Filter Fan Kits
Company Information Terminal Blocks
Applications
018000-02
Features
• Easy filter change • Outer door lock for outdoor models • Impact resistant • Weather/UV resistant UL 94V-0 (indoor)/UL94H-B (outdoor) • No-screw installation - except outdoor models • Low noise • 120 VAC and 24 VDC models available • Service life - 50,000 hrs@77°F (25°C) + 65%RH • Connection type - 12 to 69 CFM - 2 wires w/case clamps, AWG 14, length 4”/136 to 373 CFM - 3 pole terminal, AWG 14, clamping torque 0.8 Nm • Airflow direction easily switched by reversing the axial fan (except on models 018040-01 and 018050-01) • Includes self-adhesive gasket pre-installed on frame • Optional mounting screws for additional support
Filter fans provide an optimum climate in enclosures. The interior temperature of enclosures is reduced by channeling cooler filtered outside air into the enclosure, thus expelling heated internal air. The resulting air flow prevents formation of localized heat pockets and protects electronic components from overheating. Outdoor filter fans are used in outdoor enclosures where warm air must be dissipated. To clean and exchange the filter mat, you open the lockable door of the outdoor hood, eliminating the need to allow interior access to the enclosure. IP55 protection type is achieved due to the special design of the hood and the use of fine filter mats.
Part Number
Standards
Free Air Delivery Max. Operating Power Filter Sound Required Amps Rated Consumption Flow Air with Static Temp. Filtering Price Density Level Cutout Level Delivery Exhaust Pressure (Max/Min (g/m2) (mA) Voltage (60 Hz for (dB) Sizes 120V models) (CFM)* (Pa)* °F/°C) (CFM)** Filter Fans
018000-02 $92.00
90
24 VDC
2.2W
12
9
19
018000-01 $68.00
160
120 VAC
13W
14
11
18
018010-02 $101.00
210
24 VDC
5W
32
25
32
018010-01 $75.00
180
120 VAC
15W
37
28
30
018020-02 $104.00
210
24 VDC
5W
60
40
23
39
018020-01 $91.00
180
120 VAC
15W
69
46
27
39
018040-01 $156.00
470
120 VAC
39W
136
84
60
018030-03 $276.00
840
24 VDC
20W
176
135
23
018030-01 $265.00
700
120 VAC
60W
202
156
27
018050-01 $218.00
780
120 VAC
85W
373
203
85
018210-04
$144.00
210
24 VDC
5W
12
11.8
48
018210-02 $123.00
180
120 VAC
15W
14
14
54
31 31 40
158/14 °F (70/-10°C)
40
350
94%
52
3.82 x 3.82 inch (97.03mm x 97.03mm) 4.92 x 4.92 inch (124.97mm x 124.97mm)
Multi-wire Connectors Sensor Cables and Connectors M12 Junction Blocks Panel Interface Connectors
53
140/-13°F (60/-25°C)
52
360
98%
40
9.84 x 9.84 inch (249.94mm x 249.94mm)
4.92 x 4.92 inch (124.97mm x 124.97mm)
Dimensions in inches (millimeters)
*Fan with filter and louver **Fan with filter, louver, exhaust filter, and grille.
Book 3 (14.3)
Enclosures Thermal Management
Cable Ties Wire Bulk Multi-conductor Cables Wire Management Products Power Supplies DC Converters Transformers and Filters Circuit Protection Tools Test Equipment
Enclosure Climate Control Safety: Electrical Components
Outdoor Filter Fans (Rain Hoods)
www.automationdirect.com/enclosures
ZIPLink Connection System
Enclosures
6.93 x 6.93 inch (176.02mm x 176.02mm)
53
158/14 °F (70/-10°C)
158/14 °F (70/-10°C)
Wiring Accessories
Wiring Duct
All models except outdoor: CE, RoHS, IP55, UL Type 12 when using supplied filter. For use with NEMA 1 and NEMA 12 enclosures only. UL #: E234324 Note: Using fine filter mat F5 reduces the airflow. (See Stego Air Volume and Pressure Data, later in this section.)
140/-13°F (60/-25°C)
Power Distribution Blocks
EN-259
Safety: Protective Wear Terms and Conditions
Prices as of April 15, 2015. Check Web site for most current prices.
