PB1
Yellow
Blk/Wht
Blue Blue
CS NOTE 8
97P774-23
RCP
Violet (28)
Orange
2
1
C1 Grn/Yel (57)
1
Green
Brown
3
4
5
ECM Fan Motor
P11
12 15
P12
Yellow (50)
10
2/16/07
Violet (28)
3
R
1 – Disconnect for 15 degree freeze detection. 2 – Acc 1 output is cycled with the compressor. 3 – Acc 2 output is cycled with the fan. 4 – R, C, Y1, Y2, and G inputs are for use with a wall mounted thermostat . TO, SC, RS, AIC, and SS are for use with a TAXXJ02 zone sensor. 5 – Network controllable 24VAC output. 6 – Network controllable PWM output. 7 – Wires 51, 52, & 53 can be configured for a field installable humidity sensor or an A99 temperature sensor. 8 – Dual Capacity only. 9 – Network configurable input.
G
Compressor
C2
WARNING: Neutral wire required. PWM
Notes:
ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL
Wiring Schematics cont.
FX10 Control 460/60/3 - ECM Motor
ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL
Envision Controls - Premier Shutdown Mode A 24VAC common signal to the “shutdown” input on the control board puts the unit into shutdown mode. Compressor, hot water pump and blower operation are suspended.
Safety Controls The Envision control receives separate signals for a high pressure switch for safety, a low pressure switch to prevent loss of charge damage, and a low suction temperature thermistor for freeze sensing. Upon a continuous 30-second measurement of the fault (immediate for high pressure), compressor operation is suspended, the appropriate lockout LED begins flashing. (Refer to the “Fault Retry” section below).
Standard Premier Microprocessor The Premier control system is a microprocessor-based printed circuit board conveniently located in the unit control box for accessibility. The microprocessor control is specifically designed for the Envision Series heat pumps and integrate single speed and dual capacity compressors, variable speed ECM blower motors and advanced features needed in geothermal applications. All variable speed ECM airflow selections are conveniently configured on the control via DIP switches. The microprocessor provides control of the entire unit as well as outputs for status modes, faults, and diagnostics. Removable low voltage thermostat terminal strips provide convenient field connections. LEDs are located on the front of the cabinet for quick inspection without removing any access panels.
Testing The Envision control allows service personnel to shorten most timing delays for faster diagnostics.
Fault Retry All faults (except for low RPM faults with the ECM blower motor) are retried twice before finally locking the unit out. An output signal is made available for a fault LED at the thermostat. The “fault retry” feature is designed to prevent nuisance service calls.
Diagnostics The Envision control board allows all inputs and outputs to be displayed on the LEDs for fast and simple control board diagnosis.
Startup The unit will not operate until all the inputs and safety controls are checked for normal conditions. At first powerup, a four minute delay is employed before the compressor is energized.
Resistance Heat Control (208-230 Units)
Component Sequencing Delays
The electric heat control module contains the appropriate high-voltage control relays. Control signals energize the relays in the proper sequence, and the LED display board indicates which stages are energized.
Components are sequenced and delayed for optimum space conditioning performance.
Heating Operation Heat, 1st Stage (Y1)
Accessory Relay An accessory relay on the control board allows for field connection of solenoid valves, electronic air cleaners, etc. The accessory relay has a normally open output and a normally closed output.
The blower motor is started on low speed immediately (PSC ON), the loop pump is energized 5 seconds after the “Y1” input is received, and the compressor is energized on low capacity 10 seconds after the “Y1” input. The blower is switched to medium speed 15 seconds after “Y1” input (ECM only).
Short Cycle Protection
Heat, 2nd Stage (Y1,Y2) Single-Speed Units
The control employs a minimum “off” time of four minutes to provide for short cycle protection of the compressor.
Blower changes to high speed 15 seconds after the “Y2” input (ECM only).
Condensate Overflow Protection
Heat, 2nd Stage (Y1,Y2) Dual Capacity Units
The Envision control board incorporates an impedance sensing liquid sensor at the top of the drain pan. Upon a continuous 30-second sensing of the condensate, compressor operation is suspended (see Fault Retry), and the condensate overflow lockout LED begins flashing.
The second stage compressor will be activated 5 seconds after receiving a “Y2” input as long as the minimum first stage compressor run time of 1 minute has expired. The ECM blower changes from medium to high speed 15 seconds after the “Y2” input. 29
ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL
Envision Controls - Premier cont. NOTE: Blower speed can change automatically only with an ECM Motor.
Heat, 3rd Stage (Y1,Y2,W) Single-Speed Units The first stage of resistance heat is energized 10 seconds after “W” input, and with continuous 3rd stage demand, the additional stages of resistance heat engage sequentially every 5 minutes.
ECM Airflow Selection DIP Switches (SW1) A 12-position DIP switch package on the Envision control allows the airflow levels to be set for low, medium and high speed. (Refer to Blower Performance Data - ECM Motor). Only three of the DIP switches can be in the “on” position. The first “on” switch (the lowest position number) determines the “low speed blower” setting. The second “on” switch determines the “medium speed blower” setting, and the third “on” switch determines the “high speed blower” setting.
Heat, 3rd Stage (Y1,Y2,W) Dual Capacity Units The 1st stage of resistance heat is energized 10 seconds after “W” input, and with continuous 3rd stage demand, the additional stages of resistance heat engage sequentially every 5 minutes.
Emergency Heat (W only) The blower is started on high speed, and the first stage of resistance heat is energized 10 seconds after the “W” input. Continuing demand will engage the additional stages of resistance heat sequentially every 2 minutes.
Lockout Conditions During lockout mode, the appropriate unit and thermostat lockout LEDs will illuminate. The compressor, loop pump, hot water pump, and accessory outputs are de-energized. Unless the lockout is caused by an ECM low RPM fault, the blower will continue to run on low speed. If the thermostat calls for heating, emergency heat operation will occur.
Cooling Operation In all cooling operations, the reversing valve directly tracks the “O” input. Thus, anytime the “O” input is present, the reversing valve will be energized.
All lockout modes can be reset at the thermostat after turning the unit off, then on, which restores normal operation but keeps the unit lockout LED illuminated. Interruption of power to the unit will reset a lockout without a waiting period and clear all lockout LEDs.
Cool, 1st Stage (Y1,O) The blower motor and hot water pump are started immediately, the loop pump(s) is energized 5 seconds after the “Y1” input is received. The compressor will be energized (on low capacity for Dual Capacity units) 10 seconds after the “Y1” input. The ECM blower will shift from low to medium speed 15 seconds after the “Y1” input (85% of medium speed if in dehumidification mode).
High Pressure This lockout mode occurs when the normally closed safety switch is opened momentarily (set at 600 psi).
Low Pressure Cool, 2nd Stage (Y1, Y2, O) Single Speed Units
This lockout mode occurs when the normally closed low pressure switch is opened for 30 continuous seconds (set at 40 psi).
The blower changes to high speed (85% of high speed if in dehumidification mode) 15 seconds after the “Y2” input (ECM only).
Freeze Detection (Water Flow)
Cool, 2nd Stage (Y1, Y2, O) Dual Capacity Units The second stage compressor will be activated 5 seconds after receiving a “Y2” input as long as the minimum first stage compressor run time of 1 minute has expired. The ECM blower changes to high speed 15 seconds after the “Y2” input. (85% of high speed if in dehumidification mode).
This lockout mode occurs when the freeze thermistor temperature is at or below the selected freeze sensing point (well 30°F or loop 15°F) for 30 continuous seconds.
Condensate Overflow
Blower (G only)
This lockout mode occurs when the condensate overflow level has been reached for 30 continuous seconds.
The blower starts on low speed (PSC ON). Regardless of blower input “G” from thermostat, the blower will remain on low speed for 30 seconds at the end of each heating, cooling or emergency heat cycle.
Blower RPM The control board monitors blower RPM to sense operation. This lockout mode occurs if the blower RPM falls below the low RPM limit (100 RPM) for 30 continuous seconds (ECM only).
A DIP switch on the Envision control allows field selection of 15% reduced blower speeds for cooling in the dehumidification mode or medium and high blower speeds for cooling in the normal mode.
30
ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL
Envision Controls - Premier cont. DIP Switch Settings Prior to powering unit, ensure that all DIP switches on SW2 and SW3 are set properly according to the tables below. FACTORY SETUP DIP SWITCHES (SW3) DIP SWITCH NUMBER
DESCRIPTION
OFF POSITION
ON POSITION
SW 3-
1
Dual Capacity/Single-Speed Configures the control for single-speed compressor operation or dual capacity operation.
Dual Capacity Operation
Single-Speed Operation
SW 3-
2
Zoned/Finish on Second Stage This switch allows the unit to down stage with the thermostat when off and finish with second stage when on. Finish on second stage reduces stage changing in reciprocating dual capacity compressors.
Normal - All Other Systems
Finish on 2nd - Unzoned Dual Capacity E Series or Premier 2 Speed
SW 3-
3
No RPM/RPM Configures the control to monitor the RPM output of an variable speed ECM blower motor. When using IntelliZone or a PSC blower motor, the control should be configured for “NO RPM” sensing.
PSC Blower/RPM Monitoring Disabled
ECM Blower/RPM Monitoring Enabled
SW 3-
4
Electric heat and Variable Speed ECM Allows backward compatibility with older P Series. In the Off position this switch allows older electric heat board (17P501A01) and older ECM (square end) compatibility. On is for all newer EH board (17P514A01) and ECM (round end).
Old EH and Old ECM
Normal
SW 3-
5
On dual capacity units this switch allows stage change: on the fly when off, and 1 minute delay when on. A delay is required on all reciprocating dual capacity units.
Envision
E Series or P Series
FACTORY SETUP DIP SWITCHES (SW3) DIP SWITCH NUMBER
DESCRIPTION
OFF POSITION
ON POSITION
SW 2-
1
Service Test Mode On the control, allows field selection of “NORMAL” or “TEST” operational modes. Test mode accelerates most timing functions 16 times to allow faster troubleshooting. Test mode also allows viewing the “CURRENT” status of the fault inputs on the LED display.
Test Mode
Normal Speed Operation
SW 2-
2
Freeze Detection Sensing This DIP switch allows field selection of low source water thermistor fault sensing for well water (30°F) or antifreeze-protected (15°F) earth loops.
Loop Water Freeze Detection 15° F
Well Water Freeze Detection 30° F
SW 2-
3
Accessory Relay Allows field selection of the accessory relay to operate with the compressor or blower.
Acc Relay Tracks Blower
Acc Relay Tracks Compressor
SW 2-
4
Blower Speed Control Allows field selection of reduced blower speed (85% of selected medium and high speed – variable speed ECM only) for cooling in the dehumidification mode.
