Transcript
FA 12-180
12V180Ah
Front Access SLA Battery Range Summary By combining the newly developed paste formula with up-to-date AGM structures, BSB created the innovation FA range of batteries. The range features 12 years design life and front access connections for fast, easy installation and maintenance. This series is highly suited to telecom applications, UPS systems and other back up applications.
Application · Telecom · Control Equipment · UPS
· Communication Equipment · Medical Equipment · Emergency Power System
General Features · Easy maintenance and installation · No need for extra (wrench space) above battery · Sealed and maintenance free operation · Non-Spillable construction design · ABS containers and covers(UL94 V0,optional) · Safety valve installation for explosion proof · Maximized energy density for installation in relay rack trays · High quality and high reliability · Exceptional deep discharge recovery performance
3mm (0.12inch)
19mm (0.75inch)
M8mm (0.31inch)
Construction Lead dioxide Lead ABS ABS Epoxy Resin
Safety valve Terminal Separator Electrolyte
...... ...... ...... ......
EPDM Copper AGM Sulfuric acid
Terminal Dimensions
315mm(12.4inch)
Positive ...... Negative ...... Container ...... ...... Cover Sealant ......
546mm(21.5inch)
125mm(4.92inch)
Battery Model
FA12-180
Designed Floating Life Capacity(20oC)
12 Years 20HR(9.53A,1.80V)
10HR(18.0A,1.80V)
191Ah Dimensions
5HR(30.8A,1.75V)
180Ah
154Ah
115Ah
Length
Width
Height
Total Height
546mm(21.5inch)
125mm(4.92inch)
315mm(12.4inch)
315mm(12.4inch)
Approx. Weight
53.5Kg (118 lbs)
Internal Resistance
Full charged at 20oC: 0.004 Ohm
Self Discharge
3% of capacity declined per month at (20oC)
Capacity Affected by Temp.(10HR) Charge Voltage(20oC)
1HR(115A,1.60V)
40oC
20oC
0oC
-15oC
109%
100%
85%
65%
Cycle use o
14.1-14.4V(-30mV/ C), max. Current: 45A
Page 1 of 2
Float use 13.5-13.7V(-18mV/ oC)
FA 12-180
12V180Ah
Charge Voltage
(CA) (V/Cell)
(%) 120 100 80
0.25
Constant Charge at 0.25CA-2.35V (20oC) Charge Capacity
Charge Voltage
2.35
2.17 100%Discharge
0.20
60
2.00
50%Discharge
0.15
40
0.10 20
1.83
0.05
0
0
Discharge Characteristic (20oC)
Charge Characteristic
Charge Current
0
2
4
6
8
10
Discharge Voltage (V/Cell)
Current
Charge
Charge Capacity
Front Access SLA Battery
2.17 2.00 1.83
0.25CA 0.1CA 0.05CA
1.67
3CA
1CA
0.6CA
1.33 0
12
2
6
12 Min
Time(hour)
30
60
3
10 Hour
20
Self Discharge Characteristics
Relationship of OCV and state of charge 2.25
110 105
2.17
100 95 90
Capacity (%)
Battery Voltage (V/Cell)
2CA
1.60
2.08
2.00
85 80 75 70 65 60 55 50
1.92
45
1.83
0
10
20
30
40
50
60
70
80
90
100
40 0
o
1
2
20oC
o
40 C
30 C 3 4
5
6
7
8
9 10 11 12 13 14 15 16 17 18 19 20
Storage time:months
Remained Capacity(%)
Constant current discharge ratings-amperes at 20oC F.V/T im e 1 .60 V 1 .67 V 1 .70 V 1 .75 V 1 .80 V 1 .85 V
5 m in 63 0 56 7 53 8 47 9 43 2 32 8
10 m in 432 394 380 351 326 268
1 5 m in 3 15 3 06 2 95 2 79 2 66 2 30
3 0m in 18 9 18 4 18 0 17 6 17 1 15 7
1h 115 113 112 111 110 109
3h 49 .1 49 .0 48 .8 48 .6 48 .4 48 .2
5h 3 1 .4 3 1 .2 3 1 .0 3 0 .8 3 0 .5 3 0 .2
10h 1 9.1 1 8.8 1 8.7 1 8.3 1 8.0 1 7.7
2 0h 9.9 6 9.9 2 9.9 0 9.8 8 9.5 3 8.9 6
3 0m in 35 6 34 9 34 0 33 1 32 2 29 5
1h 222 215 209 207 204 202
3h 94 .5 94 .3 94 .0 92 .9 91 .6 91 .3
5h 6 0 .0 5 9 .8 5 9 .6 5 9 .1 5 8 .1 5 7 .3
10h 3 8.2 3 7.6 3 7.3 3 6.7 3 6.0 3 5.4
2 0h 20 .2 20 .0 19 .8 19 .6 19 .1 17 .9
Constant power discharge ratings-watts at 20oC F.V/T im e 1 .60 V 1 .67 V 1 .70 V 1 .75 V 1 .80 V 1 .85 V
5 m in 1 0 39 98 5 92 0 85 7 76 9 61 6
10 m in 716 707 689 644 599 497
1 5 m in 5 58 5 53 5 44 5 11 4 81 4 19
ISO9001
COPYRIGHT BSB POWER COMPANY LIMITED Page 2 of 2
(Updated: 1-May-2011)