Transcript
FA 12-160
12V160Ah
Front Access SLA Battery Range Summary By combining the newly developed paste formula with up-to-date AGM structures, BSB created the innovation FA range of batteries. The range features 12 years design life and front access connections for fast, easy installation and maintenance. This series is highly suited to telecom applications, UPS systems and other back up applications.
Application · Telecom · Control Equipment · UPS
· Communication Equipment · Medical Equipment · Emergency Power System
General Features · Easy maintenance and installation · No need for extra (wrench space) above battery · Sealed and maintenance free operation · Non-Spillable construction design · ABS containers and covers(UL94 V0,optional) · Safety valve installation for explosion proof · Maximized energy density for installation in relay rack trays · High quality and high reliability · Exceptional deep discharge recovery performance · Flexible design for multiple installation positions
3mm (0.12inch)
16mm (0.63inch)
M8mm (0.31inch)
Construction Lead dioxide Lead ABS ABS Epoxy Resin
Safety valve Terminal Separator Electrolyte
...... ...... ...... ......
EPDM Copper AGM Sulfuric acid
Terminal Dimensions
315mm(12.4inch)
Positive ...... Negative ...... Container ...... ...... Cover Sealant ......
546mm(21.5inch)
125mm(4.92inch)
Battery Model
FA12-160
Designed Floating Life Capacity(20oC)
Dimensions
12 Years 20HR(8.5A,1.80V)
10HR(16.0A,1.80V)
5HR(28.0A,1.75V)
170Ah
160Ah
140Ah
100Ah
Length
Width
Height
Total Height
546mm(21.5inch)
125mm(4.92inch)
315mm(12.4inch)
315mm(12.4inch)
Approx. Weight
51Kg (112 lbs)
Internal Resistance
Full charged at 20oC: 0.004 Ohm
Self Discharge
3% of capacity declined per month at (20oC)
Capacity Affected by Temp.(10HR) Charge Voltage(20oC)
1HR(100A,1.60V)
40oC
20oC
0oC
-15oC
109%
100%
85%
65%
Cycle use o
14.1-14.4V(-30mV/ C), max. Current: 40A
Page 1 of 2
Float use 13.5-13.7V(-18mV/ oC)
FA 12-160
12V160Ah
Charge Voltage
(CA) (V/Cell)
(%) 120 100
0.25
Charge Capacity
2.17 100%Discharge
0.20
60
2.00
50%Discharge
0.15
40
0.10 20
1.83
0.05
0
0
Discharge Characteristic (20 C)
Constant Charge at 0.25CA-2.35V (20oC) Charge Voltage
2.35 80
o
Charge Characteristic
Charge Current
0
2
4
6
8
10
Discharge Voltage (V/Cell)
Current
Charge
Charge Capacity
Front Access SLA Battery
2.17 2.00 1.83 0.25CA 0.1CA 0.05CA
1.67 1.60
3CA
2CA
1CA
6
12
30
1.33 0
12
2
2.25
110 105
2.17
100 95 90
Capacity (%)
Battery Voltage (V/Cell)
3
10 Hour
20
Self Discharge Characteristics
Relationship of OCV and state of charge
2.00
60
Min
Time(hour)
2.08
0.6CA
85 80 75 70 65 60 55 50
1.92
1.83
40oC
45
0
10
20
30
40
50
60
70
80
90
100
40 0
1
2
20oC
30oC 3 4
5
6
7
8
9 10 11 12 13 14 15 16 17 18 19 20
Storage time:months
Remained Capacity(%)
Constant current discharge ratings-amperes at 20oC F.V/T im e 1 .60 V 1 .67 V 1 .70 V 1 .75 V 1 .80 V 1 .85 V
5 m in 56 0 50 4 47 8 42 6 38 4 29 1
10 m in 384 350 338 312 290 238
1 5 m in 2 80 2 72 2 62 2 48 2 37 2 05
3 0m in 16 8 16 3 16 0 15 7 15 2 14 0
1h 100 9 9.5 9 9.0 9 8.5 9 8.0 9 7.2
3h 43 .7 43 .5 43 .4 43 .2 43 .0 42 .9
5h 2 8 .6 2 8 .4 2 8 .2 2 8 .0 2 7 .9 2 7 .7
10h 1 7.0 1 6.7 1 6.6 1 6.3 1 6.0 1 5.7
2 0h 8.8 5 8.8 2 8.8 0 8.7 8 8.5 0 7.9 6
1h 208 201 196 194 191 189
3h 83 .8 83 .5 83 .0 82 .6 81 .4 81 .1
5h 5 4 .8 5 4 .6 5 4 .4 5 4 .2 5 3 .3 5 2 .5
10h 3 3.9 3 3.4 3 3.2 3 2.6 3 2.0 3 1.5
2 0h 17 .7 17 .5 17 .3 17 .1 16 .9 15 .9
Constant power discharge ratings-watts at 20oC F.V/T im e 1 .60 V 1 .67 V 1 .70 V 1 .75 V 1 .80 V 1 .85 V
5 m in 92 3 87 5 81 8 76 2 68 3 54 7
10 m in 637 629 613 573 533 442
1 5 m in 4 96 4 91 4 83 4 54 4 27 3 73
3 0m in 31 7 31 0 30 2 29 4 28 6 26 2
ISO9001
COPYRIGHT BSB POWER COMPANY LIMITED Page 2 of 2
(Updated: 1-May-2011)