Dehumidification Blower Speeds
Normal Blower Speeds
SW 2-
5
Auxiliary Off Disables 3rd-stage Heating. Full emergency heat would still be available if needed.
Disable Heating Stage 3
Enable Heating Stage 3
SW 2-
6
Diagnostics Inputs Allows viewing the inputs from the thermostat to the control board such as Y1, Y2, O, G, W, SL1-In on the LED display.
Diagnostic Inputs Viewed at LEDs
Normal Display Viewed at LEDs
SW 2-
7
Diagnostics Outputs Allows viewing the outputs from the control board such as compressor, reversing valve, blower, hot water pump, and loop pump on the LED display.
Diagnostic Outputs Viewed at LEDs
Normal Display Viewed at LEDs
SW 2-
8
Thermostat Selection Configures the control for a pulsed lockout signal (ComforTalk and FaultFlash thermostats) or continuous 5 VAC lockout signal.
Pulsed “L” signal
Continuous “L” signal
31
ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL
Envision Controls - Premier cont. Operation Logic Data Table OPERATION LOGIC
STG1
HEATING STG2 STG3
EMERG
COOLING STG1 STG2
Blower ON SL1 - IN ON
SINGLE SPEED UNITS Compressor ECM Normal ECM Dehumidify
On
On
On
Off
On
On
-
-
Med Med
High High
High High
High High
Med 85% Med
High 85% High
Low Low
-
PSC
On
On
On
On
On
On
On
Rev Valve Loop Pump
Off
Off
Off
Off
On
On
-
-
On
On
On
Off
On
On
-
On
Aux Heater
Off On
Off On
Staged On
Staged Off
Off On
Off On
-
-
Off Y1
Off
Off
Off
Y1, Y2, W
On W
Off
Y1, Y2
Y1, O
Y1, Y2, O
Off G
-
On Off Med Med Off On Off On Off Off Y1
Off On High High Off On Off On On Off Y1, Y2
Off On High High Off On Staged On On Off Y1, Y2, W
Off Off High High Off Off Staged Off Off On W
On Off Med 85% Med On On Off On Off Off Y1, O
Off On High 85% High On On Off On On Off Y1, Y2, O
Low Low G
On -
Secondary 1- Out Emerg LED T-Stat Signal DUAL CAPACITY UNITS Compressor-Lo Compressor-Hi ECM Normal ECM Dehumidify Rev Valve Loop Pumps Aux Heater Secondary 1- Out Secondary 2- Out Emerg LED T-Stat Signal
Thermostat Displays
ComforTalk
Fault Flash
When using a TP32U03, 04 or 05 thermostat and SW2-8 is in the pulsing “L” position, ComforTalk will enable the user to view the thermostat and determine the fault. The thermostat can be configured to show either lockout text or lockout codes.
When using a TA32W01 or TP32W02 thermostat and SW28 is in the pulsing “L” position, FaultFlash will enable a user to view the thermostat and count the fault indicator flashes to determine the lockout condition the unit is experiencing.
The following tables show the codes that will be displayed on the different ComforTalk and FaultFlash thermostats. FaultFlash Thermostats ComforTalk Thermostats
TA32W01 and TP32W02 Thermostats Thermostat Display Lockout Code 2 Flashes 3 Flashes 4 Flashes 5 Flashes 6 Flashes 7 Flashes 8 Flashes 9 Flashes 10 Flashes
TP32U03, TP32U04 and TP32U05 Thermostats Thermostat Display Lockout Code
Lockout Description High Pressure Fault Low Pressure Fault Not Applicable Water Flow Fault Not Applicable Condensate Fault Voltage out of Range RPM Fault Not Available
"High Pressure" or "E2" "Low Pressure" or "E3" "E4" "Water Flow" or "E5" "E6" "Condensate" or "E7" "Voltage Range" or "E8" "RPM" or "E9" "Comfort Alert" or "E10"
Lockout Description High Pressure Fault Low Pressure Fault Not Applicable Water Flow Fault Not Applicable Condensate Fault Voltage out of Range RPM Fault Not Avaialble
These thermostats can be configured to display the lockout condition "text" or error number. * A slow flash of 1 second on and off means the heat pump microprocessor SW2-1 is configured for "Test Mode" or thermostat is miswired.
32
ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL
Troubleshooting 4)
Standard Microprocessor Controls To check the unit control board for proper operation: 1) Disconnect thermostat wires at the control board. 2) Jumper the desired test input (Y1, Y2, W, O or G) to the R terminal to simulate a thermostat signal. 3) If control functions properly: • Check for thermostat and field control wiring (use the diagnostic inputs mode).
If control responds improperly: • Ensure that component being controlled is functioning (compressor, blower, reversing valve, etc.). • Ensure that wiring from control to the component is functioning (refer to the LED Definition table below and use the diagnostic outputs mode). • If steps above check properly, replace unit control.
LED Definitions and Diagnostics Standard Microprocessor DIAGNOSTIC MODES LED
NORMAL DISPLAY MODE
CURRENT FAULT STATUS
INPUTS
OUTPUTS 1
OUTPUTS 2
Field Selection DIPS SW2-
1 On
SW2-
1 Off
SW2-
1 NA
SW2-
6 On
SW2-
6 On
SW2-
6 Off
SW2-
7 On
SW2-
7 On
SW2-
7 On
SW2-
1 NA
SW2-
1 NA
SW2-
6 On
SW2-
6 Off
SW2-
7 Off
SW2-
7 Off
Drain
Drain Pan Overflow Lockout
Drain Pan Overflow
Y1
Compressor (On or Low)
Blower Low
Water Flow
Freeze Detection Thermistor (Loop <15°F, Well<30°F) Lockout
Freeze Detection Thermistor (Loop <15°F, Well<30°F)
Y2
Compressor (On or High)
Blower Medium
High Pressure
High Pressure >600 psi Lockout
High Pressure >600
O
Reversing Valve
Blower High
Low Pressure
Low Pressure <40 psi Lockout
Low Pressure <40
G
Blower
Aux Heat 1
Airflow
ECM RPM <100 RPM
ECM RPM <100 RPM
W
DHW Pump
Aux Heat 2
Status
Microprocessor Malfunction
Not Used
SL1
Loop Pump(s)
Aux Heat 3
DHW Limit
HWL Thermistor >130°
HWL Thermistor >130°F
Not Used
–
Aux Heat 4
DHW Off
DHW Pump Switch Off
DHW Pump Switch Off
–
–
–
Refrigerant Systems
numbers calculated. If superheat and subcooling are outside recommended ranges, an adjustment to the refrigerant charge may be necessary.
To maintain sealed circuit integrity, do not install service gauges unless unit operation appears abnormal. Compare the change in temperature on the air side as well as the water side to the Unit Operating Parameters tables. If the unit’s performance is not within the ranges listed, and the airflow and water flow are known to be correct, gauges should then be installed and superheat and subcooling
NOTE: Refrigerant tests must be made with hot water generator turned “OFF”. Verify that air and water flow rates are at proper levels before servicing the refrigerant circuit.
33
ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL
Envision Controls - FX10 (optional) FX10 Advanced Control Overview The Johnson Controls FX10 board is specifically designed for commercial heat pumps and provides control of the entire unit as well as input ports for Open N2, LonTalk, BACnet (MS/TP @ 19,200 Baud rate) communication protocols as well as an input port for a user interface. The user interface is an accessory item that can be used to aid in diagnostics and unit setup. A 16-pin low voltage terminal board provides terminals for common field connections. The FX10 Control provides: • Operational sequencing • High and low-pressure switch monitoring • General lockout • Freeze Detection • Condensate overflow sensing • Lockout mode control • Emergency shutdown mode • Random start and short cycle protection
Main FX 10 Board
Optional Plug-in Communication Modules (compatible with standard BAS protocols)
Short Cycle Protection
• Open N2 • LonTalk • BACnet (MS/TP @ 19,200 Baud rate)
Allows a minimum compressor “off” time of four minutes and a minimum “on” time of two minutes.
Display Requires DLI Card/Kit. Up to 2 displays, either 1 local and 1 remote, or 2 remote. (A 2-display configuration requires identical displays.) Local display can be up to 3 meters from the controller, power supply, and data communication. Remote display can be up to 300 meters from the controller. Remote display must be independently powered with data communication done via 3 pole shielded cable.
Random Start A delay of 1 to 120 seconds is generated after each powerup to prevent simultaneous startup of all units within a building after the release from an unoccupied cycle or power loss.
Emergency Shutdown Control Timing and Fault Recognition Delays
A field-applied dry contact can be used to place the control into emergency shutdown mode. During this mode, all outputs on the board are disabled.
Lead compressor “ON” delay ..........................................90 seconds (not applicable for single compressor models) Minimum compressor “ON” time ...................................... 2 minutes (except for fault condition) Short cycle delay ..................................................................... 5 minutes Random start delay .......................................................0-120 seconds High pressure fault ................................................................. <1 second Low pressure fault ...............................................................30 seconds Freeze Detection fault........................................................30 seconds Condensate overflow fault ...............................................30 seconds Low pressure fault bypass ................................................... 2 minutes Freeze detection fault bypass ............................................ 2 minutes
Freeze Detection Field selectable for 15° or 30°F (-9° or -1°C)
Installation Options • Standalone controlled by standard room thermostat • Standalone with a Zone Temperature Sensor (must have user interface to change set points beyond the allowed +/- 5°F) • Integrated into BAS by adding communication module
Accessory Outputs Quantity 2. One cycled with blower, other with compressor.
User Interface 4 x 20 backlit LCD.
34
ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL
Envision Controls - FX10 cont. An optional Medium User Interface (MUI) for control setup and advanced diagnostics is available with some mounting kits, MUIK3 - Panel mount version and the MUIK4 - Wall mount version.
Optional FX10 Microprocessor and BAS S Interface
Zone Sensors There are two options for zone sensors that can be used with the FX10 control. Both sensors use a Johnson controls A99 positive temperature coefficient type sensor. The TAXXJ02 has a set point adjustment now which will give the end user a +/- 5°F adjustment from the set point as well as a push button that can be used for temporary occupancy. The control leaves the factory set to operate with a TAXXJ02 sensor and can be changed to read the TAXXA04 sensor through a building automation system or with a user interface.
The FX10 is a microprocessor based control that not only monitors and controls the heat pump but also can communicate any of this information back to the building automation system (BAS). This means that not only does the control monitor the heat pump at the unit you can also monitor and control many the features over the BAS. This clearly puts the FX10 in a class of its own.
Standard Features • • • • • • • • • •
The control will enumerate all fault conditions (HP, LP, CO, LOC, and Freeze Detection) over a BAS as well as display them on a medium user interface (MUI). HP, LP, CO and Freeze Detection faults can all be reset over a BAS. A Loss Of Charge fault can not be reset or bypassed until the problem has been corrected. A MUI is invaluable as a service tool for the building service team.
