Transcript
K60 Series Protection Relay Test Set
Catalogue
Exclusive: 6*60A large current 1.Use modularization switch power and self-RD hi-fi digital amplifier, with capacity efficient more than 85%, high output power, low weight and small heating value, to make sure for long time and reliable ×10A output. Strong ability for overloading for reliable quality hardware. 2.Internal high-capacity SSD solid state disk, to make sure the normal running in the status of high speed moving or even tilting, so that the data will not lose when collision and shock. 3.Internal dual core CPU industrial PC, 9.7 inch large LED display screen, 1024×768 resolution, embedded Windows XPE system, to provide friendly interface for use for the onsite calibration at smart substations..
Functions Characteristic 1. 13 pcs of channels simultaneous output, that is to output 7 phase voltage and 6 phase current with different amplitude, frequency, phase; 2. With wave form distortion test function, judgment of wrong wiring alarm, self-locking, housing grounding alarm. 3. Provide convenient and prompt all software calibration for amplitude and phase, no need to open the housing to calibrate the output precision;
4. 0~300V/0 .6A remote aux. DC power output; 5. To test by manual or automatic mode for various types of voltage, current, frequency, power, impedance, harmonic, differential, simultaneous relays, and can simulate various types of failure to perform the experiment of distance, zero sequence and reclose test. With GPS trigger function, to perform the test of reserve supply, prompt switch, etc. 6. Internal GPS function; 7. Optional function for standard meter, transducer, energy meter, etc.
K60 Series Tester Model List Model K6066 K6063 K6030
Current 6×30A 6×30A 6×60A 6×30A 6×30A 3×30A 3×30A
K6066 K6066i K6066S K6063 K6063i K6030 K6030i
K6066 Main Technical Parameters AC Voltage Source
Output range
Output power
Precision Resolution
7-phase AC(L-N) 3-phase AC(L-L) 7×130 V (L-N) 2×600 V (L-L)
7×0~130V 3×0~260V 1×70 VA max 1×110 VA max
±2 mV (0.2 V~2 V) ±0.1% (2 V~130 V)
1mV
AC Current Source
Output range
Output power
6-phase AC(L-N) 1 phase AC(6L-N)
6×0~30 A 1×0~100 A
6×30A(L-N)
6×220 VA max
1×30A(L-N)
1×450 VA max
1×100A(LN)
1×1000 VA max
Voltage 7×130V 7×300V 7×130V 4×130V 4×300V 4×130V 4×300V
±1 mA (0.2A~0.5A) Precision
±0.1% (0.5A~20A) ±0.1% (20A~Imax)
Resolution
1mA
Frequency Output Range
5~1000 Hz <0.001 Hz (5~65 Hz)
Precision
<0.01 Hz (65~450 Hz) <0.02 Hz (450~1000 Hz)
Resolution Phase Output
0.001 Hz
Range
-360°~360°
Precision
<0.2°
Resolution
0.1°
Timing Function Timing range
0.1 ms~1.5×105 s
Timing accuracy
±1ms(0.001s~1s)±0.1%(1s~1.50× 105 s)
DC voltage、DC current Range DC voltage
Accuracy Range
DC current Aux.DC
Accuracy
0~300V/180W ±10mV (0.5 V~5 V) ±0.5% (5 V~300 V) 0~30A/300W ±5mA (0.2 A~1 A) ±0.5% (1 A~30 A)
Voltage Source
Range
0~300V/0.6A
Binary Input Number
8pairs
Compatible voltage
0V~250V
Binary Output Number
4pairs
Capacity
250V/3A (AC/DC)
DC Measurement Input(Optional) Voltage Range
0~±10V,1MΩ
Current Range
0~±20mA,15Ω
Precision
<0.05% RG
AC Measurement Input(Optional) Voltage Range
0~130V,<0.2% RG
Current Range
0~5A (Clamp-shape CT Connection),<0.5% RG
Frequency Range
45~65 Hz,< 0.01 Hz
Phase
0~360°,< 0.5°
Harmonic
2~20times,<0.5% RG
Synchronization Synchronization mode
GPS
Harmonic Superimposed Numbers
2~20times
Power supply Rated voltage
220V
Power supply range
88~264VAC,125~350VDC
Power
1500 VA
Power supply frequency
47Hz~63Hz
Working Condition Working temperature
-20℃~70℃
Humidity
≤95%, No condensation
Weight & Size Weight
17.5 kg
Size
360×480×190(mm)
Online interface
RJ45