Filter Fan Kit Cutouts and Dimensions Dimensions [in mm] 018000-01 018000-02
018010-01 018010-02
Book 3 (14.3)
EN-260
Enclosures Thermal Management
1-800-633-0405
Prices as of April 15, 2015. Check Web site for most current prices.
Filter Fan Kit Cutouts and Dimensions
Company Information Terminal Blocks
Dimensions [in mm]
Power Distribution Blocks
018210-04 018210-02
Wiring Accessories ZIPLink Connection System Multi-wire Connectors Sensor Cables and Connectors M12 Junction Blocks Panel Interface Connectors Wiring Duct Cable Ties Wire Bulk Multi-conductor Cables Wire Management Products Power Supplies DC Converters Transformers and Filters
018020-01 018020-02
Circuit Protection Tools Test Equipment Enclosures Enclosure Climate Control Safety: Electrical Components Safety: Protective Wear Terms and Conditions
www.automationdirect.com/enclosures
Book 3 (14.3)
Enclosures Thermal Management
EN-261
Prices as of April 15, 2015. Check Web site for most current prices.
Filter Fan Kit Cutouts and Dimensions Dimensions [in mm] 018040-01
018030-01 018030-03
Book 3 (14.3)
EN-262
Enclosures Thermal Management
1-800-633-0405
Prices as of April 15, 2015. Check Web site for most current prices.
Filter Fan Kit Cutouts and Dimensions
Company Information Terminal Blocks Power Distribution Blocks
Dimensions [in mm]
Wiring Accessories ZIPLink Connection System
018050-01
Multi-wire Connectors Sensor Cables and Connectors M12 Junction Blocks Panel Interface Connectors Wiring Duct Cable Ties Wire Bulk Multi-conductor Cables Wire Management Products Power Supplies DC Converters Transformers and Filters Circuit Protection Tools Test Equipment Enclosures Enclosure Climate Control Safety: Electrical Components Safety: Protective Wear Terms and Conditions
www.automationdirect.com/enclosures
Book 3 (14.3)
Enclosures Thermal Management
EN-263
Prices as of April 15, 2015. Check Web site for most current prices.
Exhaust Grilles With Filters Features
118000-00
• No-screw installation • Mounting depth 0.6 in. (16mm)
Accessories
• Come with gaskets attached (adhesive-sided to stick on panel)
Part Number
Price
Filter Density (g/ m2)
Mass Filter Level %
Exhaust Grilles 118000-00
$15.50
118010-00
$19.50
118020-00
$22.00
118030-00
$56.00
350
94%
Outdoor Exhaust Grilles 118210-00
$89.00
360
98%
Dimensions in inches (millimeters)
Dimensions [in mm] 118000-00
Book 3 (14.3)
EN-264
Enclosures Thermal Management
1-800-633-0405
Prices as of April 15, 2015. Check Web site for most current prices.
Exhaust Grille and Filter Accessories
Company Information Terminal Blocks Power Distribution Blocks
118010-00
Wiring Accessories ZIPLink Connection System Multi-wire Connectors Sensor Cables and Connectors M12 Junction Blocks Panel Interface Connectors Wiring Duct Cable Ties Wire Bulk Multi-conductor Cables Wire Management Products Power Supplies DC Converters
118020-00
Transformers and Filters Circuit Protection Tools Test Equipment Enclosures Enclosure Climate Control Safety: Electrical Components Safety: Protective Wear Terms and Conditions
www.automationdirect.com/enclosures
Book 3 (14.3)
Enclosures Thermal Management
EN-265
Prices as of April 15, 2015. Check Web site for most current prices.
Exhaust Grille and Filter Accessories 118030-00
118210-00
Book 3 (14.3)
EN-266
Enclosures Thermal Management
1-800-633-0405
Prices as of April 15, 2015. Check Web site for most current prices.
Replacement Filter Elements 086000-00
Company Information Terminal Blocks
Applications
Power Distribution Blocks
•Replacement filter mats for Stego series filter fans and Stego series exhaust grilles
Features
Wiring Accessories
• Filter media for enclosure fans • Fine or medium density • Fits 3.82 x 3.82, 4.92 x 4.92, 6.93 x 6.93, or 9.84 x 9.84 inch filter fans • Package of 3
ZIPLink Connection System Multi-wire Connectors Sensor Cables and Connectors
Replacement Filter Elements Part Number
Price
086000-00
$5.00
086010-00
$6.00
086020-00 086080-00 086030-00
With Filter Pieces per Use Fan Kit Package NumberPart 018000-01 018000-02
3
3.5 x 3.5 (88.90x88.90)
118010-00
4.6 x 4.6 (116.84x116.84) G4 (Med.)