Anti Short Cycle High Pressure Protection Low Pressure Protection Freeze Detection Loss Of Charge Detection Random Start Display for diagnostics Reset Lockout at disconnect or through BAS 2 Accessory outputs Optional BAS add-on controls
DDC Operation and Connection
The unit can be commanded to run by a typical heat pump thermostat or run based on heating and cooling set points supplied by a BAS. The control board is wired with quick connect harnesses for easy field change out of a bad control board. All ECM variable blower speed settings can be changed over a BAS or with a MUI. The control has an input programmed to enable field installed emergency heat in the event that the compressor is locked out. This input can also be commanded on from a BAS as needed. An alarm history can be viewed through the MUI and will be held in memory until the unit is power cycled. Relative humidity can be read by a 0-5VDC humidity sensor that is displayed over the network. If you are using an ECM blower motor the control can enable dehumidification mode based on a set point in the control. The dehumidification set point itself can also be changed over a BAS or with a MUI. Dehumidification mode can also be enabled by the BAS. Because the FX10 is not factory configured to read CO2 levels, contact the factory for application assistance.
Other optional network protocol boards that can be added to the FX10 are: • Johnson Control N2 • LonWorks • BACnet - MS/TP @ 19,200 Baud rate - Limit devices to 30 on a single trunk line.
Control and Safety Feature Details Emergency Shutdown The emergency shutdown mode can be activated by a command from a facility management system or a closed contact on BI-2. The default state for the emergency shutdown data point is off. When the emergency shutdown mode is activated, all outputs will be turned off immediately and will remain off until the emergency shutdown mode is de-activated. The first time the compressor starts after the emergency shutdown mode has been de-activated, there will be a random start delay present.
The FX10 control has unused analog and digital inputs for field installed items such as air temperature, water temperature, CO2 or current status switches. The control has unused binary and PWM outputs that can be commanded over the BAS for field use. 35
ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL
Envision Controls - FX10 cont. Lockout Mode
Low Pressure (BI-3)
Lockout mode can be activated by any of the following fault signals: refrigerant system high pressure, refrigerant system low pressure, freeze detection, and condensate overflow. When any valid fault signal remains continuously active for the length of its recognition delay, the controller will go into fault retry mode, which will turn off the compressor. After the Compressor short cycle delay, the compressor will attempt to operate once again. If three consecutive faults occur in 60 minutes during a single heating or cooling demand, the unit will go into lockout mode, turning off the compressor, enabling the alarm output, and setting the blower back to low speed operation until the controller is reset. If the control faults due to the low pressure input (BI-3) being open during the pre-compressor startup check, the control will go into lockout mode immediately, disabling the compressor from starting and enabling the alarm output (BO-6). The lockout condition can be reset by powering down the controller, by a command from the BAS, or by the holding the ESC and Return keys on the MUI for 5 seconds.
The low-pressure switch shall be a normally closed (NC) switch that monitors the systems refrigerant pressure. The input shall be checked 15 seconds before compressor start up to be sure the pressure switch is closed and then ignored for the first 2 minutes after the compressor output (BO-2) is enabled. If the switch is open continuously for (30) seconds during compressor operation the compressor output (BO-2) will be disabled. The compressor will not restart until the compressor short cycle time delay has been satisfied.
Condensate Overflow The condensate overflow sensing circuit will monitor the condensate level as a resistance input to AI-3. If the condensate water level rises resulting in the input resistance rising above the set point for the recognition delay period, the condition will be recognized as a fault. The condensate will be subjected to a (30) second lockout delay which requires that the fault be sensed for a continuous (30) seconds before suspending unit operation.
Alarm Output (BO-6) The alarm output will be enabled when the control is in the lockout mode and will be disabled when the lockout is reset.
Test Mode Raising the zone temperature input (AI-1) reading to 180–220°F or by holding the ESC and down arrow keys on the MUI for 5 seconds will put the control into test mode. In test mode the random start delay and the compressor fixed on delay time will both be shortened to 5 seconds and the reversing valve will be allowed to cycle with out shutting down the compressor. If an MUI is connected to the control LED 8 will flash and the words “Test Mode Enabled” will be shown on the LCD display when the control is in test mode. Test mode will be disabled after a power cycle, 30 minute timeout, or by holding the ESC and Up arrow keys on the MUI.
Freeze Detection (AI-5) The freeze detection sensor will monitor the liquid refrigerant temperature entering the water coil in the heating mode. If the temperature drops below the freeze detection trip point for the recognition delay period, the condition will be recognized as a fault. The freeze detection trip point will be factory set for 30°F and will be field selectable for 15°F by removing a jumper wire on BI-5. The freeze detection fault condition will be bypassed 2 minutes at normal compressor startup, to allow the refrigeration circuit to stabilize. If the freeze detection sensor becomes unreliable at any time compressor operation will immediately be suspended until the problem is corrected. This should be displayed as an alarm on the BAS and the MUI. This alarm will be reported a “Water Low Temp Limit” fault.
Sequence of Operation Power Fail Restart When the controller is first powered up, the outputs will be disabled for a random start delay. The delay is provided to prevent simultaneous starting of multiple heat pumps. Once the timer expires, the controller will operate normally.
High Pressure (BI-11) The high-pressure switch shall be a normally closed (NC) switch that monitors the systems refrigerant pressure. If the input senses the high-pressure switch is open it must disable the compressor output immediately and count the fault. The compressor minimum on time does not apply if the highpressure switch opens. The compressor will not restart until the compressor short cycle time delay has been satisfied. 36
ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL
Envision Controls - FX10 cont. medium speed and will operate in high speed when the compressor is operating at full capacity.
Random Start Delay This delay will be used after every power failure, as well as the first time the compressor is started after the control exits the unoccupied mode or the emergency shutdown mode. The delay should not be less than 1 second and not longer than 120 seconds. If the control is in test mode the random start delay will be shortened to 5 seconds.
Thermostat Control Mode In thermostat mode the compressor will be cycled based on Y1 and Y2 calls from a room thermostat. When the control receives a Y1 command (BI-7) from the thermostat the low capacity compressor output (BO2) will be enabled and the ECM blower will operate in medium speed. When the control receives a Y2 command (BI-8) from the thermostat the full capacity compressor output will be enabled and the ECM blower will operate in high speed. During the heating cycle the reversing valve will be commanded into the off position.
Compressor Fixed On Delay Time The Compressor Fixed On Delay Time will ensure that the compressor output (B02) is not enabled for (90) seconds after the control receives a call to start the compressor. This delay is adjustable from 30 – 300 seconds over a BAS or a MUI. If the control is in test mode the Compressor Fixed On Delay Timer will be shortened to 5 seconds.
Cooling Cycle On a call for cooling, the blower enable output and accessory output 2 will turn on immediately after the random start delay timer has been satisfied. If the compressor short cycle time delay has been satisfied, the compressor will turn on after the blower enable and accessory output 2 are on and the fixed compressor start delay timers have been satisfied.
Compressor Minimum On Delay The compressor minimum on delay will ensure that the compressor output is enabled for a minimum of (2) minute each time the compressor output is enabled. This will apply in every instance except in the event the high pressure switch is tripped or emergency shutdown then the compressor output will be disable immediately.
Set Point Control Mode In set point control mode the reversing valve output will be enabled. As the temperature falls below the cooling set point and begins to operate in the cooling proportional band, the low capacity compressor output (BO-2) will be enabled. A PI loop in the programming of the control will determine when the full capacity compressor output (BO-4) is to be enabled. The compressor must be operating in low capacity for a minimum of 30 seconds before the full capacity compressor output can be enabled. During low capacity compressor operation the ECM blower will operate in medium speed and will operate in high speed when the compressor is operating at full capacity.
Compressor Short Cycle Delay Time The compressor short cycle time delay will ensure that the compressor output will not be enabled for a minimum of (5) minutes after it is disabled. This allows for the system refrigerant pressures to equalize after the compressor is disabled.
Heating Cycle On a call for heating, the blower enable output and accessory output 2 will turn on immediately after the random start delay timer has been satisfied. If the compressor short cycle time delay has been satisfied, the compressor will turn on after the blower enable and accessory output 2 are on and the fixed compressor start delay timers have been satisfied.
Thermostat Control Mode In thermostat mode the compressor will be cycled based on Y1 and Y2 calls from a room thermostat. When the control receives a Y1 command (BI-7) from the thermostat the low capacity compressor output (BO2) will be enabled and the ECM blower will operate in medium speed. When the control receives a Y2 command (BI-8) from the thermostat the full capacity compressor output will be enabled and the ECM blower will operate in high speed. During the cooling cycle the reversing valve will be commanded into the “ON” position.
Auxiliary heat output can be controlled over the BAS. Set Point Control Mode In set point control mode the reversing valve output will be disabled. As the temperature drops below the heating set point and begins to operate in the heating proportional band, the low capacity compressor output (BO-2) will be enabled. A PI loop in the programming of the control will determine when the full capacity compressor output (BO-4) is to be enabled. The compressor must be operating in low capacity for a minimum of 30 seconds before the full capacity compressor output can be enabled. During low capacity compressor operation the ECM blower will operate in 37
ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL
Envision Controls - FX10 cont. Variable Speed ECM Blower Operation
Inputs and Outputs Configuration
Blower speeds will be selected through the user interface or the facility management system. There will be a total of 12 speeds selectable with only three being selected at any one time. The lowest numbered speed selection set to ON will select the low-speed blower setting, the middle selection set to ON will select the medium-speed blower setting and the highest selection set to ON will select the high-speed blower setting. If all selections are set to OFF the software shall select speed setting 10 for low-speed, 11 for medium-speed, and will select speed setting 12 for high speed. If only one selection is set to ON, that selection will set the low-speed blower setting, the medium-speed setting will be 11, and the high-speed setting will be speed 12. The maximum low-speed setting will be speed 10 and the minimum high-speed setting will be speed 3. In addition there is a low limit setting in the software to prevent the ECM blower speed from being set below acceptable limits for each unit size.
Field Selectable Options Freeze Detection Set Point (BI-5) The freeze detection set point input allows you to adjust the freeze detection set point (AI-5). When the jumper is installed on BI-5 (Wire #24) the freeze detection set point is factory set for 30°F. When the jumper on BI-5 (Wire #24) is removed the freeze detection set point will be 15°F. Accessory Outputs (BO-7 and BO-8) Accessory Output 1 will be energized 90 seconds prior to the compressor output being energized. Accessory Output 2 will be energized with the blower output (BO-1). When the corresponding compressor output is turned off the accessory output will be deactivated immediately. These outputs are selectable for normally open or normally closed operation through the Medium User interface or through the Building Automation System. SINGLE and DUAL STAGE WATER-TO-AIR
ECM Blower air flow “Soft Switch Settings” A set of 12 “soft switches” accessible through the user interface or building automation system are used to select the three blower speed settings for the ECM blower motor. The 12 soft switches work in exactly the same way as the hardware switches used on the Premier control (Refer to Blower Performance Data - ECM Motor for proper settings). No more than three soft switches may be set to the “ON” position. The first “ON” switch (the lowest number switch) determines the “low speed blower” setting. The second determines the “medium speed blower” setting, and the third determines the “high speed blower” setting.
