Preview only show first 10 pages with watermark. For full document please download

F4-3 2w - Pertronic Industries

   EMBED


Share

Transcript

F4-3 2W Four Zone 2-Wire Conventional Fire Alarm Panel Product Overview: Head Office Wellington Pertronic Industries F4-3 2W is a four-zone 2-Wire Fire Alarm control unit designed for low cost, Housing NZ Fire Alarm systems. The F4-3 2W is modified to meet Housing NZ requirements for small residential applications and meets most requirements of NZS 4512:2010. The F4-3 2W supports Pertronic Indicating Manual Call-Points, Indicating Heat Detectors, PS1 sounders and System Sensor Smoke Detectors with the facility to internally mount one or two 20W Evacuation amplifiers. PO Box 35-063 Naenae, 5011 Standard Features: Lower Hutt ‘Normal’, ‘Defect’ and per circuit ‘Fire’ indication on front panel 17 Eastern Hutt Rd ‘Internal Bell Cut-Off’ and ‘External Bell Cut-Off’ (BCO) Wingate Alarm reset available from a front panel key-switch Lower Hutt 5019 Trial Evacuation key-switch Tel (04) 567-3229 Local or remote Hush button option temporarily silences sounders Fax (04) 567-3644 for 2 minutes www.pertronic.co.nz [email protected] [email protected] Auckland Office Detectors are automatically reset at end of the Hush period Combined Detector and Sounder Circuit: monitored with a 10kΩ EOL resistor The combined Sounder and Detector circuit support a mix of System Sensor 2WTA-B Smoke/Thermal Detectors with in-built sounder, System Sensor 1151, 2151 Smoke detectors, Pertronic indicating Heat Detectors and indicating Manual Call-Points and Pertronic PS1 sounders and strobes Fire & Defect C/O relays with Fire relay Isolate switch Automatic Alarm Verification Facility (AVF) provides substantial protection against transient false alarm activation Monitored Bell circuit with up two (2) 100VRMS line amplifiers with voiced Evacuation message ‘Battery Absent’ detection circuitry Earth Leakage monitoring Integrated piezo alarm and ‘Piezo on Defect’ warning System ‘Defect’ LED indicates source of fault Door Interlock Brigade ‘Isolate’ and ‘Test’ switches Electrically isolated interface to an alarm transmitter (SGD) ‘Bell Only’ configuration available (on Circuit 4) to monitor DBA Fire Alarm Operating Instructions Fire Alarm Activation When the Fire Alarm panel activates: - the fire sounders will sound - the red ‘Fire’ indicator will flash on the zone(s) in ‘Alarm’ on the panel a) If the Alarm is a genuine fire: - Evacuate the building. - Call 111 and ask for the Fire Service. b) If the Alarm is a false alarm (eg. burnt toast, steam, etc.) - push the fire alarm HUSH button(s) to silence the sounders - investigate the source of the Alarm condition. Open windows to allow smoke/steam to disperse. If the alarms resound, due to a false alarm, push the HUSH button again for a further silence period. If the alarms continue to resound after two Hush periods call your fire alarm service company. When the DEFECT light activates: In the event of a defect on the system: - the ‘Defect’ indicator will flash - the internal buzzer sounds to indicate a system defect - call your fire alarm service company . 2W Panel NZ Issue 3, 200703 Housing New Zealand: Call 0800 801-601 to request assistance PO Box 15-867 New Lynn Auckland 0640 359 Onehunga Mall Onehunga Detector Circuits Auckland 1061 Four (4) zones terminated with 10kΩ EOL resistors Tel (09) 633-0226 Accepts a mix of Smoke Detectors, indicating Heat Detectors and indicating Manual Call-Points Fax (09) 633-0228 Smoke detectors operate after a 1 second Alarm Verification Facility (AVF) delay Indicating Heat detectors and indicating Manual Call-Points give instantaneous (< 0.5 sec) response Zone circuit self-test on start-up and every 24 hours Up to 40 System Sensor Series 100 detectors, fitted to B401R relay bases, may be connected to each zone circuit with up to five (5) Pertronic indicating Heat Detectors and indicating Manual Call-Points Sounder Circuit Bell circuit Relay: 12Vdc, 5A. - monitored with a 10kΩ EOL resistance Recommended Sounders: 