018020-01 018020-02 018040-01 018030-01 018030-03 018050-01 018000-01 018000-02
$20.00
118000-00
M12 Junction Blocks Panel Interface Connectors Wiring Duct
018010-01 018010-02
$8.00
$6.00
Mass Dimensions HxW Use With Exhaust Grille Filter Filter Density Filter and Filter Part Number Rating g/m2 Level % in (mm)
350
94
118020-00
6.6 x 6.6 (167.64x167.64)
118030-00
9.7 x 9.7 (246.38x246.38)
118000-00
3.5 x 3.5 (88.90x88.90)
Cable Ties Wire Bulk Multi-conductor Cables Wire Management Products Power Supplies
086040-00
086050-00 086090-00
018010-01 018010-02 018210-02 018210-04
118010-00
$12.00
018020-01 018020-02 018040-01
118020-00
$24.00
018030-01 018030-03 018050-01
118030-00
$7.50
4.6 x 4.6 (116.84x116.84) F5 (Fine)
360
DC Converters Transformers and Filters
98 6.6 x 6.6 (167.64x167.64)
Circuit Protection Tools
9.7x9.7 (246.38x246.38mm)
Test Equipment Enclosures
Air Volume and Pressure Data Part Number 018000-02 018000-01 018010-02 018010-01 018020-02 018020-01 018040-01 018030-03 018030-01 018050-01 018210-04 018210-02
Filter Mat Air Volume (cfm) G4 filter free flow*
G4 filter with exhaust filter**
F5 filter free flow*
Filter Mat Static Pressure (Pa) F5 filter with exhaust filter**
G4 filter free flow*
F5 filter free flow*
12
9
4
3
19
37
14
11
5
4
18
35
32
25
16
13
32
53
37
28
19
15
30
50
60
40
31
21
23
30
69
46
36
24
27
35
136
84
58
36
60
100
176
135
47
36
23
46
202
156
54
42
27
54
373
203
145
83
85
140
30
n/a
12
n/a
48
74
35
n/a
14
n/a
35
54
*Fan with filter and louver **Fan with filter, louver, exhaust filter, and grille.
www.automationdirect.com/enclosures
Book 3 (14.3)
Enclosures Thermal Management
EN-267
Enclosure Climate Control Safety: Electrical Components Safety: Protective Wear Terms and Conditions
Prices as of October 21, 2015. Check Web site for most current prices.
Enclosure Accessories - Miscellaneous
Company Information
Vapor Capsule
Terminal Blocks Power Distribution Blocks
Carrying Handle
Wiring Accessories ZIPLink Connection System Multi-wire Connectors Sensor Cables and Connectors
Carrying Handle
Price
HW-CARRYINGHANDLE
Description
Vapor Capsule
Wt.
Non-metallic black handle, for $16.50 use on Hubbell-Wiegmann 2 oz. non-metallic enclosures.
HW-C12
Strip Gasket
Price
Wt.
Non-toxic vapor emitted from the capsule passivates the metal surfaces on the interior of the enclosure against atmospheric corrosion for $13.50 up to one year by reducing the electro-chemical activity of the metal surfaces. Installs easily with a self-adhesive strip.
M12 Junction Blocks Panel Interface Connectors
1 oz.
Wiring Duct Cable Ties Wire
Strip Gasket Price
1 - 14 days
Description
Wt.
WGAS51634
Hubbell-Wiegmann strip gasket, replacement, self-adhesive, microcell urethane foam, $16.00 5/16 inch thick x 3/4 inch wide x 10 ft long roll. For gasket replacement on HubbellWiegmann wall-mount NEMA 12, 4 & 4X enclosures.
7oz.
WGAS3834
Hubbell-Wiegmann strip gasket, replacement, self-adhesive, closed cell sponge rubber, $16.00 3/8 inch thick x 3/4 inch wide x 10 ft long roll. For gasket replacement on HubbellWiegmann floor-mount and freestanding NEMA 12, 4 & 4X enclosures.
7oz.