Emergency Heat/Network Enabled Output (BO5) This output is set from the factory to enable/disable emergency heat. If a problem occurs with the unit resulting in the compressor being locked out in heating mode, the control will automatically enable this output to turn on field installed electric heat. This output is interlocked with the blower proving input BI-6 (Blower proving sensors must be field supplied and installed). BI-6 must be connected to PB2 position 3 (see unit schematic) in the field if no blower proving sensor is desired. There is a configurable parameter available through a BAS network that must be enabled if this output is to be commanded over the BAS network.
Input Name Zone Temp 1 Relative Humidity Input Condensate Level Universal Temp Input Water Coil Low Temperature Limit Warm/Cool Adjust and Temp Occ
Input AI 1 AI 2 AI 3 AI 4 AI 5 AI 6
Occupied Emergency Shutdown Stage 1 Low Pressure Network Viewable Input 1 Water Coil Low Temp Limit Set Point Network Viewable Input 2 Thermostat Y1 Thermostat Y2 Thermostat O Thermostat G Stage 1 High Pressure Compressor Proving XP10 Expansion Card Input Name Unused Unused Unused Unused
BI 1 BI 2 BI 3 BI 4 BI 5 BI 6 BI 7 BI 8 BI 9 B10 BI11 BI12 Input AI 1 AI 2 AI 3 AI 4
Output Name Fan Enable Comp – Low Capacity Reversing Valve Comp – Full Capacity Network Output/EH Output Alarm Accessory 1 Output Accessory 2 Output Network Controlled Output
Output BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 B09
Variable Speed ECM Blower Network Controlled Output
PWM1 PWM2
Output Name Unused Unused Unused Unused
Output BO 1 BO 2 BO 3 BO 4
Control Accessories Zone Sensors • TAXXJ02 Room Command Module • TAXXA04 LCD Room Command Module • A99 Sensor
MUI Alarm History Reporting If a fault occurs the fault will be recorded in history for display on the medium user interface in the History Menu. Each fault type will be displayed in the history menu with a number between 0 and 3. A reading of 3+ will mean that fault has occurred more than three times in the past. The history menu can be cleared with a power cycle only. Alarm date and time are not included in the history.
MUI (LCD User interface) for diagnostics and commissioning. • MUIK3 - Panel Mount, Portable • MUIK4 - Wall Mount
38
ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL
Envision Controls - FX10 cont. FX10 User Interface (MUI) Physical Layout Alarm LED
Power LED
Up Arrow
Right Arrow
Escape (ESC) Button
LED 1
Return Button LED 4
Left Arrow
LED 8
Down Arrow
Alarm LED - Indicates a Lock-Out or a bad Freeze Sensor
LED 3 - On shows Fan running
Power LED - Shows FX processor is operational
LED 4 - On shows Reversing Valve in cool
LED 1 - Flashing shows Compressor 1 running
LED 8 - Flashing shows unit in ‘Test’ Mode
LED 2 - Flashing shows Full Capacity Compressor running
MUI Menu Navigation for Single Compressor - Envision Water-to-Air Welcome
Info
Status
Info
Temps
Outputs
Settings
Maint
Outputs
Temps
Status
Alarms
Alm-History
Settings
WFI
Run Mode
Auto
Zone Temp
77.2 ºF
nvoFanStatus
ON
Unit of Measure
Envision Series
Eff Occup’y
Occ
Dis Air Temp
51.0 ºF
CmpCmd Status
OFF
Occ Clg Setpt
73.9 ºF
PROFXENV-XX
Y1 Input
OFF
Eff Clg Setpt
70.0°F
Cmp Capacity
OFF
Occ Htg Setpt
69.9 ºF
3/8/07
Y2 Input
OFF
Eff Htg Setpt
66.0°F
Rev Valve
Heat
Unocc Clg
84.0 ºF
G Input
OFF
Water Coil
77.8°F
X1 Output
OFF
Unocc Htg
60.0 ºF
O Input
OFF
Low WC Limit
30.0°F
X2 Output
OFF
DeHumSetpt
0%
Occ Input
Occ
Humidity
56.7 %RH
PWMOut
98%
SensorSelect
TAXXJ02
Temp Occ Inp
OFF
WarmCool AI
14.6
BO5
OFF
Condensate
NML
WarmCoolAdj
0.2
BO9
OFF
Emg Input
Run
AO2 Output
0%
Lo Press
ON
Hi Press
ON
Rndm Tmr
0
BI-4 Input
OFF
39
F
ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL
Envision Controls - FX10 cont. MUI Menu Navigation for Single Compressor - Envision Water-to-Air ECM
Maintenance MinClgSetpt
60.0 ºF
SW1
OFF
MaxHtgSetpt
89.9 ºF
SW2
OFF
W Coil LoLim1
30.0 ºF
SW3
ON
W Coil LoLim2
15.0 ºF
SW4
OFF
TmpOccTime
120 min
SW5
OFF
SW6
OFF
Rev Vlv
Default Heating
Press right arrow key one time from Maintenance Menu
BO5 Mode
Network
SW7
ON
CompStrtDly
90 sec
SW8
OFF
SpaceT Offset
-1 ºF
SW9
OFF
DehumEnaDis
Dis
SW10
ON
Acc1 Action
On Comp
SW11
OFF
Acc2 Action
On Fan
SW12
OFF
No more than three speeds should be “ON” at one time
Alm-History
Alarms ALARM SUMMARY ^/High Pressure
Alarm
#Events
Condensate
0
Hi Pressure
0
Low Pressure
0
Low Temp
0
Bad Sensor
0
NOTE: This FX10 application implements an alarm history which is reset only by cycling power . This history shows on the Alm-History page. Any alarm showing 4+ events has occurred more than 4 times. Alarm lock-outs are reset by cycling power, by pressing the “ESC” and Return keys simultaneously for a minimum of 15 seconds, or by commanding the nviAlarmReset over the BAS network. Test mode is enabled by holding the ‘Esc’ and Down Arrow simultaneously for a minimum of 15 seconds and releasing. Test mode times out after 30 minutes, and may also be ended by pressing ‘ESC’ and Up Arrow simultaneously and releasing . Test Mode bypasses the On Delay (90 sec) and Random Start timers for quicker troubleshooting. It also allows cycling the reversing valve without compressor shutdown.
40
ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL
Unit Startup 5.
Before Powering Unit, Check The Following: NOTE: Remove and discard the two compressor hold down shipping bolts located at the front and rear of the compressor mounting bracket. The bolts can then be discarded.
6. • • • • • • • • • • • • • • • • •
High voltage is correct and matches nameplate. Fuses, breakers and wire size correct. Low voltage wiring complete. Piping completed and water system cleaned and flushed. Air is purged from closed loop system. Isolation valves are open, water control valves or loop pumps wired. Condensate line open and correctly pitched. Transformer switched to 208V if applicable. Black/white and gray/white wires in unit control box have been removed if auxiliary heat has been installed. Dip switches are set correctly. DHW pump switch is “OFF” unless piping is completed and air has been purged. Blower rotates freely. Blower speed correct (dip switch is set correctly). Air filter/cleaner is clean and in position. Service/access panels are in place. Return air temperature is between 50-80ºF heating and 60-95ºF cooling. Check air coil cleanliness to insure optimum performance. Clean as needed according to maintenance guidelines. To obtain maximum performance the air coil should be cleaned before startup. A 10% solution of dishwasher detergent and water is recommended for both sides of coil, a thorough water rinse should follow.
7.
8. 9.
10.
11. 12. 13.
14.
15.
16.
Startup Steps
17.
NOTE: Complete the Equipment Start-Up/Commissioning Check Sheet during this procedure. Refer to thermostat operating instructions and complete the startup procedure. 1. 2.
3.
4.
18.
Initiate a control signal to energize the blower motor. Check blower operation. Initiate a control signal to place the unit in the cooling mode. Cooling setpoint must be set below room temperature. First stage cooling will energize after a time delay. Check for correct rotation of scroll compressors in 3 phase applications Incorrect rotation will cause low refrigerant pressures and possibly unusual noise. Switch any two power leads at the compressor or contactor to reverse rotation. Be sure that the compressor and water control valve or loop pump(s) are activated.
Verify that the water flow rate is correct by measuring the pressure drop through the heat exchanger using the P/T plugs and comparing to unit capacity data in specification catalog. Check the temperature of both the supply and discharge water (Refer to Unit Operating Parameters tables). Check for an air temperature drop of 15°F to 25°F across the air coil, depending on the blower speed and entering water temperature. Decrease the cooling set point several degrees and verify high-speed blower operation (ECM only). Adjust the cooling setpoint above the room temperature and verify that the compressor and water valve or loop pumpsdeactivate. 1Initiate a control signal to place the unit in the heating mode. Heating set point must be set above room temperature. First stage heating will energize after a time delay. Check the temperature of both the supply and discharge water (Refer to Unit Operating Parameters tables). Check for an air temperature rise of 20°F to 35°F across the air coil, depending on the blower speed and entering water temperature. If auxiliary electric heaters are installed, increase the heating setpoint until the electric heat banks are sequenced on. All stages of the auxiliary heater should be sequenced on when the thermostat is in the Emergency Heat mode. Check amperage of each element. Adjust the heating setpoint below room temperature and verify that the compressor and water valve or loop pumps deactivate. During all testing, check for excessive vibration, noise or water leaks. Correct or repair as required. Set system to desired normal operating mode and set temperature to maintain desired comfort level. Instruct the owner/operator in the proper operation of the thermostat and system maintenance.
NOTE: Be certain to fill out and forward all warranty registration papers.
41
ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL
Operating Limits Cooling (°F) (°C)
Operating Limits
Air Limits Min. Ambient Air 45 Rated Ambient Air 80 Max. Ambient Air 100 Min. Entering Air 50 Rated Entering Air db/wb 80.6/66.2 Max. Entering Air db/wb 110/83 Water Limits Min. Entering Water 30 Normal Entering Water 50-110 Max. Entering Water 120
NOTE: Minimum/maximum limits are only for start-up conditions, and are meant for bringing the space up to occupancy temperature. Units are not designed to operate at the minimum/maximum conditions on a regular basis. The operating limits are dependant upon three primary factors: 1) water temperature, 2) return air temperature, and 3) ambient temperature. When any of the factors are at the minimum or maximum levels, the other two factors must be at the normal level for proper and reliable unit operation.