2WTA-B Detector-Sounder or Pertronic PS1 Sounder Alternative Sounder : one or two Pertronic EVAC20W12V Amplifiers Recommended Speakers : Pertronic PSSB401 Speaker Bases and/or Pertronic PSS1 Speakers Optional Features: Front or Rear Service cabinet Compatible with Pertronic SGD7 or SGD8 for Fire Brigade connection Specifications Electrical: Battery ISO 9001: 2008 International Standards Certifications QAC/R64/0012 Environmental: Mechanical: Cabinet: FS or RS Power Supply 230Vac, 50Hz, 5W 13.7Vdc, 275mA. Quiescent Current 28mA at 12Vdc Defect Current 30mA at 12Vdc Alarm Current 135mA at 12Vdc - plus Sounder load Battery Charger Integral Float Charger 13.7Vdc, 250mA Battery Type Sealed lead acid (gelcell) 12Vdc, 7AHr - internally mounted Operating Temperature Range 0 to +40 oC Humidity 10 to 95% RH (non-condensing) Dimensions (H x W x D mm) 350 x 245 x 80 Weight 2.2Kg - excluding battery Material 1.2mm mild steel, powder coated Colour Beige - other colours optional Power Supply Timer: Automatic 24-Hour load test with automatic ‘Battery Absent’ detection circuitry. 0011-F4-3 2W Four Zone 2-Wire Conventional Fire Alarm Panel Iss 12, 201205 Benefits: 1. The F4-3 2W and its detectors provide a cost effective solution for residential applications. 2. Installation is made simple as the detectors and sounders are wired on the same pair of cables. 3. The sounders and detectors are fully monitored for open and short circuits. 4. Long battery standby period of up to 7 days. 5. The detectors (2WTA-B) have two detection elements (Smoke / Thermal) with built in sounder. 6. Reduced false alarms due to environmental conditions. The 2WTA-B detector sensitivity is automatically adjusted to compensate for contamination caused by environmental conditions such as dust and dirt. 7. Optional Local or remote Hush button facility enables sounders to be silenced for 3 minutes allowing investigation of alarm. 8. Hush facility may be operated globally and/or per zone 9. Detectors automatically resets at end of the Hush period. 10. Panel Silence and Evacuate facility. System Wiring: Link MJ5 Fitted REMOVE LINK FOR COMMS LED8 K17 0V +5 +13.7 INSERT FOR DEFECT BUZZER K3 LED9 MJ2 TP1 LED2 Normal DEFECT MJ3 Defect PERTRONIC INDUSTRIES FACTORY TEST +5 K2 10 9 TP2 T.E. Common 10 9 LED1 F4 MASTER BOARD V4.10 07/06 K1 HS1 FAULT DECODE 1. CCT 1 2. CCT 2 3. CCT 3 4. CCT 4 5. BELL FAULT 6. COMMS ERR 7. BATTERY 8. 20 VOLTS 9. EARTH 10. ROM ERROR FIRE 1 LED10 VREG2 LED4 U1 2 LED11 LED5 RLY2 K4 RLY1 4 2 3 SGD MJ4 LED13 LED7 4 INSERT FOR DBA on CCT4 Bell Monitoring 0V SW3 Ext Interlock MJ1 K7 +20 TP3 DISABLE ENABLE TP5 + 1 M + 2 M + 3 M + 4 M (DBA) NORMAL NORMAL + + + + K6 S1 SW2 1A FUSE2 SW1 FUSE1 1 COM TEST ISOL DEF FIRE LED12 LED6 VR1 5A Fire 2 1 K9 TP4 0V BCO LED3 NORMAL MJ5 RD TD 2 1 DOOR 18V AC RESET K8 DB#0011 PN#PBF4 K11 (+)BELLS(-) K10 Battery + BCO Ext I/Lock ISOL. 1 M 2 M Global Hush 3 M 4 M (DBA) TEST ATS USE ONLY! Zonal Hush 10k EOL F4-2W Connection 20070129 2-Wire Detector/Sounder Circuit 10k EOL Product Codes NZS Code F4RS-3 2W F4FS-3 2W F4-2W 2WTA-B 1151 2151 B401R Description NZS Code F4 RS Panel with 4-Zone Reversal Relay board F4 FS Panel with 4-Zone Reversal Relay board F4-2W board 2W-B, 2 Wire PE I3 Detector + Thermal and Sounder 1151 Low Pro Ion Detector excl Base 2151 Low Pro Photo Detector excl Base B401R 2-wire base with current limiting resistor. EVAC20W12V PSS1-R PS1-R SR AMRH IHDB-3 CPPIN-3 Description Evacuation Amplifier 20W, 12V, NZS4512:2010 Pertronic Sounder Speaker 1W Flush Red Pertronic Sounder AS2220 Flush- Red SpectrAlert Advance 2 Wire Strobe 12/24V Remote Hush Unit Indicating Heat Detector, Blue (57°C) Conventional Indicating Call-Point PERTRONIC INDUSTRIES LTD Head Office: 17 Eastern Hutt Rd, Wingate, Lower Hutt 5019 Telephone (04) 567-3229 Fax (04) 567-3644 www.pertronic.co.nz [email protected] [email protected] Auckland Office: 59 Onehunga Mall, Onehunga, Auckland 1061 Telephone (09) 633-0226 Fax (09) 633-0228 ‘Pertronic’ and ‘Firetronix’ are registered trademarks of Pertronic Industries Ltd