Enclosure Shipping Schedule Same day
Description
Color indicates shipping lead time in business days.
Bulk Multi-conductor Cables Wire Management Products Power Supplies DC Converters Transformers and Filters Circuit Protection
Dimensions in [mm]
Tools Test Equipment
Locking Protective Cover
Enclosures Enclosure Climate Control Safety: Electrical Components Safety: Protective Wear Terms and Conditions
Features
• Packaged multi-purpose protective cover • Locking door • Weather and UV resistant (UL 94-HB) • IP 20 Protection Class • Includes mounting screws
Locking Protective Cover 086110-00
Description
Price
Stego multi-purpose protective cover with locking door, weather and UV resistant (UL 94-HB), IP20 protection class. Includes mounting screws and keys.
$37.00
Book 3 (14.3)
www.automationdirect.com/enclosures
Enclosures Accessories
EN-239
Prices as of April 15, 2015. Check Web site for most current prices.
Enclosure Cooling – Selecting a Fan or Air Conditioner Fan selection
Fan Selection Example
To select the proper size (CFM) fan for your forced air cooling solution, you need to determine the amount of heat to be removed (in watts) and determine the Delta T (Max. allowable internal enclosure temperature °F – Max. outside ambient temperature°F). CFM = Cubic Feet per Minute P = Power to be dissipated in watts CFM = (3.17 x Pwatts) / Delta T °F Delta T = m ax. allowable internal enclosure temperature °F – max. outside ambient temperature °F
A NEMA 12 Hubbell Wiegmann N12302412 enclosure (30” high x 24” wide x 12” deep) contains a GS3-2020 AC drive (20 HP 230 volt) that has a maximum allowable operating temperature of 104°F and is located in a warehouse that has a maximum outside ambient air temperature of 95°F. Power to be dissipated is stated in the specifications of the GS3-2020 and is found to be 750 watts, so P=750 watts Delta T = Max. operating temperature for the GS3-2020 is 104°F – Max. ambient air temperature of 95°F Delta T = 9°F CFM = (3.17 x 750 watts) / 9°F CFM = 264
Choose a Hubbell Wiegmann WPF60-115BK filter fan kit that provides 295 CFM with exhaust kit WPFA50-60BK
Air conditioner and vortex cooler selection To select the proper size air conditioner or vortex cooler, the worst-case conditions should be considered, but take care not to choose an oversized unit. There are two main factors in choosing an uninsulated metal NEMA rated enclosure located indoors: • Internal heat load • Heat load transfer
Internal Heat Load Internal heat load is the heat generated by the components inside the enclosure. This can be determined by a few different methods. The preferred method is to add the maximum heat output specifications that the manufacturers list for all the equipment installed in the cabinet. This is typically given in Watts, so use the following conversion: BTU per Hour = Watts x 3.413
Example: The Watt-loss chart for the GS3 Drives shows that a GS3-2020 AC drive has a Watt-loss of 750 watts. BTU per Hour = 750 watts x 3.413 BTU per Hour = 2559
Heat Load Transfer Heat load transfer is the heat lost (negative heat load transfer) or gained (positive heat load transfer) through the enclosure walls with the surrounding ambient air. This can be calculated by the following formula: Heat load transfer (BTU/H) = 1.25 x surface area (sq. ft. ) x (max. outside ambient air (°F) – max. allowable internal enclosure temperature air (°F)) Surface Area (sq. ft.) = 2 [(H x W) + (H x D) + (W x D)] / 144 sq. inches
Air Conditioner Selection Example A NEMA 12 Hubbell Wiegmann N12302412 enclosure (30” high x 24” wide x 12” deep) contains a GS3-4030 AC drive 30 HP 460 volt) that has a maximum allowable operating temperature of 104°F and is located in a warehouse that has a maximum outside ambient air temperature of 115°F. Power to be dissipated is stated in the specifications of the GS3-4030 and is found to be 1290 watts. Internal heat load: BTU per Hour = 1290 watts x 3.413 BTU per Hour = 4403 BTU/H
Heat load transfer: Heat load transfer (BTU/H) = 1.25 x 19 sq. ft. x (115°F – 104°F) Heat load transfer (BTU/H) = 261.25 BTU/H
Cooling capacity: Cooling capacity (BTU/H) = 4403 BTU/H + 261.25 BTU/H Cooling capacity (BTU/H) = 4664.25 BTU/H
In this example, you are able to determine that a 5000 BTU/H unit is needed. Select a TA10-050-16-12 Stratus air conditioner. Note: The same calculation method is used for sizing Stratus vortex coolers. However, in this example the cooling requirements exceed the maximum capacity of the largest available vortex cooler.