Heating (°F) (°C)
7.2 26.7 37.8 10.0 27/19 43/28.3
45 70 85 40 68 80
7.2 21.1 29.4 4.4 20.0 26.7
-1.1 10-43.3 48.9
20 30-70 90
-6.7 -1.1 32.2
Operating Parameters Single Speed Models Cooling -- No Hot Water Generation Entering Water Temp °F
Water Flow gpm/ton 1.5
Suction Pressure psig
Discharge Pressure psig
Superheat
Subcooling
Water Temp Rise °F
Air Temp Drop °F DB
115 - 125
150 - 170
20 - 35
10 - 17
17 - 22
17 - 23
30 3.0
105 - 120
130 - 145
20 - 35
10 - 17
8 - 10
17 - 23
1.5
130 - 140
215 - 235
12 - 20
8 - 14
16 - 22
17 - 23
50 3.0
128 - 138
190 - 210
12 - 20
8 - 14
8 - 12
17 - 23
1.5
138 - 148
280 - 310
10 - 16
10 - 16
15 - 21
17 - 23
3.0
136 - 146
250 - 280
10 - 16
8 - 14
7 - 13
17 - 23
1.5
145 - 155
350 - 380
9 - 14
10 - 16
14 - 20
17 - 23
70
90 3.0
143 - 153
320 - 350
9 - 14
8 - 14
6 - 10
17 - 23
1.5
145 - 155
420 - 450
9 - 14
10 - 16
14 - 20
17 - 23
3.0
143 - 153
405 - 435
9 - 14
8 - 14
6 - 10
17 - 23
Suction Pressure psig
Discharge Pressure psig
Subcooling
Water Temp Drop °F
Air Temp Rise °F DB
1.5
73 - 85
270 - 305
8 - 14
3 - 10
6 - 10
15 - 21
3.0
77 - 90
280 - 315
8 - 14
3 - 10
4-8
17 - 23
110
Heating - No Hot Water Generation Entering Water Temp °F
Water Flow gpm/ton
Superheat
30 1.5
97 - 110
290 - 325
10 - 16
3 - 10
9 - 13
22 - 28
3.0
102 - 115
300 - 335
10 - 16
3 - 10
7 - 11
24 - 30
50 1.5
130 - 145
320 - 355
13 - 19
3 - 10
10 - 14
30 - 36
3.0
135 - 150
325 - 360
13 - 19
3 - 10
8 - 12
32 - 38
1.5
150 - 160
350 - 390
13 - 19
3 - 10
10 - 14
30 - 36
3.0
155 - 165
365 - 405
13 - 19
3 - 10
8 - 12
32 - 38
70
90 1.5 110 3.0 Cooling performance based on entering air temperatures of 80°F DB, 67°F WB. Heating performance based on entering air temperature of 70°F DB.
42
10/1/10
ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL
Operating Parameters cont. Dual Capacity Models FIRST STAGE OPERATION Entering Water Temp °F 30 50 70 90 110
Entering Water Temp °F 30 50 70 90 110
Water Flow gpm/ton 1.5 3.0 1.5 3.0 1.5 3.0 1.5 3.0 1.5 3.0
Water Flow gpm/ton 1.5 3.0 1.5 3.0 1.5 3.0 1.5 3.0 1.5 3.0
Cooling -- No Hot Water Generation Suction Pressure psig 105 - 120 100 - 115 125 - 140 120 - 135 135 - 145 133 - 143 142 - 152 140 - 150 152 - 158 148 - 153
Discharge Pressure psig 140 - 155 115 - 130 205 - 225 180 - 200 280 - 290 250 - 260 345 - 355 330 - 340 405 - 435 390 - 420
Suction Pressure psig 76 - 84 80 - 88 100 - 115 105 - 120 135 - 150 140 - 155 155 - 165 160 - 170
Discharge Pressure psig 270 - 285 275 - 290 280 - 310 290 - 315 310 - 325 315 - 330 330 - 370 340 - 380
Superheat
Subcooling
20 - 35 20 - 35 12 - 20 12 - 20 10 - 16 10 - 16 8 - 12 8 - 12 8 - 12 8 - 12
9 - 17 9 - 17 8 - 14 8 - 14 8 - 14 8 - 14 8 - 14 8 - 14 8 - 14 8 - 14
Water Temp Rise °F 17 - 21 8 - 12 17 - 21 8 - 12 16 - 20 9 - 13 14 - 20 8 - 12 14 - 20 8 - 12
Air Temp Drop °F DB 17 - 23 17 - 23 17 - 23 17 - 23 17 - 23 17 - 23 17 - 23 17 - 23 17 - 23 17 - 23
Water Temp Drop °F 5-9 3-7 7 - 11 5-9 8 - 12 6 - 10 8 - 12 6 - 10
Air Temp Rise °F DB 12 - 16 14 - 18 18 - 22 20 - 24 24 - 28 22 - 30 24 - 28 22 - 30
Heating -- No Hot Water Generation Superheat
Subcooling
8 - 12 8 - 12 10 - 14 10 - 14 12 - 16 12 - 16 12 - 16 12 - 16
3 - 10 3 - 10 3 - 10 3 - 10 3 - 10 3 - 10 3 - 10 3 - 10
10/1/10
SECOND STAGE OPERATION Entering Water Temp °F 30 50 70 90 110
Entering Water Temp °F
Water Flow gpm/ton 1.5 3.0 1.5 3.0 1.5 3.0 1.5 3.0 1.5 3.0
Water Flow gpm/ton
Cooling -- No Hot Water Generation Suction Pressure psig 115 - 125 105 - 120 130 - 140 128 - 138 138 - 148 136 - 146 145 - 155 143 - 153 145 - 155 143 - 153
Discharge Pressure psig 150 - 170 130 - 145 215 - 235 190 - 210 280 - 310 250 - 280 350 - 380 320 - 350 420 - 450 405 - 435
Suction Pressure psig 73 - 85 77 - 90 97 - 110 102 - 115 130 - 145 135 - 150 150 - 160 155 - 165
Discharge Pressure psig 270 - 305 280 - 315 290 - 325 300 - 335 320 - 355 325 - 360 350 - 390 365 - 405
Superheat
Subcooling
20 - 35 20 - 35 12 - 20 12 - 20 10 - 16 10 - 16 9 - 14 9 - 14 9 - 14 9 - 14
10 - 17 10 - 17 8 - 14 8 - 14 10 - 16 8 - 14 10 - 16 8 - 14 10 - 16 8 - 14
Air Temp Drop °F DB 17 - 23 17 - 23 17 - 23 17 - 23 17 - 23 17 - 23 17 - 23 17 - 23 17 - 23 17 - 23
Water Temp Drop °F 6 - 10 4-8 9 - 13 7 - 11 10 - 14 8 - 12 10 - 14 8 - 12
Air Temp Rise °F DB 15 - 21 17 - 23 22 - 28 24 - 30 30 - 36 32 - 38 30 - 36 32 - 38
Heating -- No Hot Water Generation Superheat
1.5 3.0 1.5 50 3.0 1.5 70 3.0 1.5 90 3.0 1.5 110 3.0 Cooling performance based on entering air temperatures of 80°F DB, 67°F WB. Heating performance based on entering air temperature of 70°F DB. 30
Water Temp Rise °F 17 - 22 8 - 10 16 - 22 8 - 12 15 - 21 7 - 13 14 - 20 6 - 10 14 - 20 6 - 10
43
8 - 14 8 - 14 10 - 16 10 - 16 13 - 19 13 - 19 13 - 19 13 - 19
Subcooling 3 - 10 3 - 10 3 - 10 3 - 10 3 - 10 3 - 10 3 - 10 3 - 10
10/1/10
ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL
Pressure Drop Single Speed Model
009
012
015
018
022
030
036
042
048
060
070
GPM 1.5 2.0 3.0 4.0 1.5 2.5 3.5 4.5 2.0 3.0 4.0 5.0 3.0 4.0 5.0 6.0 3.0 4.5 6.0 8.0 4.0 6.0 8.0 10.0 5.0 7.0 9.0 12.0 5.0 8.0 11.0 14.0 6.0 9.0 12.0 16.0 9.0 12.0 15.0 20.0 12.0 15.0 18.0 24.0
30°F 1.9 3.5 6.9 12.0 0.3 1.0 1.7 2.5 0.6 1.6 2.6 3.7 1.6 2.9 4.2 6.0 0.9 1.7 2.8 4.7 1.5 3.0 5.1 7.7 1.0 2.1 3.6 6.3 0.8 2.1 4.2 7.6 1.1 2.3 3.9 6.7 2.4 3.9 5.7 9.5 3.0 4.4 6.0 9.7
Pressure Drop (psi) 50°F 70°F 90°F 1.8 1.7 1.6 3.4 3.2 3.1 6.5 6.3 6.0 11.4 11.0 10.8 0.3 0.3 0.3 1.0 1.0 1.0 1.7 1.7 1.6 2.4 2.4 2.4 0.6 0.6 0.6 1.6 1.6 1.6 2.6 2.6 2.6 3.7 3.6 3.6 1.6 1.5 1.5 2.9 2.8 2.8 4.2 4.1 4.0 5.8 5.7 5.6 0.9 0.8 0.7 1.6 1.5 1.4 2.7 2.5 2.3 4.4 4.1 3.9 1.4 1.3 1.2 2.8 2.7 2.5 4.8 4.5 4.2 7.2 6.8 6.3 1.0 0.9 0.8 1.9 1.8 1.7 3.3 3.0 2.8 5.9 5.5 5.1 0.7 0.7 0.7 2.1 1.9 1.8 4.1 3.8 3.5 6.7 6.3 5.8 1.0 1.0 0.9 2.1 2.0 1.9 3.7 3.4 3.2 6.3 5.9 5.5 2.2 2.1 2.0 3.6 3.4 3.2 5.3 5.0 4.7 8.9 8.3 7.8 2.8 2.6 2.4 4.0 3.8 3.5 5.5 5.1 4.8 9.1 8.5 7.9
Valve
110°F 1.5 3.0 5.7 10.5 0.3 1.0 1.6 2.3 0.6 1.6 2.5 3.5 1.4 2.7 3.9 5.5 0.7 1.3 2.2 3.6 1.1 2.3 3.9 5.8 0.8 1.6 2.6 4.8 0.6 1.7 3.3 5.4 0.8 1.7 3.0 5.1 1.8 2.9 4.3 7.2 2.2 3.3 4.4 7.3 10/1/10
1/2 in.
1/2 in.
3/4 in.
3/4 in.
3/4 in.
3/4 in.
1 in.
1 in.
1 in.
1 in.
1 in.
