Transcript
Models: ST7P-2A15S-ADC, ST7P-2A13T-ADC, ST7P-2A16T-ADC, ST7P-2A11N-ADC ST7P-2A16N-ADC
FUJI MINIATURE DIN TIMER MANUAL Safety Precautions To ensure safe and proper operation, read this manual before installation, wiring, operation, maintenance, and inspection. Manual should be furnished to the final user.
Original Edition May 2003
WARNING: Incorrect installation or operation may cause death or serious injury, and damage to equipment. It may also be necessay to use fail-safe measures if controlling a critical process or safety application.
•
Remove input power before installation, wiring, maintenance or inspection to prevent electrical shock.
•
Do not use this device if damaged when unpacked.
•
Only qualified personnal should perform installation, maintenance or inspection of this device.
•
To prevent fire, accidents and malfunction of this device, do not install in environments with high temperature, high humidity, dust, corrosive gases, water, direct sunlight or excessive vibration. Do no expose the case to solvents or corrosive substances such as benzene, strong acids or alkaloids.
•
Use this device within the range of its rated voltage and current.
•
Fire may occur if the power supply and load are incorrectly connected.
•
To prevent poor contact operation, keep timer from exposure to dust, concrete chips, iron filings and similar materials.
•
To prevent terminal malfunction, tighten periodically.
•
Never disassemble, modify or repair this device.
•
If replacing this device, be sure to dispose of it properly.
Operation •
Set the time within the range of the timing scale divisions. To make timer output a signal as soon as power is turned on, turn timer dial fully counterclockwise.
•
The timer dial can be turned while the timer is operating, but the time for that operation will not be correct.
•
Do not try to turn the timer dial outside the timing range. Turn dial carefully and do not force.
•
Do not remove the timer case, or the operating characteristics will change.
Dimensions (Timer and Socket Shown Attached)
Control
ON
4
6
2
8
0
10 860
ST7
32.4
85.6
Set t i ng Dial 69
UP
P ower I ndi cat or
4.5
O u tput In d icator
Fuji Miniature DIN Timer Manual
1
Specifications Approvals
UL file no.: Body - E44592, Socket - E90265; CSA file no.: LR20479; TÜV license no: R9551799
Repeat Accuracy Reset Time Maximum Operating Cycle
±01% at maximum setting time 0.1 second or less 1800 cycles/hour
Operating Voltage Range
85-132VAC
20.4-26.4VDC
ST7P-2A15S-ADC ST7P-2A13T-ADC ST7P-2A16T-ADC ST7P-2A11N-ADC ST7P-2A16N-ADC
ST7P-2DE5S-ADC ST7P-2DE3T-ADC ST7P-2DE6T-ADC ST7P-2DE1N-ADC ST7P-2DE6N-ADC
Operating Temperature Range Humidity
-10 to +50°C (14 to 122°F)
Contact Ratings
3A @ 240VAC resistive load, 1A @120VAC inductive load; 3A @ 30VDC resistive load, 0.5A @ 30VDC inductive load Approx. 1.2VA at 100VAC, approx. 1.5VA at 200VAC, 1.1W at 24VDC.
35 to 85% (no condensation)
Power Consumption Insulation Resistance Surge Voltage*
100M at 500VDC insulation tested 3000 Volts
Dielectric Strength
2000VAC 1 min. between current carrying part and noncurrent carrying part 2000VAC 1 min. between output contact and control circuit 1000VAC 1 min. between open contacts
Vibration
Malfunction durability: 10 to 55Hz, 0.5mm double amplitude Mechanical durability: 10 to 55Hz, 0.7mm double amplitude
Shock
Malfunction durability: 50m/s2 Mechanical durability: 1000m/s2
Life Expectancy
Mechanical: 50 million operations Electrical: 500,000 operations
Weight
36.288g (1.28 oz.)
Dimensions - ST7P Body
5.7
2.2
0.5
All dimensions in mm
4
18.5
1 5
8
9
12
13
14
27.8
UP
ON
X1
4
X10
1.8
52.6
21
Dimensions - TP88X2 Body 32.4 6.8 4 1
Approx. 56.6
5
12
9
69
59
8
Panel Drilling
29 22.6 10.5
24.5 14
13
10.6
Wiring Diagram
(- )
1
4
5
8
9
12
13
14
Timing Diagram
Sockets/Screw Terminal and Rail Mounting 4 8
1 5
(+ )
INPUT
2
2- 4 (M3, M4) 34
Terminal M3.5x8
Fuji Miniature DIN Timer Manual
12 14
9 13
Power (13-14) Timed NO (9-5) (12-8) Timed NC (9-1) (12-4)
t