If the example
application required the use of a vortex cooler instead of an air conditioner, two
(2) TV35-025-4X units would
be needed. Thermal Expansion Valve Evaporator
Condenser
Note: 1.25 is an industry standard constant for metal enclosures; 0.62 should be used for plastic enclosures.
Once you have determined your Internal Heat Load and the Heat Load Transfer, you can choose the proper size unit by calculating the needed cooling capacity.
Compressor
Cooling capacity (BTU/H) = Internal Heat Load ± Heat Load Transfer Book 3 (14.3)
EN-242
Enclosures Thermal Management
1-800-633-0405
Prices as of April 15, 2015. Check Web site for most current prices.
Enclosure Cooling – Selecting a Heat Exchanger Heat exchanger selection To select the proper size heat exchanger, the worst-case conditions should be considered. For a heat exchanger to work, the ambient air temperature must be lower than the desired internal enclosure air temperature. There are three main factors in choosing a heat exchanger for an uninsulated metal NEMA rated enclosure located indoors: • Internal heat load • Delta T • Heat load transfer
Internal Heat Load Internal heat load is the heat generated by the components inside the enclosure. This can be determined by a few different methods. The preferred method is to add the maximum heat output specifications that the manufacturers list for all the equipment installed in the cabinet. This is typically given in Watts.
Delta T (ΔT) Delta T = maximum allowable internal enclosure temperature °F – maximum outside ambient temperature °F.
Heat Load Transfer Heat load transfer is the heat lost (negative heat load transfer) or gained (positive heat load transfer) through the enclosure walls with the surrounding ambient air. This can be calculated by the following formulas: Surface Area (sq. ft.) = 2 [(H x W) + (H x D) + (W x D)] / (144 sq. inches/sq. ft.)
Company Information Terminal Blocks Power Distribution Blocks Wiring Accessories
Heat Exchanger Selection Example A NEMA 12 Hubbell Wiegmann N12302412 enclosure (30” high x 24” wide x 12” deep) contains a GS3-4010 AC drive 10 HP 460 volt) that has a maximum allowable operating temperature of 104°F and is located in a warehouse that has a maximum outside ambient air temperature of 90°F.
ZIPLink Connection System
Power to be dissipated is stated in the specifications of the GS3-4010 and is found to be 345 watts.
Sensor Cables and Connectors
Multi-wire Connectors
M12 Junction Blocks
Internal heat load:
Panel Interface Connectors
Internal Heat Load = 345 Watts
Wiring Duct
Delta T:
Cable Ties
ΔT (°F) 104°F – 90°F = 14°F
Wire
Heat load transfer:
Surface Area (ft.2) = 2 [(30 x 24) + (30 x 12) + (24 x 12)] / 144 sq. inches = 19 ft.2 Heat Load Transfer = 0.22 x 19 ft2 = 4.2 Watts/°F
Cooling capacity: Cooling Capacity = 345 Watts/14°F - 4.2 Watts/°F = 20.4 Watts/°F
Bulk Multi-conductor Cables Wire Management Products Power Supplies DC Converters
In this example, you are able to determine that a Stratus heat exchanger, with a capacity of at least 20.4 Watts/°F is needed, such as a TE30-030-17-04.
Transformers and Filters Circuit Protection
*This selection procedure applies to metal and non-metal, uninsulated, sealed enclosures in indoor locations. This selection procedure gives the minimum required size; be careful not to undersize when purchasing.
Note: Only include exposed surfaces of enclosue in calculations. Exclude surfaces such as a surface mounted to a wall.
Test Equipment Enclosures Enclosure Climate Control Safety: Electrical Components
Heat Load Transfer (W/°F) = 0.22 W/°F sq. ft. x surface area
Safety: Protective Wear
Note: Use 0.22 Watts/°F sq. ft. for painted steel and nonmetallic enclosures. Use .10 Watts/°F sq. ft. for stainless steel and bare aluminum enclosures.