GPM
Cv
1.5 2.0 3.0 4.0 1.5 2.5 3.5 4.5 2.0 3.0 4.0 5.0 3.0 4.0 5.0 6.0 3.0 4.5 6.0 8.0 4.0 6.0 8.0 10.0 5.0 7.0 9.0 12.0 5.0 8.0 11.0 14.0 6.0 9.0 12.0 16.0 9.0 12.0 15.0 20.0 12.0 15.0 18.0 24.0
9.6 9.7 9.9 10.1 9.6 9.8 10.0 10.2 9.7 9.9 10.1 10.4 9.9 10.1 10.4 10.6 9.9 10.2 10.6 11.0 10.1 10.6 11.0 11.5 15.9 16.6 17.2 17.9 15.9 16.6 17.2 17.9 16.1 16.8 17.4 18.3 16.8 17.4 18.1 19.2 17.4 18.1 18.7 20.1
GPM
Cv
4.0 6.0 8.0 10.0 5.0 7.0 9.0 12.0 6.0 9.0 12.0 15.0 9.0 12.0 16.0 20.0 12.0 15.0 18.0 24.0
10.1 10.6 11.0 11.5 10.4 10.8 11.2 11.9 16.1 16.8 17.4 18.1 16.8 17.4 18.3 19.2 17.4 18.1 18.7 20.1
Pressure Drop (psi) 0.02 0.04 0.09 0.16 0.02 0.06 0.12 0.19 0.04 0.09 0.16 0.23 0.09 0.16 0.23 0.32 0.09 0.19 0.32 0.53 0.16 0.32 0.53 0.76 0.10 0.23 0.41 0.61 0.10 0.23 0.41 0.61 0.14 0.29 0.47 0.76 0.29 0.47 0.69 1.09 0.47 0.69 0.92 1.43 10/1/10
Dual Capacity Model
026
038
049
064
072
GPM 4.0 6.0 8.0 10.0 5.0 7.0 9.0 11.0 6.0 9.0 12.0 15.0 8.0 12.0 16.0 20.0 12.0 15.0 18.0 21.0
30°F 1.4 2.8 4.7 7.0 1.2 2.2 3.4 4.9 1.2 2.4 3.9 5.7 1.8 3.8 6.5 9.7 3.2 4.5 6.0 7.8
Pressure Drop (psi) 50°F 70°F 90°F 1.3 1.2 1.1 2.6 2.4 2.3 4.4 4.1 3.8 6.6 6.2 5.8 1.2 1.1 1.0 2.1 1.9 1.8 3.2 3.0 2.8 4.6 4.3 4 1.2 1.1 1.0 2.2 2.1 2.0 3.6 3.4 3.2 5.3 5 4.7 1.7 1.6 1.4 3.5 3.3 3.0 6.0 5.6 5.2 9.1 8.5 8.0 3.0 2.8 2.6 4.2 4.0 3.7 5.7 5.3 4.9 7.3 6.8 6.4
Valve
110°F 1.0 2.1 3.5 5.3 1.0 1.7 2.6 3.7 1.0 1.8 2.9 4.3 1.3 2.8 4.8 7.4 2.4 3.4 4.6 5.9 10/1/10
3/4 in.
3/4 in.
1 in.
1 in.
1 in.
44
Pressure Drop (psi) 0.16 0.32 0.53 0.76 0.23 0.42 0.64 1.02 0.14 0.29 0.47 0.69 0.29 0.47 0.76 1.09 0.47 0.69 0.92 1.43 10/1/10
ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL
Compressor and Thermistor Resistance Compressor Resistance Chart
Dual Capacity
Single Speed
Model 009 012 015 018 022 030 036 042 048 060 070 026 038 049 064 072
208-230/60/1 Run Start 3.65 - 4.19 3.75 - 4.31 3.35 - 3.85 2.80 - 3.22 2.74 - 3.16 2.60 - 3.00 2.24 - 2.58 2.84 - 3.26 1.39 - 1.53 2.15 - 2.30 1.21 - 1.39 1.53 - 1.75 0.95 - 1.09 1.81 - 2.09 0.83 - 0.95 1.54 - 1.78 0.51 - 0.59 1.13 - 1.31 0.42 - 0.48 0.73 - 0.85 0.34 - 0.40 0.51 - 0.59 1.23 - 1.41 1.30 - 1.50 0.83 - 0.95 1.20 - 1.38 0.60 - 0.68 1.41 - 1.63 0.46 - 0.52 0.56 - 0.64 0.34 - 0.40 0.49 - 0.57
265/60/1 Run Start 3.73 - 4.27 4.45 - 5.13 3.73 - 4.27 4.45 - 5.13 3.03 - 3.49 2.39 - 2.75 3.03 - 3.49 2.39 - 2.75 1.66 - 1.91 1.66 - 1.91 1.38 - 1.58 2.02 - 2.32 1.24 - 1.42 2.42 - 2.78 n/a n/a n/a n/a 1.71 - 1.97 0.97 - 1.11 n/a n/a n/a n/a
Thermistor Resistance Chart Thermistor Temperature (°F) 5 14 23 32 41 50 59 68 77 86 95 104 113 122 131 140 149
Microprocessor Resistance (Ohms) 75757-70117 57392-53234 43865-40771 33809-31487 26269-24513 20570-19230 16226-15196 12889-12093 10310-9688 8300-7812 6723-6337 5480-5172 4490-4246 3700-3504 3067-2907 2554-2424 2149-2019
FX10 Resistance (Ohms) 746-770 775-803 808-836 841-869 875-903 910-938 946-974 981-1013 1019-1051 1058-1090 1097-1129 1137-1169 1179-1211 1221-1253 1261-1297 1305-1341 1350-1386 7/6/10
45
208-230/60/3
460/60/3
575/60/3
n/a n/a n/a n/a n/a n/a 1.77 - 2.04 1.42 - 1.64 0.96 - 1.10 0.63 - 0.73 0.63 - 0.73 2.30 - 2.64 1.45 - 1.67 0.93 - 1.07 0.64 - 0.74 0.64 - 0.74
n/a n/a n/a n/a n/a n/a 7.57 - 8.71 5.46 - 6.28 3.88 - 4.46 2.98 - 3.42 2.30 - 2.64 5.60 - 6.44 3.88 - 4.46 3.88 - 4.46 2.60 - 3.00 2.60 - 3.00
n/a n/a n/a n/a n/a n/a n/a 8.26 - 9.50 5.88 - 6.76 4.96 - 5.70 3.31 - 3.81 n/a n/a n/a n/a n/a 10/1/10
ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL
Refrigerant Circuit Guideline Head Pressure Under Charged System (Possible Leak) Low Over Charged System High Low Air Flow Heating High Low Air Flow Cooling Low Low Water Flow Heating Low/Normal Low Water Flow Cooling High High Air Flow Heating Low High Air Flow Cooling Low High Water Flow Heating Normal High Water Flow Cooling Low Low Indoor Air Temperature Heating Low Low Indoor Air Temperature Cooling Low High Indoor Air Temperature Heating High High Indoor Air Temperature Cooling High Restricted TXV (Check Service Advisory) High Insufficient Compressor (Possible Bad Valves) Low TXV - Bulb Loss of Charge Low Scaled Coaxial Heat Exchanger Heating Low Scaled Coaxial Heat Exchanger Cooling High Restricted Filter Drier Symptom
Suction Compressor Air Temp. Water Temp. Superheat Subcooling Pressure Amp Draw Differential Differential Low Low High Low Low Low High High Normal High Normal/Low Normal High High High/Normal Low High Low Low Low Low/Normal High High Low Low/Normal Low Low High Low High High High High Low Low High Low Low Low High Low Low High Normal High Low Low Normal Low Normal High Normal Normal Low Low Low Low High Normal Low Low Low Normal High Normal Normal/High Low Low Normal/Low High Low Low High High Normal/High Normal/Low Low Normal High High High Low Low High Low Normal/Low High High Low Low High Low High Normal/High Low Low Low Low High High Low Low Low Low Normal/Low High Low Low High High Normal/Low Low Low Low Check temperature difference (delta T) across filter drier. 7/6/10
Reference Calculations Heating Calculations:
Cooling Calculations: HR gpm x 500
LWT = EWT -
HE gpm x 500
LWT = EWT +
LAT = EAT +
HC cfm x 1.08
LAT(DB) = EAT(DB) -
SC cfm x 1.08
LC = TC - SC TH = HC + HWC S/T =
SC TC
Legend ABBREVIATIONS AND DEFINITIONS: cfm EWT gpm WPD EAT
= = = = =
HC TC SC kW HR
= = = = =
airflow, cubic feet/minute entering water temperature, Fahrenheit water flow in gallons/minute water pressure drop, psi and feet of water entering air temperature, Fahrenheit (dry bulb/wet bulb) air heating capacity, MBtu/h total cooling capacity, MBtu/h sensible cooling capacity, MBtu/h total power unit input, kilowatts total heat of rejection, MBtu/h
HE = total heat of extraction, MBtu/h HWC = hot water generator capacity, MBtu/h EER = Energy Efficient Ratio = BTU output/Watt input COP = Coefficient of Performance = Btu output/Btu input LWT = leaving water temperature, °F LAT = leaving air temperature, °F TH = total heating capacity, MBtu/h LC = latent cooling capacity, MBtu/h S/T = sensible to total cooling ratio
46
ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL
Heat of Extraction/Rejection Data Model 009
012
015
018
Single Speed
022
030
036
042
048
060
070
026 Lo
026 Hi
038 Lo
Dual Capacity
038 Hi
049 Lo
049 Hi
064 Lo
064 Hi
072 Lo
072 Hi