Terms and Conditions
Cooling Capacity Once you have determined your Internal Heat Load, the Heat Load Transfer and the Delta T, you can choose the proper size unit by calculating the needed cooling capacity. Cooling Capacity (W/°F) = Internal Heat Load / ∆T - Heat Load Transfer
www.automationdirect.com/enclosures
Tools
Book 3 (14.3)
Enclosures Thermal Management
EN-243
Prices as of April 15, 2015. Check Web site for most current prices.
This “.com” is powered by “.awesomepeople” Check us out for our prices, keep coming back for our service. For over twenty years our sole focus has been customer service. That takes many forms: great prices, fast delivery, and quality products. But regardless of our product selection and other tangibles like pricing, the intangible value of customer service is something that cannot be faked, replaced by machinery or glossed over with a free lunch from a visiting sales rep. Our team members here at AutomationDirect.com approach every day with this one goal in mind - serve the customer. It’s a simple philosophy that many companies forget or make too complex and then fail at it. If the answer to any decision is “Yes, this is good for our customers”, then we do it.
It’s that simple. “Should we have real upfront pricing online and realtime stock availability? Yes, this is good for our customers.”
“Should we have FREE tech support before, during, and after any sale instead of charging yearly fees for tech support?
Yes, this is good for our customers.”
“Should we offer FREE software on many products instead of charging licensing fees? Yes, this is good for our customers.”
“Should we have all our documentation online for FREE so people can access anytime, even before they choose to purchase? Yes, this is good for our customers.”
“Should we offer more selection by consistenly introducing more new quality products with great prices monthly, sometimes weekly? Yes, this is good for our customers.”
“Should we offer FREE shipping for orders over $49? Yes, this is good for our customers.”
Voted #1 in service since 2001:
“Should we be fiscally responsible and run an efficient business so customers can rely on us decade after decade after decade? Yes, this is good for our customers.”
www.automationdirect.com/awards
Voted #1 mid-size company to work for in Atlanta:
www.automationdirect.com/workplace
Our company has evolved dramatically since 1994 and it’s this type of decision making by all our team members over the years that keeps our customers coming back and new customers checking us out daily.
What our current customers think:
If you’re a current customer, we sincerely thank you for your business. We wouldn’t be here if it wasn’t for you and promise to do our best for you every day. If you’re new and checking us out for the first time, we hope you give us an opportunity to serve you.
www.automationdirect.com/reviews Book 3 (14.3)
All these are discussions we’ve had internally and all have had certain aspects of “can we do that?”, “that will be hard to accomplish”, “no one else is doing that, how can we?”. But if you bring it back to the simple answer, “Yes, this is good for our customers”, then the perceived obstacles really don’t matter.
EN-244
Enclosures Thermal Management
1-800-633-0405
Prices as of April 15, 2015. Check Web site for most current prices.
Air Conditioners For NEMA 12 Enclosures Applications
Company Information Terminal Blocks Power Distribution Blocks
Features
Construction
• F ree-standing rigid chassis for easy installation and maintenance • F abricated from 16-gauge cold rolled steel •A NSI-61 gray polyester powder coating inside and out • P re-cut mounting gasket included, to be field installed •A ll mounting hardware, full-size template and instruction manual included • Power input terminal block on all models
Wiring Accessories
• Digital LED temperature controller with visible alarm features and 14.2 mm (0.55”) numbers • Pre-wired for external alarm monitoring connections (22 AWG three-conductor cable, 7 ft. long) • CFC-free refrigerant • Active condensate management system • Thermal expansion valve for maximum efficiency over wide range of temperatures and loads • Fits 12 inch deep enclosures that have smooth/flat sides. Check enclosure dimensions/specifications before ordering. • Anti short-cycle compressor protection • High and low refrigerant cut-outs with fault indication • Highly energy-efficient compressors • UL/cUL listed
Designed to maintain the temperature inside an electrical enclosure at or below a safe level for the enclosed equipment, while maintaining a closed loop environment inside the enclosure to keep out contaminates that can be in the ambient air. Can be used in such environments as steel, food processing, petro-chemical, cement, paper/pulp and plastics industries.