gpm 1.5 2.0 3.0 1.5 2.5 3.5 2.0 3.0 4.0 3.0 4.0 5.0 3.0 4.5 6.0 4.0 6.0 8.0 5.0 7.0 9.0 5.0 8.0 11.0 6.0 9.0 12.0 9.0 12.0 15.0 12.0 15.0 18.0 3.0 5.0 7.0 4.0 6.0 8.0 4.0 6.0 8.0 5.0 7.0 9.0 5.0 8.0 11.0 6.0 9.0 12.0 6.0 10.0 14.0 8.0 12.0 16.0 10.0 13.0 16.0 12.0 15.0 18.0
30°F 5.1 5.0 6.3 6.3 7.9 8.0 10.1 10.3 10.7 10.8 14.6 14.9 17.7 18.1 21.0 21.4 26.8 27.3 30.8 31.8 37.2 37.3 10.2 10.4 14.1 14.3 13.5 14.5 19.7 20.2 19.6 20.3 26.8 27.4 22.4 23.5 33.9 34.3 26.3 27.9 39.1 39.5
Heat Of Extraction (HE) - MBtu/h 50°F 70°F 90°F 6.5 8.6 11.3 6.7 8.9 11.6 7.1 9.3 11.8 7.8 10.0 12.8 8.2 10.5 13.4 8.5 11.0 13.5 9.7 12.4 15.7 10.1 13.0 16.4 10.5 13.5 16.5 12.4 16.0 20.4 12.8 16.3 20.5 13.2 16.6 20.7 14.7 19.4 23.6 15.6 20.5 24.8 15.9 20.9 25.3 20.0 26.0 31.0 20.8 27.1 32.3 21.3 27.6 32.8 23.8 31.3 37.6 24.9 32.6 39.2 25.5 33.2 39.8 27.2 33.7 40.0 28.5 35.5 42.4 29.3 36.6 43.9 35.1 43.9 51.2 36.7 46.3 54.3 37.7 47.7 56.2 43.1 55.1 63.7 44.4 56.2 67.6 45.3 58.6 68.5 51.4 65.6 76.5 52.7 68.4 81.2 53.2 69.5 83.0 14.1 18.9 23.0 14.9 20.0 24.2 15.2 20.3 24.6 18.7 24.5 29.8 19.8 25.9 31.4 20.2 26.3 32.0 18.6 24.1 29.0 19.4 25.3 30.7 20.4 26.0 30.7 26.3 32.8 37.6 27.5 34.6 40.2 28.2 35.7 41.6 24.5 30.0 34.3 27.0 33.2 38.2 28.0 35.0 40.6 34.4 41.8 47.4 35.8 44.1 50.6 36.8 45.5 52.4 32.1 40.4 47.4 32.4 42.1 51.0 33.6 42.9 51.1 43.2 55.6 68.0 46.2 58.0 69.1 47.2 59.8 72.0 37.8 48.3 56.7 38.2 50.3 61.2 39.7 51.3 61.3 50.5 65.5 78.6 54.0 68.2 79.9 55.1 70.4 83.2
47
30°F 13.3 12.9 17.8 18.0 18.0 17.1 22.1 21.4 26.2 26.4 30.0 30.4 34.7 35.0 47.0 47.3 56.3 56.6 80.2 80.8 83.4 83.8 24.3 24.6 33.2 33.5 32.5 33.0 45.2 45.5 41.7 41.1 57.5 57.6 58.3 58.1 76.2 76.6 63.6 63.2 82.5 83.1
Heat of Rejection (HR) - MBtu/h 50°F 70°F 90°F 13.0 12.4 12.1 13.0 12.4 12.1 13.1 12.4 11.6 17.1 16.7 16.5 17.1 16.7 16.5 17.2 16.7 16.3 19.3 18.3 17.6 19.4 18.3 17.6 19.5 18.4 17.6 23.3 21.9 20.7 23.3 21.9 20.8 23.3 21.9 21.1 28.2 27.8 26.2 28.3 27.9 26.1 28.4 28.0 26.2 35.1 35.4 33.1 35.0 35.3 33.0 35.3 35.5 33.2 41.2 42.4 40.6 41.1 42.3 40.5 41.5 42.6 40.7 50.3 51.4 48.9 50.5 51.7 49.3 50.8 51.9 49.4 60.7 60.7 57.3 60.9 61.0 57.6 61.3 61.3 57.7 84.6 82.7 77.7 84.4 83.0 77.5 84.7 82.6 77.7 92.7 91.1 84.3 92.8 91.0 84.0 93.5 91.9 85.0 26.3 26.2 24.0 26.4 26.3 24.0 26.6 26.4 24.1 34.4 34.5 33.1 34.5 34.6 33.0 34.7 34.7 33.1 35.3 34.5 32.4 35.6 34.7 32.5 36.1 35.2 32.9 48.3 48.5 45.8 48.8 49.2 46.7 49.1 49.6 47.0 46.1 47.3 45.2 46.2 47.0 44.5 46.1 47.4 45.4 61.7 61.7 57.8 61.8 62.3 58.8 62.0 62.7 59.0 62.6 61.4 57.4 62.5 61.5 57.7 62.5 61.6 58.0 83.7 85.7 79.1 84.2 86.2 79.4 84.7 86.7 79.8 69.8 69.3 64.5 69.7 69.3 64.8 69.6 69.6 65.1 91.4 92.4 86.4 91.8 92.8 86.6 92.4 93.4 87.1
110°F 11.9 11.1 16.5 16.2 17.3 16.7 20.0 19.8 24.3 24.3 29.3 29.4 37.8 38.0 46.1 46.1 54.0 54.0 73.0 73.1 77.9 78.8 22.1 22.1 30.9 30.9 30.3 30.7 43.6 43.8 41.5 42.5 54.1 54.4 54.1 54.4 73.9 74.1 60.0 60.4 79.4 79.7 10/1/10
ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL
DEALER: PHONE #:
DATE:
PROBLEM: MODEL #:
Startup/Troubleshooting Form
SERIAL #:
COOLING CYCLE ANALYSIS PSI =
SAT °F
°F Unit Amp Draw:
°F
AIR COIL
Loop:
Open Closed
Line Voltage:
°F SUCTION
COMPRESSOR
COAX
COAX
EXPANSION VALVE
LOAD
REVERSING VALVE
SOURCE
DISCHARGE Hot Water Generator
°F
°F LIQUID LINE
°F
°F
°F
°F
PSI
PSI
PSI
PSI
°F BRINE IN
BRINE IN
BRINE OUT
SAT °F
PSI =
Superheat
°F
Subcooling
BRINE OUT
Water to Water Application
Heat of Extraction/Rejection = GPM x 500 (485 for water/antifreeze) x ∆T Note: DO NOT hook up pressure gauges unless there appears to be a performance problem.
HEATING CYCLE ANALYSIS PSI =
SAT °F
°F Loop:
Unit Amp Draw:
°F
AIR COIL
Open Closed
Line Voltage:
°F SUCTION
COMPRESSOR
COAX
EXPANSION VALVE
LOAD
REVERSING VALVE
COAX SOURCE
DISCHARGE Hot Water Generator
°F
°F
LIQUID LINE
PSI =
°F
°F
°F
°F
PSI
PSI
PSI
PSI
°F BRINE IN
BRINE OUT
BRINE IN
°F
SAT °F
Superheat
Subcooling
BRINE OUT
Water to Water Application WFS37 10/07
48
ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL
Preventive Maintenance Water Coil Maintenance
Condensate Drain
1.
In areas where airborne bacteria produce a slime in the drain pan, it may be necessary to treat chemically to minimize the problem. The condensate drain can pick up lint and dirt, especially with dirty filters. Inspect twice a year to avoid the possibility of overflow.
2.
Keep all air out of the water. An open loop system should be checked to ensure that the well head is not allowing air to infiltrate the water line. Lines should always be airtight. Keep the system under pressure at all times. It is recommended in open loop systems that the water control valve be placed in the discharge line to prevent loss of pressure during off cycles. Closed loop systems must have positive static pressure.
Blower Motors Blower motors are equipped with sealed ball bearings and require no periodic oiling.
NOTE: On open loop systems, if the installation is in an area with a known high mineral content (125 ppm or greater) in the water, it is best to establish with the owner a periodic maintenance schedule so the coil can be checked regularly. Should periodic coil cleaning be necessary, use standard coil cleaning procedures which are compatible with either the cupronickel or copper water lines. Generally, the more water flowing through the unit the less chance for scaling.
Hot Water Generator Coil See Water Coil Maintenance section.
Air Coil The air coil must be cleaned to obtain maximum performance. Check once a year under normal operating conditions and, if dirty, brush or vacuum (with a brush attachment) clean. Care must be taken not to damage the aluminum fins while cleaning.
Other Maintenance Filters
CAUTION: Fin edges are sharp.
Filters must be clean to obtain maximum performance. They should be inspected monthly under normal operating conditions and be replaced when necessary. Units should never be operated without a filter.
Replacement Procedures Obtaining Parts
In-Warranty Material Return
When ordering service or replacement parts, refer to the model number and serial number of the unit as stamped on the serial plate attached to the unit. If replacement parts are required, mention the date of installation of the unit and the date of failure, along with an explanation of the malfunctions and a description of the replacement parts required.
Material may not be returned except by permission of authorized warranty personnel. Contact your local distributor for warranty return authorization and assistance.