ZIPLink Connection System Multi-wire Connectors Sensor Cables and Connectors M12 Junction Blocks Panel Interface Connectors Wiring Duct Cable Ties Wire Bulk Multi-conductor Cables
Listings
• UL File: SA33404 • UL 50, Type 12 • Made in USA
Wire Management Products Power Supplies DC Converters
TA10-060-26-12 shown
Part Number
Price BTU/Hour Voltage/Hz Running Amps
TA10-010-16-12
$1,266.00
TA10-010-26-12
$1,481.00
TA10-015-16-12
$1,536.00
TA10-015-26-12
$1,607.00
TA10-020-16-12
$1,633.00
TA10-020-26-12
$1,713.00
TA10-020-46-12
$2,323.00
TA10-040-16-12
$1,757.00
TA10-040-26-12
$1,841.00
TA10-040-46-12
$2,378.00
TA10-050-16-12
$1,909.00
TA10-050-26-12
$1,941.00
TA10-050-46-12 TA10-060-16-12 TA10-060-26-12
$2,226.00
TA10-060-46-12
$3,213.00
Weight with/without Packaging (lbs)
120/60
3.44
72/54
230/60
2.67
72/54
120/60
3.89
72/54
230/60
2.67
72/54
120/60
5.15
87/69
230/60
3.07
87/69
480/60
1.51
113/95
120/60
3.76
88/70
230/60
3.07
88/70
480/60
0.93
114/96
120/60
7.26
107/89
230/60
3.76
107/89
$2,928.00
480/60
1.44
150/132
$2,205.00
120/60
7.83
114/96
230/60
4.80
114/96
480/60
1.80
157/39
1000 1500
2000
3000 - 4000
5000
6000 - 8000
Max. Ambient Frame Temp Size
1
Circuit Protection Tools Test Equipment Enclosures Enclosure Climate Control Safety: Electrical Components
2 125°F (51.67°C)
3
Book 3 (14.3)
Enclosures Thermal Management
Safety: Protective Wear Terms and Conditions
* Voltage variation no greater than ± 10% from nameplate rating and Frequency variation no greater than ± 3Hz from nameplate rating.
www.automationdirect.com/enclosures
Transformers and Filters
EN-245
Prices as of April 15, 2015. Check Web site for most current prices.
Air Conditioners For NEMA 4 Enclosures Applications
Features
• Digital LED temperature controller with visible alarm features and 14.2 mm (0.55”) numbers • Pre-wired for external alarm monitoring connections (22 AWG three-conductor cable, 7 ft. long) • CFC-free refrigerant • Protective coated condenser coils for corrosion resistance • Active condensate management system • Thermal expansion valve for maximum efficiency over wide range of temperatures and loads • Fits 12-inch deep enclosures that have smooth/flat sides. Check enclosure dimensions/specifications before ordering. • Anti short-cycle compressor protection • High and low refrigerant cut-outs with fault indication • Highly energy-efficient compressors • UL/cUL listed
Designed to maintain the temperature inside an electrical enclosure at or below a safe level for the enclosed equipment, while maintaining a closed loop environment inside the enclosure to keep out contaminates that can be in the ambient air. Can be used in such environments as steel, food processing, petro-chemical, cement, paper/pulp and plastics industries.
Construction
• Free-standing rigid chassis for easy installation and maintenance • Fabricated from 16-gauge cold rolled steel • ANSI-61 gray polyester powder coating inside and out • Pre-cut mounting gasket installed for NEMA/ UL type rating on all units • All mounting hardware, full-size template and instruction manual included • Power input terminal block on all models
Listings
• UL File: SA33404 • UL 50, Type 4 • Made in USA
TA10-060-26-04 shown
Part Number
Price
TA10-010-16-04 TA10-010-26-04 TA10-015-16-04 TA10-015-26-04 TA10-020-16-04 TA10-020-26-04 TA10-020-46-04 TA10-040-16-04 TA10-040-26-04 TA10-040-46-04 TA10-050-16-04 TA10-050-26-04 TA10-050-46-04 TA10-060-16-04 TA10-060-26-04
$1,575.00
TA10-060-46-04
$3,378.00
$1,599.00 $1,657.00 $1,737.00
BTU/Hour 1000 1500
$1,763.00 $1,778.00
Running Amps
Weight with/without Packaging (lbs)
120/60
3.44
72/54
230/60
2.67
72/54
120/60
3.89
72/54
230/60
2.67
72/54
120/60
5.15
87/69
230/60
3.07
87/69
$2,343.00
480/60
1.51
113/95
$1,896.00
120/60
3.76
88/70
$1,907.00
2000
Voltage/Hz
3000 - 4000
230/60
3.07
88/70
$2,400.00
480/60
0.93
114/96
$2,059.00
120/60
7.26
107/89
$2,089.00
5000
230/60
3.76
107/89
$3,073.00
480/60
1.44
150/32
$2,366.00
120/60
7.83
114/96
230/60
4.80
114/96
480/60
1.80
157/139
$2,394.00
6000 - 8000
Max. Ambient Temp
Frame Size 1
2 125°F (51.67°C)
3
* Voltage variation no greater than ± 10% from nameplate rating and Frequency variation no greater than ± 3Hz from nameplate rating.
Book 3 (14.3)
EN-246
Enclosures Thermal Management
1-800-633-0405
Prices as of April 15, 2015. Check Web site for most current prices.
Air Conditioners For NEMA 4X Enclosures Applications
Company Information Terminal Blocks Power Distribution Blocks
Features
• Digital LED temperature controller with visible alarm features and 14.2 mm (0.55”) numbers • Pre-wired for external alarm monitoring connections (22 AWG three-conductor cable, 7 ft. long) • CFC-free refrigerant • Protective coated condenser coils for corrosion resistance • Active condensate management system • Thermal expansion valve for maximum efficiency over wide range of temperatures and loads • Fits 12-inch deep enclosures that have smooth/flat sides. Check enclosure dimensions/specifications before ordering. • Anti short-cycle compressor protection • High and low refrigerant cut-outs with fault indication • Highly energy-efficient compressors • UL/cUL listed
Designed to maintain the temperature inside an electrical enclosure at or below a safe level for the enclosed equipment, while maintaining a closed loop environment inside the enclosure to keep out contaminates that can be in the ambient air. Can be used in such environments as steel, food processing, petro-chemical, cement, paper/pulp and plastics industries.
Construction
• F ree-standing rigid chassis for easy installation and maintenance • F abricated from 16-gauge 304 stainless steel • P re-cut mounting gasket installed for NEMA/ UL type rating on all units •A ll mounting hardware, full-size template and instruction manual included • P ower input terminal block on all models
Wiring Accessories ZIPLink Connection System Multi-wire Connectors Sensor Cables and Connectors M12 Junction Blocks Panel Interface Connectors Wiring Duct Cable Ties Wire Bulk Multi-conductor Cables
Listings
Wire Management Products
• UL File: SA33404 • UL 50, Type 4X • Made in USA
TA10-060-16-4X shown
Power Supplies DC Converters Transformers and Filters
Part Number
Price
BTU/Hour
Voltage/Hz
Running Amps
Weight with/without Packaging (lbs)
120/60
3.44
72/54
230/60
2.67
72/54
120/60
3.89
72/54
230/60
2.67
72/54
120/60
5.15
87/69
TA10-010-16-4X
$2,341.00
TA10-010-26-4X
$2,367.00
TA10-015-16-4X
$2,426.00
TA10-015-26-4X
$2,452.00
TA10-020-16-4X
$2,434.00
TA10-020-26-4X
$2,495.00
230/60
3.07
87/69
TA10-020-46-4X
$2,740.00
480/60
1.51
113/95
TA10-040-16-4X
$2,857.00
120/60
3.76
88/70
TA10-040-26-4X
$2,923.00
230/60
3.07
88/70
TA10-040-46-4X
$2,923.00
480/60
0.93
114/96
TA10-050-16-4X
$2,904.00
120/60
7.26
107/89
TA10-050-26-4X
$2,931.00
230/60
3.76
107/89
TA10-050-46-4X
$3,248.00
480/60
1.44
150/132
TA10-060-16-4X
$3,106.00
120/60
7.83
114/96
TA10-060-26-4X
$3,131.00
230/60
4.80
114/96
TA10-060-46-4X
$3,448.00
480/60
1.80
157/139
1000 1500
2000
3000 - 4000
5000
6000 - 8000
www.automationdirect.com/enclosures
Max. Ambient Temp
Frame Size
Circuit Protection Tools Test Equipment
1
Enclosures Enclosure Climate Control Safety: Electrical Components
2 125°F (51.67°C)
Terms and Conditions
3
Book 3 (14.3)
Enclosures Thermal Management
Safety: Protective Wear
EN-247