49
ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL
Service Parts Single Speed Vertical Units Part Description
Compressor
009
012
015
018
022
34P592-01 34P593-01
34P581-01
265/60/1
34P590-02 34P591-02 34P592-02 34P593-02 34P581-02 34P582-02 34P583-02
ECM Motor & Blower PSC Motor & Blower Refrigeration Components
048
060
070
Not Available
Not Available
34P582-03 34P583-03 34P578-03 34P579-03 34P580-03 34P561-06
460/60/3
Not Available
34P582-04 34P583-04 34P578-04 34P579-04 34P580-04 34P561-07
575/60/3
Not Available
34P578-05 34P579-05 34P580-05 34P561-08
Run Capacitor 208-230/60/1 16P002D17 16P002D18 16P002D19 16P002D19 16P002-18
16P002-20
Sound Jacket
92P504A05
92P504A01
16P002-21
16P002-25 16P002-24 92P504A16
11P521A01
11P781-01 Not Available
ECM Motor 208-230/60/1
Not Available
14S551-01
ECM Motor 265/60/1
Not Available
14S551-02
ECM Motor 230/60/3
Not Available
14S551-01
ECM Motor 460/60/3
Not Available
ECM Blower Housing
Not Available
ECM Harness
Not Available
ECM Power Harness
Not Available
14S552-01
14S553-01
14S552-02
14S551-02
Not Available 14S552-01
14S553-01
14S552-02
14S553-02
53P500B01
53P501B01 11P607B02 11P585B02
PSC Motor 208-230/60/1
14P506B01
14P507B01
14P508B01 14P509B01
PSC Motor 265/60/1
14P506B02
14P507B02
14P508B02 14P510B02 14P510B02
14P511B01
14P512B01
14P514B01 Not Available
PSC Motor 230/60/3
Not Available
14P511B01
14P512B01
14P514B01
PSC Motor 460/60/3
Not Available
14P511B02
14P512B02
14P514B02
14P511B03
14P514B03
PSC Motor 575/60/3 PSC Blower & Housing
Hot Water Generator
042
34P582-01 34P583-01 34P578-01 34P579-01 34P580-01 34P561-05
230/60/3
Solenoid Harness
Not Available 53P502B01
53P500B01
61P500C02 61P501C02
Coax
62P501B01 62P502B01 62P503B01 62P503B01 62P504B01 62P541-01
TXV
33P608-12 33P608-13 33P608-02 33P608-02
33P608-02
Reversing Valve
33P502-05
33P506-04
Filter Drier
36P500B01
How Water Generator
61P502C02
53P517-01
Air Coil
Comfort Alert
61S548C02
61S505C02
53P501B01
61S506C02
62P542B01
61S547-02 62P543B01
Not Available
33P503-05
33P526-04
62P516-03
19P571-01 13P004A03
Transformer 208-230/60/1
15P501B01
Transformer 265/60/1
15P507B01
Not Available
Transformer 230/60/3
Not Available
15P501B01
Transformer 460/60/3
Not Available
15P505B01
Transformer 575/60/3 3 Pole Power Block
Not Available
15P506B01
Not Available
12P503-06
2 Pole Screw Term. Block
12P500A01
Status Light Board
17P503-02
Premier Board
17P513-03
17P513-07
Freeze Protection Thermistor
12P505B01
12P505B03
HWL Thermistor
33P608-10
36P500B02
62P516-05
Not Available
62P555-01
33P608-09 33P608-05 33P608-04
36P500B01
Contactor
Electrical
036
34P590-01 34P591-01
Power Harness
Sensors & Safeties
030
Compressor 208-230/60/1
Not Available
12P505B02
High Pressure Switch
35P506B02
Low Pressure Switch
35P506B01
Part numbers subject to change
01/09/13
50
ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL
Service Parts cont. Dual Capacity Vertical Units Part Description 026
038
049
064
072
34P585-01
34P573-01
34P574-01
34P575-01
34P586-01
230/60/3
Not available
34P573-03
34P574-03
34P575-03
Not Available
460/60/3
Not available
34P573-04
34P574-04
34P575-04
Not Available
Compressor 208-230/60/1
Compressor
265/60/1
Not available
575/60/3 Run Capacitor 208-230/60/1
Not available 16P002-19
16P002-20
16P002-21
ECM Motor & Blower
Sound Jacket Power Harness
11P781-01
Solenoid Harness
11P782-01
ECM Motor 208-230/60/1
14S551-01
ECM Motor 265/60/1
14S551-02
14S552-01
14S551-01
14S552-01
14S553-01
ECM Motor 460/60/3
14S551-02
14S552-02
14S553-02
ECM Blower Housing
53P500B01
53P501B01
ECM Harness
11P607B01 11P585B01
PSC Motor & Blower
Not available
PSC Motor 265/60/1
Not available
PSC Motor 230/60/3
Not available
PSC Motor 460/60/3
Not available
PSC Motor 575/60/3
Not available
Refrigeration Components
PSC Blower & Housing
Hot Water Generator
Not Available
ECM Motor 230/60/3
ECM Power Harness
Not available
Air Coil
61S548-02
61S505C02
Coax
62P504B01
62P542B01
TXV
33P608-02
33P608-03
Reversing Valve
33P506-04
33P503-05
Filter Drier
How Water Generator
61S506C02
61S547-02
62P543B01 33P608-04
62P555-01 33P608-10
33P608-11
33P526-04
36P500B01
36P500B02
62P516-05
Comfort Alert
62P516-03
19P571-02
Contactor
13P004A03
Transformer 208-230/60/1
15P501B01
Transformer 265/60/1 Electrical
14S553-01
14S552-02
PSC Motor 208-230/60/1
Not available
Transformer 230/60/3
Not available
15P501B01
Not available
Transformer 460/60/3
Not available
15P505B01
Not available
Transformer 575/60/3
Not available
3 Pole Power Block
12P503-06
2 Pole Screw Term. Block
12P500A01
Status Light Board
17P503-02
Premier Board Sensors & Safeties
16P002-24
92P504A16
Freeze Protection Thermistor
17P513-07 12P505B03
HWL Thermistor
12P505B02
High Pressure Switch
35P506B02
Low Pressure Switch
35P506B01
Part numbers subject to change
01/09/13
51
ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL
Service Parts cont. Single Speed Horizontal Units Part Description
Compressor
009
012
015
018
022
Not Available
460/60/3
ECM Motor & Blower PSC Motor & Blower
060
070
Run Capacitor 208-230/60/1
Not Available
34P582-03 34P583-03 34P578-03 34P579-03 34P580-03 34P561-06
Not Available
575/60/3
34P582-04 34P583-04 34P578-04 34P579-04 34P580-04 34P561-07 Not Available
Not Available 16P002D17 16P002D18 16P002D19 16P002D19 16P002-18
34P578-05 34P579-05 34P580-05 34P561-08
16P002-20
92P504A01
16P002-21
16P002-25 16P002-24
92P504A05
92P504A16
11P521A01
11P781-01 Not Available
ECM Motor 208-230/60/1
Not Available
14S551-01
ECM Motor 265/60/1
Not Available
14S551-02
ECM Motor 230/60/3
Not Available
14S551-01
ECM Motor 460/60/3
14S552-01
Not Available
ICM Harness
Not Available
ICM Power Harness
Not Available
14S553-01
14S552-02
Not Available
ECM Blower Housing
14S551-02
Not Available 14S552-01
14S553-01
14S552-02
14S553-02
53P500B01
53P501B01 11P607B02 11P585B02
PSC Motor 208-230/60/1
14P506B01
14P507B01
14P508B01 14P509B01 14P511B01
PSC Motor 265/60/1
14P506B02
14P507B02
14P508B02 14P510B02 14P510B02
14P512B01
14P514B01 Not Available
PSC Motor 230/60/3
Not Available
Not Available
14P511B01
14P512B01
14P514B01
PSC Motor 460/60/3
Not Available
Not Available
14P511B02
14P512B02
14P514B02
14P511B03
14P514B03
PSC Motor 575/60/3 PSC Blower & Housing
Refrigeration Components
048
34P590-02 34P591-02 34P592-02 34P593-02 34P581-02 34P582-02 34P583-02
230/60/3
Solenoid Harness
Hot Water Generator
042
265/60/1
Power Harness
Not Available 53P502B01
Not Available 53P500B01
53P517-01
Air Coil
61P500C02 61P501C02 61P508C02 61P508C02
Coax
62P501B01 62P502B01 62P503B01 62P503B01 62P504B01 62P541-01
TXV
61P510C02
33P608-12 33P608-13 33P608-02 33P608-02
33P608-02
Reversing Valve
33P502-05
33P506-04
Filter Dryer
36P500B01
Hot Water Generator
Comfort Alert
61P511C02 62P542B01 33P608-09
53P501B01
61P512C02
33P60804
61P513C02 62P543B01
Not Available
33P503-05
33P526-04
62P516-03
19P571-01 13P004A03
Transformer 208-230/60/1
15P501B01
Transformer 265/60/1
15P507B01
Not Available
Transformer 230/60/3
Not Available
Not available
15P501B01
Transformer 460/60/3
Not Available
Not available
15P505B01
Transformer 575/60/3
Not Available
3 Pole Power Block
Not Available
Not available
15P506B01 12P503-06
2 Pole Screw Term. Block
12P500A01
Status Light Board
17P503-02
Premier Board
17P513-03
17P513-07
Freeze Protection Thermistor
12P505B01
12P505B03
HWL Thermistor
33P608-10
36P500B02
62P516-05
Not Available
62P555-01
33P608-05
36P500B01
Contactor
Electrical
036
34P590-01 34P591-01 34P592-01 34P593-01 34P581-01 34P582-01 34P583-01 34P578-01 34P579-01 34P580-01 34P561-05
Sound Jacket
Sensors & Safeties
030
Compressor 208-230/60/1
Not Available
12P505B02
High Pressure Switch
35P506B02
Low Pressure Switch
35P506B01
Part numbers subject to change
01/09/13
52
ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL
Service Parts cont. Dual Capacity Horizontal Units Part Description 026
038
049
064
072
34P585-01
34P573-01
34P574-01
34P575-01
34P586-01
230/60/3
Not available
34P573-03
34P574-03
34P575-03
Not Available
460/60/3
Not available
34P573-04
34P574-04
34P575-04
Not Available
Compressor 208-230/60/1
Compressor
265/60/1
Not available
Not available
575/60/3 Run Capacitor 208-230/60/1
16P002-19
16P002-20
16P002-21
ECM Motor & Blower
Sound Jacket Power Harness
11P781-01
Solenoid Harness
11P782-01
ECM Motor 208-230/60/1
14S551-01
ECM Motor 265/60/1
14S551-02
14S552-01
Not Available
ECM Motor 230/60/3
14S551-01
14S552-01
14S553-01
ECM Motor 460/60/3
14S551-02
14S552-02
14S553-02
ECM Blower Housing
53P500B01
53P501B01
ICM Harness
11P607B02 11P585B02
PSC Motor & Blower
PSC Motor 208-230/60/1
Not available
PSC Motor 265/60/1
Not available
PSC Motor 230/60/3
Not available
PSC Motor 460/60/3
Not available
PSC Motor 575/60/3
Not available
Hot Water Generator
Refrigeration Components
PSC Blower & Housing
Not available
Air Coil
61P510C02
61P511C02
Coax
62P504B01
62P542B01
TXV
33P608-02
33P608-03
Reversing Valve
33P506-04
33P503-05
61P549-01 62P543B01
33P608-05
62P555-01 33P608-10
33P608-11
33P526-04
36P500B01
Filter Dryer
Hot Water Generator
61P512C02
36P500B02
62P516-05
62P516-03
Comfort Alert
19P571-02
Contactor
13P004A03
Transformer 208-230/60/1
15P501B01
Transformer 265/60/1 Electrical
14S553-01
14S552-02
ICM Power Harness
Not available
Transformer 230/60/3
Not available
15P501B01
Not available
Transformer 460/60/3
Not available
15P505B01
Not available
Transformer 575/60/3
Not available
3 Pole Power Block
12P503-06
2 Pole Screw Term. Block
12P500A01
Status Light Board
17P503-02
Premier Board Sensors & Safeties
16P002-24
92P504A16
17P513-07
Freeze Protection Thermistor
12P505B03
HWL Thermistor
12P505B02
High Pressure Switch
35P506B02
Low Pressure Switch
35P506B01
Part numbers subject to change
01/09/13
53
ENVISION COMMERCIAL 0.75-6 TONS INSTALLATION MANUAL
Revision Guide Pages:
Description:
Date:
By:
All
Updated Nomenclature to Reflect new ECM Blower Motor
09 Jan 2013
DS
All
Removed FX10 & BACnet Variables Tables
09 Jan 2013
DS
11
Updated Weight Distribution Table
09 Jan 2013
DS
Updated Parts Lists
09 Jan 2013
DS
Added Revision Guide
09 Jan 2013
DS
50-53 54
54
Manufactured by WaterFurnace International, Inc. 9000 Conservation Way Fort Wayne, IN 46809 www.waterfurnace.com
IM1020AN
01/13
Product: Type: Size: Document:
Envision Series Geothermal/Water Source Heat Pump Commercial 0.75-6 Tons Installation Manual
©2013 WaterFurnace International, Inc., 9000 Conservation Way, Fort Wayne, IN 46809-9794. WaterFurnace has a policy of continual product research and development and reserves the right to change design and specifications without notice.